Science.gov

Sample records for dc fault current

  1. Current Zero Missing Phenomena caused by D.C. Current which Flows from Shunt Reactor at the Ground Fault and its Interruption

    NASA Astrophysics Data System (ADS)

    Kobayashi, Takayuki; Eto, Atsushi; Koshizuka, Tadashi; Nishiwaki, Susumu; Kudo, Kietsu; Matsushita, Kozo; Hosokawa, Osamu

    At substations where shunt reactors are installed, when a ground fault occurs near the reactor, d.c. current flows from the reactor to the fault point. There are cases where circuit breakers installed near the reactor interrupt only the d.c. current from the reactor with long arcing times. In those cases, attention should be paid to the damage of the contacts. This paper shows the investigation of the d.c. current interrupting performance for the 550kV one-break SF6 gas circuit breaker. In the range of some hundreds amperes, the d.c. arc voltages with long arcing times of the 550kV one-break circuit breaker were measured. The d.c. current waveform and arcing time at the d.c. current interruption by 550kV one-break circuit breaker in the 500kV cable system were calculated. Interrupting test circuit for the d.c. current interruption was constructed in the high power laboratory. From the interrupting test results, it was made clear that the circuit breaker had a good interrupting performance after the d.c. current interruptions.

  2. Fault current limiter

    DOEpatents

    Darmann, Francis Anthony

    2013-10-08

    A fault current limiter (FCL) includes a series of high permeability posts for collectively define a core for the FCL. A DC coil, for the purposes of saturating a portion of the high permeability posts, surrounds the complete structure outside of an enclosure in the form of a vessel. The vessel contains a dielectric insulation medium. AC coils, for transporting AC current, are wound on insulating formers and electrically interconnected to each other in a manner such that the senses of the magnetic field produced by each AC coil in the corresponding high permeability core are opposing. There are insulation barriers between phases to improve dielectric withstand properties of the dielectric medium.

  3. DC current monitor

    NASA Technical Reports Server (NTRS)

    Canter, Stanley (Inventor)

    1991-01-01

    A non-intrusive DC current monitor is presented which emulates the theoretical operation of an AC transformer. A conductor, carrying the current to be measured, acts as the primary of a DC current transformer. This current is passed through the center of a secondary coil, and core positioned thereabout, and produces a magnetic flux which induces a current in the secondary proportional to the current flowing in the primary. Means are provided to periodically reset the transformer core such that the measurement inaccuracies associated with core saturation are obviated. A reset current is caused to periodically flow through the secondary coil which produces a magnetic flux oppositely polarized to the flux created by the current in the primary, thus allowing ongoing measurements to be made.

  4. Early Oscillation Detection for DC/DC Converter Fault Diagnosis

    NASA Technical Reports Server (NTRS)

    Wang, Bright L.

    2011-01-01

    The electrical power system of a spacecraft plays a very critical role for space mission success. Such a modern power system may contain numerous hybrid DC/DC converters both inside the power system electronics (PSE) units and onboard most of the flight electronics modules. One of the faulty conditions for DC/DC converter that poses serious threats to mission safety is the random occurrence of oscillation related to inherent instability characteristics of the DC/DC converters and design deficiency of the power systems. To ensure the highest reliability of the power system, oscillations in any form shall be promptly detected during part level testing, system integration tests, flight health monitoring, and on-board fault diagnosis. The popular gain/phase margin analysis method is capable of predicting stability levels of DC/DC converters, but it is limited only to verification of designs and to part-level testing on some of the models. This method has to inject noise signals into the control loop circuitry as required, thus, interrupts the DC/DC converter's normal operation and increases risks of degrading and damaging the flight unit. A novel technique to detect oscillations at early stage for flight hybrid DC/DC converters was developed.

  5. DC-Compensated Current Transformer.

    PubMed

    Ripka, Pavel; Draxler, Karel; Styblíková, Renata

    2016-01-01

    Instrument current transformers (CTs) measure AC currents. The DC component in the measured current can saturate the transformer and cause gross error. We use fluxgate detection and digital feedback compensation of the DC flux to suppress the overall error to 0.15%. This concept can be used not only for high-end CTs with a nanocrystalline core, but it also works for low-cost CTs with FeSi cores. The method described here allows simultaneous measurements of the DC current component. PMID:26805830

  6. Passive fault current limiting device

    DOEpatents

    Evans, D.J.; Cha, Y.S.

    1999-04-06

    A passive current limiting device and isolator is particularly adapted for use at high power levels for limiting excessive currents in a circuit in a fault condition such as an electrical short. The current limiting device comprises a magnetic core wound with two magnetically opposed, parallel connected coils of copper, a high temperature superconductor or other electrically conducting material, and a fault element connected in series with one of the coils. Under normal operating conditions, the magnetic flux density produced by the two coils cancel each other. Under a fault condition, the fault element is triggered to cause an imbalance in the magnetic flux density between the two coils which results in an increase in the impedance in the coils. While the fault element may be a separate current limiter, switch, fuse, bimetal strip or the like, it preferably is a superconductor current limiter conducting one-half of the current load compared to the same limiter wired to carry the total current of the circuit. The major voltage during a fault condition is in the coils wound on the common core in a preferred embodiment. 6 figs.

  7. Passive fault current limiting device

    DOEpatents

    Evans, Daniel J.; Cha, Yung S.

    1999-01-01

    A passive current limiting device and isolator is particularly adapted for use at high power levels for limiting excessive currents in a circuit in a fault condition such as an electrical short. The current limiting device comprises a magnetic core wound with two magnetically opposed, parallel connected coils of copper, a high temperature superconductor or other electrically conducting material, and a fault element connected in series with one of the coils. Under normal operating conditions, the magnetic flux density produced by the two coils cancel each other. Under a fault condition, the fault element is triggered to cause an imbalance in the magnetic flux density between the two coils which results in an increase in the impedance in the coils. While the fault element may be a separate current limiter, switch, fuse, bimetal strip or the like, it preferably is a superconductor current limiter conducting one-half of the current load compared to the same limiter wired to carry the total current of the circuit. The major voltage during a fault condition is in the coils wound on the common core in a preferred embodiment.

  8. Superconducting fault current limiter for railway transport

    SciTech Connect

    Fisher, L. M. Alferov, D. F.; Akhmetgareev, M. R.; Budovskii, A. I.; Evsin, D. V.; Voloshin, I. F.; Kalinov, A. V.

    2015-12-15

    A resistive switching superconducting fault current limiter (SFCL) for DC networks with voltage of 3.5 kV and nominal current of 2 kA is developed. The SFCL consists of two series-connected units: block of superconducting modules and high-speed vacuum breaker with total disconnection time not more than 8 ms. The results of laboratory tests of superconducting SFCL modules in current limiting mode are presented. The recovery time of superconductivity is experimentally determined. The possibility of application of SFCL on traction substations of Russian Railways is considered.

  9. Superconducting fault current limiter for railway transport

    NASA Astrophysics Data System (ADS)

    Fisher, L. M.; Alferov, D. F.; Akhmetgareev, M. R.; Budovskii, A. I.; Evsin, D. V.; Voloshin, I. F.; Kalinov, A. V.

    2015-12-01

    A resistive switching superconducting fault current limiter (SFCL) for DC networks with voltage of 3.5 kV and nominal current of 2 kA is developed. The SFCL consists of two series-connected units: block of superconducting modules and high-speed vacuum breaker with total disconnection time not more than 8 ms. The results of laboratory tests of superconducting SFCL modules in current limiting mode are presented. The recovery time of superconductivity is experimentally determined. The possibility of application of SFCL on traction substations of Russian Railways is considered.

  10. Superconducting fault current controller/current controller

    DOEpatents

    Cha, Yung S.

    2004-06-15

    A superconducting fault current controller/current controller employs a superconducting-shielded core reactor (SSCR) with a variable impedance in a secondary circuit to control current in a primary circuit such as an electrical distribution system. In a second embodiment, a variable current source is employed in a secondary circuit of an SSCR to control current in the primary circuit. In a third embodiment, both a variable impedance in one secondary circuit and a variable current source in a second circuit of an SSCR are employed for separate and independent control of current in the primary circuit.

  11. Detection of High-impedance Arcing Faults in Radial Distribution DC Systems

    NASA Technical Reports Server (NTRS)

    Gonzalez, Marcelo C.; Button, Robert M.

    2003-01-01

    High voltage, low current arcing faults in DC power systems have been researched at the NASA Glenn Research Center in order to develop a method for detecting these 'hidden faults', in-situ, before damage to cables and components from localized heating can occur. A simple arc generator was built and high-speed and low-speed monitoring of the voltage and current waveforms, respectively, has shown that these high impedance faults produce a significant increase in high frequency content in the DC bus voltage and low frequency content in the DC system current. Based on these observations, an algorithm was developed using a high-speed data acquisition system that was able to accurately detect high impedance arcing events induced in a single-line system based on the frequency content of the DC bus voltage or the system current. Next, a multi-line, radial distribution system was researched to see if the arc location could be determined through the voltage information when multiple 'detectors' are present in the system. It was shown that a small, passive LC filter was sufficient to reliably isolate the fault to a single line in a multi-line distribution system. Of course, no modification is necessary if only the current information is used to locate the arc. However, data shows that it might be necessary to monitor both the system current and bus voltage to improve the chances of detecting and locating high impedance arcing faults

  12. Large transient fault current test of an electrical roll ring

    NASA Technical Reports Server (NTRS)

    Yenni, Edward J.; Birchenough, Arthur G.

    1992-01-01

    The space station uses precision rotary gimbals to provide for sun tracking of its photoelectric arrays. Electrical power, command signals and data are transferred across the gimbals by roll rings. Roll rings have been shown to be capable of highly efficient electrical transmission and long life, through tests conducted at the NASA Lewis Research Center and Honeywell's Satellite and Space Systems Division in Phoenix, AZ. Large potential fault currents inherent to the power system's DC distribution architecture, have brought about the need to evaluate the effects of large transient fault currents on roll rings. A test recently conducted at Lewis subjected a roll ring to a simulated worst case space station electrical fault. The system model used to obtain the fault profile is described, along with details of the reduced order circuit that was used to simulate the fault. Test results comparing roll ring performance before and after the fault are also presented.

  13. Adjustable direct current and pulsed circuit fault current limiter

    DOEpatents

    Boenig, Heinrich J.; Schillig, Josef B.

    2003-09-23

    A fault current limiting system for direct current circuits and for pulsed power circuit. In the circuits, a current source biases a diode that is in series with the circuits' transmission line. If fault current in a circuit exceeds current from the current source biasing the diode open, the diode will cease conducting and route the fault current through the current source and an inductor. This limits the rate of rise and the peak value of the fault current.

  14. DC-Compensated Current Transformer †

    PubMed Central

    Ripka, Pavel; Draxler, Karel; Styblíková, Renata

    2016-01-01

    Instrument current transformers (CTs) measure AC currents. The DC component in the measured current can saturate the transformer and cause gross error. We use fluxgate detection and digital feedback compensation of the DC flux to suppress the overall error to 0.15%. This concept can be used not only for high-end CTs with a nanocrystalline core, but it also works for low-cost CTs with FeSi cores. The method described here allows simultaneous measurements of the DC current component. PMID:26805830

  15. High temperature superconducting fault current limiter

    DOEpatents

    Hull, J.R.

    1997-02-04

    A fault current limiter for an electrical circuit is disclosed. The fault current limiter includes a high temperature superconductor in the electrical circuit. The high temperature superconductor is cooled below its critical temperature to maintain the superconducting electrical properties during operation as the fault current limiter. 15 figs.

  16. High temperature superconducting fault current limiter

    DOEpatents

    Hull, John R.

    1997-01-01

    A fault current limiter (10) for an electrical circuit (14). The fault current limiter (10) includes a high temperature superconductor (12) in the electrical circuit (14). The high temperature superconductor (12) is cooled below its critical temperature to maintain the superconducting electrical properties during operation as the fault current limiter (10).

  17. Double storey three phase saturated cores fault current limiter

    NASA Astrophysics Data System (ADS)

    Wolfus, Y.; Nikulshin, Y.; Friedman, A.; Yeshurun, Y.

    2014-05-01

    A novel saturated-cores Fault-Current-Limiter (FCL) configuration is described. This FCL is based on two parallel planes of iron rectangular cores, on which three-phase coils are mounted and connected in series to the grid. Two DC coils are mounted in between the planes on perpendicular core limbs connecting the two AC planes. The DC coils are set to magnetically saturate the AC cores. The transition to three-dimensional, double-storey design enables handling three-phase symmetrical faults while offering better decoupling between the AC and DC circuits. At the same time, it shortens the AC limb lengths and enables deeper magnetic saturation levels in comparison to other saturated cores FCL designs. Hence, this FCL configuration exhibits lower insertion impedance and higher ratio of fault to nominal state impedance in comparison with other designs.

  18. Self-triggering superconducting fault current limiter

    DOEpatents

    Yuan, Xing; Tekletsadik, Kasegn

    2008-10-21

    A modular and scaleable Matrix Fault Current Limiter (MFCL) that functions as a "variable impedance" device in an electric power network, using components made of superconducting and non-superconducting electrically conductive materials. The matrix fault current limiter comprises a fault current limiter module that includes a superconductor which is electrically coupled in parallel with a trigger coil, wherein the trigger coil is magnetically coupled to the superconductor. The current surge doing a fault within the electrical power network will cause the superconductor to transition to its resistive state and also generate a uniform magnetic field in the trigger coil and simultaneously limit the voltage developed across the superconductor. This results in fast and uniform quenching of the superconductors, significantly reduces the burnout risk associated with non-uniformity often existing within the volume of superconductor materials. The fault current limiter modules may be electrically coupled together to form various "n" (rows).times."m" (columns) matrix configurations.

  19. Current Sensor Fault Reconstruction for PMSM Drives

    PubMed Central

    Huang, Gang; Luo, Yi-Ping; Zhang, Chang-Fan; He, Jing; Huang, Yi-Shan

    2016-01-01

    This paper deals with a current sensor fault reconstruction algorithm for the torque closed-loop drive system of an interior PMSM. First, sensor faults are equated to actuator ones by a new introduced state variable. Then, in αβ coordinates, based on the motor model with active flux linkage, a current observer is constructed with a specific sliding mode equivalent control methodology to eliminate the effects of unknown disturbances, and the phase current sensor faults are reconstructed by means of an adaptive method. Finally, an αβ axis current fault processing module is designed based on the reconstructed value. The feasibility and effectiveness of the proposed method are verified by simulation and experimental tests on the RT-LAB platform. PMID:26840317

  20. Current Sensor Fault Reconstruction for PMSM Drives.

    PubMed

    Huang, Gang; Luo, Yi-Ping; Zhang, Chang-Fan; He, Jing; Huang, Yi-Shan

    2016-01-01

    This paper deals with a current sensor fault reconstruction algorithm for the torque closed-loop drive system of an interior PMSM. First, sensor faults are equated to actuator ones by a new introduced state variable. Then, in αβ coordinates, based on the motor model with active flux linkage, a current observer is constructed with a specific sliding mode equivalent control methodology to eliminate the effects of unknown disturbances, and the phase current sensor faults are reconstructed by means of an adaptive method. Finally, an αβ axis current fault processing module is designed based on the reconstructed value. The feasibility and effectiveness of the proposed method are verified by simulation and experimental tests on the RT-LAB platform. PMID:26840317

  1. An Optimal Current Observer for Predictive Current Controlled Buck DC-DC Converters

    PubMed Central

    Min, Run; Chen, Chen; Zhang, Xiaodong; Zou, Xuecheng; Tong, Qiaoling; Zhang, Qiao

    2014-01-01

    In digital current mode controlled DC-DC converters, conventional current sensors might not provide isolation at a minimized price, power loss and size. Therefore, a current observer which can be realized based on the digital circuit itself, is a possible substitute. However, the observed current may diverge due to the parasitic resistors and the forward conduction voltage of the diode. Moreover, the divergence of the observed current will cause steady state errors in the output voltage. In this paper, an optimal current observer is proposed. It achieves the highest observation accuracy by compensating for all the known parasitic parameters. By employing the optimal current observer-based predictive current controller, a buck converter is implemented. The converter has a convergently and accurately observed inductor current, and shows preferable transient response than the conventional voltage mode controlled converter. Besides, costs, power loss and size are minimized since the strategy requires no additional hardware for current sensing. The effectiveness of the proposed optimal current observer is demonstrated experimentally. PMID:24854061

  2. An optimal current observer for predictive current controlled buck DC-DC converters.

    PubMed

    Min, Run; Chen, Chen; Zhang, Xiaodong; Zou, Xuecheng; Tong, Qiaoling; Zhang, Qiao

    2014-01-01

    In digital current mode controlled DC-DC converters, conventional current sensors might not provide isolation at a minimized price, power loss and size. Therefore, a current observer which can be realized based on the digital circuit itself, is a possible substitute. However, the observed current may diverge due to the parasitic resistors and the forward conduction voltage of the diode. Moreover, the divergence of the observed current will cause steady state errors in the output voltage. In this paper, an optimal current observer is proposed. It achieves the highest observation accuracy by compensating for all the known parasitic parameters. By employing the optimal current observer-based predictive current controller, a buck converter is implemented. The converter has a convergently and accurately observed inductor current, and shows preferable transient response than the conventional voltage mode controlled converter. Besides, costs, power loss and size are minimized since the strategy requires no additional hardware for current sensing. The effectiveness of the proposed optimal current observer is demonstrated experimentally. PMID:24854061

  3. Dynamic Resistance of YBCO-Coated Conductors in Applied AC Fields with DC Transport Currents and DC Background Fields

    SciTech Connect

    Duckworth, Robert C; Zhang, Yifei; Ha, Tam T; Gouge, Michael J

    2011-01-01

    In order to predict heat loads in future saturable core fault-current-limiting devices due to ac fringing fields, dynamic resistance in YBCO-coated conductors was measured at 77 K in peak ac fields up to 25 mT at 60 Hz and in dc fields up to 1 T. With the sample orientation set such that the conductor face was either parallel or perpendicular to the ac and dc applied fields, the dynamic resistance was measured at different fractions of the critical current to determine the relationship between the dc transport current and the applied fields. With respect to field orientation, the dynamic resistance for ac fields that were perpendicular to the conductor face was significantly higher than when the ac fields were parallel to the conductor face. It was also observed that the dynamic resistance: (1) increased with increasing fraction of the dc transport current to the critical current, (2) was proportional to the inverse of the critical current, and (3) demonstrated a linear dependence with the applied ac field once a threshold field was exceeded. This functional behavior was consistent with a critical state model for the dynamic resistance, but discrepancies in absolute value of the dynamic resistance suggested that further theoretical development is needed.

  4. Transport characteristics of meander and bispiral types resistive fault current limiters

    NASA Astrophysics Data System (ADS)

    Kim, S. B.; Nishimoto, M.; Joo, J. H.; Murase, S.

    2008-09-01

    The resistive type fault current limiter based on YBCO thin film with high critical current density was proposed and developed because of its fast recovery characteristics. We have been developing a magnetic field measurement system with hall sensor to study the critical current density distribution or magnetic properties of high- Tc superconductors such as thin film, tape conductor and coated conductors. In this study, the transport current distribution in straight line and U-corner region of meander type resistive fault current limiter using YBCO thin film was investigated experimentally. The both axial and radial self-magnetic field components according to the direct (DC) and alternating (AC) transport currents were measured by two-axis hall probe to estimate the current distribution. And also, the self-magnetic field at the corner of bispiral type fault current limiter was measured by two-axis hall probe with a high spatial resolution to compare with the meander type fault current limiter.

  5. Large transient fault current test of an electrical roll ring. [for Space Station Freedom

    NASA Technical Reports Server (NTRS)

    Yenni, Edward J.; Birchenough, Arthur G.

    1991-01-01

    The Space Station Freedom uses precision rotary gimbals to provide for sun tracking of its photoelectric arrays. Electrical power, command signals, and data are transferred across the gimbals by roll rings. Roll rings have been shown to be capable of highly efficient electrical transmission and long life, through tests conducted at the NASA Lewis Research Center and Honeywell's Satellite and Space Systems Division in Phoenix, AZ. Large potential fault currents inherent to the power system's DC distribution architecture have brought about the need to evaluate the effects of large transient fault currents on roll rings. A test recently conducted at Lewis subjected a roll ring to a simulated worst case space station electrical fault. The system model used to obtain the fault profile is described, along with details of the reduced order circuit that was used to simulate the fault. Test results comparing roll ring performance before and after the fault are also presented.

  6. Performance analysis of saturated iron core superconducting fault current limiter using Jiles-Atherton hysteresis model

    NASA Astrophysics Data System (ADS)

    Sarkar, D.; Roy, D.; Choudhury, A. B.; Yamada, S.

    2015-09-01

    In this paper study of the Saturated Iron Core Superconducting Fault Current Limiter (SISFCL) has been carried out. Since in an SISFCL, the iron core plays a key role in distributing the magnetic flux, the hysteresis property of the core material has been introduced in a mathematical model to get a more accurate result. In this paper the Jiles-Atherton hysteresis model has been used for modeling the core. The equations are solved through numerical method and performances of SISFCL are analyzed for both normal and fault conditions. On further analysis it is observed that for suppression of higher value of fault current a high voltage develops across the DC source. Hence there is a chance of the DC source being damaged by the rise in voltage under fault condition. In order to protect the DC source, a shorted ring is introduced in the SISFCL circuit and its effects have been analyzed. It is noticed that the shorted ring has successfully reduced the voltage across the DC coil during fault condition while the performance of the limiter remains the same.

  7. Fault current limiter and alternating current circuit breaker

    DOEpatents

    Boenig, H.J.

    1998-03-10

    A solid-state circuit breaker and current limiter are disclosed for a load served by an alternating current source having a source impedance, the solid-state circuit breaker and current limiter comprising a thyristor bridge interposed between the alternating current source and the load, the thyristor bridge having four thyristor legs and four nodes, with a first node connected to the alternating current source, and a second node connected to the load. A coil is connected from a third node to a fourth node, the coil having an impedance of a value calculated to limit the current flowing therethrough to a predetermined value. Control means are connected to the thyristor legs for limiting the alternating current flow to the load under fault conditions to a predetermined level, and for gating the thyristor bridge under fault conditions to quickly reduce alternating current flowing therethrough to zero and thereafter to maintain the thyristor bridge in an electrically open condition preventing the alternating current from flowing therethrough for a predetermined period of time. 9 figs.

  8. Fault current limiter and alternating current circuit breaker

    DOEpatents

    Boenig, Heinrich J.

    1998-01-01

    A solid-state circuit breaker and current limiter for a load served by an alternating current source having a source impedance, the solid-state circuit breaker and current limiter comprising a thyristor bridge interposed between the alternating current source and the load, the thyristor bridge having four thyristor legs and four nodes, with a first node connected to the alternating current source, and a second node connected to the load. A coil is connected from a third node to a fourth node, the coil having an impedance of a value calculated to limit the current flowing therethrough to a predetermined value. Control means are connected to the thyristor legs for limiting the alternating current flow to the load under fault conditions to a predetermined level, and for gating the thyristor bridge under fault conditions to quickly reduce alternating current flowing therethrough to zero and thereafter to maintain the thyristor bridge in an electrically open condition preventing the alternating current from flowing therethrough for a predetermined period of time.

  9. Superconducting Fault Current Limiter optimized design

    NASA Astrophysics Data System (ADS)

    Tixador, Pascal; Badel, Arnaud

    2015-11-01

    The SuperConducting Fault Current Limiter (SCFCL) appears as one of the most promising SC applications for the electrical grids. Despite its advantages and many successful field experiences the market of SCFCL has difficulties to take off even if the first orders for permanent operation in grids are taken. The analytical design of resistive SCFCL will be discussed with the objective to reduce the quantity of SC conductor (length and section) to be more cost-effective. For that the SC conductor must have a high resistivity in normal state. It can be achieved by using high resistivity alloy for shunt, such as Hastelloy®. One of the most severe constraint is that the SCFCL should operate safely for any faults, especially those with low prospective short-circuit currents. This constraint requires to properly design the thickness of the SC tape in order to limit the hot spot temperature. An operation at 65 K appears as very interesting since it decreases the SC cost at least by a factor 2 with a simple LN2 cryogenics. Taking into account the cost reduction in a near future, the SC conductor cost could be rather low, half a dollar per kV A.

  10. Fault current limiter with shield and adjacent cores

    SciTech Connect

    Darmann, Francis Anthony; Moriconi, Franco; Hodge, Eoin Patrick

    2013-10-22

    In a fault current limiter (FCL) of a saturated core type having at least one coil wound around a high permeability material, a method of suppressing the time derivative of the fault current at the zero current point includes the following step: utilizing an electromagnetic screen or shield around the AC coil to suppress the time derivative current levels during zero current conditions.

  11. Self field triggered superconducting fault current limiter

    DOEpatents

    Tekletsadik, Kasegn D.

    2008-02-19

    A superconducting fault current limiter array with a plurality of superconductor elements arranged in a meanding array having an even number of supconductors parallel to each other and arranged in a plane that is parallel to an odd number of the plurality of superconductors, where the odd number of supconductors are parallel to each other and arranged in a plane that is parallel to the even number of the plurality of superconductors, when viewed from a top view. The even number of superconductors are coupled at the upper end to the upper end of the odd number of superconductors. A plurality of lower shunt coils each coupled to the lower end of each of the even number of superconductors and a plurality of upper shunt coils each coupled to the upper end of each of the odd number of superconductors so as to generate a generally orthoganal uniform magnetic field during quenching using only the magenetic field generated by the superconductors.

  12. Superconducting Fault Current Limiter for Transmission Voltage

    NASA Astrophysics Data System (ADS)

    Kraemer, Hans-Peter; Schmidt, Wolfgang; Cai, Hong; Gamble, Bruce; Madura, David; MacDonald, Tim; McNamara, Joe; Romanosky, Walther; Snitchler, Greg; Lallouet, Nicolas; Schmidt, Frank; Ahmed, Syed

    Within a collaboration of American Superconductor, Siemens, Nexans and Southern California Edison one electrical phase of a resistive superconducting fault current limiter for the 115 kV transmission voltage level has been designed and manufactured. The active part of the limiter consists of 63 bifilar coils made of 12 mm wide steel-stabilized YBCO conductor and is housed in a cryostat operated at 5 bar and 74 K. The first phase was completely assembled and successfully subjected to power switching tests and high voltage tests. The basic design of the system and the test results are reported. The work was funded in part by US-DOE under Contract Number DE-FC26-07NT43243.

  13. Microwave Induced Enhancement of the Subgap Josephson dc Current

    NASA Astrophysics Data System (ADS)

    Lundin, N. I.; Shekhter, R. I.; Jonson, M.; Gorelik, L. Y.; Shumeiko, V. S.

    1998-03-01

    We introduce a mechanism for lifting the suppression of the subgap dc-Josephson current in a ballistic, normal, one-dimensional quantum channel between two superconducting electrodes with moderate amount of backscattering. The current appears when a non-equilibrium population of the Andreev levels carrying the current, is developed due to photon-induced Landua-Zener transitions.

  14. Experimental study on superconducting fault current limiting transformer for fault current suppression and system stability improvement

    NASA Astrophysics Data System (ADS)

    Kagawa, H.; Hayakawa, N.; Kashima, N.; Nagaya, S.; Okubo, H.

    2002-08-01

    We have been developing a superconducting fault current limiting transformer (SFCLT) with 3-phase, 500/275 kV, 625 MVA and optimized the main parameters by EMTP simulation. In this paper, we designed and fabricated an experimental scale-down model of SFCLT with 3-phase, 275/105 V, 6.25 kVA, using NbTi superconducting wire. We introduced the experimental model SFCLT into a transient network analyzer consisted of synchronous generators, transformers, transmission lines, circuit breakers and an infinite bus. It was revealed that experimental model had effective function-parameters as was simulated and experimental results clarified the effectiveness of SFCLT having both functions of the fault current suppression and the system stability improvement in a future superconducting power system.

  15. Induction machine faults detection using stator current parametric spectral estimation

    NASA Astrophysics Data System (ADS)

    El Bouchikhi, El Houssin; Choqueuse, Vincent; Benbouzid, Mohamed

    2015-02-01

    Current spectrum analysis is a proven technique for fault diagnosis in electrical machines. Current spectral estimation is usually performed using classical techniques such as periodogram (FFT) or its extensions. However, these techniques have several drawbacks since their frequency resolution is limited and additional post-processing algorithms are required to extract a relevant fault detection criterion. Therefore, this paper proposes a new parametric spectral estimator that fully exploits the faults sensitive frequencies. The proposed technique is based on the maximum likelihood estimator (MLE) and offers high-resolution capabilities. Based on this approach, a fault criterion is derived for detecting several fault types. The proposed technique is assessed using simulation signals, issued from a coupled electromagnetic circuits approach-based simulation tool for mechanical unbalance and electrical asymmetry faults detection. It is afterward validated using experiments on a 0.75-kW induction machine test bed for the particular case of bearing faults.

  16. Fault tolerance control of phase current in permanent magnet synchronous motor control system

    NASA Astrophysics Data System (ADS)

    Chen, Kele; Chen, Ke; Chen, Xinglong; Li, Jinying

    2014-08-01

    As the Photoelectric tracking system develops from earth based platform to all kinds of moving platform such as plane based, ship based, car based, satellite based and missile based, the fault tolerance control system of phase current sensor is studied in order to detect and control of failure of phase current sensor on a moving platform. By using a DC-link current sensor and the switching state of the corresponding SVPWM inverter, the failure detection and fault control of three phase current sensor is achieved. Under such conditions as one failure, two failures and three failures, fault tolerance is able to be controlled. The reason why under the method, there exists error between fault tolerance control and actual phase current, is analyzed, and solution to weaken the error is provided. The experiment based on permanent magnet synchronous motor system is conducted, and the method is proven to be capable of detecting the failure of phase current sensor effectively and precisely, and controlling the fault tolerance simultaneously. With this method, even though all the three phase current sensors malfunction, the moving platform can still work by reconstructing the phase current of the motor.

  17. Multiple output zero-current switching switched-capacitor bidirectional dc-dc converter

    NASA Astrophysics Data System (ADS)

    Lee, Yuang-Shung; Ko, Yi-Pin; Chi, Chien-An

    2010-08-01

    The proposed circuit is a multiple output quasi-resonant (QR) zero-current switching (ZCS) switched-capacitor (SC) converter with a bidirectional power flow control conversion scheme. The principles of the proposed multiple output QR ZCS SC bidirectional dc-dc converter are described using a detailed circuit model for analysis. Simulation and experimental results are carried out to verify the validity and the soft switching performance of the proposed converter. The maximum efficiency achievable is about 94 and 92% for the forward and reverse power flow control schemes, respectively. The output voltage can be regulated by changing the switching frequency for the designed compensated closed-loop controller.

  18. Analysis of the effects of asymmetric faults in three-phase superconducting inductive fault current limiters

    NASA Astrophysics Data System (ADS)

    Ferreira, R.; Pina, J. M.; Vilhena, N.; Arsénio, P.; Pronto, A. G.; Martins, J.

    2014-05-01

    Inductive fault current limiters of magnetic shielding type can be described in terms of the excursion in the plane defined by flux linked with primary and line current, and this methodology has been previously applied to single-phase devices. Practical applications, however, require three-phase limiters, which, for the sake of compactness, may be built by three legged cores, instead of three single phase units. This has the advantage of using well established methods of power transformers industry, but the performance of the devices depends on the type of fault, e.g. phase to ground or phase to phase. For instance, in a three legged core, a phase to ground fault affects healthy phases, and these are the most frequent faults in distribution grids, where such systems are envisaged. The effects of asymmetric faults are analysed in this paper, by means of measured excursions in the linked flux-current plane.

  19. Elucidation of DC Magnetic Deviation in Converter Transformers Used for a Self-Commutated BTB System during Single-Line-to-Ground Faults

    NASA Astrophysics Data System (ADS)

    Hagiwara, Makoto; Pham, Phuong Viet; Akagi, Hirofumi

    This paper deals with a 50-MW self-commutated BTB (Back-To-Back) system intended for power-flow control between transmission networks. It focuses on the dynamic behavior of the BTB system during single-line-to-ground (SLG) faults. During an SLG fault, a dc magnetic deviation appears in the converter-transformers used for the BTB system just after the occurrence and restoration of the fault. It is indispensable to understand an amount of deviation because it may bring magnetic saturation as well as a large amount of magnetizing current to the transformers. This paper derives theoretical equations related to the deviation during the SLG fault. The theoretical analysis developed in this paper would make significant contributions to designing the transformers.

  20. DC wiring system grounding and ground fault protection issues for central station photovoltaic power plants

    NASA Technical Reports Server (NTRS)

    Simburger, E. J.

    1983-01-01

    The DC wiring system for a photovoltaic power plant presents a number of unique challenges to be overcome by the plant designers. There are a number of different configurations that the grounding of the DC wiring system can take, and the choice will affect the number and type of protective devices required to ensure safety of personnel and protection of equipment. The major grounding and fault protection considerations that must be taken into account when selecting the basic overall circuit configuration are summarized. The inherent advantages and disadvantages of each type of circuit grounding (resistance or solid) along with the personnel safety and equipment protection issues for each of these grounding methods are presented.

  1. Fault Current Distribution and Pole Earth Potential Rise (EPR) Under Substation Fault

    NASA Astrophysics Data System (ADS)

    Nnassereddine, M.; Rizk, J.; Hellany, A.; Nagrial, M.

    2013-09-01

    New high-voltage (HV) substations are fed by transmission lines. The position of these lines necessitates earthing design to ensure safety compliance of the system. Conductive structures such as steel or concrete poles are widely used in HV transmission mains. The earth potential rise (EPR) generated by a fault at the substation could result in an unsafe condition. This article discusses EPR based on substation fault. The pole EPR assessment under substation fault is assessed with and without mutual impedance consideration. Split factor determination with and without the mutual impedance of the line is also discussed. Furthermore, a simplified formula to compute the pole grid current under substation fault is included. Also, it includes the introduction of the n factor which determines the number of poles that required earthing assessments under substation fault. A case study is shown.

  2. Input current shaped ac-to-dc converters

    NASA Technical Reports Server (NTRS)

    1985-01-01

    Input current shaping techniques for ac-to-dc converters were investigated. Input frequencies much higher than normal, up to 20 kHz were emphasized. Several methods of shaping the input current waveform in ac-to-dc converters were reviewed. The simplest method is the LC filter following the rectifier. The next simplest method is the resistor emulation approach in which the inductor size is determined by the converter switching frequency and not by the line input frequency. Other methods require complicated switch drive algorithms to construct the input current waveshape. For a high-frequency line input, on the order of 20 kHz, the simple LC cannot be discarded so peremptorily, since the inductor size can be compared with that for the resistor emulation method. In fact, since a dc regulator will normally be required after the filter anyway, the total component count is almost the same as for the resistor emulation method, in which the filter is effectively incorporated into the regulator.

  3. A feasibility study of full-bridge type superconducting fault current controller on electric machine power stability

    NASA Astrophysics Data System (ADS)

    Jang, J. Y.; Hwang, Y. J.; Lee, J.; Ko, T. K.

    2016-02-01

    Recently, because of the advent of Smart Grid and integration of distributed generations, electrical power grids are facing uncountable challenges. Increase of fault current is one of such serious challenges and there are some fault current limiters (FCLs) that can limit the fault current. Existing grid protection FCLs, however, simply limit the fault current passively and can allow the existing protection coordination schemes to fail. This phenomenon leads to catastrophic failure in the complex system and may cause unpredictable power grid operation. Unlike a FCL, a superconducting fault current controller (SFCC) employs a full-bridge thyristor rectifier, a high temperature superconducting (HTS) DC reactor, and an embedded control unit to maintain the fault current level at a proper value by adjusting the phase angle of thyristors. This paper contains experimental and numerical analysis to design and fabricate a SFCC system for protection and stability improvement in power grids. At first, fundamental characteristics of a SFCC system were introduced. System circuit diagram and operational principles were proposed. Secondly, the developed small-scale SFCC system was introduced and verified. A 40 Vrms/30 Arms class prototype SFCC employing HTS DC reactor was fabricated and short circuit tests that simulate various fault conditions were implemented to verify the control performance of the fault current. Finally, the practical feasibility of application of the SFCC system to the power system was studied. The problems caused by three-phase faults from the power grid were surveyed and transient stability analysis of the power system was conducted by simulations. From the experimental and simulation results, we can verify the feasibility of the SFCC in power system.

  4. AC-DC converter with an improved input current waveform

    SciTech Connect

    Yuvarajan, S.; Weng, D.F.; Chen, M.S.

    1995-12-31

    The paper proposes a new control scheme for an ac-dc converter that will reduce the total harmonic distortion in the input current while operating at an improved power factor. The circuit uses a diode rectifier whose output is varied by a boost regulator with a second-harmonic injected PWM. An approximate analysis shows that the addition of a second harmonic component in the PWM helps to reduce the third harmonic in the input current. The design parameters are obtained using digital simulation. The results obtained on an experimental converter are compared with the ones obtained from a conventional scheme.

  5. Fault current limiter with solid-state circuit breakers

    NASA Astrophysics Data System (ADS)

    Bălan, H.; Neamț, L.; Buzdugan, M. I.; Varodi, T.; Pop, E.

    2016-08-01

    Switching of power circuit breakers is an important technical issue, especially at short circuit, since the fault current cause thermal and dynamic stresses, and the power quality worsens. Recently, the development of distributed renewable electricity induces the short circuit protection problematic because the distributed production of electric energy cause the transport networks to lose their radial character and disturbs the protective relays coordination. The modern technologies for power switching uses static fault current limiters, which offers a viable solution to remove the problems caused by large fault currents in the system. An appropriate design of the current limiting device reduces the thermal and dynamic stress and limits the fault current to a low value. The static switches are based on high power semiconductor devices that offer advantages compared to mechanical switches. Using a fault current limiter that minimizes the effect of distributed generation of electricity in a radial network on the co-ordination of protective relays is a solution to this problem in terms of switching speed and lifespan of power switches.

  6. Assessment on the influence of resistive superconducting fault current limiter in VSC-HVDC system

    NASA Astrophysics Data System (ADS)

    Lee, Jong-Geon; Khan, Umer Amir; Hwang, Jae-Sang; Seong, Jae-Kyu; Shin, Woo-Ju; Park, Byung-Bae; Lee, Bang-Wook

    2014-09-01

    Due to fewer risk of commutation failures, harmonic occurrences and reactive power consumptions, Voltage Source Converter (VSC) based HVDC system is known as the optimum solution of HVDC power system for the future power grid. However, the absence of suitable fault protection devices for HVDC system hinders the efficient VSC-HVDC power grid design. In order to enhance the reliability of the VSC-HVDC power grid against the fault current problems, the application of resistive Superconducting Fault Current Limiters (SFCLs) could be considered. Also, SFCLs could be applied to the VSC-HVDC system with integrated AC Power Systems in order to enhance the transient response and the robustness of the system. In this paper, in order to evaluate the role of SFCLs in VSC-HVDC systems and to determine the suitable position of SFCLs in VSC-HVDC power systems integrated with AC power System, a simulation model based on Korea Jeju-Haenam HVDC power system was designed in Matlab Simulink/SimPowerSystems. This designed model was composed of VSC-HVDC system connected with an AC microgrid. Utilizing the designed VSC-HVDC systems, the feasible locations of resistive SFCLs were evaluated when DC line-to-line, DC line-to-ground and three phase AC faults were occurred. Consequently, it was found that the simulation model was effective to evaluate the positive effects of resistive SFCLs for the effective suppression of fault currents in VSC-HVDC systems as well as in integrated AC Systems. Finally, the optimum locations of SFCLs in VSC-HVDC transmission systems were suggested based on the simulation results.

  7. Bifurcation boundary conditions for current programmed PWM DC-DC converters at light loading

    NASA Astrophysics Data System (ADS)

    Fang, Chung-Chieh

    2012-10-01

    Three types of bifurcations (instabilities) in the PWM DC-DC converter at light loading under current mode control in continuous-conduction mode (CCM) or discontinuous-conduction mode (DCM) are analysed: saddle-node bifurcation (SNB) in CCM or DCM, border-collision bifurcation during the CCM-DCM transition, and period-doubling bifurcation in CCM. Different bifurcations occur in some particular loading ranges. Bifurcation boundary conditions separating stable regions from unstable regions in the parametric space are derived. A new methodology to analyse the SNB in the buck converter based on the peak inductor current is proposed. The same methodology is applied to analyse the other types of bifurcations and converters. In the buck converter, multiple stable/unstable CCM/DCM steady-state solutions may coexist. Possibility of multiple solutions deserves careful study, because an ignored solution may merge with a desired stable solution and make both disappear. Understanding of SNB can explain some sudden disappearances or jumps of steady-state solutions observed in switching converters.

  8. Input-current shaped ac to dc converters

    NASA Technical Reports Server (NTRS)

    1986-01-01

    The problem of achieving near unity power factor while supplying power to a dc load from a single phase ac source of power is examined. Power processors for this application must perform three functions: input current shaping, energy storage, and output voltage regulation. The methods available for performing each of these three functions are reviewed. Input current shaping methods are either active or passive, with the active methods divided into buck-like and boost-like techniques. In addition to large reactances, energy storage methods include resonant filters, active filters, and active storage schemes. Fast voltage regulation can be achieved by post regulation or by supplementing the current shaping topology with an extra switch. Some indications of which methods are best suited for particular applications concludes the discussion.

  9. High voltage fault current limiter having immersed phase coils

    SciTech Connect

    Darmann, Francis Anthony

    2014-04-22

    A fault current limiter including: a ferromagnetic circuit formed from a ferromagnetic material and including at least a first limb, and a second limb; a saturation mechanism surrounding a limb for magnetically saturating the ferromagnetic material; a phase coil wound around a second limb; a dielectric fluid surrounding the phase coil; a gaseous atmosphere surrounding the saturation mechanism.

  10. New Approaches for Direct Current (DC) Balanced SpaceWire

    NASA Technical Reports Server (NTRS)

    Kisin, Alex; Rakow, Glenn

    2016-01-01

    Direct Current (DC) line balanced SpaceWire is attractive for a number of reasons. Firstly, a DC line balanced interface provides the ability to isolate the physical layer with either a transformer or capacitor to achieve higher common mode voltage rejection and or the complete galvanic isolation in the case of a transformer. And secondly, it provides the possibility to reduce the number of conductors and transceivers in the classical SpaceWire interface by half by eliminating the Strobe line. Depending on the modulator scheme the clock data recovery frequency requirements may be only twice that of the transmit clock, or even match the transmit clock: depending on the Field Programmable Gate Array (FPGA) decoder design. In this paper, several different implementation scenarios will be discussed. Two of these scenarios are backward compatible with the existing SpaceWire hardware standards except for changes at the character level. Three other scenarios, while decreasing by half the standard SpaceWire hardware components, will require changes at both the character and signal levels and work with fixed rates. Other scenarios with variable data rates will require an additional SpaceWire interface handshake initialization sequence.

  11. Test Report - Fault Current Through Graphite Filament Reinforced Plastic

    NASA Technical Reports Server (NTRS)

    Evans, R. W.

    1997-01-01

    Tests were performed to determine the damage to samples of composite material when a current carrying wire is shorted to the surface of the composite material, and to determine whether enough current can flow through the material to blow a fuse before damage can occur. Fault current tests were performed on samples of graphite epoxy materials. Samples consisted of six layers of IM7 graphite fiber mat in Hercules 8552 epoxy resin. A variable power supply provided up to 35 amps of current. The high voltage side of the power supply was attached to a wire at the end of a hinged arm, and the low side was attached to the edge of the sample. To test joints, the return was connected to the edge of one sample, and the high side was shorted to the top of the other sample. Tests show that when current exceeds approximately 5 amps, the graphite glows, and the epoxy melts out at the shorted contact. At higher current levels the epoxy burns. At voltages above 15 volts the epoxy outer coat is easily broken, and fire, flame, and a rise in current occur suddenly. When joints are introduced, resistance is increased, and the maximum current resulting from a short circuit to the graphite epoxy is reduced. This condition can easily result in fault current lower than the circuit breaker limit and higher than the 5 amp ignition level. The shorting contact and the joint become hot spots with melting epoxy, smoke, and fire.

  12. Superconducting fault current-limiter with variable shunt impedance

    DOEpatents

    Llambes, Juan Carlos H; Xiong, Xuming

    2013-11-19

    A superconducting fault current-limiter is provided, including a superconducting element configured to resistively or inductively limit a fault current, and one or more variable-impedance shunts electrically coupled in parallel with the superconducting element. The variable-impedance shunt(s) is configured to present a first impedance during a superconducting state of the superconducting element and a second impedance during a normal resistive state of the superconducting element. The superconducting element transitions from the superconducting state to the normal resistive state responsive to the fault current, and responsive thereto, the variable-impedance shunt(s) transitions from the first to the second impedance. The second impedance of the variable-impedance shunt(s) is a lower impedance than the first impedance, which facilitates current flow through the variable-impedance shunt(s) during a recovery transition of the superconducting element from the normal resistive state to the superconducting state, and thus, facilitates recovery of the superconducting element under load.

  13. A new low-cost, fully fault-protected PWM-VSI inverter with true phase-current information

    SciTech Connect

    Blaabjerg, F.; Pedersen, J.K.

    1997-01-01

    This paper proposes a new topology for a low-cost three-phase pulse width modulation (PWM) VSI inverter where a true phase current information exists with the use of only one current sensor in the dc link. The topology also has the benefits of full protection of the inverter such as short circuits in the dc link, output phase faults, and output earth faults. Previously suggested methods have problems at low speed in detecting the phase current, but by the use of space vector modulation in a double-sided implementation, the PWM-pulses are adjusted so true information about the phase current exists even at very low speed. The dc link current is sampled twice during one switching period, and it is proposed to sample in the center of the PWM-pulses to obtain a real average phase current. The effects of blanking-time and overmodulation are also discussed. The strategy is implemented in a 16-b microcontroller, and the test results show the technique is useful in the whole speed range. It is concluded by the use of the proposed topology that only one current sensor will be necessary in the future for PWM-VSI inverters.

  14. Influence of slot number and pole number in fault-tolerant brushless dc motors having unequal tooth widths

    NASA Astrophysics Data System (ADS)

    Ishak, D.; Zhu, Z. Q.; Howe, D.

    2005-05-01

    The electromagnetic performance of fault-tolerant three-phase permanent magnet brushless dc motors, in which the wound teeth are wider than the unwound teeth and their tooth tips span approximately one pole pitch and which have similar numbers of slots and poles, is investigated. It is shown that they have a more trapezoidal phase back-emf wave form, a higher torque capability, and a lower torque ripple than similar fault-tolerant machines with equal tooth widths. However, these benefits gradually diminish as the pole number is increased, due to the effect of interpole leakage flux.

  15. Measurements of the dc Josephson current in proximity systems

    SciTech Connect

    Camerlingo, C.; Monaco, R.; Ruggiero, B.; Russo, M. ); Testa, G. )

    1995-03-01

    Junctions modeled as [ital S]-[ital N]/[ital I]/[ital S] and [ital S]-[ital N]/[ital I]/[ital N]-[ital S] proximity systems (where [ital S], [ital I], and [ital N] indicate a superconductor, an insulator, and a normal metal, respectively) are widely discussed in literature from both the experimental and theoretical point of view. In the present paper experimental aspects concerning Nb/Nb junctions including a proximity bilayer are considered. Nb-[ital M]/[ital I]/Nb and [ital M]-Nb/[ital I]/Nb structures (where [ital M] is a normal metal, a semimetal, or a superconductor) are investigated by using a semimetal (bismuth) and a superconductor (aluminum) as the [ital M] layer. In particular, how the deposition of a back layer influences the behavior of Nb/[ital I]/Nb high-quality junctions is discussed, focusing the interest on measurements of the temperature dependence of the maximum dc Josephson current. Experimental data are discussed in the framework of Kresin's theoretical calculations based on the thermodynamic Green's function method.

  16. Low-voltage, wide-range, current-controlled DC current generator

    NASA Astrophysics Data System (ADS)

    Mathew, M.; Hart, B. L.; Hayatleh, K.; Lidgey, F. J.

    2011-08-01

    Operating from a 1 V rail supply, a proposed CMOS current-controlled DC current generator can function as a repeater, attenuator or amplifier over the input current range, 1 µA to 1 mA, with a current-transfer ratio accuracy better than 1% using IBM technology, characterised by a process with a 0.13 µm minimum feature size. In repeater mode, the incremental output resistance exceeds 30 MΩ for an output current of 500 µA at an output voltage of 0.20 V, and exceeds 1 MΩ for an output current of 1 mA at an output voltage of 0.22 V. For zero input current, the circuit dissipation is 117 µW.

  17. Rotor position sensor switches currents in brushless dc motors

    NASA Technical Reports Server (NTRS)

    1965-01-01

    Reluctance switch incorporated in an induction motor is used for sensing rotor position and switching armature circuits in a brushless dc motor. This device drives the solar array system of an unmanned space satellite.

  18. Discrete time domain modelling and analysis of dc-dc converters with continuous and discontinuous inductor current

    NASA Technical Reports Server (NTRS)

    Iwens, R. P.; Lee, F. C.; Triner, J. E.

    1977-01-01

    Using discrete time state variable representation, a generalized computer-aided modeling and analysis of dc-dc converters is presented. The methodology provides exact modeling and is applicable to all types of power stages and duty-cycle control, including continuous and discontinuous inductor current operation. Converter stability, transient behavior and audio susceptibility can be analytically evaluated and predicted. The generalized theory of the proposed approach to converter modeling and analysis is presented first, followed by a demonstrative example applying the theory to a constant frequency buck converter operating in continuous and discontinuous inductor current mode. Excellent agreement with laboratory test data has been observed.

  19. Fault Analysis of Space Station DC Power Systems-Using Neural Network Adaptive Wavelets to Detect Faults

    NASA Technical Reports Server (NTRS)

    Momoh, James A.; Wang, Yanchun; Dolce, James L.

    1997-01-01

    This paper describes the application of neural network adaptive wavelets for fault diagnosis of space station power system. The method combines wavelet transform with neural network by incorporating daughter wavelets into weights. Therefore, the wavelet transform and neural network training procedure become one stage, which avoids the complex computation of wavelet parameters and makes the procedure more straightforward. The simulation results show that the proposed method is very efficient for the identification of fault locations.

  20. Study of a piezoelectric transformer-based DC/DC converter with a cooling system and current-doubler rectifier

    NASA Astrophysics Data System (ADS)

    Su, Yu-Hao; Liu, Yuan-Ping; Vasic, Dejan; Costa, Francois; Wu, Wen-Jong; Lee, Chuih-Kung

    2013-09-01

    The objective of this study was to increase the output current and power in a piezoelectric transformer (PT)-based DC/DC converter by using a cooling system. It is known that the output current of a PT is limited by temperature build-up because of losses, especially when driving at high vibration velocity. Although connecting different inductive circuits at the PT secondary terminal can increase the output current, the root cause of the temperature build-up problem has not yet been solved. This paper presents a study of a PT with cooling system in a DC/DC converter with a commonly used full-bridge rectifier and current-doubler rectifier. The advantages and disadvantages of the proposed technique were investigated. A theoretical-phenomenological model was developed to explain the relationship between the losses and the temperature rise. It will be shown that the vibration velocity as well as heat generation increases the losses. In our design, the maximum output current capacity can increase by 100% when the temperature of operation of the PT is kept below 55 ° C. The study comprises a theoretical part and experimental proof-of-concept demonstration of the proposed design method.

  1. Superconducting matrix fault current limiter with current-driven trigger mechanism

    DOEpatents

    Yuan; Xing

    2008-04-15

    A modular and scalable Matrix-type Fault Current Limiter (MFCL) that functions as a "variable impedance" device in an electric power network, using components made of superconducting and non-superconducting electrically conductive materials. An inductor is connected in series with the trigger superconductor in the trigger matrix and physically surrounds the superconductor. The current surge during a fault will generate a trigger magnetic field in the series inductor to cause fast and uniform quenching of the trigger superconductor to significantly reduce burnout risk due to superconductor material non-uniformity.

  2. Superconducting power link for power transmission and fault current limitation

    NASA Astrophysics Data System (ADS)

    Paasi, J.; Herrmann, P. F.; Verhaege, T.; Lehtonen, J.; Bock, J.; Cowey, L.; Freyhardt, H. C.; Usoskin, A.; Moulaert, G.; Collet, M.

    2001-05-01

    Superconducting power links (SUPERPOLI) will offer the opportunity for low-loss power transmission of high nominal currents and fault current limitation simultaneously in a single device. This paper presents the status of European SUPERPOLI project where the long term goal is to build a GVA class, 20 kV, three-phased, 200 m long superconducting power link. As a step towards the GVA-class application, a one-phase demonstrator of 2 m length for 20 kV, 2-5 kA rms operation has been designed and is now under construction. The project includes the development of two alternative low-ac-loss conductor designs suitable for current limitation: a tubular Bi-2212 bulk conductor with moderate Jc and a tubular YBCO coated conductor with high Jc.

  3. Pupils' Representations of Electric Current before, during and after Instruction on DC Circuits.

    ERIC Educational Resources Information Center

    Psillos, D.; And Others

    1987-01-01

    Reported are compulsory education pupils' representations of electric current in a constructivist approach to introducing direct current (DC) circuits. Suggests that the pupils views can be modelled after an energy framework. Makes suggestions about the content, the apparatus and the experiments used in teaching DC circuits. (CW)

  4. New fault locating system for air-insulated substations using optical current detector

    SciTech Connect

    Yoshida, Y.; Kawazoe, S. ); Ibuki, K.; Yamada, K.; Ochi, N. . Itami Works)

    1992-10-01

    This paper deals with a newly developed fault locating system. This fault locating system helps to shorten the time required for restoration of service after the occurrence of a busbar fault in an air-insulated distribution substation. Recent optical and electronic technologies allow highly accurate and compact fault locating system, which consists of optical current detectors using Faraday effect and a fault locating processor employing digital data processing technique. The fault location is made by discriminating the direction of zero-sequence currents. Through various tests and field operations it has been confirmed that the system has sufficient performance for practical application.

  5. Restoration and testing of an HTS fault current controller

    SciTech Connect

    Waynert, J. A.; Boenig, H.; Mielke, C. H.; Willis, J. O.; Burley, B. L.

    2002-01-01

    A three-phase, 1200 A, 12.5 kV fault current controller using three HTS 4 mH coils, was built by industry and tested in 1999 at the Center Substation of Southern California Edison in Norwalk, CA. During the testing, it appeared that each of the three single-phase units had experienced a voltage breakdown, one externally and two internally. Los Alamos National Laboratory (LANL) was asked by DOE to restore the operation of the fault current controller provided the HTS coils had not been damaged during the initial substation tests. When the internally-failed coil vacuum vessels were opened it became evident that in these two vessels, a flashover had occurred at the high voltage bus section leading to the terminals of the superconducting coil. An investigation into the failure mechanism resulted in six possible causes for the flashover. Based on these causes, the high voltage bus was completely redesigned. Single-phase tests were successfully performed on the modified unit at a 13.7 kV LANL substation. This paper presents the postulated voltage flashover failure mechanisms, the new high voltage bus design which mitigates the failure mechanisms, the sequence of tests used to validate the new design, and finally, the results of variable load and short-circuit tests with the single-phase unit operating on the LANL 13.7 kV substation.

  6. Observation of self-magnetic field relaxations in Bi2223 and Y123 HTS tapes after over-current pulse and DC current operation

    NASA Astrophysics Data System (ADS)

    Tallouli, M.; Sun, J.; Chikumoto, N.; Otabe, E. S.; Shyshkin, O.; Charfi-Kaddour, S.; Yamaguchi, S.

    2016-07-01

    The development of power transmission lines based on long-length HTS tapes requires the production of high quality tapes. Due to fault conditions, technical mistakes and human errors during the operation of a DC power transmission line, an over-current pulse, several times larger than the rated current, could occur. To study the effect of such over-current pulses on the transport current density distribution in the HTS tapes, we simulated two start-up scenarios for one BSCCO and two YBCO tapes. The first start-up scenario is an initial over-current pulse during which the transport current was turned on rapidly, rising to 900 A during the first milliseconds, then reduced to a 100 A DC current. The second start-up scenario is normal operation, and involved increasing the transport current slowly from 0 A to 100 A at a rate of 1 A/s. For both scenarios, we then measured the vertical component of the self-magnetic field by means of a Hall probe above the tape, and afterward, by solving a linear equation of the inverse problem we obtain the current density profiles. We observe a change of the self-magnetic field above the edge of the BSCCO and YBCO tapes during 30 min after the 5 ms of over-current pulse and during the normal operation. The current density profiles are peaked in the centre for over-current pulse, and more peaked around the edge of the HTS tape for normal operation, which means that the limited time over-current pulse changes the current density profiles of the HTS tapes. We observe also a loop of current for YBCO tapes and we show the role of the HTS tape stabilizer.

  7. Multiphase soft switched DC/DC converter and active control technique for fuel cell ripple current elimination

    DOEpatents

    Lai, Jih-Sheng; Liu, Changrong; Ridenour, Amy

    2009-04-14

    DC/DC converter has a transformer having primary coils connected to an input side and secondary coils connected to an output side. Each primary coil connects a full-bridge circuit comprising two switches on two legs, the primary coil being connected between the switches on each leg, each full-bridge circuit being connected in parallel wherein each leg is disposed parallel to one another, and the secondary coils connected to a rectifying circuit. An outer loop control circuit that reduces ripple in a voltage reference has a first resistor connected in series with a second resistor connected in series with a first capacitor which are connected in parallel with a second capacitor. An inner loop control circuit that reduces ripple in a current reference has a third resistor connected in series with a fourth resistor connected in series with a third capacitor which are connected in parallel with a fourth capacitor.

  8. System and method for motor fault detection using stator current noise cancellation

    DOEpatents

    Zhou, Wei; Lu, Bin; Nowak, Michael P.; Dimino, Steven A.

    2010-12-07

    A system and method for detecting incipient mechanical motor faults by way of current noise cancellation is disclosed. The system includes a controller configured to detect indicia of incipient mechanical motor faults. The controller further includes a processor programmed to receive a baseline set of current data from an operating motor and define a noise component in the baseline set of current data. The processor is also programmed to acquire at least on additional set of real-time operating current data from the motor during operation, redefine the noise component present in each additional set of real-time operating current data, and remove the noise component from the operating current data in real-time to isolate any fault components present in the operating current data. The processor is then programmed to generate a fault index for the operating current data based on any isolated fault components.

  9. System and method for bearing fault detection using stator current noise cancellation

    DOEpatents

    Zhou, Wei; Lu, Bin; Habetler, Thomas G.; Harley, Ronald G.; Theisen, Peter J.

    2010-08-17

    A system and method for detecting incipient mechanical motor faults by way of current noise cancellation is disclosed. The system includes a controller configured to detect indicia of incipient mechanical motor faults. The controller further includes a processor programmed to receive a baseline set of current data from an operating motor and define a noise component in the baseline set of current data. The processor is also programmed to repeatedly receive real-time operating current data from the operating motor and remove the noise component from the operating current data in real-time to isolate any fault components present in the operating current data. The processor is then programmed to generate a fault index for the operating current data based on any isolated fault components.

  10. Design, Test and Demonstration of Saturable Reactor High-Temperature Superconductor Fault Current Limiters

    SciTech Connect

    Darmann, Frank; Lombaerde, Robert; Moriconi, Franco; Nelson, Albert

    2012-03-01

    Zenergy Power has successfully designed, built, tested, and installed in the US electrical grid a saturable reactor Fault Current Limiter. Beginning in 2007, first as SC Power Systems and from 2008 as Zenergy Power, Inc., ZP used DOE matching grant and ARRA funds to help refine the design of the saturated reactor fault current limiter. ZP ultimately perfected the design of the saturated reactor FCL to the point that ZP could reliably design a suitable FCL for most utility applications. Beginning with a very basic FCL design using 1G HTS for a coil housed in a LN2 cryostat for the DC bias magnet, the technology progressed to a commercial system that was offered for sale internationally. Substantial progress was made in two areas. First, the cryogenics cooling system progressed from a sub-cooled liquid nitrogen container housing the HTS coils to cryostats utilizing dry conduction cooling and reaching temperatures down to less than 20 degrees K. Large, round cryostats with warm bore diameters of 1.7 meters enabled the design of large tanks to hold the AC components. Second, the design of the AC part of the FCL was refined from a six legged spider design to a more compact and lighter design with better fault current limiting capability. Further refinement of the flux path and core shape led to an efficient saturated reactor design requiring less Ampere-turns to saturate the core. In conclusion, the development of the saturable reactor FCL led to a more efficient design not requiring HTS magnets and their associated peripheral equipment, which yielded a more economical product in line with the electric utility industry expectations. The original goal for the DOE funding of the ZP project Design, Test and Demonstration of Saturable Reactor High-Temperature Superconductor Fault Current Limiters was to stimulate the HTS wire industry with, first 1G, then 2G, HTS wire applications. Over the approximately 5 years of ZP's product development program, the amount of HTS wire

  11. Complete bifurcation analysis of DC-DC converters under current mode control

    NASA Astrophysics Data System (ADS)

    Pikulin, D.

    2014-03-01

    The purpose of this research is to investigate to what extend application of novel method of complete bifurcation groups to the analysis of global dynamics of piecewise-smooth hybrid systems enables one to highlight new nonlinear effects before periodic and chaotic regimes. Results include the construction of complete one and two-parameter bifurcation diagrams, detection of various types of bifurcation groups and investigation of their interactions, localization of rare attractors, and the investigation of different principles of birth of chaotic attractors. Effectiveness of the approach is illustrated in respect to one of the most widely used switching systems-boost converter under current mode control operating in continuous current mode.

  12. AC and DC transport currents in melt-grown YBCO

    SciTech Connect

    Yi, Z.; Ashworth, S.; Becluz, C.; Scurlock, R.G. )

    1991-03-01

    It has been suggested that the transport J{sub c} in multi-grain samples of bulk YBCO are limited by the intergrain links. This paper reports on preliminary measurements of intergrain currents. The intergrain critical currents in melt grown YBCO do not appear to be as sensitive to the precise crystallographic alignment of adjacent grains a has been reported for thin films. The measured critical current of similar grain boundaries varies widely, between 15000 A/cm{sup 2} and 200A/Cm{sub 2} for adjacent boundaries in the same sample.

  13. Impact of quasi-dc currents on three-phase distribution transformer installations

    SciTech Connect

    McConnell, B.W.; Barnes, P.R. ); Tesche, F.M. , Dallas, TX ); Schafer, D.A. )

    1992-06-01

    This report summarizes a series of tests designed to determine the response of quasi-dc currents on three-phase power distribution transformers for electric power systems. In general, if the dc injection is limited to the primary side of a step-down transformer, significant harmonic distortion is noted and an increase in the reactive power demand results. For dc injection on the secondary (load) side of the step-down transformer the harmonic content at the secondary side is quite high and saturation occurs with a relatively low level of dc injection; however, the reactive power demand is significantly lower. These tests produced no apparent damage to the transformers. Transformer damage is dependent on the duration of the dc excitation, the level of the excitation, and on thermal characteristics of the transfer. The transformer response time is found to be much shorter than seen in power transformer tests at lower dc injection levels. This shorter response time suggests that the response time is strongly dependent on the injected current levels, and that higher levels of dc injection for shorter durations could produce very high reactive power demands and harmonic distortion within a few tenths of a second. The added reactive power load could result in the blowing of fuses on the primary side of the transformer for even moderate dc injection levels, and neutral currents are quite large under even low-level dc injection. This smoking neutral'' results in high-level harmonic injection into equipment via the neutral and in possible equipment failure.

