Science.gov

Sample records for gas transmission lines

  1. Upgrading a 24-in. gas transmission line

    SciTech Connect

    Stiles, R.E.

    1986-10-01

    Because of increasing population density, Texas Eastern Transmission Corp. removed an existing 24-in. gas line and replaced it with a higher yield line pipe with a greater wall thickness. Work was through exclusive lake subdivisions and across a golf course and required special construction techniques.

  2. Gas insulated transmission line having tapered particle trapping ring

    DOEpatents

    Cookson, Alan H.

    1982-01-01

    A gas-insulated transmission line includes an outer sheath, an inner conductor, insulating supports and an insulating gas. A particle-trapping ring is secured to each insulating support, and it is comprised of a central portion and two tapered end portions. The ends of the particle trapping ring have a smaller diameter than the central portion of the ring, so as to enable the use of the particle trapping ring in a curved transmission line.

  3. Corrugated outer sheath gas-insulated transmission line

    DOEpatents

    Kemeny, George A.; Cookson, Alan H.

    1981-01-01

    A gas-insulated transmission line includes two transmission line sections each of which are formed of a corrugated outer housing enclosing an inner high-voltage conductor disposed therein, with insulating support means supporting the inner conductor within the outer housing and an insulating gas providing electrical insulation therebetween. The outer housings in each section have smooth end sections at the longitudinal ends thereof which are joined together by joining means which provide for a sealing fixed joint.

  4. 75 FR 19963 - Florida Gas Transmission Company, LLC; Transcontinental Gas Pipe Line Company, LLC; Florida Gas...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-04-16

    ... Energy Regulatory Commission Florida Gas Transmission Company, LLC; Transcontinental Gas Pipe Line... Transcontinental Gas Pipe Line Company, LLC (Transco) in the above referenced dockets. The EA assesses the... pig launcher in Grand Bay, Alabama (MP 8.8); One new Over Pressure Protection Regulator Station...

  5. High voltage gas insulated transmission line with continuous particle trapping

    DOEpatents

    Cookson, Alan H.; Dale, Steinar J.

    1983-01-01

    This invention provides a novel high voltage gas insulated transmission line utilizing insulating supports spaced at intervals with snap-in means for supporting a continuous trapping apparatus and said trapping apparatus having perforations and cutouts to facilitate trapping of contaminating particles and system flexibility.

  6. Gas insulated transmission line with insulators having field controlling recesses

    DOEpatents

    Cookson, Alan H.; Pederson, Bjorn O.

    1984-01-01

    A gas insulated transmission line having a novel insulator for supporting an inner conductor concentrically within an outer sheath. The insulator has a recess contiguous with the periphery of one of the outer and inner conductors. The recess is disposed to a depth equal to an optimum gap for the dielectric insulating fluid used for the high voltage insulation or alternately disposed to a large depth so as to reduce the field at the critical conductor/insulator interface.

  7. Gas insulated transmission line having low inductance intercalated sheath

    DOEpatents

    Cookson, Alan H.

    1978-01-01

    A gas insulated transmission line including an outer sheath, an inner conductor disposed within the outer sheath, and an insulating gas between the inner conductor and the outer sheath. The outer sheath comprises an insulating tube having first and second ends, and having interior and exterior surfaces. A first electrically conducting foil is secured to the interior surface of the insulating tube, is spirally wound from one tube end to the second tube end, and has a plurality of overlapping turns. A second electrically conducting foil is secured to the exterior surface of the insulating tube, and is spirally wound in the opposite direction from the first electrically conducting foil. By winding the foils in opposite directions, the inductances within the intercalated sheath will cancel each other out.

  8. INSTRUMENTATION FOR SURVEYING ACOUSTIC SIGNALS IN NATURAL GAS TRANSMISSION LINES

    SciTech Connect

    John L. Loth; Gary J. Morris; George M. Palmer; Richard Guiler; Deepak Mehra

    2003-09-01

    In the U.S. natural gas is distributed through more than one million miles of high-pressure transmission pipelines. If all leaks and infringements could be detected quickly, it would enhance safety and U.S. energy security. Only low frequency acoustic waves appear to be detectable over distances up to 60 km where pipeline shut-off valves provide access to the inside of the pipeline. This paper describes a Portable Acoustic Monitoring Package (PAMP) developed to record and identify acoustic signals characteristic of: leaks, pump noise, valve and flow metering noise, third party infringement, manual pipeline water and gas blow-off, etc. This PAMP consists of a stainless steel 1/2 inch NPT plumbing tree rated for use on 1000 psi pipelines. Its instrumentation is designed to measure acoustic waves over the entire frequency range from zero to 16,000 Hz by means of four instruments: (1) microphone, (2) 3-inch water full range differential pressure transducer with 0.1% of range sensitivity, (3) a novel 3 inch to 100 inch water range amplifier, using an accumulator with needle valve and (4) a line-pressure transducer. The weight of the PAMP complete with all accessories is 36 pounds. This includes a remote control battery/switch box assembly on a 25-foot extension chord, a laptop data acquisition computer on a field table and a sun shield.

  9. Particle trap with dielectric barrier for use in gas insulated transmission lines

    DOEpatents

    Dale, S.J.

    1982-06-15

    A gas-insulated transmission line includes an outer sheath, an inner conductor within the outer sheath, insulating supports supporting the inner conductor within the outer sheath, and an insulating gas electrically insulating the inner conductor from the outer sheath. An apertured particle trapping electrode is disposed within the outer sheath, and the electrode has a pair of dielectric members secured at each longitudinal end thereof, with the dielectric members extending outwardly from the apertured electrode. 7 figs.

  10. Particle trap with dielectric barrier for use in gas insulated transmission lines

    DOEpatents

    Dale, Steinar J.

    1982-01-01

    A gas-insulated transmission line includes an outer sheath, an inner conductor within the outer sheath, insulating supports supporting the inner conductor within the outer sheath, and an insulating gas electrically insulating the inner conductor from the outer sheath. An apertured particle trapping electrode is disposed within the outer sheath, and the electrode has a pair of dielectric members secured at each longitudinal end thereof, with the dielectric members extending outwardly from the apertured electrode.

  11. Construction of 8000A class 275kV gas insulated transmission line

    SciTech Connect

    Kuroyanagi, Y.; Toya, A. ); Hayashi, T. ); Araki, T. )

    1990-01-01

    The 8000A class 275kV gas insulated transmission lines (GIL), 138m and 158m long, completed as getaway lines in the Shin Noda substation in 1988 is described. The GIL was designed to match large current capacity. New techniques were applied to construct these lines. Thermal expansion and contraction of a straight section of GIL is absorbed by an angle variation of a deflection unit. Supports were designed to absorb a ground depression. Units of GIL were installed with gantry cranes. Joints of enclosure were welded by an automatic welding machine.

  12. Hybrid particle traps and conditioning procedure for gas insulated transmission lines

    DOEpatents

    Dale, Steinar J.; Cookson, Alan H.

    1982-01-01

    A gas insulated transmission line includes an outer sheath, an inner condor within the outer sheath, insulating supports supporting the inner conductor within the outer sheath, and an insulating gas electrically insulating the inner conductor from the outer sheath. An apertured particle trapping ring is disposed within the outer sheath, and the trapping ring has a pair of dielectric members secured at each longitudinal end thereof, with the dielectric members extending outwardly from the trapping ring along an arc. A support sheet having an adhesive coating thereon is secured to the trapping ring and disposed on the outer sheath within the low field region formed between the trapping ring and the outer sheath. A conditioning method used to condition the transmission line prior to activation in service comprises applying an AC voltage to the inner conductor in a plurality of voltage-time steps, with the voltage-time steps increasing in voltage magnitude while decreasing in time duration.

  13. Vertically aligned gas-insulated transmission line having particle traps at the inner conductor

    DOEpatents

    Dale, Steinar J.

    1984-01-01

    Gas insulated electrical apparatus having first and second conductors separated by an insulating support within an insulating gas environment, and particle traps disposed along the surface of the high potential conductor for trapping and inactivating foreign particles which may be present within the insulating gas medium. Several embodiments of the invention were developed which are particularly suited for vertically aligned gas insulated transmission lines. The particle traps are grooves or cavities formed into the walls of the tubular inner conductor, without extending into the hollow portion of the conductor. In other embodiments, the traps are appendages or insert flanges extending from the inner conductor, with the insulator supports contacting the appendages instead of the inner conductor.

  14. Particle trap to sheath contact for a gas-insulated transmission line having a corrugated outer conductor

    DOEpatents

    Fischer, William H.; Cookson, Alan H.; Yoon, Kue H.

    1984-04-10

    A particle trap to outer elongated conductor or sheath contact for gas-insulated transmission lines. The particle trap to outer sheath contact of the invention is applicable to gas-insulated transmission lines having either corrugated or non-corrugated outer sheaths. The contact of the invention includes an electrical contact disposed on a lever arm which in turn is rotatably disposed on the particle trap and biased in a direction to maintain contact between the electrical contact and the outer sheath.

  15. Development of fault section detecting system for gas insulated transmission lines

    SciTech Connect

    Nakamura, E.; Uchida, K.; Koshilishi, M.; Mitsui, T.; Miyamoto, S.; Nakamura, K.; Itaka, K.; Hara, T.; Yoda, T.

    1986-01-01

    A fault section detecting system using optical magnetic field sensors developed for gas insulated transmission lines (GIL) is reported. A bismuth silicon oxide (Bi/sub 12/SiO/sub 20/, or BSO) single crystal was adopted for the optical magnetic field sensor. A method of mounting the sensors to GIL which enables the sensors to detect the conductor current from outside the enclosure was developed. With the developed fault detector, faults occurring inside a section of GIL between sensors are detected by discriminating the phases of conductor currents detected by the sensors. The system was confirmed to have sufficient performance for application to commerical GILS.

  16. Flexible gas insulated transmission line having regions of reduced electric field

    DOEpatents

    Cookson, Alan H.; Fischer, William H.; Yoon, Kue H.; Meyer, Jeffry R.

    1983-01-01

    A gas insulated transmission line having radially flexible field control means for reducing the electric field along the periphery of the inner conductor at predetermined locations wherein the support insulators are located. The radially flexible field control means of the invention includes several structural variations of the inner conductor, wherein careful controlling of the length to depth of surface depressions produces regions of reduced electric field. Several embodiments of the invention dispose a flexible connector at the predetermined location along the inner conductor where the surface depressions that control the reduced electric field are located.

  17. Semi-flexible gas-insulated transmission line using sandwiched discs for intermittent flexing joints

    DOEpatents

    Kommineni, P.R.

    1983-02-15

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by the use of main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. The flexing elements are formed by sandwiching together, by fusing, a pair of thin hollow discs which are fixedly secured to both the main conductor sections and the conductor hub section. 4 figs.