  14. High current DC negative ion source for cyclotron

    NASA Astrophysics Data System (ADS)

    Etoh, H.; Onai, M.; Aoki, Y.; Mitsubori, H.; Arakawa, Y.; Sakuraba, J.; Kato, T.; Mitsumoto, T.; Hiasa, T.; Yajima, S.; Shibata, T.; Hatayama, A.; Okumura, Y.

    2016-02-01

    A filament driven multi-cusp negative ion source has been developed for proton cyclotrons in medical applications. In Cs-free operation, continuous H- beam of 10 mA and D- beam of 3.3 mA were obtained stably at an arc-discharge power of 3 kW and 2.4 kW, respectively. In Cs-seeded operation, H- beam current reached 22 mA at a lower arc power of 2.6 kW with less co-extracted electron current. The optimum gas flow rate, which gives the highest H- current, was 15 sccm in the Cs-free operation, while it decreased to 4 sccm in the Cs-seeded operation. The relationship between H- production and the design/operating parameters has been also investigated by a numerical study with KEIO-MARC code, which gives a reasonable explanation to the experimental results of the H- current dependence on the arc power.

  15. High current DC negative ion source for cyclotron.

    PubMed

    Etoh, H; Onai, M; Aoki, Y; Mitsubori, H; Arakawa, Y; Sakuraba, J; Kato, T; Mitsumoto, T; Hiasa, T; Yajima, S; Shibata, T; Hatayama, A; Okumura, Y

    2016-02-01

    A filament driven multi-cusp negative ion source has been developed for proton cyclotrons in medical applications. In Cs-free operation, continuous H(-) beam of 10 mA and D(-) beam of 3.3 mA were obtained stably at an arc-discharge power of 3 kW and 2.4 kW, respectively. In Cs-seeded operation, H(-) beam current reached 22 mA at a lower arc power of 2.6 kW with less co-extracted electron current. The optimum gas flow rate, which gives the highest H(-) current, was 15 sccm in the Cs-free operation, while it decreased to 4 sccm in the Cs-seeded operation. The relationship between H(-) production and the design/operating parameters has been also investigated by a numerical study with KEIO-MARC code, which gives a reasonable explanation to the experimental results of the H(-) current dependence on the arc power. PMID:26932017

  16. Integrated on-chip 0.35 μm BiCMOS current-mode DC-DC buck converter

    NASA Astrophysics Data System (ADS)

    Lee, Chan-Soo; Kim, Nam-Soo; Gendensuren, Munkhsuld; Choi, Jae-Ho; Choi, Joong-Ho

    2012-12-01

    A current-mode DC-DC buck converter with a fully integrated power module is presented in this article. The converter is implemented using BiCMOS technology in amplifier and power MOSFET in a current sensor. The current sensor is realised by the power lateral double-diffused MOSFET with the aspect ratio much larger than that of a matched p-MOSFET. In addition, BiCMOS technology is applied in the error amplifier for an accurate current sensing and a fast transient response. The DC-DC converter is fabricated with 0.35 µm BiCMOS process. Experimental results show that the fully integrated converter operates at 1.3 MHz switching frequency with a supply voltage of 5 V. The output DC voltage is obtained as expected and the output ripple is controlled to be within 2% with a 30 µH off-chip inductor and 100 µF off-chip capacitor.

  17. DC characterisation of HBTS using the observed kink effect on the base current

    NASA Astrophysics Data System (ADS)

    Sotoodeh, M.; Khalid, A. H.; Rezazadeh, A. A.

    1998-04-01

    Large parasitic series resistances of the heterostructure bipolar transistors are shown to cause a sharp rise in the base current of the Gummel plot at high current levels. This effect is analysed and attributed to a forward-biased base-collector junction due to the large voltage drop across the collector series resistance of the device. The occurrence of this effect results in a severe reduction in current gain of the device at high current levels. A DC Ebers-Moll model is presented with all the parameters extracted from DC characterisation of the HBT, and an excellent fit between the model and experimental data is obtained. The method can be used to determine the base, collector and emitter series resistances of the bipolar transistors for DC applications. Finally, the effect of temperature on the onset of this effect is demonstrated.

  18. Implementation of superconducting fault current limiter for flexible operation in the power substation

    NASA Astrophysics Data System (ADS)

    Song, Chong Suk; Lee, Hansang; Cho, Yoon-sung; Suh, Jaewan; Jang, Gilsoo

    2014-09-01

    The concentration of large-scale power loads located in the metropolitan areas have resulted in high fault current levels during a fault thereby requiring the substation to operate in the double busbar configuration mode. However, the double busbar configuration mode results in deterioration of power system reliability and unbalanced power flow in the adjacent transmission lines which may result in issues such as overloading of lines. This paper proposes the implementation of the superconducting fault current limiter (SFCL) to be installed between the two substation busbars for a more efficient and flexible operation of the substation enabling both single and double busbar configurations depending on the system conditions for guaranteeing power system reliability as well as fault current limitations. Case studies are being performed for the effectiveness of the SFCL installation and results are compared for the cases where the substation is operating in single and double busbar mode and with and without the installation of the SFCL for fault current mitigation.

  19. Low current linearization of magnetic amplifier for dc transducer

    NASA Technical Reports Server (NTRS)

    Nagano, S. (Inventor)

    1981-01-01

    A magnetic amplifier having two saturable reactor cores with a separate excitation winding on each connected in series opposition, a common control winding, and a common output winding, is adapted for use as a low level signal transducer. The separate excitation windings are excited in push-pull mode through a center tapped transformer, and at least one diode is included in series with a load resistor connected to the output winding. A resistor in series with the output winding and load resistor is connected between the center tap of the excitation transformer and the connection between the two excitation windings of the saturable cores. This series resistor provides a return current path for the output winding and allows the excitation windings of the saturable cores to operate as primary windings of transformers.

  20. DC bias effect on alternating current electrical conductivity of poly(ethylene terephthalate)/alumina nanocomposites

    NASA Astrophysics Data System (ADS)

    Nikam, Pravin N.; Deshpande, Vineeta D.

    2016-05-01

    Polymer nanocomposites based on metal oxide (ceramic) nanoparticles are a new class of materials with unique properties and designed for various applications such as electronic device packaging, insulation, fabrication and automotive industries. Poly(ethylene terephthalate) (PET)/alumina (Al2O3) nanocomposites with filler content between 1 wt% and 5 wt% were prepared by melt compounding method using co-rotating twin screw extruder and characterized by scanning electron microscopy (SEM), transmission electron microscopy (TEM) and precision LCR meter techniques. The results revealed that proper uniform dispersion at lower content up to 2 wt% of nano-alumina observed by using TEM. Aggregation of nanoparticles was observed at higher content of alumina examined by using SEM and TEM. The frequency dependences of the alternating current (AC) conductivity (σAC) of PET/alumina nanocomposites on the filler content and DC bias were investigated in the frequency range of 20Hz - 1MHz. The results showed that the AC and direct current (DC) conductivity increases with increasing DC bias and nano-alumina content upto 3 wt%. It follows the Jonscher's universal power law of solids. It revealed that σAC of PET/alumina nanocomposites can be well characterized by the DC conductivity (σDC), critical frequency (ωc), critical exponent of the power law (s). Roll of DC bias potential led to an increase of DC conductivity (σDC) due to the creation of additional conducting paths with the polymer nanocomposites and percolation behavior achieved through co-continuous morphology.

  1. Sensorless Vector Control of IPMSM with DC Link Current Measurement at Low Speeds

    NASA Astrophysics Data System (ADS)

    Kubota, Hisao; Nakagawa, Satoshi; Kobayashi, Takayuki

    This paper presents a method of estimating pole position of interior permanent magnet synchronous motors, IPMSMs. The proposed method estimates the pole position at low speeds and standstill by measuring only the DC link current of the inverter. The pole position is estimated by using the saliency of the IPMSMs. In order to detect the saliency, the three phase triangular carrier waves are used. The DC link current is measured at tops and bottoms of the carrier waves. Experimentation is performed to confirm the validity of the proposed method.

  2. Current Fault Management Trends in NASA's Planetary Spacecraft

    NASA Technical Reports Server (NTRS)

    Fesq, Lorraine M.

    2009-01-01

    The key product of this three-day workshop is a NASA White Paper that documents lessons learned from previous missions, recommended best practices, and future opportunities for investments in the fault management domain. This paper summarizes the findings and recommendations that are captured in the White Paper.

  3. Development of Fault Point Locating System for Underground Transmission Lines using Optical Fiber Current Sensors

    NASA Astrophysics Data System (ADS)

    Kurosawa, Kiyoshi; Kondo, Reishi; Nasukawa, Shinsuke; Yamaguchi, Tatsushi; Amano, Kazuo

    Fault point locating systems based on surge current detection have recently been used for fast recovery of underground transmission line from the fault. Electromagnetic induction type sensors have mainly been used for detection of the surge current. However they are susceptible to electromagnetic noise which causes unstable system operation. To solve this problem, Tokyo Electric Power Co., Toko Electric Corporation and Fujikura Ltd., by a joint research, have developed a new system that applies optical fiber current sensors.

  4. 1 kW, 9 kV dc-dc converter module with time-sharing control of output voltage and input current

    SciTech Connect

    Borgatti, R.; Stefani, R.; Bressan, O.; Bicciato, F.; Tenti, P.; Rossetto, L.

    1993-10-01

    The paper describes a dc-dc power module based on a single-stage current-fed converter structure. Control is made according to a time-sharing strategy allowing simultaneous regulation of output voltage and input current. This solution is suitable for high-performance space and avionic applications, giving high efficiency, compactness, and accuracy, speed and robustness of control. Theoretical analysis, design criteria, and experimental results are reported. Application to radar supplies is discussed.

  5. Detecting arcing downed-wires using fault current flicker and half-cycle asymmetry

    SciTech Connect

    Sultan, A.F.; Swift, G.W. . Dept. of Electrical and Computer Engineering); Fedirchuk, D.J. . System Operating Dept.)

    1994-01-01

    The downed-wires problem, known as high impedance faults, is described. A high voltage laboratory setup was devised to investigate the phenomenon. The laboratory model results agreed with field test results, and previous research efforts. The arcing fault model was justified. The setup was used as a source of fault current signal. A simple approach was taken to design an arcing fault detector. The algorithm utilizes the random behavior of the fault current. It compares the positive and negative current peaks in one cycle to those in the next cycle to measure the flicker in the current signal. The asymmetry of the current is calculated by comparing the positive peak to the negative peak, for each cycle; the moving window length is half a cycle. Both values are used as a signature of arcing. The result is filtered and compared with a suitable detection threshold. The algorithm was tested by traces of normal load, and no-load current disturbed by currents of faults on dry and wet soil, arc welders, computers, and fluorescent light loads, as well as short circuit currents. The algorithm performed well under the test conditions, except for the arc welder load. This load is also a source of insecurity for other algorithms. The detection criterion will be integrated with another detection method to improve the security during arcing load events. On-line testing is required to demonstrate algorithm dependability.

  6. Operation of the DC current transformer intensity monitors at FNAL during run II

    SciTech Connect

    Crisp, J.; Fellenz, B.; Heikkinen, D.; Ibrahim, M.A.; Meyer, T.; Vogel, G.; /Fermilab

    2012-01-01

    Circulating beam intensity measurements at FNAL are provided by five DC current transformers (DCCT), one per machine. With the exception of the DCCT in the Recycler, all DCCT systems were designed and built at FNAL. This paper presents an overview of both DCCT systems, including the sensor, the electronics, and the front-end instrumentation software, as well as their performance during Run II.

  7. New Current Control Method of DC Power Supply for Magnetic Perturbation Coils on J-TEXT

    NASA Astrophysics Data System (ADS)

    Zeng, Wubing; Ding, Yonghua; Yi, Bin; Xu, Hangyu; Rao, Bo; Zhang, Ming; Liu, Minghai

    2014-11-01

    In order to advance the research on suppressing tearing modes and driving plasma rotation, a DC power supply (PS) system has been developed for dynamic resonant magnetic perturbation (DRMP) coils and applied in the J-TEXT experiment. To enrich experimental phenomena in the J-TEXT tokamak, applying the circulating current four-quadrant operation mode in the DRMP DC PS system is proposed. By using the circulating current four-quadrant operation, DRMP coils can be smoothly controlled without the dead-time when the current polarity reverses. Essential circuit analysis, control optimization and simulation of desired scenarios have been performed for normal current. Relevant simulation and test results are also presented.

  8. Analysis of transient state in HTS tapes under ripple DC load current

    NASA Astrophysics Data System (ADS)

    Stepien, M.; Grzesik, B.

    2014-05-01

    The paper concerns the analysis of transient state (quench transition) in HTS tapes loaded with the current having DC component together with a ripple component. Two shapes of the ripple were taken into account: sinusoidal and triangular. Very often HTS tape connected to a power electronic current supply (i.e. superconducting coil for SMES) that delivers DC current with ripples and it needs to be examined under such conditions. Additionally, measurements of electrical (and thermal) parameters under such ripple excitation is useful to tape characterization in broad range of load currents. The results presented in the paper were obtained using test bench which contains programmable DC supply and National Instruments data acquisition system. Voltage drops and load currents were measured vs. time. Analysis of measured parameters as a function of the current was used to tape description with quench dynamics taken into account. Results of measurements were also used to comparison with the results of numerical modelling based on FEM. Presented provisional results show possibility to use results of measurements in transient state to prepare inverse models of superconductors and their detailed numerical modelling.

  9. Investigation of DC current injection effect on the microwave characteristics of HTS YBCO microstrip resonators

    NASA Astrophysics Data System (ADS)

    Nurgaliev, T.; Blagoev, B.; Mateev, E.; Neshkov, L.; Strbik, V.; Uspenskaya, L.; Nedkov, I.; Chromik, Š.

    2014-03-01

    The DC current injection effect from a ferromagnetic (FM) La0.7Sr0.3MnO3 (LSMO) to a high temperature superconducting (HTS) Y1Ba2Cu3O7-x (YBCO) thin film was investigated by the microwave surface impedance measurements in a FM/HTS structure, formed as a microstrip resonator for improving the sensitivity of the experiments. The quality factor and the resonance frequency of this structure were found to strongly depend on the current strength, injected from the LSMO electrode into the HTS microstrip electrode. The magnetic penetration depth and the quasiparticle conductivity of the HTS component were determined to increase under DC current injection process, which in all probability stimulated breaking of Cooper pairs and led to a decrease of the superfluid concentration and an increase of the normal fluid concentration without significantly affecting the relaxation time of the quasiparticles.

  10. Electrical motor current signal analysis using a modified bispectrum for fault diagnosis of downstream mechanical equipment

    NASA Astrophysics Data System (ADS)

    Gu, F.; Shao, Y.; Hu, N.; Naid, A.; Ball, A. D.

    2011-01-01

    This paper presents the use of the induction motor current to identify and quantify common faults within a two-stage reciprocating compressor based on bispectrum analysis. The theoretical basis is developed to understand the nonlinear characteristics of current signals when the motor undertakes a varying load under different faulty conditions. Although conventional bispectrum representation of current signal allows the inclusion of phase information and the elimination of Gaussian noise, it produces unstable results due to random phase variation of the sideband components in the current signal. A modified bispectrum based on the amplitude modulation feature of the current signal is then adopted to combine both lower sidebands and higher sidebands simultaneously and hence characterise the current signal more accurately. Based on this new bispectrum analysis a more effective diagnostic feature, namely normalised bispectral peak, is developed for fault classification. In association with the kurtosis value of the raw current signal, the bispectrum feature gives rise to reliable fault classification results. In particular, the low feature values can differentiate the belt looseness from the other fault cases and different degrees of discharge valve leakage and inter-cooler leakage can be separated easily using two linear classifiers. This work provides a novel approach to the analysis of stator current for the diagnosis of motor drive faults from downstream driving equipment.

  11. Current-based sensorless detection of stator winding turn faults in induction machines

    NASA Astrophysics Data System (ADS)

    Tallam, Rangarajan M.

    To improve the reliability of motor-driven processes, condition monitoring of electric machines has received considerable attention from industry. For small- and medium-sized machines, the focus is on low-cost sensorless schemes that use only measured voltages and currents for fault diagnostics. Turn faults arising from stator winding insulation deterioration account for a large percentage of motor failures. The objective of a turn-fault detection scheme is to provide a warning before the fault propagates further and results in ground current, causing irreversible damage to the magnetic material. In this work, a neural-network-based robust scheme for early detection of turn faults in induction machines is developed. The negative-sequence component of line currents is used as the fault signature, and a neural network is trained to compensate for the effects of unbalanced supply voltages and nonidealities in the machine or instrumentation. Novel training algorithms for self-commissioning and on-line training of the neural network have also been developed. Experimental results, obtained on a specially-rewound machine, are provided to demonstrate that the method is capable of early fault detection. Data memory and computational requirements are also minimal, making the scheme viable for commercial implementation. The method is also extended to turn-fault detection in open-loop inverter-fed induction machines. Data obtained from a thermally accelerated insulation failure experiment is also used to test the performance and sensitivity of the method, and to show that a turn fault can be detected before failure of insulation to ground.

  12. Acoustic Noise Alters Selective Attention Processes as Indicated by Direct Current (DC) Brain Potential Changes

    PubMed Central

    Trimmel, Karin; Schätzer, Julia; Trimmel, Michael

    2014-01-01

    Acoustic environmental noise, even of low to moderate intensity, is known to adversely affect information processing in animals and humans via attention mechanisms. In particular, facilitation and inhibition of information processing are basic functions of selective attention. Such mechanisms can be investigated by analyzing brain potentials under conditions of externally directed attention (intake of environmental information) versus internally directed attention (rejection of environmental stimuli and focusing on memory/planning processes). This study investigated brain direct current (DC) potential shifts—which are discussed to represent different states of cortical activation—of tasks that require intake and rejection of environmental information under noise. It was hypothesized that without background noise rejection tasks would show more positive DC potential changes compared to intake tasks and that under noise both kinds of tasks would show positive DC shifts as an expression of cortical inhibition caused by noise. DC potential shifts during intake and rejection tasks were analyzed at 16 standard locations in 45 persons during irrelevant speech or white noise vs. control condition. Without noise, rejection tasks were associated with more positive DC potential changes compared to intake tasks. During background noise, however, this difference disappeared and both kinds of tasks led to positive DC shifts. Results suggest—besides some limitations—that noise modulates selective attention mechanisms by switching to an environmental information processing and noise rejection mode, which could represent a suggested “attention shift”. Implications for fMRI studies as well as for public health in learning and performance environments including susceptible persons are discussed. PMID:25264675

  13. Fault diagnosis of motor drives using stator current signal analysis based on dynamic time warping

    NASA Astrophysics Data System (ADS)

    Zhen, D.; Wang, T.; Gu, F.; Ball, A. D.

    2013-01-01

    Electrical motor stator current signals have been widely used to monitor the condition of induction machines and their downstream mechanical equipment. The key technique used for current signal analysis is based on Fourier transform (FT) to extract weak fault sideband components from signals predominated with supply frequency component and its higher order harmonics. However, the FT based method has limitations such as spectral leakage and aliasing, leading to significant errors in estimating the sideband components. Therefore, this paper presents the use of dynamic time warping (DTW) to process the motor current signals for detecting and quantifying common faults in a downstream two-stage reciprocating compressor. DTW is a time domain based method and its algorithm is simple and easy to be embedded into real-time devices. In this study DTW is used to suppress the supply frequency component and highlight the sideband components based on the introduction of a reference signal which has the same frequency component as that of the supply power. Moreover, a sliding window is designed to process the raw signal using DTW frame by frame for effective calculation. Based on the proposed method, the stator current signals measured from the compressor induced with different common faults and under different loads are analysed for fault diagnosis. Results show that DTW based on residual signal analysis through the introduction of a reference signal allows the supply components to be suppressed well so that the fault related sideband components are highlighted for obtaining accurate fault detection and diagnosis results. In particular, the root mean square (RMS) values of the residual signal can indicate the differences between the healthy case and different faults under varying discharge pressures. It provides an effective and easy approach to the analysis of motor current signals for better fault diagnosis of the downstream mechanical equipment of motor drives in the time

  14. Wavelet transform-based fault diagnosis and line selection method of small current grounding system

    NASA Astrophysics Data System (ADS)

    Yang, Ni; Zhang, Shuqing; Zhang, Liguo; Zhang, Kexin; Sun, Lingyun

    2008-12-01

    Small current grounding system is the system that the neutral point doesn't ground or grounds across the arc suppressing coils, which has been applied commonly in distribution system of many countries. As the grounding fault occurs, current is the one caused by capacity of circuit to ground only and it is rather small. The status of fault is complexity, e.g., the electromagnet interferes together with the amplified impact of zero-order loops to high-order singularity waves and various temporary variables. All these result in the lower ratio of the fault element signal to noise caused by zero-order current. In this paper, the position of signal singularity and the magnitude of the singularity degree are analyzed based on the variable focus character of wavelet, and the time fault occurs is then determined. The series db wavelet with close sustain is adopted, and the line selection is according to the zero-order voltage of the generatrix and the current of various outlet line. It is proved by the experiment that the fault circuit diagnosis method based on wavelet analysis to the character of temporary status of single-phase grounding fault plays an important role to a finer line selection.

  15. Phase-compensation-based dynamic time warping for fault diagnosis using the motor current signal

    NASA Astrophysics Data System (ADS)

    Zhen, D.; Zhao, H. L.; Gu, F.; Ball, A. D.

    2012-05-01

    Dynamic time warping (DTW) is a time-domain-based method and widely used in various similar recognition and data mining applications. This paper presents a phase-compensation-based DTW to process the motor current signals for detecting and quantifying various faults in a two-stage reciprocating compressor under different operating conditions. DTW is an effective method to align two signals for dissimilarity analysis. However, it has drawbacks such as singularities and high computational demands that limit its application in processing motor current signals for obtaining modulation characteristics accurately in diagnosing compressor faults. Therefore, a phase compensation approach is developed to reduce the singularity effect and a sliding window is designed to improve computing efficiency. Based on the proposed method, the motor current signals measured from the compressor induced with different common faults are analysed for fault diagnosis. Results show that residual signal analysis using the phase-compensation-based DTW allows the fault-related sideband features to be resolved more accurately for obtaining reliable fault detection and diagnosis. It provides an effective and easy approach to the analysis of motor current signals for better diagnosis in the time domain in comparison with conventional Fourier-transform-based methods.

  16. A current-mode DC—DC buck converter with adaptive zero compensation

    NASA Astrophysics Data System (ADS)

    Ling, Yang; Guoding, Dai; Chongwei, Xu; Yuezhi, Liu

    2013-08-01

    To achieve fast transient response for a DC—DC buck converter, an adaptive zero compensation circuit is presented. The compensation resistance is dynamically adjusted according to the different output load conditions, and achieves an adequate system phase margin under the different conditions. An improved capacitor multiplier circuit is adopted to realize the minimized compensation capacitance size. In addition, analysis of the small-signal model shows the correctness of the mechanism of the proposed adaptive zero compensation technique. A current-mode DC—DC buck converter with the proposed structure has been implemented in a 0.35 μm CMOS process, and the die size is only 800 × 1040 μm2. The experimental results show that the transient undershoot/overshoot voltage and the recovery times do not exceed 40 mV and 30 μs for a load current variation from 100 mA to 1 A.

  17. Switch contact device for interrupting high current, high voltage, AC and DC circuits

    DOEpatents

    Via, Lester C.; Witherspoon, F. Douglas; Ryan, John M.

    2005-01-04

    A high voltage switch contact structure capable of interrupting high voltage, high current AC and DC circuits. The contact structure confines the arc created when contacts open to the thin area between two insulating surfaces in intimate contact. This forces the arc into the shape of a thin sheet which loses heat energy far more rapidly than an arc column having a circular cross-section. These high heat losses require a dramatic increase in the voltage required to maintain the arc, thus extinguishing it when the required voltage exceeds the available voltage. The arc extinguishing process with this invention is not dependent on the occurrence of a current zero crossing and, consequently, is capable of rapidly interrupting both AC and DC circuits. The contact structure achieves its high performance without the use of sulfur hexafluoride.

  18. SIM regional comparison of ac-dc current transfer difference SIM.EM-K12

    NASA Astrophysics Data System (ADS)

    Di Lillo, Lucas

    2015-01-01

    The ac-dc current transfer difference identified as SIM.EM.K-12 began in July 2010 and was completed in September 2012. Six NMIs in the SIM region and one NMI in the AFRIMET region took part: NRC (Canada), NIST (United States of America), CENAM (Mexico), INTI (Argentina), UTE (Uruguay), INMETRO (Brazil) and NIS (Egypt). The comparisons were proposed to assess the measurement capabilities in ac-dc current transfer difference of the participants NMIs. The ac-dc current transfer differences of the travelling standard had been measured at 10 mA and 5 A at 10 Hz, 55 Hz, 1 kHz, 10 kHz, 20 kHz, 50 kHz and 100 kHz. The test points were selected to link the results with the equivalent CCEM Key Comparisons (CCEM-K12), through three NMIs participating in both SIM and CCEM key comparisons (INTI, NRC and NIST). The report shows the degree of equivalence in the SIM region and also the degree of equivalence with the corresponding CCEM reference value. The results of all participants support the values and uncertainties of the applicable CMC entries for ac-dc current transfer difference in the Key Comparison Database held at the BIPM. Main text. To reach the main text of this paper, click on Final Report. Note that this text is that which appears in Appendix B of the BIPM key comparison database kcdb.bipm.org/. The final report has been peer-reviewed and approved for publication by the CCEM, according to the provisions of the CIPM Mutual Recognition Arrangement (CIPM MRA).

  19. A hybrid superconducting fault current limiter for enhancing transient stability in Korean power systems

    NASA Astrophysics Data System (ADS)

    Seo, Sangsoo; Kim, Seog-Joo; Moon, Young-Hwan; Lee, Byongjun

    2013-11-01

    Additional power generation sites have been limited in Korea, despite the fact load demands are gradually increasing. In order to meet these increasing demands, Korea’s power system company has begun constructing new generators at existing sites. Thus, multi-unit plants can create problems in terms of transient stability when a large disturbance occurs. This paper proposes a hybrid superconducting fault current limiter (SFCL) application to enhance the transient stability of multi-unit power plants. SFCLs reduce fault currents, and limitation currents decrease the imbalance of the mechanical and electrical torque of the generators, resulting in an improvement in transient stability.

  20. Prony`s method: An efficient tool for the analysis of earth fault currents in Petersen-coil-protected networks

    SciTech Connect

    Chaari, O.; Bastard, P.; Meunier, M.

    1995-07-01

    Prony`s method is a technique for estimating the modal components present in a signal. Every modal component is defined by four parameters: frequency, magnitude, phase, and damping. This method is used to analyze earth fault currents in Petersen-coil-protected 20 kV networks. The variations of Prony`s parameters in terms of some of the power system characteristics (distance between the busbar and the fault, fault resistance and capacitive current of the whole network) are presented. It is shown that some of the Prony`s parameters relating to the fault current transient may be useful to determine what kind of fault occurred, and where it did.

  1. Current-voltage characteristics of dc corona discharges in air between coaxial cylinders

    NASA Astrophysics Data System (ADS)

    Zheng, Yuesheng; Zhang, Bo; He, Jinliang

    2015-02-01

    This paper presents the experimental measurement and numerical analysis of the current-voltage characteristics of dc corona discharges in air between coaxial cylinders. The current-voltage characteristics for both positive and negative corona discharges were measured within a specially designed corona cage. Then the measured results were fitted by different empirical formulae and analyzed by the fluid model. The current-voltage characteristics between coaxial cylinders can be expressed as I = C(U - U0)m, where m is within the range 1.5-2.0, which is similar to the point-plane electrode system. The ionization region has no significant effect on the current-voltage characteristic under a low corona current, while it will affect the distribution for the negative corona under a high corona current. The surface onset fields and ion mobilities were emphatically discussed.

  2. Current-voltage characteristics of dc corona discharges in air between coaxial cylinders

    SciTech Connect

    Zheng, Yuesheng; Zhang, Bo He, Jinliang

    2015-02-15

    This paper presents the experimental measurement and numerical analysis of the current-voltage characteristics of dc corona discharges in air between coaxial cylinders. The current-voltage characteristics for both positive and negative corona discharges were measured within a specially designed corona cage. Then the measured results were fitted by different empirical formulae and analyzed by the fluid model. The current-voltage characteristics between coaxial cylinders can be expressed as I = C(U − U{sub 0}){sup m}, where m is within the range 1.5–2.0, which is similar to the point-plane electrode system. The ionization region has no significant effect on the current-voltage characteristic under a low corona current, while it will affect the distribution for the negative corona under a high corona current. The surface onset fields and ion mobilities were emphatically discussed.

  3. Electric currents along earthquake faults and the magnetization of pseudotachylite veins

    NASA Astrophysics Data System (ADS)

    Freund, Friedemann; Salgueiro da Silva, Manuel A.; Lau, Bobby W. S.; Takeuchi, Akihiro; Jones, Hollis H.

    2007-02-01

    Pseudotachylites occur in the form of thin glassy veins quenched from frictional melts along the fault planes of major earthquakes. They contain finely grained magnetite and often exhibit a high natural remanent magnetization (NRM). High NRM values imply strong local electric currents. These currents must persist for some time, while the pseudotachylite veins cool through the Curie temperature of magnetite around 580 °C. There is no generally accepted theory explaining how such powerful, persistent currents may be generated along the fault plane. Data presented here suggest the activation of electronic charge carriers, which are present in igneous rocks in a dormant, inactive form. These charge carriers can be "awakened" by the application of stress. They are electrons and defect electrons, also known as positive holes or p-holes for short. While p-holes are capable of spreading out of the stressed rock volume into adjacent p-type conductive unstressed rocks, electrons require a connection to the hot, n-type conductive lower crust. However, as long as the (downward) electron flow is not connected, the circuit is not closed. Hence, with the outflow of p-holes impeded, no current can be sustained. This situation is comparable to that of a charged battery where one pole remains unconnected. The friction melt that forms coseismically during rupture, provides a conductive path downward, which closes the circuit. This allows a current to flow along the fault plane. Extrapolating from laboratory data, every km 3 of stressed igneous rocks adjacent to the fault plane can deliver 10 3-10 5 A. Hence, the current along the fault plane will not be limited by the number of charge carriers but more likely by the (electronic) conductivity of the cooling pseudotachylite vein. The sheet current will produce a magnetic field, whose vectors will lie in the fault plane and perpendicular to the flow direction.

  4. A high average current DC GaAs photocathode gun for ERLs and FELs

    SciTech Connect

    C. Hernandez-Garcia; T. Siggins; S. Benson; D. Bullard; H. F. Dylla; K. Jordan; C. Murray; G. R. Neil; Michelle D. Shinn; R. Walker

    2005-05-01

    The Jefferson Lab (JLab) 10 kW IR Upgrade FEL DC GaAs photocathode gun is presently the highest average current electron source operational in the U.S., delivering a record 9.1 mA CW, 350 kV electron beam with 122 pC/bunch at 75 MHz rep rate. Pulsed operation has also been demonstrated with 8 mA per pulse (110 pC/bunch) in 16 ms-long pulses at 2 Hz rep rate. Routinely the gun delivers 5 mA CW and pulse current at 135 pC/bunch for FEL operations. The Upgrade DC photocathode gun is a direct evolution of the DC photocathode gun used in the previous JLab 1 kW IR Demo FEL. Improvements in the vacuum conditions, incorporation of two UHV motion mechanisms (a retractable cathode and a photocathode shield door) and a new way to add cesium to the GaAs photocathode surface have extended its lifetime to over 450 Coulombs delivered between re-cesiations (quantum efficiency replenishment). With each photocathode activation quantum efficiencies above 6% are routinely achieved. The photocathode activation and performance will be described in detail.

  5. A Simplified Sensorless Vector Control Based on Average DC Bus Current for Fan Motor

    NASA Astrophysics Data System (ADS)

    Sumita, Satoshi; Tobari, Kazuaki; Aoyagi, Shigehisa; Maeda, Daisuke

    This paper describes a simplified sensorless vector control based on the average DC bus current for PMSM. This method can be used to design a drive control system at a relatively low cost because the microcontroller does not require a precise timer and the calculation load is slight. In the proposed method, one of the two possible current estimation processes is chosen according to the operation mode. First, the controller estimates d-axis current and identifies the back-EMF parameter in the synchronous operation mode at low speeds. The error in the back-EMF identification affects the efficiency of the proposed system, so it needs to be zero. Second, the controller estimates q-axis current in vector control mode. The identified parameter and q-axis current define voltage reference to realize high efficiency drive. The obtained experimental results confirm the effectiveness of the proposed method.

  6. Current Sensor Fault Diagnosis Based on a Sliding Mode Observer for PMSM Driven Systems

    PubMed Central

    Huang, Gang; Luo, Yi-Ping; Zhang, Chang-Fan; Huang, Yi-Shan; Zhao, Kai-Hui

    2015-01-01

    This paper proposes a current sensor fault detection method based on a sliding mode observer for the torque closed-loop control system of interior permanent magnet synchronous motors. First, a sliding mode observer based on the extended flux linkage is built to simplify the motor model, which effectively eliminates the phenomenon of salient poles and the dependence on the direct axis inductance parameter, and can also be used for real-time calculation of feedback torque. Then a sliding mode current observer is constructed in αβ coordinates to generate the fault residuals of the phase current sensors. The method can accurately identify abrupt gain faults and slow-variation offset faults in real time in faulty sensors, and the generated residuals of the designed fault detection system are not affected by the unknown input, the structure of the observer, and the theoretical derivation and the stability proof process are concise and simple. The RT-LAB real-time simulation is used to build a simulation model of the hardware in the loop. The simulation and experimental results demonstrate the feasibility and effectiveness of the proposed method. PMID:25970258

  7. Current Sensor Fault Diagnosis Based on a Sliding Mode Observer for PMSM Driven Systems.

    PubMed

    Huang, Gang; Luo, Yi-Ping; Zhang, Chang-Fan; Huang, Yi-Shan; Zhao, Kai-Hui

    2015-01-01

    This paper proposes a current sensor fault detection method based on a sliding mode observer for the torque closed-loop control system of interior permanent magnet synchronous motors. First, a sliding mode observer based on the extended flux linkage is built to simplify the motor model, which effectively eliminates the phenomenon of salient poles and the dependence on the direct axis inductance parameter, and can also be used for real-time calculation of feedback torque. Then a sliding mode current observer is constructed in αβ coordinates to generate the fault residuals of the phase current sensors. The method can accurately identify abrupt gain faults and slow-variation offset faults in real time in faulty sensors, and the generated residuals of the designed fault detection system are not affected by the unknown input, the structure of the observer, and the theoretical derivation and the stability proof process are concise and simple. The RT-LAB real-time simulation is used to build a simulation model of the hardware in the loop. The simulation and experimental results demonstrate the feasibility and effectiveness of the proposed method. PMID:25970258

  8. Spin Hall voltages from a.c. and d.c. spin currents

    PubMed Central

    Wei, Dahai; Obstbaum, Martin; Ribow, Mirko; Back, Christian H.; Woltersdorf, Georg

    2014-01-01

    In spin electronics, the spin degree of freedom is used to transmit and store information. To this end the ability to create pure spin currents—that is, without net charge transfer—is essential. When the magnetization vector in a ferromagnet–normal metal junction is excited, the spin pumping effect leads to the injection of pure spin currents into the normal metal. The polarization of this spin current is time-dependent and contains a very small d.c. component. Here we show that the large a.c. component of the spin currents can be detected efficiently using the inverse spin Hall effect. The observed a.c.-inverse spin Hall voltages are one order of magnitude larger than the conventional d.c.-inverse spin Hall voltages measured on the same device. Our results demonstrate that ferromagnet–normal metal junctions are efficient sources of pure spin currents in the gigahertz frequency range. PMID:24780927

  9. Enhancement of Accuracy in the Estimated Power-Angle Curve Considering Current Immediately after Fault Clearance

    NASA Astrophysics Data System (ADS)

    Iimura, Hayato; Sato, Masahiro

    A fault that occurs near a power station may cause a loss of synchronism of generators in the power station against the remaining generators and result in a widespread blackout. When swing of generators in the power station with respect to the remaining generators is similar to that of a generator in one machine and an infinite bus system, a power-angle curve (P-δ curve) is often used for studying the stability of the system and deciding the number of generators to be shed for stabilization. In operation, power system stabilizers predict loss of synchronism, determine the number of generators to be shed, and then shed them in a very short time period. Such stabilizers use data measured during a period of about 200 ms after fault occurence. The voltage and current measured on the bus and line connected to a power station are used to compute the P-δ curve. When a line is removed to clear a fault, the current in the damper circuit of a generator decays significantly in a very short period. This causes significant changes in the line current. However, when the P-δ curve is estimated using these data, and is applied to a stability study, the number of generators to be shed sometimes exceeds the optimum number. This is caused by the practice of measuring the current immediately after a fault is cleaed. Therefore, the authors propose a current detection method in which the portion of current that decays immediately after a fault is cleared. Such current has three distinct terms. Two are exponential functions in which one has extremely short time constant, while the other has a longer time constant. By using these estimated functions, the fast decaying component is removed from the measured current, which can then be used to estimate the P-δ curve more precisely. The method was verified via simulations using an infinite bus system model and the EAST10 model of IEEJ.

  10. ­­Are current models for normal fault array evolution applicable to natural rifts?

    NASA Astrophysics Data System (ADS)

    Bell, R. E.; Jackson, C. A. L.

    2015-12-01

    Conceptual models predicting the geometry and evolution of normal fault arrays are vital to assess rift physiography, syn-rift sediment dispersal and seismic hazard. Observations from data-rich rifts and numerical and physical models underpin widely used fault array models predicting: i) during rift initiation, arrays are defined by multiple, small, isolated faults; ii) as rifting progresses, strain localises onto fewer larger structures; and iii) with continued strain, faulting migrates toward the rift axis, resulting in rift narrowing. Some rifts display these characteristics whereas others do not. Here we present several case studies documenting fault migration patterns that do not fit this ideal. In this presentation we will begin by reviewing existing fault array models before presenting a series of case studies (including from the northern North Sea and the Gulf of Corinth), which document fault migration patterns that are not predicted by current fault evolution models. We show that strain migration onto a few, large faults is common in many rifts but that, rather than localising onto these structures until the cessation of rifting, strain may 'sweep' across the basin. Furthermore, crustal weaknesses developed in early tectonic events can cause faults during subsequent phases of extension to grow relatively quickly and accommodate the majority if not all of the rift-related strain; in these cases, strain migration does not and need not occur. Finally, in salt-influenced rifts, strain localisation may not occur at all; rather, strain may become progressively more diffuse due to tilting of the basement and intrastratal salt décollements, thus leading to superimposition of thin-skinned, gravity-driven and thick-skinned, plate-driven, basement-involved extension. We call for the community to unite to develop the next-generation of normal fault array models that include complexities such as the thermal and rheological properties of the lithosphere, specific

  11. A Method to Simultaneously Detect the Current Sensor Fault and Estimate the State of Energy for Batteries in Electric Vehicles.

    PubMed

    Xu, Jun; Wang, Jing; Li, Shiying; Cao, Binggang

    2016-01-01

    Recently, State of energy (SOE) has become one of the most fundamental parameters for battery management systems in electric vehicles. However, current information is critical in SOE estimation and current sensor is usually utilized to obtain the latest current information. However, if the current sensor fails, the SOE estimation may be confronted with large error. Therefore, this paper attempts to make the following contributions: Current sensor fault detection and SOE estimation method is realized simultaneously. Through using the proportional integral observer (PIO) based method, the current sensor fault could be accurately estimated. By taking advantage of the accurate estimated current sensor fault, the influence caused by the current sensor fault can be eliminated and compensated. As a result, the results of the SOE estimation will be influenced little by the fault. In addition, the simulation and experimental workbench is established to verify the proposed method. The results indicate that the current sensor fault can be estimated accurately. Simultaneously, the SOE can also be estimated accurately and the estimation error is influenced little by the fault. The maximum SOE estimation error is less than 2%, even though the large current error caused by the current sensor fault still exists. PMID:27548183

  12. Electrical Motor Current Signal Analysis using a Dynamic Time Warping Method for Fault Diagnosis

    NASA Astrophysics Data System (ADS)

    Zhen, D.; Alibarbar, A.; Zhou, X.; Gu, F.; Ball, A. D.

    2011-07-01

    This paper presents the analysis of phase current signals to identify and quantify common faults from an electrical motor based on dynamic time warping (DTW) algorithm. In condition monitoring, measurements are often taken when the motor undertakes varying loads and speeds. The signals acquired in these conditions show similar profiles but have phase shifts, which do not line up in the time-axis for adequate comparison to discriminate the small changes in machine health conditions. In this study, DTW algorithms are exploited to align the signals to an ideal current signal constructed based on average operating conditions. In this way, comparisons between the signals can be made directly in the time domain to obtain residual signals. These residual signals are then based on to extract features for detecting and diagnosing the faults of the motor and components operating under different loads and speeds. This study provides a novel approach to the analysis of electrical current signal for diagnosis of motor faults. Experimental data sets of electrical motor current signals have been studied using DTW algorithms. Results show that DTW based residual signals highlights more the modulations due to the compressor process. And hence can obtain better fault detection and diagnosis results.

  13. A superconducting fault current limiter integrated in the cold heat exchanger of a thermoacoustic refrigerator

    NASA Astrophysics Data System (ADS)

    Osorio, M. R.; Bétrancourt, A.; François, M. X.; Veira, J. A.; Vidal, F.

    2008-09-01

    In this work we probe a compact superconducting fault current limiter (SFCL) integrated in the cold heat exchanger of a thermoacoustic refrigerator. A design for an SFCL device with a power of about 2.2 kW is presented and described in detail. A thermoacoustic refrigerator is also proposed which, under fault conditions, must be able to remove around 50 W at 80 K. A simulation routine is run to test the performance of the SFCL, based on YBCO films, in terms of both the limiting capacity and the energy to be dissipated and removed inside the heat exchanger.

  14. Current limiting behavior in three-phase transformer-type SFCLs using an iron core according to variety of fault

    NASA Astrophysics Data System (ADS)

    Cho, Yong-Sun; Jung, Byung-Ik; Ha, Kyoung-Hun; Choi, Soo-Geun; Park, Hyoung-Min; Choi, Hyo-Sang

    To apply the superconducting fault current limiter (SFCL) to the power system, the reliability of the fault-current-limiting operation must be ensured in diverse fault conditions. The SFCL must also be linked to the operation of the high-speed recloser in the power system. In this study, a three-phase transformer-type SFCL, which has a neutral line to improve the simultaneous quench characteristics of superconducting elements, was manufactured to analyze the fault-current-limiting characteristic according to the single, double, and triple line-to-ground faults. The transformer-type SFCL, wherein three-phase windings are connected to one iron core, reduced the burden on the superconducting element as the superconducting element on the sound phase was also quenched in the case of the single line-to-ground fault. In the case of double or triple line-to-ground faults, the flux from the faulted phase winding was interlinked with other faulted or sound phase windings, and the fault-current-limiting rate decreased because the windings of three phases were inductively connected by one iron core.

  15. Research on fast fault identification method of 10.5 kV/1.5 kA superconducting fault current limiter

    NASA Astrophysics Data System (ADS)

    Zhang, Zhifeng; Sun, Qiang; Xiao, Liye; Liu, Daqian; Qiu, Ming; Qiu, Qinquan; Zhang, Guomin; Dai, Shaotao; Lin, Liangzhen

    2014-09-01

    Superconducting fault current limiter (SFCL) is a prospective electric devices connected in series in power grid to limit short-circuit current. A 10.5 kV/1.5 kA 3-phase SFCL with HTS coil of 6.24 mH was developed at IEECAS in China in 2005, which was operated in a local power grid in Hunan province for more than 11,000 h, and integrated lately in a superconducting power substation in Baiyin city in 2011 and is still running safely and reliably. In order to reduce the fault response time and enhance the performance of the SFCL, we analyzed the structure characteristics of the SFCL and discussed the variation of currents and voltages of the HTS coil and the bridge during the fault time. The simulation and tests results of power system validate the feasibility of the fast fault identification method.

  16. Analysis and comparison for rotor eddy current losses of permanent magnet synchronous generator according to dc and ac load conditions

    NASA Astrophysics Data System (ADS)

    Jang, Seok-Myeong; Kim, Hyun-Kyu; Choi, Jang-Young; Ko, Kyoung-Jin

    2009-04-01

    This paper presents an analytical procedure for the calculation of the eddy current losses of permanent magnet synchronous generator (PMSG). The dc and ac loading effects on the eddy current is examined through the suggested analytical procedure that considers the radial and tangential flux density waveform through a phase current harmonic analysis. The corresponding test results are also presented to quantify and compare those loading effects on the eddy current. The results verified the suggested analytical procedures and show that the rotor eddy current losses for PMSG with the dc loads turned out to be more significant than those with the ac loads.

  17. Symmetrical and Unsymmetrical Fault Currents of a Wind Power Plant: Preprint

    SciTech Connect

    Gevorgian, V.; Singh, M.; Muljadi, E.

    2011-12-01

    This paper investigates the short-circuit behavior of a wind power plant for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. The size of wind power plants (WPPs) keeps getting bigger and bigger. The number of wind plants in the U.S. has increased very rapidly in the past 10 years. It is projected that in the U.S., the total wind power generation will reach 330 GW by 2030. As the importance of WPPs increases, planning engi-neers must perform impact studies used to evaluate short-circuit current (SCC) contribution of the plant into the transmission network under different fault conditions. This information is needed to size the circuit breakers, to establish the proper sys-tem protection, and to choose the transient suppressor in the circuits within the WPP. This task can be challenging to protec-tion engineers due to the topology differences between different types of wind turbine generators (WTGs) and the conventional generating units. This paper investigates the short-circuit behavior of a WPP for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. Three different soft-ware packages are utilized to develop this paper. Time domain simulations and steady-state calculations are used to perform the analysis.

  18. Comparative study of superconducting fault current limiter both for LCC-HVDC and VSC-HVDC systems

    NASA Astrophysics Data System (ADS)

    Lee, Jong-Geon; Khan, Umer Amir; Lim, Sung-Woo; Shin, Woo-ju; Seo, In-Jin; Lee, Bang-Wook

    2015-11-01

    High Voltage Direct Current (HVDC) system has been evaluated as the optimum solution for the renewable energy transmission and long-distance power grid connections. In spite of the various advantages of HVDC system, it still has been regarded as an unreliable system compared to AC system due to its vulnerable characteristics on the power system fault. Furthermore, unlike AC system, optimum protection and switching device has not been fully developed yet. Therefore, in order to enhance the reliability of the HVDC systems mitigation of power system fault and reliable fault current limiting and switching devices should be developed. In this paper, in order to mitigate HVDC fault, both for Line Commutated Converter HVDC (LCC-HVDC) and Voltage Source Converter HVDC (VSC-HVDC) system, an application of resistive superconducting fault current limiter which has been known as optimum solution to cope with the power system fault was considered. Firstly, simulation models for two types of LCC-HVDC and VSC-HVDC system which has point to point connection model were developed. From the designed model, fault current characteristics of faulty condition were analyzed. Second, application of SFCL on each types of HVDC system and comparative study of modified fault current characteristics were analyzed. Consequently, it was deduced that an application of AC-SFCL on LCC-HVDC system with point to point connection was desirable solution to mitigate the fault current stresses and to prevent commutation failure in HVDC electric power system interconnected with AC grid.

  19. A Novel Wide-Area Backup Protection Based on Fault Component Current Distribution and Improved Evidence Theory

    PubMed Central

    Zhang, Zhe; Kong, Xiangping; Yin, Xianggen; Yang, Zengli; Wang, Lijun

    2014-01-01

    In order to solve the problems of the existing wide-area backup protection (WABP) algorithms, the paper proposes a novel WABP algorithm based on the distribution characteristics of fault component current and improved Dempster/Shafer (D-S) evidence theory. When a fault occurs, slave substations transmit to master station the amplitudes of fault component currents of transmission lines which are the closest to fault element. Then master substation identifies suspicious faulty lines according to the distribution characteristics of fault component current. After that, the master substation will identify the actual faulty line with improved D-S evidence theory based on the action states of traditional protections and direction components of these suspicious faulty lines. The simulation examples based on IEEE 10-generator-39-bus system show that the proposed WABP algorithm has an excellent performance. The algorithm has low requirement of sampling synchronization, small wide-area communication flow, and high fault tolerance. PMID:25050399

  20. An Analysis of Superconducting Fault Current Limiter for Stabilization of Synchronous Generators in Multi-Machine System

    NASA Astrophysics Data System (ADS)

    Yagami, Masaki; Shibata, Shinsuke; Murata, Toshiaki; Tamura, Junji

    This paper presents the results of analyses of the effectiveness of a superconducting fault current limiter (SFCL) to stabilize the synchronous generators, suppress turbine shaft torque oscillations, and limit the fault current in a two-machine-infinite bus system. In this study, the system model with two SFCLs having shunt resistance installed at each generator terminal was used taking 3LG (three lines to ground) fault at 12 fault points into account. These analyses were performed using EMTP/ATP. It is concluded that the use of SFCL with shunt resistance value of 1.1 pu is most effective for all fault points for the stabilization of synchronous generators, the suppression of turbine shaft torque oscillations, and the limitation of fault current.

  1. Impact of quasi-dc currents on three-phase distribution transformer installations. Power Systems Technology Program

    SciTech Connect

    McConnell, B.W.; Barnes, P.R.; Tesche, F.M.; Schafer, D.A.

    1992-06-01

    This report summarizes a series of tests designed to determine the response of quasi-dc currents on three-phase power distribution transformers for electric power systems. In general, if the dc injection is limited to the primary side of a step-down transformer, significant harmonic distortion is noted and an increase in the reactive power demand results. For dc injection on the secondary (load) side of the step-down transformer the harmonic content at the secondary side is quite high and saturation occurs with a relatively low level of dc injection; however, the reactive power demand is significantly lower. These tests produced no apparent damage to the transformers. Transformer damage is dependent on the duration of the dc excitation, the level of the excitation, and on thermal characteristics of the transfer. The transformer response time is found to be much shorter than seen in power transformer tests at lower dc injection levels. This shorter response time suggests that the response time is strongly dependent on the injected current levels, and that higher levels of dc injection for shorter durations could produce very high reactive power demands and harmonic distortion within a few tenths of a second. The added reactive power load could result in the blowing of fuses on the primary side of the transformer for even moderate dc injection levels, and neutral currents are quite large under even low-level dc injection. This ``smoking neutral`` results in high-level harmonic injection into equipment via the neutral and in possible equipment failure.

  2. Measurement of ion current density at ground level in the vicinity of high voltage DC transmission lines

    NASA Astrophysics Data System (ADS)

    McKnight, R. H.; Kotter, F. R.; Misakian, M.

    1981-12-01

    Sensors for measuring vertical current density at ground level near high voltage dc (HVDC) transmission lines are subject to error when the sensor is not in the ground plane. The magnitude of this error, for guarded and unguarded sensors, was investigated using both dc electric fields with space charge and ac electric fields in a parallel plate facility. For conditions like those expected under HVDC transmission lines, the results obtained using ac and dc methods agreed to within experimental uncertainty. The measured errors are as large as 25 percent for guarded sensors and significantly larger for unguarded sensors. Graphs of data for various sensor elevations and guarding are presented.

  3. Non-invasive long-term recordings of cortical 'direct current' (DC-) activity in humans using magnetoencephalography.

    PubMed

    Mackert, B M; Wübbeler, G; Burghoff, M; Marx, P; Trahms, L; Curio, G

    1999-10-01

    Recently, biomagnetic fields below 0.1 Hz arising from nerve or muscle injury currents have been measured non-invasively using superconducting quantum interference devices (SQUIDs). Here we report first long-term recordings of cortical direct current (DC) fields in humans based on a horizontal modulation (0.4 Hz) of the body and, respectively, head position beneath the sensor array: near-DC fields with amplitudes between 90 and 540 fT were detected in 5/5 subjects over the auditory cortex throughout prolonged stimulation periods (here: 30 s) during which subjects were listening to concert music. These results prove the feasibility to record non-invasively low amplitude near-DC magnetic fields of the human brain and open the perspective for studies on DC-phenomena in stroke, such as anoxic depolarization or periinfarct depolarization, and in migraine patients. PMID:10515183

  4. The bridge-type fault current controller--a new facts controller

    SciTech Connect

    Boenig, Heinrich J.; Mielke, C. H.; Burley, B. L.; Chen, Hong; Waynert, J. A.; Willis, J. O.

    2002-01-01

    The operation of a novel current controller, which can also function as a fault current limiter and as a solid-state ac circuit breaker, is presented. The controller, which consists of a thyristor bridge, an inductor, and an optional bias power supply, is installed in series with the voltage source and the load, For load current values smaller than a preset value, the inductor of the current controller presents no impedance to the ac current flow. For values higher than the preset current value, the inductor is switched automatically into the ac circuit and limits the amount of current flow. Theoretical results in the form of circuit simulations and experimental results with a single-phase unit, operating on a 13.7 kV three-phase system with peak short-circuit currents of 3140 Arms, are presented.

  5. Modeling and Dynamic Analysis of Paralleled dc/dc Converters With Master-Slave Current Sharing Control

    NASA Technical Reports Server (NTRS)

    Rajagopalan, J.; Xing, K.; Guo, Y.; Lee, F. C.; Manners, Bruce

    1996-01-01

    A simple, application-oriented, transfer function model of paralleled converters employing Master-Slave Current-sharing (MSC) control is developed. Dynamically, the Master converter retains its original design characteristics; all the Slave converters are forced to depart significantly from their original design characteristics into current-controlled current sources. Five distinct loop gains to assess system stability and performance are identified and their physical significance is described. A design methodology for the current share compensator is presented. The effect of this current sharing scheme on 'system output impedance' is analyzed.

  6. Modeling and Dynamic Analysis of Paralleled of dc/dc Converters with Master-Slave Current Sharing Control

    NASA Technical Reports Server (NTRS)

    Rajagopalan, J.; Xing, K.; Guo, Y.; Lee, F. C.; Manners, Bruce

    1996-01-01

    A simple, application-oriented, transfer function model of paralleled converters employing Master-Slave Current-sharing (MSC) control is developed. Dynamically, the Master converter retains its original design characteristics; all the Slave converters are forced to depart significantly from their original design characteristics into current-controlled current sources. Five distinct loop gains to assess system stability and performance are identified and their physical significance is described. A design methodology for the current share compensator is presented. The effect of this current sharing scheme on 'system output impedance' is analyzed.

  7. Design and control of the phase current of a brushless dc motor to eliminate cogging torque

    NASA Astrophysics Data System (ADS)

    Jang, G. H.; Lee, C. J.

    2006-04-01

    This paper presents a design and control method of the phase current to reduce the torque ripple of a brushless dc (BLDC) motor by eliminating cogging torque. The cogging torque is the main source of torque ripple and consequently of speed error, and it is also the excitation source to generate the vibration and noise of a motor. This research proposes a modified current wave form, which is composed of main and auxiliary currents. The former is the conventional current to generate the commutating torque. The latter generates the torque with the same magnitude and opposite sign of the corresponding cogging torque at the given position in order to eliminate the cogging torque. Time-stepping finite element method simulation considering pulse-width-modulation switching method has been performed to verify the effectiveness of the proposed method, and it shows that this proposed method reduces torque ripple by 36%. A digital-signal-processor-based controller is also developed to implement the proposed method, and it shows that this proposed method reduces the speed ripple significantly.

  8. A Novel Transient Fault Current Sensor Based on the PCB Rogowski Coil for Overhead Transmission Lines.

    PubMed

    Liu, Yadong; Xie, Xiaolei; Hu, Yue; Qian, Yong; Sheng, Gehao; Jiang, Xiuchen

    2016-01-01

    The accurate detection of high-frequency transient fault currents in overhead transmission lines is the basis of malfunction detection and diagnosis. This paper proposes a novel differential winding printed circuit board (PCB) Rogowski coil for the detection of transient fault currents in overhead transmission lines. The interference mechanism of the sensor surrounding the overhead transmission line is analyzed and the guideline for the interference elimination is obtained, and then a differential winding printed circuit board (PCB) Rogowski coil is proposed, where the branch and return line of the PCB coil were designed to be strictly symmetrical by using a joining structure of two semi-rings and collinear twisted pair differential windings in each semi-ring. A serial test is conducted, including the frequency response, linearity, and anti-interference performance as well as a comparison with commercial sensors. Results show that a PCB Rogowski coil has good linearity and resistance to various external magnetic field interferences, thus enabling it to be widely applied in fault-current-collecting devices. PMID:27213402

  9. A Novel Transient Fault Current Sensor Based on the PCB Rogowski Coil for Overhead Transmission Lines

    PubMed Central

    Liu, Yadong; Xie, Xiaolei; Hu, Yue; Qian, Yong; Sheng, Gehao; Jiang, Xiuchen

    2016-01-01

    The accurate detection of high-frequency transient fault currents in overhead transmission lines is the basis of malfunction detection and diagnosis. This paper proposes a novel differential winding printed circuit board (PCB) Rogowski coil for the detection of transient fault currents in overhead transmission lines. The interference mechanism of the sensor surrounding the overhead transmission line is analyzed and the guideline for the interference elimination is obtained, and then a differential winding printed circuit board (PCB) Rogowski coil is proposed, where the branch and return line of the PCB coil were designed to be strictly symmetrical by using a joining structure of two semi-rings and collinear twisted pair differential windings in each semi-ring. A serial test is conducted, including the frequency response, linearity, and anti-interference performance as well as a comparison with commercial sensors. Results show that a PCB Rogowski coil has good linearity and resistance to various external magnetic field interferences, thus enabling it to be widely applied in fault-current-collecting devices. PMID:27213402

  10. A Study of University Students' Understanding of Simple Electric Circuits. Part 1: Current in d.c. Circuits.

    ERIC Educational Resources Information Center

    Picciarelli, V.; And Others

    1991-01-01

    The results of an investigation concerned with sequential reasoning in interpreting the current flow in d.c. electric circuits are presented. Analysis of the results of a questionnaire completed by 236 college sophomores shows the presence of a common misunderstanding based on a "local" interpretation of the current flow. A copy of the…

  11. Simultaneous DC measurements of ion current density and electron temperature using a tunnel probe

    NASA Astrophysics Data System (ADS)

    Gunn, J. P.; Dejarnac, R.; Stöckel, J.

    2016-03-01

    The tunnel probe is a concave Langmuir probe designed to operate in strongly magnetized plasma. Due to its shape, the tunnel probe is immune to sheath expansion effects and thus provides absolutely calibrated measurements of the parallel ion current density. A two-dimensional, self-consistent kinetic model is employed to model the flow of charges within the cavity of the tunnel probe. The calculation predicts that the distribution of the ion flux onto the inner conductors depends on the electric field inside the tunnel, which in turn depends on the electron temperature. Therefore, if the tunnel is divided into two negatively biased collectors, it is possible to use the simulation results to determine the electron temperature from the measured ion current ratio. This means that a DC-biased tunnel probe can be used to provide fast, simultaneous measurements of the parallel ion current density and the electron temperature without collecting a single electron. Measurements in the CASTOR and Tore Supra tokamaks agree well with the numerical simulations.

  12. Design and development of DC high current sensor using Hall-Effect method

    NASA Astrophysics Data System (ADS)

    Dewi, Sasti Dwi Tungga; Panatarani, C.; Joni, I. Made

    2016-02-01

    This paper report a newly developed high DC current sensor by using a Hall effect method and also the measurement system. The Hall effect sensor receive the magnetic field generated by a current carrying conductor wire. The SS49E (Honeywell) magnetoresistive sensor was employed to sense the magnetic field from the field concentrator. The voltage received from SS49E then converted into digital by using analog to digital converter (ADC-10 bit). The digital data then processed in the microcontroller to be displayed as the value of the electric current in the LCD display. In addition the measurement was interfaced into Personal Computer (PC) using the communication protocols of RS232 which was finally displayed in real-time graphical form on the PC display. The performance test on the range ± 40 Ampere showed that the maximum relative error is 5.26%. It is concluded that the sensors and the measurement system worked properly according to the design with acceptable accuracy.

  13. Simulation analysis of three-phase current type AC-to-DC converter with high power factor

    SciTech Connect

    Okui, Yoshiaki; Yamada, Hajime

    1997-03-01

    A new three-phase current type AC-to-DC converter has been developed by the authors. This paper describes the principle of the circuit operation and the circuit configuration of the AC-to-DC converter controlled by PWM. Simulation analysis of each waveform, such as AC and DC voltages and currents, are calculated by Euler`s method. The simulated values of the total power factor agreed with the measured values within the difference of 5.8% on the condition of full load, 10kW. When the AC side voltage is unbalanced, it is found by simulation that the total harmonic distortion controlled by both feedforward control and AC side current feedback control (proportion gain, k{sub 4} = 1) is restrained at only 38% compared with only feedforward control (k{sub 4} = 0).

  14. Sectionalizing interconnected transmission network to improve system performance and achieve fault current reduction

    SciTech Connect

    Ray, B.

    1998-12-31

    An analysis was recently undertaken at Northern States Power Company (NSP) in an attempt to identify the advantages and disadvantages of sectionalizing Twin Cities metropolitan area transmission system. Five specific sectionalization schemes were developed to evaluate the transmission system performance associated with each scenario. These schemes were judged against the following performance characteristics: fault current level, severity of voltage depression during faults, NSP system losses, system through flow and contingency operation. Study results indicated that by careful application of the splitting scheme, sectionalization can provide significant performance improvements and still have economic feasibility. A comparison between sectionalization costs (increased system losses) and its benefits (improved performance) would help determine to what degree sectionalization is economically feasible and make the final decision. Of the five schemes tested, the contour that appeared the best in terms of reliability, performance and economics was chosen for implementation in NSP system during 1997 summer.

  15. Quantitative Thermal Microscopy Measurement with Thermal Probe Driven by dc+ac Current

    NASA Astrophysics Data System (ADS)

    Bodzenta, Jerzy; Juszczyk, Justyna; Kaźmierczak-Bałata, Anna; Firek, Piotr; Fleming, Austin; Chirtoc, Mihai

    2016-07-01

    Quantitative thermal measurements with spatial resolution allowing the examination of objects of submicron dimensions are still a challenging task. The quantity of methods providing spatial resolution better than 100 nm is very limited. One of them is scanning thermal microscopy (SThM). This method is a variant of atomic force microscopy which uses a probe equipped with a temperature sensor near the apex. Depending on the sensor current, either the temperature or the thermal conductivity distribution at the sample surface can be measured. However, like all microscopy methods, the SThM gives only qualitative information. Quantitative measuring methods using SThM equipment are still under development. In this paper, a method based on simultaneous registration of the static and the dynamic electrical resistances of the probe driven by the sum of dc and ac currents, and examples of its applications are described. Special attention is paid to the investigation of thin films deposited on thick substrates. The influence of substrate thermal properties on the measured signal and its dependence on thin film thermal conductivity and film thickness are analyzed. It is shown that in the case where layer thicknesses are comparable or smaller than the probe-sample contact diameter, a correction procedure is required to obtain actual thermal conductivity of the layer. Experimental results obtained for thin SiO2 and BaTiO_{3 }layers with thicknesses in the range from 11 nm to 100 nm are correctly confirmed with this approach.