  18. Semi-flexible gas-insulated transmission line using sandwiched discs for intermittent flexing joints

    DOEpatents

    Kommineni, Prasad R.

    1983-02-15

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by the use of main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. The flexing elements are formed by sandwiching together, by fusing, a pair of thin hollow discs which are fixedly secured to both the main conductor sections and the conductor hub section.

  19. Semi-flexible gas-insulated transmission line using electric field stress shields

    DOEpatents

    Cookson, Alan H.; Dale, Steinar J.; Bolin, Philip C.

    1982-12-28

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by use of main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. The flexing elements and the stress shields may also be utilized in connection with a plug and socket arrangement for providing electrical connection between main conductor sections.

  20. Semi-flexible gas-insulated transmission line using electric field stress shields

    DOEpatents

    Cookson, A.H.; Dale, S.J.; Bolin, P.C.

    1982-12-28

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by use of main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. The flexing elements and the stress shields may also be utilized in connection with a plug and socket arrangement for providing electrical connection between main conductor sections. 10 figs.

  1. Fault and partial discharge location systems for gas-insulated transmission lines. Final report

    SciTech Connect

    Boggs, S.A.; Ford, G.L.; Fujimoto, N.; Stone, G.C.

    1983-12-01

    Partial discharge and faults in gas-insulated transmission line (GITL) can be difficult to locate. This report describes the development, testing, and application of systems for fault and partial discharge location in GITL. Both systems are based on timing of electromagnetic transients generated by a fault/partial discharge source. Both systems employ microcomputers to facilitate automated data acquisition and analysis. The major problems solved in developing the fault location system were coupling of high frequency signals from and between phases and isolation of high voltage short risetime signals from high speed digital logic. The problems addressed in the partial discharge location project include handling a large number of pulses which may include noise, the large dynamic range of partial discharge induced transients (> 80 dB), and achieving an accurate correlation resolution of 2 ns.

  2. Series Transmission Line Transformer

    DOEpatents

    Buckles, Robert A.; Booth, Rex; Yen, Boris T.

    2004-06-29

    A series transmission line transformer is set forth which includes two or more of impedance matched sets of at least two transmissions lines such as shielded cables, connected in parallel at one end ans series at the other in a cascading fashion. The cables are wound about a magnetic core. The series transmission line transformer (STLT) which can provide for higher impedance ratios and bandwidths, which is scalable, and which is of simpler design and construction.

  3. Transmission Line Security Monitor

    SciTech Connect

    2011-01-01

    The Transmission Line Security Monitor is a multi-sensor monitor that mounts directly on high-voltage transmission lines to detect, characterize and communicate terrorist activity, human tampering and threatening conditions around support towers. For more information about INL's critical infrastructure protection research, visit http://www.facebook.com/idahonationallaboratory.

  4. Transmission Line Security Monitor

    ScienceCinema

    None

    2013-05-28

    The Transmission Line Security Monitor is a multi-sensor monitor that mounts directly on high-voltage transmission lines to detect, characterize and communicate terrorist activity, human tampering and threatening conditions around support towers. For more information about INL's critical infrastructure protection research, visit http://www.facebook.com/idahonationallaboratory.

  5. Conductor load bearing roller for a gas-insulated transmission line having a corrugated outer conductor

    DOEpatents

    Fischer, William H.; Yoon, Kue H.

    1984-04-10

    A gas-insulated transmission line includes a corrugated outer conductor, an inner conductor disposed within and insulated from the outer conductor by means of support insulators and an insulating gas, and a transport device for supporting and permitting movement of the inner conductor/insulating support assembly axially along the corrugated outer conductor without radial displacement. The transport device includes two movable contacts, such as skids or rollers, supported on a common pivot lever, the pivot lever being rotatably disposed about a pivot lever axis, which pivot lever axis is in turn disposed on the periphery of a support insulator or particle trap if one is used. The movable contacts are separated axially a distance equal to the axial distance between the peaks and valleys of the corrugations of the outer conductor and separated radially a distance equal to the radial distance between the peaks and valleys of the corrugations of the outer conductor. The transport device has the pivot lever axis disposed perpendicular to the direction of travel of the inner conductor/insulating support assembly.

  6. Semi-flexible gas-insulated transmission line using protection tube in conductor plug-in joint

    DOEpatents

    Kommineni, P.R.

    1983-01-25

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. A plug and socket arrangement is utilized for joining adjacent sections of the inner conductor, and a protection tube is utilized inside the hollow plug to maintain proper alignment of the joint when the transmission line is bent. 3 figs.

  7. Semi-flexible gas-insulated transmission line using protection tube in conductor plug-in joint

    DOEpatents

    Kommineni, Prasad R.

    1983-01-25

    A gas-insulated transmission line includes an outer sheath, an inner conductor, an insulating gas electrically insulating the inner conductor from the outer sheath, and insulating supports insulatably supporting the inner conductor within the outer sheath. The inner conductor is provided with flexibility by main conductor sections which are joined together through a conductor hub section and flexible flexing elements. Stress shields are provided to control the electric field at the locations of the conductor hub sections where the insulating supports are contacting the inner conductor. A plug and socket arrangement is utilized for joining adjacent sections of the inner conductor, and a protection tube is utilized inside the hollow plug to maintain proper alignment of the joint when the transmission line is bent.

  8. Particle trap to sheath non-binding contact for a gas-insulated transmission line having a corrugated outer conductor

    DOEpatents

    Fischer, William H.

    1984-04-24

    A non-binding particle trap to outer sheath contact for use in gas insulated transmission lines having a corrugated outer conductor. The non-binding feature of the contact according to the teachings of the invention is accomplished by having a lever arm rotatably attached to a particle trap by a pivot support axis disposed parallel to the direction of travel of the inner conductor/insulator/particle trap assembly.

  9. Printed circuit dispersive transmission line

    DOEpatents

    Ikezi, H.; Lin-Liu, Y.R.; DeGrassie, J.S.

    1991-08-27

    A printed circuit dispersive transmission line structure is disclosed comprising an insulator, a ground plane formed on one surface of the insulator, a first transmission line formed on a second surface of the insulator, and a second transmission line also formed on the second surface of the insulator and of longer length than the first transmission line and periodically intersecting the first transmission line. In a preferred embodiment, the transmission line structure exhibits highly dispersive characteristics by designing the length of one of the transmission line between two adjacent periodic intersections to be longer than the other. 5 figures.

  10. Printed circuit dispersive transmission line

    DOEpatents

    Ikezi, Hiroyuki; Lin-Liu, Yuh-Ren; DeGrassie, John S.

    1991-01-01

    A printed circuit dispersive transmission line structure is disclosed comprising an insulator, a ground plane formed on one surface of the insulator, a first transmission line formed on a second surface of the insulator, and a second transmission line also formed on the second surface of the insulator and of longer length than the first transmission line and periodically intersecting the first transmission line. In a preferred embodiment, the transmission line structure exhibits highly dispersive characteristics by designing the length of one of the transmission line between two adjacent periodic intersections to be longer than the other.

  11. Drill string transmission line

    DOEpatents

    Hall, David R.; Hall, Jr., H. Tracy; Pixton, David S.; Bradford, Kline; Fox, Joe

    2006-03-28

    A transmission line assembly for transmitting information along a downhole tool comprising a pin end, a box end, and a central bore traveling between the pin end and the box end, is disclosed in one embodiment of the invention as including a protective conduit. A transmission line is routed through the protective conduit. The protective conduit is routed through the central bore and the ends of the protective conduit are routed through channels formed in the pin end and box end of the downhole tool. The protective conduit is elastically forced into a spiral or other non-linear path along the interior surface of the central bore by compressing the protective conduit to a length within the downhole tool shorter than the protective conduit.

  12. Fast calculation of the Voight profile absorption line of gas for the atmospheric transmission function determination

    NASA Astrophysics Data System (ADS)

    Chayanova, Eleonora A.; Ivanovsky, A. I.; Borisov, Yury A.; Glazkov, V. N.; Bankova, T. V.

    2004-01-01

    A fast method is offered for calculation of Voight spectral absorption line contour. A line profile is represented by a sum of terms of an absolutely converging series, containing undimensioned parameters a and b, connected with a property of the absorbing molecule, atmospheric temperature and pressure. The value b changes in a large limit from zero at the line center to 1000 and more at far wing of the line. The value a, describing a ratio of the Lorenz and Doppler effects, changes from a value ~5 near the surface of the Earth to 10-5 in the stratosphere. Twenty terms of series ensure the high accuracy of the approximation for values b ranging from 0 to 5. The deviation from accurate Voight contour formula is less than 4*10-4 or 0.04%. However, a large b value implies increase the number of terms, and the computing time increases accordingly. Numerical integration of Voight formula by Gauss-Hermite quadrature is simple, fast and accurate calculation for a value b> 5. In this case the deviation from accurate Voight formula is less than 2*10-5 or 0.002%. Using the proposed approximation of the Voight profile line, the atmospheric transmission function was computed for the path Sun- satellite represented as a net of tangent heights relative to the Earth"s surface up to 100 km with 1 km step. The computation method involves 29 spectral channels of the water absorption region (933-959 nm) and 14 channels of the molecular oxygen absorption region (758-771 nm). The computations were performed for certain profiles of H2O, O2, temperature and pressure. The computations results were compared with experimental data.

  13. Monitoring of the dielectric strength of the air/SF6-mixtures for application in gas insulated transmission lines

    NASA Astrophysics Data System (ADS)

    Moukengué Imano, A.

    2004-11-01

    This paper investigates the dielectric properties of various air/SF{6} gas mixtures based upon a cylindrical spacer model with adhering particle on the surface under homogeneous field conditions. The investigation involves a comparison with pure SF{6}. The flashover field strength for clean and particle contaminated spacer surface under lightning impulse (LI) and alternating voltage (AC) stress is determined. The results of the investigations show the sensitivity of air/SF{6} gas mixtures to conducting particles on spacer surfaces for gas pressure up to 1000 kPa. Moreover, the correspondence between pure SF{6} and air/SF{6} gas mixtures for AC and LI flashover field strength range from 50 to 178 kV/cm is determined. Conclusions are drawn about the ability of air/SF{6} gas mixtures to serve as technically efficient media for long Gas Insulated Transmission Lines (GITL). The results shed light on the issue of the SF{6} reduction and the particle detectability in GITL.

  14. A Quantitative Transmission Line Experiment

    ERIC Educational Resources Information Center

    Johnston, D. C.; Silbernagel, B. G.