  16. 2D modeling of DC potential structures induced by RF sheaths with transverse currents in front of ICRF antenna

    SciTech Connect

    Faudot, E.; Heuraux, S.; Colas, L.

    2005-09-26

    Understanding DC potential generation in front of ICRF antennas is crucial for long pulse high RF power systems. DC potentials are produced by sheath rectification of these RF potentials. To reach this goal, near RF parallel electric fields have to be computed in 3D and integrated along open magnetic field lines to yield a 2D RF potential map in a transverse plane. DC potentials are produced by sheath rectification of these RF potentials. As RF potentials are spatially inhomogeneous, transverse polarization currents are created, modifying RF and DC maps. Such modifications are quantified on a 'test map' having initially a Gaussian shape and assuming that the map remains Gaussian near its summit,the time behavior of the peak can be estimated analytically in presence of polarization current as a function of its width r0 and amplitude {phi}0 (normalized to a characteristic length for transverse transport and to the local temperature). A 'peaking factor' is built from the DC peak potential normalized to {phi}0, and validated with a 2D fluid code and a 2D PIC code (XOOPIC). In an unexpected way transverse currents can increase this factor. Realistic situations of a Tore Supra antenna are also studied, with self-consistent near fields provided by ICANT code. Basic processes will be detailed and an evaluation of the 'peaking factor' for ITER will be presented for a given configuration.

  17. Improvement in operational characteristics of KEPCO’s line-commutation-type superconducting hybrid fault current limiter

    NASA Astrophysics Data System (ADS)

    Yim, S.-W.; Park, B.-C.; Jeong, Y.-T.; Kim, Y.-J.; Yang, S.-E.; Kim, W.-S.; Kim, H.-R.; Du, H.-I.

    2013-01-01

    A 22.9 kV class hybrid fault current limiter (FCL) developed by Korea Electric Power Corporation and LS Industrial Systems in 2006 operates using the line commutation mechanism and begins to limit the fault current after the first half-cycle. The first peak of the fault current is available for protective coordination in the power system. However, it also produces a large electromagnetic force and imposes a huge stress on power facilities such as the main transformer and gas-insulated switchgear. In this study, we improved the operational characteristics of the hybrid FCL in order to reduce the first peak of the fault current. While maintaining the structure of the hybrid FCL system, we developed a superconducting module that detects and limits the fault current during the first half-cycle. To maintain the protective coordination capacity, the hybrid FCL was designed to reduce the first peak value of the fault current by up to approximately 30%. The superconducting module was also designed to produce a minimum AC loss, generating a small, uniform magnetic field distribution during normal operation. Performance tests confirmed that when applied to the hybrid FCL, the superconducting module showed successful current limiting operation without any damage.

  18. The current tectonic motion of the Northern Andes along the Algeciras Fault System in SW Colombia

    NASA Astrophysics Data System (ADS)

    Velandia, Francisco; Acosta, Jorge; Terraza, Roberto; Villegas, Henry

    2005-04-01

    Riedel, synthetic and antithetic type faults, principal displacement zones (PDZ), pull-apart basins (such as lazy-S shaped releasing bend, extensive and rhomboidal shaped and releasing sidestep basins) and minor folds located oblique to the main trace of the Algeciras Fault System (AFS) are interpreted from Landsat TM 5 images and geological mapping. These tectonic features are affecting Quaternary deposits and are related to major historical earthquakes and recent registered seismic events, indicating neotectonic activity of the structure. The AFS is classified as a right lateral wrench complex structure, with an important vertical component in which sedimentary cover and basement rocks are involved. In addition, the system represents a simple shear caused by the oblique convergence between the Nazca Plate and the northern Andes. The transpressive boundary in SW Colombia was previously located along the Eastern Frontal Fault System. However, this paper shows that the AFS constitutes the actual boundary of the current transpressive regime along the Northern Andes, which begins at the Gulf of Guayaquil in Ecuador and continues into Colombia and Venezuela.

  19. Fault current limiter based on high temperature superconductors - different concepts, test results, simulations, applications

    NASA Astrophysics Data System (ADS)

    Paul, W.; Chen, M.; Lakner, M.; Rhyner, J.; Braun, D.; Lanz, W.

    2001-05-01

    All electric equipment in a power system has to be designed to withstand the mechanical and thermal stresses of potential short-circuit currents. Any reduction of these currents can lead to significant cost savings. Among all current limiting devices, superconducting fault current limiters (SCFCL) offer ideal performance: in normal operation the SCFCL is in its superconducting state and has negligible impedance, in the event of a fault, the transition into the normal conducting state passively limits the current. Different high temperature superconductors (HTS) materials, like YBCO films, Bi2223 wires or Bi2212 bulk are under development for the use in SCFCL. Due to the brittle nature of HTS and the hot-spot problem, most HTS components for current limitation are composites comprising the HTS, a mechanical substrate or support, and an electrical bypass. The performance of the composites largely depend on the parameters: critical current density, I- V characteristics, thermal conductivity, thermal mass, and electrical bypass. Mainly two different concepts of SCFCL, namely, the “resistive” and the “shielded core” concept have been pursued in the past. In 1996 the first ever SCFCL was installed in a hydro-power plant. The device had a rated power of 1.2 MVA, it was of the “shielded core” type and was based on tubes of Bi2212-bulk material. The feasibility of the technology has been demonstrated in a one-year-endurance test. Recently more compact “resistive” SCFCLs based on the same Bi2212-bulk material have been developed. Theoretical models for the SCFCL show good agreement with experimental data. They are used to study the influence of SCFCLs in power systems in order to evaluate technical and economical advantages.

  20. A Simulation Method of Voltages and Currents on a Gas Pipeline and its Fault Location

    NASA Astrophysics Data System (ADS)

    Ametani, Akihiro; Kanba, Junsuke; Hosokawa, Yuji

    The present paper develops a numerical simulation method of steady-state and transient voltages and currents on a gas pipeline by applying a generalized circuit analysis program EMTP which is realized as a worldwide standard software. A buried gas pipeline is represented as an underground cable consisting of a tubular core and its outer insulator. The series impedance and the shunt admittance are easily evaluated by the EMTP supporting routine Cable Parameters. The paper has carried out simulations of steady-state and transient voltages and currents along the buried gas pipeline by EMTP. Based on the simulation results, it has become clear that the distributions of the voltages and the currents along the pipeline differ notably in the front and in the rear of a fault position. Thus, a detecting method is developed by observing a difference of a voltage amplitude between sound and fault states. The proposed techniques are investigated on real gas pipelines based on EMTP simulations, and it has been confirmed that the technique can be used in practice.

  1. Status of high temperature superconductor cable and fault current limiter projects at American Superconductor

    NASA Astrophysics Data System (ADS)

    Maguire, J. F.; Yuan, J.

    2009-10-01

    This paper will describe the status of three key programs currently underway at American Superconductor Corp. The first program is the LIPA project which is a transmission voltage high temperature superconducting cable program, with funding support from the US Department of Energy. The 600 m cable, capable of carrying 574 MVA, was successfully installed and commissioned in LIPA grid on April 22, 2008. An overview of the project, system level design details and operational data will be provided. In addition, the status of the newly awarded LIPA II project will be described. The second program is Project Hydra, with funding support from the US Department of Homeland Security, to design, develop and demonstrate an HTS cable with fault current limiting functionality. The cable is 300 m long and is being designed to carry 96 MVA at a distribution level voltage of 13.8 kV. The cable will be permanently installed and energized in Manhattan, New York in 2010. The initial status of Project Hydra will be presented. The final program to be discussed is a transmission voltage, high temperature superconducting fault current limiter funded by the US DOE. The project encompasses the design, construction and test of a 115 kV FCL for power transmission within a time frame of 4-5 years. Installation and testing are planned for a Southern California Edison substation. A project overview and progress under the first phase will be reported.

  2. A fast novel soft-start circuit for peak current-mode DC—DC buck converters

    NASA Astrophysics Data System (ADS)

    Jie, Li; Miao, Yang; Weifeng, Sun; Xiaoxia, Lu; Shen, Xu; Shengli, Lu

    2013-02-01

    A fully integrated soft-start circuit for DC—DC buck converters is presented. The proposed high speed soft-start circuit is made of two sections: an overshoot suppression circuit and an inrush current suppression circuit. The overshoot suppression circuit is presented to control the input of the error amplifier to make output voltage limit increase in steps without using an external capacitor. A variable clock signal is adopted in the inrush current suppression circuit to increase the duty cycle of the system and suppress the inrush current. The DC—DC converter with the proposed soft-start circuit has been fabricated with a standard 0.13 μm CMOS process. Experimental results show that the proposed high speed soft-start circuit has achieved less than 50 μs start-up time. The inductor current and the output voltage increase smoothly over the whole load range.

  3. Ripple current loss measurement with DC bias condition for high temperature superconducting power cable using calorimetry method

    NASA Astrophysics Data System (ADS)

    Kim, D. W.; Kim, J. G.; Kim, A. R.; Park, M.; Yu, I. K.; Sim, K. D.; Kim, S. H.; Lee, S. J.; Cho, J. W.; Won, Y. J.

    2010-11-01

    The authors calculated the loss of the High Temperature Superconducting (HTS) model cable using Norris ellipse formula, and measured the loss of the model cable experimentally. Two kinds of measuring method are used. One is the electrical method, and the other is the calorimetric method. The electrical method can be used only in AC condition. But the calorimetric method can be used in both AC and DC bias conditions. In order to propose an effective measuring approach for Ripple Dependent Loss (RDL) under DC bias condition using the calorimetric method, Bismuth Strontium Calcium Copper Oxide (BSCCO) wires were used for the HTS model cable, and the SUS tapes were used as a heating tape to make the same pattern of the temperature profiles as in the electrical method without the transport current. The temperature-loss relations were obtained by the electrical method, and then applied to the calorimetric method by which the RDL under DC bias condition was well estimated.

  4. Detection of combined faults in induction machines with stator parallel branches through the DWT of the startup current

    NASA Astrophysics Data System (ADS)

    Antonino-Daviu, J.; Jover Rodriguez, P.; Riera-Guasp, M.; Pineda-Sánchez, M.; Arkkio, A.

    2009-10-01

    The main objective of this paper is to diagnose the presence of combined faults in induction machines. For this purpose, a methodology based on the application of the Discrete Wavelet Transform (DWT) to the stator startup current is used. This approach was applied in previous works with success to the diagnosis of rotor asymmetries and mixed eccentricities in motors with different sizes and conditions. However, as most of the diagnosis methods hitherto developed, the application of the proposed approach was circumscribed to situations in which a single fault was present in the machine. In addition, the influence of other phenomena such as load torque oscillations or voltage fluctuations was studied, but without considering the combination of these phenomena and the fault in the machine. This work is intended, first, to apply the proposed transient-based methodology to several cases in which different faults (rotor asymmetries, mixed eccentricities and inter-turn and inter-coil stator short-circuits) are simultaneously present in the machine and, second, to apply it to cases regarding faults combined with other phenomena making difficult the diagnosis, such as load torque oscillations. Interesting considerations regarding the preponderance of the effects of some of the faults are also done in the paper. The application of the methodology is focused on induction machines with stator parallel branches; in this sense, the suitability of the use either of the phase current or of the branch current for the diagnosis of each particular fault is analysed. The results look promising with regard to the validity of the methodology for the reliable discrimination of simultaneous electromechanical faults and the diagnosis of faults combined with other phenomena.

  5. Performance test of the cryogenic cooling system for the superconducting fault current limiter

    NASA Astrophysics Data System (ADS)

    Hong, Yong-Ju; In, Sehwan; Yeom, Han-Kil; Kim, Heesun; Kim, Hye-Rim

    2015-12-01

    A Superconducting Fault Current Limiter is an electric power device which limits the fault current immediately in a power grid. The SFCL must be cooled to below the critical temperature of high temperature superconductor modules. In general, they are submerged in sub-cooled liquid nitrogen for their stable thermal characteristics. To cool and maintain the target temperature and pressure of the sub-cooled liquid nitrogen, the cryogenic cooling system should be designed well with a cryocooler and coolant circulation devices. The pressure of the cryostat for the SFCL should be pressurized to suppress the generation of nitrogen bubbles in quench mode of the SFCL. In this study, we tested the performance of the cooling system for the prototype 154 kV SFCL, which consist of a Stirling cryocooler, a subcooling cryostat, a pressure builder and a main cryostat for the SFCL module, to verify the design of the cooling system and the electric performance of the SFCL. The normal operation condition of the main cryostat is 71 K and 500 kPa. This paper presents tests results of the overall cooling system.

  6. Current leads and joints for HTS DC cable of 2.5 kA 20 kV

    NASA Astrophysics Data System (ADS)

    Naumov, Andrey V.; Diev, Dmitry N.; Dinisilov, Andrey N.; Anashkin, Oleg P.; Keilin, Victor E.; Kovalev, Ivan A.; Lobyntsev, Vladimir V.; Scherbakov, Vladimir I.; Shutova, Darya I.; Sytnykov, Victor E.

    2014-01-01

    Design of current lead boxes and joint boxes for 2.5 km long St. Petersbubrg HTS DC cable project (2.5 kA, 20 kV) is described. Maximum internal pressure of sub-cooled nitrogen is 1.4 MPa. Both current lead boxes and joint boxes are equipped with terminals for temperature and pressure measurements. Current leads of different polarities have independent electrical insulators. Two current lead boxes and one joint box have been preliminary tested. The first test results are reported.

  7. Computational Study on the Steady-state Impedance of Saturated-core Superconducting Fault Current Limiter

    NASA Astrophysics Data System (ADS)

    Zhang, C.; Tang, Y.; Liang, S.; Ren, L.; Wang, Z.; Xu, Y.

    This paper presents the electromagnetic analysis of a high voltage saturated-core superconducting fault current limiter (SCSFCL). The numerical analyses of a three-dimensional (3D) model is shown, and the specific parameters are given. The model focus on the steady-state impedance of the limiter when connected to the power grid. It analyzed the dependence of steady-state impedance on the AC coil current, and the relationship between oil gap and coil inductance. The results suggest that, adding oil gap between slice of silicon steel can reduce the core cross-section, restrain the ultraharmonic and decrease the steady-state impedance. As the core cross-section of AC limb decreased from 4344 cm2 to 3983 cm2, the total harmonic distortion for voltage decreased from 2.4% to 1.8%, and the impedance decreased from 1.082 Ω to 1.069 Ω(Idc=400A,Iac=1296A).

  8. Application of a modified flux-coupling type superconducting fault current limiter to transient performance enhancement of micro-grid

    NASA Astrophysics Data System (ADS)

    Chen, Lei; Zheng, Feng; Deng, Changhong; Li, Shichun; Li, Miao; Liu, Hui; Zhu, Lin; Guo, Fang

    2015-11-01

    Concerning the application and development of a micro-grid system which is designed to accommodate high penetration of intermittent renewable resources, one of the main issues is related to an increase in the fault-current level. It is crucial to ensure the micro-grid's operational stability and service reliability when a fault occurs in the main network. In this paper, our research group suggests a modified flux-coupling type superconducting fault current limiter (SFCL) to enhance the transient performance of a typical micro-grid system. The SFCL is installed at the point of common coupling (PCC) between the main network and the micro-grid, and it is expected to actively improve the micro-grid's fault ride-through capability. And for some specific faults, the micro-grid should disconnect from the main network, and the SFCL's contribution is to make the micro-grid carry out a smooth transition between its grid-connected and islanded modes. Related theory derivation, technical discussion and simulation analysis are performed. From the demonstrated results, applying the SFCL can effectively limit the fault current, maintain the power balance, and enhance the voltage and frequency stability of the micro-grid.

  9. Modeling of DC potential structures induced by RF sheaths with transverse currents in front of ICRF antenna

    SciTech Connect

    Faudot, E.; Heuraux, S.; Colas, L.

    2007-09-28

    RF heating is fully dependent on edge plasma conditions and particularly on convection of accelerated particles which can damage ICRH antennas (hot spots and impurity injection). These accelerated particle fluxes born in DC potential structures are induced by sheaths which rectify RF potentials. The potential map in front of antenna is not uniform so that transverse (to magnetic field) RF currents occur and can significantly modify the final DC potential map and thus convective flux distribution. The behavior of rectified potentials is investigated here for f = F{sub ci} and f>F{sub ci}, which was not yet achieved in our last works [1]. Therefore, a 2D fluid modeling including RF sheaths physics (parallel current) coupled with transverse RF currents has been built. The full description of the currents exhibits a maximum for frequencies around Fci, which can be explained by the fact that RF oscillation is capacitive at low frequency and inductive at high frequency. Both effects are present at frequencies around F{sub ci} and the DC peak potential appears for f = F{sub ci}/2. This is due to the rectification of the sinusoidal signal, which doubles the effective RF frequency radiated by the antenna. The theoretical DC peak value is 0.5 time the RF amplitude of the applied potential instead of 1/{pi} without transverse currents. For typical potential structures in front of ICRH antennas (centimetric wide and 1000 Volts peak potential), a factor between 0.4 and 0.45 can be expected according to 2D fiuid code results.

  10. Comparison of the quench and fault current limiting characteristics of the flux-coupling type SFCL with single and three-phase transformer

    NASA Astrophysics Data System (ADS)

    Jung, Byung Ik; Cho, Yong Sun; Park, Hyoung Min; Chung, Dong Chul; Choi, Hyo Sang

    2013-01-01

    The South Korean power grid has a network structure for the flexible operation of the system. The continuously increasing power demand necessitated the increase of power facilities, which decreased the impedance in the power system. As a result, the size of the fault current in the event of a system fault increased. As this increased fault current size is threatening the breaking capacity of the circuit breaker, the main protective device, a solution to this problem is needed. The superconducting fault current limiter (SFCL) has been designed to address this problem. SFCL supports the stable operation of the circuit breaker through its excellent fault-current-limiting operation [1-5]. In this paper, the quench and fault current limiting characteristics of the flux-coupling-type SFCL with one three-phase transformer were compared with those of the same SFCL type but with three single-phase transformers. In the case of the three-phase transformers, both the superconducting elements of the fault and sound phases were quenched, whereas in the case of the single-phase transformer, only that of the fault phase was quenched. For the fault current limiting rate, both cases showed similar rates for the single line-to-ground fault, but for the three-wire earth fault, the fault current limiting rate of the single-phase transformer was over 90% whereas that of the three-phase transformer was about 60%. It appears that when the three-phase transformer was used, the limiting rate decreased because the fluxes by the fault current of each phase were linked in one core. When the power loads of the superconducting elements were compared by fault type, the initial (half-cycle) load was great when the single-phase transformer was applied, whereas for the three-phase transformer, its power load was slightly lower at the initial stage but became greater after the half fault cycle.

  11. Large reduction of the depinning field for a transverse domain wall under application of rf and dc currents

    NASA Astrophysics Data System (ADS)

    Metaxas, P. J.; Anane, A.; Cros, V.; Grollier, J.; Deranlot, C.; Petroff, F.; Fert, A.; Ulysse, C.; Faini, G.

    2010-03-01

    A new generation of proposed spintronic devices are based on domain wall (DW) motion (DW-MRAM, DW logic, racetrack memory...). However, reliable depinning of domain walls remains elusive, especially in zero field. Here, we have studied the combined effect of rf and dc currents on the depinning of transverse walls in the soft NiFe layer of a 100 nm wide Co/Cu/NiFe spin valve wire. Using the GMR effect, we ensure that the domain wall is always prepared at the same intrinsic defect and then measure the depinning field for different applied dc and rf currents. Notably, for a narrow range of rf frequencies at around 3GHz, we evidence a strong reduction in the depinning field (from ˜80 Oe to ˜30 Oe). Our results are suggestive of a very efficient resonant depinning effect in our spin valve wire which depends not only on the rf power but also on the polarity and amplitude of the accompanying dc current.

  12. Charge and fluence lifetime measurements of a dc high voltage GaAs photogun at high average current

    SciTech Connect

    J. Grames, R. Suleiman, P.A. Adderley, J. Clark, J. Hansknecht, D. Machie, M. Poelker, M.L. Stutzman

    2011-04-01

    GaAs-based dc high voltage photoguns used at accelerators with extensive user programs must exhibit long photocathode operating lifetime. Achieving this goal represents a significant challenge for proposed high average current facilities that must operate at tens of milliamperes or more. This paper describes techniques to maintain good vacuum while delivering beam, and techniques that minimize the ill effects of ion bombardment, the dominant mechanism that reduces photocathode yield of a GaAs-based dc high voltage photogun. Experimental results presented here demonstrate enhanced lifetime at high beam currents by: (a) operating with the drive laser beam positioned away from the electrostatic center of the photocathode, (b) limiting the photocathode active area to eliminate photoemission from regions of the photocathode that do not support efficient beam delivery, (c) using a large drive laser beam to distribute ion damage over a larger area, and (d) by applying a relatively low bias voltage to the anode to repel ions created within the downstream beam line. A combination of these techniques provided the best total charge extracted lifetimes in excess of 1000 C at dc beam currents up to 9.5 mA, using green light illumination of bulk GaAs inside a 100 kV photogun.

  13. Electromembrane extraction using stabilized constant d.c. electric current--a simple tool for improvement of extraction performance.

    PubMed

    Slampová, Andrea; Kubáň, Pavel; Boček, Petr

    2012-04-20

    This contribution presents an experimental approach for improvement of analytical performance of electromembrane extraction (EME), which is based on the use of stabilized constant d.c. electric current. Extractions were performed using a high voltage power supply, which provided stabilized constant d.c. current down to 1μA and facilitated current-controlled transfer of ions of interest from a donor solution through a supported liquid membrane (SLM) into an acceptor solution. Repeatability of the extraction process has significantly improved for EME at constant electric current compared to EME at constant voltage. The improved repeatability of the extraction process was demonstrated on EME-capillary electrophoresis (EME-CE) analyses of selected basic drugs and amino acids in standard solutions and in human urine and serum samples. RSD values of peak areas of the analytes for EME-CE analyses were about two-fold better for EME at constant electric current (2.8-8.9%) compared to EME at constant voltage (3.6-17.8%). Other analytical parameters of the EME-CE methods, such as limits of detection, linear ranges and correlation coefficients were not statistically different for the two EME modes. Moreover, EME at constant electric current did not suffer from SLM instabilities frequently observed for EME at constant voltage. PMID:22154457

  14. Adaptive switching frequency buck DC—DC converter with high-accuracy on-chip current sensor

    NASA Astrophysics Data System (ADS)

    Jinguang, Jiang; Fei, Huang; Zhihui, Xiong

    2015-05-01

    A current-mode PWM buck DC—DC converter is proposed. With the high-accuracy on-chip current sensor, the switching frequency can be selected automatically according to load requirements. This method improves efficiency and obtains an excellent transient response. The high accuracy of the current sensor is achieved by a simple switch technique without an amplifier. This has the direct benefit of reducing power dissipation and die size. Additionally, a novel soft-start circuit is presented to avoid the inrush current at the starting up state. Finally, this DC—DC converter is fabricated with the 0.5 μm standard CMOS process. The chip occupies 3.38 mm2. The accuracy of the proposed current sensor can achieve 99.5% @ 200 mA. Experimental results show that the peak efficiency is 91.8%. The input voltage ranges from 5 to 18 V, while a 2 A load current can be obtained. Project supported by the National Natural Science Foundation of China (No. 41274047), the Natural Science Foundation of Jiangsu Province (No. BK2012639), the Science and Technology Enterprises in Jiangsu Province Technology Innovation Fund (No. BC2012121), and the Changzhou Science and Technology Support (Industrial) Project (No. CE20120074).

  15. Simplified dc to dc converter

    NASA Technical Reports Server (NTRS)

    Gruber, R. P. (Inventor)

    1984-01-01

    A dc to dc converter which can start with a shorted output and which regulates output voltage and current is described. Voltage controlled switches directed current through the primary of a transformer the secondary of which includes virtual reactance. The switching frequency of the switches is appropriately varied to increase the voltage drop across the virtual reactance in the secondary winding to which there is connected a low impedance load. A starting circuit suitable for voltage switching devices is provided.

  16. Test Results For a 25-m Prototype Fault Current Limiting HTS Cable for Project Hydra

    SciTech Connect

    Rey, Christopher M; Duckworth, Robert C; Demko, Jonathan A; Ellis, Alvin R; Gouge, Michael J; James, David Randy; Tuncer, Enis

    2010-01-01

    The Oak Ridge National Laboratory (ORNL) has tested a 25-m long prototype High Temperature Superconducting (HTS) cable with inherent Fault-Current Limiting (FCL) capability at its recently upgraded HTS cable test facility in Oak Ridge, TN. The HTS-FCL cable and terminations were designed and fabricated by Ultera, which is a joint venture of Southwire and nkt cables with FCL features and HTS wire provided by American Superconductor Corporation. The overall project is sponsored by the U.S. Department of Homeland Security. The ultimate goal of the 25-m HTS-FCL cable test program was to verify the design and ensure the operational integrity for the eventual installation of a ~ 200-m fully functional HTS-FCL cable in the Consolidated Edison electric grid located in downtown New York City. The 25-m HTS-FCL cable consisted of a three-phase (3- ) Triax design with a cold dielectric between the phases. The HTS-FCL cable had an operational voltage of 13.8 kV phase-to-phase and an operating current of 4000 Arms per phase, which is the highest operating current to date of any HTS cable. The 25-m HTS-FCL cable was subjected to a series of cryogenic and electrical tests. Test results from the 25-m HTS-FCL cable are presented and discussed.

  17. Test Results for a 25 Meter Prototype Fault Current Limiting Hts Cable for Project Hydra

    NASA Astrophysics Data System (ADS)

    Rey, C. M.; Duckworth, R. C.; Demko, J. A.; Ellis, A.; James, D. R.; Gouge, M. J.; Tuncer, E.

    2010-04-01

    The Oak Ridge National Laboratory (ORNL) has tested a 25-m long prototype High Temperature Superconducting (HTS) cable with inherent Fault-Current Limiting (FCL) capability at its HTS cable test facility. The HTS-FCL cable and terminations were designed and fabricated by Ultera, which is a joint venture between Southwire and nkt cables. System integration and HTS wire were provided by American Superconductor Corporation who was the overall team leader of the project. The ultimate goal of the 25-m HTS-FCL cable test program was to verify the design and ensure the operational integrity for the eventual installation of a ˜200-m fully functional HTS-FCL cable in the Consolidated Edison electric grid located in downtown New York City. The 25-m HTS-FCL cable consisted of a three-phase (3-Φ) HTS Triax™ design with a cold dielectric between the phases. The HTS-FCL cable had an operational voltage of 13.8 kV phase-to-phase (7967 V phase-to-ground) and an operating current of 4000 Arms per phase, which is the highest operating current to date of any HTS cable. The 25-m HTS-FCL cable was subjected to a series of cryogenic and electrical tests. Test results from the 25-m HTS-FCL cable are presented and discussed.

  18. Characteristics of sheath-driven tangential flow produced by a low-current DC surface glow discharge plasma actuator

    NASA Astrophysics Data System (ADS)

    Shin, Jichul; Shajid Rahman, Mohammad

    2014-08-01

    An experimental investigation of low-speed flow actuation at near-atmospheric pressure is presented. The flow actuation is achieved via low-current ( \\lesssim 1.0 mA) continuous or pulsed DC surface glow discharge plasma. The plasma actuator, consisting of two sharp-edged nickel electrodes, produces a tangential flow in a direction from anode to cathode, and is visualized using high-speed schlieren photography. The induced flow velocity estimated via the schlieren images reaches up to 5 m/s in test cases. The actuation capability increases with pressure and electrode gap distances, and the induced flow velocity increases logarithmically with the discharge power. Pulsed DC exhibits slightly improved actuation capability with better directionality. An analytic estimation of induced flow velocity obtained based on ion momentum in the cathode sheath and gas dynamics in one-dimensional flow yields values similar to those measured.

  19. Influence of a voltage compensation type active superconducting fault current limiter on the transient stability of power system

    NASA Astrophysics Data System (ADS)

    Chen, L.; Tang, Y. J.; Shi, J.; Chen, N.; Song, M.; Cheng, S. J.; Hu, Y.; Chen, X. S.

    2009-10-01

    We have proposed a voltage compensation type active superconducting fault current limiter (SFCL). In this paper, the influence of the SFCL on the transient stability of power system is investigated. For the typical one-machine infinite-bus system, the power-angle characteristics of generator with SFCL are studied in different working conditions, and the transient physical process is analyzed. Using MATLAB SIMULINK, the power-angle swing curves are simulated under different current-limiting modes, fault types and fault clearance times. The results show that the proposed SFCL can effectively reduce the transient swing amplitude of rotor and extend the critical clearance time under mode 1, compared with mode 2 and mode 3 having few effects on enhancing the transient stability.

  20. Status and Progress of a Fault Current Limiting Hts Cable to BE Installed in the con EDISON Grid

    NASA Astrophysics Data System (ADS)

    Maguire, J.; Folts, D.; Yuan, J.; Henderson, N.; Lindsay, D.; Knoll, D.; Rey, C.; Duckworth, R.; Gouge, M.; Wolff, Z.; Kurtz, S.

    2010-04-01

    In the last decade, significant advances in the performance of second generation (2G) high temperature superconducting wire have made it suitable for commercially viable applications such as electric power cables and fault current limiters. Currently, the U.S. Department of Homeland Security is co-funding the design, development and demonstration of an inherently fault current limiting HTS cable under the Hydra project with American Superconductor and Consolidated Edison. The cable will be approximately 300 m long and is being designed to carry 96 MVA at a distribution level voltage of 13.8 kV. The underground cable will be installed and energized in New York City. The project is led by American Superconductor teamed with Con Edison, Ultera (Southwire and nkt cables joint venture), and Air Liquide. This paper describes the general goals, design criteria, status and progress of the project. Fault current limiting has already been demonstrated in 3 m prototype cables, and test results on a 25 m three-phase cable will be presented. An overview of the concept of a fault current limiting cable and the system advantages of this unique type of cable will be described.

  1. Electrical Motor Current Signal Analysis using a Modulation Signal Bispectrum for the Fault Diagnosis of a Gearbox Downstream

    NASA Astrophysics Data System (ADS)

    Haram, M.; Wang, T.; Gu, F.; Ball, A. D.

    2012-05-01

    Motor current signal analysis has been an effective way for many years of monitoring electrical machines themselves. However, little work has been carried out in using this technique for monitoring their downstream equipment because of difficulties in extracting small fault components in the measured current signals. This paper investigates the characteristics of electrical current signals for monitoring the faults from a downstream gearbox using a modulation signal bispectrum (MSB), including phase effects in extracting small modulating components in a noisy measurement. An analytical study is firstly performed to understand amplitude, frequency and phase characteristics of current signals due to faults. It then explores the performance of MSB analysis in detecting weak modulating components in current signals. Experimental study based on a 10kw two stage gearbox, driven by a three phase induction motor, shows that MSB peaks at different rotational frequencies can be based to quantify the severity of gear tooth breakage and the degrees of shaft misalignment. In addition, the type and location of a fault can be recognized based on the frequency at which the change of MSB peak is the highest among different frequencies.

  2. Transient thermal analysis of a tri-axial HTS cable on fault current condition

    NASA Astrophysics Data System (ADS)

    Hu, N.; Cao, K.; Wang, D.; Song, M.; Miyagi, D.; Tsuda, M.; Hamajima, T.

    2013-11-01

    High-temperature superconducting (HTS) tri-axial cable, which consists of three concentric phases, was developed as a potential commercial solution for next generation distribution power network. In our previous research, we simulate the transient thermal behavior of the cable by solving the heat equation using one-dimension difference method. The result shows that it takes time to recover the cable temperature to the steady-state operation level due to a low thermal conductivity of the insulation layer after a fault. However for a long cable system, when middle phase in concentric structure is rated under an over current, accumulated heat from middle phase might continually warm up the liquid nitrogen (LN2) flow by heat transfer even the over current has been stopped. In this research, we improve the numerically calculation which includes the consideration of flowing liquid nitrogen and the heat transfer in both radius and longitudinal directions. A long tri-axial cable system thermal stability is discussed based on the calculation results.

  3. Comparison microstructure and sliding wear properties of nickel-cobalt/CNT composite coatings by DC, PC and PRC current electrodeposition

    NASA Astrophysics Data System (ADS)

    Karslioglu, Ramazan; Akbulut, Hatem

    2015-10-01

    Nickel-cobalt (Ni-Co) alloys and Ni-Co/multiwalled carbon nanotube (MWCNT) composite coatings were prepared under direct current (DC), pulse current (PC) and pulse reverse current (PRC) methods. The effect of different deposition currents on the surface microstructure, crystallographic structure, microhardness, and reciprocating sliding wear behavior were investigated. MWCNT co-deposition caused to modify Ni-Co surface morphology, decrease in grain size, and increase in surface roughness, since MWCNTs effected the deposition mechanisms of Ni-Co alloy. The nanocomposite coatings deposited using PC and PRC deposition exhibited significant improvement in microhardness and wear resistance due to unique enhanced reinforcement of MWCNTs in Ni-Co coatings. Reciprocating sliding wear tests evidenced that co-deposition of MWCNTs provided effective load bearing ability and self-lubrication between the friction surfaces. However, the friction coefficient increases for all the nanocomposites produced with DC, PC and PRC methods showed to be increased. In the Ni-Co alloy coatings, the predominant wear mechanisms was delamination caused by fatigue micro cracking whereas in the MWCNT co-deposited composites wear mechanism showed abrasive grooves and plastic deformation due to decreased real contact area.

  4. Design, Fabrication and Testing of a Superconducting Fault Current Limiter (SFCL)

    SciTech Connect

    Gouge, M..; Schwenterly, S.W.; Hazelton, D.

    2011-06-15

    The purpose of this project was to conduct R&D on specified components and provide technical design support to a SuperPower team developing a high temperature superconducting Fault Current Limiter (SFCL). ORNL teamed with SuperPower, Inc. on a Superconductivity Partnerships with Industry (SPI) proposal for the SFCL that was submitted to DOE and approved in FY 2003. A contract between DOE and SuperPower, Inc. was signed on July 14, 2003 to design, fabricate and test the SFCL. This device employs high temperature superconducting (HTS) elements and SuperPower's proprietary technology. The program goal was to demonstrate a device that will address a broad range of the utility applications and meet utility industry requirements. This DOE-sponsored Superconductivity Partnership with Industry project would positively impact electric power transmission reliability and security by introducing a new element in the grid that can significantly mitigate fault currents and provide lower cost solutions for grid protection. The project will conduct R&D on specified components and provide technical design support to a SuperPower-led team developing a SFCL as detailed in tasks 1-5 below. Note the SuperPower scope over the broad SPI project is much larger than that shown below which indicates only the SuperPower tasks that are complementary to the ORNL tasks. SuperPower is the Project Manager for the SFCL program, and is responsible for completion of the project on schedule and budget. The scope of work for ORNL is to provide R&D support for the SFCL in the following four broad areas: (1) Assist with high voltage subsystem R&D, design, fabrication and testing including characterization of the general dielectric performance of LN2 and component materials; (2) Consult on cryogenic subsystem R&D, design, fabrication and testing; (3) Participate in project conceptual and detailed design reviews; and (4) Guide commercialization by participation on the Technical Advisory Board (TAB). Super

  5. Novel DC ring topology and protection system - a comprehensive solution for mega city power grids

    NASA Astrophysics Data System (ADS)

    Haj-Maharsi, Mohamed Yassine

    2009-07-01

    using data provided by ABB corporate research located in China. I built on the work that had been performed in ABB China by considering different contingencies and I applied solutions using individual FACTS devices such as FCL, SVC-LightRTM, and HVDC-LightRTM. I analyzed the results from each solution in order to assess its merits and limitations in dealing with fault current and voltage stability problems. Then I presented a novel DC ring topology that provides redundancy, better protection against cascading faults, and does not increase short circuit levels. With this topology, adding loads or power sources does not impact system protection or performance. (2) I proposed two novel designs for a DC circuit breaker that is of critical importance to DC applications using multiple converter stations. The proposed designs solve the problem of DC fault clearing without causing significant voltage drops, current oscillations, or shutting down of any converter station connected to the DC bus. The DC breaker rated at a voltage of 320 kV and a current of 3000 A can interrupt DC currents as high as 70 kA within 800 mus. (3) I proposed a novel placement of the DC circuit breakers within the DC ring topology combined with an intelligent protection algorithm that optimizes fault detection and isolation without affecting the rest of the DC system. The protection scheme uses local measurements and special coordination techniques for clearing solid faults and uses differential measurements to identify and isolate high impedance faults.

  6. High-angle origin of the currently low-angle Badwater Turtleback fault, Death Valley, California

    SciTech Connect

    Miller, M.G. )

    1991-04-01

    The late Cenozoic Badwater Turtleback fault separates an upper plate of volcanic and sedimentary rocks from a lower plate of predominantly mylonitic plutonic and metamorphic rocks. The Turtleback fault, however, is not a single continuous surface, but consists of a least three generations of faults. These faults occur as discrete, crosscutting segments that progressively decrease in age and increase in dip to the west. Therefore, they probably began at moderate to steep angles but rotated to lower angles with extensional strain. If so, lower plate mylonitic rocks also restore to steeper dips and suggest that transport of the upper plate occurred on moderate to steeply dipping surfaces in the middle and upper crust. The crosscutting nature of the fault segments and their initial moderate to steep dips, plus a possible offset marker on one of the segments, are most consistent with moderate amounts of extension in the Death Valley region.

  7. Photovoltaic ground fault and blind spot electrical simulations.

    SciTech Connect

    Flicker, Jack David; Johnson, Jay

    2013-06-01

    Ground faults in photovoltaic (PV) systems pose a fire and shock hazard. To mitigate these risks, AC-isolated, DC grounded PV systems in the United States use Ground Fault Protection Devices (GFPDs), e.g., fuses, to de-energize the PV system when there is a ground fault. Recently the effectiveness of these protection devices has come under question because multiple fires have started when ground faults went undetected. In order to understand the limitations of fuse-based ground fault protection in PV systems, analytical and numerical simulations of different ground faults were performed. The numerical simulations were conducted with Simulation Program with Integrated Circuit Emphasis (SPICE) using a circuit model of the PV system which included the modules, wiring, switchgear, grounded or ungrounded components, and the inverter. The derivation of the SPICE model and the results of parametric fault current studies are provided with varying array topologies, fuse sizes, and fault impedances. Closed-form analytical approximations for GFPD currents from faults to the grounded current carrying conductor-known as %E2%80%9Cblind spot%E2%80%9D ground faults-are derived to provide greater understanding of the influence of array impedances on fault currents. The behavior of the array during various ground faults is studied for a range of ground fault fuse sizes to determine if reducing the size of the fuse improves ground fault detection sensitivity. The results of the simulations show that reducing the amperage rating of the protective fuse does increase fault current detection sensitivity without increasing the likelihood of nuisance trips to a degree. Unfortunately, this benefit reaches a limit as fuses become smaller and their internal resistance increases to the point of becoming a major element in the fault current circuit.

  8. Study of recovery characteristics of 2nd generation HTS tapes with different stabilizers for resistive type superconducting fault current limiters

    NASA Astrophysics Data System (ADS)

    Sheng, Jie; Zeng, Weina; Ma, Jun; Yao, Zhihao; Li, Zhuyong; Jin, Zhijian; Hong, Zhiyong

    2016-02-01

    The resistive type superconducting fault current limiter (SFCL) is one of the most important superconducting power applications nowadays. As known, this type of SFCL is settled directly in the power transmission line. When a short fault happens, the temperature of the superconductors in the SFCL will increase sharply due to the huge generated heat. This means the superconductors need time to recover the superconducting properties and be ready for the next short fault. So the recovery characteristics become one of the most crucial features of the resistive type SFCL. In this paper, several different kinds of measuring methods are presented to calculate the recovery time of the HTS tapes, and comparison of these methods is also carried out by a standard test. On basis of this, samples with different kinds of stabilizers are used to explore the influence of stabilizer on their recovery characteristics. In addition, the influence of the encapsulation technology is also discussed in this paper.

  9. Development, Testing and Installation of a Superconducting Fault Current Limiter for Medium Voltage Distribution Networks

    NASA Astrophysics Data System (ADS)

    Martini, Luciano; Bocchi, Marco; Ascade, Massimo; Valzasina, Angelo; Rossi, Valerio; Angeli, Giuliano; Ravetta, Cesare

    Since 2009 Ricerca sul Sistema Energetico (RSE S.p.A.) has been involved in the design of resistive-type Superconducting Fault Current Limiter (SFCL) for MV applications to be installed in the A2A Reti Elettriche S.p.A distribution grid in the Milano area. The project started with simulations, design and testing activities for a singlephase device; in this paper we report on the successive step, which is concerned with developing, testing and installation at the hosting utility of the final three-phase SFCL prototype. The result of this research activity is a resistive-type 9 kV/3.4 MVA SFCL device, based on first generation (1G) BSCCO tapes, developed by RSE in the framework of a R&D national project. Owing to the positive test results of partial discharge, dielectric and shortcircuit results the three-phase SFCL device is being to be installed in the A2A distribution grid in the Milano area and it is going to be soon energized starting a one-year long field-testing activity.

  10. Diagnosis of Stator-Winding-Turn Faults of Induction Motor by Direct Detection of Negative-Sequence Currents

    NASA Astrophysics Data System (ADS)

    Kato, Toshiji; Inoue, Kaoru; Yoshida, Keisuke

    In an AC motor, the quick detection of an initially small fault is important for preventing any consequent large fault. Various detection approaches have been proposed in previous papers, for example, by the Park vector (PV), AI techniques, wavelet analysis, and negative-sequence analysis. This paper proposes a method for diagnosing the stator-winding faults of an induction motor by the direct detection of its negative-sequence current. Before starting the diagnosis, the asymmetry admittances for the considered fault cases are obtained by analysis or simulation. The amplitude and phase of the positive-sequence voltage, Vp, and of the positive-sequence current, Ip, are extracted from the voltage PV and current PV, respectively. The amplitude and phase of the negative-sequence, In, are extracted from the residue. The asymmetry admittance, Ya, is calculated from In and Vp. When the positive-sequence admittance is known, Ya can also be calculated from Yp, Ip, and In. These steps are repeated for each sample time and the motor condition is diagnosed according to the variations in the Ya values. The simulation and experimental results are also shown and the proposed method is investigated and validated.

  11. A short review of our current understanding of the development of ring faults during collapse caldera formation

    NASA Astrophysics Data System (ADS)

    Geyer, Adelina; Marti, Joan

    2014-09-01

    The term collapse caldera refers to those volcanic depressions resulting from the sinking of the chamber roof due to the rapid withdrawal of magma during the course of an eruption. During the last three decades, collapse caldera dynamics has been the focus of attention of numerous, theoretical, numerical and experimental studies. Nonetheless, even if there is a tendency to go for a general and comprehensive caldera dynamics model, some key aspects remain unclear, controversial or completely unsolved. This is the case of ring fault nucleation points and propagation and dip direction. Since direct information on calderas’ deeper structure comes mainly from partially eroded calderas or few witnessed collapses, ring faults layout at depth remains still uncertain. This has generated a strong debate over the detailed internal fault and fracture configuration of a caldera collapse and, in more detail, how ring faults initiate and propagate. We offer here a very short description of the main results obtained by those analogue and theoretical/mathematical models applied to the study of collapse caldera formation. We place special attention on those observations related to the nucleation and propagation of the collapse-controlling ring faults. This summary is relevant to understand the current state-of-the-art of this topic and it should be taken under consideration in future works dealing with collapse caldera dynamics.

  12. Explaining the current geodetic field with geological models: A case study of the Haiyuan fault system

    NASA Astrophysics Data System (ADS)

    Daout, S.; Jolivet, R.; Lasserre, C.; Doin, M. P.; Barbot, S.; Peltzer, G.; Tapponnier, P.

    2015-12-01

    Oblique convergence across Tibet leads to slip partitioning with the co-existence of strike-slip, normal and thrust motion in major fault systems. While such complexity has been shown at the surface, the question is to understand how faults interact and accumulate strain at depth. Here, we process InSAR data across the central Haiyuan restraining bend, at the north-eastern boundary of the Tibetan plateau and show that the surface complexity can be explained by partitioning of a uniform deep-seated convergence rate. We construct a time series of ground deformation, from Envisat radar data spanning from 2001-2011 period, across a challenging area because of the high jump in topography between the desert environment and the plateau. To improve the signal-to-noise ratio, we used the latest Synthetic Aperture Radar interferometry methodology, such as Global Atmospheric Models (ERA Interim) and Digital Elevation Model errors corrections before unwrapping. We then developed a new Bayesian approach, jointly inverting our InSAR time series together with published GPS displacements. We explore fault system geometry at depth and associated slip rates and determine a uniform N86±7E° convergence rate of 8.45±1.4 mm/yr across the whole fault system with a variable partitioning west and east of a major extensional fault-jog. Our 2D model gives a quantitative understanding of how crustal deformation is accumulated by the various branches of this thrust/strike-slip fault system and demonstrate the importance of the geometry of the Haiyuan Fault, controlling the partitioning or the extrusion of the block motion. The approach we have developed would allow constraining the low strain accumulation along deep faults, like for example for the blind thrust faults or possible detachment in the San Andreas "big bend", which are often associated to a poorly understood seismic hazard.

  13. Direct current (DC) resistivity and induced polarization (IP) monitoring of active layer dynamics at high temporal resolution

    NASA Astrophysics Data System (ADS)

    Doetsch, Joseph; Ingeman-Nielsen, Thomas; Christiansen, Anders V.; Fiandaca, Gianluca; Auken, Esben; Adamson, Kathryn; Lane, Timothy; Elberling, Bo

    2014-05-01

    With climatic changes, permafrost thawing and changes in active layer dynamics influencing microbial activity and greenhouse gas feedbacks to the climate system, understanding of the interaction between biogeochemical and thermal processes in the ground is of increasing interest. Here we present results of from an on-going field experiment, where the active layer dynamics are monitored using direct current (DC) resistivity and induced polarization (IP) measurements at high temporal resolution. These DC/IP measurements are supplemented by pore water analysis, continuous ground temperature monitoring (0-150 cm depth) and structural information from ground penetrating radar (GPR). The study site (N69°15', W53°30', 30 m a.s.l.) is located at a Vaccinium/Empetrum heath tundra area near the Arctic Station on Qeqertarsuaq on the west coast of Greenland. Mean air temperatures of the warmest (July) and the coldest (February-March) months are 7.1 and -16.0°C, respectively. The DC/IP monitoring system was installed in July 2013 and has since been acquiring at least 6 data sets per day on a 42-electrode profile with 0.5 m electrode spacing. Recorded data include DC resistivity, stacked full-decay IP responses and full waveform data at 1 kHz sampling frequency. The monitoring system operates fully automatic and data are backed up locally and uploaded to a web server. Time-lapse DC resistivity inversions of data acquired during the freezing period of October - December 2013 clearly image the soil freezing as a strong increase in resistivity. While the freezing horizon generally moves deeper with time, some variations in the freezing depth are observed along the profile. Comparison with soil temperature measurements at different depths indicates a linear relationship between the logarithm of electrical resistivity and temperature. Preliminary time-lapse inversions of the full-decay induced polarization (IP) data indicate a decrease of chargeability with freezing of the ground

  14. Position-and Velocity- Sensorless Control of Cylindrical Brushless DC Motors Driven by Sinusoidal Current at Low Speed Using Eddy Current

    NASA Astrophysics Data System (ADS)

    Takashima, Hiroshi; Tomita, Mutuwo; Chen, Zhiqian; Satoh, Mitsuhiko; Doki, Shinji; Okuma, Shigeru

    This paper proposes to paste non-magnetic materials on the rotor surface of a cylindrical brushless DC motor and to use the model including the extended e.m.f. for sensorless control. In the proposed method, the inductance changes depending on the rotor position because of eddy currents, which flow on the non-magnetic material at high frequency. The rotor position can be estimated at standstill and at low speeds. The simulation results show that the proposed method is very useful.

  15. DC to DC battery charger

    SciTech Connect

    Carr, F.L.; Terrill, L.R.

    1987-01-20

    A DC to DC battery charger is described for a vehicle comprising: adapter plug means for making electrical connections to a first battery through a cigarette lighter socket in the vehicle; means of making electrical connections to a second battery to be charged; a DC to AC converter and an AC to DC rectifier for elevating the voltage from the first battery to a voltage above that of the second battery; integrated circuit means for generating a pulse width modulated current as a function for the charged condition of the second battery; transistor switch means supplied with the pulse width modulated current for developing a charging voltage; a choke coil and a capacitor serially connected to the transistor switch means; and a diode connected across the choke coil and the capacitor whereby the capacitor is charged during pulses of current from the transistor switch means through the choke coil. The choke coil reverses polarity at the termination of the pulses of current and continues to charge the battery through the diode. The DC rectified voltage is controlled by the integrated circuit means for regulating current through the choke coil.

  16. dc3dm: Software to efficiently form and apply a 3D DDM operator for a nonuniformly discretized rectangular planar fault

    NASA Astrophysics Data System (ADS)

    Bradley, A. M.

    2013-12-01

    My poster will describe dc3dm, a free open source software (FOSS) package that efficiently forms and applies the linear operator relating slip and traction components on a nonuniformly discretized rectangular planar fault in a homogeneous elastic (HE) half space. This linear operator implements what is called the displacement discontinuity method (DDM). The key properties of dc3dm are: 1. The mesh can be nonuniform. 2. Work and memory scale roughly linearly in the number of elements (rather than quadratically). 3. The order of accuracy of my method on a nonuniform mesh is the same as that of the standard method on a uniform mesh. Property 2 is achieved using my FOSS package hmmvp [AGU 2012]. A nonuniform mesh (property 1) is natural for some problems. For example, in a rate-state friction simulation, nucleation length, and so required element size, scales reciprocally with effective normal stress. Property 3 assures that if a nonuniform mesh is more efficient than a uniform mesh (in the sense of accuracy per element) at one level of mesh refinement, it will remain so at all further mesh refinements. I use the routine DC3D of Y. Okada, which calculates the stress tensor at a receiver resulting from a rectangular uniform dislocation source in an HE half space. On a uniform mesh, straightforward application of this Green's function (GF) yields a DDM I refer to as DDMu. On a nonuniform mesh, this same procedure leads to artifacts that degrade the order of accuracy of the DDM. I have developed a method I call IGA that implements the DDM using this GF for a nonuniformly discretized mesh having certain properties. Importantly, IGA's order of accuracy on a nonuniform mesh is the same as DDMu's on a uniform one. Boundary conditions can be periodic in the surface-parallel direction (in both directions if the GF is for a whole space), velocity on any side, and free surface. The mesh must have the following main property: each uniquely sized element must tile each element

  17. Setting method of parameters for SN transition fault current limiter into 6.6kV distribution system

    NASA Astrophysics Data System (ADS)

    Kameda (Criepi, H.; Torii(Criepi, S.

    2008-02-01

    A fault current limiter (FCL) is an outstanding apparatus which the impedance does not appear when no fault occurs, but the impedance appears only when a fault occurs in a power system. The operation of the FCL causes the effective reduction of the fault current. Although there are various kinds of FCLs in principles which have ever proposed, we think that a SN transition FCL with small normal loss will be promising since it is connected in series. However, we need to solve many problems toward practical use. In this paper, we propose the setting method of the parameters in the case of applying a SN transition FCLs to the feeders, or the busbar, or the lower voltage side of the transformers in the 6.6kV model distribution system. And we evaluate how to introduce the FCLs into it from the point of the requirements and the design. Finally, we suggest the hopeful installation of the FCLs into the distribution system.

  18. Current-voltage characteristics of hydrogen DC plasma torches with different sizes in an external axial magnetic field

    NASA Astrophysics Data System (ADS)

    Ma, Jie; Wen, Guang-Dong; Su, Bao-Gen; Yang, Yi-Wen; Ren, Qi-Long

    2015-06-01

    Current-voltage (I-V) characteristics of hydrogen DC plasma torches with different sizes in an external axial magnetic field under atmospheric pressure are reported. Three anodes with different diameters are adopted in a 50-kW torch: 25 mm, 30 mm, and 35 mm, respectively. Two different diameters of anodes, that is, 100 mm and 130 mm, are adopted in a 1-MW plasma torch. The arc voltage shows a negative trend with the increase of arc current under the operating regimes. On the contrary, arc voltage shows a positive trend as the flow rate of carrier gas increases, and a similar trend is found with increasing the external magnetic flux density. A similarity formula is constructed to correlate the experimental data of the torches mentioned above. Linear fitting shows that the Pearson correlation coefficient is 0.9958. Project supported by the Special Fund for Basic Scientific Research of Central Colleges, China (Grant No. 2012FZA4023).

  19. Design and Development of High Voltage Direct Current (DC) Sources for the Solar Array Module Plasma Interaction Experiment

    NASA Technical Reports Server (NTRS)

    Bibyk, Irene K.; Wald, Lawrence W.

    1995-01-01

    Two programmable, high voltage DC power supplies were developed as part of the flight electronics for the Solar Array Module Plasma Interaction Experiment (SAMPIE). SAMPIE's primary objectives were to study and characterize the high voltage arcing and parasitic current losses of various solar cells and metal samples within the space plasma of low earth orbit (LEO). High voltage arcing can cause large discontinuous changes in spacecraft potential which lead to damage of the power system materials and significant Electromagnetic Interference (EMI). Parasitic currents cause a change in floating potential which lead to reduced power efficiency. These primary SAMPIE objectives were accomplished by applying artificial biases across test samples over a voltage range from -600 VDC to +300 VDC. This paper chronicles the design, final development, and test of the two programmable high voltage sources for SAMPIE. The technical challenges to the design for these power supplies included vacuum, space plasma effects, thermal protection, Shuttle vibrations and accelerations.

  20. Analysis of Current Harmonics in 3kV DC Catenary Caused by Specific Current Harmonics of an Asynchronous Motor

    NASA Astrophysics Data System (ADS)

    Lewandowski, Mirosław

    2010-01-01

    The mathematical model of vehicle supply system as well as the mathematical model of main circuit of locomotive with asynchronous motors have been described in this article. The necessity of analysis of disturbances caused by distorted current run of drive motors emerged together with the introduction of high power vehicles with power electronic converters. Analysis of the compatibility of traction high current circuits with circuits of the signal and traffic control systems requires the knowledge of current spectrum in a catenary, which has been taken by a vehicle. The author has described the algebraic method of calculating of the spectrum amplitudes in a catenary. It does not require laborious and time-consuming simulations of a system, which considerably decreases preliminary costs of designation and dimensioning of a vehicle drive system.

  1. Leakage current and stability of acrylic elastomer subjected to high DC voltage

    NASA Astrophysics Data System (ADS)

    Hammami, S.; Jean-Mistral, C.; Jomni, F.; Gallot-Lavallée, O.; Rain, P.; Yangui, B.; Sylvestre, A.

    2015-04-01

    Dielectric elastomers such as 3M VHB4910 acrylate film have been widely used for electromechanical energy conversion such as actuators, sensors and generators, due to their lightweight, high efficiency, low cost and high energy density. Mechanical and electric properties of such materials have been deeply investigated according to various parameters (temperature, frequency, pre-stress, nature of the compliant electrodes…). Models integrating analytic laws deduced from experiments increase their accuracy. Nevertheless, leakage current and electrical breakdown reduce the efficiency and the lifetime of devices made with these polymers. These two major phenomena are not deeply investigated in the literature. Thus, this paper describes the current-voltage characteristics of acrylate 3M VHB4910 and investigates the stability of the current under high electric field (kV) for various temperatures (from 20°C to 80°C) and over short (300 s) and long (12h) periods. Experimental results show that, with gold electrodes at ambient temperature, the current decreases with time to a stable value corresponding to the conduction current. This decrease occurs during 6 hours, whereas in the literature values of current at short time (less than 1 hour) are generally reported. This decrease can be explained by relaxations mechanisms in the polymer. Schottky emission and Poole-Frenkel emission are both evaluated to explain the leakage current. It emerges from this study that the Schottky effect constitutes the main mechanism of electric current in the 3M VHB4910. For high temperatures, the steady state is reached quickly. To end, first results on the leakage current changes for pre-stretch VHB4910 complete this study.

  2. Negative huge magnetoresistance in high-mobility 2D electron gases: DC-current dependence

    NASA Astrophysics Data System (ADS)

    Iñarrea, J.; Bockhorn, L.; Haug, R. J.

    2016-07-01

    Two-dimensional electron gases with very high mobility show a huge or giant negative magnetoresistance at low temperatures and low magnetic fields. We present an experimental and theoretical work on the influence of the applied current on the negative huge magnetoresistance of these systems. We obtain an unexpected and strong nonlinear behavior consisting in an increase of the negative huge magnetoresistance with increasing current, in other words, for increasing current the magnetoresistance collapses at small magnetic fields. This nonlinearity is explained by the subtle interplay of elastic scattering within Landau levels and between Landau levels.

  3. Phase response curve for the ultradian rhythm of the lateral leaflets of Desmodium gyrans using DC current pulses.

    PubMed

    Sharma, V K; Jensen, C; Johnsson, A

    2001-01-01

    In the present study the leaf movement rhythm was perturbed by the application of DC current pulses (15 microA, 10 seconds, voltage applied: 10 V) to the upper part of the pulvinus, passing through the pulvinus and its stalk. The pulses were applied at four different positions of the leaflets: when the leaves were at the lowermost position, when moving up, at the uppermost position and when moving down. The pre-perturbed and the post-perturbed rhythms were compared. We found that the rhythms were shifted in phase and the phase shifts observed at the four different positions of the leaflets were significantly different in magnitude as well as direction. Furthermore, we could also observe phase advances, which is in contrast to an earlier finding. A phase response curve (PRC) was constructed to illustrate the sensitivity of the oscillating leaflet system to DC pulses. Substantial delays of about 50 s (as compared to the period of about 200 s) were obtained when pulses were administered at the lowermost position and when leaflet were moving upwards, while advances or no phase shifts were recorded in the uppermost position and when leaflet were moving down respectively. PMID:11302218

  4. Spin-Hall-Effect-Assisted Electroresistance in Antiferromagnets via 105 A/cm2 dc Current

    PubMed Central

    Han, Jiahao; Wang, Yuyan; Pan, Feng; Song, Cheng

    2016-01-01

    Antiferromagnet (AFM) spintronics with reduced electrical current is greatly expected to process information with high integration and low power consumption. In Pt/FeMn and Ta/FeMn hybrids, we observe significant resistance variation (up to 7% of the total resistance) manipulated by 105 A/cm2 dc current. We have excluded the contribution of isotropic structural effects, and confirmed the critical role of the spin Hall injection from Pt (or Ta) to FeMn. This electrical current-manipulated resistance (i.e. electroresistance) is proposed to be attributed to the spin-Hall-effect-induced spin-orbit torque in FeMn. Similar results have also been detected in plain IrMn films, where the charge current generates spin current via the spin Hall effect with the existence of Ir atoms. All the measurements are free from external magnetic fields and ferromagnets. Our findings present an interesting step towards high-efficiency spintronic devices. PMID:27546199

  5. Spin-Hall-Effect-Assisted Electroresistance in Antiferromagnets via 10(5) A/cm(2) dc Current.

    PubMed

    Han, Jiahao; Wang, Yuyan; Pan, Feng; Song, Cheng

    2016-01-01

    Antiferromagnet (AFM) spintronics with reduced electrical current is greatly expected to process information with high integration and low power consumption. In Pt/FeMn and Ta/FeMn hybrids, we observe significant resistance variation (up to 7% of the total resistance) manipulated by 10(5) A/cm(2) dc current. We have excluded the contribution of isotropic structural effects, and confirmed the critical role of the spin Hall injection from Pt (or Ta) to FeMn. This electrical current-manipulated resistance (i.e. electroresistance) is proposed to be attributed to the spin-Hall-effect-induced spin-orbit torque in FeMn. Similar results have also been detected in plain IrMn films, where the charge current generates spin current via the spin Hall effect with the existence of Ir atoms. All the measurements are free from external magnetic fields and ferromagnets. Our findings present an interesting step towards high-efficiency spintronic devices. PMID:27546199

  6. High-current dc power transmission in flexible RE-Ba2Cu3O7 - δ coated conductor cables

    NASA Astrophysics Data System (ADS)

    van der Laan, D. C.; Goodrich, L. F.; Haugan, T. J.

    2012-01-01

    Transmission cables made from high-temperature superconductors have been successfully demonstrated within the electric power grid. These cables carry an ac current of up to 3000 A in a much smaller cross-sectional area than conventional transmission lines, but they are not flexible enough for certain applications that involve very tight cable bends. Certain on-board Air Force applications require 5 MW of dc power transmission at 270 V and current of 18 500 A and would benefit from superconducting transmission in lightweight, flexible cables that would be cooled with helium gas down to about 55 K. To address these needs, we have constructed a 10 mm diameter RE-Ba2Cu3O7 - δ (RE = rare earth) coated conductor cable that is lighter and more flexible than the current generation of superconducting cables, and that has a critical current of 7561 A at 76 K. The cable is expected to have a critical current of more than 20 000 A at 55 K and therefore will likely exceed the requirements for 5 MW on-board power transmission. The cable consists of two electrically insulated phases that can be operated in different modes, which allows us to study the effect of self-field on the cable performance. Contribution of NIST, not subject to US copyright.

  7. Joint operation of the superconducting fault current limiter and magnetic energy storage system in an electric power network

    NASA Astrophysics Data System (ADS)

    Kopylov, S. I.; Balashov, N. N.; Ivanov, S. S.; Veselovsky, A. S.; Zhemerikin, V. D.

    2010-06-01

    An opportunity of using superconductors as active elements of electric power systems designed to control the electric power distribution, to enhance the systems operating modes and to limit fault currents, was very attractive for investigators for a long time. In this paper, is considered an opportunity to enhance the electric power systems with the aid of superconducting magnetic energy storage systems (SMES) and superconducting fault current limiters (SFCL) operating together. It has been shown that the joint operation of both these superconducting devices allows additional varying of their parameters, what in turn gives a further opportunity to reduce their mass and dimensions and consequently the costs. There had been also shown an additional advantage of the SMES and SFCL joint operation consisting in that they ensure a more effective protection for a power system, preventing its uncontrolled load-off and subsequent acceleration up to the inaccessible rotation speed.

  8. Quench behavior of Sr0.6K0.4Fe2As2/Ag tapes with AC and DC transport currents at different temperature

    NASA Astrophysics Data System (ADS)

    Liu, Qi; Zhang, Guomin; Yang, Hua; Li, Zhenming; Liu, Wei; Jing, Liwei; Yu, Hui; Liu, Guole

    2016-09-01

    In applications, superconducting wires may carry AC or DC transport current. Thus, it is important to understand the behavior of normal zone propagation in conductors and magnets under different current conditions in order to develop an effective quench protection system. In this paper, quench behavior of Ag sheathed Sr0.6K0.4Fe2As2 (Sr-122 in the family of iron-based superconductor) tapes with AC and DC transport current is reported. The measurements are performed as a function of different temperature (20 K-30 K), varying transport current and operating frequency (50 Hz-250 Hz). The focus of the research is the minimum quench energy (MQE), the normal zone propagation velocity (NZPV) and the comparison of the related results with AC and DC transport current.

  9. The technique of entropy optimization in motor current signature analysis and its application in the fault diagnosis of gear transmission

    NASA Astrophysics Data System (ADS)

    Chen, Xiaoguang; Liang, Lin; Liu, Fei; Xu, Guanghua; Luo, Ailing; Zhang, Sicong

    2012-05-01

    Nowadays, Motor Current Signature Analysis (MCSA) is widely used in the fault diagnosis and condition monitoring of machine tools. However, although the current signal has lower SNR (Signal Noise Ratio), it is difficult to identify the feature frequencies of machine tools from complex current spectrum that the feature frequencies are often dense and overlapping by traditional signal processing method such as FFT transformation. With the study in the Motor Current Signature Analysis (MCSA), it is found that the entropy is of importance for frequency identification, which is associated with the probability distribution of any random variable. Therefore, it plays an important role in the signal processing. In order to solve the problem that the feature frequencies are difficult to be identified, an entropy optimization technique based on motor current signal is presented in this paper for extracting the typical feature frequencies of machine tools which can effectively suppress the disturbances. Some simulated current signals were made by MATLAB, and a current signal was obtained from a complex gearbox of an iron works made in Luxembourg. In diagnosis the MCSA is combined with entropy optimization. Both simulated and experimental results show that this technique is efficient, accurate and reliable enough to extract the feature frequencies of current signal, which provides a new strategy for the fault diagnosis and the condition monitoring of machine tools.

  10. Regulated-current dc power supply for gaseous-discharge lamps

    NASA Technical Reports Server (NTRS)

    Freeman, W.; Huguenin, D.

    1970-01-01

    Controlled current source having a high output resistance feeds continuous-flow hydrogen lamps in vacuum-ultraviolet photometric equipment. The power supply, also used with low-pressure sealed lamps, has a short recovery time and smooth regulation without overshoot.

  11. DC BUFFERING AND FLOATING CURRENT FOR A HIGH VOLTAGE IMB APPLICATION

    SciTech Connect

    J.L. Morrison

    2014-08-01

    An interface technique for the latest generation of the Impedance Measurement Box (IMB) has been conceived to enable measurement of impedance spectra for battery modules up to 300V. A 300V capable or higher IMB is an enabling technology for in-situ diagnostics within electric vehicle charging stations or battery back-ups within power distribution sub-stations. It is possible that the existing IMB can be adapted via a 300V interface module to a test battery with voltage significantly greater than 50V. Recently a new concept was conceived for the calibration, algorithm and electronics of the IMB. That algorithm and calibration for that concept have been physically validated. The principal feature of the new electronics is the floating current source excitation of the battery under test. The single ended current excitation of the battery under test, used in the 50V IMB, requires that the negative terminal of the test battery must be the analog ground for the IMB. The new floating current technique allows the test battery to be fully high impedance isolated for a measurement. That isolation will improve IMB noise immunity and enable interrogation of cells internal to a battery module. All these techniques still use the same rapid concept for impedance measurement with the IMB. The purpose of this disclosure is to provide an overview of the analytical validation for three concepts to interface the floating current excitation to a high voltage battery. Recursive simulation models were used in different test scenarios to validate the various new concepts. The analysis will show that it is possible to interface the floating signal current to obtain an impedance measurement on a high voltage test battery. Additionally, the analysis will investigate stress seen by electronics while testing a 300V battery.

  12. Near DC eddy current measurement of aluminum multilayers using MR sensors and commodity low-cost computer technology

    NASA Astrophysics Data System (ADS)

    Perry, Alexander R.

    2002-06-01

    Low Frequency Eddy Current (EC) probes are capable of measurement from 5 MHz down to DC through the use of Magnetoresistive (MR) sensors. Choosing components with appropriate electrical specifications allows them to be matched to the power and impedance characteristics of standard computer connectors. This permits direct attachment of the probe to inexpensive computers, thereby eliminating external power supplies, amplifiers and modulators that have heretofore precluded very low system purchase prices. Such price reduction is key to increased market penetration in General Aviation maintenance and consequent reduction in recurring costs. This paper examines our computer software CANDETECT, which implements this approach and permits effective probe operation. Results are presented to show the intrinsic sensitivity of the software and demonstrate its practical performance when seeking cracks in the underside of a thick aluminum multilayer structure. The majority of the General Aviation light aircraft fleet uses rivets and screws to attach sheet aluminum skin to the airframe, resulting in similar multilayer lap joints.

  13. Radial Broadening of DC potential structures in front of ICRF antennas by transverse exchange of RF currents

    SciTech Connect

    Faudot, E.; Heuraux, S.; Colas, L.; Gunn, J.

    2009-11-26

    Measurements show that the vicinity of powered Ion Cyclotron Range of Frequency (ICRF) antennae is biased positively with respect to its environment. This is attributed to RF-sheaths. The radial penetration of DC potentials into Tokamak SOL determines the power deposition on the walls and especially on the antenna structure, which is a key point for long time clean discharges. Within independent flux tube models of RF-sheath rectification the radial penetration of DC potentials is determined by the skin depth x{sub 0} = c/{omega}{sub pe} for the slow wave. When self-consistent exchanges of transverse RF currents are allowed between neighboring flux tubes, such a structure can be broadened radially up to a characteristic transverse length L. Broadening arises as soon as L>r{sub 0}. A linear modeling gives a first evaluation of the theoretical length L{approx_equal}(L{sub parallel} {rho}{sub ci}/){sup 1/2}. Within the 'flute assumption' it scales with the length L{sub parallel} of open flux tubes and the ion Larmor radius {rho}{sub ci}. This has been confirmed by the SEM code which takes into account non-linear rectifications. Applying our model to several potential maps generated by an ITER antenna, it comes out that L ranges between 1 and 10 cm depending on local L{sub parallel} and on typical ITER plasma parameters. Langmuir probe measurements on Tore Supra suggest that the broadening is lower than predicted by the code, which supposes that currents do not occur all over the parallel magnetic lines but on a fraction of it.

  14. DC resistance comparison between a current comparator bridge and the quantum Hall system at Inmetro

    NASA Astrophysics Data System (ADS)

    da Silva, M. C.; Carvalho, H. R.; Vasconcellos, R. T. B.

    2016-07-01

    This paper presents a comparison results between the Quantum Hall System (QHS) under development at the Quantum Electrical Metrology Laboratory (Lameq) and the current comparator calibration system, traceable to the Bureau International des Poids et Mesures (BIPM), at the Electrical Standardization Metrology Laboratory (Lampe), both part of the Electrical Metrology Division, at Inmetro. Comparisons were performed with 1 Ω, 10 Ω, 100 Ω, 1 kΩ and 10 kΩ resistors. The results obtained over two years of work are presented here, showing that the comparison contributed to improve the calibration systems of both Lampe and Lameq.

  15. Effects of energy distribution of interface traps on recombination dc current-voltage line shape

    NASA Astrophysics Data System (ADS)

    Chen, Zuhui; Jie, Bin B.; Sah, Chih-Tang

    2006-12-01

    The effects of energy distributions of Si /SiO2 interface traps in the energy gap of oxidized silicon on the current versus voltage line shape of the electron-hole recombination current are analyzed using the steady-state Shockley-Read-Hall kinetics. Slater's [Insulators, Semiconductors and Metals; Quantum Theory of Molecules and Solids (McGraw-Hill, New York, 1967)] localized bulk perturbation theory applied by us to the interface anticipates U-shaped energy distributions of the density of neutral electron and hole interface traps from random variations of the Si:Si and Si:O bond angles and lengths. Conservation in dissipative transition energy anticipates the rate of electron capture into neutral electron trap to be faster for electron trap energy levels nearer the conduction band edge, and similarly, the rate of hole capture into neutral hole trap to be faster for hole trap energy levels nearer the valence band edge. Line shape broadening is analyzed for discrete and U-shaped energy distributions of interface trap energy levels. The broadened line shapes observed in past experiments, previously attributed to spatial variations of surface dopant impurity concentrations, could also arise from energy distributions of interface trap energy levels.

  16. Solid-State Fault Current Limiter Development : Design and Testing Update of a 15kV SSCL Power Stack

    SciTech Connect

    Dr. Ram Adapa; Mr. Dante Piccone

    2012-04-30

    ABSTRACT The Solid-State Fault Current Limiter (SSCL) is a promising technology that can be applied to utility power delivery systems to address the problem of increasing fault currents associated with load growth. As demand continues to grow, more power is added to utility system either by increasing generator capacity or by adding distributed generators, resulting in higher available fault currents, often beyond the capabilities of the present infrastructure. The SSCL is power-electronics based equipment designed to work with the present utility system to address this problem. The SSCL monitors the line current and dynamically inserts additional impedance into the line in the event of a fault being detected. The SSCL is based on a modular design and can be configured for 5kV through 69kV systems at nominal current ratings of 1000A to 4000A. Results and Findings This report provides the final test results on the development of 15kV class SSCL single phase power stack. The scope of work included the design of the modular standard building block sub-assemblies, the design and manufacture of the power stack and the testing of the power stack for the key functional tests of continuous current capability and fault current limiting action. Challenges and Objectives Solid-State Current Limiter technology impacts a wide spectrum of utility engineering and operating personnel. It addresses the problems associated with load growth both at Transmission and Distribution class networks. The design concept is pioneering in terms of developing the most efficient and compact power electronics equipment for utility use. The initial test results of the standard building blocks are promising. The independent laboratory tests of the power stack are promising. However the complete 3 phase system needs rigorous testing for performance and reliability. Applications, Values, and Use The SSCL is an intelligent power-electronics device which is modular in design and can provide current

  17. Development of 6.6 kV/600 A superconducting fault current limiter using coated conductors

    NASA Astrophysics Data System (ADS)

    Yazawa, T.; Koyanagi, K.; Takahashi, M.; Toba, K.; Takigami, H.; Urata, M.; Iijima, Y.; Saitoh, T.; Amemiya, N.; Shiohara, Y.; Ito, T.

    2009-10-01

    As one of the programs in the Ministry of Economy, Trade and Industry (METI) project regarding R&D on superconducting coated conductor, three-phase superconducting fault current limiter (SFCL) for 6.6 kV application was developed and successfully tested. The developed SFCL was mainly comprised three-phase set of current limiting coils installed in a sub-cooled nitrogen cryostat with a GM cryocooler, circuit breakers and a sequence circuit. The whole system was installed in a cubicle. Two tapes of coated conductor were wound in parallel in each coil to obtain the rated current of 72 A rms. After developing the whole SFCL system, short circuit experiments were implemented with a short circuit generator. In a three-line ground fault test, the SFCL successfully restricted the prospected short circuit current over 1.6 kA to about 800 A by the applied voltage of 6.6 kV. The SFCL was installed in a user field and connected with a gas engine generator, followed by a consecutive operation. In this program, 600 A class FCL coil, with which four coated conductor tapes were wound, was also developed. The coil showed sufficiently low AC loss at the rated current. With these results, the program attained the planned target of the fundamentals for the 6.6 kV/600 A SFCL.

  18. Development of an in situ calibration method for current-to-voltage converters for high-accuracy SI-traceable low dc current measurements

    NASA Astrophysics Data System (ADS)

    Eppeldauer, George P.; Yoon, Howard W.; Jarrett, Dean G.; Larason, Thomas C.

    2013-10-01

    For photocurrent measurements with low uncertainties, wide dynamic range reference current-to-voltage converters and a new converter calibration method have been developed at the National Institute of Standards and Technology (NIST). The high-feedback resistors of a reference converter were in situ calibrated on a high-resistivity, printed circuit board placed in an electrically shielded box electrically isolated from the operational amplifier using jumpers. The feedback resistors, prior to their installation, were characterized, selected and heat treated. The circuit board was cleaned with solvents, and the in situ resistors were calibrated using measurement systems for 10 kΩ to 10 GΩ standard resistors. We demonstrate that dc currents from 1 nA to 100 µA can be measured with uncertainties of 55 × 10-6 (k = 2) or lower, which are lower in uncertainties than any commercial device by factors of 10 to 30 at the same current setting. The internal (NIST) validations of the reference converter are described.

  19. Detection and characterization of stacking faults by light beam induced current mapping and scanning infrared microscopy in silicon

    NASA Astrophysics Data System (ADS)

    Vève-Fossati, C.; Martinuzzi, S.

    1998-08-01

    Non destructive techniques like scanning infrared microscopy and light beam induced current mapping are used to reveal the presence of stacking faults in heat treated Czochralski grown silicon wafers. In oxidized or contaminated samples, scanning infrared microscopy reveals that stacking faults grow around oxygen precipitates. This could be due to an aggregation of silicon self-interstitials emitted by the growing precipitates in the (111) plane. Light beam induced current maps show that the dislocations which surround the stacking faults are the main source of recombination centers, especially when they are decorated by a fast diffuser like copper. Des techniques non destructives telles que la microscopie infrarouge à balayage et la cartographie de photocourant induit par un spot lumineux ont été utilisées pour révéler la présence de fautes d'empilement après traitements thermiques, dans des plaquettes de silicium préparées par tirage Czochralski. Dans des échantillons oxydés ou contaminés, la microscopie infrarouge à balayage révèle des fautes d'empilement qui se développent autour des précipités d'oxygène. Cela peut être dû à la formation d'un agglomérat d'auto-interstitiels de silicium émis par la croissance des précipités dans les plans (111). Les cartographies de photocourant montrent que les dislocations qui entourent les fautes d'empilement sont la principale source de centres de recombinaison, et cela tout particulièrement quand ces fautes sont décorées par un diffuseur rapide tel que le cuivre.

  20. Fault-tolerant three-level inverter

    DOEpatents

    Edwards, John; Xu, Longya; Bhargava, Brij B.

    2006-12-05

    A method for driving a neutral point clamped three-level inverter is provided. In one exemplary embodiment, DC current is received at a neutral point-clamped three-level inverter. The inverter has a plurality of nodes including first, second and third output nodes. The inverter also has a plurality of switches. Faults are checked for in the inverter and predetermined switches are automatically activated responsive to a detected fault such that three-phase electrical power is provided at the output nodes.

  1. Quench distribution in superconducting fault current limiters at various voltages H.-R. Kim, H.-S. Choi,

    NASA Astrophysics Data System (ADS)

    Kim, Hye-Rim; Choi, Hyo-Sang; Lim, Hae-Ryong; Kim, In-Seon; Hyun, Ok-Bae

    2001-04-01

    We investigated the quench distribution in resistive superconducting fault current limiters (SFCLs) based on YBa 2Cu 3O 7 thin films at various source voltages. The film was grown on sapphire substrates, coated in situ with a gold layer and patterned into pairs of 1 mm wide and 26 cm long meander lines by photolithography. Fabricated limiters were tested with simulated AC fault currents. The resistivity of Au/YBa 2Cu 3O 7 meander lines was relatively uniform in the center stripes at all voltages. This result is important because it means the dissipated power was distributed relatively evenly among most of stripes. The resistivity of the stripes near electrodes was significantly lower than that of center stripes, reflecting the cooling power of the electrode area. The difference increased with the source voltage. These results could be explained quantitatively in terms of heat transfer from limiter meander lines to surroundings. Data fit reasonably well to the solution of heat balance equation obtained with appropriate boundary conditions.

  2. Application of a combined superconducting fault current limiter and STATCOM to enhancement of power system transient stability

    NASA Astrophysics Data System (ADS)

    Mahdad, Belkacem; Srairi, K.

    2013-12-01

    Stable and reliable operation of the power system network is dependent on the dynamic equilibrium between energy production and power demand under large disturbance such as short circuit or important line tripping. This paper investigates the use of combined model based superconducting fault current limiter (SFCL) and shunt FACTS Controller (STATCOM) for assessing the transient stability of a power system considering the automatic voltage regulator. The combined model located at a specified branch based on voltage stability index using continuation power flow. The main role of the proposed combined model is to achieve simultaneously a flexible control of reactive power using STATCOM Controller and to reduce fault current using superconducting technology based SFCL. The proposed combined model has been successfully adapted within the transient stability program and applied to enhance the transient power system stability of the WSCC9-Bus system. Critical clearing time (CCT) has been used as an index to evaluate and validate the contribution of the proposed coordinated Controller. Simulation results confirm the effectiveness and perspective of this combined Controller to enhance the dynamic power system performances.

  3. Experimental studies of the quench behaviour of MgB2 superconducting wires for fault current limiter applications

    NASA Astrophysics Data System (ADS)

    Ye, Lin; Majoros, M.; Campbell, A. M.; Coombs, T.; Astill, D.; Harrison, S.; Husband, M.; Rindfleisch, M.; Tomsic, M.

    2007-07-01

    Various MgB2 wires with different sheath materials provided by Hyper Tech Research Inc., have been tested in the superconducting fault current limiter (SFCL) desktop tester at 24-26 K in a self-field. Samples 1 and 2 are similarly fabricated monofilamentary MgB2 wires with a sheath of CuNi, except that sample 2 is doped with SiC and Mg addition. Sample 3 is a CuNi sheathed multifilamentary wire with Cu stabilization and Mg addition. All the samples with Nb barriers have the same diameter of 0.83 mm and superconducting fractions ranging from 15% to 27% of the total cross section. They were heat-treated at temperatures of 700 °C for a hold time of 20-40 min. Current limiting properties of MgB2 wires subjected to pulse overcurrents have been experimentally investigated in an AC environment in the self-field at 50 Hz. The quench currents extracted from the pulse measurements were in a range of 200-328 A for different samples, corresponding to an average engineering critical current density (Je) of around 4.8 × 104 A cm-2 at 25 K in the self-field, based on the 1 µV cm-1 criterion. This work is intended to compare the quench behaviour in the Nb-barrier monofilamentary and multifilamentary MgB2 wires with CuNi and Cu/CuNi sheaths. The experimental results can be applied to the design of fault current limiter applications based on MgB2 wires. This work is supported by Rolls-Royce plc and the UK Department of Trade and Industry (DTI).

  4. Specific Intensity Direct Current (DC) Electric Field Improves Neural Stem Cell Migration and Enhances Differentiation towards βIII-Tubulin+ Neurons

    PubMed Central

    Zhao, Huiping; Steiger, Amanda; Nohner, Mitch; Ye, Hui

    2015-01-01

    Control of stem cell migration and differentiation is vital for efficient stem cell therapy. Literature reporting electric field–guided migration and differentiation is emerging. However, it is unknown if a field that causes cell migration is also capable of guiding cell differentiation—and the mechanisms for these processes remain unclear. Here, we report that a 115 V/m direct current (DC) electric field can induce directional migration of neural precursor cells (NPCs). Whole cell patching revealed that the cell membrane depolarized in the electric field, and buffering of extracellular calcium via EGTA prevented cell migration under these conditions. Immunocytochemical staining indicated that the same electric intensity could also be used to enhance differentiation and increase the percentage of cell differentiation into neurons, but not astrocytes and oligodendrocytes. The results indicate that DC electric field of this specific intensity is capable of promoting cell directional migration and orchestrating functional differentiation, suggestively mediated by calcium influx during DC field exposure. PMID:26068466

  5. Soft-Fault Detection Technologies Developed for Electrical Power Systems

    NASA Technical Reports Server (NTRS)

    Button, Robert M.

    2004-01-01

    The NASA Glenn Research Center, partner universities, and defense contractors are working to develop intelligent power management and distribution (PMAD) technologies for future spacecraft and launch vehicles. The goals are to provide higher performance (efficiency, transient response, and stability), higher fault tolerance, and higher reliability through the application of digital control and communication technologies. It is also expected that these technologies will eventually reduce the design, development, manufacturing, and integration costs for large, electrical power systems for space vehicles. The main focus of this research has been to incorporate digital control, communications, and intelligent algorithms into power electronic devices such as direct-current to direct-current (dc-dc) converters and protective switchgear. These technologies, in turn, will enable revolutionary changes in the way electrical power systems are designed, developed, configured, and integrated in aerospace vehicles and satellites. Initial successes in integrating modern, digital controllers have proven that transient response performance can be improved using advanced nonlinear control algorithms. One technology being developed includes the detection of "soft faults," those not typically covered by current systems in use today. Soft faults include arcing faults, corona discharge faults, and undetected leakage currents. Using digital control and advanced signal analysis algorithms, we have shown that it is possible to reliably detect arcing faults in high-voltage dc power distribution systems (see the preceding photograph). Another research effort has shown that low-level leakage faults and cable degradation can be detected by analyzing power system parameters over time. This additional fault detection capability will result in higher reliability for long-lived power systems such as reusable launch vehicles and space exploration missions.

  6. Control algorithm for the inverter fed induction motor drive with DC current feedback loop based on principles of the vector control

    SciTech Connect

    Vuckovic, V.; Vukosavic, S. )

    1992-01-01

    This paper brings out a control algorithm for VSI fed induction motor drives based on the converter DC link current feedback. It is shown that the speed and flux can be controlled over the wide speed and load range quite satisfactorily for simpler drives. The base commands of both the inverter voltage and frequency are proportional to the reference speed, but each of them is further modified by the signals derived from the DC current sensor. The algorithm is based on the equations well known from the vector control theory, and is aimed to obtain the constant rotor flux and proportionality between the electrical torque, the slip frequency and the active component of the stator current. In this way, the problems of slip compensation, Ri compensation and correction of U/f characteristics are solved in the same time. Analytical considerations and computer simulations of the proposed control structure are in close agreement with the experimental results measured on a prototype drive.

  7. Origin of dc voltage in type II superconducting flux pumps: field, field rate of change, and current density dependence of resistivity

    NASA Astrophysics Data System (ADS)

    Geng, J.; Matsuda, K.; Fu, L.; Fagnard, J.-F.; Zhang, H.; Zhang, X.; Shen, B.; Dong, Q.; Baghdadi, M.; Coombs, T. A.

    2016-03-01

    Superconducting flux pumps are the kind of devices which can generate direct current into superconducting circuit using external magnetic field. The key point is how to induce a dc voltage across the superconducting load by ac fields. Giaever (1966 IEEE Spectr. 3 117) pointed out flux motion in superconductors will induce a dc voltage, and demonstrated a rectifier model which depended on breaking superconductivity. van de Klundert et al (1981 Cryogenics 21 195, 267) in their review(s) described various configurations for flux pumps all of which relied on inducing the normal state in at least part of the superconductor. In this letter, following their work, we reveal that a variation in the resistivity of type II superconductors is sufficient to induce a dc voltage in flux pumps and it is not necessary to break superconductivity. This variation in resistivity is due to the fact that flux flow is influenced by current density, field intensity, and field rate of change. We propose a general circuit analogy for travelling wave flux pumps, and provide a mathematical analysis to explain the dc voltage. Several existing superconducting flux pumps which rely on the use of a travelling magnetic wave can be explained using the analysis enclosed. This work can also throw light on the design and optimization of flux pumps.

  8. Earthquake nucleation on faults with rate-and state-dependent strength

    USGS Publications Warehouse

    Dieterich, J.H.

    1992-01-01

    Dieterich, J.H., 1992. Earthquake nucleation on faults with rate- and state-dependent strength. In: T. Mikumo, K. Aki, M. Ohnaka, L.J. Ruff and P.K.P. Spudich (Editors), Earthquake Source Physics and Earthquake Precursors. Tectonophysics, 211: 115-134. Faults with rate- and state-dependent constitutive properties reproduce a range of observed fault slip phenomena including spontaneous nucleation of slip instabilities at stresses above some critical stress level and recovery of strength following slip instability. Calculations with a plane-strain fault model with spatially varying properties demonstrate that accelerating slip precedes instability and becomes localized to a fault patch. The dimensions of the fault patch follow scaling relations for the minimum critical length for unstable fault slip. The critical length is a function of normal stress, loading conditions and constitutive parameters which include Dc, the characteristic slip distance. If slip starts on a patch that exceeds the critical size, the length of the rapidly accelerating zone tends to shrink to the characteristic size as the time of instability approaches. Solutions have been obtained for a uniform, fixed-patch model that are in good agreement with results from the plane-strain model. Over a wide range of conditions, above the steady-state stress, the logarithm of the time to instability linearly decreases as the initial stress increases. Because nucleation patch length and premonitory displacement are proportional to Dc, the moment of premonitory slip scales by D3c. The scaling of Dc is currently an open question. Unless Dc for earthquake faults is significantly greater than that observed on laboratory faults, premonitory strain arising from the nucleation process for earthquakes may by too small to detect using current observation methods. Excluding the possibility that Dc in the nucleation zone controls the magnitude of the subsequent earthquake, then the source dimensions of the smallest

  9. Fault model development for fault tolerant VLSI design

    NASA Astrophysics Data System (ADS)

    Hartmann, C. R.; Lala, P. K.; Ali, A. M.; Visweswaran, G. S.; Ganguly, S.

    1988-05-01

    Fault models provide systematic and precise representations of physical defects in microcircuits in a form suitable for simulation and test generation. The current difficulty in testing VLSI circuits can be attributed to the tremendous increase in design complexity and the inappropriateness of traditional stuck-at fault models. This report develops fault models for three different types of common defects that are not accurately represented by the stuck-at fault model. The faults examined in this report are: bridging faults, transistor stuck-open faults, and transient faults caused by alpha particle radiation. A generalized fault model could not be developed for the three fault types. However, microcircuit behavior and fault detection strategies are described for the bridging, transistor stuck-open, and transient (alpha particle strike) faults. The results of this study can be applied to the simulation and analysis of faults in fault tolerant VLSI circuits.

  10. Analysis of the influence of the normal zone propagation velocity on the design of resistive fault current limiters

    NASA Astrophysics Data System (ADS)

    Colangelo, Daniele; Dutoit, Bertrand

    2014-12-01

    Commercial high-temperature superconducting coated conductors (HTS-CCs) have low thermal diffusivity and nonuniform critical current density. These two factors lead commercial HTS-CCs to a partial quench when they are subjected to a transport current around their average critical current ({{I}c.av}). The consequence is the appearance of localized resistive zones, and a high risk of thermal runaway can arise when HTS-CCs are used for resistive fault current limiter (RFCL) purposes. The enhancement of the normal zone propagation velocity (NZPV) of HTS-CCs is a desirable solution for achieving sufficient thermal stability while keeping the cost of RFCLs under an acceptable threshold. Even though in recent years, several valid methods to increase the NZPV have been proposed, their impact on the design of RFCLs is not clear. For this reason, we developed a one-dimensional numerical model that enables us to simulate HTS-CCs with enhanced NZPV and to study the limitation performance of a HTS-CC-based RFCL in real operating conditions. Our preliminary re sults demonstrate that the NZPV enhancement can effectively limit the needed amount of HTS-CCs with important economic benefits for the design of RFCLs.

  11. Fault diagnosis

    NASA Technical Reports Server (NTRS)

    Abbott, Kathy

    1990-01-01

    The objective of the research in this area of fault management is to develop and implement a decision aiding concept for diagnosing faults, especially faults which are difficult for pilots to identify, and to develop methods for presenting the diagnosis information to the flight crew in a timely and comprehensible manner. The requirements for the diagnosis concept were identified by interviewing pilots, analyzing actual incident and accident cases, and examining psychology literature on how humans perform diagnosis. The diagnosis decision aiding concept developed based on those requirements takes abnormal sensor readings as input, as identified by a fault monitor. Based on these abnormal sensor readings, the diagnosis concept identifies the cause or source of the fault and all components affected by the fault. This concept was implemented for diagnosis of aircraft propulsion and hydraulic subsystems in a computer program called Draphys (Diagnostic Reasoning About Physical Systems). Draphys is unique in two important ways. First, it uses models of both functional and physical relationships in the subsystems. Using both models enables the diagnostic reasoning to identify the fault propagation as the faulted system continues to operate, and to diagnose physical damage. Draphys also reasons about behavior of the faulted system over time, to eliminate possibilities as more information becomes available, and to update the system status as more components are affected by the fault. The crew interface research is examining display issues associated with presenting diagnosis information to the flight crew. One study examined issues for presenting system status information. One lesson learned from that study was that pilots found fault situations to be more complex if they involved multiple subsystems. Another was pilots could identify the faulted systems more quickly if the system status was presented in pictorial or text format. Another study is currently under way to

  12. Method and apparatus for generating motor current spectra to enhance motor system fault detection

    DOEpatents

    Linehan, Daniel J.; Bunch, Stanley L.; Lyster, Carl T.

    1995-01-01

    A method and circuitry for sampling periodic amplitude modulations in a nonstationary periodic carrier wave to determine frequencies in the amplitude modulations. The method and circuit are described in terms of an improved motor current signature analysis. The method insures that the sampled data set contains an exact whole number of carrier wave cycles by defining the rate at which samples of motor current data are collected. The circuitry insures that a sampled data set containing stationary carrier waves is recreated from the analog motor current signal containing nonstationary carrier waves by conditioning the actual sampling rate to adjust with the frequency variations in the carrier wave. After the sampled data is transformed to the frequency domain via the Discrete Fourier Transform, the frequency distribution in the discrete spectra of those components due to the carrier wave and its harmonics will be minimized so that signals of interest are more easily analyzed.

  13. Method and apparatus for generating motor current spectra to enhance motor system fault detection

    DOEpatents

    Linehan, D.J.; Bunch, S.L.; Lyster, C.T.

    1995-10-24

    A method and circuitry are disclosed for sampling periodic amplitude modulations in a nonstationary periodic carrier wave to determine frequencies in the amplitude modulations. The method and circuit are described in terms of an improved motor current signature analysis. The method insures that the sampled data set contains an exact whole number of carrier wave cycles by defining the rate at which samples of motor current data are collected. The circuitry insures that a sampled data set containing stationary carrier waves is recreated from the analog motor current signal containing nonstationary carrier waves by conditioning the actual sampling rate to adjust with the frequency variations in the carrier wave. After the sampled data is transformed to the frequency domain via the Discrete Fourier Transform, the frequency distribution in the discrete spectra of those components due to the carrier wave and its harmonics will be minimized so that signals of interest are more easily analyzed. 29 figs.

  14. Ground Fault Diagnosctic System for PEP-II

    NASA Astrophysics Data System (ADS)

    James, Glen; Himel, Tom; Johnson, Ralph

    1997-05-01

    This paper describes a diagnostic system designed into the String Magnet Power Conversion System that localizes magnet or cable ground faults in the PEP-II rings. This system provides online diagnostics that allow the operator/maintenance personnel to identify the magnet string that has the ground fault and the region in the ring where the ground fault exists. Furthermore, it is our goal to identify within 2 adjacent magnets where this fault exists. The system utilizes the existing PEP-II control system with transient digitizers, ADCs to monitor voltages and currents from the DC/DC converters and the voltage across the soft ground resistor at each bulk power supply. Also, the magnet string voltages are monitored in six locations around the ring to provide an adaptive model of the voltage distribution for each for each magnet string. These signals are utilized in a ground fault location algorithm that identifies and displays the magnet string and specific magnet candidate with the ground fault, on the operators console. Wave forms taken during the fault event are also available for examination at the operators console.

  15. Microwave polarization angle study of the radiation-induced magnetoresistance oscillations in the GaAs/AlGaAs 2D electron system under dc current bias

    NASA Astrophysics Data System (ADS)

    Iqbal, Muhammad-Zahir; Liu, Han-Chun; Heimbeck, Martin S.; Everitt, Henry O.; Wegscheider, Werner; Mani, Ramesh G.

    Microwave-induced magnetoresistance oscillations followed by the vanishing resistance states are a prime representation of non-equilibrium transport phenomena in two-dimensional electron systems (2DES). The effect of a dc current bias on the nonlinear response of 2DES with microwave polarization angle under magnetic field is a subject of interest. Here, we have studied the effect of various dc current bias on microwave radiation-induced magnetoresistance oscillations in a high mobility 2DES. Further, we systematically investigate the effect of the microwave polarization angle on the magneto-resistance oscillations at two different frequencies 152.78 GHz and 185.76 GHz. This study aims to better understand the effects of both dc current and microwave polarization angle in the GaAs/AlGaAs system, both of which modify the observed magneto-transport properties DOE-BES, Mat'l. Sci. & Eng. Div., DE-SC0001762; ARO W911NF-14-2-0076; ARO W911NF-15-1-0433.

  16. Charge Lifetime Measurements at High Average Current Using a K{sub 2}CsSb Photocathode inside a DC High Voltage Photogun

    SciTech Connect

    Mammei, Russell; Feingold, Joshua; Adderley, Philip; Clark, James; Covert, Steven; Grames, Joseph; Hansknecht, John; Machie, Danny; Poelker, Benard; Rao, Triveni; Smedley, John; Walsh, John; McCarter, James; Ruiz-Oses, M

    2013-03-01

    Two K{sub 2}CsSb photocathodes were manufactured at Brookhaven National Lab and delivered to Jefferson Lab within a compact vacuum apparatus at pressure ~ 10{sup -11} Torr. These photocathodes were evaluated using a dc high voltage photogun biased at voltages up to 200 kV, and illuminated with laser light at wavelengths 440 or 532 nm, to generate dc electron beams at currents up to 20 mA. Some conditions produced exceptionally large photocathode charge lifetimes, without measurable quantum efficiency (QE) decay, even from the center of the photocathode where operation using GaAs photocathodes is precluded due to ion bombardment. Under other conditions the charge lifetime was poor, suggesting a complex QE decay mechanism likely related to chemistry and localized heating via the laser beam. Following beam delivery, the photocathodes were evaluated using a scanning electron microscope with energy dispersive x-ray spectroscopy capability, to determine surface morphology and chemical composition.

  17. Determination of torque speed current characteristics of a brushless DC motor by utilizing back-EMF of non-energized phase

    NASA Astrophysics Data System (ADS)

    Jang, G. H.; Yeom, J. H.; Kim, M. G.

    2007-03-01

    This paper presents a method to determine the torque constant and the torque-speed-current characteristics of a brushless DC (BLDC) motor by utilizing back-EMF variation of nonenergized phase. It also develops a BLDC motor controller with a digital signal processor (DSP) to monitor its current, voltage and speed in real time. Torque-speed-current characteristics of a BLDC motor are determined by using the proposed method and the developed controller. They are compared with the torque-speed-current characteristics measured by dynamometer experimentally. This research shows that the proposed method is an effective method to determine the torque constant and the torque-speed-current characteristics of the BLDC motor without using dynamometer.

  18. Angular Dependence of Transport AC Losses in Superconducting Wire with Position-Dependent Critical Current Density in a DC Magnetic Field

    NASA Astrophysics Data System (ADS)

    Su, Xing-liang; Xiong, Li-ting; Gao, Yuan-wen; Zhou, You-he

    2013-07-01

    Transport AC losses play a very important role in high temperature superconductors (HTSs), which usually carry AC transport current under applied magnetic field in typical application-like conditions. In this paper, we propose the analytical formula for transport AC losses in HTS wire by considering critical current density of both inhomogeneous and anisotropic field dependent. The angular dependence of critical current density is described by effective mass theory, and the HTS wire has inhomogeneous distribution cross-section of critical current density. We calculate the angular dependence of normalized AC losses under different DC applied magnetic fields. The numerical results of this formula agree well with the experiment data and are better than the results of Norris formula. This analytical formula can explain the deviation of experimental transport current losses from the Norris formula and apply to calculate transport AC losses in realistic practical condition.

  19. Detection of DC currents and resistance measurements in longitudinal spin Seebeck effect experiments on Pt/YIG and Pt/NFO

    NASA Astrophysics Data System (ADS)

    Meier, Daniel; Kuschel, Timo; Meyer, Sibylle; Goennenwein, Sebastian T. B.; Shen, Liming; Gupta, Arunava; Schmalhorst, Jan-Michael; Reiss, Günter

    2016-05-01

    In this work we investigated thin films of the ferrimagnetic insulators Y 3Fe5O12 and NiFe2O4 capped with thin Pt layers in terms of the longitudinal spin Seebeck effect (LSSE). The electric response detected in the Pt layer under an out-of-plane temperature gradient can be interpreted as a pure spin current converted into a charge current via the inverse spin Hall effect. Typically, the transverse voltage is the quantity investigated in LSSE measurements (in the range of μV). Here, we present the directly detected DC current (in the range of nA) as an alternative quantity. Furthermore, we investigate the resistance of the Pt layer in the LSSE configuration. We found an influence of the test current on the resistance. The typical shape of the LSSE curve varies for increasing test currents.

  20. Effect of ordered array of magnetic dots on the dynamics of Josephson vortices in stacked SNS Josephson junctions under DC and AC current

    NASA Astrophysics Data System (ADS)

    Berdiyorov, Golibjon R.; Savel'ev, Sergey; Kusmartsev, Feodor V.; Peeters, François M.

    2015-11-01

    We use the anisotropic time-dependent Ginzburg-Landau theory to investigate the effect of a square array of out-of-plane magnetic dots on the dynamics of Josephson vortices (fluxons) in artificial stacks of superconducting-normal-superconducting (SNS) Josephson junctions in the presence of external DC and AC currents. Periodic pinning due to the magnetic dots distorts the triangular lattice of fluxons and results in the appearance of commensurability features in the current-voltage characteristics of the system. For the larger values of the magnetization, additional peaks appear in the voltage-time characteristics of the system due to the creation and annihilation of vortex-antivortex pairs. Peculiar changes in the response of the system to the applied current is found resulting in a "superradiant" vortex-flow state at large current values, where a rectangular lattice of moving vortices is formed. Synchronizing the motion of fluxons by adding a small ac component to the biasing dc current is realized. However, we found that synchronization becomes difficult for large magnetization of the dots due to the formation of vortex-antivortex pairs.

  1. A dc glow discharge as a source of electrons for a portable mass spectrometer: characterization of the electron current intensity and electron kinetic energy distribution

    NASA Astrophysics Data System (ADS)

    Chalkha, A.; Despenes, C.; Janulyte, A.; Zerega, Y.; Andre, J.; Brkic, B.; Taylor, S.

    2015-02-01

    A dc glow discharge cell with planar electrodes operating at about 1 Torr has been characterized with an inlet flow from ambient air. It will be used as a source of electrons to further ionize molecules by electron impact in a portable mass spectrometer. The Paschen curve has been measured for six values of the pressure around the minimum of the curve. The voltage-current characteristic, observed until 7 mA for different values of the pressure, increases with current in the normal glow regime. The temporal evolution of the discharge current has been recorded over long periods greater than one day for different insulator materials. The best stability has been obtained with Macor and Nylon. The available electron current for ionization has been measured at about 0.6 µA and the electron kinetic energy distribution has been found to be between 0 and a few tens of eV.

  2. The first Italian Superconducting Fault Current Limiter: Results of the field testing experience after one year operation

    NASA Astrophysics Data System (ADS)

    Martini, L.; Bocchi, M.; Ascade, M.; Valzasina, A.; Rossi, V.; Ravetta, C.; Angeli, G.

    2014-05-01

    Ricerca sul Sistema Energetico S.p.A. (RSE) has been gaining a relevant experience in the simulation, design and installation of resistive-type Superconducting Fault Current Limiter (SFCL) devices for more than five years in the framework of a R&D national project funded by the Ricerca di Sistema (RdS). The most recent outcome of this research activity is the installation of a resistive-type BSCCO-based 9 kV / 3.4 MVA SFCL device in a single feeder branch of the Medium Voltage (MV) distribution network managed by A2A Reti Elettriche S.p.A (A2A) in the Milano area. This installation represents the first SFCL successfully installed in Italy. In this paper, we report on the main outcomes after a more than 1-year long steady-state field testing activity. The design of an upgraded device to be installed in the same substation has already been initiated: the new SFCL will allow to protect four different feeders, therefore implying a device upgrade up to 15.6 MVA.

  3. Multilevel DC link inverter

    DOEpatents

    Su, Gui-Jia

    2003-06-10

    A multilevel DC link inverter and method for improving torque response and current regulation in permanent magnet motors and switched reluctance motors having a low inductance includes a plurality of voltage controlled cells connected in series for applying a resulting dc voltage comprised of one or more incremental dc voltages. The cells are provided with switches for increasing the resulting applied dc voltage as speed and back EMF increase, while limiting the voltage that is applied to the commutation switches to perform PWM or dc voltage stepping functions, so as to limit current ripple in the stator windings below an acceptable level, typically 5%. Several embodiments are disclosed including inverters using IGBT's, inverters using thyristors. All of the inverters are operable in both motoring and regenerating modes.

  4. A Single-Phase Current Source Solar Inverter with Constant Instantaneous Power, Improved Reliability, and Reduced-Size DC-Link Filter

    NASA Astrophysics Data System (ADS)

    Bush, Craig R.

    This dissertation presents a novel current source converter topology that is primarily intended for single-phase photovoltaic (PV) applications. In comparison with the existing PV inverter technology, the salient features of the proposed topology are: a) the low frequency (double of line frequency) ripple that is common to single-phase inverters is greatly reduced; b) the absence of low frequency ripple enables significantly reduced size pass components to achieve necessary DC-link stiffness and c) improved maximum power point tracking (MPPT) performance is readily achieved due to the tightened current ripple even with reduced-size passive components. The proposed topology does not utilize any electrolytic capacitors. Instead an inductor is used as the DC-link filter and reliable AC film capacitors are utilized for the filter and auxiliary capacitor. The proposed topology has a life expectancy on par with PV panels. The proposed modulation technique can be used for any current source inverter where an unbalanced three-phase operation is desires such as active filters and power controllers. The proposed topology is ready for the next phase of microgrid and power system controllers in that it accepts reactive power commands. This work presents the proposed topology and its working principle supported by with numerical verifications and hardware results. Conclusions and future work are also presented.

  5. Dc characterization of lateral bipolar devices in standard CMOS technology: a new model for base current partitioning

    NASA Astrophysics Data System (ADS)

    Corsi, F.; Di Ciano, M.; Marzocca, C.

    1999-05-01

    As is generally known, compared with MOSFETs bipolar transistors provide better performance in terms of small signal transconductance, intrinsic cut-off frequency and noise characteristics, at the cost of a more expensive technology. A good compromise between the low costs proper of standard CMOS technology and the excellent performance typical of bipolar devices can be achieved by using bipolar transistors derived from MOS structures. Naturally suitable models combined with efficient parameter extraction techniques are mandatory to provide designers with reliable simulation tools. A dc parameter extraction procedure for a PNP lateral transistor realized in a standard CMOS technology based on an existing composite circuit model is presented here. The extraction results provide accurate fitting between measured and simulated data for different operating regions without resort to numerical optimization, thus preserving the physical meaning of the extracted parameters and retaining a good correlation with process variations.

  6. An improved low-voltage ride-through performance of DFIG based wind plant using stator dynamic composite fault current limiter.

    PubMed

    Gayen, P K; Chatterjee, D; Goswami, S K

    2016-05-01

    In this paper, an enhanced low-voltage ride-through (LVRT) performance of a grid connected doubly fed induction generator (DFIG) has been presented with the usage of stator dynamic composite fault current limiter (SDCFCL). This protection circuit comprises of a suitable series resistor-inductor combination and parallel bidirectional semiconductor switch. The SDCFCL facilitates double benefits such as reduction of rotor induced open circuit voltage due to increased value of stator total inductance and concurrent increase of rotor impedance. Both effects will limit rotor circuit over current and over voltage situation more secured way in comparison to the conventional scheme like the dynamic rotor current limiter (RCL) during any type of fault situation. The proposed concept is validated through the simulation study of the grid integrated 2.0MW DFIG. PMID:26876377

  7. A novel electro-driven membrane for removal of chromium ions using polymer inclusion membrane under constant D.C. electric current.

    PubMed

    Kaya, Ahmet; Onac, Canan; Alpoguz, H Korkmaz

    2016-11-01

    In this study, the use of polymer inclusion membrane under constant electric current for the removal of Cr(VI) from water has investigated for the first time. Transport of Cr(VI) is performed by an electric current from the donor phase to the acceptor phase with a constant electric current of 0.5A. The optimized membrane includes of 12.1% 2-nitrophenyl octyl ether (2-NPOE), 77.6% cellulose triacetate (CTA), 10.3% tricapryl-methylammonium chloride (Aliquat 336) as a carrier. We tested the applicability of the selected membrane for Cr(VI) removal in real environmental water samples and evaluated its reusability. Electro membrane experiments were carried out under various parameters, such as the effect of electro membrane voltage at constant DC electric current; electro membrane current at constant voltage, acceptor phase pH, and stable electro membrane; and a comparison of polymer inclusion membrane and electro membrane transport studies. The Cr(VI) transport was achieved 98.33% after 40min under optimized conditions. An alternative method has been employed that eliminates the changing of electrical current by the application of constant electric current for higher reproducibility of electro membrane extraction experiments by combining the excellent selective and long-term use features of polymer inclusion membrane. PMID:27239722

  8. Carbon doping of precursor boron powder for control of normal resistance of MgB2 bulks for specific use in fault current limiter applications

    NASA Astrophysics Data System (ADS)

    Archer, J.; Jarvis, A. L. L.

    2014-05-01

    Magnesium Diboride (MgB2) bulk superconductor has been manufactured in order to study the enhancement of the normal resistivity for application to superconducting fault current limiters (SFCLs). SFCLs have proven to be a viable means for limiting surge currents by dissipating fault energy as the superconductor quenches. As the current limiting behaviour is determined by the normal resistivity (ρn), research has been conducted to evaluate an effective means to increase ρn for bulk superconducting MgB2, which is intrinsically much lower than for high temperature superconductors. Intragranular carbon doping has been confirmed as a means to increase ρn, and was implemented by chemical vapour deposition (CVD) on the boron precursor powder by ethylene gas at 600 °C for durations up to 6 hours in a tubular furnace apparatus. In situ manufacturing of MgB2 bulk was performed using the reactive liquid magnesium infiltration technique. Overall, carbon doping provided a factor of 11.00 increase in the residual resistivity, ρ0, which provides the initial limiting action to fault currents, for an accompanying decrease in the critical temperature, Tc, of 2 K.

  9. The Servita Fault, Colombian Eastern Cordillera: Origin, Geotectonics, and Seismicity

    NASA Astrophysics Data System (ADS)

    Chicangana, G.; Kammer, A.; Vargas Jiménez, C. A.; Caneva, A.; Pedraza, P.; Salcedo, E.; Gomez, A.; Muñoz, F.

    2014-12-01

    The Servita fault is a thrust located in the center of Colombia and whose main scarp is at 5 km west of Villavicencio (500.000 inhabitants). According to geophysics data as gravity, magnetic, and seismic, this fault was confirmed how a large cortical structure in the Colombian Eastern Cordillera. The Servita fault possibly was originated like a suture that derived of a continental collision in Late Mesoproterozoic times when Rodinia was conform totally. The Servita Fault as normal fault in Mesozoic times contributed to the Colombian Cretaceous basin development. In Late Cretaceous because to collision of the Caribbean plate with the northwestern corner of South America a strong compressive stress was occur and kinematics changes were presented in the normal faults restrained to the basin like among others the Servita Fault, where these were converted in inverse faults. From early Pliocene until Present times the Servita Fault controlled the growth of the Cordillera and the Llanos foothills in this sector of Central Colombia. Result of this is the seismicity activity registered for this region from historical times (less of 500 years for Colombian case). Two earthquakes have transcended in this region in last three centuries: the first one occurred on October 18th, 1743 with a current probabilistic magnitude greater than 6.5 and the second one struck on May 24th, 2008 with a M = 5.9. In this work we show how this fault has develop from its origin, and how this can would produce a M > 6.5 earthquake very close to metropolitan area of Bogota D.C., and Villavicencio. This earthquake would destroy both urban areas resulting in high losses in lives and economic terms. The seismicity activity of the Servita Fault and its associated structures is registered by the National Seismological Network of Colombia and the Sabana de Bogotá Seismological Network.

  10. DC-to-DC switching converter

    NASA Technical Reports Server (NTRS)

    Cuk, Slobodan M. (Inventor); Middlebrook, Robert D. (Inventor)

    1980-01-01

    A dc-to-dc converter having nonpulsating input and output current uses two inductances, one in series with the input source, the other in series with the output load. An electrical energy transferring device with storage, namely storage capacitance, is used with suitable switching means between the inductances to DC level conversion. For isolation between the source and load, the capacitance may be divided into two capacitors coupled by a transformer, and for reducing ripple, the inductances may be coupled. With proper design of the coupling between the inductances, the current ripple can be reduced to zero at either the input or the output, or the reduction achievable in that way may be divided between the input and output.

  11. Crafting glass vessels: current research on the ancient glass collections in the Freer Gallery of Art, Washington, D.C.

    NASA Astrophysics Data System (ADS)

    Nagel, Alexander; McCarthy, Blythe; Bowe, Stacy

    Our knowledge of glass production in ancient Egypt has been well augmented by the publication of recently excavated materials and glass workshops, but also by more recent materials analysis, and experiments of modern glass-makers attempting to reconstruct the production process of thin-walled coreformed glass vessels. From the mounting of a prefabricated core to the final glass product our understanding of this profession has much improved. The small but well preserved glass collection of the Freer Gallery of Art in Washington, D.C. is a valid tool for examining and studying the technology and production of ancient Egyptian core formed glass vessels. Charles Lang Freer (1854-1919) acquired most of the material from Giovanni Dattari in Cairo in 1909. Previously the glass had received only limited discussion, suggesting that most of these vessels were produced in the 18th Dynasty in the 15th and 14th centuries BCE, while others date from the Hellenistic period and later. In an ongoing project we conducted computed radiography in conjunction with qualitative x-ray fluorescence analysis on a selected group of vessels to understand further aspects of the ancient production process. This paper will provide an overview of our recent research and present our data-gathering process and preliminary results. How can the examinations of core formed glass vessels in the Freer Gallery contribute to our understanding of ancient glass production and technology? By focusing on new ways of looking at old assumptions using the Freer Gallery glass collections, we hope to increase understanding of the challenges of the production process of core-vessel technology as represented by these vessels.

  12. Fault zone hydrogeology

    NASA Astrophysics Data System (ADS)

    Bense, V. F.; Gleeson, T.; Loveless, S. E.; Bour, O.; Scibek, J.

    2013-12-01

    Deformation along faults in the shallow crust (< 1 km) introduces permeability heterogeneity and anisotropy, which has an important impact on processes such as regional groundwater flow, hydrocarbon migration, and hydrothermal fluid circulation. Fault zones have the capacity to be hydraulic conduits connecting shallow and deep geological environments, but simultaneously the fault cores of many faults often form effective barriers to flow. The direct evaluation of the impact of faults to fluid flow patterns remains a challenge and requires a multidisciplinary research effort of structural geologists and hydrogeologists. However, we find that these disciplines often use different methods with little interaction between them. In this review, we document the current multi-disciplinary understanding of fault zone hydrogeology. We discuss surface- and subsurface observations from diverse rock types from unlithified and lithified clastic sediments through to carbonate, crystalline, and volcanic rocks. For each rock type, we evaluate geological deformation mechanisms, hydrogeologic observations and conceptual models of fault zone hydrogeology. Outcrop observations indicate that fault zones commonly have a permeability structure suggesting they should act as complex conduit-barrier systems in which along-fault flow is encouraged and across-fault flow is impeded. Hydrogeological observations of fault zones reported in the literature show a broad qualitative agreement with outcrop-based conceptual models of fault zone hydrogeology. Nevertheless, the specific impact of a particular fault permeability structure on fault zone hydrogeology can only be assessed when the hydrogeological context of the fault zone is considered and not from outcrop observations alone. To gain a more integrated, comprehensive understanding of fault zone hydrogeology, we foresee numerous synergistic opportunities and challenges for the discipline of structural geology and hydrogeology to co-evolve and

  13. Methods for locating ground faults and insulation degradation condition in energy conversion systems

    DOEpatents

    Agamy, Mohamed; Elasser, Ahmed; Galbraith, Anthony William; Harfman Todorovic, Maja

    2015-08-11

    Methods for determining a ground fault or insulation degradation condition within energy conversion systems are described. A method for determining a ground fault within an energy conversion system may include, in part, a comparison of baseline waveform of differential current to a waveform of differential current during operation for a plurality of DC current carrying conductors in an energy conversion system. A method for determining insulation degradation within an energy conversion system may include, in part, a comparison of baseline frequency spectra of differential current to a frequency spectra of differential current transient at start-up for a plurality of DC current carrying conductors in an energy conversion system. In one embodiment, the energy conversion system may be a photovoltaic system.

  14. Effect of natural convection on the current-voltage characteristic of a DC discharge in neon at intermediate pressures

    SciTech Connect

    Uvarov, A. V.; Sakharova, N. A.; Vinnichenko, N. A.

    2011-12-15

    The parameters of the positive column of a glow discharge in neon are calculated with allowance for the induced hydrodynamic motion. It is shown that natural convection in the pressure range of {approx}0.1 atm significantly affects the profiles of the parameters of the positive column and its current-voltage characteristic. The convection arising at large deposited energies improves heat removal, due to which the temperature in the central region of the discharge becomes lower than that calculated from the heat conduction equation. As a result, the current-voltage characteristic is shifted. With allowance for convection, the current-voltage characteristic changes at currents much lower than the critical current at which a transition into the constricted state is observed. This change is uniquely related to the Rayleigh number in the discharge. Thus, a simplified analysis of thermal conduction and diffusion, even with detailed account of kinetic processes occurring in the positive column, does not allow one to accurately calculate the current-voltage characteristic and other discharge parameters at intermediate gas pressures.

  15. Milliwatt dc/dc Inverter

    NASA Technical Reports Server (NTRS)

    Mclyman, C. W.

    1983-01-01

    Compact dc/dc inverter uses single integrated-circuit package containing six inverter gates that generate and amplify 100-kHz square-wave switching signal. Square-wave switching inverts 10-volt local power to isolated voltage at another desired level. Relatively high operating frequency reduces size of filter capacitors required, resulting in small package unit.

  16. Measurements of photocathode operational lifetime at beam currents up to 10-mA using an improved DC high voltage GaAs photogun

    SciTech Connect

    J. Grames; M. Poelker; P. Adderley; J. Brittian; J. Clark; J. Hansknecht; D. Machie; M.L. Stutzman; K. Surles-Law

    2007-06-01

    This work extends past research at Jefferson Lab aimed at better appreciating the mechanisms that limit photocathode operational lifetime at high current (> 1 mA). Specifically, the performance of an improved 100 kV DC high voltage load locked photogun will be described. Although difficult to measure directly, we believe the new gun has better vacuum conditions compared to the original gun, as indicated by enhanced photocathode lifetimes exceeding 2000 C using a 1.55 mm diameter drive laser spot at the photocathode. In addition, the dependence of the lifetime on the laser spot size at the photocathode was measured and a charge density lifetime exceeding 10^6 C/cm^2 was measured with a 0.32 mm laser spot diameter.

  17. Study of Stand-Alone Microgrid under Condition of Faults on Distribution Line

    NASA Astrophysics Data System (ADS)

    Malla, S. G.; Bhende, C. N.

    2014-10-01

    The behavior of stand-alone microgrid is analyzed under the condition of faults on distribution feeders. During fault since battery is not able to maintain dc-link voltage within limit, the resistive dump load control is presented to do so. An inverter control is proposed to maintain balanced voltages at PCC under the unbalanced load condition and to reduce voltage unbalance factor (VUF) at load points. The proposed inverter control also has facility to protect itself from high fault current. Existing maximum power point tracker (MPPT) algorithm is modified to limit the speed of generator during fault. Extensive simulation results using MATLAB/SIMULINK established that the performance of the controllers is quite satisfactory under different fault conditions as well as unbalanced load conditions.

  18. Loop heating by D.C. electric current and electromagnetic wave emissions simulated by 3-D EM particle zone

    NASA Technical Reports Server (NTRS)

    Sakai, J. I.; Zhao, J.; Nishikawa, K.-I.

    1994-01-01

    We have shown that a current-carrying plasma loop can be heated by magnetic pinch driven by the pressure imbalance between inside and outside the loop, using a 3-dimensional electromagnetic (EM) particle code. Both electrons and ions in the loop can be heated in the direction perpendicular to the ambient magnetic field, therefore the perpendicular temperature can be increased about 10 times compared with the parallel temperature. This temperature anisotropy produced by the magnetic pinch heating can induce a plasma instability, by which high-frequency electromagnetic waves can be excited. The plasma current which is enhanced by the magnetic pinch can also excite a kinetic kink instability, which can heat ions perpendicular to the magnetic field. The heating mechanism of ions as well as the electromagnetic emission could be important for an understanding of the coronal loop heating and the electromagnetic wave emissions from active coronal regions.

  19. Implementation of GNSS-Constrained Real-Time Finite Fault Modeling for Improved Earthquake Early Warning: Current Activities at USGS, Menlo Park

    NASA Astrophysics Data System (ADS)

    Smith, D. E.; Minson, S. E.; Langbein, J. O.; Murray, J. R.; Guillemot, C.

    2014-12-01

    Currently implemented Earthquake Early Warning (EEW) algorithms based on seismic data alone should provide the most robust warnings for most M<6 earthquakes, since real-time GPS positions are too noisy to aid in EEW. However, for larger events, which generate larger fault offsets, GPS data can provide a direct on-scale displacement measurements and has sufficient precision. In such situations, the GPS observations may enable more accurate estimation of magnitude and rupture extent than seismic data. The USGS Earthquake Science Center in Menlo Park currently obtains real-time data from approximately 100 GNSS stations in northern California. These stations, which span the San Andreas fault system from the Mendocino Triple Junction to San Juan Bautista, are operated by USGS-Menlo Park, UC Berkeley, and UNAVCO. We have developed software tools for monitoring and troubleshooting data acquisition and quality. We have evaluated the latency and precision of position estimates obtained through real-time processing and we have found these results satisfactory for EEW. We are now implementing the BEFORES algorithm (Minson et al., 2014) that uses Bayesian analysis to determine the best-fitting coseismic fault orientation and finite fault slip distribution (from which moment and rupture extent are obtained) in real-time. BEFORES has been tested extensively on both simulated and real data (retrospectively) for a variety of earthquakes. We are now focusing on three aspects of its implementation: 1) receiving real-time earthquake locations from independent seismic EEW algorithms, that are obtained through multiple TCP/IP connections, and 3) optimizing the computation of elastic Green's functions. Completion of these tasks plus additional tests using simulated waveforms of earthquakes displacements superimposed on actual data will prepare the algorithm for implementation in the West Coast EEW system.

  20. Effect of high energy electrons on H- production and destruction in a high current DC negative ion source for cyclotron

    NASA Astrophysics Data System (ADS)

    Onai, M.; Etoh, H.; Aoki, Y.; Shibata, T.; Mattei, S.; Fujita, S.; Hatayama, A.; Lettry, J.

    2016-02-01

    Recently, a filament driven multi-cusp negative ion source has been developed for proton cyclotrons in medical applications. In this study, numerical modeling of the filament arc-discharge source plasma has been done with kinetic modeling of electrons in the ion source plasmas by the multi-cusp arc-discharge code and zero dimensional rate equations for hydrogen molecules and negative ions. In this paper, main focus is placed on the effects of the arc-discharge power on the electron energy distribution function and the resultant H- production. The modelling results reasonably explains the dependence of the H- extraction current on the arc-discharge power in the experiments.

  1. Multiple high voltage output DC-to-DC power converter

    NASA Technical Reports Server (NTRS)

    Cronin, Donald L. (Inventor); Farber, Bertrand F. (Inventor); Gehm, Hartmut K. (Inventor); Goldin, Daniel S. (Inventor)

    1977-01-01

    Disclosed is a multiple output DC-to-DC converter. The DC input power is filtered and passed through a chopper preregulator. The chopper output is then passed through a current source inverter controlled by a squarewave generator. The resultant AC is passed through the primary winding of a transformer, with high voltages induced in a plurality of secondary windings. The high voltage secondary outputs are each solid-state rectified for passage to individual output loads. Multiple feedback loops control the operation of the chopper preregulator, one being responsive to the current through the primary winding and another responsive to the DC voltage level at a selected output.

  2. Effect of high energy electrons on H⁻ production and destruction in a high current DC negative ion source for cyclotron.

    PubMed

    Onai, M; Etoh, H; Aoki, Y; Shibata, T; Mattei, S; Fujita, S; Hatayama, A; Lettry, J

    2016-02-01

    Recently, a filament driven multi-cusp negative ion source has been developed for proton cyclotrons in medical applications. In this study, numerical modeling of the filament arc-discharge source plasma has been done with kinetic modeling of electrons in the ion source plasmas by the multi-cusp arc-discharge code and zero dimensional rate equations for hydrogen molecules and negative ions. In this paper, main focus is placed on the effects of the arc-discharge power on the electron energy distribution function and the resultant H(-) production. The modelling results reasonably explains the dependence of the H(-) extraction current on the arc-discharge power in the experiments. PMID:26932009

  3. 3D magnetohydrodynamic modelling of a dc low-current plasma arc batch reactor at very high pressure in helium

    NASA Astrophysics Data System (ADS)

    Lebouvier, A.; Iwarere, S. A.; Ramjugernath, D.; Fulcheri, L.

    2013-04-01

    This paper deals with a three-dimensional (3D) time-dependent magnetohydrodynamic (MHD) model under peculiar conditions of very high pressures (from 2 MPa up to 10 MPa) and low currents (<1 A). Studies on plasma arc working under these unusual conditions remain almost unexplored because of the technical and technological challenges to develop a reactor able to sustain a plasma at very high pressures. The combined effect of plasma reactivity and high pressure would probably open the way towards new promising applications in various fields: chemistry, lightning, materials or nanomaterial synthesis. A MHD model helps one to understand the complex and coupled phenomena surrounding the plasma which cannot be understood by simply experimentation. The model also provides data which are difficult to directly determine experimentally. The model simulates an experimental-based batch reactor working with helium. The particular reactor in question was used to investigate the Fischer-Tropsch application, fluorocarbon production and CO2 retro-conversion. However, as a first approach in terms of MHD, the model considers the case for helium as a non-reactive working gas. After a detailed presentation of the model, a reference case has been fully analysed (P = 8 MPa, I = 0.35 A) in terms of physical properties. The results show a bending of the arc and displacement of the anodic arc root towards the top of the reactor, due to the combined effects of convection, gravity and electromagnetic forces. A parametric study on the pressure (2-10 MPa) and current (0.25-0.4 A) was then investigated. The operating pressure does not show an influence on the contraction of the arc but higher pressures involve a higher natural convection in the reactor, driven by the density gradients between the cold and hot gas.

  4. Investigation of Ground-Fault Protection Devices for Photovoltaic Power Systems Applications

    SciTech Connect

    BOWER,WARD I.; WILES,JOHN

    2000-10-03

    Photovoltaic (PV) power systems, like other electrical systems, may be subject to unexpected ground faults. Installed PV systems always have invisible elements other than those indicated by their electrical schematics. Stray inductance, capacitance and resistance are distributed throughout the system. Leakage currents associated with the PV modules, the interconnected array, wires, surge protection devices and conduit add up and can become large enough to look like a ground-fault. PV systems are frequently connected to other sources of power or energy storage such as batteries, standby generators, and the utility grid. This complex arrangement of distributed power and energy sources, distributed impedance and proximity to other sources of power requires sensing of ground faults and proper reaction by the ground-fault protection devices. The different dc grounding requirements (country to country) often add more confusion to the situation. This paper discusses the ground-fault issues associated with both the dc and ac side of PV systems and presents test results and operational impacts of backfeeding commercially available ac ground-fault protection devices under various modes of operation. Further, the measured effects of backfeeding the tripped ground-fault devices for periods of time comparable to anti-islanding allowances for utility interconnection of PV inverters in the United States are reported.