    1969-01-01

    Describes modifications of a commercially available strip-type transmission line, which makes possible reproducible measurements of standing waves on the line. Experimental data yield values for the characteristic impedance, phase velocity and line wavelength of radiation in the transmission line, and the dielectric constant of material in the…

  15. Development and installation of 275kV SF/sub 6/ gas-insulated transmission line

    SciTech Connect

    Memita, N.; Furukawa, H.; Itaka, K.; Kikuchi, K.; Nihomiya, K.; Suzuki, T.

    1984-04-01

    In order to install a commercial 275kV gas-insulated transmission line (called GIL by the authors) on a route with many bends and inclines, a temperature rise test and long-term field test were performed to confirm the current capacity and thermomechanical and dielectric characteristics. Fault location and leakage gas removal tests were carried out to evaluate maintenance methods. Based on satisfactory results in all these tests, two circuits of 275kV GILs were installed to connect a gas-insulated substation of the Kansai Electric Power Co., Inc. to an overhead line. After completion, a switching surge test was carried out, and surge voltage on conductor and potential rise on enclosure, produced by switching a circuit breaker on and off, were measured to evaluate the suitability of various grounding methods for GILs. It was found that switching the circuit breaker on caused a 9MHz high-frequency surge on the enclosure and that, therefore, multiple grounding of GILs, especially near both ends, is desirable.

  16. Cryoresistive gas insulated line

    NASA Astrophysics Data System (ADS)

    Hidaka, K.; Matsumoto, S.; Kouno, T.

    An insulation strength of more than 16 kV mm -1 has been realized using nitrogen gas at 133 K and 0.4 MPa with the application of a.c. and impulse voltages. A cryoresistive gas insulated line (CRGIL) using nitrogen gas is proposed on the basis of the measured insulation strength. An efficient method for use of the cooling heat of liquefied natural gas is also proposed so that no refrigerator is required and the cost of cooling is reduced. The CRGIL has the advantages of having a large current carrying capacity, small power loss and small capacitance. Moreover, a given transmission capacity is achieved by a CRGIL whose rated voltage is about half that in a conventional gas insulated line.

  17. EC Transmission Line Materials

    SciTech Connect

    Bigelow, Tim S

    2012-05-01

    The purpose of this document is to identify materials acceptable for use in the US ITER Project Office (USIPO)-supplied components for the ITER Electron cyclotron Heating and Current Drive (ECH&CD) transmission lines (TL), PBS-52. The source of material property information for design analysis shall be either the applicable structural code or the ITER Material Properties Handbook. In the case of conflict, the ITER Material Properties Handbook shall take precedence. Materials selection, and use, shall follow the guidelines established in the Materials Assessment Report (MAR). Materials exposed to vacuum shall conform to the ITER Vacuum Handbook. [Ref. 2] Commercial materials shall conform to the applicable standard (e.g., ASTM, JIS, DIN) for the definition of their grade, physical, chemical and electrical properties and related testing. All materials for which a suitable certification from the supplier is not available shall be tested to determine the relevant properties, as part of the procurement. A complete traceability of all the materials including welding materials shall be provided. Halogenated materials (example: insulating materials) shall be forbidden in areas served by the detritiation systems. Exceptions must be approved by the Tritium System and Safety Section Responsible Officers.

  18. Non-binding conductor load bearing roller for a gas-insulated transmission line having a corrugated outer conductor

    SciTech Connect

    Fischer, W.H.

    1984-04-24

    A gas-insulated transmission line includes a corrugated outer conductor, an inner conductor disposed within and insulated from the outer conductor by means of support insulators and an insulating gas, and a non-binding transport device for supporting and permitting movement of the inner conductor/insulating support assembly axially along the corrugated outer conductor without radial displacement and for moving without binding along corrugations of any slope less than vertical. The transport device includes two movable contacts, such as skids or rollers, supported on a common pivot lever, the pivot lever being rotatably disposed about a pivot lever axis, which pivot lever axis is in turn disposed on the periphery of a support insulator or particle trap if one is used. The movable contacts are separated axially a distance equal to the axial distance between the peaks and valleys of the corrugations of the outer conductor and separated radially a distance equal to the radial distance between the peaks and valleys of the corrugations of the outer conductor. The transport device has the pivot lever axis disposed parallel to the motion of travel of the inner conductor/insulating support assembly. 7 figs.

  19. Non-binding conductor load bearing roller for a gas-insulated transmission line having a corrugated outer conductor

    DOEpatents

    Fischer, William H.

    1984-01-01

    A gas-insulated transmission line includes a corrugated outer conductor, an inner conductor disposed within and insulated from the outer conductor by means of support insulators and an insulating gas, and a non-binding transport device for supporting and permitting movement of the inner conductor/insulating support assembly axially along the corrugated outer conductor without radial displacement and for moving without binding along corrugations of any slope less than vertical. The transport device includes two movable contacts, such as skids or rollers, supported on a common pivot lever, the pivot lever being rotatably disposed about a pivot lever axis, which pivot lever axis is in turn disposed on the periphery of a support insulator or particle trap if one is used. The movable contacts are separated axially a distance equal to the axial distance between the peaks and valleys of the corrugations of the outer conductor and separated radially a distance equal to the radial distance between the peaks and valleys of the corrugations of the outer conductor. The transport device has the pivot lever axis disposed parallel to the motion of travel of the inner conductor/insulating support assembly.

  20. Electrical transmission line diametrical retainer

    DOEpatents

    Hall, David R.; Hall, Jr., H. Tracy; Pixton, David; Dahlgren, Scott; Sneddon, Cameron; Briscoe, Michael; Fox, Joe

    2004-12-14

    The invention is a mechanism for retaining an electrical transmission line. In one embodiment of the invention it is a system for retaining an electrical transmission line within down hole components. In accordance with one aspect of the invention, the system includes a plurality of downhole components, such as sections of pipe in a drill string. The system also includes a coaxial cable running between the first and second end of a drill pipe, the coaxial cable having a conductive tube and a conductive core within it. The invention allows the electrical transmission line to with stand the tension and compression of drill pipe during routine drilling cycles.

  1. Load-resistant coaxial transmission line

    DOEpatents

    Hall, David R.; Fox, Joe

    2006-01-03

    A transmission line for downhole tools that make up all or part of a tool string for drilling and production of oil, gas, and geothermal wells that can withstand the dynamic gravitational forces and other accelerations associated with downhole excavations. The transmission line has a metal tube, or outer conductor, that houses a coaxial wire inner conductor. A non-metallic dielectric material is interposed between the inner and outer conductors. The outer and inner conductors and the dielectric are sufficiently compressed together so that independent motion between them is abated. Compression of the components of the transmission line may be achieved by drawing the transmission through one or more dies in order to draw down the outer conductor onto the dielectric, or by expanding the inner conductor against the dielectric using a mandrel or hydraulic pressure. Non-metallic bead segments may be used in aid of the compression necessary to resist the dynamic forces and accelerations of drilling.

  2. Transmission Line Series Compensation for Wind Energy Transmission

    NASA Astrophysics Data System (ADS)

    Palanichamy, Dr C., Prof; Wong, Y. C.

    2015-04-01

    Wind energy has demonstrated to be a clean, copious and absolutely renewable source of energy, and the large penetration of it into the power grid indicates that wind energy is considered an effective means of power generation, Transmission of wind energy from remote locations to load centers necessitates long transmission lines. Series compensation is a proven and economical transmission solution to address system power transfer strength, grid stability, and voltage profile issues of long transmission lines. In this paper, a programmable approach to determine the capacitive reactance of series capacitor and optimum location for its placement to achieve maximum power transfer gas been presented. The respective program with sample solutions has been provided for real-time applications.

  3. 49 CFR 192.705 - Transmission lines: Patrolling.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Patrolling. 192.705 Section... NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.705 Transmission... adjacent to the transmission line right-of-way for indications of leaks, construction activity, and...

  4. 49 CFR 192.705 - Transmission lines: Patrolling.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Patrolling. 192.705 Section... NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.705 Transmission... adjacent to the transmission line right-of-way for indications of leaks, construction activity, and...

  5. 49 CFR 192.705 - Transmission lines: Patrolling.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission lines: Patrolling. 192.705 Section... NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.705 Transmission... adjacent to the transmission line right-of-way for indications of leaks, construction activity, and...

  6. 49 CFR 192.705 - Transmission lines: Patrolling.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Patrolling. 192.705 Section... NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.705 Transmission... adjacent to the transmission line right-of-way for indications of leaks, construction activity, and...

  7. 49 CFR 192.705 - Transmission lines: Patrolling.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission lines: Patrolling. 192.705 Section... NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.705 Transmission... adjacent to the transmission line right-of-way for indications of leaks, construction activity, and...

  8. Nonceramic insulators for transmission lines

    SciTech Connect

    Schneider, H.M. . High Voltage Transmission Research Center); Hall, J.F. ); Karady, G. ); Rendowden, J. )

    1989-10-01

    Progress in development of nonceramic transmission lines insulator technology is reviewed. The results of a survey to utilities in the United States are presented to indicate the range of applications, distribution by voltage class, appraisal of performance, and failure modes. Concerns expressed by utility representatives at a recent workshop are described and future research and standardization needs are presented.

  9. Pulse shaping with transmission lines

    DOEpatents

    Wilcox, R.B.

    1985-08-15

    A method and apparatus for forming shaped voltage pulses uses passive reflection from a transmission line with nonuniform impedance. The impedance of the reflecting line varies with length in accordance with the desired pulse shape. A high voltage input pulse is transmitted to the reflecting line. A reflected pulse is produced having the desired shape and is transmitted by pulse removal means to a load. Light activated photoconductive switches made of silicon can be utilized. The pulse shaper can be used to drive a Pockels cell to produce shaped optical pulses.

  10. Pulse shaping with transmission lines

    DOEpatents

    Wilcox, Russell B.

    1987-01-01

    A method and apparatus for forming shaped voltage pulses uses passive reflection from a transmission line with nonuniform impedance. The impedance of the reflecting line varies with length in accordance with the desired pulse shape. A high voltage input pulse is transmitted to the reflecting line. A reflected pulse is produced having the desired shape and is transmitted by pulse removal means to a load. Light activated photoconductive switches made of silicon can be utilized. The pulse shaper can be used to drive a Pockels cell to produce shaped optical pulses.