  5. DC current induced metal-insulator transition in epitaxial Sm{sub 0.6}Nd{sub 0.4}NiO{sub 3}/LaAlO{sub 3} thin film

    SciTech Connect

    Huang, Haoliang; Luo, Zhenlin Yang, Yuanjun; Yang, Mengmeng; Wang, Haibo; Hu, Sixia; Bao, Jun; Yun, Yu; Meng, Dechao; Lu, Yalin; Gao, Chen

    2014-05-15

    The metal-insulator transition (MIT) in strong correlated electron materials can be induced by external perturbation in forms of thermal, electrical, optical, or magnetic fields. We report on the DC current induced MIT in epitaxial Sm{sub 0.6}Nd{sub 0.4}NiO{sub 3} (SNNO) thin film deposited by pulsed laser deposition on (001)-LaAlO{sub 3} substrate. It was found that the MIT in SNNO film not only can be triggered by thermal, but also can be induced by DC current. The T{sub MI} of SNNO film decreases from 282 K to 200 K with the DC current density increasing from 0.003 × 10{sup 9} A•m{sup −2} to 4.9 × 10{sup 9} A•m{sup −2}. Based on the resistivity curves measured at different temperatures, the MIT phase diagram has been successfully constructed.

  6. Cost reduction and minimization of land based on an accurate determination of fault current distribution in shield wires and grounding systems

    SciTech Connect

    Daily, W.K. ); Dawalibi, F. )

    1993-01-01

    Careful analysis of Fault Current Distribution in neutral metallic paths, Power System Protection requirements and Ground Potential Rise (GPR) evaluations were carried out at FPL's Lauderdale Power Plant and associated switchyard. These studies resulted in substantial cost savings and land utilization minimization for the power system expansions at Lauderdale Plant by confirming that the in-situ expansion and reconfiguration aimed at constructing two electrically independent substations sharing the same site and grounding system is a sound economical alternative to the construction of a new substation and associated significant site preparation and construction costs. This paper describes the methodology used to conduct this study.

  7. Forback DC-to-DC converter

    NASA Technical Reports Server (NTRS)

    Lukemire, Alan T. (Inventor)

    1995-01-01

    A pulse-width modulated DC-to-DC power converter including a first inductor, i.e. a transformer or an equivalent fixed inductor equal to the inductance of the secondary winding of the transformer, coupled across a source of DC input voltage via a transistor switch which is rendered alternately conductive (ON) and nonconductive (OFF) in accordance with a signal from a feedback control circuit is described. A first capacitor capacitively couples one side of the first inductor to a second inductor which is connected to a second capacitor which is coupled to the other side of the first inductor. A circuit load shunts the second capacitor. A semiconductor diode is additionally coupled from a common circuit connection between the first capacitor and the second inductor to the other side of the first inductor. A current sense transformer generating a current feedback signal for the switch control circuit is directly coupled in series with the other side of the first inductor so that the first capacitor, the second inductor and the current sense transformer are connected in series through the first inductor. The inductance values of the first and second inductors, moreover, are made identical. Such a converter topology results in a simultaneous voltsecond balance in the first inductance and ampere-second balance in the current sense transformer.

  8. Forback DC-to-DC converter

    NASA Technical Reports Server (NTRS)

    Lukemire, Alan T. (Inventor)

    1993-01-01

    A pulse-width modulated DC-to-DC power converter including a first inductor, i.e. a transformer or an equivalent fixed inductor equal to the inductance of the secondary winding of the transformer, coupled across a source of DC input voltage via a transistor switch which is rendered alternately conductive (ON) and nonconductive (OFF) in accordance with a signal from a feedback control circuit is described. A first capacitor capacitively couples one side of the first inductor to a second inductor which is connected to a second capacitor which is coupled to the other side of the first inductor. A circuit load shunts the second capacitor. A semiconductor diode is additionally coupled from a common circuit connection between the first capacitor and the second inductor to the other side of the first inductor. A current sense transformer generating a current feedback signal for the switch control circuit is directly coupled in series with the other side of the first inductor so that the first capacitor, the second inductor and the current sense transformer are connected in series through the first inductor. The inductance values of the first and second inductors, moreover, are made identical. Such a converter topology results in a simultaneous voltsecond balance in the first inductance and ampere-second balance in the current sense transformer.

  9. Auxiliary resonant DC tank converter

    DOEpatents

    Peng, Fang Z.

    2000-01-01

    An auxiliary resonant dc tank (ARDCT) converter is provided for achieving soft-switching in a power converter. An ARDCT circuit is coupled directly across a dc bus to the inverter to generate a resonant dc bus voltage, including upper and lower resonant capacitors connected in series as a resonant leg, first and second dc tank capacitors connected in series as a tank leg, and an auxiliary resonant circuit comprising a series combination of a resonant inductor and a pair of auxiliary switching devices. The ARDCT circuit further includes first clamping means for holding the resonant dc bus voltage to the dc tank voltage of the tank leg, and second clamping means for clamping the resonant dc bus voltage to zero during a resonant period. The ARDCT circuit resonantly brings the dc bus voltage to zero in order to provide a zero-voltage switching opportunity for the inverter, then quickly rebounds the dc bus voltage back to the dc tank voltage after the inverter changes state. The auxiliary switching devices are turned on and off under zero-current conditions. The ARDCT circuit only absorbs ripples of the inverter dc bus current, thus having less current stress. In addition, since the ARDCT circuit is coupled in parallel with the dc power supply and the inverter for merely assisting soft-switching of the inverter without participating in real dc power transmission and power conversion, malfunction and failure of the tank circuit will not affect the functional operation of the inverter; thus a highly reliable converter system is expected.

  10. Comparative Analysis of Various Superconducting and Non-Superconducting Fault Current Limiting Devices Designed for Operation in a 110 kV/100 MW Power Network

    NASA Astrophysics Data System (ADS)

    Kopylov, S. I.; Altov, V. A.; Balashov, N. N.; Ivanov, S. S.; Zheltov, V. V.; Zemerikin, V. D.

    As it is known one of the most promising fault current limiting (FCL) devices for high-power electric networks can be the so-called transformer type superconducting fault current limiter (SFCL) with the primary winding connected to the load in series and the secondary one shortened by a fast-acting circuit-breaker. These devices when made of conventional materials can be very large and expensive - e.g., for a 100 MW circuit under protection the total mass of copper winding conductors can exceed 15 tons and the heat losses in a normal operating mode can be more than 200 kW. Therefore, using of high-temperature superconductors (HTSC) can be a solution which can sufficiently improve the mass, geometrical and operational characteristics of an FCL. Unlike other superconducting AC devices, the magnetic field in SFCL does not exceed 0.1 - 0.2 T what allows using HTSC windings even at a comparatively high level of AC losses existing nowadays. In this paper is performed a comparative analysis of various designs of SCFL with the non-superconducting FCL. It has been shown that the former have a mass by an order of magnitude lower than the latter and the rate of lowering of heat losses in a normal operating mode is the same. The equalization of costs of both designs is expected to be reached within the nearest 3 - 5 five years.

  11. High voltage DC switchgear development for multi-kW space power system: Aerospace technology development of three types of solid state power controllers for 200-1100VDC with current ratings of 25, 50, and 80 amperes with one type utilizing an electromechanical device

    NASA Technical Reports Server (NTRS)

    Billings, W. W.

    1981-01-01

    Three types of solid state power controllers (SSPC's) for high voltage, high power DC system applications were developed. The first type utilizes a SCR power switch. The second type employes an electromechanical power switch element with solid state commutation. The third type utilizes a transistor power switch. Significant accomplishments include high operating efficiencies, fault clearing, high/low temperature performance and vacuum operation.

  12. Fault Locating, Prediction and Protection (FLPPS)

    SciTech Connect

    Yinger, Robert, J.; Venkata, S., S.; Centeno, Virgilio

    2010-09-30

    installation. Because of some testing problems with the Zenergy fault current limiter, installation was delayed until early 2009 with it being put into operation on March 6, 2009. A malfunction of the FCL controller caused the DC power supply to the superconducting magnet to be turned off. This inserted the FCL impedance into the circuit while it was in normal operation causing a voltage resonance condition. While these voltages never reached a point where damage would occur on customer equipment, steps were taken to insure this would not happen again. The FCL was reenergized with load on December 18, 2009. A fault was experienced on the circuit with the FCL in operation on January 14, 2010. The FCL operated properly and reduced the fault current by about 8%, what was expected from tests and modeling. As of the end of the project, the FCL was still in operation on the circuit. The third phase of the project involved the exploration of several advanced protection ideas that might be at a state where they could be applied to the Circuit of the Future and elsewhere in the SCE electrical system. Based on the work done as part of the literature review and survey, as well as a number of internal meetings with engineering staff at SCE, a number of ideas were compiled. These ideas were then evaluated for applicability and ability to be applied on the Circuit of the Future in the time remaining for the project. Some of these basic ideas were implemented on the circuit including measurement of power quality before and after the FCL. It was also decided that we would take what was learned as part of the Circuit of the Future work and extend it to the next generation circuit protection for SCE. Also at this time, SCE put in a proposal to the DOE for the Irvine Smart Grid Demonstration using ARRA funding. SCE was successful in obtaining funding for this proposal, so it was felt that exploration of new protection schemes for this Irvine Smart Grid Demonstration would be a good use of the

  13. Towards Fault Resilient Global Arrays

    SciTech Connect

    Tipparaju, Vinod; Krishnan, Manoj Kumar; Palmer, Bruce J.; Petrini, Fabrizio; Nieplocha, Jaroslaw

    2007-09-03

    The focus of the current paper is adding fault resiliency to the Global Arrays. We extended the GA toolkit to provide a minimal level of capabilities to enable programmer to implement fault resiliency at the user level. Our fault-recovery approach is programmer assisted and based on frequent incremental checkpoints and rollback recovery. In addition, it relies of pool of spare nodes that are used to replace the failing node. We demonstrate usefulness of fault resilient Global Arrays in application context.

  14. ENSYSTROB - Design, manufacturing and test of a 3-phase resistive fault current limiter based on coated conductors for medium voltage application

    NASA Astrophysics Data System (ADS)

    Elschner, S.; Kudymow, A.; Brand, J.; Fink, S.; Goldacker, W.; Grilli, F.; Noe, M.; Vojenciak, M.; Hobl, A.; Bludau, M.; Jänke, C.; Krämer, S.; Bock, J.

    2012-11-01

    Within the German project ENSYSTROB a 3-phase resistive fault current limiter for medium voltage applications (12 kV, 533 Arms) was designed, built, tested and installed in the grid for a one year’s field test. The superconducting modules are made of YBCO coated conductors and replace the modules of an already successfully tested limiter on the basis of BSCCO 2212 bulk material. The components are multifilar spirals equipped with pairs of 12 mm wide YBCO tapes. The single components were characterized with respect to critical current, AC losses and limitation behavior under all possible operation conditions. The finally mounted limiter was successfully tested with respect to high voltage and limitation according to the standards of the customer. It is now installed and operating in its field test location. Finally we give a first comparison of both materials with respect to the different operational aspects.

  15. Scaling of the critical slip distance for seismic faulting with shear strain in fault zones

    USGS Publications Warehouse

    Marone, C.; Kilgore, B.

    1993-01-01

    THEORETICAL and experimentally based laws for seismic faulting contain a critical slip distance1-5, Dc, which is the slip over which strength breaks down during earthquake nucleation. On an earthquake-generating fault, this distance plays a key role in determining the rupture nucleation dimension6, the amount of premonitory and post-seismic slip7-10, and the maximum seismic ground acceleration1,11. In laboratory friction experiments, Dc has been related to the size of surface contact junctions2,5,12; thus, the discrepancy between laboratory measurements of Dc (??? 10-5 m) and values obtained from modelling earthquakes (??? 10-2 m) has been attributed to differences in roughness between laboratory surfaces and natural faults5. This interpretation predicts a dependence of Dc on the particle size of fault gouge 2 (breccia and wear material) but not on shear strain. Here we present experimental results showing that Dc scales with shear strain in simulated fault gouge. Our data suggest a new physical interpretation for the critical slip distance, in which Dc is controlled by the thickness of the zone of localized shear strain. As gouge zones of mature faults are commonly 102-103 m thick13-17, whereas laboratory gouge layers are 1-10 mm thick, our data offer an alternative interpretation of the discrepancy between laboratory and field-based estimates of Dc.

  16. DC Breakdown Experiments

    SciTech Connect

    Calatroni, S.; Descoeudres, A.; Levinsen, Y.; Taborelli, M.; Wuensch, W.

    2009-01-22

    In the context of the CLIC (Compact Linear Collider) project investigations of DC breakdown in ultra high vacuum are carried out in parallel with high power RF tests. From the point of view of saturation breakdown field the best material tested so far is stainless steel, followed by titanium. Copper shows a four times weaker breakdown field than stainless steel. The results indicate clearly that the breakdown events are initiated by field emission current and that the breakdown field is limited by the cathode. In analogy to RF, the breakdown probability has been measured in DC and the data show similar behaviour as a function of electric field.

  17. DC attenuation meter

    DOEpatents

    Hargrove, Douglas L.

    2004-09-14

    A portable, hand-held meter used to measure direct current (DC) attenuation in low impedance electrical signal cables and signal attenuators. A DC voltage is applied to the signal input of the cable and feedback to the control circuit through the signal cable and attenuators. The control circuit adjusts the applied voltage to the cable until the feedback voltage equals the reference voltage. The "units" of applied voltage required at the cable input is the system attenuation value of the cable and attenuators, which makes this meter unique. The meter may be used to calibrate data signal cables, attenuators, and cable-attenuator assemblies.

  18. DC to DC power converters and methods of controlling the same

    DOEpatents

    Steigerwald, Robert Louis; Elasser, Ahmed; Sabate, Juan Antonio; Todorovic, Maja Harfman; Agamy, Mohammed

    2012-12-11

    A power generation system configured to provide direct current (DC) power to a DC link is described. The system includes a first power generation unit configured to output DC power. The system also includes a first DC to DC converter comprising an input section and an output section. The output section of the first DC to DC converter is coupled in series with the first power generation unit. The first DC to DC converter is configured to process a first portion of the DC power output by the first power generation unit and to provide an unprocessed second portion of the DC power output of the first power generation unit to the output section.

  19. Zipper Faults

    NASA Astrophysics Data System (ADS)

    Platt, J. P.; Passchier, C. W.

    2015-12-01

    Intersecting simultaneously active pairs of faults with different orientations and opposing slip sense ("conjugate faults") present geometrical and kinematic problems. Such faults rarely offset each other, even when they have displacements of many km. A simple solution to the problem is that the two faults merge, either zippering up or unzippering, depending on the relationship between the angle of intersection and the slip senses. A widely recognized example of this is the so-called blind front developed in some thrust belts, where a backthrust branches off a decollement surface at depth. The decollement progressively unzippers, so that its hanging wall becomes the hanging wall of the backthrust, and its footwall becomes the footwall of the active decollement. The opposite situation commonly arises in core complexes, where conjugate low-angle normal faults merge to form a single detachment; in this case the two faults zipper up. Analogous situations may arise for conjugate pairs of strike-slip faults. We present kinematic and geometrical analyses of the Garlock and San Andreas faults in California, the Najd fault system in Saudi Arabia, the North and East Anatolian faults, the Karakoram and Altyn Tagh faults in Tibet, and the Tonale and Guidicarie faults in the southern Alps, all of which appear to have undergone zippering over distances of several tens to hundreds of km. The zippering process may produce complex and significant patterns of strain and rotation in the surrounding rocks, particularly if the angle between the zippered faults is large. A zippering fault may be inactive during active movement on the intersecting faults, or it may have a slip rate that differs from either fault. Intersecting conjugate ductile shear zones behave in the same way on outcrop and micro-scales.

  20. The origin of high magnetic remanence in fault pseudotachylites: Theoretical considerations and implication for coseismic electrical currents

    NASA Astrophysics Data System (ADS)

    Ferré, E. C.; Zechmeister, M. S.; Geissman, J. W.; MathanaSekaran, N.; Kocak, K.

    2005-06-01

    Several examples of fault-related pseudotachylites display a significantly higher initial magnetic susceptibility than their granitic host rock (10:1 to 20:1). These higher values are attributed to the presence of fine magnetic particles formed during melt quenching. The hysteresis properties of the particles indicate a single domain (SD) to pseudo single domain (PSD) magnetic grain size. The Curie temperature (Tc) of the magnetic particles is close to 580 °C. The natural remanent magnetization (NRM) of these pseudotachylites is also significantly higher than that of the host rock (up to 300:1). Such anomalously high remanence cannot be explained by a magnetization acquired in the Earth's magnetic field, regardless of pseudotachylite age. Ground lightning and other strong electric pulses can cause anomalously high NRM intensities. A ground lightning explanation seems unlikely to explain the systematically high NRM intensities, particularly in the case of recently exposed samples that have been collected from active quarries. Alternatively, high NRM intensities could be explained by earthquake lightning (EQL), a seismic phenomenon occasionally reported in connection with large magnitude earthquakes ( M > 6.0). The coseismic electrical properties of the pseudotachylite vein-host rock system are characterized by (1) a core of molten material (high conductivity), (2) vapor-rich margins of thermally and mechanically fractured host rocks (low conductivity) and (3) moderately fractured to undeformed host rock (normal conductivity). Such a core conductor bordered by insulating margins is potentially responsible for the propagation of EQL pulses. The coseismic thermal history of pseudotachylite veins has been modeled in 2-D using conductive heat transfer equations. It shows that EQL can be recorded only during a brief time interval (less than 1 min) for a given vein thickness and host-rock temperatures. If the vein is too thick or if the host rock is too hot, the

  1. Fault finder

    DOEpatents

    Bunch, Richard H.

    1986-01-01

    A fault finder for locating faults along a high voltage electrical transmission line. Real time monitoring of background noise and improved filtering of input signals is used to identify the occurrence of a fault. A fault is detected at both a master and remote unit spaced along the line. A master clock synchronizes operation of a similar clock at the remote unit. Both units include modulator and demodulator circuits for transmission of clock signals and data. All data is received at the master unit for processing to determine an accurate fault distance calculation.

  2. Earthquakes and fault creep on the northern San Andreas fault

    USGS Publications Warehouse

    Nason, R.

    1979-01-01

    At present there is an absence of both fault creep and small earthquakes on the northern San Andreas fault, which had a magnitude 8 earthquake with 5 m of slip in 1906. The fault has apparently been dormant after the 1906 earthquake. One possibility is that the fault is 'locked' in some way and only produces great earthquakes. An alternative possibility, presented here, is that the lack of current activity on the northern San Andreas fault is because of a lack of sufficient elastic strain after the 1906 earthquake. This is indicated by geodetic measurements at Fort Ross in 1874, 1906 (post-earthquake), and 1969, which show that the strain accumulation in 1969 (69 ?? 10-6 engineering strain) was only about one-third of the strain release (rebound) in the 1906 earthquake (200 ?? 10-6 engineering strain). The large difference in seismicity before and after 1906, with many strong local earthquakes from 1836 to 1906, but only a few strong earthquakes from 1906 to 1976, also indicates a difference of elastic strain. The geologic characteristics (serpentine, fault straightness) of most of the northern San Andreas fault are very similar to the characteristics of the fault south of Hollister, where fault creep is occurring. Thus, the current absence of fault creep on the northern fault segment is probably due to a lack of sufficient elastic strain at the present time. ?? 1979.

  3. Fault detection and isolation

    NASA Technical Reports Server (NTRS)

    Bernath, Greg

    1994-01-01

    In order for a current satellite-based navigation system (such as the Global Positioning System, GPS) to meet integrity requirements, there must be a way of detecting erroneous measurements, without help from outside the system. This process is called Fault Detection and Isolation (FDI). Fault detection requires at least one redundant measurement, and can be done with a parity space algorithm. The best way around the fault isolation problem is not necessarily isolating the bad measurement, but finding a new combination of measurements which excludes it.

  4. Investigation of DC hybrid circuit breaker based on high-speed switch and arc generator.

    PubMed

    Wu, Yifei; Rong, Mingzhe; Wu, Yi; Yang, Fei; Li, Mei; Zhong, Jianying; Han, Guohui; Niu, Chunping; Hu, Yang

    2015-02-01

    A new design of DC hybrid circuit breaker based on high-speed switch (HSS) and arc generator (AG), which can drastically profit from low heat loss in normal state and fast current breaking under fault state, is presented and analyzed in this paper. AG is designed according to the magnetic pinch effect of liquid metal. By utilizing the arc voltage generated across AG, the fault current is rapidly commutated from HSS into parallel connected branch. As a consequence, the arcless open of HSS is achieved. The post-arc conducting resume time (Δ tc) of AG and the commutation original voltage (Uc), two key factors in the commutation process, are investigated experimentally. Particularly, influences of the liquid metal channel diameter (Φ) of AG, fault current rate of rise (di/dt) and Uc on Δ tc are focused on. Furthermore, a suitable Uc is determined during the current commutation process, aiming at the reliable arcless open of HSS and short breaking time. Finally, the fault current breaking test is carried out for the current peak value of 11.8 kA, and the validity of the design is confirmed by the experimental results. PMID:25725867

  5. Investigation of DC hybrid circuit breaker based on high-speed switch and arc generator

    NASA Astrophysics Data System (ADS)

    Wu, Yifei; Rong, Mingzhe; Wu, Yi; Yang, Fei; Li, Mei; Zhong, Jianying; Han, Guohui; Niu, Chunping; Hu, Yang

    2015-02-01

    A new design of DC hybrid circuit breaker based on high-speed switch (HSS) and arc generator (AG), which can drastically profit from low heat loss in normal state and fast current breaking under fault state, is presented and analyzed in this paper. AG is designed according to the magnetic pinch effect of liquid metal. By utilizing the arc voltage generated across AG, the fault current is rapidly commutated from HSS into parallel connected branch. As a consequence, the arcless open of HSS is achieved. The post-arc conducting resume time (Δ tc) of AG and the commutation original voltage (Uc), two key factors in the commutation process, are investigated experimentally. Particularly, influences of the liquid metal channel diameter (Φ) of AG, fault current rate of rise (di/dt) and Uc on Δ tc are focused on. Furthermore, a suitable Uc is determined during the current commutation process, aiming at the reliable arcless open of HSS and short breaking time. Finally, the fault current breaking test is carried out for the current peak value of 11.8 kA, and the validity of the design is confirmed by the experimental results.

  6. Efficient Design in a DC to DC Converter Unit

    NASA Technical Reports Server (NTRS)

    Bruemmer, Joel E.; Williams, Fitch R.; Schmitz, Gregory V.

    2002-01-01

    Space Flight hardware requires high power conversion efficiencies due to limited power availability and weight penalties of cooling systems. The International Space Station (ISS) Electric Power System (EPS) DC-DC Converter Unit (DDCU) power converter is no exception. This paper explores the design methods and tradeoffs that were utilized to accomplish high efficiency in the DDCU. An isolating DC to DC converter was selected for the ISS power system because of requirements for separate primary and secondary grounds and for a well-regulated secondary output voltage derived from a widely varying input voltage. A flyback-current-fed push-pull topology or improved Weinberg circuit was chosen for this converter because of its potential for high efficiency and reliability. To enhance efficiency, a non-dissipative snubber circuit for the very-low-Rds-on Field Effect Transistors (FETs) was utilized, redistributing the energy that could be wasted during the switching cycle of the power FETs. A unique, low-impedance connection system was utilized to improve contact resistance over a bolted connection. For improved consistency in performance and to lower internal wiring inductance and losses a planar bus system is employed. All of these choices contributed to the design of a 6.25 KW regulated dc to dc converter that is 95 percent efficient. The methodology used in the design of this DC to DC Converter Unit may be directly applicable to other systems that require a conservative approach to efficient power conversion and distribution.

  7. Cable-fault locator

    NASA Technical Reports Server (NTRS)

    Cason, R. L.; Mcstay, J. J.; Heymann, A. P., Sr.

    1979-01-01

    Inexpensive system automatically indicates location of short-circuited section of power cable. Monitor does not require that cable be disconnected from its power source or that test signals be applied. Instead, ground-current sensors are installed in manholes or at other selected locations along cable run. When fault occurs, sensors transmit information about fault location to control center. Repair crew can be sent to location and cable can be returned to service with minimum of downtime.

  8. Adaptable DC offset correction

    NASA Technical Reports Server (NTRS)

    Golusky, John M. (Inventor); Muldoon, Kelly P. (Inventor)

    2009-01-01

    Methods and systems for adaptable DC offset correction are provided. An exemplary adaptable DC offset correction system evaluates an incoming baseband signal to determine an appropriate DC offset removal scheme; removes a DC offset from the incoming baseband signal based on the appropriate DC offset scheme in response to the evaluated incoming baseband signal; and outputs a reduced DC baseband signal in response to the DC offset removed from the incoming baseband signal.

  9. Controls and protective devices for d-c constant potential crane power supplies

    SciTech Connect

    Boldt, A.E. ); Gomez, H.R. )

    1993-07-01

    Many changes have taken place in the American steel industry in recent years. Improvements in the efficiency of processes and systems are noticeable in all areas. To compete in the world market, older, less efficient mills and processes have been eliminated in favor of the new and more efficient. This drive for improvement has been noticeable in the area of electric overhead traveling cranes. Older, obsolete electrical equipment has been replaced by newer, more efficient systems. Improvements in collector systems and use of festooned systems has changed the characteristics of the typical soft d-c crane power supply. The 230-v or less d-c utilization voltage on cranes has now become 250 v (or higher) in many mills. The one large resistive element (ie, collectors, m-g sets, etc) in crane power distribution systems has all but disappeared. The changes in d-c crane power supplies have resulted in the need for changes in protection and in the design of traditional d-c constant potential controls. Higher fault currents are now available, and the 10 to 15 ms inductive time constant, traditionally used to determine the interrupting rating of protective devices (such as fuses and circuit breaker) may no longer be adequate. In addition, constant potential controls designed for 230 v may experience problems at voltages higher than 250 v d-c. This paper will discuss these problems and possible solutions involving testing of protective devices and changes to the traditional d-c crane control system.

  10. Approximate Entropy Based Fault Localization and Fault Type Recognition for Non-solidly Earthed Network

    NASA Astrophysics Data System (ADS)

    Pang, Qingle; Liu, Xinyun; Sun, Bo; Ling, Qunli

    2012-12-01

    For non-solidly earthed network, the fault localization of single phase grounding fault has been a problem. A novel fault localization and fault type recognition method of single phase grounding fault based on approximate entropy is presented. The approximate entropies of transient zero sequence current at both ends of healthy section are approximately equal, and the ratio is close to 1. On the contrary, the approximate entropies at both ends of fault section are different, and the ratio is far from 1. So, the fault section is located. At the same fault section, the smaller is the fault resistance, the larger is the approximate entropy of transient zero sequence current. According to the function between approximate entropy and fault resistance, the fault type is determined. The method has the advantages of transferring less data and unneeded synchronous sampling accurately. The simulation results show that the proposed method is feasible and accurate.

  11. Hysteretic Dependence of Magnetic Flux Density on Primary AC Current in Flat-Type Inductive Fault Current Limiter with YBCO Thin Film Discs

    NASA Astrophysics Data System (ADS)

    Harada, Masayuki; Yokomizu, Yasunobu; Matsumura, Toshiro

    2014-05-01

    This paper focuses on a flat-type inductive superconducting FCL (FIS-FCL) consisting of a pancake coil and a YBCO thin layer disc. AC current injection experiments and magnetic field analysis were carried out for two kinds of FIS-FCL, single-disc model and double-discs model. In the former, the pancake coil was putted on the YBCO disc. In the latter, the pancake coil was sandwiched with two YBCO discs. The double-discs model cancels out the magnetic flux density more effectively than the single-disc model. In the double-discs model, the superconducting state period is longer than in the single-disc model. Thus, it may be concluded that the double-discs model is considered to be suitable for FIS-FCL.

  12. Fault Analysis in Solar Photovoltaic Arrays

    NASA Astrophysics Data System (ADS)

    Zhao, Ye

    Fault analysis in solar photovoltaic (PV) arrays is a fundamental task to increase reliability, efficiency and safety in PV systems. Conventional fault protection methods usually add fuses or circuit breakers in series with PV components. But these protection devices are only able to clear faults and isolate faulty circuits if they carry a large fault current. However, this research shows that faults in PV arrays may not be cleared by fuses under some fault scenarios, due to the current-limiting nature and non-linear output characteristics of PV arrays. First, this thesis introduces new simulation and analytic models that are suitable for fault analysis in PV arrays. Based on the simulation environment, this thesis studies a variety of typical faults in PV arrays, such as ground faults, line-line faults, and mismatch faults. The effect of a maximum power point tracker on fault current is discussed and shown to, at times, prevent the fault current protection devices to trip. A small-scale experimental PV benchmark system has been developed in Northeastern University to further validate the simulation conclusions. Additionally, this thesis examines two types of unique faults found in a PV array that have not been studied in the literature. One is a fault that occurs under low irradiance condition. The other is a fault evolution in a PV array during night-to-day transition. Our simulation and experimental results show that overcurrent protection devices are unable to clear the fault under "low irradiance" and "night-to-day transition". However, the overcurrent protection devices may work properly when the same PV fault occurs in daylight. As a result, a fault under "low irradiance" and "night-to-day transition" might be hidden in the PV array and become a potential hazard for system efficiency and reliability.

  13. FAULT & COORDINATION STUDY FOR T PLANT COMPLEX

    SciTech Connect

    MCDONALD, G.P.; BOYD-BODIAU, E.A.

    2004-09-01

    A short circuit study is performed to determine the maximum fault current that the system protective devices, transformers, and interconnections would he subject to in event of a three phase, phase-to-phase, or phase-to-ground fault. Generally, the short circuit study provides the worst case fault current levels at each bus or connection point of the system.

  14. ANNs pinpoint underground distribution faults

    SciTech Connect

    Glinkowski, M.T.; Wang, N.C.

    1995-10-01

    Many offline fault location techniques in power distribution circuits involve patrolling along the lines or cables. In overhead distribution lines, most of the failures can be located quickly by visual inspection without the aid of special equipment. However, locating a fault in underground cable systems is more difficult. It involves additional equipment (e.g., thumpers, radars, etc.) to transform the invisibility of the cable into other forms of signals, such as acoustic sound and electromagnetic pulses. Trained operators must carry the equipment above the ground, follow the path of the signal, and draw lines on their maps in order to locate the fault. Sometimes, even smelling the burnt cable faults is a way of detecting the problem. These techniques are time consuming, not always reliable, and, as in the case of high-voltage dc thumpers, can cause additional damage to the healthy parts of the cable circuit. Online fault location in power networks that involve interconnected lines (cables) and multiterminal sources continues receiving great attention, with limited success in techniques that would provide simple and practical solutions. This article features a new online fault location technique that: uses the pattern recognition feature of artificial neural networks (ANNs); utilizes new capabilities of modern protective relaying hardware. The output of the neural network can be graphically displayed as a simple three-dimensional (3-D) chart that can provide an operator with an instantaneous indication of the location of the fault.

  15. Light-weight DC to very high voltage DC converter

    DOEpatents

    Druce, R.L.; Kirbie, H.C.; Newton, M.A.

    1998-06-30

    A DC-DC converter capable of generating outputs of 100 KV without a transformer comprises a silicon opening switch (SOS) diode connected to allow a charging current from a capacitor to flow into an inductor. When a specified amount of charge has flowed through the SOS diode, it opens up abruptly; and the consequential collapsing field of the inductor causes a voltage and current reversal that is steered into a load capacitor by an output diode. A switch across the series combination of the capacitor, inductor, and SOS diode closes to periodically reset the SOS diode by inducing a forward-biased current. 1 fig.

  16. Light-weight DC to very high voltage DC converter

    DOEpatents

    Druce, Robert L.; Kirbie, Hugh C.; Newton, Mark A.

    1998-01-01

    A DC-DC converter capable of generating outputs of 100 KV without a transformer comprises a silicon opening switch (SOS) diode connected to allow a charging current from a capacitor to flow into an inductor. When a specified amount of charge has flowed through the SOS diode, it opens up abruptly; and the consequential collapsing field of the inductor causes a voltage and current reversal that is steered into a load capacitor by an output diode. A switch across the series combination of the capacitor, inductor, and SOS diode closes to periodically reset the SOS diode by inducing a forward-biased current.

  17. Triple voltage dc-to-dc converter and method

    SciTech Connect

    Su, Gui-Jia

    2008-08-05

    A circuit and method of providing three dc voltage buses and transforming power between a low voltage dc converter and a high voltage dc converter, by coupling a primary dc power circuit and a secondary dc power circuit through an isolation transformer; providing the gating signals to power semiconductor switches in the primary and secondary circuits to control power flow between the primary and secondary circuits and by controlling a phase shift between the primary voltage and the secondary voltage. The primary dc power circuit and the secondary dc power circuit each further comprising at least two tank capacitances arranged in series as a tank leg, at least two resonant switching devices arranged in series with each other and arranged in parallel with the tank leg, and at least one voltage source arranged in parallel with the tank leg and the resonant switching devices, said resonant switching devices including power semiconductor switches that are operated by gating signals. Additional embodiments having a center-tapped battery on the low voltage side and a plurality of modules on both the low voltage side and the high voltage side are also disclosed for the purpose of reducing ripple current and for reducing the size of the components.

  18. High-Efficiency dc/dc Converter

    NASA Technical Reports Server (NTRS)

    Sturman, J.

    1982-01-01

    High-efficiency dc/dc converter has been developed that provides commonly used voltages of plus or minus 12 Volts from an unregulated dc source of from 14 to 40 Volts. Unique features of converter are its high efficiency at low power level and ability to provide output either larger or smaller than input voltage.

  19. YBa2Cu3O7-delta dc SQUID array for multichannel magnetometry and multichannel flip-chip current sensors

    NASA Astrophysics Data System (ADS)

    Ramos, J.; Zakosarenko, V.; IJsselsteijn, R.; Stolz, R.; Schultze, V.; Chwala, A.; Hoenig, H. E.; Meyer, H.-G.

    1999-09-01

    We have prepared arrays of single-layer washer-type dc superconducting quantum interference devices (SQUIDs) on 10 mm × 10 mm bicrystal substrates. Each SQUID in the array is equipped with its own modulation loop, which makes a separate operation of them possible. Arrays containing nine or 11 dc SQUIDs have been tested and the crosstalk between neighbouring channels has been found to be 5%. The field sensitivity of the SQUIDs is 85 nT icons/Journals/Common/Phi" ALT="Phi" ALIGN="TOP"/>0-1 and 105 nT icons/Journals/Common/Phi" ALT="Phi" ALIGN="TOP"/>0-1 for the nine- and 11-device array, respectively. The equivalent flux noise is typically icons/Journals/Common/le" ALT="le" ALIGN="TOP"/> 20 icons/Journals/Common/mu" ALT="mu" ALIGN="TOP"/>icons/Journals/Common/Phi" ALT="Phi" ALIGN="TOP"/>0 Hz-1/2 down to 1 Hz with ac bias reversal. A field resolution of less than 2.1 pT Hz-1/2 has been obtained for at least eight channels on a chip. By using multiturn YBa2Cu3O7-icons/Journals/Common/delta" ALT="delta" ALIGN="MIDDLE"/> input coils and mounting them in a flip-chip configuration together with the single-layer dc SQUIDs we have been able to build three-channel current sensors. The current sensitivity equals 3-3.5 icons/Journals/Common/mu" ALT="mu" ALIGN="TOP"/>A icons/Journals/Common/Phi" ALT="Phi" ALIGN="TOP"/>0-1 depending on the alignment of the flip-chip configuration. The current resolution of the devices is < 70 pA Hz-1/2. We show the possibility of building sensitive magnetometers by connecting the input coil of these current sensors to a normal-conducting pickup antenna.

  20. The dc power circuits: A compilation

    NASA Technical Reports Server (NTRS)

    1972-01-01

    A compilation of reports concerning power circuits is presented for the dissemination of aerospace information to the general public as part of the NASA Technology Utilization Program. The descriptions for the electronic circuits are grouped as follows: dc power supplies, power converters, current-voltage power supply regulators, overload protection circuits, and dc constant current power supplies.

  1. Comparative study of reference currents and DC bus voltage control for Three-Phase Four-Wire Four-Leg SAPF to compensate harmonics and reactive power with 3D SVM.

    PubMed

    Chebabhi, A; Fellah, M K; Kessal, A; Benkhoris, M F

    2015-07-01

    In this paper the performances of three reference currents and DC bus voltage control techniques for Three-Phase Four-Wire Four-Leg SAPF are compared for balanced and unbalanced load conditions. The main goals are to minimize the harmonics, reduce the magnitude of neutral current, eliminate the zero-sequence current components caused by single-phase nonlinear loads and compensate the reactive power, and on the other hand improve performances such as robustness, stabilization, trajectory pursuit, and reduce time response. The three techniques are analyzed mathematically and simulation results are compared. The techniques considered for comparative study are the PI Control, Sliding Mode Control and the Backstepping Control. Synchronous reference frame theory (SRF) in the dqo-axes is used to generate the reference currents, of the inverter. PMID:25704056

  2. Fault mechanics

    SciTech Connect

    Segall, P. )

    1991-01-01

    Recent observational, experimental, and theoretical modeling studies of fault mechanics are discussed in a critical review of U.S. research from the period 1987-1990. Topics examined include interseismic strain accumulation, coseismic deformation, postseismic deformation, and the earthquake cycle; long-term deformation; fault friction and the instability mechanism; pore pressure and normal stress effects; instability models; strain measurements prior to earthquakes; stochastic modeling of earthquakes; and deep-focus earthquakes. Maps, graphs, and a comprehensive bibliography are provided. 220 refs.

  3. Method of locating ground faults

    NASA Astrophysics Data System (ADS)

    Patterson, Richard L.; Rose, Allen H.; Cull, Ronald C.

    1994-11-01

    The present invention discloses a method of detecting and locating current imbalances such as ground faults in multiwire systems using the Faraday effect. As an example, for 2-wire or 3-wire (1 ground wire) electrical systems, light is transmitted along an optical path which is exposed to magnetic fields produced by currents flowing in the hot and neutral wires. The rotations produced by these two magnetic fields cancel each other, therefore light on the optical path does not read the effect of either. However, when a ground fault occurs, the optical path is exposed to a net Faraday effect rotation due to the current imbalance thereby exposing the ground fault.

  4. Method of locating ground faults

    NASA Technical Reports Server (NTRS)

    Patterson, Richard L. (Inventor); Rose, Allen H. (Inventor); Cull, Ronald C. (Inventor)

    1994-01-01

    The present invention discloses a method of detecting and locating current imbalances such as ground faults in multiwire systems using the Faraday effect. As an example, for 2-wire or 3-wire (1 ground wire) electrical systems, light is transmitted along an optical path which is exposed to magnetic fields produced by currents flowing in the hot and neutral wires. The rotations produced by these two magnetic fields cancel each other, therefore light on the optical path does not read the effect of either. However, when a ground fault occurs, the optical path is exposed to a net Faraday effect rotation due to the current imbalance thereby exposing the ground fault.

  5. Simultaneous distribution of AC and DC power

    DOEpatents

    Polese, Luigi Gentile

    2015-09-15

    A system and method for the transport and distribution of both AC (alternating current) power and DC (direct current) power over wiring infrastructure normally used for distributing AC power only, for example, residential and/or commercial buildings' electrical wires is disclosed and taught. The system and method permits the combining of AC and DC power sources and the simultaneous distribution of the resulting power over the same wiring. At the utilization site a complementary device permits the separation of the DC power from the AC power and their reconstruction, for use in conventional AC-only and DC-only devices.

  6. PV Systems Reliability Final Technical Report: Ground Fault Detection

    SciTech Connect

    Lavrova, Olga; Flicker, Jack David; Johnson, Jay

    2016-01-01

    We have examined ground faults in PhotoVoltaic (PV) arrays and the efficacy of fuse, current detection (RCD), current sense monitoring/relays (CSM), isolation/insulation (Riso) monitoring, and Ground Fault Detection and Isolation (GFID) using simulations based on a Simulation Program with Integrated Circuit Emphasis SPICE ground fault circuit model, experimental ground faults installed on real arrays, and theoretical equations.

  7. Digital Control Technologies for Modular DC-DC Converters

    NASA Technical Reports Server (NTRS)

    Button, Robert M.; Kascak, Peter E.; Lebron-Velilla, Ramon

    2002-01-01

    Recent trends in aerospace Power Management and Distribution (PMAD) systems focus on using commercial off-the-shelf (COTS) components as standard building blocks. This move to more modular designs has been driven by a desire to reduce costs and development times, but is also due to the impressive power density and efficiency numbers achieved by today's commercial DC-DC converters. However, the PMAD designer quickly learns of the hidden "costs" of using COTS converters. The most significant cost is the required addition of external input filters to meet strict electromagnetic interference (MIAMI) requirements for space systems. In fact, the high power density numbers achieved by the commercial manufacturers are greatly due to the lack of necessary input filters included in the COTS module. The NASA Glenn Research Center is currently pursuing a digital control technology that addresses this problem with modular DC-DC converters. This paper presents the digital control technologies that have been developed to greatly reduce the input filter requirements for paralleled, modular DC-DC converters. Initial test result show that the input filter's inductor size was reduced by 75 percent, and the capacitor size was reduced by 94 percent while maintaining the same power quality specifications.

  8. Novel bidirectional DC-DC converters based on the three-state switching cell

    NASA Astrophysics Data System (ADS)

    da Silva Júnior, José Carlos; Robles Balestero, Juan Paulo; Lessa Tofoli, Fernando

    2016-05-01

    It is well known that there is an increasing demand for bidirectional DC-DC converters for applications that range from renewable energy sources to electric vehicles. Within this context, this work proposes novel DC-DC converter topologies that use the three-state switching cell (3SSC), whose well-known advantages over conventional existing structures are ability to operate at high current levels, while current sharing is maintained by a high frequency transformer; reduction of cost and dimensions of magnetics; improved distribution of losses, with consequent increase of global efficiency and reduction of cost associated to the need of semiconductors with lower current ratings. Three distinct topologies can be derived from the 3SSC: one DC-DC converter with reversible current characteristic able to operate in the first and second quadrants; one DC-DC converter with reversible voltage characteristic able to operate in the first and third quadrants and one DC-DC converter with reversible current and voltage characteristics able to operate in four quadrants. Only the topology with bidirectional current characteristic is analysed in detail in terms of the operating stages in both nonoverlapping and overlapping modes, while the design procedure of the power stage elements is obtained. In order to validate the theoretical assumptions, an experimental prototype is also implemented, so that relevant issues can be properly discussed.

  9. Variable load automatically tests dc power supplies

    NASA Technical Reports Server (NTRS)

    Burke, H. C., Jr.; Sullivan, R. M.

    1965-01-01

    Continuously variable load automatically tests dc power supplies over an extended current range. External meters monitor current and voltage, and multipliers at the outputs facilitate plotting the power curve of the unit.

  10. dc power system for deuteron accelerator

    SciTech Connect

    Creek, K.O.; Liska, D.J.

    1981-01-01

    The Fusion Materials Irradiation Test (FMIT) Facility dc power system provides excitation current for all linac and High-Energy Beam Transport (HEBT) quadrupole and bending magnets, excitation for horizontal and vertical beam steering, and current-bypass shunts.

  11. A DC Transformer

    NASA Technical Reports Server (NTRS)

    Youngquist, Robert C.; Ihlefeld, Curtis M.; Starr, Stanley O.

    2013-01-01

    A component level dc transformer is described in which no alternating currents or voltages are present. It operates by combining features of a homopolar motor and a homopolar generator, both de devices, such that the output voltage of a de power supply can be stepped up (or down) with a corresponding step down (or up) in current. The basic theory for this device is developed, performance predictions are made, and the results from a small prototype are presented. Based on demonstrated technology in the literature, this de transformer should be scalable to low megawatt levels, but it is more suited to high current than high voltage applications. Significant development would be required before it could achieve the kilovolt levels needed for de power transmission.

  12. Arc burst pattern analysis fault detection system

    NASA Technical Reports Server (NTRS)

    Russell, B. Don (Inventor); Aucoin, B. Michael (Inventor); Benner, Carl L. (Inventor)

    1997-01-01

    A method and apparatus are provided for detecting an arcing fault on a power line carrying a load current. Parameters indicative of power flow and possible fault events on the line, such as voltage and load current, are monitored and analyzed for an arc burst pattern exhibited by arcing faults in a power system. These arcing faults are detected by identifying bursts of each half-cycle of the fundamental current. Bursts occurring at or near a voltage peak indicate arcing on that phase. Once a faulted phase line is identified, a comparison of the current and voltage reveals whether the fault is located in a downstream direction of power flow toward customers, or upstream toward a generation station. If the fault is located downstream, the line is de-energized, and if located upstream, the line may remain energized to prevent unnecessary power outages.

  13. Ground Fault--A Health Hazard

    ERIC Educational Resources Information Center

    Jacobs, Clinton O.

    1977-01-01

    A ground fault is especially hazardous because the resistance through which the current is flowing to ground may be sufficient to cause electrocution. The Ground Fault Circuit Interrupter (G.F.C.I.) protects 15 and 25 ampere 120 volt circuits from ground fault condition. The design and examples of G.F.C.I. functions are described in this article.…

  14. DC/DC Converter Stability Testing Study

    NASA Technical Reports Server (NTRS)

    Wang, Bright L.

    2008-01-01

    This report presents study results on hybrid DC/DC converter stability testing methods. An input impedance measurement method and a gain/phase margin measurement method were evaluated to be effective to determine front-end oscillation and feedback loop oscillation. In particular, certain channel power levels of converter input noises have been found to have high degree correlation with the gain/phase margins. It becomes a potential new method to evaluate stability levels of all type of DC/DC converters by utilizing the spectral analysis on converter input noises.

  15. Fault ride-through enhancement using an enhanced field oriented control technique for converters of grid connected DFIG and STATCOM for different types of faults.

    PubMed

    Ananth, D V N; Nagesh Kumar, G V

    2016-05-01

    With increase in electric power demand, transmission lines were forced to operate close to its full load and due to the drastic change in weather conditions, thermal limit is increasing and the system is operating with less security margin. To meet the increased power demand, a doubly fed induction generator (DFIG) based wind generation system is a better alternative. For improving power flow capability and increasing security STATCOM can be adopted. As per modern grid rules, DFIG needs to operate without losing synchronism called low voltage ride through (LVRT) during severe grid faults. Hence, an enhanced field oriented control technique (EFOC) was adopted in Rotor Side Converter of DFIG converter to improve power flow transfer and to improve dynamic and transient stability. A STATCOM is coordinated to the system for obtaining much better stability and enhanced operation during grid fault. For the EFOC technique, rotor flux reference changes its value from synchronous speed to zero during fault for injecting current at the rotor slip frequency. In this process DC-Offset component of flux is controlled, decomposition during symmetric and asymmetric faults. The offset decomposition of flux will be oscillatory in a conventional field oriented control, whereas in EFOC it was aimed to damp quickly. This paper mitigates voltage and limits surge currents to enhance the operation of DFIG during symmetrical and asymmetrical faults. The system performance with different types of faults like single line to ground, double line to ground and triple line to ground was applied and compared without and with a STATCOM occurring at the point of common coupling with fault resistance of a very small value at 0.001Ω. PMID:25840675

  16. Quantum states and linear response in dc and electromagnetic fields for the charge current and spin polarization of electrons at the Bi/Si interface with the giant spin-orbit coupling

    SciTech Connect

    Khomitsky, D. V.

    2012-05-15

    An expansion of the nearly free-electron model constructed by Frantzeskakis, Pons, and Grioni [1] describing quantum states at the Bi/Si(111) interface with the giant spin-orbit coupling is developed and applied for the band structure and spin polarization calculation, as well as for the linear response analysis of the charge current and induced spin caused by a dc field and by electromagnetic radiation. It is found that the large spin-orbit coupling in this system may allow resolving the spin-dependent properties even at room temperature and at a realistic collision rate. The geometry of the atomic lattice combined with spin-orbit coupling leads to an anisotropic response for both the current and spin components related to the orientation of the external field. The in-plane dc electric field produces only the in-plane components of spin in the sample, while both the in-plane and out-of-plane spin components can be excited by normally propagating electromagnetic wave with different polarizations.

  17. Current limiting performance test of 3-phase tri-axial transformer-type SFCL with re-wound structure at 3-line-to-ground fault in lab-scale transmission system

    NASA Astrophysics Data System (ADS)

    Shirai, Yasuyuki; Noda, Sho; Yamabe, Kenta; Hattori, Keisuke; Baba, Jumpei; Kobayashi, Shinichi; Sato, Kenichi

    2013-01-01

    We have proposed a transformer-type SFCL of a re-wound structure, which can produce a limiting reactance (L-limiting) for smaller fault current and, for larger one, additively give a limiting resistance (L + R limiting). The single-phase proposed model SFCL had been tested and shown good limiting characteristics and excellent recovery performance. A 3-phase tri-axial SFCL of the proposed type had been designed and made using BSCCO2223. This paper describes demonstration tests of the model SFCL carried out using a lab-scale one-machine infinite bus transmission model system. The experimental results on the current limiting performance of the SFCL at the 3-line-to-ground (3LG) fault were shown and discussed. The peak fault current 560 A without SFCL was reduced to 230 A with SFCL immediately. The 3-phase SFCL successfully worked without large inter-phase interaction. The SFCL recovered to the stand-by mode under a typical Circuit Breaker (CB) operation sequence.

  18. Signal differentiation in position tracking control of dc motors

    NASA Astrophysics Data System (ADS)

    Beltran-Carbajal, F.; Valderrabano-Gonzalez, A.; Rosas-Caro, J. C.

    2015-01-01

    An asymptotic differentiation approach with respect to time is used for on-line estimation of velocity and acceleration signals in controlled dc motors. The attractive feature of this differentiator of signals is that it does not require any system mathematical model, which allows its use in engineering systems that require the signal differentiation for its control, identification, fault detection, among other applications. Moreover, it is shown that the differentiation approach can be applied for output signals showing a chaotic behavior. In addition a differential flatness control scheme with additional integral compensation of the output error is proposed for tracking tasks of position reference trajectories for direct current electric motors using angular position measurements only.

  19. A dc to dc converter

    NASA Technical Reports Server (NTRS)

    Willis, A. E.; Gould, J. M.; Matheney, J. L.; Garrett, H. (Inventor)

    1984-01-01

    The object of the invention is to provide an improved converter for converting one direct current voltage to another. A plurality of phased square wave voltages are provided from a ring counter through amplifiers to a like plurality of output transformers. Each of these transformers has two windings, and S(1) winding and an S(2) winding. The S(1) windings are connected in series, then the S(2) windings are connected in series, and finally, the two sets of windings are connected in series. One of six SCRs is connected between each two series connected windings to a positive output terminal and one of diodes is connected between each set of two windings of a zero output terminal. By virtue of this configuration, a quite high average direct current voltage is obtained, which varies between full voltage and two-thirds full voltage rather than from full voltage to zero. Further, its variation, ripple frequency, is reduced to one-sixth of that present in a single phase system. Application to raising battery voltage for an ion propulsion system is mentioned.

  20. Fault analysis of multichannel spacecraft power systems

    NASA Technical Reports Server (NTRS)

    Dugal-Whitehead, Norma R.; Lollar, Louis F.

    1990-01-01

    The NASA Marshall Space Flight Center proposes to implement computer-controlled fault injection into an electrical power system breadboard to study the reactions of the various control elements of this breadboard. Elements under study include the remote power controllers, the algorithms in the control computers, and the artificially intelligent control programs resident in this breadboard. To this end, a study of electrical power system faults is being performed to yield a list of the most common power system faults. The results of this study will be applied to a multichannel high-voltage DC spacecraft power system called the large autonomous spacecraft electrical power system (LASEPS) breadboard. The results of the power system fault study and the planned implementation of these faults into the LASEPS breadboard are described.

  1. Polyscale, polymodal fault geometries: evolution and predictive capability

    NASA Astrophysics Data System (ADS)

    Blenkinsop, T. G.; Carvell, J.; Clarke, G.; Tonelli, M.

    2012-12-01

    The Late Permian Rangal coal measures on the edge of the Nebo synclinorium in the Bowen basin, NE Queensland, Australia, are cut by normal faults. Mining operations allow 13 faults to be mapped in some detail to depths of 200m. These faults cut Tertiary intrusions and a reverse fault as well as the coal seams, and show no obvious signs of reactivation. The steeply dipping faults are clustered into groups of two to four, separated by hundreds of meters. The faults trend ENE and NE; both trends of faults dip in both directions, defining a quadrimodal geometry. The odd axis construction for these faults suggests that vertical shortening was accompanied by horizontal extension along both principal directions of 153° and 063°. The mapped extents of the faults are limited by erosion and the depth to which the faults have been drilled, but displacement profiles along the lengths of the faults show maxima within the fault planes. The displacement profiles suggest that the currently mapped faults have similar lengths to the total preserved lengths of the faults, and that they will continue into the unmined ground to a limited, but predictable extent. The fault planes have a complex geometry, with segments of individual faults showing a similar variability in orientation to the ensemble of fault planes: the fault planes themselves are polymodal. Displacement profiles show a good correlation with segment orientation. An odd axis construction based on fault segments, rather than individual faults, gives principal extension directions within 4° of the above results. The variable orientation of fault segments, the correlation of the displacement profiles with fault orientation, and the similarity between the segment and ensemble fault kinematics suggest that the faults have evolved by propagation and linking of smaller polymodal faults in the same bulk strain field.ross section of polymodal fault at Hail Creek coal mine

  2. DC-Powered Jumping Ring

    ERIC Educational Resources Information Center

    Jeffery, Rondo N.; Farhang, Amiri

    2016-01-01

    The classroom jumping ring demonstration is nearly always performed using alternating current (AC), in which the ring jumps or flies off the extended iron core when the switch is closed. The ring jumps higher when cooled with liquid nitrogen (LN2). We have performed experiments using DC to power the solenoid and find similarities and significant…

  3. The role of fluid pressure in fault creep vs. frictional instability: insights from rock deformation experiments on carbonates

    NASA Astrophysics Data System (ADS)

    Scuderi, Marco M.; Collettini, Cristiano

    2016-04-01

    Fluid overpressure is one of the primary mechanisms for tectonic fault slip. This mechanism is appealing as fluids lubricate the fault and fluid pressure, Pf, reduces the effective normal stress that holds the fault in place. However, current models of earthquake nucleation imply that stable sliding is favored by the increase of pore fluid pressure. Despite this opposite effects, currently, there are only a few studies on the role of fluid pressure under controlled, laboratory conditions. Here, we use laboratory experiments, conducted on a biaxial apparatus within a pressure vessel on limestone fault gouge, to: 1) evaluate the rate- and state- friction parameters as the pore fluid pressure is increased from hydrostatic to near lithostatic values and 2) fault creep evolution as a function of a step increase in fluid pressure. In this second suite of experiments we reached 85% of the maximum shear strength and than in load control we induced fault slip by increasing fluid pressure. Our data show that the friction rate parameter (a-b) evolves from slightly velocity strengthening to velocity neutral behaviour and the critical slip distance, Dc, decreases from about 100 to 20 μm as the pore fluid pressure is increased. Fault creep is slow (i.e 0.001μm/s) away from the maximum shear strength and for small increases in fluid pressure and it accelerates near the maximum shear strength and for larger fluid pressure build-ups, where we observe episodic accelerations/decelerations that in some cases evolve to small dynamic events. Our data suggest that fluid overpressure can increase aseismic creep with the development of frictional instability. Since fault rheology and fault stability parameters change with fluid pressure, we suggest that a comprehensive characterization of these parameters is fundamental for better assessing the role of fluid pressure in natural and human induced earthquakes.

  4. Nonlinear Phenomena and Resonant Parametric Perturbation Control in QR-ZCS Buck DC-DC Converters

    NASA Astrophysics Data System (ADS)

    Hsieh, Fei-Hu; Liu, Feng-Shao; Hsieh, Hui-Chang

    The purpose of this study is to investigate the chaotic phenomena and to control in current-mode controlled quasi-resonant zero-current-switching (QR-ZCS) DC-DC buck converters, and to present control of chaos by resonant parametric perturbation control methods. First of all, MATLAB/SIMULINK is used to derive a mathematical model for QR-ZCS DC-DC buck converters, and to simulate the converters to observe the waveform of output voltages, inductance currents and phase-plane portraits from the period-doubling bifurcation to chaos by changing the load resistances. Secondly, using resonant parametric perturbation control in QR-ZCS buck DC-DC converters, the simulation results of the chaotic converter form chaos state turn into stable state period 1, and improve ripple amplitudes of converters under the chaos, to verify the validity of the proposes method.

  5. Current sensor

    DOEpatents

    Yakymyshyn, Christopher Paul; Brubaker, Michael Allen; Yakymyshyn, Pamela Jane

    2007-01-16

    A current sensor is described that uses a plurality of magnetic field sensors positioned around a current carrying conductor. The sensor can be hinged to allow clamping to a conductor. The current sensor provides high measurement accuracy for both DC and AC currents, and is substantially immune to the effects of temperature, conductor position, nearby current carrying conductors and aging.

  6. A High Voltage Ratio and Low Ripple Interleaved DC-DC Converter for Fuel Cell Applications

    PubMed Central

    Chang, Long-Yi; Chao, Kuei-Hsiang; Chang, Tsang-Chih

    2012-01-01

    This paper proposes a high voltage ratio and low ripple interleaved boost DC-DC converter, which can be used to reduce the output voltage ripple. This converter transfers the low DC voltage of fuel cell to high DC voltage in DC link. The structure of the converter is parallel with two voltage-doubler boost converters by interleaving their output voltages to reduce the voltage ripple ratio. Besides, it can lower the current stress for the switches and inductors in the system. First, the PSIM software was used to establish a proton exchange membrane fuel cell and a converter circuit model. The simulated and measured results of the fuel cell output characteristic curve are made to verify the correctness of the established simulation model. In addition, some experimental results are made to validate the effectiveness in improving output voltage ripple of the proposed high voltage ratio interleaved boost DC-DC converters. PMID:23365536

  7. A high voltage ratio and low ripple interleaved DC-DC converter for fuel cell applications.

    PubMed

    Chang, Long-Yi; Chao, Kuei-Hsiang; Chang, Tsang-Chih

    2012-01-01

    This paper proposes a high voltage ratio and low ripple interleaved boost DC-DC converter, which can be used to reduce the output voltage ripple. This converter transfers the low DC voltage of fuel cell to high DC voltage in DC link. The structure of the converter is parallel with two voltage-doubler boost converters by interleaving their output voltages to reduce the voltage ripple ratio. Besides, it can lower the current stress for the switches and inductors in the system. First, the PSIM software was used to establish a proton exchange membrane fuel cell and a converter circuit model. The simulated and measured results of the fuel cell output characteristic curve are made to verify the correctness of the established simulation model. In addition, some experimental results are made to validate the effectiveness in improving output voltage ripple of the proposed high voltage ratio interleaved boost DC-DC converters. PMID:23365536

  8. Inrush Current Control Circuit

    NASA Technical Reports Server (NTRS)

    Cole, Steven W. (Inventor)

    2002-01-01

    An inrush current control circuit having an input terminal connected to a DC power supply and an output terminal connected to a load capacitor limits the inrush current that charges up the load capacitor during power up of a system. When the DC power supply applies a DC voltage to the input terminal, the inrush current control circuit produces a voltage ramp at the load capacitor instead of an abrupt DC voltage. The voltage ramp results in a constant low level current to charge up the load capacitor, greatly reducing the current drain on the DC power supply.

  9. Arc fault detection system

    DOEpatents

    Jha, K.N.

    1999-05-18

    An arc fault detection system for use on ungrounded or high-resistance-grounded power distribution systems is provided which can be retrofitted outside electrical switchboard circuits having limited space constraints. The system includes a differential current relay that senses a current differential between current flowing from secondary windings located in a current transformer coupled to a power supply side of a switchboard, and a total current induced in secondary windings coupled to a load side of the switchboard. When such a current differential is experienced, a current travels through a operating coil of the differential current relay, which in turn opens an upstream circuit breaker located between the switchboard and a power supply to remove the supply of power to the switchboard. 1 fig.

  10. Arc fault detection system

    DOEpatents

    Jha, Kamal N.

    1999-01-01

    An arc fault detection system for use on ungrounded or high-resistance-grounded power distribution systems is provided which can be retrofitted outside electrical switchboard circuits having limited space constraints. The system includes a differential current relay that senses a current differential between current flowing from secondary windings located in a current transformer coupled to a power supply side of a switchboard, and a total current induced in secondary windings coupled to a load side of the switchboard. When such a current differential is experienced, a current travels through a operating coil of the differential current relay, which in turn opens an upstream circuit breaker located between the switchboard and a power supply to remove the supply of power to the switchboard.

  11. DC source assemblies

    DOEpatents

    Campbell, Jeremy B; Newson, Steve

    2013-02-26

    Embodiments of DC source assemblies of power inverter systems of the type suitable for deployment in a vehicle having an electrically grounded chassis are provided. An embodiment of a DC source assembly comprises a housing, a DC source disposed within the housing, a first terminal, and a second terminal. The DC source also comprises a first capacitor having a first electrode electrically coupled to the housing, and a second electrode electrically coupled to the first terminal. The DC source assembly further comprises a second capacitor having a first electrode electrically coupled to the housing, and a second electrode electrically coupled to the second terminal.

  12. Federal Child Care Policy. Current and Proposed. Family Impact Seminar (Washington, D.C., April 28, 1989). Meeting Highlights and Background Briefing Report.

    ERIC Educational Resources Information Center

    Ooms, Theodora; Herendeen, Lisa

    The purpose of this policy seminar, one of a series of family impact seminars, was to consider current and proposed policies of the federal government that concern child care. This document provides highlights of presentations by the seminar panelists and a background briefing report prepared before the meeting. The highlights section summarizes:…

  13. Current Issues in Mental Retardation and Human Development: Selected Papers from the 1970 Staff Development Conferences of the President's Committee on Mental Retardation (Washington, D.C., 1971).

    ERIC Educational Resources Information Center

    Stedman, Donald J., Ed.

    Six papers discuss some of the current issues in the field of mental retardation and human development. Epidemiology of mental retardation from a sociological and clinical point of view is analyzed by Jane R. Mercer, based on studies of mental retardation in the community in Pomona, California. The role of genetics and intra-uterine diagnosis of…

  14. Current level detector

    DOEpatents

    Kerns, Cordon R.

    1977-01-01

    A device is provided for detecting the current level of a DC signal. It includes an even harmonic modulator to which a reference AC signal is applied. The unknown DC signal acts on the reference AC signal so that the output of the modulator includes an even harmonic whose amplitude is proportional to the unknown DC current.

  15. High concentration effects of neutral-potential-well interface traps on recombination dc current-voltage lineshape in metal-oxide-silicon transistors

    NASA Astrophysics Data System (ADS)

    Chen, Zuhui; Jie, Bin B.; Sah, Chih-Tang

    2008-11-01

    Steady-state Shockley-Read-Hall kinetics is employed to explore the high concentration effect of neutral-potential-well interface traps on the electron-hole recombination direct-current current-voltage (R-DCIV) properties in metal-oxide-silicon field-effect transistors. Extensive calculations include device parameter variations in neutral-trapping-potential-well electron interface-trap density NET (charge states 0 and -1), dopant impurity concentration PIM, oxide thickness Xox, forward source/drain junction bias VPN, and transistor temperature T. It shows significant distortion of the R-DCIV lineshape by the high concentrations of the interface traps. The result suggests that the lineshape distortion observed in past experiments, previously attributed to spatial variation in surface impurity concentration and energy distribution of interface traps in the silicon energy gap, can also arise from interface-trap concentration along surface channel region.

  16. Dynamic Fault Detection Chassis

    SciTech Connect

    Mize, Jeffery J

    2007-01-01

    Abstract The high frequency switching megawatt-class High Voltage Converter Modulator (HVCM) developed by Los Alamos National Laboratory for the Oak Ridge National Laboratory's Spallation Neutron Source (SNS) is now in operation. One of the major problems with the modulator systems is shoot-thru conditions that can occur in a IGBTs H-bridge topology resulting in large fault currents and device failure in a few microseconds. The Dynamic Fault Detection Chassis (DFDC) is a fault monitoring system; it monitors transformer flux saturation using a window comparator and dV/dt events on the cathode voltage caused by any abnormality such as capacitor breakdown, transformer primary turns shorts, or dielectric breakdown between the transformer primary and secondary. If faults are detected, the DFDC will inhibit the IGBT gate drives and shut the system down, significantly reducing the possibility of a shoot-thru condition or other equipment damaging events. In this paper, we will present system integration considerations, performance characteristics of the DFDC, and discuss its ability to significantly reduce costly down time for the entire facility.

  17. From fissure to fault: A model of fault growth in the Krafla Fissure System, NE Iceland

    NASA Astrophysics Data System (ADS)

    Bramham, Emma; Paton, Douglas; Wright, Tim

    2015-04-01

    Current models of fault growth examine the relationship of fault length (L) to vertical displacement (D) where the faults exhibit the classic fault shape of gradually increasing vertical displacement from zero at the fault tips to a maximum displacement (Dmax) at the middle of the fault. These models cannot adequately explain displacement-length observations at the Krafla fissure swarm, in Iceland's northern volcanic zone, where we observe that many of the faults with significant vertical displacements still retain fissure-like features, with no vertical displacement, along portions of their lengths. We have created a high resolution digital elevation model (DEM) of the Krafla region using airborne LiDAR and measured the displacement/length profiles of 775 faults, with lengths ranging from 10s to 1000s of metres. We have categorised the faults based on the proportion of the profile that was still fissure-like. Fully-developed faults (no fissure-like regions) were further grouped into those with profiles that had a flat-top geometry (i.e. significant proportion of fault length with constant throw), those with a bell-shaped throw profile and those that show regions of fault linkage. We suggest that a fault can most easily accommodate stress by displacing regions that are still fissure-like, and that a fault would be more likely to accommodate stress by linkage once it has reached the maximum displacement for its fault length. Our results demonstrate that there is a pattern of growth from fissure to fault in the Dmax/L ratio of the categorised faults and propose a model for this growth. These data better constrain our understanding of how fissures develop into faults but also provide insights into the discrepancy in D/L profiles from a typical bell-shaped distribution.

  18. Perspective View, Garlock Fault

    NASA Technical Reports Server (NTRS)

    2000-01-01

    California's Garlock Fault, marking the northwestern boundary of the Mojave Desert, lies at the foot of the mountains, running from the lower right to the top center of this image, which was created with data from NASA's shuttle Radar Topography Mission (SRTM), flown in February 2000. The data will be used by geologists studying fault dynamics and landforms resulting from active tectonics. These mountains are the southern end of the Sierra Nevada and the prominent canyon emerging at the lower right is Lone Tree canyon. In the distance, the San Gabriel Mountains cut across from the leftside of the image. At their base lies the San Andreas Fault which meets the Garlock Fault near the left edge at Tejon Pass. The dark linear feature running from lower right to upper left is State Highway 14 leading from the town of Mojave in the distance to Inyokern and the Owens Valley in the north. The lighter parallel lines are dirt roads related to power lines and the Los Angeles Aqueduct which run along the base of the mountains.

    This type of display adds the important dimension of elevation to the study of land use and environmental processes as observed in satellite images. The perspective view was created by draping a Landsat satellite image over an SRTM elevation model. Topography is exaggerated 1.5 times vertically. The Landsat image was provided by the United States Geological Survey's Earth Resources Observations Systems (EROS) Data Center, Sioux Falls, South Dakota.

    Elevation data used in this image was acquired by the Shuttle Radar Topography Mission (SRTM) aboard the Space Shuttle Endeavour, launched on February 11,2000. SRTM used the same radar instrument that comprised the Spaceborne Imaging Radar-C/X-Band Synthetic Aperture Radar (SIR-C/X-SAR) that flew twice on the Space Shuttle Endeavour in 1994. SRTM was designed to collect three-dimensional measurements of the Earth's surface. To collect the 3-D data, engineers added a 60-meter-long (200-foot) mast

  19. Radiation effects on DC-DC Converters

    NASA Technical Reports Server (NTRS)

    Zhang, Dexin; Attia, John O.; Kankam, Mark D. (Technical Monitor)

    2000-01-01

    DC-DC switching converters are circuits that can be used to convert a DC voltage of one value to another by switching action. They are increasing being used in space systems. Most of the popular DC-DC switching converters utilize power MOSFETs. However power MOSFETs, when subjected to radiation, are susceptible to degradation of device characteristics or catastrophic failure. This work focuses on the effects of total ionizing dose on converter performance. Four fundamental switching converters (buck converter, buck-boost converter, cuk converter, and flyback converter) were built using Harris IRF250 power MOSFETs. These converters were designed for converting an input of 60 volts to an output of about 12 volts with a switching frequency of 100 kHz. The four converters were irradiated with a Co-60 gamma source at dose rate of 217 rad/min. The performances of the four converters were examined during the exposure to the radiation. The experimental results show that the output voltage of the converters increases as total dose increases. However, the increases of the output voltage were different for the four different converters, with the buck converter and cuk converter the highest and the flyback converter the lowest. We observed significant increases in output voltage for cuk converter at a total dose of 24 krad (si).

  20. Subaru FATS (fault tracking system)

    NASA Astrophysics Data System (ADS)

    Winegar, Tom W.; Noumaru, Junichi

    2000-07-01

    The Subaru Telescope requires a fault tracking system to record the problems and questions that staff experience during their work, and the solutions provided by technical experts to these problems and questions. The system records each fault and routes it to a pre-selected 'solution-provider' for each type of fault. The solution provider analyzes the fault and writes a solution that is routed back to the fault reporter and recorded in a 'knowledge-base' for future reference. The specifications of our fault tracking system were unique. (1) Dual language capacity -- Our staff speak both English and Japanese. Our contractors speak Japanese. (2) Heterogeneous computers -- Our computer workstations are a mixture of SPARCstations, Macintosh and Windows computers. (3) Integration with prime contractors -- Mitsubishi and Fujitsu are primary contractors in the construction of the telescope. In many cases, our 'experts' are our contractors. (4) Operator scheduling -- Our operators spend 50% of their work-month operating the telescope, the other 50% is spent working day shift at the base facility in Hilo, or day shift at the summit. We plan for 8 operators, with a frequent rotation. We need to keep all operators informed on the current status of all faults, no matter the operator's location.

  1. Parallel fault-tolerant robot control

    NASA Technical Reports Server (NTRS)

    Hamilton, D. L.; Bennett, J. K.; Walker, I. D.

    1992-01-01

    A shared memory multiprocessor architecture is used to develop a parallel fault-tolerant robot controller. Several versions of the robot controller are developed and compared. A robot simulation is also developed for control observation. Comparison of a serial version of the controller and a parallel version without fault tolerance showed the speedup possible with the coarse-grained parallelism currently employed. The performance degradation due to the addition of processor fault tolerance was demonstrated by comparison of these controllers with their fault-tolerant versions. Comparison of the more fault-tolerant controller with the lower-level fault-tolerant controller showed how varying the amount of redundant data affects performance. The results demonstrate the trade-off between speed performance and processor fault tolerance.

  2. The application of standardized control and interface circuits to three dc to dc power converters.

    NASA Technical Reports Server (NTRS)

    Yu, Y.; Biess, J. J.; Schoenfeld, A. D.; Lalli, V. R.

    1973-01-01

    Standardized control and interface circuits were applied to the three most commonly used dc to dc converters: the buck-boost converter, the series-switching buck regulator, and the pulse-modulated parallel inverter. The two-loop ASDTIC regulation control concept was implemented by using a common analog control signal processor and a novel digital control signal processor. This resulted in control circuit standardization and superior static and dynamic performance of the three dc-to-dc converters. Power components stress control, through active peak current limiting and recovery of switching losses, was applied to enhance reliability and converter efficiency.

  3. DC-Powered Jumping Ring

    NASA Astrophysics Data System (ADS)

    Jeffery, Rondo N.; Amiri, Farhang

    2016-02-01

    The classroom jumping ring demonstration is nearly always performed using alternating current (AC), in which the ring jumps or flies off the extended iron core when the switch is closed. The ring jumps higher when cooled with liquid nitrogen (LN2). We have performed experiments using DC to power the solenoid and find similarities and significant differences from the AC case. In particular, the ring does not fly off the core but rises a short distance and then falls back. If the ring jumps high enough, the rising and the falling motion of the ring does not follow simple vertical motion of a projectile. This indicates that there are additional forces on the ring in each part of its motion. Four possible stages of the motion of the ring with DC are identified, which result from the ring current changing directions during the jump in response to a changing magnetic flux through the moving ring.

  4. High power density dc/dc converter: Selection of converter topology

    NASA Technical Reports Server (NTRS)

    Divan, Deepakraj M.

    1990-01-01

    The work involved in the identification and selection of a suitable converter topology is described. Three new dc/dc converter topologies are proposed: Phase-Shifted Single Active Bridge DC/DC Converter; Single Phase Dual Active Bridges DC/DC Converter; and Three Phase Dual Active Bridges DC/DC Converter (Topology C). The salient features of these topologies are: (1) All are minimal in structure, i.e., each consists of an input and output bridge, input and output filter and a transformer, all components essential for a high power dc/dc conversion process; (2) All devices of both the bridges can operate under near zero-voltage conditions, making possible a reduction of device switching losses and hence, an increase in switching frequency; (3) All circuits operate at a constant frequency, thus simplifying the task of the magnetic and filter elements; (4) Since, the leakage inductance of the transformer is used as the main current transfer element, problems associated with the diode reverse recovery are eliminated. Also, this mode of operation allows easy paralleling of multiple modules for extending the power capacity of the system; (5) All circuits are least sensitive to parasitic impedances, infact the parasitics are efficently utilized; and (6) The soft switching transitions, result in low electromagnetic interference. A detailed analysis of each topology was carried out. Based on the analysis, the various device and component ratings for each topology operating at an optimum point, and under the given specifications, are tabulated and discussed.

  5. Single Event Burnout in DC-DC Converters for the LHC Experiments

    SciTech Connect

    Claudio H. Rivetta et al.

    2001-09-24

    High voltage transistors in DC-DC converters are prone to catastrophic Single Event Burnout in the LHC radiation environment. This paper presents a systematic methodology to analyze single event effects sensitivity in converters and proposes solutions based on de-rating input voltage and output current or voltage.

  6. Mesoscopic electronics beyond DC transport

    NASA Astrophysics Data System (ADS)

    di Carlo, Leonardo

    Since the inception of mesoscopic electronics in the 1980's, direct current (dc) measurements have underpinned experiments in quantum transport. Novel techniques complementing dc transport are becoming paramount to new developments in mesoscopic electronics, particularly as the road is paved toward quantum information processing. This thesis describes seven experiments on GaAs/AlGaAs and graphene nanostructures unified by experimental techniques going beyond traditional dc transport. Firstly, dc current induced by microwave radiation applied to an open chaotic quantum dot is investigated. Asymmetry of mesoscopic fluctuations of induced current in perpendicular magnetic field is established as a tool for separating the quantum photovoltaic effect from classical rectification. A differential charge sensing technique is next developed using integrated quantum point contacts to resolve the spatial distribution of charge inside a double quantum clot. An accurate method for determining interdot tunnel coupling and electron temperature using charge sensing is demonstrated. A two-channel system for detecting current noise in mesoscopic conductors is developed, enabling four experiments where shot noise probes transmission properties not available in dc transport and Johnson noise serves as an electron thermometer. Suppressed shot noise is observed in quantum point contacts at zero parallel magnetic field, associated with the 0.7 structure in conductance. This suppression evolves with increasing field into the shot-noise signature of spin-lifted mode degeneracy. Quantitative agreement is found with a phenomenological model for density-dependent mode splitting. Shot noise measurements of multi-lead quantum-dot structures in the Coulomb blockade regime distill the mechanisms by which Coulomb interaction and quantum indistinguishability correlate electron flow. Gate-controlled sign reversal of noise cross correlation in two capacitively-coupled dots is observed, and shown to

  7. Test Results of Selected Commercial DC/DC Converters under Cryogenic Temperatures - A Digest

    NASA Technical Reports Server (NTRS)

    Patterson, Richard; Hammoud, Ahmad

    2010-01-01

    DC/DC converters are widely used in space power systems in the areas of power management and distribution, signal conditioning, and motor control. Design of DC/DC converters to survive cryogenic temperatures will improve the power system performance, simplify design, and reduce development and launch costs. In this work, the performance of nine COTS modular, low-tomedium power DC/DC converters was investigated under cryogenic temperatures. The converters were evaluated in terms of their output regulation, efficiency, and input and output currents. At a given temperature, these properties were obtained at various input voltages and at different load levels. A summary on the performance of the tested converters was given. More comprehensive testing and in-depth analysis of performance under long-term exposure to extreme temperatures are deemed necessary to establish the suitability of these and other devices for use in the harsh environment of space exploration missions.

  8. Transform fault earthquakes in the North Atlantic: Source mechanisms and depth of faulting

    NASA Technical Reports Server (NTRS)

    Bergman, Eric A.; Solomon, Sean C.

    1987-01-01

    The centroid depths and source mechanisms of 12 large earthquakes on transform faults of the northern Mid-Atlantic Ridge were determined from an inversion of long-period body waveforms. The earthquakes occurred on the Gibbs, Oceanographer, Hayes, Kane, 15 deg 20 min, and Vema transforms. The depth extent of faulting during each earthquake was estimated from the centroid depth and the fault width. The source mechanisms for all events in this study display the strike slip motion expected for transform fault earthquakes; slip vector azimuths agree to 2 to 3 deg of the local strike of the zone of active faulting. The only anomalies in mechanism were for two earthquakes near the western end of the Vema transform which occurred on significantly nonvertical fault planes. Secondary faulting, occurring either precursory to or near the end of the main episode of strike-slip rupture, was observed for 5 of the 12 earthquakes. For three events the secondary faulting was characterized by reverse motion on fault planes striking oblique to the trend of the transform. In all three cases, the site of secondary reverse faulting is near a compression jog in the current trace of the active transform fault zone. No evidence was found to support the conclusions of Engeln, Wiens, and Stein that oceanic transform faults in general are either hotter than expected from current thermal models or weaker than normal oceanic lithosphere.

  9. Radiation Effects on DC-DC Converters

    NASA Technical Reports Server (NTRS)

    Zhang, De-Xin; AbdulMazid, M. D.; Attia, John O.; Kankam, Mark D. (Technical Monitor)

    2001-01-01

    In this work, several DC-DC converters were designed and built. The converters are Buck Buck-Boost, Cuk, Flyback, and full-bridge zero-voltage switched. The total ionizing dose radiation and single event effects on the converters were investigated. The experimental results for the TID effects tests show that the voltages of the Buck Buck-Boost, Cuk, and Flyback converters increase as total dose increased when using power MOSFET IRF250 as a switching transistor. The change in output voltage with total dose is highest for the Buck converter and the lowest for Flyback converter. The trend of increase in output voltages with total dose in the present work agrees with those of the literature. The trends of the experimental results also agree with those obtained from PSPICE simulation. For the full-bridge zero-voltage switch converter, it was observed that the dc-dc converter with IRF250 power MOSFET did not show a significant change of output voltage with total dose. In addition, for the dc-dc converter with FSF254R4 radiation-hardened power MOSFET, the output voltage did not change significantly with total dose. The experimental results were confirmed by PSPICE simulation that showed that FB-ZVS converter with IRF250 power MOSFET's was not affected with the increase in total ionizing dose. Single Event Effects (SEE) radiation tests were performed on FB-ZVS converters. It was observed that the FB-ZVS converter with the IRF250 power MOSFET, when the device was irradiated with Krypton ion with ion-energy of 150 MeV and LET of 41.3 MeV-square cm/mg, the output voltage increased with the increase in fluence. However, for Krypton with ion-energy of 600 MeV and LET of 33.65 MeV-square cm/mg, and two out of four transistors of the converter were permanently damaged. The dc-dc converter with FSF254R4 radiation hardened power MOSFET's did not show significant change at the output voltage with fluence while being irradiated by Krypton with ion energy of 1.20 GeV and LET of 25

  10. The fault-tree compiler

    NASA Technical Reports Server (NTRS)

    Martensen, Anna L.; Butler, Ricky W.

    1987-01-01

    The Fault Tree Compiler Program is a new reliability tool used to predict the top event probability for a fault tree. Five different gate types are allowed in the fault tree: AND, OR, EXCLUSIVE OR, INVERT, and M OF N gates. The high level input language is easy to understand and use when describing the system tree. In addition, the use of the hierarchical fault tree capability can simplify the tree description and decrease program execution time. The current solution technique provides an answer precise (within the limits of double precision floating point arithmetic) to the five digits in the answer. The user may vary one failure rate or failure probability over a range of values and plot the results for sensitivity analyses. The solution technique is implemented in FORTRAN; the remaining program code is implemented in Pascal. The program is written to run on a Digital Corporation VAX with the VMS operation system.

  11. Inferred depth of creep on the Hayward Fault, central California

    USGS Publications Warehouse

    Savage, J.C.; Lisowski, M.

    1993-01-01

    A relation between creep rate at the surface trace of a fault, the depth to the bottom of the creeping zone, and the rate of stress accumulation on the fault is derived from Weertman's 1964 friction model of slip on a fault. A 5??1 km depth for the creeping zone on the Hayward fault is estimated from the measured creep rate (5mm/yr) at the fault trace and the rate of stress increase on the upper segment of the fault trace inferred from geodetic measurements across the San Francisco Bay area. Although fault creep partially accommodates the secular slip rate on the Hayward fault, a slip deficit is accumulating equivalent to a magnitude 6.6 earthquake on each 40 km segment of the fault each century. Thus, the current behavior of the fault is consistent with its seismic history, which includes two moderate earthquakes in the mid-1800s. -Authors

  12. Design and power management of an offshore medium voltage DC microgrid realized through high voltage power electronics technologies and control

    NASA Astrophysics Data System (ADS)

    Grainger, Brandon Michael

    The growth in the electric power industry's portfolio of Direct Current (DC) based generation and loads have captured the attention of many leading research institutions. Opportunities for using DC based systems have been explored in electric ship design and have been a proven, reliable solution for transmitting bulk power onshore and offshore. To integrate many of the renewable resources into our existing AC grid, a number of power conversions through power electronics are required to condition the equipment for direct connection. Within the power conversion stages, there is always a requirement to convert to or from DC. The AC microgrid is a conceptual solution proposed for integrating various types of renewable generation resources. The fundamental microgrid requirements include the capability of operating in islanding mode and/or grid connected modes. The technical challenges associated with microgrids include (1) operation modes and transitions that comply with IEEE1547 without extensive custom engineering and (2) control architecture and communication. The Medium Voltage DC (MVDC) architecture, explored by the University of Pittsburgh, can be visualized as a special type of DC microgrid. This dissertation is multi-faceted, focused on many design aspects of an offshore DC microgrid. The focal points of the discussion are focused on optimized high power, high frequency magnetic material performance in electric machines, transformers, and DC/DC power converters---all components found within offshore, power system architectures. A new controller design based upon model reference control is proposed and shown to stabilize the electric motor drives (modeled as constant power loads), which serve as the largest power consuming entities in the microgrid. The design and simulation of a state-of-the-art multilevel converter for High Voltage DC (HVDC) is discussed and a component sensitivity analysis on fault current peaks is explored. A power management routine is

  13. High impedance fault detection in low voltage networks

    SciTech Connect

    Christie, R.D. . Dept. of Electrical Engineering); Zadehgol, H.; Habib, M.M. )

    1993-10-01

    High impedance faults are those with fault current magnitude similar to load currents. Experimental results were obtained that conform operating experience that such faults can occur in the low voltage (600V and below) underground distribution networks typically found in urban power systems. These faults produce current waveforms qualitatively similar to those found on overhead feeders, but quantitatively smaller. Loose connectors can produce similar, but cleaner current characteristics. Noisy loads remain a major impediment to reliable detection. Design and installation of an inexpensive prototype fault detector on the Seattle City Light street network is described.

  14. Fault Location Methods for Ungrounded Distribution Systems Using Local Measurements

    NASA Astrophysics Data System (ADS)

    Xiu, Wanjing; Liao, Yuan

    2013-08-01

    This article presents novel fault location algorithms for ungrounded distribution systems. The proposed methods are capable of locating faults by using obtained voltage and current measurements at the local substation. Two types of fault location algorithms, using line to neutral and line to line measurements, are presented. The network structure and parameters are assumed to be known. The network structure needs to be updated based on information obtained from utility telemetry system. With the help of bus impedance matrix, local voltage changes due to the fault can be expressed as a function of fault currents. Since the bus impedance matrix contains information about fault location, superimposed voltages at local substation can be expressed as a function of fault location, through which fault location can be solved. Simulation studies have been carried out based on a sample distribution power system. From the evaluation study, it is evinced that very accurate fault location estimates are obtained from both types of methods.

  15. Design of Current Source Dc/Dc Converter for Interfacing a 5 Kw Pem Fuel Cell / Paaugstinošā Strāvas Avota Līdzsprieguma Pārveidotāja Izstrāde 5 Kw Ūdeņraža Degvielas Elementam

    NASA Astrophysics Data System (ADS)

    Andreičiks, A.; Steiks, I.; Krievs, O.

    2013-08-01

    In domestic applications the low DC output voltage of a hydrogen fuel cell used as the main power supply or a backup power source has to be matched to the level and frequency of the AC voltage of utility grid. The interfacing power converter system usually consists of a DC/DC converter and an inverter. In this work, a DC/DC step-up converter stage is designed for interfacing a 5kW proton exchange membrane (PEM) fuel cell. The losses of DC/DC conversion are estimated and, basing on the relevant analysis, the most appropriate configuration of converter modules is selected for a DC/DC converter stage of increased efficiency. The authors present the results of experimental analysis and simulation for the selected configuration of four double inductor step-up push-pull converter modules Ūdeņraža degvielas elementa invertoru sistēmas mājsaimniecības pielietojumiem parasti sastāv no līdzsprieguma paaugstināšanas un invertēšanas mezgliem. Šis raksts ir veltīts paaugstinošā līdzsprieguma pārveidotāja izstrādei 5 kW protonu apmaiņas membrānas degvielas elementam. Rakstā izpētīts divu induktoru divtaktu strāvas avota paaugstinošais līdzsprieguma pārveidotājs, aplūkojot gan datormodelēšanas, gan eksperimentālos rezultātus. Lai palielinātu DC/DC pārveidotāja efektivitāti var izmantot vairākus pārveidotāja moduļus, kam ieejas savienotas paralēli un izejās - virkne. Analīze Šajā raksta ir veikta analīze, balstoties uz kuras var izvēlieties skaitu pārveidotāj moduļu skaitu, kuri nodrošina vislabāko efektivitāti DC/DC pārveidotāja posmā. Kopējais eksperimentāli noteiktais izstrādātās degvielas elementa pārveidotāju sistēmas fizikālā modeļa lietderības koeficients ir 93%

  16. Has the San Gabriel fault been offset

    SciTech Connect

    Sheehan, J.R.

    1988-03-01

    The San Gabriel fault (SGF) in southern California is a right-lateral, strike-slip fault extending for 85 mi in an arcuate, southwestward-bowing curve from near the San Andreas fault at Frazier Mountain to its intersection with the left-lateral San Antonio Canyon fault (SACF) in the eastern San Gabriel Mountains. Termination of the SGF at the presently active SACF is abrupt and prompts the question Has the San Gabriel Fault been offset. Tectonic and geometric relationships in the area suggest that the SGF has been offset approximately 6 mi in a left-lateral sense and that the offset continuation of the SGF, across the SACF, is the right-lateral, strike-slip San Jacinto fault (SJF), which also terminates at the SACF. Reversing the left-lateral movement on the SACF to rejoin the offset ends of the SGF and SJF reveals a fault trace that is remarkably similar in geometry and movement (and perhaps in tectonic history), to the trace of the San Andreas fault through the southern part of the San Bernardino Mountains. The relationship of the Sierra Madre-Cucamonga fault system to the restored SGF-SJF fault is strikingly similar to the relationship of the Banning fault to the Mission Creek-Mill Creek portion of the San Andreas fault. Structural relations suggest that the San Gabriel-San Jacinto system predates the San Andreas fault in the eastern San Gabriel Mountains and that continuing movement on the SACF is currently affecting the trace of the San Andreas fault in the Cajon Pass area.

  17. Fault slip distribution and fault roughness

    NASA Astrophysics Data System (ADS)

    Candela, Thibault; Renard, François; Schmittbuhl, Jean; Bouchon, Michel; Brodsky, Emily E.

    2011-11-01

    We present analysis of the spatial correlations of seismological slip maps and fault topography roughness, illuminating their identical self-affine exponent. Though the complexity of the coseismic spatial slip distribution can be intuitively associated with geometrical or stress heterogeneities along the fault surface, this has never been demonstrated. Based on new measurements of fault surface topography and on statistical analyses of kinematic inversions of slip maps, we propose a model, which quantitatively characterizes the link between slip distribution and fault surface roughness. Our approach can be divided into two complementary steps: (i) Using a numerical computation, we estimate the influence of fault roughness on the frictional strength (pre-stress). We model a fault as a rough interface where elastic asperities are squeezed. The Hurst exponent ?, characterizing the self-affinity of the frictional strength field, approaches ?, where ? is the roughness exponent of the fault surface in the direction of slip. (ii) Using a quasi-static model of fault propagation, which includes the effect of long-range elastic interactions and spatial correlations in the frictional strength, the spatial slip correlation is observed to scale as ?, where ? represents the Hurst exponent of the slip distribution. Under the assumption that the origin of the spatial fluctuations in frictional strength along faults is the elastic squeeze of fault asperities, we show that self-affine geometrical properties of fault surface roughness control slip correlations and that ?. Given that ? for a wide range of faults (various accumulated displacement, host rock and slip movement), we predict that ?. Even if our quasi-static fault model is more relevant for creeping faults, the spatial slip correlations observed are consistent with those of seismological slip maps. A consequence is that the self-affinity property of slip roughness may be explained by fault geometry without considering

  18. Flight elements: Fault detection and fault management

    NASA Technical Reports Server (NTRS)

    Lum, H.; Patterson-Hine, A.; Edge, J. T.; Lawler, D.

    1990-01-01

    Fault management for an intelligent computational system must be developed using a top down integrated engineering approach. An approach proposed includes integrating the overall environment involving sensors and their associated data; design knowledge capture; operations; fault detection, identification, and reconfiguration; testability; causal models including digraph matrix analysis; and overall performance impacts on the hardware and software architecture. Implementation of the concept to achieve a real time intelligent fault detection and management system will be accomplished via the implementation of several objectives, which are: Development of fault tolerant/FDIR requirement and specification from a systems level which will carry through from conceptual design through implementation and mission operations; Implementation of monitoring, diagnosis, and reconfiguration at all system levels providing fault isolation and system integration; Optimize system operations to manage degraded system performance through system integration; and Lower development and operations costs through the implementation of an intelligent real time fault detection and fault management system and an information management system.

  19. Preparative separation of 1,3,6-pyrenetrisulfonic acid trisodium salt from the color additive D&C Green No. 8 (pyranine) by pH-zone-refining counter-current chromatography.

    PubMed

    Weisz, Adrian; Mazzola, Eugene P; Ito, Yoichiro

    2011-11-11

    In developing analytical methods for batch certification of the color additive D&C Green No. 8 (G8), the U.S. Food and Drug Administration needed the trisodium salt of 1,3,6-pyrenetrisulfonic acid (P3S) for use as a reference material. Since P3S was not commercially available, preparative quantities of it were separated from portions of a sample of G8 that contained ∼3.5% P3S. The separations were performed by pH-zone-refining counter-current chromatography using dodecylamine (DA) as the hydrophobic counterion. The added DA enabled partitioning of the polysulfonated components into the organic stationary phase of the two-phase solvent system used, 1-butanol-water (1:1). Thus, a typical separation that involved 20.3g of G8, using sulfuric acid as the retainer acid and 20% DA in the stationary phase and 0.1M sodium hydroxide as the mobile phase, resulted in ∼0.58 g of P3S of greater than 99% purity. The identification and characterization of the separated P3S were performed by elemental analyses, proton nuclear magnetic resonance, high-resolution mass spectrometry, ultra-violet spectra, and high-performance liquid chromatography. PMID:21982993

  20. Preparative separation of 1,3,6-pyrenetrisulfonic acid trisodium salt from the color additive D&C Green No. 8 by affinity-ligand pH-zone-refining counter-current chromatography

    PubMed Central

    Weisz, Adrian; Mazzola, Eugene P.; Ito, Yoichiro

    2011-01-01

    In developing analytical methods for batch certification of the color additive D&C Green No. 8 (G8), the U.S. Food and Drug Administration needed the trisodium salt of 1,3,6-pyrenetrisulfonic acid (P3S) for use as a reference material. Since P3S was not commercially available, preparative quantities of it were separated from portions of a sample of G8 that contained ~ 3.5% P3S. The separations were performed by affinity-ligand pH-zone-refining counter-current chromatography using dodecylamine (DA) as the ligand. The added ligand enabled partitioning of the polysulfonated components into the organic stationary phase of the two-phase solvent system used, 1-butanol – water (1:1). A typical separation that involved 20.3 g of G8, using sulfuric acid as the retainer acid and 20% DA in the stationary phase and 0.1M sodium hydroxide as the mobile phase, resulted in ~0.58 g of P3S of greater than 99% purity. The identification and characterization of the separated P3S were performed by proton nuclear magnetic resonance, high-resolution mass spectrometry, ultra-violet spectra and high-performance liquid chromatography. PMID:21982993

  1. Fault damage zones

    NASA Astrophysics Data System (ADS)

    Kim, Young-Seog; Peacock, David C. P.; Sanderson, David J.

    2004-03-01

    Damage zones show very similar geometries across a wide range of scales and fault types, including strike-slip, normal and thrust faults. We use a geometric classification of damage zones into tip-, wall-, and linking-damage zones, based on their location around faults. These classes can be sub-divided in terms of fault and fracture patterns within the damage zone. A variety of damage zone structures can occur at mode II tips of strike-slip faults, including wing cracks, horsetail fractures, antithetic faults, and synthetic branch faults. Wall damage zones result from the propagation of mode II and mode III fault tips through a rock, or from damage associated with the increase in slip on a fault. Wall damage zone structures include extension fractures, antithetic faults, synthetic faults, and rotated blocks with associated triangular openings. The damage formed at the mode III tips of strike-slip faults (e.g. observed in cliff sections) are classified as wall damage zones, because the damage zone structures are distributed along a fault trace in map view. Mixed-mode tips are likely to show characteristics of both mode II and mode III tips. Linking damage zones are developed at steps between two sub-parallel faults, and the structures developed depend on whether the step is extensional or contractional. Extension fractures and pull-aparts typically develop in extensional steps, whilst solution seams, antithetic faults and synthetic faults commonly develop in contractional steps. Rotated blocks, isolated lenses or strike-slip duplexes may occur in both extensional and contractional steps. Damage zone geometries and structures are strongly controlled by the location around a fault, the slip mode at a fault tip, and by the evolutionary stage of the fault. Although other factors control the nature of damage zones (e.g. lithology, rheology and stress system), the three-dimensional fault geometry and slip mode at each tip must be considered to gain an understanding of

  2. Radiation-Tolerant DC-DC Converters

    NASA Technical Reports Server (NTRS)

    Skutt, Glenn; Sable, Dan; Leslie, Leonard; Graham, Shawn

    2012-01-01

    A document discusses power converters suitable for space use that meet the DSCC MIL-PRF-38534 Appendix G radiation hardness level P classification. A method for qualifying commercially produced electronic parts for DC-DC converters per the Defense Supply Center Columbus (DSCC) radiation hardened assurance requirements was developed. Development and compliance testing of standard hybrid converters suitable for space use were completed for missions with total dose radiation requirements of up to 30 kRad. This innovation provides the same overall performance as standard hybrid converters, but includes assurance of radiation- tolerant design through components and design compliance testing. This availability of design-certified radiation-tolerant converters can significantly reduce total cost and delivery time for power converters for space applications that fit the appropriate DSCC classification (30 kRad).

  3. Dynamic Behavior of a 21-Level (Line-to-Line) BTB System Based on Series Connection of Sixteen Converter-Cells under a Single-Line-to-Ground Fault Condition: Experimental Verification by a 200-V, 20-kW Laboratory System

    NASA Astrophysics Data System (ADS)

    Hagiwara, Makoto; Wada, Keiji; Fujita, Hideaki; Akagi, Hirofumi

    This paper deals with the dynamic behavior of a 21-level (line-to-line) BTB system based on series connection of sixteen converter-cells under a single-line-to-ground fault condition. A laboratory system rated at 200V and 20 kW was designed and built up to confirm the validity of the system. Experimental results obtained from the system lead to the following conclusions: i) The BTB system has a capability of reducing both negative-sequence voltage and current appearing during the fault. ii) A dc-capacitor voltage regulator that has been already developed by the authors makes it possible to suppress the dc-voltage fluctuation sufficiently. iii) Flux fluctuations in transformers used for the system strongly depend on a voltage depth during the fault. These would make a significant contribution to putting the BTB system into practical use.

  4. The Curiosity Mars Rover's Fault Protection Engine

    NASA Technical Reports Server (NTRS)

    Benowitz, Ed

    2014-01-01

    The Curiosity Rover, currently operating on Mars, contains flight software onboard to autonomously handle aspects of system fault protection. Over 1000 monitors and 39 responses are present in the flight software. Orchestrating these behaviors is the flight software's fault protection engine. In this paper, we discuss the engine's design, responsibilities, and present some lessons learned for future missions.

  5. Performance of 22.4-kW nonlaminated-frame dc series motor with chopper controller. [a dc to dc voltage converter

    NASA Technical Reports Server (NTRS)

    Schwab, J. R.

    1979-01-01

    Performance data obtained through experimental testing of a 22.4 kW traction motor using two types of excitation are presented. Ripple free dc from a motor-generator set for baseline data and pulse width modulated dc as supplied by a battery pack and chopper controller were used for excitation. For the same average values of input voltage and current, the motor power output was independent of the type of excitation. However, at the same speeds, the motor efficiency at low power output (corresponding to low duty cycle of the controller) was 5 to 10 percentage points lower on chopped dc than on ripple free dc. The chopped dc locked-rotor torque was approximately 1 to 3 percent greater than the ripple free dc torque for the same average current.

  6. Effect of design variables on irreversible magnet demagnetization in brushless dc motor

    NASA Astrophysics Data System (ADS)

    Kim, Tae Heoung; Lee, Ju

    2005-05-01

    The large demagnetizing currents in brushless dc (BLdc) motor are generated by the short-circuited stator windings and the fault of a drive circuit. So, irreversible magnet demagnetization occurs due to the external demagnetizing field by these currents. In this paper, we deal with the effect of design variables on irreversible magnet demagnetization in BLdc motor through the modeling approach using a two-dimensional finite-element method (2D FEM). The nonlinear analysis of a permanent magnet is added to 2D FEM to consider irreversible demagnetization. As a result, it is shown that magnet thickness, teeth surface width, and rotor back yoke thickness are the most important geometrical dimensions of BLdc motor in terms of irreversible magnet demagnetization.

  7. Results of an electrical power system fault study

    NASA Technical Reports Server (NTRS)

    Dugal-Whitehead, Norma R.; Johnson, Yvette B.

    1992-01-01

    NASA-Marshall conducted a study of electrical power system faults with a view to the development of AI control systems for a spacecraft power system breadboard. The results of this study have been applied to a multichannel high voltage dc spacecraft power system, the Large Autonomous Spacecraft Electrical Power System (LASEPS) breadboard. Some of the faults encountered in testing LASEPS included the shorting of a bus an a falloff in battery cell capacity.

  8. Results of an electrical power system fault study

    NASA Astrophysics Data System (ADS)

    Dugal-Whitehead, Norma R.; Johnson, Yvette B.

    NASA-Marshall conducted a study of electrical power system faults with a view to the development of AI control systems for a spacecraft power system breadboard. The results of this study have been applied to a multichannel high voltage dc spacecraft power system, the Large Autonomous Spacecraft Electrical Power System (LASEPS) breadboard. Some of the faults encountered in testing LASEPS included the shorting of a bus an a falloff in battery cell capacity.

  9. Fault tolerant operation of switched reluctance machine

    NASA Astrophysics Data System (ADS)

    Wang, Wei

    experiments. With the proposed optimal waveform, torque production is greatly improved under the same Root Mean Square (RMS) current constraint. Additionally, position sensorless operation methods under phase faults are investigated to account for the combination of physical position sensor and phase winding faults. A comprehensive solution for position sensorless operation under single and multiple phases fault are proposed and validated through experiments. Continuous position sensorless operation with seamless transition between various numbers of phase fault is achieved.

  10. Gravity Compensation Technique Uses Small dc Motor

    NASA Technical Reports Server (NTRS)

    Hollow, Richard

    1988-01-01

    Small dc servomotor powered by simple constant-current source and with suitable gearing used to cancel effect of gravity upon load. Lead-screw positioning system has load counterbalanced by small supplementary motor powered by constant current source. Motor lighter and more compact alternative to counterbalance. Used in variety of mechanical systems where load positioned or accelerated in vertical plane.

  11. Paleoseismicity of two historically quiescent faults in Australia: Implications for fault behavior in stable continental regions

    USGS Publications Warehouse

    Crone, A.J.; De Martini, P. M.; Machette, M.M.; Okumura, K.; Prescott, J.R.

    2003-01-01

    Paleoseismic studies of two historically aseismic Quaternary faults in Australia confirm that cratonic faults in stable continental regions (SCR) typically have a long-term behavior characterized by episodes of activity separated by quiescent intervals of at least 10,000 and commonly 100,000 years or more. Studies of the approximately 30-km-long Roopena fault in South Australia and the approximately 30-km-long Hyden fault in Western Australia document multiple Quaternary surface-faulting events that are unevenly spaced in time. The episodic clustering of events on cratonic SCR faults may be related to temporal fluctuations of fault-zone fluid pore pressures in a volume of strained crust. The long-term slip rate on cratonic SCR faults is extremely low, so the geomorphic expression of many cratonic SCR faults is subtle, and scarps may be difficult to detect because they are poorly preserved. Both the Roopena and Hyden faults are in areas of limited or no significant seismicity; these and other faults that we have studied indicate that many potentially hazardous SCR faults cannot be recognized solely on the basis of instrumental data or historical earthquakes. Although cratonic SCR faults may appear to be nonhazardous because they have been historically aseismic, those that are favorably oriented for movement in the current stress field can and have produced unexpected damaging earthquakes. Paleoseismic studies of modern and prehistoric SCR faulting events provide the basis for understanding of the long-term behavior of these faults and ultimately contribute to better seismic-hazard assessments.

  12. Nonlinear control of voltage source converters in AC-DC power system.

    PubMed

    Dash, P K; Nayak, N

    2014-07-01

    This paper presents the design of a robust nonlinear controller for a parallel AC-DC power system using a Lyapunov function-based sliding mode control (LYPSMC) strategy. The inputs for the proposed control scheme are the DC voltage and reactive power errors at the converter station and the active and reactive power errors at the inverter station of the voltage-source converter-based high voltage direct current transmission (VSC-HVDC) link. The stability and robust tracking of the system parameters are ensured by applying the Lyapunov direct method. Also the gains of the sliding mode control (SMC) are made adaptive using the stability conditions of the Lyapunov function. The proposed control strategy offers invariant stability to a class of systems having modeling uncertainties due to parameter changes and exogenous inputs. Comprehensive computer simulations are carried out to verify the proposed control scheme under several system disturbances like changes in short-circuit ratio, converter parametric changes, and faults on the converter and inverter buses for single generating system connected to the power grid in a single machine infinite-bus AC-DC network and also for a 3-machine two-area power system. Furthermore, a second order super twisting sliding mode control scheme has been presented in this paper that provides a higher degree of nonlinearity than the LYPSMC and damps faster the converter and inverter voltage and power oscillations. PMID:24906895

  13. Intelligent dc-dc Converter Technology Developed and Tested

    NASA Technical Reports Server (NTRS)

    Button, Robert M.

    2001-01-01

    The NASA Glenn Research Center and the Cleveland State University have developed a digitally controlled dc-dc converter to research the benefits of flexible, digital control on power electronics and systems. Initial research and testing has shown that conventional dc-dc converters can benefit from improved performance by using digital-signal processors and nonlinear control algorithms.

  14. POTENTIAL EFFECTS OF FAULTS ON GROUNDWATER FLOW FOR THE YUCCA FLAT BASIN, NEVADA TEST SITE, NEVADA

    NASA Astrophysics Data System (ADS)

    Dickerson, R. P.; Fryer, W.

    2009-12-01

    The permeability changes resulting from finely comminuted material in fault cores and the fractured and brecciated rock in fault damage zones allows faults to channelize groundwater flow along the plane of the fault. The efficiency of faults as permeability structures depends on fault zone width, fault offset, depth at which the fault developed, type of faulted rock, extent of secondary mineralization, and fault orientation within current stress field. Studies of faulted volcanic rocks at Yucca Mountain, Nevada, indicate that fault zone width and brecciation increase with fault offset, that faulted welded tuff is more permeable than nonwelded or bedded tuff, and that non-hydrothermal secondary mineralization commonly diminishes fracture permeability. These results are applied to the groundwater conceptual flow model for Yucca Flat (YF) on the Nevada Test Site (NTS). Yucca Flat contains Tertiary volcanic rocks similar to thoise at Yucca Mountain deposited on Paleozoic carbonate rocks whose thickness is increased by local thrust-faults. The YF basin contains north-striking normal faults and is bordered by southwest-striking strike-slip faults to the south and east. Fault permeability values derived from faulted volcanic rocks at Yucca Mountain suggests that major normal faults in Yucca Flat potentially manifest permeability values along the fault plane equal to the highest values determined for volcanic aquifers. Numerous minor faults not assigned specific permeability values are assumed to imbue the basin with a hydraulic anisotropy favoring fault-parallel flow. In this scenario groundwater flows generally from north to south in the Yucca Flat basin, even as the head gradient is primarily towards the centrally located Yucca Fault, which acts as the main subsurface drainage feature within the basin. Studies show that the regional stress field has rotated clockwise such that southwest-striking strike-slip faults are currently under tension. In this scenario these

  15. Fault tree handbook

    SciTech Connect

    Haasl, D.F.; Roberts, N.H.; Vesely, W.E.; Goldberg, F.F.

    1981-01-01

    This handbook describes a methodology for reliability analysis of complex systems such as those which comprise the engineered safety features of nuclear power generating stations. After an initial overview of the available system analysis approaches, the handbook focuses on a description of the deductive method known as fault tree analysis. The following aspects of fault tree analysis are covered: basic concepts for fault tree analysis; basic elements of a fault tree; fault tree construction; probability, statistics, and Boolean algebra for the fault tree analyst; qualitative and quantitative fault tree evaluation techniques; and computer codes for fault tree evaluation. Also discussed are several example problems illustrating the basic concepts of fault tree construction and evaluation.

  16. Comparison of solar panel cooling system by using dc brushless fan and dc water

    NASA Astrophysics Data System (ADS)

    Irwan, Y. M.; Leow, W. Z.; Irwanto, M.; M, Fareq; Hassan, S. I. S.; Safwati, I.; Amelia, A. R.

    2015-06-01

    The purpose of this article is to discuss comparison of solar panel cooling system by using DC brushless fan and DC water pump. Solar photovoltaic (PV) power generation is an interesting technique to reduce non-renewable energy consumption and as a renewable energy. The temperature of PV modules increases when it absorbs solar radiation, causing a decrease in efficiency. A solar cooling system is design, construct and experimentally researched within this work. To make an effort to cool the PV module, Direct Current (DC) brushless fan and DC water pump with inlet/outlet manifold are designed for constant air movement and water flow circulation at the back side and front side of PV module representatively. Temperature sensors were installed on the PV module to detect temperature of PV. PIC microcontroller was used to control the DC brushless fan and water pump for switch ON or OFF depend on the temperature of PV module automatically. The performance with and without cooling system are shown in this experiment. The PV module with DC water pump cooling system increase 3.52%, 36.27%, 38.98%in term of output voltage, output current, output power respectively. It decrease 6.36 °C compare than to PV module without DC water pump cooling system. While DC brushless fan cooling system increase 3.47%, 29.55%, 32.23%in term of output voltage, output current, and output power respectively. It decrease 6.1 °C compare than to PV module without DC brushless fan cooling system. The efficiency of PV module with cooling system was increasing compared to PV module without cooling system; this is because the ambient temperature dropped significantly. The higher efficiency of PV cell, the payback period of the system can be shorted and the lifespan of PV module can also be longer.

  17. High voltage DC power supply

    DOEpatents

    Droege, T.F.

    1989-12-19

    A high voltage DC power supply having a first series resistor at the output for limiting current in the event of a short-circuited output, a second series resistor for sensing the magnitude of output current, and a voltage divider circuit for providing a source of feedback voltage for use in voltage regulation is disclosed. The voltage divider circuit is coupled to the second series resistor so as to compensate the feedback voltage for a voltage drop across the first series resistor. The power supply also includes a pulse-width modulated control circuit, having dual clock signals, which is responsive to both the feedback voltage and a command voltage, and also includes voltage and current measuring circuits responsive to the feedback voltage and the voltage developed across the second series resistor respectively. 7 figs.

  18. High voltage DC power supply

    DOEpatents

    Droege, Thomas F.

    1989-01-01

    A high voltage DC power supply having a first series resistor at the output for limiting current in the event of a short-circuited output, a second series resistor for sensing the magnitude of output current, and a voltage divider circuit for providing a source of feedback voltage for use in voltage regulation is disclosed. The voltage divider circuit is coupled to the second series resistor so as to compensate the feedback voltage for a voltage drop across the first series resistor. The power supply also includes a pulse-width modulated control circuit, having dual clock signals, which is responsive to both the feedback voltage and a command voltage, and also includes voltage and current measuring circuits responsive to the feedback voltage and the voltage developed across the second series resistor respectively.

  19. Adaptive output voltage tracking controller for uncertain DC/DC boost converter

    NASA Astrophysics Data System (ADS)

    Lee, Byoung-Seoup; Kim, Seok-Kyoon; Park, Jin-Hyuk; Lee, Kyo-Beum

    2016-06-01

    This paper presents a cascade output voltage control strategy for an uncertain DC/DC boost converter adopting an adaptive current controller in its inner loop. Considering the non-linearity, load uncertainties and parameter uncertainties of the converter, the proposed controller is designed following the conventional cascade voltage controller design method. The proposed method makes the following three contributions. First, a coordinate transformation is introduced for the inner loop, enabling avoidance of the singularity problem caused by the estimates of uncertain parameters. Second, a slight modification to the adaptation law is performed to guarantee closed-loop stability in the presence of the time-varying component of the load current. Third, the outer-loop controller is devised such that its performance can be adjusted without any parameter information. The closed-loop performance is demonstrated through simulations and experiments using the DSP28335 with a 3 kW DC/DC boost converter.

  20. RISK D/C

    NASA Technical Reports Server (NTRS)

    Dias, W. C.

    1994-01-01

    RISK D/C is a prototype program which attempts to do program risk modeling for the Space Exploration Initiative (SEI) architectures proposed in the Synthesis Group Report. Risk assessment is made with respect to risk events, their probabilities, and the severities of potential results. The program allows risk mitigation strategies to be proposed for an exploration program architecture and to be ranked with respect to their effectiveness. RISK D/C allows for the fact that risk assessment in early planning phases is subjective. Although specific to the SEI in its present form, RISK D/C can be used as a framework for developing a risk assessment program for other specific uses. RISK D/C is organized into files, or stacks, of information, including the architecture, the hazard, and the risk event stacks. Although predefined, all stacks can be upgraded by a user. The architecture stack contains information concerning the general program alternatives, which are subsequently broken down into waypoints, missions, and mission phases. The hazard stack includes any background condition which could result in a risk event. A risk event is anything unfavorable that could happen during the course of a specific point within an architecture, and the risk event stack provides the probabilities, consequences, severities, and any mitigation strategies which could be used to reduce the risk of the event, and how much the risk is reduced. RISK D/C was developed for Macintosh series computers. It requires HyperCard 2.0 or later, as well as 2Mb of RAM and System 6.0.8 or later. A Macintosh II series computer is recommended due to speed concerns. The standard distribution medium for this package is one 3.5 inch 800K Macintosh format diskette. RISK D/C was developed in 1991 and is a copyrighted work with all copyright vested in NASA. Macintosh and HyperCard are trademarks of Apple Computer, Inc.

  1. The Scaling of the Slip Weakening Distance (Dc) With Final Slip During Dynamic Earthquake Rupture

    NASA Astrophysics Data System (ADS)

    Tinti, E.; Fukuyama, E.; Cocco, M.; Piatanesi, A.

    2005-12-01

    Several numerical approaches have been recently proposed to retrieve the evolution of dynamic traction during the earthquake propagation on extended faults. Although many studies have shown that the shear traction evolution as a function of time and/or slip may be complex, they all reveal an evident dynamic weakening behavior during faulting. The main dynamic parameters describing traction evolution are: the yield stress, the residual kinetic stress level and the characteristic slip weakening distance Dc. Recent investigations on real data yield the estimate of large Dc values on the fault plane and a correlation between Dc and the final slip. In this study, we focus our attention on the characteristic slip weakening distance Dc and on its variability on the fault plane. Different physical mechanisms have been proposed to explain the origin of Dc, some of them consider this parameter as a scale dependent quantity. We have computed the rupture history from several spontaneous dynamic models imposing a slip weakening law with prescribed Dc distributions on the fault plane. These synthetic models provide the slip velocity evolution during the earthquake rupture. We have therefore generated a set of slip velocity models by fitting the "true" slip velocity time histories with an analytical source time function. To this goal we use the Yoffe function [Tinti et al. 2005], which is dynamically consistent and allows a flexible parameterization. We use these slip velocity histories as a boundary condition on the fault plane to compute the traction evolution. We estimate the Dc values from the traction versus slip curves. We therefore compare the inferred Dc values with those of the original dynamic models and we found that the Dc estimates are very sensitive to the adopted slip velocity function. Despite the problem of resolution that limits the estimate of Dc from kinematic earthquake models and the tradeoff that exists between Dc and strength excess, we show that to

  2. High performance dc-dc conversion with voltage multipliers. [using transformerless capacitor diode circuit

    NASA Technical Reports Server (NTRS)

    Harrigill, W. T., Jr.; Myers, I. T.

    1974-01-01

    An experimental 100W 1000V dc-dc converter using a capacitor diode voltage multipler (CDVM) with a nominal frequency of 100 kHz is studied. A component weight of about 1 kg/kW was obtained. Design equations for current, output -ripple and -power, efficiency and output voltage are derived. Agreement between experimental results and calculations is fairly good except for ripple.

  3. Solid-state circuit breaker with current limiting characteristic using a superconducting coil

    DOEpatents

    Boenig, Heinrich J.

    1984-01-01

    A thyristor bridge interposes an ac source and a load. A series connected DC source and superconducting coil within the bridge biases the thyristors thereof so as to permit bidirectional ac current flow therethrough under normal operating conditions. Upon a fault condition a control circuit triggers the thyristors so as to reduce ac current flow therethrough to zero in less than two cycles and to open the bridge thereafter. Upon a temporary overload condition the control circuit triggers the thyristors so as to limit ac current flow therethrough to an acceptable level.

  4. Solid-state circuit breaker with current-limiting characteristic using a superconducting coil

    DOEpatents

    Boenig, H.J.

    1982-08-16

    A thyristor bridge interposes an ac source and a load. A series connected DC source and superconducting coil within the bridge biases the thyristors thereof so as to permit bidirectional ac current flow therethrough under normal operating conditions. Upon a fault condition a control circuit triggers the thyristors so as to reduce ac current flow therethrough to zero in less than two eyeles and to open the bridge thereafter. Upon a temporary overload condition the control circuit triggers the thyristors so as to limit ac current flow therethrough to an acceptable level.

  5. SFT: Scalable Fault Tolerance

    SciTech Connect

    Petrini, Fabrizio; Nieplocha, Jarek; Tipparaju, Vinod

    2006-04-15

    In this paper we will present a new technology that we are currently developing within the SFT: Scalable Fault Tolerance FastOS project which seeks to implement fault tolerance at the operating system level. Major design goals include dynamic reallocation of resources to allow continuing execution in the presence of hardware failures, very high scalability, high efficiency (low overhead), and transparency—requiring no changes to user applications. Our technology is based on a global coordination mechanism, that enforces transparent recovery lines in the system, and TICK, a lightweight, incremental checkpointing software architecture implemented as a Linux kernel module. TICK is completely user-transparent and does not require any changes to user code or system libraries; it is highly responsive: an interrupt, such as a timer interrupt, can trigger a checkpoint in as little as 2.5μs; and it supports incremental and full checkpoints with minimal overhead—less than 6% with full checkpointing to disk performed as frequently as once per minute.

  6. Monitoring and fault diagnosis of hybrid systems.

    PubMed

    Zhao, Feng; Koutsoukos, Xenofon; Haussecker, Horst; Reich, Jim; Cheung, Patrick

    2005-12-01

    Many networked embedded sensing and control systems can be modeled as hybrid systems with interacting continuous and discrete dynamics. These systems present significant challenges for monitoring and diagnosis. Many existing model-based approaches focus on diagnostic reasoning assuming appropriate fault signatures have been generated. However, an important missing piece is the integration of model-based techniques with the acquisition and processing of sensor signals and the modeling of faults to support diagnostic reasoning. This paper addresses key modeling and computational problems at the interface between model-based diagnosis techniques and signature analysis to enable the efficient detection and isolation of incipient and abrupt faults in hybrid systems. A hybrid automata model that parameterizes abrupt and incipient faults is introduced. Based on this model, an approach for diagnoser design is presented. The paper also develops a novel mode estimation algorithm that uses model-based prediction to focus distributed processing signal algorithms. Finally, the paper describes a diagnostic system architecture that integrates the modeling, prediction, and diagnosis components. The implemented architecture is applied to fault diagnosis of a complex electro-mechanical machine, the Xerox DC265 printer, and the experimental results presented validate the approach. A number of design trade-offs that were made to support implementation of the algorithms for online applications are also described. PMID:16366248

  7. Fault recovery characteristics of the fault tolerant multi-processor

    NASA Technical Reports Server (NTRS)

    Padilla, Peter A.

    1990-01-01

    The fault handling performance of the fault tolerant multiprocessor (FTMP) was investigated. Fault handling errors detected during fault injection experiments were characterized. In these fault injection experiments, the FTMP disabled a working unit instead of the faulted unit once every 500 faults, on the average. System design weaknesses allow active faults to exercise a part of the fault management software that handles byzantine or lying faults. It is pointed out that these weak areas in the FTMP's design increase the probability that, for any hardware fault, a good LRU (line replaceable unit) is mistakenly disabled by the fault management software. It is concluded that fault injection can help detect and analyze the behavior of a system in the ultra-reliable regime. Although fault injection testing cannot be exhaustive, it has been demonstrated that it provides a unique capability to unmask problems and to characterize the behavior of a fault-tolerant system.

  8. DC arc weld starter

    DOEpatents

    Campiotti, Richard H.; Hopwood, James E.

    1990-01-01

    A system for starting an arc for welding uses three DC power supplies, a high voltage supply for initiating the arc, an intermediate voltage supply for sustaining the arc, and a low voltage welding supply directly connected across the gap after the high voltage supply is disconnected.

  9. DYLOS DC110

    EPA Science Inventory

    The Dylos DC1100 air quality monitor measures particulate matter (PM) to provide a continuous assessment of indoor air quality. The unit counts particles in two size ranges: large and small. According to the manufacturer, large particles have diameters between 2.5 and 10 micromet...

  10. Description of the SSF PMAD DC testbed control system data acquisition function

    NASA Technical Reports Server (NTRS)

    Baez, Anastacio N.; Mackin, Michael; Wright, Theodore

    1992-01-01

    The NASA LeRC in Cleveland, Ohio has completed the development and integration of a Power Management and Distribution (PMAD) DC Testbed. This testbed is a reduced scale representation of the end to end, sources to loads, Space Station Freedom Electrical Power System (SSF EPS). This unique facility is being used to demonstrate DC power generation and distribution, power management and control, and system operation techniques considered to be prime candidates for the Space Station Freedom. A key capability of the testbed is its ability to be configured to address system level issues in support of critical SSF program design milestones. Electrical power system control and operation issues like source control, source regulation, system fault protection, end-to-end system stability, health monitoring, resource allocation, and resource management are being evaluated in the testbed. The SSF EPS control functional allocation between on-board computers and ground based systems is evolving. Initially, ground based systems will perform the bulk of power system control and operation. The EPS control system is required to continuously monitor and determine the current state of the power system. The DC Testbed Control System consists of standard controllers arranged in a hierarchical and distributed architecture. These controllers provide all the monitoring and control functions for the DC Testbed Electrical Power System. Higher level controllers include the Power Management Controller, Load Management Controller, Operator Interface System, and a network of computer systems that perform some of the SSF Ground based Control Center Operation. The lower level controllers include Main Bus Switch Controllers and Photovoltaic Controllers. Power system status information is periodically provided to the higher level controllers to perform system control and operation. The data acquisition function of the control system is distributed among the various levels of the hierarchy. Data

  11. Effects of Fault Displacement on Emplacement Drifts

    SciTech Connect

    F. Duan

    2000-04-25

    The purpose of this analysis is to evaluate potential effects of fault displacement on emplacement drifts, including drip shields and waste packages emplaced in emplacement drifts. The output from this analysis not only provides data for the evaluation of long-term drift stability but also supports the Engineered Barrier System (EBS) process model report (PMR) and Disruptive Events Report currently under development. The primary scope of this analysis includes (1) examining fault displacement effects in terms of induced stresses and displacements in the rock mass surrounding an emplacement drift and (2 ) predicting fault displacement effects on the drip shield and waste package. The magnitude of the fault displacement analyzed in this analysis bounds the mean fault displacement corresponding to an annual frequency of exceedance of 10{sup -5} adopted for the preclosure period of the repository and also supports the postclosure performance assessment. This analysis is performed following the development plan prepared for analyzing effects of fault displacement on emplacement drifts (CRWMS M&O 2000). The analysis will begin with the identification and preparation of requirements, criteria, and inputs. A literature survey on accommodating fault displacements encountered in underground structures such as buried oil and gas pipelines will be conducted. For a given fault displacement, the least favorable scenario in term of the spatial relation of a fault to an emplacement drift is chosen, and the analysis is then performed analytically. Based on the analysis results, conclusions are made regarding the effects and consequences of fault displacement on emplacement drifts. Specifically, the analysis will discuss loads which can be induced by fault displacement on emplacement drifts, drip shield and/or waste packages during the time period of postclosure.

  12. Poro-Elasto-Plastic Off-Fault Response and Dynamics of Earthquake Faulting

    NASA Astrophysics Data System (ADS)

    Hirakawa, Evan Tyler

    Previous models of earthquake rupture dynamics have neglected interesting deformational properties of fault zone materials. While most current studies involving off-fault inelastic deformation employ simple brittle failure yield criteria such as the Drucker-Prager yield criterion, the material surrounding the fault plane itself, known as fault gouge, has the tendency to deform in a ductile manner accompanied by compaction. We incorporate this behavior into a new constitutive model of undrained fault gouge in a dynamic rupture model. Dynamic compaction of undrained fault gouge occurs ahead of the rupture front. This corresponds to an increase in pore pressure which preweakens the fault, reducing the static friction. Subsequent dilatancy and softening of the gouge causes a reduction in pore pressure, resulting in fault restrengthening and brief slip pulses. This leads to localization of inelastic failure to a narrow shear zone. We extend the undrained gouge model to a study of self-similar rough faults. Extreme compaction and dilatancy occur at restraining and releasing bends, respectively. The consequent elevated pore pressure at restraining bends weakens the fault and allows the rupture to easily pass, while the decrease in pore pressure at releasing bends dynamically strengthens the fault and slows rupture. In comparison to other recent models, we show that the effects of fault roughness on propagation distance, slip distribution, and rupture velocity are diminished or reversed. Next, we represent large subduction zone megathrust earthquakes with a dynamic rupture model of a shallow dipping fault underlying an accretionary wedge. In previous models by our group [Ma, 2012; Ma and Hirakawa, 2013], inelastic deformation of wedge material was shown to enhance vertical uplift and potential tsunamigenesis. Here, we include a shallow region of velocity strengthening friction with a rate-and-state framework. We find that coseismic increase of the basal friction drives

  13. Kilovolt dc solid state remote power controller development

    NASA Technical Reports Server (NTRS)

    Mitchell, J. T.

    1982-01-01

    The experience gained in developing and applying solid state power controller (SSPC) technology at high voltage dc (HVDC) potentials and power levels of up to 25 kilowatts is summarized. The HVDC switching devices, power switching concepts, drive circuits, and very fast acting overcurrent protection circuits were analyzed. A 25A bipolar breadboard with Darlington connected switching transistor was built. Fault testing at 900 volts was included. A bipolar transistor packaged breadboard design was developed. Power MOSFET remote power controller (RPC) was designed.