  11. Coiled transmission line pulse generators

    DOEpatents

    McDonald, Kenneth Fox

    2010-11-09

    Methods and apparatus are provided for fabricating and constructing solid dielectric "Coiled Transmission Line" pulse generators in radial or axial coiled geometries. The pour and cure fabrication process enables a wide variety of geometries and form factors. The volume between the conductors is filled with liquid blends of monomers, polymers, oligomers, and/or cross-linkers and dielectric powders; and then cured to form high field strength and high dielectric constant solid dielectric transmission lines that intrinsically produce ideal rectangular high voltage pulses when charged and switched into matched impedance loads. Voltage levels may be increased by Marx and/or Blumlein principles incorporating spark gap or, preferentially, solid state switches (such as optically triggered thyristors) which produce reliable, high repetition rate operation. Moreover, these Marxed pulse generators can be DC charged and do not require additional pulse forming circuitry, pulse forming lines, transformers, or an a high voltage spark gap output switch. The apparatus accommodates a wide range of voltages, impedances, pulse durations, pulse repetition rates, and duty cycles. The resulting mobile or flight platform friendly cylindrical geometric configuration is much more compact, light-weight, and robust than conventional linear geometries, or pulse generators constructed from conventional components. Installing additional circuitry may accommodate optional pulse shape improvements. The Coiled Transmission Lines can also be connected in parallel to decrease the impedance, or in series to increase the pulse length.

  12. 49 CFR 192.707 - Line markers for mains and transmission lines.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Line markers for mains and transmission lines. 192... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.707 Line markers for mains and transmission lines. (a) Buried pipelines. Except as provided...

  13. 49 CFR 192.707 - Line markers for mains and transmission lines.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Line markers for mains and transmission lines. 192... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.707 Line markers for mains and transmission lines. (a) Buried pipelines. Except as provided...

  14. 49 CFR 192.707 - Line markers for mains and transmission lines.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Line markers for mains and transmission lines. 192... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.707 Line markers for mains and transmission lines. (a) Buried pipelines. Except as provided...

  15. Coaxial tube array space transmission line characterization

    NASA Technical Reports Server (NTRS)

    Switzer, Colleen A.; Bents, David J.

    1987-01-01

    The coaxial tube array tether/transmission line used to connect an SP-100 nuclear power system to the space station was characterized over the range of reactor-to-platform separation distances of 1 to 10 km. Characterization was done with respect to array performance, physical dimensions and masses. Using a fixed design procedure, a family of designs was generated for the same power level (300 kWe), power loss (1.5 percent), and meteoroid survival probability (99.5 percent over 10 yr). To differentiate between vacuum insulated and gas insulated lines, two different maximum values of the E field were considered: 20 kV/cm (appropriate to vacuum insulation) and 50 kV/cm (compressed SF6). Core conductor, tube, bumper, standoff, spacer and bumper support dimensions, and masses were also calculated. The results of the characterization show mainly how transmission line size and mass scale with reactor-to-platform separation distance.

  16. Coaxial tube array space transmission line characterization

    NASA Astrophysics Data System (ADS)

    Switzer, Colleen A.; Bents, David J.

    The coaxial tube array tether/transmission line used to connect an SP-100 nuclear power system to the space station was characterized over the range of reactor-to-platform separation distances of 1 to 10 km. Characterization was done with respect to array performance, physical dimensions and masses. Using a fixed design procedure, a family of designs was generated for the same power level (300 kWe), power loss (1.5 percent), and meteoroid survival probability (99.5 percent over 10 yr). To differentiate between vacuum insulated and gas insulated lines, two different maximum values of the E field were considered: 20 kV/cm (appropriate to vacuum insulation) and 50 kV/cm (compressed SF6). Core conductor, tube, bumper, standoff, spacer and bumper support dimensions, and masses were also calculated. The results of the characterization show mainly how transmission line size and mass scale with reactor-to-platform separation distance.

  17. 18 CFR 2.2 - Transmission lines.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... 18 Conservation of Power and Water Resources 1 2010-04-01 2010-04-01 false Transmission lines. 2.2... Under the Federal Power Act § 2.2 Transmission lines. In a public statement dated March 7, 1941, the Commission announced its determination that transmission lines which are not primary lines transmitting...

  18. 18 CFR 2.2 - Transmission lines.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... 18 Conservation of Power and Water Resources 1 2014-04-01 2014-04-01 false Transmission lines. 2.2... Under the Federal Power Act § 2.2 Transmission lines. In a public statement dated March 7, 1941, the Commission announced its determination that transmission lines which are not primary lines transmitting...

  19. 18 CFR 2.2 - Transmission lines.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... 18 Conservation of Power and Water Resources 1 2012-04-01 2012-04-01 false Transmission lines. 2.2... Under the Federal Power Act § 2.2 Transmission lines. In a public statement dated March 7, 1941, the Commission announced its determination that transmission lines which are not primary lines transmitting...

  20. 18 CFR 2.2 - Transmission lines.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... 18 Conservation of Power and Water Resources 1 2013-04-01 2013-04-01 false Transmission lines. 2.2... Under the Federal Power Act § 2.2 Transmission lines. In a public statement dated March 7, 1941, the Commission announced its determination that transmission lines which are not primary lines transmitting...

  1. 18 CFR 2.2 - Transmission lines.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... 18 Conservation of Power and Water Resources 1 2011-04-01 2011-04-01 false Transmission lines. 2.2... Under the Federal Power Act § 2.2 Transmission lines. In a public statement dated March 7, 1941, the Commission announced its determination that transmission lines which are not primary lines transmitting...

  2. Transmission line including support means with barriers

    DOEpatents

    Cookson, Alan H.

    1982-01-01

    A gas insulated transmission line includes an elongated outer sheath, a plurality of inner conductors disposed within and extending along the outer sheath, and an insulating gas which electrically insulates the inner conductors from the outer sheath. A support insulator insulatably supports the inner conductors within the outer sheath, with the support insulator comprising a main body portion including a plurality of legs extending to the outer sheath, and barrier portions which extend between the legs. The barrier portions have openings therein adjacent the main body portion through which the inner conductors extend.

  3. Development of compact 500 kV 8000 A gas insulated transmission line-dust control during field jointing and method for detecting conductive particles

    SciTech Connect

    Kaminaga, K.; Koshiishi, M.; Hayashi, T.; Matsuki, M.; Hara, T.; Sugiyama, N.

    1987-10-01

    This paper describes the results of studies made on dust control during field jointing and a method for detecting conductive particles after installation in the development of a compact 500 kV 8000 A gas insulated transmission line (GIL). The study on dust control during field jointing proved that field jointing of the compact GIL can be done like conventional GIL in an easily fabricated vinyl shelter without a clean air flow. Harmful conductive particles can be detected with an Acoustic Emission (AE) sensor. This sensor is effective in improving the reliability of the compact GIL when used with a suitable ac voltage during field test. A 120 m long test line of compact 500 kV 8000 A GIL was constructed and, in a long-term field test, proved to have properties sufficient for practical use.

  4. 75 FR 13524 - Northern Natural Gas Company, Southern Natural Gas Company, Florida Gas Transmission Company, LLC...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-03-22

    ... Energy Regulatory Commission Northern Natural Gas Company, Southern Natural Gas Company, Florida Gas Transmission Company, LLC, Transcontinental Gas Pipe Line Company, LLC, Enterprise Field Services, LLC; Notice of Application March 16, 2010. Take notice that on March 5, 2010, Northern Natural Gas...

  5. Superconducting transmission line particle detector

    DOEpatents

    Gray, Kenneth E.

    1989-01-01

    A microvertex particle detector for use in a high energy physic collider including a plurality of parallel superconducting thin film strips separated from a superconducting ground plane by an insulating layer to form a plurality of superconducting waveguides. The microvertex particle detector indicates passage of a charged subatomic particle by measuring a voltage pulse measured across a superconducting waveguide caused by the transition of the superconducting thin film strip from a superconducting to a non-superconducting state in response to the passage of a charged particle. A plurality of superconducting thin film strips in two orthogonal planes plus the slow electromagnetic wave propogating in a superconducting transmission line are used to resolve N.sup.2 ambiguity of charged particle events.

  6. Superconducting transmission line particle detector

    DOEpatents

    Gray, K.E.

    1988-07-28

    A microvertex particle detector for use in a high energy physic collider including a plurality of parallel superconducting thin film strips separated from a superconducting ground plane by an insulating layer to form a plurality of superconducting waveguides. The microvertex particle detector indicates passage of a charged subatomic particle by measuring a voltage pulse measured across a superconducting waveguide caused by the transition of the superconducting thin film strip from a superconducting to a non- superconducting state in response to the passage of a charged particle. A plurality of superconducting thin film strips in two orthogonal planes plus the slow electromagnetic wave propagating in a superconducting transmission line are used to resolve N/sup 2/ ambiguity of charged particle events. 6 figs.

  7. Magnetically insulated transmission line oscillator

    DOEpatents

    Bacon, L.D.; Ballard, W.P.; Clark, M.C.; Marder, B.M.

    1987-05-19

    A magnetically insulated transmission line oscillator employs self-generated magnetic fields to generate microwave energy. An anode of the oscillator includes slow-wave structures which are formed of a plurality of thin conductive vanes defining cavities therebetween, and a gap is formed between the anode and a cathode of the oscillator. In response to a pulsed voltage applied to the anode and cathode, self-generated magnetic fields are produced in a cross-field orientation with respect to the orientation of the electric field between the anode and the cathode. The cross-field magnetic fields insulate the flow of electrons in the gap and confine the flow of electrons within the gap. 11 figs.

  8. Magnetically insulated transmission line oscillator

    DOEpatents

    Bacon, Larry D.; Ballard, William P.; Clark, M. Collins; Marder, Barry M.

    1988-01-01

    A magnetically insulated transmission line oscillator employs self-generated magnetic fields to generate microwave energy. An anode of the oscillator includes slow-wave structures which are formed of a plurality of thin conductive vanes defining cavities therebetween, and a gap is formed between the anode and a cathode of the oscillator. In response to a pulsed voltage applied to the anode and cathode, self-generated magnetic fields arfe produced in a cross-field orientation with respect to the orientation of the electric field between the anode and the cathode. The cross-field magnetic fields insulate the flow of electrons in the gap and confine the flow of electrons within the gap.

  9. 75 FR 51030 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-08-18

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application August 12, 2010. Take notice that on August 5, 2010, Columbia Gas Transmission Corporation (Columbia), 5151 San Felipe, Suite... Transmission, L.P. (Texas Eastern), approximately 2 miles of 16-inch pipeline on Columbia's Line 1528...

  10. RF Transmission Lines on Silicon Substrates

    NASA Technical Reports Server (NTRS)

    Ponchak, George E.

    1999-01-01

    A review of RF transmission lines on silicon substrates is presented. Through measurements and calculated results, it is shown that attenuation is dominated by conductor loss if silicon substrates with a resistivity greater than 2500 Ohm-cm are used. Si passivation layers affect the transmission line attenuation; however, measured results demonstrate that passivation layers do not necessarily increase attenuation. If standard, low resistivity Si wafers must be used, alternative transmission lines such as thin film microstrip and Co-Planar Waveguide (CPW) on thick polyimide layers must be used. Measured results presented here show that low loss per unit length is achievable with these transmission lines.