  14. Applying to the DC Opportunity Scholarship Program: How Do Parents Rate Their Children's Current Schools at Time of Application and What Do They Want in New Schools? NCEE Evaluation Brief. NCEE 2016-4003

    ERIC Educational Resources Information Center

    Dynarski, Mark; Betts, Julian; Feldman, Jill

    2016-01-01

    The DC Opportunity Scholarship Program (OSP), established in 2004, is the only federally-funded private school voucher program for low-income parents in the United States. This evaluation brief describes findings using data from more than 2,000 applicants' parents, who applied to the program from spring 2011 to spring 2013 following…

  15. Preparative separation and identification of novel subsidiary colors of the color additive D&C Red No. 33 (Acid Red 33) using spiral high-speed counter-current chromatography☆

    PubMed Central

    Weisz, Adrian; Ridge, Clark D.; Mazzola, Eugene P.; Ito, Yoichiro

    2015-01-01

    Three low-level subsidiary color impurities (A, B, and C) often present in batches of the color additive D&C Red No. 33 (R33, Acid Red 33, Colour Index No. 17200) were separated from a portion of R33 by spiral high-speed counter-current chromatography (HSCCC). The separation involved use of a very polar solvent system, 1-BuOH/5 mM aq. (NH4)2SO4. Addition of ammonium sulfate to the lower phase forced partition of the components into the upper phase, thereby eliminating the need to add a hydrophobic counterion as was previously required for separations of components from sulfonated dyes. The very polar solvent system used would not have been retained in a conventional multi-layer coil HSCCC instrument, but the spiral configuration enabled retention of the stationary phase, and thus, the separation was possible. A 1 g portion of R33 enriched in A, B, and C was separated using the upper phase of the solvent system as the mobile phase. The retention of the stationary phase was 38.1%, and the separation resulted in 4.8 mg of A of >90% purity, 18.3 mg of B of >85% purity, and 91 mg of C of 65–72% purity. A second separation of a portion of the C mixture resulted in 7 mg of C of >94% purity. The separated impurities were identified by high-resolution mass spectrometry and NMR spectroscopic techniques as follows: 5-amino-3-biphenyl-3-ylazo-4-hydroxy-naphthalene-2,7-disulfonic acid, A; 5-amino-4-hydroxy-6-phenyl-3-phenylazo-naphthalene-2,7-disulfonic acid, B; and 5-amino-4-hydroxy-3,6-bis-phenylazo-naphthalene-2,7-disulfonic acid, C. The isomers A and B are compounds reported for the first time. Application of the spiral HSCCC method resulted in the additional benefit of yielding 930 mg of the main component of R33, 5-amino-4-hydroxy-3-phenylazo-naphthalene-2,7-disulfonic acid, of >97% purity. PMID:25591404

  16. Preparative separation and identification of novel subsidiary colors of the color additive D&C Red No. 33 (Acid Red 33) using spiral high-speed counter-current chromatography.

    PubMed

    Weisz, Adrian; Ridge, Clark D; Mazzola, Eugene P; Ito, Yoichiro

    2015-02-01

    Three low-level subsidiary color impurities (A, B, and C) often present in batches of the color additive D&C Red No. 33 (R33, Acid Red 33, Colour Index No. 17200) were separated from a portion of R33 by spiral high-speed counter-current chromatography (HSCCC). The separation involved use of a very polar solvent system, 1-BuOH/5mM aq. (NH4)2SO4. Addition of ammonium sulfate to the lower phase forced partition of the components into the upper phase, thereby eliminating the need to add a hydrophobic counterion as was previously required for separations of components from sulfonated dyes. The very polar solvent system used would not have been retained in a conventional multi-layer coil HSCCC instrument, but the spiral configuration enabled retention of the stationary phase, and thus, the separation was possible. A 1g portion of R33 enriched in A, B, and C was separated using the upper phase of the solvent system as the mobile phase. The retention of the stationary phase was 38.1%, and the separation resulted in 4.8 mg of A of >90% purity, 18.3mg of B of >85% purity, and 91 mg of C of 65-72% purity. A second separation of a portion of the C mixture resulted in 7 mg of C of >94% purity. The separated impurities were identified by high-resolution mass spectrometry and NMR spectroscopic techniques as follows: 5-amino-3-biphenyl-3-ylazo-4-hydroxy-naphthalene-2,7-disulfonic acid, A; 5-amino-4-hydroxy-6-phenyl-3-phenylazo-naphthalene-2,7-disulfonic acid, B; and 5-amino-4-hydroxy-3,6-bis-phenylazo-naphthalene-2,7-disulfonic acid, C. The isomers A and B are compounds reported for the first time. Application of the spiral HSCCC method resulted in the additional benefit of yielding 930 mg of the main component of R33, 5-amino-4-hydroxy-3-phenylazo-naphthalene-2,7-disulfonic acid, of >97% purity. PMID:25591404

  17. DC-DC powering for the CMS pixel upgrade

    NASA Astrophysics Data System (ADS)

    Feld, Lutz; Fleck, Martin; Friedrichs, Marcel; Hensch, Richard; Karpinski, Waclaw; Klein, Katja; Rittich, David; Sammet, Jan; Wlochal, Michael

    2013-12-01

    The CMS experiment plans to replace its silicon pixel detector with a new one with improved rate capability and an additional detection layer at the end of 2016. In order to cope with the increased number of detector modules the new pixel detector will be powered via DC-DC converters close to the sensitive detector volume. This paper reviews the DC-DC powering scheme and reports on the ongoing R&D program to develop converters for the pixel upgrade. Design choices are discussed and results from the electrical and thermal characterisation of converter prototypes are shown. An emphasis is put on system tests with up to 24 converters. The performance of pixel modules powered by DC-DC converters is compared to conventional powering. The integration of the DC-DC powering scheme into the pixel detector is described and system design issues are reviewed.

  18. Regulated dc-to-dc converter features low power drain

    NASA Technical Reports Server (NTRS)

    Thornwall, J.

    1968-01-01

    A regulated dc-to-dc converter requires negligible standby power for the operation of critical electronic equipment. The main operating circuitry consumes power intermittently according to load conditions, rather than constantly.

  19. Integration of offshore wind farms through high voltage direct current networks

    NASA Astrophysics Data System (ADS)

    Livermore, Luke

    The integration of offshore wind farms through Multi Terminal DC (MTDC) networks into the GB network was investigated. The ability of Voltage Source Converter (VSC) High Voltage Direct Current (HVDC) to damp Subsynchronous Resonance (SSR) and ride through onshore AC faults was studied. Due to increased levels of wind generation in Scotland, substantial onshore and offshore reinforcements to the GB transmission network are proposed. Possible inland reinforcements include the use of series compensation through fixed capacitors. This potentially can lead to SSR. Offshore reinforcements are proposed by two HVDC links. In addition to its primary functions of bulk power transmission, a HVDC link can be used to provide damping against SSR, and this function has been modelled. Simulation studies have been carried out in PSCAD. In addition, a real-time hardware-in-the-loop HVDC test rig has been used to implement and validate the proposed damping scheme on an experimental platform. When faults occur within AC onshore networks, offshore MTDC networks are vulnerable to DC overvoltages, potentially damaging the DC plant and cables. Power reduction and power dissipation control systems were investigated to ride through onshore AC faults. These methods do not require dedicated fast communication systems. Simulations and laboratory experiments are carried out to evaluate the control systems, with the results from the two platforms compared..

  20. Tractable particle filters for robot fault diagnosis

    NASA Astrophysics Data System (ADS)

    Verma, Vandi

    Experience has shown that even carefully designed and tested robots may encounter anomalous situations. It is therefore important for robots to monitor their state so that anomalous situations may be detected in a timely manner. Robot fault diagnosis typically requires tracking a very large number of possible faults in complex non-linear dynamic systems with noisy sensors. Traditional methods either ignore the uncertainly or use linear approximations of nonlinear system dynamics. Such approximations are often unrealistic, and as a result faults either go undetected or become confused with non-fault conditions. Probability theory provides a natural representation for uncertainty, but an exact Bayesian solution for the diagnosis problem is intractable. Classical Monte Carlo methods, such as particle filters, suffer from substantial computational complexity. This is particularly true with the presence of rare, yet important events, such as many system faults. The thesis presents a set of complementary algorithms that provide an approach for computationally tractable fault diagnosis. These algorithms leverage probabilistic approaches to decision theory and information theory to efficiently track a large number of faults in a general dynamic system with noisy measurements. The problem of fault diagnosis is represented as hybrid (discrete/continuous) state estimation. Taking advantage of structure in the domain it dynamically concentrates computation in the regions of state space that are currently most relevant without losing track of less likely states. Experiments with a dynamic simulation of a six-wheel rocker-bogie rover show a significant improvement in performance over the classical approach.

  1. Fault Management Techniques in Human Spaceflight Operations

    NASA Technical Reports Server (NTRS)

    O'Hagan, Brian; Crocker, Alan

    2006-01-01

    This paper discusses human spaceflight fault management operations. Fault detection and response capabilities available in current US human spaceflight programs Space Shuttle and International Space Station are described while emphasizing system design impacts on operational techniques and constraints. Preflight and inflight processes along with products used to anticipate, mitigate and respond to failures are introduced. Examples of operational products used to support failure responses are presented. Possible improvements in the state of the art, as well as prioritization and success criteria for their implementation are proposed. This paper describes how the architecture of a command and control system impacts operations in areas such as the required fault response times, automated vs. manual fault responses, use of workarounds, etc. The architecture includes the use of redundancy at the system and software function level, software capabilities, use of intelligent or autonomous systems, number and severity of software defects, etc. This in turn drives which Caution and Warning (C&W) events should be annunciated, C&W event classification, operator display designs, crew training, flight control team training, and procedure development. Other factors impacting operations are the complexity of a system, skills needed to understand and operate a system, and the use of commonality vs. optimized solutions for software and responses. Fault detection, annunciation, safing responses, and recovery capabilities are explored using real examples to uncover underlying philosophies and constraints. These factors directly impact operations in that the crew and flight control team need to understand what happened, why it happened, what the system is doing, and what, if any, corrective actions they need to perform. If a fault results in multiple C&W events, or if several faults occur simultaneously, the root cause(s) of the fault(s), as well as their vehicle-wide impacts, must be

  2. Application of current steps and design of experiments methodology to the detection of water management faults in a proton exchange membrane fuel cell stack

    NASA Astrophysics Data System (ADS)

    Moçotéguy, Philippe; Ludwig, Bastian; Yousfi Steiner, Nadia

    2016-01-01

    We apply a 25-1 fractional factorial Design of Experiments (DoE) test plan in order to discriminate the direct effects and interactions of five factors on the water management of a 500 We PEMFC stack. The stack is submitted to current steps between different operating levels and several responses are extracted for the DoE analysis. A strong ageing effect on stack and cell performances is observed. Therefore, in order to perform the DoE analysis, responses which values are too strongly affected by ageing are "corrected" prior to the analysis. A "virtual" stack, considered as "healthy", is also "reconstructed" by "putting in series" the cells exhibiting very low performance drop. The results show that stacks and cells' resistivities are mostly impacted by direct effects of both temperature and cathodic inlet relative humidity and by compensating interaction between temperature and anodic overstoichiometric ratio. It also appears that two responses are able to distinguish a "healthy" stack from a degraded stack: heterogeneities in cell voltages and cell resistivities distributions. They are differently impacted by considered effects and interactions. Thus, a customised water management strategy could be developed, depending on the stack's state of health to maintain it in the best possible operating conditions.

  3. Perspective View, San Andreas Fault

    NASA Technical Reports Server (NTRS)

    2000-01-01

    The prominent linear feature straight down the center of this perspective view is California's famous San Andreas Fault. The image, created with data from NASA's Shuttle Radar Topography Mission (SRTM), will be used by geologists studying fault dynamics and landforms resulting from active tectonics. This segment of the fault lies west of the city of Palmdale, Calif., about 100 kilometers (about 60 miles) northwest of Los Angeles. The fault is the active tectonic boundary between the North American plate on the right, and the Pacific plate on the left. Relative to each other, the Pacific plate is moving away from the viewer and the North American plate is moving toward the viewer along what geologists call a right lateral strike-slip fault. Two large mountain ranges are visible, the San Gabriel Mountains on the left and the Tehachapi Mountains in the upper right. Another fault, the Garlock Fault lies at the base of the Tehachapis; the San Andreas and the Garlock Faults meet in the center distance near the town of Gorman. In the distance, over the Tehachapi Mountains is California's Central Valley. Along the foothills in the right hand part of the image is the Antelope Valley, including the Antelope Valley California Poppy Reserve. The data used to create this image were acquired by SRTM aboard the Space Shuttle Endeavour, launched on February 11, 2000.

    This type of display adds the important dimension of elevation to the study of land use and environmental processes as observed in satellite images. The perspective view was created by draping a Landsat satellite image over an SRTM elevation model. Topography is exaggerated 1.5 times vertically. The Landsat image was provided by the United States Geological Survey's Earth Resources Observations Systems (EROS) Data Center, Sioux Falls, South Dakota.

    SRTM uses the same radar instrument that comprised the Spaceborne Imaging Radar-C/X-Band Synthetic Aperture Radar (SIR-C/X-SAR) that flew twice on the Space

  4. DC-DC power converter research for Orbiter/Station power exchange

    NASA Technical Reports Server (NTRS)

    Ehsani, M.

    1993-01-01

    This project was to produce innovative DC-DC power converter concepts which are appropriate for the power exchange between the Orbiter and the Space Station Freedom (SSF). The new converters must interface three regulated power buses on SSF, which are at different voltages, with three fuel cell power buses on the Orbiter which can be at different voltages and should be tracked independently. Power exchange is to be bi-directional between the SSF and the Orbiter. The new converters must satisfy the above operational requirements with better weight, volume, efficiency, and reliability than is available from the present conventional technology. Two families of zero current DC-DC converters were developed and successfully adapted to this application. Most of the converters developed are new and are presented.

  5. Cryogenic Evaluation of an Advanced DC/DC Converter Module for Deep Space Applications

    NASA Technical Reports Server (NTRS)

    Elbuluk, Malik E.; Hammoud, Ahmad; Gerber, Scott S.; Patterson, Richard

    2003-01-01

    DC/DC converters are widely used in power management, conditioning, and control of space power systems. Deep space applications require electronics that withstand cryogenic temperature and meet a stringent radiation tolerance. In this work, the performance of an advanced, radiation-hardened (rad-hard) commercial DC/DC converter module was investigated at cryogenic temperatures. The converter was investigated in terms of its steady state and dynamic operations. The output voltage regulation, efficiency, terminal current ripple characteristics, and output voltage response to load changes were determined in the temperature range of 20 to -140 C. These parameters were obtained at various load levels and at different input voltages. The experimental procedures along with the results obtained on the investigated converter are presented and discussed.

  6. DC conductivity of magnetised holographic matter

    NASA Astrophysics Data System (ADS)

    Donos, Aristomenis; Gauntlett, Jerome P.; Griffin, Tom; Melgar, Luis

    2016-01-01

    We consider general black hole solutions of Einstein-Maxwell-scalar theory that are holographically dual to conformal field theories at finite charge density with nonvanishing magnetic fields and local magnetisation currents, which generically break translation invariance explicitly. We show that the thermoelectric DC conductivity of the field theory can be obtained by solving a system of generalised Stokes equations on the black hole horizon. For various examples, including Q-lattices and one-dimensional lattices, we solve the Stokes equations explicitly and obtain expressions for the DC conductivity in terms of the solution at the black hole horizon.

  7. FTAPE: A fault injection tool to measure fault tolerance

    NASA Technical Reports Server (NTRS)

    Tsai, Timothy K.; Iyer, Ravishankar K.

    1995-01-01

    The paper introduces FTAPE (Fault Tolerance And Performance Evaluator), a tool that can be used to compare fault-tolerant computers. The tool combines system-wide fault injection with a controllable workload. A workload generator is used to create high stress conditions for the machine. Faults are injected based on this workload activity in order to ensure a high level of fault propagation. The errors/fault ratio and performance degradation are presented as measures of fault tolerance.

  8. FTAPE: A fault injection tool to measure fault tolerance

    NASA Technical Reports Server (NTRS)

    Tsai, Timothy K.; Iyer, Ravishankar K.

    1994-01-01

    The paper introduces FTAPE (Fault Tolerance And Performance Evaluator), a tool that can be used to compare fault-tolerant computers. The tool combines system-wide fault injection with a controllable workload. A workload generator is used to create high stress conditions for the machine. Faults are injected based on this workload activity in order to ensure a high level of fault propagation. The errors/fault ratio and performance degradation are presented as measures of fault tolerance.

  9. FTAPE: A fault injection tool to measure fault tolerance

    NASA Astrophysics Data System (ADS)

    Tsai, Timothy K.; Iyer, Ravishankar K.

    1994-07-01

    The paper introduces FTAPE (Fault Tolerance And Performance Evaluator), a tool that can be used to compare fault-tolerant computers. The tool combines system-wide fault injection with a controllable workload. A workload generator is used to create high stress conditions for the machine. Faults are injected based on this workload activity in order to ensure a high level of fault propagation. The errors/fault ratio and performance degradation are presented as measures of fault tolerance.

  10. Coordinated Fault Tolerance for High-Performance Computing

    SciTech Connect

    Dongarra, Jack; Bosilca, George; et al.

    2013-04-08

    Our work to meet our goal of end-to-end fault tolerance has focused on two areas: (1) improving fault tolerance in various software currently available and widely used throughout the HEC domain and (2) using fault information exchange and coordination to achieve holistic, systemwide fault tolerance and understanding how to design and implement interfaces for integrating fault tolerance features for multiple layers of the software stack—from the application, math libraries, and programming language runtime to other common system software such as jobs schedulers, resource managers, and monitoring tools.

  11. Study on fault diagnose expert system for large astronomy telescope

    NASA Astrophysics Data System (ADS)

    Liu, Jia-jing; Luo, Ming-Cheng; Tang, Peng-yi; Wu, Wen-qing; Zhang, Guang-yu; Zhang, Hong-fei; Wang, Jian

    2014-08-01

    The development of astronomical techniques and telescopes currently entered a new vigorous period. The telescopes have trends of the giant, complex, diversity of equipment and wide span of control despite of optical, radio space telescopes. That means, for telescope observatory, the control system must have these specifications: flexibility, scalability, distributive, cross-platform and real-time, especially the fault locating and fault processing is more important when fault or exception arise. Through the analysis of the structure of large telescopes, fault diagnosis expert system of large telescope based on the fault tree and distributed log service is given.

  12. A 10 kW dc-dc converter using IGBTs with active snubbers. [Insulated Gate Bipolar Transistor

    NASA Technical Reports Server (NTRS)

    Masserant, Brian J.; Shriver, Jeffrey L.; Stuart, Thomas A.

    1993-01-01

    This full bridge dc-dc converter employs zero voltage switching (ZVS) on one leg and zero current switching (ZCS) on the other. This technique produces exceptionally low IGBT switching losses through the use of an active snubber that recycles energy back to the source. Experimental results are presented for a 10 kW, 20 kHz converter.

  13. Concatenated codes for fault tolerant quantum computing

    SciTech Connect

    Knill, E.; Laflamme, R.; Zurek, W.

    1995-05-01

    The application of concatenated codes to fault tolerant quantum computing is discussed. We have previously shown that for quantum memories and quantum communication, a state can be transmitted with error {epsilon} provided each gate has error at most c{epsilon}. We show how this can be used with Shor`s fault tolerant operations to reduce the accuracy requirements when maintaining states not currently participating in the computation. Viewing Shor`s fault tolerant operations as a method for reducing the error of operations, we give a concatenated implementation which promises to propagate the reduction hierarchically. This has the potential of reducing the accuracy requirements in long computations.

  14. Cooperative human-machine fault diagnosis

    NASA Technical Reports Server (NTRS)

    Remington, Roger; Palmer, Everett

    1987-01-01

    Current expert system technology does not permit complete automatic fault diagnosis; significant levels of human intervention are still required. This requirement dictates a need for a division of labor that recognizes the strengths and weaknesses of both human and machine diagnostic skills. Relevant findings from the literature on human cognition are combined with the results of reviews of aircrew performance with highly automated systems to suggest how the interface of a fault diagnostic expert system can be designed to assist human operators in verifying machine diagnoses and guiding interactive fault diagnosis. It is argued that the needs of the human operator should play an important role in the design of the knowledge base.

  15. Isolability of faults in sensor fault diagnosis

    NASA Astrophysics Data System (ADS)

    Sharifi, Reza; Langari, Reza

    2011-10-01

    A major concern with fault detection and isolation (FDI) methods is their robustness with respect to noise and modeling uncertainties. With this in mind, several approaches have been proposed to minimize the vulnerability of FDI methods to these uncertainties. But, apart from the algorithm used, there is a theoretical limit on the minimum effect of noise on detectability and isolability. This limit has been quantified in this paper for the problem of sensor fault diagnosis based on direct redundancies. In this study, first a geometric approach to sensor fault detection is proposed. The sensor fault is isolated based on the direction of residuals found from a residual generator. This residual generator can be constructed from an input-output or a Principal Component Analysis (PCA) based model. The simplicity of this technique, compared to the existing methods of sensor fault diagnosis, allows for more rational formulation of the isolability concepts in linear systems. Using this residual generator and the assumption of Gaussian noise, the effect of noise on isolability is studied, and the minimum magnitude of isolable fault in each sensor is found based on the distribution of noise in the measurement system. Finally, some numerical examples are presented to clarify this approach.

  16. An example of complex fault geometries in a young, rapidly deforming transform fault system: The Maacama Fault in northern California

    NASA Astrophysics Data System (ADS)

    Schroeder, R. D.; Brady, R. J.

    2009-12-01

    The Maacama Fault Zone (MFZ) in northern California is a young transform system that developed behind the northward migrating Mendocino Triple Junction, and comprises a complex set of active, linked fault strands that form a series of pull-apart basins within the rapidly slipping (~13.9 mm/yr) right-lateral fault system. Surface fault traces within the MFZ are defined by geomorphic features, shallow resistivity profiles, and previously published surface creep and paleoseismic trenching studies. The surface traces of these faults outline classic pull-apart rhomohedrons, with all of the bounding faults inferred to be kinematically linked and currenty active. This activity is supported not only by paleoseismic and surface creep studies, which have tended to focus on the single main strand of the Maacama Fault, but also by the location of tabular seismogenic zones that project from the subsurface into several of the mapped surface fault traces. For each of the 3 mapped pull-apart basins, at least two of the interpreted bounding faults can be shown to be currently active, requiring near-synchronous activity on all of the kinematically linked faults. Historically, active displacement across the MFZ has been assigned to only one relatively well-studied main strand of the fault zone, which slips at ~6.5 mm/yr, resulting in an apparent slip deficit of ~7.4 mm/yr. However, the newly studied adjacent faults in this complex system could accommodate as much or more slip than the historically defined main fault trace, thus resulting in a possibly broader zone of seismic hazard, but less risk of major earthquakes on the main trace. Timing of pull-apart basin initiations is not well constrained, with data permitting either the interpretation that basins formed due to oblique subduction and are currently being reactivated by similar stresses, or that they are newly formed and rapidly evolving. Limited data even allows that the largest pull-apart system may be a reactivated pre

  17. Advanced medium-voltage bidirectional dc-dc conversion systems for future electric energy delivery and management systems

    NASA Astrophysics Data System (ADS)

    Fan, Haifeng

    2011-12-01

    The distributed renewable energy generation and utilization are constantly growing, and are expected to be integrated with the conventional grid. The growing pressure for innovative solutions will demand power electronics to take an even larger role in future electric energy delivery and management systems, since power electronics are required for the conversion and control of electric energy by most dispersed generation systems Furthermore, power electronics systems can provide additional intelligent energy management, grid stability and power quality capabilities. Medium-voltage isolated dc-dc converter will become one of the key interfaces for grid components with moderate power ratings. To address the demand of medium voltage (MV) and high power capability for future electric energy delivery and management systems, the power electronics community and industry have been reacting in two different ways: developing semiconductor technology or directly connecting devices in series/parallel to reach higher nominal voltages and currents while maintaining conventional converter topologies; and by developing new converter topologies with traditional semiconductor technology, known as multilevel converters or modular converters. The modular approach uses the well-known, mature, and cheaper power semiconductor devices by adopting new converter topologies. The main advantages of the modular approach include: significant improvement in reliability by introducing desired level of redundancy; standardization of components leading to reduction in manufacturing cost and time; power systems can be easily reconfigured to support varying input-output specifications; and possibly higher efficiency and power density of the overall system. Input-series output-parallel (ISOP) modular configuration is a good choice to realize MV to low voltage (LV) conversion for utility application. However, challenges still remain. First of all, for the high-frequency MV utility application, the low

  18. Active faulting in the Walker Lane

    NASA Astrophysics Data System (ADS)

    Wesnousky, Steven G.

    2005-06-01

    Deformation across the San Andreas and Walker Lane fault systems accounts for most relative Pacific-North American transform plate motion. The Walker Lane is composed of discontinuous sets of right-slip faults that are located to the east and strike approximately parallel to the San Andreas fault system. Mapping of active faults in the central Walker Lane shows that right-lateral shear is locally accommodated by rotation of crustal blocks bounded by steep-dipping east striking left-slip faults. The left slip and clockwise rotation of crustal blocks bounded by the east striking faults has produced major basins in the area, including Rattlesnake and Garfield flats; Teels, Columbus and Rhodes salt marshes; and Queen Valley. The Benton Springs and Petrified Springs faults are the major northwest striking structures currently accommodating transform motion in the central Walker Lane. Right-lateral offsets of late Pleistocene surfaces along the two faults point to slip rates of at least 1 mm/yr. The northern limit of northwest trending strike-slip faults in the central Walker Lane is abrupt and reflects transfer of strike-slip to dip-slip deformation in the western Basin and Range and transformation of right slip into rotation of crustal blocks to the north. The transfer of strike slip in the central Walker Lane to dip slip in the western Basin and Range correlates to a northward broadening of the modern strain field suggested by geodesy and appears to be a long-lived feature of the deformation field. The complexity of faulting and apparent rotation of crustal blocks within the Walker Lane is consistent with the concept of a partially detached and elastic-brittle crust that is being transported on a continuously deforming layer below. The regional pattern of faulting within the Walker Lane is more complex than observed along the San Andreas fault system to the west. The difference is attributed to the relatively less cumulative slip that has occurred across the Walker

  19. 500 V/200 A fault current limiter modules made of large-area MOD-YBa2Cu3O7 thin films with high-resistivity Au-Ag alloy shunt layers

    NASA Astrophysics Data System (ADS)

    Yamasaki, H.; Arai, K.; Kaiho, K.; Nakagawa, Y.; Sohma, M.; Kondo, W.; Yamaguchi, I.; Matsui, H.; Kumagai, T.; Natori, N.; Higuchi, N.

    2009-12-01

    We developed 500 Vrms/ 200 Arms superconducting thin-film fault current limiter (FCL) modules that can withstand high electric fields (E>30 Vrms cm-1) by using large-area YBa2Cu3O7 (YBCO) thin films with high-resistivity Au-Ag alloy shunt layers. Au-Ag alloy films about 60 nm thick were sputter-deposited on YBCO/CeO2/sapphire films (2.7 cm × 20 cm) prepared using a fluorine-free MOD method. Each 20 cm long Au-Ag/YBCO film was then divided into three segments (each ~5.7 cm long) by four Ag electrodes deposited on the Au-Ag layer, resulting in an effective length of 17 cm. The 500 V/200 A FCL modules were then fabricated by first connecting two of the segmented films in parallel using Ag-sheathed Bi-2223 superconducting tapes and then connecting in parallel an external resistor and a capacitor for each segment to protect the Au-Ag/YBCO film from hot spots. Switching tests using a short-circuit generator revealed that all the modules carried a superconducting ac current of >=237 Arms and that modules prepared with YBCO films having a relatively homogeneous critical current Ic distribution successfully withstood >=515 Vrms for five cycles without any damage. These results demonstrate that (a) the FCL modules fabricated here successfully achieved the rated current of 200 Arms and rated voltage of 500 Vrms and (b) total area of the YBCO films on sapphire substrates required for the 500 V/200 A (100 kV A) module was less than one-third that for conventional thin-film FCL modules that use gold shunt layers, leading to the significantly reduced cost of thin-film FCLs. Film damage due to hot spots depended on the difference in Ic between the two parallel-connected films and on the inhomogeneity of the Ic distribution in the film, and is most probably due to nonlinear current flows at the moment of quenching that cause local overheating.

  20. Perspective View, San Andreas Fault

    NASA Technical Reports Server (NTRS)

    2000-01-01

    The prominent linear feature straight down the center of this perspective view is the San Andreas Fault in an image created with data from NASA's shuttle Radar Topography Mission (SRTM), which will be used by geologists studying fault dynamics and landforms resulting from active tectonics. This segment of the fault lies west of the city of Palmdale, California, about 100 kilometers (about 60 miles) northwest of Los Angeles. The fault is the active tectonic boundary between the North American plate on the right, and the Pacific plate on the left. Relative to each other, the Pacific plate is moving away from the viewer and the North American plate is moving toward the viewer along what geologists call a right lateral strike-slip fault. This area is at the junction of two large mountain ranges, the San Gabriel Mountains on the left and the Tehachapi Mountains on the right. Quail Lake Reservoir sits in the topographic depression created by past movement along the fault. Interstate 5 is the prominent linear feature starting at the left edge of the image and continuing into the fault zone, passing eventually over Tejon Pass into the Central Valley, visible at the upper left.

    This type of display adds the important dimension of elevation to the study of land use and environmental processes as observed in satellite images. The perspective view was created by draping a Landsat satellite image over an SRTM elevation model. Topography is exaggerated 1.5 times vertically. The Landsat image was provided by the United States Geological Survey's Earth Resources Observations Systems (EROS) Data Center, Sioux Falls, South Dakota.

    Elevation data used in this image was acquired by the Shuttle Radar Topography Mission (SRTM) aboard the Space Shuttle Endeavour, launched on February 11,2000. SRTM used the same radar instrument that comprised the Spaceborne Imaging Radar-C/X-Band Synthetic Aperture Radar (SIR-C/X-SAR) that flew twice on the Space Shuttle Endeavour in 1994

  1. Fault zone structure and inferences on past activities of the active Shanchiao Fault in the Taipei metropolis, northern Taiwan

    NASA Astrophysics Data System (ADS)

    Chen, C.; Lee, J.; Chan, Y.; Lu, C.

    2010-12-01

    The Taipei Metropolis, home to around 10 million people, is subject to seismic hazard originated from not only distant faults or sources scattered throughout the Taiwan region, but also active fault lain directly underneath. Northern Taiwan including the Taipei region is currently affected by post-orogenic (Penglai arc-continent collision) processes related to backarc extension of the Ryukyu subduction system. The Shanchiao Fault, an active normal fault outcropping along the western boundary of the Taipei Basin and dipping to the east, is investigated here for its subsurface structure and activities. Boreholes records in the central portion of the fault were analyzed to document the stacking of post- Last Glacial Maximum growth sediments, and a tulip flower structure is illuminated with averaged vertical slip rate of about 3 mm/yr. Similar fault zone architecture and post-LGM tectonic subsidence rate is also found in the northern portion of the fault. A correlation between geomorphology and structural geology in the Shanchiao Fault zone demonstrates an array of subtle geomorphic scarps corresponds to the branch fault while the surface trace of the main fault seems to be completely erased by erosion and sedimentation. Such constraints and knowledge are crucial in earthquake hazard evaluation and mitigation in the Taipei Metropolis, and in understanding the kinematics of transtensional tectonics in northern Taiwan. Schematic 3D diagram of the fault zone in the central portion of the Shanchiao Fault, displaying regional subsurface geology and its relation to topographic features.

  2. Frictional Strength of Hayward Fault Gouge

    NASA Astrophysics Data System (ADS)

    Morrow, C.; Moore, D.; Lockner, D.

    2007-12-01

    A recent 3-D geologic model of the Hayward fault in the San Francisco Bay Region shows that a number of different rock units are juxtaposed across the fault surface as a result of lateral displacement. The fault gouge formed therein is likely a mixture of these various rock types. To better model the mechanical behavior of the Hayward fault, which is known to both creep and have large earthquakes, frictional properties of mixtures of the principal rock types were determined in the laboratory. Room temperature triaxial shearing tests were conducted on binary and ternary mixtures of Great Valley Sequence graywacke, Franciscan jadeite-bearing metagraywacke, Franciscan pumpellyite-bearing metasandstone, Franciscan melange matrix, serpentinite and two-pyroxene gabbro. The gouge samples were crushed and sieved (<150 μm grains), then applied in a 1-mm layer between saw-cut sliding blocks. Each sample assemblage was saturated and sheared at constant pore water pressure of 1 MPa and normal stress of 51 MPa. Coefficients of friction, μ, ranged from a low of 0.38 for the serpentinite to a maximum of 0.85 for the gabbro. While the serpentinite and the Franciscan melange matrix were relatively weak, all other rock types obeyed Byerlee's Law. The friction coefficient of mixtures could be reliably predicted by a simple average based on dry weight percent of the end member strengths. This behavior is in contrast to some mixtures of common gouge materials such as montmorillonite+quartz, which exhibit non- linear frictional strength trends with varying weight percent of constituents. All materials tested except serpentinite were velocity strengthening, therefore promoting creeping behavior. The addition of serpentinite decreased a-b values of the gouge and increased the characteristic displacement, dc, of strength evolution. Because temperature strongly influences the mechanical properties of fault gouge as well as speeding chemical reactions between the constituents, elevated

  3. Three-dimensional fault drawing

    SciTech Connect

    Dongan, L. )

    1992-01-01

    In this paper, the author presents a structure interpretation based on three-dimensional fault drawing. It is required that fault closure must be based on geological theory, spacial plotting principle and restrictions in seismic exploration. Geological structure can be well ascertained by analysing the shapes and interrelation of the faults which have been drawn through reasonable fault point closure and fault point correlation. According to this method, the interrelation of fault points is determined by first closing corresponding fault points in intersecting sections, then reasonably correlating the relevant fault points. Fault point correlation is not achieved in base map, so its correctness can be improved greatly. Three-dimensional fault closure is achieved by iteratively revising. The closure grid should be densified gradually. The distribution of major fault system is determined prior to secondary faults. Fault interpretation by workstation also follows this procedure.

  4. Nearly Unity Power-Factor of the Modular Three-Phase AC to DC Converter with Minimized DC Bus Capacitor

    NASA Astrophysics Data System (ADS)

    Chunkag, Viboon; Kamnarn, Uthen

    The analysis and design of nearly unity power-factor and fast dynamic response of the modular three-phase ac to dc converter using three single-phase isolated SEPIC rectifier modules with minimized dc bus capacitor is discussed, based on power balance control technique. The averaged small-signal technique is used to obtain the inductor current compensator, thus resulting in the output impedance and audio susceptibility become zero, that is, the output voltage of the converter presented in this paper is independent of the variations of the dc load current and the utility voltage. The proposed system significantly improves the dynamic response of the converter to load steps with minimized dc bus capacitor for Distributed Power System (DPS). A 600W prototype modular three-phase ac to dc converter comprising three 200W single-phase SEPIC rectifier modules with the proposed control scheme has been designed and implemented. The proposed system is confirmed by experimental implementation.

  5. How Faults Shape the Earth.

    ERIC Educational Resources Information Center

    Bykerk-Kauffman, Ann

    1992-01-01

    Presents fault activity with an emphasis on earthquakes and changes in continent shapes. Identifies three types of fault movement: normal, reverse, and strike faults. Discusses the seismic gap theory, plate tectonics, and the principle of superposition. Vignettes portray fault movement, and the locations of the San Andreas fault and epicenters of…

  6. Controllable Bidirectional dc Power Sources For Large Loads

    NASA Technical Reports Server (NTRS)

    Tripp, John S.; Daniels, Taumi S.

    1995-01-01

    System redesigned for greater efficiency, durability, and controllability. Modern electronically controlled dc power sources proposed to supply currents to six electromagnets used to position aerodynamic test model in wind tunnel. Six-phase bridge rectifier supplies load with large current at voltage of commanded magnitude and polarity. Current-feedback circuit includes current-limiting feature giving some protection against overload.

  7. Fault location of underground distribution network based on RBF network optimized by improved PSO algorithm

    NASA Astrophysics Data System (ADS)

    Tian, Shu; Zhao, Min

    2013-03-01

    To solve the difficult problem that exists in the location of single-phase ground fault for coal mine underground distribution network, a fault location method using RBF network optimized by improved PSO algorithm based on the mapping relationship between wavelet packet transform modulus maxima of specific frequency bands transient state zero sequence current in the fault line and fault point position is presented. The simulation analysis results in the cases of different transition resistances and fault distances show that the RBF network optimized by improved PSO algorithm can obtain accurate and reliable fault location results, and the fault location perfor- mance is better than traditional RBF network.

  8. Fault detection and fault tolerance in robotics

    NASA Technical Reports Server (NTRS)

    Visinsky, Monica; Walker, Ian D.; Cavallaro, Joseph R.

    1992-01-01

    Robots are used in inaccessible or hazardous environments in order to alleviate some of the time, cost and risk involved in preparing men to endure these conditions. In order to perform their expected tasks, the robots are often quite complex, thus increasing their potential for failures. If men must be sent into these environments to repair each component failure in the robot, the advantages of using the robot are quickly lost. Fault tolerant robots are needed which can effectively cope with failures and continue their tasks until repairs can be realistically scheduled. Before fault tolerant capabilities can be created, methods of detecting and pinpointing failures must be perfected. This paper develops a basic fault tree analysis of a robot in order to obtain a better understanding of where failures can occur and how they contribute to other failures in the robot. The resulting failure flow chart can also be used to analyze the resiliency of the robot in the presence of specific faults. By simulating robot failures and fault detection schemes, the problems involved in detecting failures for robots are explored in more depth.

  9. Modeling and Control of VSC Based DC Connection for Active Stall Wind Farms to Grid

    NASA Astrophysics Data System (ADS)

    Iov, Florin; Sørensen, Poul; Hansen, Anca Daniela; Blaabjerg, Frede

    Currently, there is an increasing trend to connect large MW wind farms to the transmission system. Therefore the power system becomes more vulnerable and dependent on the wind energy production. At the same time requirements that focus on the influence of the farms on the grid stability and power quality, and on the control capabilities of wind farms have already been established. The main trends of modern wind turbines/farms are clearly the variable speed operation and a grid connection through a power electronic interface, especially using doubly-fed induction generators. Using power electronics the control capabilities of these wind turbines/farms are extended and thus the grid requirements are fulfilled. However, the traditional squirrel-cage generators based wind turbines/wind farms directly connected to the grid does not have such control capabilities. They produce maximum possible power in continuous operation and are becoming disconnected in the case of a grid fault. Moreover, these wind turbines/farms cannot regulate their production and contribute to power system stability. A DC transmission system for connection of the active stall wind farms to the grid can be a solution to these problems. Such a system has special regulating properties e.g. decoupled control of active and reactive power, continuous AC voltage regulation, variable frequency control, black-start capability, etc. This paper focuses on the modeling of such systems and proposes a control method of a voltage source converter based DC transmission system for connecting active stall wind farms to the grid.

  10. Overview and evolution of the LeRC PMAD DC Testbed

    NASA Astrophysics Data System (ADS)

    Soeder, James F.; Frye, Robert J.

    1992-08-01

    Since the beginning of the Space Station Freedom Program (SSFP), the Lewis Research Center (LeRC) has been developed electrical power system test beds to support the overall design effort. Through this time, the SSFP has changed the design baseline numerous times, however, the test bed effort has endeavored to track these changes. Beginning in August 1989 with the baseline and an all DC system, a test bed was developed to support the design baseline. The LeRC power measurement and distribution (PMAD) DC test bed and the changes in the restructure are described. The changes includeed the size reduction of primary power channel and various power processing elements. A substantial reduction was also made in the amount of flight software with the subsequent migration of these functions to ground control centers. The impact of these changes on the design of the power hardware, the controller algorithms, the control software, and a description of their current status is presented. An overview of the testing using the test bed is described, which includes investigation of stability and source impedance, primary and secondary fault protection, and performance of a rotary utility transfer device. Finally, information is presented on the evolution of the test bed to support the verification and operational phases of the SSFP in light of these restructure scrubs.

  11. Overview and evolution of the LeRC PMAD DC test bed

    NASA Astrophysics Data System (ADS)

    Soeder, James F.; Frye, Robert J.

    Since the beginning of the Space Station Freedom Program (SSFP), the Lewis Research Center (LeRC) has been developed electrical power system test beds to support the overall design effort. Through this time, the SSFP has changed the design baseline numerous times, however, the test bed effort has endeavored to track these changes. Beginning in August 1989 with the baseline and an all DC system, a test bed was developed to support the design baseline. The LeRC power measurement and distribution (PMAD) DC test bed and the changes in the restructure are described. The changes included the size reduction of primary power channel and various power processing elements. A substantial reduction was also made in the amount of flight software with the subsequent migration of these functions to ground control centers. The impact of these changes on the design of the power hardware, the controller algorithms, the control software, and a description of their current status is presented. An overview of the testing using the test bed is described, which includes investigation of stability and source impedance, primary and secondary fault protection, and performance of a rotary utility transfer device. Finally, information is presented on the evolution of the test bed to support the verification and operational phases of the SSFP in light of these restructure scrubs.

  12. Efficient, lightweight dc/dc switching converter

    NASA Technical Reports Server (NTRS)

    Cuk, S.; Middlebrook, R. D.

    1981-01-01

    Converters have input properties of boost power stage and output properties of buck power stage, yet they perform general conversion function with high efficiency. Other features include non-pulsating input/output currents, use of capacitive energy transfer, low output voltage ripple, reduced EMI, and small size.

  13. Tectonic geomorphology and neotectonics of the Kyaukkyan Fault, Myanmar

    NASA Astrophysics Data System (ADS)

    Crosetto, Silvia; Watkinson, Ian; Gori, Stefano; Falcucci, Emanuela; Min, Soe

    2016-04-01

    . Paleoseismological trenching currently underway on the cross-basin fault aims to confirm the 1912 rupture trace, and to delimit the Kyaukkyan Fault's earthquake recurrence interval in order to reveal its modern seismic hazard, fundamental to define the seismic zonation of the area.

  14. 21 CFR 74.1206 - D&C Green No. 6.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... consistent with current good manufacturing practice. (d) Labeling. The label of the color additive shall... ADDITIVES SUBJECT TO CERTIFICATION Drugs § 74.1206 D&C Green No. 6. (a) Identity. The color additive D&C... additive D&C Green No. 6 for use in coloring externally applied drugs shall conform to the...

  15. 21 CFR 74.1206 - D&C Green No. 6.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... consistent with current good manufacturing practice. (d) Labeling. The label of the color additive shall... ADDITIVES SUBJECT TO CERTIFICATION Drugs § 74.1206 D&C Green No. 6. (a) Identity. The color additive D&C... additive D&C Green No. 6 for use in coloring externally applied drugs shall conform to the...

  16. 21 CFR 74.1206 - D&C Green No. 6.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... consistent with current good manufacturing practice. (d) Labeling. The label of the color additive shall... ADDITIVES SUBJECT TO CERTIFICATION Drugs § 74.1206 D&C Green No. 6. (a) Identity. The color additive D&C... additive D&C Green No. 6 for use in coloring externally applied drugs shall conform to the...

  17. 21 CFR 74.1206 - D&C Green No. 6.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... consistent with current good manufacturing practice. (d) Labeling. The label of the color additive shall... ADDITIVES SUBJECT TO CERTIFICATION Drugs § 74.1206 D&C Green No. 6. (a) Identity. The color additive D&C... additive D&C Green No. 6 for use in coloring externally applied drugs shall conform to the...

  18. Analysis of self-oscillating dc-to-dc converters

    NASA Technical Reports Server (NTRS)

    Burger, P.

    1974-01-01

    The basic operational characteristics of dc-to-dc converters are analyzed along with the basic physical characteristics of power converters. A simple class of dc-to-dc power converters are chosen which could satisfy any set of operating requirements, and three different controlling methods in this class are described in detail. Necessary conditions for the stability of these converters are measured through analog computer simulation whose curves are related to other operational characteristics, such as ripple and regulation. Further research is suggested for the solution of absolute stability and efficient physical design of this class of power converters.

  19. High performance dc-dc conversion with voltage multipliers

    NASA Technical Reports Server (NTRS)

    Harrigill, W. T.; Myers, I. T.

    1974-01-01

    The voltage multipliers using capacitors and diodes first developed by Cockcroft and Walton in 1932 were reexamined in terms of state of the art fast switching transistors and diodes, and high energy density capacitors. Because of component improvements, the voltage multiplier, used without a transformer, now appears superior in weight to systems now in use for dc-dc conversion. An experimental 100-watt 1000-volt dc-dc converter operating at 100 kHz was built, with a component weight of about 1 kg/kW. Calculated and measured values of output voltage and efficiency agreed within experimental error.

  20. Optimization of spin-torque switching using AC and DC pulses

    SciTech Connect

    Dunn, Tom; Kamenev, Alex

    2014-06-21

    We explore spin-torque induced magnetic reversal in magnetic tunnel junctions using combined AC and DC spin-current pulses. We calculate the optimal pulse times and current strengths for both AC and DC pulses as well as the optimal AC signal frequency, needed to minimize the Joule heat lost during the switching process. The results of this optimization are compared against numeric simulations. Finally, we show how this optimization leads to different dynamic regimes, where switching is optimized by either a purely AC or DC spin-current, or a combination AC/DC spin-current, depending on the anisotropy energies and the spin-current polarization.

  1. Improved DC Gun Insulator

    SciTech Connect

    M.L. Neubauer, K.B. Beard, R. Sah, C. Hernandez-Garcia, G. Neil

    2009-05-01

    Many user facilities such as synchrotron light sources and free electron lasers require accelerating structures that support electric fields of 10-100 MV/m, especially at the start of the accelerator chain where ceramic insulators are used for very high gradient DC guns. These insulators are difficult to manufacture, require long commissioning times, and have poor reliability, in part because energetic electrons bury themselves in the ceramic, creating a buildup of charge and causing eventual puncture. A novel ceramic manufacturing process is proposed. It will incorporate bulk resistivity in the region where it is needed to bleed off accumulated charge caused by highly energetic electrons. This process will be optimized to provide an appropriate gradient in bulk resistivity from the vacuum side to the air side of the HV standoff ceramic cylinder. A computer model will be used to determine the optimum cylinder dimensions and required resistivity gradient for an example RF gun application. A ceramic material example with resistivity gradient appropriate for use as a DC gun insulator will be fabricated by glazing using doping compounds and tested.

  2. Reset tree-based optical fault detection.

    PubMed

    Lee, Dong-Geon; Choi, Dooho; Seo, Jungtaek; Kim, Howon

    2013-01-01

    In this paper, we present a new reset tree-based scheme to protect cryptographic hardware against optical fault injection attacks. As one of the most powerful invasive attacks on cryptographic hardware, optical fault attacks cause semiconductors to misbehave by injecting high-energy light into a decapped integrated circuit. The contaminated result from the affected chip is then used to reveal secret information, such as a key, from the cryptographic hardware. Since the advent of such attacks, various countermeasures have been proposed. Although most of these countermeasures are strong, there is still the possibility of attack. In this paper, we present a novel optical fault detection scheme that utilizes the buffers on a circuit's reset signal tree as a fault detection sensor. To evaluate our proposal, we model radiation-induced currents into circuit components and perform a SPICE simulation. The proposed scheme is expected to be used as a supplemental security tool. PMID:23698267

  3. Reset Tree-Based Optical Fault Detection

    PubMed Central

    Lee, Dong-Geon; Choi, Dooho; Seo, Jungtaek; Kim, Howon

    2013-01-01

    In this paper, we present a new reset tree-based scheme to protect cryptographic hardware against optical fault injection attacks. As one of the most powerful invasive attacks on cryptographic hardware, optical fault attacks cause semiconductors to misbehave by injecting high-energy light into a decapped integrated circuit. The contaminated result from the affected chip is then used to reveal secret information, such as a key, from the cryptographic hardware. Since the advent of such attacks, various countermeasures have been proposed. Although most of these countermeasures are strong, there is still the possibility of attack. In this paper, we present a novel optical fault detection scheme that utilizes the buffers on a circuit's reset signal tree as a fault detection sensor. To evaluate our proposal, we model radiation-induced currents into circuit components and perform a SPICE simulation. The proposed scheme is expected to be used as a supplemental security tool. PMID:23698267

  4. Study of fault-tolerant software technology

    NASA Technical Reports Server (NTRS)

    Slivinski, T.; Broglio, C.; Wild, C.; Goldberg, J.; Levitt, K.; Hitt, E.; Webb, J.

    1984-01-01

    Presented is an overview of the current state of the art of fault-tolerant software and an analysis of quantitative techniques and models developed to assess its impact. It examines research efforts as well as experience gained from commercial application of these techniques. The paper also addresses the computer architecture and design implications on hardware, operating systems and programming languages (including Ada) of using fault-tolerant software in real-time aerospace applications. It concludes that fault-tolerant software has progressed beyond the pure research state. The paper also finds that, although not perfectly matched, newer architectural and language capabilities provide many of the notations and functions needed to effectively and efficiently implement software fault-tolerance.

  5. Bearing Fault Detection in Induction Motor-Gearbox Drivetrain

    NASA Astrophysics Data System (ADS)

    Cibulka, Jaroslav; Ebbesen, Morten K.; Robbersmyr, Kjell G.

    2012-05-01

    The main contribution in the hereby presented paper is to investigate the fault detection capability of a motor current signature analysis by expanding its scope to include the gearbox, and not only the induction motor. Detecting bearing faults outside the induction motor through the stator current analysis represents an interesting alternative to traditional vibration analysis. Bearing faults cause changes in the stator current spectrum that can be used for fault diagnosis purposes. A time-domain simulation of the drivetrain model is developed. The drivetrain system consists of a loaded single stage gearbox driven by a line-fed induction motor. Three typical bearing faults in the gearbox are addressed, i.e. defects in the outer raceway, the inner raceway, and the rolling element. The interaction with the fault is modelled by means of kinematical and mechanical relations. The fault region is modelled in order to achieve gradual loss and gain of contact. A bearing fault generates an additional torque component that varies at the specific bearing defect frequency. The presented dynamic electromagnetic dq-model of an induction motor is adjusted for diagnostic purpose and considers such torque variations. The bearing fault is detected as a phase modulation of the stator current sine wave at the expected bearing defect frequency.

  6. Normal faults, normal friction?

    NASA Astrophysics Data System (ADS)

    Collettini, Cristiano; Sibson, Richard H.

    2001-10-01

    Debate continues as to whether normal faults may be seismically active at very low dips (δ < 30°) in the upper continental crust. An updated compilation of dip estimates (n = 25) has been prepared from focal mechanisms of shallow, intracontinental, normal-slip earthquakes (M > 5.5; slip vector raking 90° ± 30° in the fault plane) where the rupture plane is unambiguously discriminated. The dip distribution for these moderate-to-large normal fault ruptures extends from 65° > δ > 30°, corresponding to a range, 25° < θr < 60°, for the reactivation angle between the fault and inferred vertical σ1. In a comparable data set previously obtained for reverse fault ruptures (n = 33), the active dip distribution is 10° < δ = θr < 60°. For vertical and horizontal σ1 trajectories within extensional and compressional tectonic regimes, respectively, dip-slip reactivation is thus restricted to faults oriented at θr ≤ 60° to inferred σ1. Apparent lockup at θr ≈ 60° in each dip distribution and a dominant 30° ± 5° peak in the reverse fault dip distribution, are both consistent with a friction coefficient μs ≈ 0.6, toward the bottom of Byerlee's experimental range, though localized fluid overpressuring may be needed for reactivation of less favorably oriented faults.

  7. Fault-Zone Maturity Defines Maximum Earthquake Magnitude: The case of the North Anatolian Fault Zone

    NASA Astrophysics Data System (ADS)

    Bohnhoff, Marco; Bulut, Fatih; Stierle, Eva; Martinez-Garzon, Patricia; Benzion, Yehuda

    2015-04-01

    Estimating the maximum likely magnitude of future earthquakes on transform faults near large metropolitan areas has fundamental consequences for the expected hazard. Here we show that the maximum earthquakes on different sections of the North Anatolian Fault Zone (NAFZ) scale with the duration of fault zone activity, cumulative offset and length of individual fault segments. The findings are based on a compiled catalogue of historical earthquakes in the region, using the extensive literary sources that exist due to the long civilization record. We find that the largest earthquakes (M~8) are exclusively observed along the well-developed part of the fault zone in the east. In contrast, the western part is still in a juvenile or transitional stage with historical earthquakes not exceeding M=7.4. This limits the current seismic hazard to NW Turkey and its largest regional population and economical center Istanbul. Our findings for the NAFZ are consistent with data from the two other major transform faults, the San Andreas fault in California and the Dead Sea Transform in the Middle East. The results indicate that maximum earthquake magnitudes generally scale with fault-zone evolution.

  8. Solar system fault detection

    DOEpatents

    Farrington, R.B.; Pruett, J.C. Jr.

    1984-05-14

    A fault detecting apparatus and method are provided for use with an active solar system. The apparatus provides an indication as to whether one or more predetermined faults have occurred in the solar system. The apparatus includes a plurality of sensors, each sensor being used in determining whether a predetermined condition is present. The outputs of the sensors are combined in a pre-established manner in accordance with the kind of predetermined faults to be detected. Indicators communicate with the outputs generated by combining the sensor outputs to give the user of the solar system and the apparatus an indication as to whether a predetermined fault has occurred. Upon detection and indication of any predetermined fault, the user can take appropriate corrective action so that the overall reliability and efficiency of the active solar system are increased.

  9. Solar system fault detection

    DOEpatents

    Farrington, Robert B.; Pruett, Jr., James C.

    1986-01-01

    A fault detecting apparatus and method are provided for use with an active solar system. The apparatus provides an indication as to whether one or more predetermined faults have occurred in the solar system. The apparatus includes a plurality of sensors, each sensor being used in determining whether a predetermined condition is present. The outputs of the sensors are combined in a pre-established manner in accordance with the kind of predetermined faults to be detected. Indicators communicate with the outputs generated by combining the sensor outputs to give the user of the solar system and the apparatus an indication as to whether a predetermined fault has occurred. Upon detection and indication of any predetermined fault, the user can take appropriate corrective action so that the overall reliability and efficiency of the active solar system are increased.

  10. Simulating the effect of SFCL on limiting the internal fault of synchronous machine

    NASA Astrophysics Data System (ADS)

    Kheirizad, I.; Varahram, M. H.; Jahed-Motlagh, M. R.; Rahnema, M.; Mohammadi, A.

    2008-02-01

    In this paper, we have modelled a synchronous generator with internal one phase to ground fault and then the performance of this machine with internal one phase to ground fault have been analyzed. The results show that if the faults occur in vicinity of machine's terminal, then we would have serious damages. To protect the machine from this kind of faults we have suggested integrating a SFCL (superconducting fault current limiter) into the machine's model. The results show that the fault currents in this case will reduce considerably without influencing the normal operation of the machine.

  11. Trends of DC Power Technologies and their Applications

    NASA Astrophysics Data System (ADS)

    Hirose, Keiichi

    Renewable energy resources such as photovoltaic panels and wind turbines have been increasing rapidly to prevent global warming. The number of energy storage systems and many types of batteries is also growing to keep supply and demand balance in local areas. Interfaces of these facilities are direct current (DC). Most of modern electrical appliances also use DC power inside them. Therefore, DC power technologies with some features are expected to meet requirements for new electrical power systems, for example smartgrids, microgrids, and other electrical applications. In recent years, DC power applications in data centers, commercial buildings, and dwellings have been developed in Japan, the U.S. European countries, and so on. At the same time, international standardization activities had started. This paper describes trends of DC power technologies and their applications.

  12. Deformation associated with faulting within geologic and interseismic timescales

    NASA Astrophysics Data System (ADS)

    Marshall, Scott T.

    2008-04-01

    This dissertation consists of several distinct studies that use numerical modeling to better constrain deformation due to faulting over disparate timescales. Field mapping reveals a segment of the Lake Mead fault system, the Pinto Ridge fault, and a cluster of west-dipping normal faults located near Pinto Ridge. I suggest that this strike-slip segment was kinematically related to the Bitter Spring Valley fault, created the normal fault cluster at Pinto Ridge, and utilized these normal faults as linking structures between fault segments. Modeling results demonstrate that the location and orientations of the normal faults are consistent with having formed in the perturbed stress field around the slipping Pinto Ridge fault. Calculations of mechanical efficiency suggest that a preferred dip of normal faults in the region may reflect a crustal anisotropy at depth, such as a detachment. I present a methodology for simulating interseismic deformation in complex regions. I derive an analytical model of interseismic deformation that is equivalent to the conventional model. Based on this model, I formulate a two-step numerical simulation of geologic and interseismic deformation. I apply this technique to the Los Angeles region and find that model results match well both geologic slip rate estimates and geodetic velocities. Model results suggest that the Puente Hills thrusts are currently slipping at rates that are compatible with geologic estimates and that localized contraction in the San Gabriel basin is dominantly due to deep slip on the Sierra Madre fault. To assess the control of fault geometry and mechanical interactions on fault slip in a natural system, I create models of the Ventura region, California, using both planar and non-planar faults. I find that incorporating geologically-constrained fault surfaces into numerical models results in a better match to available geologic slip rate data than models utilizing planar faults. Because slip rates at most locations

  13. How clays weaken faults.

    NASA Astrophysics Data System (ADS)

    van der Pluijm, Ben A.; Schleicher, Anja M.; Warr, Laurence N.

    2010-05-01

    The weakness of upper crustal faults has been variably attributed to (i) low values of normal stress, (ii) elevated pore-fluid pressure, and (iii) low frictional strength. Direct observations on natural faults rocks provide new evidence for the role of frictional properties on fault strength, as illustrated by our recent work on samples from the San Andreas Fault Observatory at Depth (SAFOD) drillhole at Parkfield, California. Mudrock samples from fault zones at ~3066 m and ~3296 m measured depth show variably spaced and interconnected networks of displacement surfaces that consist of host rock particles that are abundantly coated by polished films with occasional striations. Transmission electron microscopy and X-ray diffraction study of the surfaces reveal the occurrence of neocrystallized thin-film clay coatings containing illite-smectite (I-S) and chlorite-smectite (C-S) phases. X-ray texture goniometry shows that the crystallographic fabric of these faults rocks is characteristically low, in spite of an abundance of clay phases. 40Ar/39Ar dating of the illitic mix-layered coatings demonstrate recent crystallization and reveal the initiation of an "older" fault strand (~8 Ma) at 3066 m measured depth, and a "younger" fault strand (~4 Ma) at 3296 m measured depth. Today, the younger strand is the site of active creep behavior, reflecting continued activation of these clay-weakened zones. We propose that the majority of slow fault creep is controlled by the high density of thin (< 100nm thick) nano-coatings on fracture surfaces, which become sufficiently smectite-rich and interconnected at low angles to allow slip with minimal breakage of stronger matrix clasts. Displacements are accommodated by localized frictional slip along coated particle surfaces and hydrated smectitic phases, in combination with intracrystalline deformation of the clay lattice, associated with extensive mineral dissolution, mass transfer and continued growth of expandable layers. The

  14. Electrostatic quadrupole DC accelerators for BNCT applications

    SciTech Connect

    Kwan, J.W.; Anderson, O.A.; Reginato, L.L.; Vella, M.C.; Yu, S.S.

    1994-04-01

    A dc electrostatic quadrupole (ESQ) accelerator is capable of producing a 2.5 MeV, 100 mA proton beam for the purpose of generating neutrons for Boron Neutron Capture Therapy. The ESQ accelerator is better than the conventional aperture column in high beam current application due to the presence of stronger transverse field for beam focusing and for suppressing secondary electrons. The major challenge in this type of accelerator is in developing the proper power supply system.

  15. Circuit Regulates Speed Of dc Motor

    NASA Technical Reports Server (NTRS)

    Weaver, Charles; Padden, Robin; Brown, Floyd A., Jr.

    1990-01-01

    Driving circuit regulates speed of small dc permanent-magnet motor in tape recorder. Two nested feedback loops maintain speed within 1 percent of constant value. Inner loop provides coarse regulation, while outer loop removes most of variation in speed that remains in the presence of regulation by the inner loop. Compares speed of motor with commanded speed and adjusts current supplied to motor accordingly.

  16. A High Power Density DC-DC Converter for Distributed PV Architectures

    SciTech Connect

    Agamy, Mohammed S; Chi, Song; Elasser, Ahmed; Harfman-Todorovic, Maja; Jiang, Yan; Mueller, Frank; Tao, Fengfeng

    2012-06-01

    In order to maximize solar energy harvesting capabilities, power converters have to be designed for high efficiency and good MPPT and voltage/current performance. When many converters are used in distributed systems, power density also becomes an important factor as it allows for simpler system integration. In this paper a high power density string dc-dc converter suitable for distributed medium to large scale PV installation is presented. A simple partial power processing topology, implemented with all silicon carbide devices provides high efficiency as well as high power density. A 3.5kW, 100kHz converter is designed and tested to verify the proposed methods.

  17. A Plasma-Based DC-DC Electrical Transformer

    NASA Astrophysics Data System (ADS)

    Nebel, Richard; Finn, John

    2013-10-01

    Previous work has indicated that it may be possible to make DC-DC electrical transformers using plasmas. The mechanism is an MHD electromagnetic relaxation process induced by helical electrodes. This process is now being tested on the Bismark device at Tibbar Technologies.

  18. Dc-To-Dc Converter Uses Reverse Conduction Of MOSFET's

    NASA Technical Reports Server (NTRS)

    Gruber, Robert P.; Gott, Robert W.

    1991-01-01

    In modified high-power, phase-controlled, full-bridge, pulse-width-modulated dc-to-dc converters, switching devices power metal oxide/semiconductor field-effect transistors (MOSFET's). Decreases dissipation of power during switching by eliminating approximately 0.7-V forward voltage drop in anti-parallel diodes. Energy-conversion efficiency increased.

  19. Strike-slip fault propagation and linkage via work optimization with application to the San Jacinto fault, California

    NASA Astrophysics Data System (ADS)

    Madden, E. H.; McBeck, J.; Cooke, M. L.

    2013-12-01

    Over multiple earthquake cycles, strike-slip faults link to form through-going structures, as demonstrated by the continuous nature of the mature San Andreas fault system in California relative to the younger and more segmented San Jacinto fault system nearby. Despite its immaturity, the San Jacinto system accommodates between one third and one half of the slip along the boundary between the North American and Pacific plates. It therefore poses a significant seismic threat to southern California. Better understanding of how the San Jacinto system has evolved over geologic time and of current interactions between faults within the system is critical to assessing this seismic hazard accurately. Numerical models are well suited to simulating kilometer-scale processes, but models of fault system development are challenged by the multiple physical mechanisms involved. For example, laboratory experiments on brittle materials show that faults propagate and eventually join (hard-linkage) by both opening-mode and shear failure. In addition, faults interact prior to linkage through stress transfer (soft-linkage). The new algorithm GROW (GRowth by Optimization of Work) accounts for this complex array of behaviors by taking a global approach to fault propagation while adhering to the principals of linear elastic fracture mechanics. This makes GROW a powerful tool for studying fault interactions and fault system development over geologic time. In GROW, faults evolve to minimize the work (or energy) expended during deformation, thereby maximizing the mechanical efficiency of the entire system. Furthermore, the incorporation of both static and dynamic friction allows GROW models to capture fault slip and fault propagation in single earthquakes as well as over consecutive earthquake cycles. GROW models with idealized faults reveal that the initial fault spacing and the applied stress orientation control fault linkage propensity and linkage patterns. These models allow the gains in

  20. Early Oscillation Detection Technique for Hybrid DC/DC Converters

    NASA Technical Reports Server (NTRS)

    Wang, Bright L.