  11. Transmission Line Security Monitor: Final Report

    SciTech Connect

    John Svoboda

    2011-04-01

    The Electric Power Transmission Line Security Monitor System Operational Test is a project funded by the Technical Support Working Group (TSWG). TSWG operates under the Combating Terrorism Technical Support Office that functions under the Department of Defense. The Transmission Line Security Monitor System is based on technology developed by Idaho National Laboratory. The technology provides a means for real-time monitoring of physical threats and/or damage to electrical transmission line towers and conductors as well as providing operational parameters to transmission line operators to optimize transmission line operation. The end use is for monitoring long stretches of transmission lines that deliver electrical power from remote generating stations to cities and industry. These transmission lines are generally located in remote transmission line corridors where security infrastructure may not exist. Security and operational sensors in the sensor platform on the conductors take power from the transmission line and relay security and operational information to operations personnel hundreds of miles away without relying on existing infrastructure. Initiated on May 25, 2007, this project resulted in pre-production units tested in realistic operational environments during 2010. A technology licensee, Lindsey Manufacturing of Azusa California, is assisting in design, testing, and ultimately production. The platform was originally designed for a security monitoring mission, but it has been enhanced to include important operational features desired by electrical utilities.

  12. Reconfigurable transmission lines with memcapacitive materials

    NASA Astrophysics Data System (ADS)

    Pershin, Y. V.; Slipko, V. A.; Di Ventra, M.

    2015-12-01

    We study transmission lines made of memory capacitive (memcapacitive) materials. The transmission properties of these lines can be adjusted on demand using an appropriate sequence of pulses. In particular, we demonstrate a pulse combination that creates a periodic modulation of dielectric properties along the line. Such a structure resembles a distributed Bragg reflector having important optical applications. We present simulation results demonstrating all major steps of such a reconfigurable device operation including reset, programming, and transmission of small amplitude signals. The proposed reconfigurable transmission lines employ only passive memory materials and can be realized using available memcapacitive devices.

  13. Detonator comprising a nonlinear transmission line

    SciTech Connect

    Elizondo-Decanini, Juan M

    2014-12-30

    Detonators are described herein. In a general embodiment, the detonator includes a nonlinear transmission line that has a variable capacitance. Capacitance of the nonlinear transmission line is a function of voltage on the nonlinear transmission line. The nonlinear transmission line receives a voltage pulse from a voltage source and compresses the voltage pulse to generate a trigger signal. Compressing the voltage pulse includes increasing amplitude of the voltage pulse and decreasing length of the voltage pulse in time. An igniter receives the trigger signal and detonates an explosive responsive to receipt of the trigger signal.

  14. Gas transmission through microporous membranes

    NASA Astrophysics Data System (ADS)

    Turel, Tacibaht

    2008-10-01

    An ideal protective clothing material should be a good barrier against harmful gases or vapor while allowing moisture vapor and air passage through the material. In the study and design of barrier materials, one of the critical issues is to balance these requirements, which may sometimes be mutually exclusive. Therefore it is critical to understand the macroscopic and microscopic structure of the attack mechanisms as well as the barrier materials and the transport phenomena in such systems. In this study, air and gas transmission through barrier systems consisting of porous membranes was investigated experimentally and a molecular-level probabilistic model was constructed to evaluate the effect of various parameters on the gas flow. The effect of membrane parameters such as porosity, pore size distribution, thickness as well as gas parameters such as molecule diameters were examined at single layer as well as multiple layers. To understand the gas behavior for harmful chemicals and to ensure safety during experimental studies, mimics of such gases were obtained which were comparable to the actual gases in shape, molecular weight and other chemical properties. Air, ammonia and several mimic gases of harmful chemical agents were studied. Beta-pinene was used as a mimic of sarin and prenol was used as a mimic of nitrogen mustard. Gas transmission experiments were conducted on polyester, nylon and polypropylene membranes each of which had different porosity and pore size distributions. Experiments were done at different pressure values and a comparison was made between permeability testing machines based on volumetric and manometric principles as to their ability to accommodate high permeability membranes. Physical and chemical adsorption of such gases on porous membranes was also investigated after the addition of active elements on the membrane surfaces which can interact with the gas molecules. An experimental setup was developed to measure concentration changes

  15. Gas line construction in frigid Canadian winter

    SciTech Connect

    Not Available

    1983-01-01

    Construction of a 128-mile, 42-in. gas transmission line through Precambrian rock formations in the Canadian shield proved difficult for contractors on TransCanada Pipeline's expansion program. Multiple construction problems included severe cold weather (-40/sup 0/F), a right-of-way sited midway between two live natural gas lines, and a system installed in eight different loops stretching almost 500 miles from one and to the other.

  16. Investigation of a stripline transmission line structure for gyromagnetic nonlinear transmission line high power microwave sources

    NASA Astrophysics Data System (ADS)

    Reale, D. V.; Parson, J. M.; Neuber, A. A.; Dickens, J. C.; Mankowski, J. J.

    2016-03-01

    A stripline gyromagnetic nonlinear transmission line (NLTL) was constructed out of yttrium iron garnet ferrite and tested at charge voltages of 35 kV-55 kV with bias fields ranging from 10 kA/m to 20 kA/m. Typically, high power gyromagnetic NLTLs are constructed in a coaxial geometry. While this approach has many advantages, including a uniform transverse electromagnetic (TEM) mode, simple interconnection between components, and the ability to use oil or pressurized gas as an insulator, the coaxial implementation suffers from complexity of construction, especially when using a solid insulator. By moving to a simpler transmission line geometry, NLTLs can be constructed more easily and arrayed on a single substrate. This work represents a first step in exploring the suitability of various transmission line structures, such as microstrips and coplanar waveguides. The resulting high power microwave (HPM) source operates in ultra high frequency (UHF) band with an average bandwidth of 40.1% and peak rf power from 2 MW to 12.7 MW.

  17. Investigation of a stripline transmission line structure for gyromagnetic nonlinear transmission line high power microwave sources.

    PubMed

    Reale, D V; Parson, J M; Neuber, A A; Dickens, J C; Mankowski, J J

    2016-03-01

    A stripline gyromagnetic nonlinear transmission line (NLTL) was constructed out of yttrium iron garnet ferrite and tested at charge voltages of 35 kV-55 kV with bias fields ranging from 10 kA/m to 20 kA/m. Typically, high power gyromagnetic NLTLs are constructed in a coaxial geometry. While this approach has many advantages, including a uniform transverse electromagnetic (TEM) mode, simple interconnection between components, and the ability to use oil or pressurized gas as an insulator, the coaxial implementation suffers from complexity of construction, especially when using a solid insulator. By moving to a simpler transmission line geometry, NLTLs can be constructed more easily and arrayed on a single substrate. This work represents a first step in exploring the suitability of various transmission line structures, such as microstrips and coplanar waveguides. The resulting high power microwave (HPM) source operates in ultra high frequency (UHF) band with an average bandwidth of 40.1% and peak rf power from 2 MW to 12.7 MW. PMID:27036802

  18. Single transmission line data acquisition system

    DOEpatents

    Fasching, George E.

    1984-01-01

    A single transmission line interrogated multiple channel data acquisition system is provided in which a plurality of remote station/sensors monitor specific process variables and transmit measurement values over the single transmission line to a master station when addressed by the master station. Power for all remote stations (up to 980) is provided by driving the line with constant voltage supplied from the master station and automatically maintained independent of the number of remote stations directly connected to the line. The transmission line can be an RG-62 coaxial cable with lengths up to about 10,000 feet with branches up to 500 feet. The remote stations can be attached randomly along the line. The remote stations can be scanned at rates up to 980 channels/second.

  19. Electrical Transmission Line Diametrical Retention Mechanism

    DOEpatents

    Hall, David R.; Hall, Jr., H. Tracy; Pixton, David; Dahlgren, Scott; Sneddon, Cameron; Briscoe, Michael; Fox, Joe

    2006-01-03

    The invention is a mechanism for retaining an electrical transmission line. In one embodiment of the invention it is a system for retaining an electrical transmission line within downhole components. The invention allows a transmission line to be attached to the internal diameter of drilling components that have a substantially uniform drilling diameter. In accordance with one aspect of the invention, the system includes a plurality of downhole components, such as sections of pipe in a drill string, drill collars, heavy weight drill pipe, and jars. The system also includes a coaxial cable running between the first and second end of a drill pipe, the coaxial cable having a conductive tube and a conductive core within it. The invention allows the electrical transmission line to withstand the tension and compression of drill pipe during routine drilling cycles.

  20. Concurrent Wind Cooling in Power Transmission Lines

    SciTech Connect

    Jake P Gentle

    2012-08-01

    Idaho National Laboratory and the Idaho Power Company, with collaboration from Idaho State University, have been working on a project to monitor wind and other environmental data parameters along certain electrical transmission corridors. The combination of both real-time historical weather and environmental data is being used to model, validate, and recommend possibilities for dynamic operations of the transmission lines for power and energy carrying capacity. The planned results can also be used to influence decisions about proposed design criteria for or upgrades to certain sections of the transmission lines.

  1. Effect of tornado loads on transmission lines

    SciTech Connect

    Ishac, M.F.; White, H.B.

    1995-01-01

    Of all the populated areas in Canada, southwestern Ontario has experienced the highest tornado incidence and faces the greatest tornado damage. About 1 or 2 tornadoes per 10,000 km{sup 2} can be expected there annually. The probability of a tornado strike at a given point is very small but the probability of a transmission line being crossed by a tornado is significant. The purpose of this paper is to review the literature related to tornadoes in Ontario and to investigate the effect of tornado loads on transmission lines. Based on this investigation a design basis tornado loading for transmission towers is proposed.

  2. Effect of tornado loads on transmission lines

    SciTech Connect

    Ishac, M.F.; White, H.B.

    1994-12-31

    Of all the populated areas in Canada, southwestern Ontario has experienced the highest tornado incidence and faces the greatest tornado damage. About 1 or 2 tornadoes per 10,000 km{sup 2} can be expected there annually. The probability of a tornado strike at a given point is very small but the probability of a transmission line being crossed by a tornado is significant. The purpose of this paper is to review the literature related to tornadoes in Ontario and to investigate the effect of tornado loads on transmission lines. Based on this investigation a design basis tornado loading for transmission towers is proposed.

  3. Bird streamer flashovers on FPL transmission lines

    SciTech Connect

    Burnham, J.T.

    1995-04-01

    FPL transmission lines with excessive unknown cause outages were investigated and determined to have experiences bird streamer flashovers. Findings are extended to similar lines and the frequency of bird streamer occurrences are estimated. Outage patterns associated with bird streamer flashovers are presented.

  4. 77 FR 55207 - Florida Gas Transmission Company, LLC, Florida Gas Transmission Company, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-09-07

    ... Energy Regulatory Commission Florida Gas Transmission Company, LLC, Florida Gas Transmission Company, LLC; Notice of Application Take notice that on August 16, 2012, Florida Gas Transmission Company, LLC (FGT... & Tariffs, Florida Gas Transmission Company, LLC, 5051 Westheimer Road, Houston, Texas, 77056, or call...

  5. Low-noise cryogenic transmission line

    NASA Technical Reports Server (NTRS)

    Norris, D.

    1987-01-01

    New low-noise cryogenic input transmission lines have been developed for the Deep Space Network (DSN) at 1.668 GHz for cryogenically cooled Field Effect Transistors (FET) and High Electron Mobility Transistor (HEMT) amplifiers. These amplifiers exhibit very low noise temperatures of 5 K to 15 K, making the requirements for a low-noise input transmission line critical. Noise contribution to the total amplifier system from the low-noise line is less than 0.5 K for both the 1.668-GHz and 2.25-GHz FET systems. The 1.668-GHz input line was installed in six FET systems which were implemented in the DSN for the Venus Balloon Experiment. The 2.25-GHz input line has been implemented in three FET systems for the DSN 34-m HEF antennas, and the design is currently being considered for use at higher frequencies.

  6. Lecture 4: transmission lines and capacitors

    SciTech Connect

    Butcher, R.R.

    1980-01-01

    The topic of this lecture is pulse forming networks. The first item of discussion will be transmission lines because they are so prevalent, even if only in the form of coaxial cable. From there the subject will proceed to pulse-forming networks: the practical problems encountered with them, their advantages, and disadvantages. Capacitors will be our final topic, as they are the limiting factor in lumped transmission elements.

  7. Robust hyperchaotic synchronization via analog transmission line

    NASA Astrophysics Data System (ADS)

    Sadoudi, S.; Tanougast, C.

    2016-02-01

    In this paper, a novel experimental chaotic synchronization technique via analog transmission is discussed. We demonstrate through Field-Programmable Gate Array (FPGA) implementation design the robust synchronization of two embedded hyperchaotic Lorenz generators interconnected with an analog transmission line. The basic idea of this work consists in combining a numerical generation of chaos and transmitting it with an analog signal. The numerical chaos allows to overcome the callback parameter mismatch problem and the analog transmission offers robust data security. As application, this technique can be applied to all families of chaotic systems including time-delayed chaotic systems.

  8. Flux Cloning in Josephson Transmission Lines

    SciTech Connect

    Gulevich, D.R.; Kusmartsev, F.V.

    2006-07-07

    We describe a novel effect related to the controlled birth of a single Josephson vortex. In this phenomenon, the vortex is created in a Josephson transmission line at a T-shaped junction. The 'baby' vortex arises at the moment when a 'mother' vortex propagating in the adjacent transmission line passes the T-shaped junction. In order to give birth to a new vortex, the mother vortex must have enough kinetic energy. Its motion can also be supported by an externally applied driving current. We determine the critical velocity and the critical driving current for the creation of the baby vortices and briefly discuss the potential applications of the found effect.

  9. EC Transmission Line Risk Identification and Analysis

    SciTech Connect

    Bigelow, Tim S

    2012-04-01

    The purpose of this document is to assist in evaluating and planning for the cost, schedule, and technical project risks associated with the delivery and operation of the EC (Electron cyclotron) transmission line system. In general, the major risks that are anticipated to be encountered during the project delivery phase associated with the implementation of the Procurement Arrangement for the EC transmission line system are associated with: (1) Undefined or changing requirements (e.g., functional or regulatory requirements) (2) Underperformance of prototype, first unit, or production components during testing (3) Unavailability of qualified vendors for critical components Technical risks associated with the design and operation of the system are also identified.

  10. The Role of Continuous Cooling Transformation Diagrams in Materials Design for High Strength Oil and Gas Transmission LinePipe Steels

    SciTech Connect

    Stalheim, Mr. Douglas; Muralidharan, Govindarajan

    2006-01-01

    The economical movement of gas and oil to the marketplace requires transmission pipelines to be designed to operate at higher pressures with improved toughness over a variety of temperature ranges. To meet the higher strength and toughness specification requirements of these transmission pipelines, appropriate materials and processes must be used in their design and construction. This includes selection of appropriate alloy composition, processing routes, microstructure control, and cost. A continuous cooling transformation (CCT) diagram is a tool that can be used to select alloy composition and processing route in order to obtain a specific, desirable microstructure for transmission pipeline steels in a cost effective manner. In the past, CCT diagrams were developed experimentally under laboratory conditions and thus not practical for commercial pipeline design considerations. However, with the vast data available and improved computational tools, reasonably accurate computer generated CCT diagrams can be produced quickly. These computer generated diagrams can give a materials design engineer, a reasonable understanding of the effect of subjecting a given alloy to various processing routes and hence the resultant microstructures. Since final microstructure is a key variable in determining the final pipeline steel material properties, the chosen alloy/processing route and its effect on the final microstructure needs to be understood. This paper will discuss the role of CCT diagrams in the design of steels (cost, alloy, processing, and microstructure) for oil and gas transmission pipelines. Examples of computer generated CCT diagrams for various API alloy designs are included.

  11. 49 CFR 192.706 - Transmission lines: Leakage surveys.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Leakage surveys. 192.706... Transmission lines: Leakage surveys. Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line...

  12. 49 CFR 192.706 - Transmission lines: Leakage surveys.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Leakage surveys. 192.706... Transmission lines: Leakage surveys. Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line...

  13. 49 CFR 192.706 - Transmission lines: Leakage surveys.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission lines: Leakage surveys. 192.706... Transmission lines: Leakage surveys. Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line...

  14. 49 CFR 192.706 - Transmission lines: Leakage surveys.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Leakage surveys. 192.706... Transmission lines: Leakage surveys. Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line...

  15. 49 CFR 192.706 - Transmission lines: Leakage surveys.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission lines: Leakage surveys. 192.706... Transmission lines: Leakage surveys. Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line...

  16. Transmission line environmental assessment guidance document

    SciTech Connect

    Jackson, J.; Pentecost, E.; Muzzarelli, J.

    1994-01-01

    Since 1939, U.S. utility companies have been required to obtain a Presidential Permit to construct electric transmission lines that cross a U.S. border and connect with a foreign utility. The purpose of this document is to provide Presidential Permit applicants with two types of guidance: (1) on the type of environmental and project descriptive information needed to assess the potential impacts of the proposed and alternative actions and (2) on compliance with applicable federal and state regulations. The main three chapters present information on the purpose and content of this document (Chapter 1); legislative, regulatory, and consultation requirements for transmission line interconnect projects (Chapter 2); and identification of basic transmission system design parameters and environmental data requirements for analysis of potential impacts of the proposed action (Chapter 3). Chapter 3 also includes information on possible techniques or measures to mitigate impacts. Appendix A presents an overview of NEPA requirements and DOE`s implementing procedures. Appendix B summarizes information on legislation that may be applicable to transmission line projects proposed in Presidential Permit applications.

  17. Integrated survey and design for transmission lines

    SciTech Connect

    Miller, M.A.; Simpson, K.D.

    1994-12-31

    Gathering and compiling information on the features and uses of the land within a proposed corridor provides the basis for selecting a route, obtaining easements, and designing and constructing a transmission line. Traditionally, gathering this information involved searches of existing maps and records to obtain the available information, which would then be supplemented with aerial photography to record current conditions. Ground surveys were performed to collect topographic data for design purposes. This information was manually transferred to drawings and other documents to show the terrain, environmentally sensitive areas, property ownership, and existing facilities. These drawing served as the base to which the transmission line right-of-way, structures, and other design information were added. As the design was completed, these drawings became the source of information for constructing the line and ultimately, the record of the facility. New technologies and the every growing need for instantly accessible information have resulted in changes in almost every step of gathering, storing and using information. Electronic data collection, global positioning systems (GPS), digitized terrain models, computerized design techniques, development of drawings using CAD, and graphical information systems (GIS) have individually resulted in significant advancements in this process. Combining these components into an integrated system, however, is truly revolutionizing transmission line engineering. This paper gives an overview of the survey and mapping information that is required for transmission line projects, review the traditional techniques that have been employed to obtain and utilize this information, and discuss the recent advances in the technology. Additionally, a system is presented that integrates the components in this process to achieve efficiency, minimize chances of errors, and provide improved access to project information.

  18. 7 CFR 1726.77 - Substation and transmission line construction.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... 7 Agriculture 11 2012-01-01 2012-01-01 false Substation and transmission line construction. 1726... and Transmission Facilities § 1726.77 Substation and transmission line construction. (a) Contract... substation and transmission line construction (including minor modifications or improvements), exclusive...

  19. 7 CFR 1726.77 - Substation and transmission line construction.

    Code of Federal Regulations, 2011 CFR

    2011-01-01

    ... 7 Agriculture 11 2011-01-01 2011-01-01 false Substation and transmission line construction. 1726... and Transmission Facilities § 1726.77 Substation and transmission line construction. (a) Contract... substation and transmission line construction (including minor modifications or improvements), exclusive...

  20. 7 CFR 1726.77 - Substation and transmission line construction.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 7 Agriculture 11 2010-01-01 2010-01-01 false Substation and transmission line construction. 1726... and Transmission Facilities § 1726.77 Substation and transmission line construction. (a) Contract... substation and transmission line construction (including minor modifications or improvements), exclusive...

  1. 7 CFR 1726.77 - Substation and transmission line construction.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... 7 Agriculture 11 2014-01-01 2014-01-01 false Substation and transmission line construction. 1726... and Transmission Facilities § 1726.77 Substation and transmission line construction. (a) Contract... substation and transmission line construction (including minor modifications or improvements), exclusive...

  2. 7 CFR 1726.77 - Substation and transmission line construction.

    Code of Federal Regulations, 2013 CFR

    2013-01-01

    ... 7 Agriculture 11 2013-01-01 2013-01-01 false Substation and transmission line construction. 1726... and Transmission Facilities § 1726.77 Substation and transmission line construction. (a) Contract... substation and transmission line construction (including minor modifications or improvements), exclusive...

  3. Application of composite insulators to transmission lines

    SciTech Connect

    Cherney, E.A.; Brown, R.L.; Karady, G.; Nicholls, J.L.; Orbeck, T.; Pargamin, L.