    2011-01-01

    Oscillation or instability is a situation that must be avoided for reliable hybrid DC/DC converters. A real-time electronics measurement technique was developed to detect catastrophic oscillations at early stages for hybrid DC/DC converters. It is capable of identifying low-level oscillation and determining the degree of the oscillation at a unique frequency for every individual model of the converters without disturbing their normal operations. This technique is specially developed for space-used hybrid DC/DC converters, but it is also suitable for most of commercial and military switching-mode power supplies. This is a weak-electronic-signal detection technique to detect hybrid DC/DC converter oscillation presented as a specific noise signal at power input pins. It is based on principles of feedback control loop oscillation and RF signal modulations, and is realized by using signal power spectral analysis. On the power spectrum, a channel power amplitude at characteristic frequency (CPcf) and a channel power amplitude at switching frequency (CPsw) are chosen as oscillation level indicators. If the converter is stable, the CPcf is a very small pulse and the CPsw is a larger, clear, single pulse. At early stage of oscillation, the CPcf increases to a certain level and the CPsw shows a small pair of sideband pulses around it. If the converter oscillates, the CPcf reaches to a higher level and the CPsw shows more high-level sideband pulses. A comprehensive stability index (CSI) is adopted as a quantitative measure to accurately assign a degree of stability to a specific DC/DC converter. The CSI is a ratio of normal and abnormal power spectral density, and can be calculated using specified and measured CPcf and CPsw data. The novel and unique feature of this technique is the use of power channel amplitudes at characteristic frequency and switching frequency to evaluate stability and identify oscillations at an early stage without interfering with a DC/DC converter s

  1. The Kunlun Fault

    NASA Technical Reports Server (NTRS)

    2002-01-01

    The Kunlun fault is one of the gigantic strike-slip faults that bound the north side of Tibet. Left-lateral motion along the 1,500-kilometer (932-mile) length of the Kunlun has occurred uniformly for the last 40,000 years at a rate of 1.1 centimeter per year, creating a cumulative offset of more than 400 meters. In this image, two splays of the fault are clearly seen crossing from east to west. The northern fault juxtaposes sedimentary rocks of the mountains against alluvial fans. Its trace is also marked by lines of vegetation, which appear red in the image. The southern, younger fault cuts through the alluvium. A dark linear area in the center of the image is wet ground where groundwater has ponded against the fault. Measurements from the image of displacements of young streams that cross the fault show 15 to 75 meters (16 to 82 yards) of left-lateral offset. The Advanced Spaceborne Thermal Emission and Reflection Radiometer (ASTER) acquired the visible light and near infrared scene on July 20, 2000. Image courtesy NASA/GSFC/MITI/ERSDAC/JAROS, and the U.S./Japan ASTER Science Team

  2. Faulting processes in active faults - Evidences from TCDP and SAFOD drill core samples

    SciTech Connect

    Janssen, C.; Wirth, R.; Wenk, H. -R.; Morales, L.; Naumann, R.; Kienast, M.; Song, S. -R.; Dresen, G.

    2014-08-20

    The microstructures, mineralogy and chemistry of representative samples collected from the cores of the San Andreas Fault drill hole (SAFOD) and the Taiwan Chelungpu-Fault Drilling project (TCDP) have been studied using optical microscopy, TEM, SEM, XRD and XRF analyses. SAFOD samples provide a transect across undeformed host rock, the fault damage zone and currently active deforming zones of the San Andreas Fault. TCDP samples are retrieved from the principal slip zone (PSZ) and from the surrounding damage zone of the Chelungpu Fault. Substantial differences exist in the clay mineralogy of SAFOD and TCDP fault gouge samples. Amorphous material has been observed in SAFOD as well as TCDP samples. In line with previous publications, we propose that melt, observed in TCDP black gouge samples, was produced by seismic slip (melt origin) whereas amorphous material in SAFOD samples was formed by comminution of grains (crush origin) rather than by melting. Dauphiné twins in quartz grains of SAFOD and TCDP samples may indicate high seismic stress. The differences in the crystallographic preferred orientation of calcite between SAFOD and TCDP samples are significant. Microstructures resulting from dissolution–precipitation processes were observed in both faults but are more frequently found in SAFOD samples than in TCDP fault rocks. As already described for many other fault zones clay-gouge fabrics are quite weak in SAFOD and TCDP samples. Clay-clast aggregates (CCAs), proposed to indicate frictional heating and thermal pressurization, occur in material taken from the PSZ of the Chelungpu Fault, as well as within and outside of the SAFOD deforming zones, indicating that these microstructures were formed over a wide range of slip rates.

  3. Thermal Fluid and Fault Interactions at the Intersection of Two Faults, Agua Caliente, California

    NASA Astrophysics Data System (ADS)

    Wood, R. E.; Evans, J. P.

    2011-12-01

    air temperature plays a larger role than anticipated for the subsurface fluids. Conductivity also displays daily cycles. We propose a larger scale map of the intersection of the two faults and the continuation of the Elsinore farther south showing the current extent and probable growth of the damage and alteration as more slip occurs. Spring flow increases post seismic events, and we believe by monitoring fluid chemistry and comparing seismicity along the faults we will see precursors to and effects from fault motion.

  4. Creating dynamic equivalent PV circuit models with impedance spectroscopy for arc-fault modeling.

    SciTech Connect

    Johnson, Jay Dean; Kuszmaul, Scott S.; Strauch, Jason E.; Schoenwald, David Alan

    2011-06-01

    Article 690.11 in the 2011 National Electrical Code{reg_sign} (NEC{reg_sign}) requires new photovoltaic (PV) systems on or penetrating a building to include a listed arc fault protection device. Currently there is little experimental or empirical research into the behavior of the arcing frequencies through PV components despite the potential for modules and other PV components to filter or attenuate arcing signatures that could render the arc detector ineffective. To model AC arcing signal propagation along PV strings, the well-studied DC diode models were found to inadequately capture the behavior of high frequency arcing signals. Instead dynamic equivalent circuit models of PV modules were required to describe the impedance for alternating currents in modules. The nonlinearities present in PV cells resulting from irradiance, temperature, frequency, and bias voltage variations make modeling these systems challenging. Linearized dynamic equivalent circuits were created for multiple PV module manufacturers and module technologies. The equivalent resistances and capacitances for the modules were determined using impedance spectroscopy with no bias voltage and no irradiance. The equivalent circuit model was employed to evaluate modules having irradiance conditions that could not be measured directly with the instrumentation. Although there was a wide range of circuit component values, the complex impedance model does not predict filtering of arc fault frequencies in PV strings for any irradiance level. Experimental results with no irradiance agree with the model and show nearly no attenuation for 1 Hz to 100 kHz input frequencies.

  5. An Adaptive Coordinated Control for an Offshore Wind Farm Connected VSC Based Multi-Terminal DC Transmission System

    NASA Astrophysics Data System (ADS)

    Kumar, M. Ajay; Srikanth, N. V.

    2014-11-01

    The voltage source converter (VSC) based multiterminal high voltage direct current (MTDC) transmission system is an interesting technical option to integrate offshore wind farms with the onshore grid due to its unique performance characteristics and reduced power loss via extruded DC cables. In order to enhance the reliability and stability of the MTDC system, an adaptive neuro fuzzy inference system (ANFIS) based coordinated control design has been addressed in this paper. A four terminal VSC-MTDC system which consists of an offshore wind farm and oil platform is implemented in MATLAB/ SimPowerSystems software. The proposed model is tested under different fault scenarios along with the converter outage and simulation results show that the novel coordinated control design has great dynamic stabilities and also the VSC-MTDC system can supply AC voltage of good quality to offshore loads during the disturbances.

  6. Measuring fault tolerance with the FTAPE fault injection tool

    NASA Technical Reports Server (NTRS)

    Tsai, Timothy K.; Iyer, Ravishankar K.

    1995-01-01

    This paper describes FTAPE (Fault Tolerance And Performance Evaluator), a tool that can be used to compare fault-tolerant computers. The major parts of the tool include a system-wide fault-injector, a workload generator, and a workload activity measurement tool. The workload creates high stress conditions on the machine. Using stress-based injection, the fault injector is able to utilize knowledge of the workload activity to ensure a high level of fault propagation. The errors/fault ratio, performance degradation, and number of system crashes are presented as measures of fault tolerance.

  7. Measuring fault tolerance with the FTAPE fault injection tool

    NASA Astrophysics Data System (ADS)

    Tsai, Timothy K.; Iyer, Ravishankar K.

    1995-05-01

    This paper describes FTAPE (Fault Tolerance And Performance Evaluator), a tool that can be used to compare fault-tolerant computers. The major parts of the tool include a system-wide fault-injector, a workload generator, and a workload activity measurement tool. The workload creates high stress conditions on the machine. Using stress-based injection, the fault injector is able to utilize knowledge of the workload activity to ensure a high level of fault propagation. The errors/fault ratio, performance degradation, and number of system crashes are presented as measures of fault tolerance.

  8. 76 FR 13926 - Airworthiness Directives; The Boeing Company Model DC-8-11, DC-8-12, DC-8-21, DC-8-31, DC-8-32...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-03-15

    ... required by AD 2008-25-05, Amendment 39-15763 (73 FR 78936, December 24, 2008), for Principal Structural... Policies and Procedures (44 FR 11034, February 26, 1979), and 3. Will not have a significant economic...-8-21, DC-8-31, DC-8-32, DC-8-33, DC-8-41, DC-8-42, DC-8-43, DC-8-51, DC-8-52, DC-8-53,......

  9. Diagnosing faults in autonomous robot plan execution

    NASA Technical Reports Server (NTRS)

    Lam, Raymond K.; Doshi, Rajkumar S.; Atkinson, David J.; Lawson, Denise M.

    1989-01-01

    A major requirement for an autonomous robot is the capability to diagnose faults during plan execution in an uncertain environment. Many diagnostic researches concentrate only on hardware failures within an autonomous robot. Taking a different approach, the implementation of a Telerobot Diagnostic System that addresses, in addition to the hardware failures, failures caused by unexpected event changes in the environment or failures due to plan errors, is described. One feature of the system is the utilization of task-plan knowledge and context information to deduce fault symptoms. This forward deduction provides valuable information on past activities and the current expectations of a robotic event, both of which can guide the plan-execution inference process. The inference process adopts a model-based technique to recreate the plan-execution process and to confirm fault-source hypotheses. This technique allows the system to diagnose multiple faults due to either unexpected plan failures or hardware errors. This research initiates a major effort to investigate relationships between hardware faults and plan errors, relationships which were not addressed in the past. The results of this research will provide a clear understanding of how to generate a better task planner for an autonomous robot and how to recover the robot from faults in a critical environment.

  10. Diagnosing faults in autonomous robot plan execution

    NASA Technical Reports Server (NTRS)

    Lam, Raymond K.; Doshi, Rajkumar S.; Atkinson, David J.; Lawson, Denise M.

    1988-01-01

    A major requirement for an autonomous robot is the capability to diagnose faults during plan execution in an uncertain environment. Many diagnostic researches concentrate only on hardware failures within an autonomous robot. Taking a different approach, the implementation of a Telerobot Diagnostic System that addresses, in addition to the hardware failures, failures caused by unexpected event changes in the environment or failures due to plan errors, is described. One feature of the system is the utilization of task-plan knowledge and context information to deduce fault symptoms. This forward deduction provides valuable information on past activities and the current expectations of a robotic event, both of which can guide the plan-execution inference process. The inference process adopts a model-based technique to recreate the plan-execution process and to confirm fault-source hypotheses. This technique allows the system to diagnose multiple faults due to either unexpected plan failures or hardware errors. This research initiates a major effort to investigate relationships between hardware faults and plan errors, relationships which were not addressed in the past. The results of this research will provide a clear understanding of how to generate a better task planner for an autonomous robot and how to recover the robot from faults in a critical environment.

  11. Laboratory Simulation of Shear Band Development in Growth Normal Fault

    NASA Astrophysics Data System (ADS)

    Chu, Sheng-Shin; Lin, Ming-Lang

    2013-04-01

    current building codes, especially for critical facilities such as the nuclear power plant. Key words: Shanchiao Fault, Growth Normal Fault, Sand Box Test, Shear Band, Offset Ratio

  12. OpenStudio - Fault Modeling

    Energy Science and Technology Software Center (ESTSC)

    2014-09-19

    This software record documents the OpenStudio fault model development portion of the Fault Detection and Diagnostics LDRD project.The software provides a suite of OpenStudio measures (scripts) for modeling typical HVAC system faults in commercial buildings and also included supporting materials: example projects and OpenStudio measures for reporting fault costs and energy impacts.

  13. Validation of Helicopter Gear Condition Indicators Using Seeded Fault Tests

    NASA Technical Reports Server (NTRS)

    Dempsey, Paula; Brandon, E. Bruce

    2013-01-01

    A "seeded fault test" in support of a rotorcraft condition based maintenance program (CBM), is an experiment in which a component is tested with a known fault while health monitoring data is collected. These tests are performed at operating conditions comparable to operating conditions the component would be exposed to while installed on the aircraft. Performance of seeded fault tests is one method used to provide evidence that a Health Usage Monitoring System (HUMS) can replace current maintenance practices required for aircraft airworthiness. Actual in-service experience of the HUMS detecting a component fault is another validation method. This paper will discuss a hybrid validation approach that combines in service-data with seeded fault tests. For this approach, existing in-service HUMS flight data from a naturally occurring component fault will be used to define a component seeded fault test. An example, using spiral bevel gears as the targeted component, will be presented. Since the U.S. Army has begun to develop standards for using seeded fault tests for HUMS validation, the hybrid approach will be mapped to the steps defined within their Aeronautical Design Standard Handbook for CBM. This paper will step through their defined processes, and identify additional steps that may be required when using component test rig fault tests to demonstrate helicopter CI performance. The discussion within this paper will provide the reader with a better appreciation for the challenges faced when defining a seeded fault test for HUMS validation.

  14. Architectural issues in fault-tolerant, secure computing systems

    SciTech Connect

    Joseph, M.K.

    1988-01-01

    This dissertation explores several facets of the applicability of fault-tolerance techniques to secure computer design, these being: (1) how fault-tolerance techniques can be used on unsolved problems in computer security (e.g., computer viruses, and denial-of-service); (2) how fault-tolerance techniques can be used to support classical computer-security mechanisms in the presence of accidental and deliberate faults; and (3) the problems involved in designing a fault-tolerant, secure computer system (e.g., how computer security can degrade along with both the computational and fault-tolerance capabilities of a computer system). The approach taken in this research is almost as important as its results. It is different from current computer-security research in that a design paradigm for fault-tolerant computer design is used. This led to an extensive fault and error classification of many typical security threats. Throughout this work, a fault-tolerance perspective is taken. However, the author did not ignore basic computer-security technology. For some problems he investigated how to support and extend basic-security mechanism (e.g., trusted computing base), instead of trying to achieve the same result with purely fault-tolerance techniques.

  15. Detachment faults: Evidence for a low-angle origin

    SciTech Connect

    Scott, R.J.; Lister, G.S. )

    1992-09-01

    The origin of low-angle normal faults or detachment faults mantling metamorphic core complexes in the southwestern United States remains controversial. If [sigma][sub 1] is vertical during extension, the formation of, or even slip along, such low-angle normal faults is mechanically implausible. No records exist of earthquakes on low-angle normal faults in areas currently undergoing continental extension, except from an area of actively forming core complexes in the Solomon Sea, Papua New Guinea. In light of such geophysical and mechanical arguments, W.R. Buck and B. Wernicke and G.J. Axen proposed models in which detachment faults originate as high-angle normal faults, but rotate to low angles and become inactive as extension proceeds. These models are inconsistent with critical field relations in several core complexes. The Rawhide fault, an areally extensive detachment fault in western Arizona, propagated at close to its present subhorizontal orientation late in the Tertiary extension of the region. Neither the Wernicke and Axen nor Buck models predict such behavior; in fact, both models preclude the operation of low-angle normal faults. The authors recommend that alternative explanations or modifications of existing models are needed to explain the evidence that detachment faults form and operate with gentle dips.

  16. A dc magnetic field distribution transducer (abstract)

    NASA Astrophysics Data System (ADS)

    Hristoforou, E.

    1991-04-01

    A new way of measuring magnetic field distribution is proposed, based on the change of the response of a magnetostrictive delay line (MDL) to varying dc magnetic field. The principal idea runs as follows: an array of wires Ci, transmitting pulsed current Ie, crosses at 45° an array of MDL Lj. The resulting pulsed field at the crossing points Pij excites an acoustic pulses in the lines, detected by short coils placed close to one end, in terms of voltage Voij. If a dc magnetic field Hdc is applied at the point Pij, the acoustic pulse and hence Voij change. Experimental results are given, showing the dependence of V0 on the applied dc field under various values of Ie for the case of a 1 mm wide Metglas 2605SC MDL. The function of Vom vs Hdc under various values of Ie is also given, where Vom is the maximum value of the absolute positive and negative peaks of V0. The first derivative of this function equals zero for two values of Hdc, corresponding to approximately equal positive and negative peaks of V0. So, having divided this function in 4 parts, comparison of these two peaks and experimental data are used to find the orientation and magnitude of the dc field on the MDL axis. It was also found that V0, corresponding to an Hdc applied at an angle v to the MDL equals the response of a dc field having a magnitude Hdc cos(v) and applied along the length of the line. So, by having another array of delay lines L'i identical but orthogonal to the previous MDL array Lj and crossing in 45° the conducting wires array Ci, we can keep the same number of crossing points. Hence, measurements from two delay lines Li and L'i corresponding to Pij, give a 2-d vector of the dc magnetic field applied at this point. The uniformity and the resolution of such a transducer can be improved by using the recently developed FeSiB wires after stress annealing. Future work is to be done to increase the frequency and the range of the measurable dc field.

  17. Real-time fault diagnosis for propulsion systems

    NASA Technical Reports Server (NTRS)

    Merrill, Walter C.; Guo, Ten-Huei; Delaat, John C.; Duyar, Ahmet

    1991-01-01

    Current research toward real time fault diagnosis for propulsion systems at NASA-Lewis is described. The research is being applied to both air breathing and rocket propulsion systems. Topics include fault detection methods including neural networks, system modeling, and real time implementations.

  18. Hayward Fault, California Interferogram

    NASA Technical Reports Server (NTRS)

    2000-01-01

    This image of California's Hayward fault is an interferogram created using a pair of images taken by Synthetic Aperture Radar(SAR) combined to measure changes in the surface that may have occurred between the time the two images were taken.

    The images were collected by the European Space Agency's Remote Sensing satellites ERS-1 and ERS-2 in June 1992 and September 1997 over the central San Francisco Bay in California.

    The radar image data are shown as a gray-scale image, with the interferometric measurements that show the changes rendered in color. Only the urbanized area could be mapped with these data. The color changes from orange tones to blue tones across the Hayward fault (marked by a thin red line) show about 2-3centimeters (0.8-1.1 inches) of gradual displacement or movement of the southwest side of the fault. The block west of the fault moved horizontally toward the northwest during the 63 months between the acquisition of the two SAR images. This fault movement is called a seismic creep because the fault moved slowly without generating an earthquake.

    Scientists are using the SAR interferometry along with other data collected on the ground to monitor this fault motion in an attempt to estimate the probability of earthquake on the Hayward fault, which last had a major earthquake of magnitude 7 in 1868. This analysis indicates that the northern part of the Hayward fault is creeping all the way from the surface to a depth of 12 kilometers (7.5 miles). This suggests that the potential for a large earthquake on the northern Hayward fault might be less than previously thought. The blue area to the west (lower left) of the fault near the center of the image seemed to move upward relative to the yellow and orange areas nearby by about 2 centimeters (0.8 inches). The cause of this apparent motion is not yet confirmed, but the rise of groundwater levels during the time between the images may have caused the reversal of a small portion of the subsidence that

  19. Fault rupture segmentation

    NASA Astrophysics Data System (ADS)

    Cleveland, Kenneth Michael

    A critical foundation to earthquake study and hazard assessment is the understanding of controls on fault rupture, including segmentation. Key challenges to understanding fault rupture segmentation include, but are not limited to: What determines if a fault segment will rupture in a single great event or multiple moderate events? How is slip along a fault partitioned between seismic and seismic components? How does the seismicity of a fault segment evolve over time? How representative are past events for assessing future seismic hazards? In order to address the difficult questions regarding fault rupture segmentation, new methods must be developed that utilize the information available. Much of the research presented in this study focuses on the development of new methods for attacking the challenges of understanding fault rupture segmentation. Not only do these methods exploit a broader band of information within the waveform than has traditionally been used, but they also lend themselves to the inclusion of even more seismic phases providing deeper understandings. Additionally, these methods are designed to be fast and efficient with large datasets, allowing them to utilize the enormous volume of data available. Key findings from this body of work include demonstration that focus on fundamental earthquake properties on regional scales can provide general understanding of fault rupture segmentation. We present a more modern, waveform-based method that locates events using cross-correlation of the Rayleigh waves. Additionally, cross-correlation values can also be used to calculate precise earthquake magnitudes. Finally, insight regarding earthquake rupture directivity can be easily and quickly exploited using cross-correlation of surface waves.

  20. Fault Tolerant Homopolar Magnetic Bearings

    NASA Technical Reports Server (NTRS)

    Li, Ming-Hsiu; Palazzolo, Alan; Kenny, Andrew; Provenza, Andrew; Beach, Raymond; Kascak, Albert

    2003-01-01

    Magnetic suspensions (MS) satisfy the long life and low loss conditions demanded by satellite and ISS based flywheels used for Energy Storage and Attitude Control (ACESE) service. This paper summarizes the development of a novel MS that improves reliability via fault tolerant operation. Specifically, flux coupling between poles of a homopolar magnetic bearing is shown to deliver desired forces even after termination of coil currents to a subset of failed poles . Linear, coordinate decoupled force-voltage relations are also maintained before and after failure by bias linearization. Current distribution matrices (CDM) which adjust the currents and fluxes following a pole set failure are determined for many faulted pole combinations. The CDM s and the system responses are obtained utilizing 1D magnetic circuit models with fringe and leakage factors derived from detailed, 3D, finite element field models. Reliability results are presented vs. detection/correction delay time and individual power amplifier reliability for 4, 6, and 7 pole configurations. Reliability is shown for two success criteria, i.e. (a) no catcher bearing contact following pole failures and (b) re-levitation off of the catcher bearings following pole failures. An advantage of the method presented over other redundant operation approaches is a significantly reduced requirement for backup hardware such as additional actuators or power amplifiers.

  1. Fault Wear and Friction Evolution: Experimental Analysis

    NASA Astrophysics Data System (ADS)

    Boneh, Y.; Chang, J. C.; Lockner, D. A.; Reches, Z.

    2011-12-01

    Wear is an inevitable product of frictional sliding of brittle rocks as evidenced by the ubiquitous occurrence of fault gouge and slickenside striations. We present here experimental observations designed to demonstrate the relationship between wear and friction and their governing mechanisms. The experiments were conducted with a rotary shear apparatus on solid, ring-shaped rock samples that slipped for displacements up to tens of meters. Stresses, wear and temperature were continuously monitored. We analyzed 86 experiments of Kasota dolomite, Sierra White granite, Pennsylvania quartzite, Karoo gabbro, and Tennessee sandstone at slip velocities ranging from 0.002 to 0.97 m/s, and normal stress from 0.25 to 6.9 MPa. We conducted two types of runs: short slip experiments (slip distance < 25 mm) primarily on fresh, surface-ground samples, designed to analyze initial wear mechanisms; and long slip experiments (slip distance > 3 m) designed to achieve mature wear conditions and to observe the evolution of wear and friction as the fault surfaces evolved. The experiments reveal three wear stages: initial, running-in, and steady-state. The initial stage is characterized by (1) discrete damage striations, the length of which is comparable to total slip , and local pits or plow features; (2) timing and magnitude of fault-normal dilation corresponds to transient changes of normal and shear stresses; and (3) surface roughness increasing with the applied normal stress. We interpret these observations as wear mechanisms of (a) plowing into the fresh rock surfaces; (b) asperity breakage; and (c) asperity climb. The running-in stage is characterized by (1) intense wear-rate over a critical wear distance of Rd = 0.3-2 m; (2) drop of friction coefficient over a weakening distance of Dc = 0.2-4 m; (3) Rd and Dc display positive, quasi-linear relation with each other. We interpret these observations as indicating the organizing of newly-created wear particles into a 'three

  2. Creating an automated chiller fault detection and diagnostics tool using a data fault library.

    PubMed

    Bailey, Margaret B; Kreider, Jan F

    2003-07-01

    Reliable, automated detection and diagnosis of abnormal behavior within vapor compression refrigeration cycle (VCRC) equipment is extremely desirable for equipment owners and operators. The specific type of VCRC equipment studied in this paper is a 70-ton helical rotary, air-cooled chiller. The fault detection and diagnostic (FDD) tool developed as part of this research analyzes chiller operating data and detects faults through recognizing trends or patterns existing within the data. The FDD method incorporates a neural network (NN) classifier to infer the current state given a vector of observables. Therefore the FDD method relies upon the availability of normal and fault empirical data for training purposes and therefore a fault library of empirical data is assembled. This paper presents procedures for conducting sophisticated fault experiments on chillers that simulate air-cooled condenser, refrigerant, and oil related faults. The experimental processes described here are not well documented in literature and therefore will provide the interested reader with a useful guide. In addition, the authors provide evidence, based on both thermodynamics and empirical data analysis, that chiller performance is significantly degraded during fault operation. The chiller's performance degradation is successfully detected and classified by the NN FDD classifier as discussed in the paper's final section. PMID:12858981

  3. Assessing active faulting by hydrogeological modeling and superconducting gravimetry: A case study for Hsinchu Fault, Taiwan

    NASA Astrophysics Data System (ADS)

    Lien, Tzuyi; Cheng, Ching-Chung; Hwang, Cheinway; Crossley, David

    2014-09-01

    We develop a new hydrology and gravimetry-based method to assess whether or not a local fault may be active. We take advantage of an existing superconducting gravimeter (SG) station and a comprehensive groundwater network in Hsinchu to apply the method to the Hsinchu Fault (HF) across the Hsinchu Science Park, whose industrial output accounts for 10% of Taiwan's gross domestic product. The HF is suspected to pose seismic hazards to the park, but its existence and structure are not clear. The a priori geometry of the HF is translated into boundary conditions imposed in the hydrodynamic model. By varying the fault's location, depth, and including a secondary wrench fault, we construct five hydrodynamic models to estimate groundwater variations, which are evaluated by comparing groundwater levels and SG observations. The results reveal that the HF contains a low hydraulic conductivity core and significantly impacts groundwater flows in the aquifers. Imposing the fault boundary conditions leads to about 63-77% reduction in the differences between modeled and observed values (both water level and gravity). The test with fault depth shows that the HF's most recent slip occurred in the beginning of Holocene, supplying a necessary (but not sufficient) condition that the HF is currently active. A portable SG can act as a virtual borehole well for model assessment at critical locations of a suspected active fault.

  4. Fault weakening across the frictional-viscous transition zone, Karakoram Fault Zone, NW Himalaya

    NASA Astrophysics Data System (ADS)

    Wallis, David; Phillips, Richard J.; Lloyd, Geoffrey E.

    2013-09-01

    fault rocks formed in the frictional-viscous transition zone (FVTZ) provide test material that can be used to assess the strength of natural fault zones. In the Karakoram Fault Zone (KFZ), such rocks contain evidence of several long-term weakening mechanisms associated with reduced coefficients of friction (<0.4). The Nubra, Tangtse, and Arganglas strands of the KFZ are focused along metavolcano-sedimentary formations indicating weakness relative to the bounding granitoids. Synkinematic retrogression suggests that reaction softening has weakened the margins of granitoids along the Nubra and Tangtse strands and the Nubra Formation within the Nubra strand. The resultant phyllosilicates have formed well-developed interconnected weak layers within phyllonites and granitic mylonites. Micaceous foliae with increased proportions of opaque minerals in granitic mylonites suggest that fluid-assisted diffusive mass transfer aided deformation within the Nubra and Tangtse strands. Microstructures within Nubra strand phyllonites suggest that frictional-viscous flow accommodated deformation at low shear stresses in the FVTZ. Multiple generations of veining within each strand indicate overpressured pore fluids within the fault zone across a range of depths. Active springs and travertines along the fault indicate ongoing suprahydrostatic fluid flow within the KFZ. Despite such evidence for weakening mechanisms, the KFZ is currently locked and most likely generates moment magnitude 7.5+ earthquakes. Evidence for multiple fault weakening mechanisms reduces potential for shear heating within the KFZ and suggests that the long-term strength of the lithosphere must reside below the depth of penetration of the fault.

  5. Bi-Directional DC-DC Converter for PHEV Applications

    SciTech Connect

    Abas Goodarzi

    2011-01-31

    Plug-In Hybrid Electric Vehicles (PHEV) require high power density energy storage system (ESS) for hybrid operation and high energy density ESS for Electric Vehicle (EV) mode range. However, ESS technologies to maximize power density and energy density simultaneously are not commercially feasible. The use of bi-directional DC-DC converter allows use of multiple energy storage, and the flexible DC-link voltages can enhance the system efficiency and reduce component sizing. This will improve fuel consumption, increase the EV mode range, reduce the total weight, reduce battery initial and life cycle cost, and provide flexibility in system design.

  6. Fault lubrication during earthquakes.

    PubMed

    Di Toro, G; Han, R; Hirose, T; De Paola, N; Nielsen, S; Mizoguchi, K; Ferri, F; Cocco, M; Shimamoto, T

    2011-03-24

    The determination of rock friction at seismic slip rates (about 1 m s(-1)) is of paramount importance in earthquake mechanics, as fault friction controls the stress drop, the mechanical work and the frictional heat generated during slip. Given the difficulty in determining friction by seismological methods, elucidating constraints are derived from experimental studies. Here we review a large set of published and unpublished experiments (∼300) performed in rotary shear apparatus at slip rates of 0.1-2.6 m s(-1). The experiments indicate a significant decrease in friction (of up to one order of magnitude), which we term fault lubrication, both for cohesive (silicate-built, quartz-built and carbonate-built) rocks and non-cohesive rocks (clay-rich, anhydrite, gypsum and dolomite gouges) typical of crustal seismogenic sources. The available mechanical work and the associated temperature rise in the slipping zone trigger a number of physicochemical processes (gelification, decarbonation and dehydration reactions, melting and so on) whose products are responsible for fault lubrication. The similarity between (1) experimental and natural fault products and (2) mechanical work measures resulting from these laboratory experiments and seismological estimates suggests that it is reasonable to extrapolate experimental data to conditions typical of earthquake nucleation depths (7-15 km). It seems that faults are lubricated during earthquakes, irrespective of the fault rock composition and of the specific weakening mechanism involved. PMID:21430777

  7. Historical Material Analysis of DC745U Pressure Pads

    SciTech Connect

    Ortiz-Acosta, Denisse

    2012-07-30

    As part of the Enhance Surveillance mission, it is the goal to provide suitable lifetime assessment of stockpile materials. This report is an accumulation of historical publication on the DC745U material and their findings. It is the intention that the B61 LEP program uses this collection of data to further develop their understanding and potential areas of study. DC745U is a commercially available silicone elastomer consisting of dimethyl, methyl-phenyl, and methyl-vinyl siloxane repeat units. Originally, this material was manufactured by Dow Corning as Silastic{reg_sign} DC745U at their manufacturing facility in Kendallville, IN. Recently, Dow Corning shifted this material to the Xiameter{reg_sign} brand product line. Currently, DC745U is available through Xiameter{reg_sign} or Dow Corning's distributor R. D. Abbott Company. DC745U is cured using 0.5 wt% vinyl-specific peroxide curing agent known as Luperox 101 or Varox DBPH-50. This silicone elastomer is used in numerous parts, including two major components (outer pressure pads and aft cap support) in the W80 and as pressure pads on the B61. DC745U is a proprietary formulation, thus Dow Corning provides limited information on its composition and properties. Based on past experience with Dow Corning, DC745U is at risk of formulation changes without notification to the costumer. A formulation change for DC745U may have a significant impact because the network structure is a key variable in determining material properties. The purpose of this report is to provide an overview of historical DC745U studies and identify gaps that need to be addressed in future work. Some of the previous studies include the following: 1. Spectroscopic characterization of raw gum stock. 2. Spectroscopic, thermal, and mechanical studies on cured DC745U. 3. Nuclear Magnetic Resonance (NMR) and solvent swelling studies on DC745U with different crosslink densities. 4. NMR, solvent swelling, thermal, and mechanical studies on thermally aged

  8. Managing systems faults on the commercial flight deck: Analysis of pilots' organization and prioritization of fault management information

    NASA Technical Reports Server (NTRS)

    Rogers, William H.

    1993-01-01

    In rare instances, flight crews of commercial aircraft must manage complex systems faults in addition to all their normal flight tasks. Pilot errors in fault management have been attributed, at least in part, to an incomplete or inaccurate awareness of the fault situation. The current study is part of a program aimed at assuring that the types of information potentially available from an intelligent fault management aiding concept developed at NASA Langley called 'Faultfinde' (see Abbott, Schutte, Palmer, and Ricks, 1987) are an asset rather than a liability: additional information should improve pilot performance and aircraft safety, but it should not confuse, distract, overload, mislead, or generally exacerbate already difficult circumstances.

  9. Artificial neural network application for space station power system fault diagnosis

    NASA Technical Reports Server (NTRS)

    Momoh, James A.; Oliver, Walter E.; Dias, Lakshman G.

    1995-01-01

    This study presents a methodology for fault diagnosis using a Two-Stage Artificial Neural Network Clustering Algorithm. Previously, SPICE models of a 5-bus DC power distribution system with assumed constant output power during contingencies from the DDCU were used to evaluate the ANN's fault diagnosis capabilities. This on-going study uses EMTP models of the components (distribution lines, SPDU, TPDU, loads) and power sources (DDCU) of Space Station Alpha's electrical Power Distribution System as a basis for the ANN fault diagnostic tool. The results from the two studies are contrasted. In the event of a major fault, ground controllers need the ability to identify the type of fault, isolate the fault to the orbital replaceable unit level and provide the necessary information for the power management expert system to optimally determine a degraded-mode load schedule. To accomplish these goals, the electrical power distribution system's architecture can be subdivided into three major classes: DC-DC converter to loads, DC Switching Unit (DCSU) to Main bus Switching Unit (MBSU), and Power Sources to DCSU. Each class which has its own electrical characteristics and operations, requires a unique fault analysis philosophy. This study identifies these philosophies as Riddles 1, 2 and 3 respectively. The results of the on-going study addresses Riddle-1. It is concluded in this study that the combination of the EMTP models of the DDCU, distribution cables and electrical loads yields a more accurate model of the behavior and in addition yielded more accurate fault diagnosis using ANN versus the results obtained with the SPICE models.

  10. A general theory of DC electromagnetic launchers

    NASA Astrophysics Data System (ADS)

    Engel, Thomas G.; Timpson, Erik J.

    2015-08-01

    The non-linear, transient operation of DC electromagnetic launchers (EMLs) complicates their theoretical understanding and prevents scaling studies and performance comparisons without the aid of detailed numerical models. This paper presents a general theory for DC electromagnetic launchers that has simplified these tasks by identifying critical EML parameters and relationships affecting the EML's voltage, current, and power scaling, as well as its performance and energy conversion efficiency. EML parameters and relationships discussed in this paper include the specific force, the operating mode, the launcher constant, the launcher characteristic velocity, the contact characteristic velocity, the energy conversion efficiency, and the kinetic power and voltage-current scaling relationship. The concepts of the ideal EML, same-scale comparisons, and EML impedance are discussed. This paper defines conditions needed for the EML to operate in the steady-state. A comparison of the general theory with experimental results of several different types of DC (i.e., non-induction) electromagnetic launchers ranging from medium velocity (100's m/s) to high velocity (1000's m/s) is performed. There is good agreement between the general theory and the experimental results.

  11. Envelope calculation of the multi-component signal and its application to the deterministic component cancellation in bearing fault diagnosis

    NASA Astrophysics Data System (ADS)

    Ming, A. B.; Zhang, W.; Qin, Z. Y.; Chu, F. L.

    2015-01-01

    Commonly presented as cyclic impulse responses with some degrees of randomness, the vibrations induced by bearing faults are multi-component signals and usually overwhelmed by other deterministic components, which may degrade the efficiency of the traditional envelope analysis used for bearing fault feature extraction. In this paper, the envelope of the multi-component signal, including both discrete frequency components and cyclic impulse responses, is theoretically calculated by the Hilbert transform in both time and frequency domains at first. Then, a novel deterministic component cancellation method is proposed based on the iterative calculation of the signal envelope. Finally, simulations and experiments are used to validate the theoretical calculation and the proposed deterministic component cancellation method. It is indicated that the oscillation part of the envelope is dominated by the cross-terms of the multi-component signal, and that the cross-terms between a discrete frequency component and cyclic impulse responses present as new cyclic impulse responses, which retain the cyclic feature of the original ones. Furthermore, the deterministic component can be canceled by iteratively subtracting the direct current (DC) offset of the envelope. Compared with the cepstrum pre-whiten (CPW) method, used to separate the deterministic (discrete frequency) component from the random component (vibration induced by the bearing fault), the proposed method is more efficient to the shifting of the cyclic impulse responses from the powerful deterministic component with little disruption, and is more suitable for the real time signal processing owing to the high efficient calculation of the Hilbert transform.

  12. Pulse-Width-Modulating Driver for Brushless dc Motor

    NASA Technical Reports Server (NTRS)

    Salomon, Phil M.

    1991-01-01

    High-current pulse-width-modulating driver for brushless dc motor features optical coupling of timing signals from low-current control circuitry to high-current motor-driving circuitry. Provides high electrical isolation of motor-power supply, helping to prevent fast, high-current motor-driving pulses from being coupled through power supplies into control circuitry, where they interfere with low-current control signals.

  13. Quaternary tectonic faulting in the Eastern United States

    USGS Publications Warehouse

    Wheeler, R.L.

    2006-01-01

    City), Lancaster Seismic Zone and the epicenter of the shallow Cacoosing Valley earthquake (Lancaster and Reading, Pennsylvania), Kingston fault (central New Jersey between New York and Philadelphia), and Everona fault-Mountain Run fault zone (Washington, D.C., and Arlington and Alexandria, Virginia). ?? 2005 Elsevier B.V. All rights reserved.

  14. Multi-kw dc power distribution system study program

    NASA Technical Reports Server (NTRS)

    Berkery, E. A.; Krausz, A.

    1974-01-01

    The first phase of the Multi-kw dc Power Distribution Technology Program is reported and involves the test and evaluation of a technology breadboard in a specifically designed test facility according to design concepts developed in a previous study on space vehicle electrical power processing, distribution, and control. The static and dynamic performance, fault isolation, reliability, electromagnetic interference characterisitics, and operability factors of high distribution systems were studied in order to gain a technology base for the use of high voltage dc systems in future aerospace vehicles. Detailed technical descriptions are presented and include data for the following: (1) dynamic interactions due to operation of solid state and electromechanical switchgear; (2) multiplexed and computer controlled supervision and checkout methods; (3) pulse width modulator design; and (4) cable design factors.

  15. Piezometer completion report for borehold cluster sites DC-19, DC-20 and DC-22

    SciTech Connect

    Jackson, R.L.; Diediker, L.D.; Ledgerwood, R.K.; Veatch, M.D.

    1984-07-01

    This report describes the design and installation of multi-level piezometers at borehole cluster sites DC-19, DC-20 and DC-22. The network of borehole cluster sites will provide facilities for multi-level water-level monitoring across the RRL for piezometer baseline monitoring and for large-scale hydraulic stress testing. These groundwater-monitoring facilities were installed between August 1983 and March 1984. Three series of piezometer nests (A-, C- and D-series) were installed in nine hydrogeologic units (monitoring horizons) within the Columbia River Basalt Group at each borehole cluster site. In addition to the piezometer facilities, a B-series pumping well was installed at borehole cluster sites DC-20 and DC-22. The A-series piezometer nest monitors the basal Ringold sediments and the Rattlesnake Ridge interbed. The C-series piezometer nests monitors the six deepest horizons, which are in increasing depth, the Priest Rapids interflow. 21 refs., 6 figs., 14 tabs.

  16. DC motor speed control using neural networks

    NASA Astrophysics Data System (ADS)

    Tai, Heng-Ming; Wang, Junli; Kaveh, Ashenayi

    1990-08-01

    This paper presents a scheme that uses a feedforward neural network for the learning and generalization of the dynamic characteristics for the starting of a dc motor. The goal is to build an intelligent motor starter which has a versatility equivalent to that possessed by a human operator. To attain a fast and safe starting from stall for a dc motor a maximum armature current should be maintained during the starting period. This can be achieved by properly adjusting the armature voltage. The network is trained to learn the inverse dynamics of the motor starting characteristics and outputs a proper armature voltage. Simulation was performed to demonstrate the feasibility and effectiveness of the model. This study also addresses the network performance as a function of the number of hidden units and the number of training samples. 1.

  17. Control and Diagnostic Model of Brushless Dc Motor

    NASA Astrophysics Data System (ADS)

    Abramov, Ivan V.; Nikitin, Yury R.; Abramov, Andrei I.; Sosnovich, Ella V.; Božek, Pavol

    2014-09-01

    A simulation model of brushless DC motor (BLDC) control and diagnostics is considered. The model has been developed using a freeware complex "Modeling in technical devices". Faults and diagnostic parameters of BLDC are analyzed. A logicallinguistic diagnostic model of BLDC has been developed on basis of fuzzy logic. The calculated rules determine dependence of technical condition on diagnostic parameters, their trends and utilized lifetime of BLDC. Experimental results of BLDC technical condition diagnostics are discussed. It is shown that in the course of BLDC degradation the motor condition change depends on diagnostic parameter values

  18. Packaged Fault Model for Geometric Segmentation of Active Faults Into Earthquake Source Faults

    NASA Astrophysics Data System (ADS)

    Nakata, T.; Kumamoto, T.

    2004-12-01

    In Japan, the empirical formula proposed by Matsuda (1975) mainly based on the length of the historical surface fault ruptures and magnitude, is generally applied to estimate the size of future earthquakes from the extent of existing active faults for seismic hazard assessment. Therefore validity of the active fault length and defining individual segment boundaries where propagating ruptures terminate are essential and crucial to the reliability for the accurate assessments. It is, however, not likely for us to clearly identify the behavioral earthquake segments from observation of surface faulting during the historical period, because most of the active faults have longer recurrence intervals than 1000 years in Japan. Besides uncertainties of the datasets obtained mainly from fault trenching studies are quite large for fault grouping/segmentation. This is why new methods or criteria should be applied for active fault grouping/segmentation, and one of the candidates may be geometric criterion of active faults. Matsuda (1990) used _gfive kilometer_h as a critical distance for grouping and separation of neighboring active faults. On the other hand, Nakata and Goto (1998) proposed the geometric criteria such as (1) branching features of active fault traces and (2) characteristic pattern of vertical-slip distribution along the fault traces as tools to predict rupture length of future earthquakes. The branching during the fault rupture propagation is regarded as an effective energy dissipation process and could result in final rupture termination. With respect to the characteristic pattern of vertical-slip distribution, especially with strike-slip components, the up-thrown sides along the faults are, in general, located on the fault blocks in the direction of relative strike-slip. Applying these new geometric criteria to the high-resolution active fault distribution maps, the fault grouping/segmentation could be more practically conducted. We tested this model

  19. Fault Roughness Records Strength

    NASA Astrophysics Data System (ADS)

    Brodsky, E. E.; Candela, T.; Kirkpatrick, J. D.

    2014-12-01

    Fault roughness is commonly ~0.1-1% at the outcrop exposure scale. More mature faults are smoother than less mature ones, but the overall range of roughness is surprisingly limited which suggests dynamic control. In addition, the power spectra of many exposed fault surfaces follow a single power law over scales from millimeters to 10's of meters. This is another surprising observation as distinct structures such as slickenlines and mullions are clearly visible on the same surfaces at well-defined scales. We can reconcile both observations by suggesting that the roughness of fault surfaces is controlled by the maximum strain that can be supported elastically in the wallrock. If the fault surface topography requires more than 0.1-1% strain, it fails. Invoking wallrock strength explains two additional observations on the Corona Heights fault for which we have extensive roughness data. Firstly, the surface is isotropic below a scale of 30 microns and has grooves at larger scales. Samples from at least three other faults (Dixie Valley, Mount St. Helens and San Andreas) also are isotropic at scales below 10's of microns. If grooves can only persist when the walls of the grooves have a sufficiently low slope to maintain the shape, this scale of isotropy can be predicted based on the measured slip perpendicular roughness data. The observed 30 micron scale at Corona Heights is consistent with an elastic strain of 0.01 estimated from the observed slip perpendicular roughness with a Hurst exponent of 0.8. The second observation at Corona Heights is that slickenlines are not deflected around meter-scale mullions. Yielding of these mullions at centimeter to meter scale is predicted from the slip parallel roughness as measured here. The success of the strain criterion for Corona Heights supports it as the appropriate control on fault roughness. Micromechanically, the criterion implies that failure of the fault surface is a continual process during slip. Macroscopically, the

  20. Fault reactivation control on normal fault growth: an experimental study

    NASA Astrophysics Data System (ADS)

    Bellahsen, Nicolas; Daniel, Jean Marc

    2005-04-01

    Field studies frequently emphasize how fault reactivation is involved in the deformation of the upper crust. However, this phenomenon is generally neglected (except in inversion models) in analogue and numerical models performed to study fault network growth. Using sand/silicon analogue models, we show how pre-existing discontinuities can control the geometry and evolution of a younger fault network. The models show that the reactivation of pre-existing discontinuities and their orientation control: (i) the evolution of the main fault orientation distribution through time, (ii) the geometry of relay fault zones, (iii) the geometry of small scale faulting, and (iv) the geometry and location of fault-controlled basins and depocenters. These results are in good agreement with natural fault networks observed in both the Gulf of Suez and Lake Tanganyika. They demonstrate that heterogeneities such as pre-existing faults should be included in models designed to understand the behavior and the tectonic evolution of sedimentary basins.

  1. 77 FR 39921 - D&C Red No. 6 and D&C Red No. 7; Change in Specification

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-07-06

    ...The Food and Drug Administration (FDA or the Agency) is revising its requirements for D&C Red No. 6 and D&C Red No. 7 by replacing the current specification for ``Ether-soluble matter'' with a maximum limit of 0.015 percent for the recently identified impurity 1- [(4-methylphenyl)azo]-2-naphthalenol. This action is in response to a petition filed by Sun Chemical...

  2. A 1.6-kW, 110-kHz dc-dc converter optimized for IGBT's

    NASA Technical Reports Server (NTRS)

    Chen, Keming; Stuart, Thomas A.

    1993-01-01

    A full bridge dc-dc converter using a zero-current and zero-voltage switching technique is described. This circuit utilizes the characteristics of the IGBT to achieve power and frequency combinations that are much higher than previously reported for this device. Experimental results are included for a 1.6-kW, 110-kHz converter with 95 percent efficiency.

  3. Lessons learned, DC-XA

    SciTech Connect

    Steinmeyer, D.

    1997-01-01

    The Delta Clipper-Experimental A (DC-XA) program was conceived and specifically developed to provide a low cost reusable flight vehicle testbed for demonstrating performance and operability testing of advanced technologies required for the development of next generation Reusable Launch Vehicles (RLVs). The three primary program objectives addressed were: To integrate a variety of advanced launch vehicle technology components into the DC-XA flight vehicle testbed. Demonstrate performance, operability, and supportability of Advanced Launch Technologies (ALT) components through ground and flight testing of the DC-XA. Demonstrate rapid prototyping of hardware and software in a combined government, industry cooperative effort. {copyright} {ital 1997 American Institute of Physics.}

  4. A study of fault injection in multichannel spacecraft power systems

    NASA Technical Reports Server (NTRS)

    Dugal-Whitehead, Norma R.; Johnson, Yvette B.

    1991-01-01

    NASA/Marshall Space Flight Center proposes to implement fault injection into an electrical power system breadboard to study the reactions of the various control elements of this breadboard. Among the elements to be studied are the remote power controllers, the algorithms in the control computers, and the artificially intelligent control programs resident in this breadboard. To this end, a study of electrical power is being performed to yield a list of the most common power system faults. The results of this study are being applied to a multichannel high-voltage DC spacecraft power system called the Large Autonomous Spacecraft Electrical Power System Breadboard. Some of the reactions of the breadboard to some of the faults which have been encountered are presented along with the results of this study.

  5. Fault Management Guiding Principles

    NASA Technical Reports Server (NTRS)

    Newhouse, Marilyn E.; Friberg, Kenneth H.; Fesq, Lorraine; Barley, Bryan

    2011-01-01

    Regardless of the mission type: deep space or low Earth orbit, robotic or human spaceflight, Fault Management (FM) is a critical aspect of NASA space missions. As the complexity of space missions grows, the complexity of supporting FM systems increase in turn. Data on recent NASA missions show that development of FM capabilities is a common driver for significant cost overruns late in the project development cycle. Efforts to understand the drivers behind these cost overruns, spearheaded by NASA's Science Mission Directorate (SMD), indicate that they are primarily caused by the growing complexity of FM systems and the lack of maturity of FM as an engineering discipline. NASA can and does develop FM systems that effectively protect mission functionality and assets. The cost growth results from a lack of FM planning and emphasis by project management, as well the maturity of FM as an engineering discipline, which lags behind the maturity of other engineering disciplines. As a step towards controlling the cost growth associated with FM development, SMD has commissioned a multi-institution team to develop a practitioner's handbook representing best practices for the end-to-end processes involved in engineering FM systems. While currently concentrating primarily on FM for science missions, the expectation is that this handbook will grow into a NASA-wide handbook, serving as a companion to the NASA Systems Engineering Handbook. This paper presents a snapshot of the principles that have been identified to guide FM development from cradle to grave. The principles range from considerations for integrating FM into the project and SE organizational structure, the relationship between FM designs and mission risk, and the use of the various tools of FM (e.g., redundancy) to meet the FM goal of protecting mission functionality and assets.

  6. Compact dc link

    SciTech Connect

    Flairty, C. )

    1991-10-01

    The EPRI Compact Substation Project (a HVDC Converter Station) was developed, designed, and constructed per EPRI Agreement RP213. In December 1983, the converter station operated at its rating (100 MW power transmission and 300 kV dc bias plus 100 kV operating voltage). From January to May 1984, the converter station operated at various power transmission levels. Operation was intermittent due to a randomly occurring voltage breakdown. The voltage breakdown was isolated to the steel tanks containing the thyristor valves in an SF{sub 6} environment. The type of insulators stressed within the valve tanks were: (1) the epoxy cone shape insulators providing an interface to the bus entering the valve tank; (2) epoxy fiberglass hydraulic columns for the flow of the R113 refrigerant to and from the thyristor valves; and (3) the epoxy fiberglass support columns supporting the thyristor valves from the floor of the valve tank. The cause of the randomly occurring breakdown was investigated and determined to be the epoxy fiberglass support columns. The random dielectric breakdowns were due to excessive voltage gradients existing at the epoxy fiberglass support columns. This probably was caused by the misplacement of an internal insert within the column with respect to an external shield on the column. The cost and time to retrofit the support columns outweighed the benefits expected from resuming the project. Consequently, work was terminated and the equipment disassembled. Examination of the epoxy fiberglass support columns revealed several arcing tracks along the inside surface confirming the earlier hypothesis. 53 figs., 32 tabs.

  7. Identifying three-phase induction motor faults using artificial neural networks

    PubMed

    Kolla; Varatharasa

    2000-01-01

    This paper presents an artificial neural network (ANN) based technique to identify faults in a three-phase induction motor. The main types of faults considered are overload, single phasing, unbalanced supply voltage, locked rotor, ground fault, over-voltage and under-voltage. Three-phase currents and voltages from the induction motor are used in the proposed approach. A feedforward layered neural network structure is used. The network is trained using the backpropagation algorithm. The trained network is tested with simulated fault current and voltage data. Fault detection is attempted in the no fault to fault transition period. Off-line testing results on a 3 HP induction motor model show that the proposed ANN based method is effective in identifying various types of faults. PMID:11106295

  8. Simulation of Fault Zone Dynamics

    NASA Astrophysics Data System (ADS)

    Mora, P.; Abe, S.; Place, D.

    2002-12-01

    is the use of regular sized particles to form grains. Here, we overview a new approach to construct irregular shaped grains from an arbitrary number of piecewise spherical patches and present simulation results of gouge layers using the new model. The ability to simulate much more general grain shapes is a key extension that will improve the model's ability to probe the issue of scaling of laboratory derived frictional constitutive relations to the fault scale, and earthquake nucleation processes. škip .3cm Mora, P., Place, D., Abe, S. and Jaume, S. (2000) Lattice solid simulation of the physics of earthquakes: the model, results and directions, in: GeoComplexity and the Physics of Earthquakes (Geophysical Monograph series; no. 120), eds. Rundle, J.B., Turcotte, D.L. and Klein, W., pp 105-125 (American Geophys. Union, Washington, DC).

  9. High voltage dc--dc converter with dynamic voltage regulation and decoupling during load-generated arcs

    DOEpatents

    Shimer, D.W.; Lange, A.C.

    1995-05-23

    A high-power power supply produces a controllable, constant high voltage output under varying and arcing loads. The power supply includes a voltage regulator, an inductor, an inverter for producing a high frequency square wave current of alternating polarity, an improved inverter voltage clamping circuit, a step up transformer, an output rectifier for producing a dc voltage at the output of each module, and a current sensor for sensing output current. The power supply also provides dynamic response to varying loads by controlling the voltage regulator duty cycle and circuitry is provided for sensing incipient arc currents at the output of the power supply to simultaneously decouple the power supply circuitry from the arcing load. The power supply includes a plurality of discrete switching type dc--dc converter modules. 5 Figs.

  10. High voltage dc-dc converter with dynamic voltage regulation and decoupling during load-generated arcs

    DOEpatents

    Shimer, Daniel W.; Lange, Arnold C.

    1995-01-01

    A high-power power supply produces a controllable, constant high voltage output under varying and arcing loads. The power supply includes a voltage regulator, an inductor, an inverter for producing a high frequency square wave current of alternating polarity, an improved inverter voltage clamping circuit, a step up transformer, an output rectifier for producing a dc voltage at the output of each module, and a current sensor for sensing output current. The power supply also provides dynamic response to varying loads by controlling the voltage regulator duty cycle and circuitry is provided for sensing incipient arc currents at the output of the power supply to simultaneously decouple the power supply circuitry from the arcing load. The power supply includes a plurality of discrete switching type dc--dc converter modules.

  11. Validated Fault Tolerant Architectures for Space Station

    NASA Technical Reports Server (NTRS)

    Lala, Jaynarayan H.

    1990-01-01

    Viewgraphs on validated fault tolerant architectures for space station are presented. Topics covered include: fault tolerance approach; advanced information processing system (AIPS); and fault tolerant parallel processor (FTPP).

  12. Experimental application of nonlinear minimum variance estimation for fault detection systems

    NASA Astrophysics Data System (ADS)

    Alkaya, Alkan; Grimble, Michael John

    2016-09-01

    The purpose of this paper is to present an experimental design and application of a novel model-based fault detection technique by using a nonlinear minimum variance (NMV) estimator. The NMV estimation technique is used to generate a residual signal which is then used to detect faults in the system. The main advantage of the approach is the simplicity of the nonlinear estimator theory and the straightforward structure of the resulting solution. The proposed method is implemented and validated experimentally on DC servo system. Experimental results demonstrate that the technique can produce acceptable performance in terms of fault detection and false alarm.

  13. Thermal image based fault diagnosis for rotating machinery

    NASA Astrophysics Data System (ADS)

    Janssens, Olivier; Schulz, Raiko; Slavkovikj, Viktor; Stockman, Kurt; Loccufier, Mia; Van de Walle, Rik; Van Hoecke, Sofie

    2015-11-01

    Infrared imaging is crucial for condition monitoring as the thermographic patterns will differ depending on the fault or machine condition. Currently, a limited number of machine faults have been studied using thermal imaging. Therefore, this paper proposes a novel automatic fault detection system using infrared imaging, focussing on bearings of rotating machinery. The set of bearing faults monitored contain faults for which state-of-the-art techniques have no general solutions such as bearing-lubricant starvation. For each fault, several recordings are made using different bearings to ensure generalization of the fault-detection system. The system contains two image-processing pipelines, each with their own respective purposes. The first pipeline focusses on detecting rotor imbalance, regardless of the bearing faults. The second pipeline focusses on the bearing faults, regardless of whether the machine is balanced or not. Within the first pipeline, imbalance is detected by differencing the consecutive image frames which are subsequently summarized by their distribution along the image axes. For the second pipeline, three features are introduced which are the standard deviation of the temperature, the Gini coefficient, and the Moment of Light. The final system is able to distinguish between all eight different conditions with an accuracy of 88.25%.

  14. Spaceborne multispectral images reveal undocumented Late Cenozoic faults, Mojave Desert, California

    SciTech Connect

    Ford, J.P.; Crippen, R.E.; Blom, R.G. ); Dokka, R.K. )

    1990-06-01

    Undocumented late Miocene and younger strike-slip and normal faults that extend up to 25 km in the eastern and central Mojave Desert Block have been detected and mapped in LANDSAT thematic mapper images. The faults are located in the Bristol Mountains, Cady Mountains, and Alvord Mountain areas. Additional strike-slip faults detected in the adjacent Fort Irwin Military Reservation have yet to be verified in the field. The images were processed to enhance the spectral responses without suppressing topography. The faults are detected on the images because of spectral contrasts mostly at wavelengths longer than the visible. The newly detected faults form part of a complex regional network of right shear that connects faults in the southern Death Valley region with the San Andreas Fault System. Some of the newly identified faults bound blocks that have experienced different Neogene rotational histories. These faults have likely served to accommodate those motions. Structural relations along the faults suggest at least two intervals of movement. In the Bristol Mountains, east of Broadwell Lake, the faults are overlain by unconsolidated alluvial fan debris (late Quaternary ) and are probably inactive. In the Cady Mountains to the west and south, the faults cut all deposits and are currently active. The discovery of these undocumented faults indicates that existing knowledge of fault distribution in the area is incomplete and not fully representative. This has important implications for seismic risk assessment and for determining the suitability of the desert for increased use by man.

  15. A novel transient rotor current control scheme of a doubly-fed induction generator equipped with superconducting magnetic energy storage for voltage and frequency support

    NASA Astrophysics Data System (ADS)

    Shen, Yang-Wu; Ke, De-Ping; Sun, Yuan-Zhang; Daniel, Kirschen; Wang, Yi-Shen; Hu, Yuan-Chao

    2015-07-01

    A novel transient rotor current control scheme is proposed in this paper for a doubly-fed induction generator (DFIG) equipped with a superconducting magnetic energy storage (SMES) device to enhance its transient voltage and frequency support capacity during grid faults. The SMES connected to the DC-link capacitor of the DFIG is controlled to regulate the transient dc-link voltage so that the whole capacity of the grid side converter (GSC) is dedicated to injecting reactive power to the grid for the transient voltage support. However, the rotor-side converter (RSC) has different control tasks for different periods of the grid fault. Firstly, for Period I, the RSC injects the demagnetizing current to ensure the controllability of the rotor voltage. Then, since the dc stator flux degenerates rapidly in Period II, the required demagnetizing current is low in Period II and the RSC uses the spare capacity to additionally generate the reactive (priority) and active current so that the transient voltage capability is corroborated and the DFIG also positively responds to the system frequency dynamic at the earliest time. Finally, a small amount of demagnetizing current is provided after the fault clearance. Most of the RSC capacity is used to inject the active current to further support the frequency recovery of the system. Simulations are carried out on a simple power system with a wind farm. Comparisons with other commonly used control methods are performed to validate the proposed control method. Project supported by the National Natural Science Foundation of China (Grant No. 51307124) and the Major Program of the National Natural Science Foundation of China (Grant No. 51190105).

  16. Bearing Damage Detection of BLDC Motors Based on Current Envelope Analysis

    NASA Astrophysics Data System (ADS)

    Lee, Chun-Yao; Hsieh, Yu-Hua

    2012-12-01

    This paper proposes current envelope analysis (CEA) to analyze bearing fault signals in brushless direct current (BLDC) motors, and back propagation neural networks (BPNN) to automatically identify bearing faults. We made sample motors which contained different types of fault, recorded the current signals, and extracted the current features using CEA and Hilbert Huang transform (HHT) for BPNN fault identification. The results indicate that this approach can efficiently identify bearing faults in BLDC motors.

  17. A Compensation Method of Conductor Parameter for Transient Fault Location

    NASA Astrophysics Data System (ADS)

    Ugbome, Chukwunweike Lucky

    Faults in underground distribution systems are predominantly caused by the deterioration of cable insulation. The inherent nature of underground distribution is such that cables are laid underground and exposed to harmful substances which can cause deterioration of cable insulation. The penetration of water into the cable splice is a common cause of cable deterioration and a common source of transitory sub-cycle cable fault in underground distribution systems. The presence of a sub-cycle fault in a distribution line is not necessarily noticeable and may not cause any protective device to operate due to its short live-span but can be destructive if it is sustained and unattended to. The location of transitory sub-cycle fault in underground cable is fundamentally important in preventing and containing a permanent fault which can potentially result to an unplanned outage. However the location of this type of fault is not easy due to so many unknowns. A few numbers of approaches have been developed for determining the location of short-lived sub-cycle (SLSC) faults, but they approximate the conductor parameter which would reduce the accuracy of the location determination. This thesis develops an algorithm for transitory sub-cycle fault location to compensate for the ignored conductor parameter by employing the X/R ratio of the distribution line. First, a model for transient faults at different locations in underground cable is presented and used to generate the voltage and current waveforms at the source side. Also presented is the performance of the fault location by the uncompensated and compensated algorithms under two configurations of the distribution line: a homogeneous distribution circuit and a heterogeneous distribution line. The result obtained from the performance studies show that the proposed compensation method would help the non-compensated fault location approaches to achieve relatively high accuracy in locating transitory sub-cycle faults in numerous

  18. 21 CFR 74.2053 - D&C Black No. 3.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... ADDITIVES SUBJECT TO CERTIFICATION Cosmetics § 74.2053 D&C Black No. 3. (a) Identity. The color additive D&C... may be avoided by current good manufacturing practices: (1) Calcium hydroxyapatite (CaO and P2O5), not... cosmetics in amounts consistent with current good manufacturing practice: Eyeliner, eye shadow, mascara,...

  19. 21 CFR 74.2053 - D&C Black No. 3.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... ADDITIVES SUBJECT TO CERTIFICATION Cosmetics § 74.2053 D&C Black No. 3. (a) Identity. The color additive D&C... may be avoided by current good manufacturing practices: (1) Calcium hydroxyapatite (CaO and P2O5), not... cosmetics in amounts consistent with current good manufacturing practice: Eyeliner, eye shadow, mascara,...

  20. 21 CFR 74.2053 - D&C Black No. 3.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... ADDITIVES SUBJECT TO CERTIFICATION Cosmetics § 74.2053 D&C Black No. 3. (a) Identity. The color additive D&C... may be avoided by current good manufacturing practices: (1) Calcium hydroxyapatite (CaO and P2O5), not... cosmetics in amounts consistent with current good manufacturing practice: Eyeliner, eye shadow, mascara,...