    1983-05-01

    The paper provides guidelines for the application of composite insulators to transmission lines. These guidelines are based on utility field experiences, results of research laboratory tests and manufacturers' recommendations. Discussed are interchangeability with porcelain and glass insulators, application in contaminated environments, material ageing, insulator icing, the use of grease, resistance to vandalism, temperature extremes, and the need for grading rings. Clarification is provided on the mechanical rating of composite insulators because there is not yet general agreement by various industry groups.

  4. A transmission line bridge for the diagnostics of plasma channels

    NASA Astrophysics Data System (ADS)

    Pechacek, R. E.; Raleigh, M.; Greig, J. R.; Dwyer, T.; Ehrlich, J.

    1984-03-01

    This paper describes a device for measuring the average electrical conductivity of a long, narrow, cylindrical plasma. Interest in plasmas of this shape originates from two areas of study: the study of electron beam propagation through neutral gas, and the study of long straight electrical discharges for use as a communication antenna. Propagation of an electron beam through a neutral gas produces an ionized channel whose properties and evolution are very important to the propagation of the beam itself. Long straight electrical discharges are created in a channel that is ionized by a pulsed laser beam focused with a long focal length lens, and the properties of the plasma in this channel are important to the propagation of the electrical discharge along with channel. The properties of these plasmas are inferred from changes in the transmission properties of a transmission line placed close to and parallel to the plasma. In this paper an analysis is made of the relation between the bridge output voltage and the conductivity of the perturbing plasma for the case in which the conductivity is very low. In this case all perturbations on the bridge parameters are small, and linear approximations are appropriate. The usefulness of the bridge, however, extends to plasma well above this low conductivity range, although a different set of approximations may be necessary to make the analysis of the experiment tractable. A transmission line bridge is a device for measuring very small changes in the properties of transmission lines.

  5. 75 FR 42432 - Northern Natural Gas Company, Southern Natural Gas Company, Florida Gas Transmission Company, LLC...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-07-21

    ... Transmission Company, LLC, Transcontinental Gas Pipe Line Company, LLC, and Enterprise Field Services, LLC..., LLC, and Enterprise Field Services, LLC, collectively referred to as the Applicants, in Refugio County... scoping process the Commission will use to gather input from the public and interested agencies on...

  6. Dispersion-free radial transmission lines

    DOEpatents

    Caporaso, George J.; Nelson, Scott D.

    2011-04-12

    A dispersion-free radial transmission line ("DFRTL") preferably for linear accelerators, having two plane conductors each with a central hole, and an electromagnetically permeable material ("EPM") between the two conductors and surrounding a channel connecting the two holes. At least one of the material parameters of relative magnetic permeability, relative dielectric permittivity, and axial width of the EPM is varied as a function of radius, so that the characteristic impedance of the DFRTL is held substantially constant, and pulse transmission therethrough is substantially dispersion-free. Preferably, the EPM is divided into concentric radial sections, with the varied material parameters held constant in each respective section but stepwise varied between sections as a step function of the radius. The radial widths of the concentric sections are selected so that pulse traversal time across each section is the same, and the varied material parameters of the concentric sections are selected to minimize traversal error.

  7. 49 CFR 192.711 - Transmission lines: General requirements for repair procedures.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... pipeline covered under Subpart O-Gas Transmission Pipeline Integrity Management, the operator must... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: General requirements for...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY...

  8. 49 CFR 192.711 - Transmission lines: General requirements for repair procedures.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... pipeline covered under Subpart O-Gas Transmission Pipeline Integrity Management, the operator must... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: General requirements for...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY...

  9. 49 CFR 192.711 - Transmission lines: General requirements for repair procedures.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... pipeline covered under Subpart O-Gas Transmission Pipeline Integrity Management, the operator must... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: General requirements for...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY...

  10. 49 CFR 192.713 - Transmission lines: Permanent field repair of imperfections and damages.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Permanent field repair of...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.713 Transmission lines: Permanent field repair of imperfections and damages. (a)...

  11. 49 CFR 192.713 - Transmission lines: Permanent field repair of imperfections and damages.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission lines: Permanent field repair of...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.713 Transmission lines: Permanent field repair of imperfections and damages. (a)...

  12. 49 CFR 192.715 - Transmission lines: Permanent field repair of welds.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.715 Transmission lines: Permanent field repair of welds. Each weld that is unacceptable...

  13. 49 CFR 192.713 - Transmission lines: Permanent field repair of imperfections and damages.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Permanent field repair of...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.713 Transmission lines: Permanent field repair of imperfections and damages. (a)...

  14. 49 CFR 192.717 - Transmission lines: Permanent field repair of leaks.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.717 Transmission lines: Permanent field repair of leaks. Each permanent field repair of a leak...

  15. 49 CFR 192.717 - Transmission lines: Permanent field repair of leaks.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.717 Transmission lines: Permanent field repair of leaks. Each permanent field repair of a leak...

  16. 49 CFR 192.715 - Transmission lines: Permanent field repair of welds.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.715 Transmission lines: Permanent field repair of welds. Each weld that is unacceptable...

  17. 49 CFR 192.717 - Transmission lines: Permanent field repair of leaks.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.717 Transmission lines: Permanent field repair of leaks. Each permanent field repair of a leak...

  18. 49 CFR 192.715 - Transmission lines: Permanent field repair of welds.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Permanent field repair of... SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.715 Transmission lines: Permanent field repair of welds. Each weld that is unacceptable...

  19. 49 CFR 192.713 - Transmission lines: Permanent field repair of imperfections and damages.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Permanent field repair of...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.713 Transmission lines: Permanent field repair of imperfections and damages. (a)...

  20. 49 CFR 192.713 - Transmission lines: Permanent field repair of imperfections and damages.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission lines: Permanent field repair of...) PIPELINE SAFETY TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Maintenance § 192.713 Transmission lines: Permanent field repair of imperfections and damages. (a)...

  1. View facing north, Structure 162 in foreground, as Transmission Line ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    View facing north, Structure 16-2 in foreground, as Transmission Line turns at intersection of Powerline Road and US 87 - Havre Rainbow Transmission Line, Havre City to Great Falls vicinity, Montana, Great Falls, Cascade County, MT

  2. 3. DETAIL, LIGHTNING ARRESTER ON SAR TRANSMISSION LINE. EEC print ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    3. DETAIL, LIGHTNING ARRESTER ON SAR TRANSMISSION LINE. EEC print no. S-C-01-00478, no date. Photographer unknown. - Santa Ana River Hydroelectric System, Transmission Lines, Redlands, San Bernardino County, CA

  3. View facing south, near Structure 515, of Transmission Line rising ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    View facing south, near Structure 51-5, of Transmission Line rising out of Marias River Valley - Havre Rainbow Transmission Line, Havre City to Great Falls vicinity, Montana, Great Falls, Cascade County, MT

  4. Transmission line icing measurement on photogrammetry method

    NASA Astrophysics Data System (ADS)

    Huang, Huan; Ma, Xiaohong; Zhao, Lijin; Du, Hao; Luo, Hong; Mao, Xianyin; Tang, Min; Liu, Yawen

    2015-12-01

    Icing thickness parameter is the basic data for power sector to make decision for icing accident prevention. In this paper, a transmission line icing measurement method is proposed. It used the photogrammetry method to realize icing parameters measurement through the integration of high resolution camera, laser range finder and inertial measurement unit. Compared with traditional icing measurement method, this method is flexible and is the effective supplement of the fixed icing detection terminal. And its high accuracy measurement guarantees the reliability of the icing thickness parameters.

  5. Giant vacuum forces via transmission lines

    PubMed Central

    Shahmoon, Ephraim; Mazets, Igor; Kurizki, Gershon

    2014-01-01

    Quantum electromagnetic fluctuations induce forces between neutral particles, known as the van der Waals and Casimir interactions. These fundamental forces, mediated by virtual photons from the vacuum, play an important role in basic physics and chemistry and in emerging technologies involving, e.g., microelectromechanical systems or quantum information processing. Here we show that these interactions can be enhanced by many orders of magnitude upon changing the character of the mediating vacuum modes. By considering two polarizable particles in the vicinity of any standard electric transmission line, along which photons can propagate in one dimension, we find a much stronger and longer-range interaction than in free space. This enhancement may have profound implications on many-particle and bulk systems and impact the quantum technologies mentioned above. The predicted giant vacuum force is estimated to be measurable in a coplanar waveguide line. PMID:25002503

  6. 49 CFR 192.745 - Valve maintenance: Transmission lines.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Valve maintenance: Transmission lines. 192.745 Section 192.745 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... maintenance: Transmission lines. (a) Each transmission line valve that might be required during any...

  7. 49 CFR 192.179 - Transmission line valves.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission line valves. 192.179 Section 192.179... BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Design of Pipeline Components § 192.179 Transmission line valves. (a) Each transmission line, other than offshore segments, must have sectionalizing...

  8. 49 CFR 192.179 - Transmission line valves.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission line valves. 192.179 Section 192.179... BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Design of Pipeline Components § 192.179 Transmission line valves. (a) Each transmission line, other than offshore segments, must have sectionalizing...

  9. 32 CFR 644.431 - Power transmission lines.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... 32 National Defense 4 2012-07-01 2011-07-01 true Power transmission lines. 644.431 Section 644.431... transmission lines. (a) Authority. Pursuant to the provisions of section 13(d) of the Surplus Property Act of... transmission line and the right of way acquired for its construction is needed for or adaptable to...

  10. 49 CFR 192.179 - Transmission line valves.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission line valves. 192.179 Section 192.179... BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Design of Pipeline Components § 192.179 Transmission line valves. (a) Each transmission line, other than offshore segments, must have sectionalizing...

  11. 32 CFR 644.431 - Power transmission lines.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... 32 National Defense 4 2014-07-01 2013-07-01 true Power transmission lines. 644.431 Section 644.431... transmission lines. (a) Authority. Pursuant to the provisions of section 13(d) of the Surplus Property Act of... transmission line and the right of way acquired for its construction is needed for or adaptable to...

  12. 49 CFR 192.745 - Valve maintenance: Transmission lines.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Valve maintenance: Transmission lines. 192.745 Section 192.745 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... maintenance: Transmission lines. (a) Each transmission line valve that might be required during any...

  13. 49 CFR 192.179 - Transmission line valves.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission line valves. 192.179 Section 192.179... BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Design of Pipeline Components § 192.179 Transmission line valves. (a) Each transmission line, other than offshore segments, must have sectionalizing...

  14. 49 CFR 192.719 - Transmission lines: Testing of repairs.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Testing of repairs. 192.719 Section 192.719 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Testing of repairs. (a) Testing of replacement pipe. If a segment of transmission line...

  15. 49 CFR 192.745 - Valve maintenance: Transmission lines.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Valve maintenance: Transmission lines. 192.745 Section 192.745 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... maintenance: Transmission lines. (a) Each transmission line valve that might be required during any...

  16. 32 CFR 644.431 - Power transmission lines.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... 32 National Defense 4 2013-07-01 2013-07-01 false Power transmission lines. 644.431 Section 644... Power transmission lines. (a) Authority. Pursuant to the provisions of section 13(d) of the Surplus... power transmission line and the right of way acquired for its construction is needed for or adaptable...

  17. 75 FR 25195 - Kake to Petersburg Transmission Line Intertie Project

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-05-07

    ... Forest Service Kake to Petersburg Transmission Line Intertie Project AGENCY: Forest Service, USDA. ACTION... operate a new electric transmission line intertie that would extend west across the Tongass National... transmission line that would transmit power at either 69 or 138 kilovolt (kV) and consist of single wood...

  18. 49 CFR 192.719 - Transmission lines: Testing of repairs.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission lines: Testing of repairs. 192.719 Section 192.719 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Testing of repairs. (a) Testing of replacement pipe. If a segment of transmission line...

  19. 49 CFR 192.485 - Remedial measures: Transmission lines.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Remedial measures: Transmission lines. 192.485... Control § 192.485 Remedial measures: Transmission lines. (a) General corrosion. Each segment of transmission line with general corrosion and with a remaining wall thickness less than that required for...

  20. 49 CFR 192.745 - Valve maintenance: Transmission lines.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Valve maintenance: Transmission lines. 192.745 Section 192.745 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... maintenance: Transmission lines. (a) Each transmission line valve that might be required during any...

  1. 49 CFR 192.719 - Transmission lines: Testing of repairs.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Testing of repairs. 192.719 Section 192.719 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Testing of repairs. (a) Testing of replacement pipe. If a segment of transmission line...

  2. 49 CFR 192.485 - Remedial measures: Transmission lines.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Remedial measures: Transmission lines. 192.485... Control § 192.485 Remedial measures: Transmission lines. (a) General corrosion. Each segment of transmission line with general corrosion and with a remaining wall thickness less than that required for...

  3. 49 CFR 192.719 - Transmission lines: Testing of repairs.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission lines: Testing of repairs. 192.719 Section 192.719 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Testing of repairs. (a) Testing of replacement pipe. If a segment of transmission line...

  4. 49 CFR 192.485 - Remedial measures: Transmission lines.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Remedial measures: Transmission lines. 192.485... Control § 192.485 Remedial measures: Transmission lines. (a) General corrosion. Each segment of transmission line with general corrosion and with a remaining wall thickness less than that required for...

  5. 49 CFR 192.719 - Transmission lines: Testing of repairs.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Testing of repairs. 192.719 Section 192.719 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Testing of repairs. (a) Testing of replacement pipe. If a segment of transmission line...

  6. 49 CFR 192.485 - Remedial measures: Transmission lines.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Remedial measures: Transmission lines. 192.485... Control § 192.485 Remedial measures: Transmission lines. (a) General corrosion. Each segment of transmission line with general corrosion and with a remaining wall thickness less than that required for...

  7. 49 CFR 192.745 - Valve maintenance: Transmission lines.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Valve maintenance: Transmission lines. 192.745 Section 192.745 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... maintenance: Transmission lines. (a) Each transmission line valve that might be required during any...

  8. 49 CFR 192.485 - Remedial measures: Transmission lines.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Remedial measures: Transmission lines. 192.485... Control § 192.485 Remedial measures: Transmission lines. (a) General corrosion. Each segment of transmission line with general corrosion and with a remaining wall thickness less than that required for...

  9. 49 CFR 192.179 - Transmission line valves.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission line valves. 192.179 Section 192.179... BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS Design of Pipeline Components § 192.179 Transmission line valves. (a) Each transmission line, other than offshore segments, must have sectionalizing...

  10. 32 CFR 644.431 - Power transmission lines.

    Code of Federal Regulations, 2010 CFR

    2010-07-01

    ... 32 National Defense 4 2010-07-01 2010-07-01 true Power transmission lines. 644.431 Section 644.431... transmission lines. (a) Authority. Pursuant to the provisions of section 13(d) of the Surplus Property Act of... transmission line and the right of way acquired for its construction is needed for or adaptable to...

  11. 32 CFR 644.431 - Power transmission lines.

    Code of Federal Regulations, 2011 CFR

    2011-07-01

    ... 32 National Defense 4 2011-07-01 2011-07-01 false Power transmission lines. 644.431 Section 644... Power transmission lines. (a) Authority. Pursuant to the provisions of section 13(d) of the Surplus... power transmission line and the right of way acquired for its construction is needed for or adaptable...

  12. 76 FR 5796 - Gas Transmission Northwest Corporation; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-02-02

    ... Energy Regulatory Commission Gas Transmission Northwest Corporation; Notice of Application January 26, 2011. Take notice that on January 14, 2011, Gas Transmission Northwest Corporation (GTN), 717 Texas..., Manager, Project Determinations & Regulatory Administration, Gas Transmission Northwest Corporation,...

  13. A radial transmission line material measurement apparatus

    SciTech Connect

    Warne, L.K.; Moyer, R.D.; Koontz, T.E.; Morris, M.E.

    1993-05-01

    A radial transmission line material measurement sample apparatus (sample holder, offset short standards, measurement software, and instrumentation) is described which has been proposed, analyzed, designed, constructed, and tested. The purpose of the apparatus is to obtain accurate surface impedance measurements of lossy, possibly anisotropic, samples at low and intermediate frequencies (vhf and low uhf). The samples typically take the form of sections of the material coatings on conducting objects. Such measurements thus provide the key input data for predictive numerical scattering codes. Prediction of the sample surface impedance from the coaxial input impedance measurement is carried out by two techniques. The first is an analytical model for the coaxial-to-radial transmission line junction. The second is an empirical determination of the bilinear transformation model of the junction by the measurement of three full standards. The standards take the form of three offset shorts (and an additional lossy Salisbury load), which have also been constructed. The accuracy achievable with the device appears to be near one percent.

  14. Modeling Transmission Line Networks Using Quantum Graphs

    NASA Astrophysics Data System (ADS)

    Koch, Trystan; Antonsen, Thomas

    Quantum graphs--one dimensional edges, connecting nodes, that support propagating Schrödinger wavefunctions--have been studied extensively as tractable models of wave chaotic behavior (Smilansky and Gnutzmann 2006, Berkolaiko and Kuchment 2013). Here we consider the electrical analog, in which the graph represents an electrical network where the edges are transmission lines (Hul et. al. 2004) and the nodes contain either discrete circuit elements or intricate circuit elements best represented by arbitrary scattering matrices. Including these extra degrees of freedom at the nodes leads to phenomena that do not arise in simpler graph models. We investigate the properties of eigenfrequencies and eigenfunctions on these graphs, and relate these to the statistical description of voltages on the transmission lines when driving the network externally. The study of electromagnetic compatibility, the effect of external radiation on complicated systems with numerous interconnected cables, motivates our research into this extension of the graph model. Work supported by the Office of Naval Research (N0014130474) and the Air Force Office of Scientific Research.

  15. 76 FR 2676 - Columbia Gas Transmission, LLC; Notice of Availability of the Environmental Assessment for the...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-01-14

    ... Assessment for the Proposed Line 1278-Line K Expansion Project January 7, 2011. The staff of the Federal... Line 1278-Line K Expansion Project proposed by Columbia Gas Transmission, LLC (Columbia) in the above... effects of the construction and operation of the Line 1278-Line K Expansion Project in accordance with...

  16. 49 CFR 192.707 - Line markers for mains and transmission lines.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Line markers for mains and transmission lines. 192... § 192.707 Line markers for mains and transmission lines. (a) Buried pipelines. Except as provided in... buried main and transmission line: (1) At each crossing of a public road and railroad; and (2)...

  17. 49 CFR 192.707 - Line markers for mains and transmission lines.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Line markers for mains and transmission lines. 192... § 192.707 Line markers for mains and transmission lines. (a) Buried pipelines. Except as provided in... buried main and transmission line: (1) At each crossing of a public road and railroad; and (2)...

  18. Method for bonding a transmission line to a downhole tool

    DOEpatents

    Hall, David R.; Fox, Joe

    2007-11-06

    An apparatus for bonding a transmission line to the central bore of a downhole tool includes a pre-formed interface for bonding a transmission line to the inside diameter of a downhole tool. The pre-formed interface includes a first surface that substantially conforms to the outside contour of a transmission line and a second surface that substantially conforms to the inside diameter of a downhole tool. In another aspect of the invention, a method for bonding a transmission line to the inside diameter of a downhole tool includes positioning a transmission line near the inside wall of a downhole tool and placing a mold near the transmission line and the inside wall. The method further includes injecting a bonding material into the mold and curing the bonding material such that the bonding material bonds the transmission line to the inside wall.

  19. Networks of nonlinear superconducting transmission line resonators

    NASA Astrophysics Data System (ADS)

    Leib, M.; Deppe, F.; Marx, A.; Gross, R.; Hartmann, M. J.

    2012-07-01

    We investigate a network of coupled superconducting transmission line resonators, each of them made nonlinear with a capacitively shunted Josephson junction coupling to the odd flux modes of the resonator. The resulting eigenmode spectrum shows anticrossings between the plasma mode of the shunted junction and the odd resonator modes. Notably, we find that the combined device can inherit the complete nonlinearity of the junction, allowing for a description as a harmonic oscillator with a Kerr nonlinearity. Using a dc SQUID instead of a single junction, the nonlinearity can be tuned between 10 kHz and 4 MHz while maintaining resonance frequencies of a few gigahertz for realistic device parameters. An array of such nonlinear resonators can be considered a scalable superconducting quantum simulator for a Bose-Hubbard Hamiltonian. The device would be capable of accessing the strongly correlated regime and be particularly well suited for investigating quantum many-body dynamics of interacting particles under the influence of drive and dissipation.

  20. Nonlinear transmission line based electron beam driver.

    PubMed

    French, David M; Hoff, Brad W; Tang, Wilkin; Heidger, Susan; Allen-Flowers, Jordan; Shiffler, Don

    2012-12-01

    Gated field emission cathodes can provide short electron pulses without the requirement of laser systems or cathode heating required by photoemission or thermionic cathodes. The large electric field requirement for field emission to take place can be achieved by using a high aspect ratio cathode with a large field enhancement factor which reduces the voltage requirement for emission. In this paper, a cathode gate driver based on the output pulse train from a nonlinear transmission line is experimentally demonstrated. The application of the pulse train to a tufted carbon fiber field emission cathode generates short electron pulses. The pulses are approximately 2 ns in duration with emission currents of several mA, and the train contains up to 6 pulses at a frequency of 100 MHz. Particle-in-cell simulation is used to predict the characteristic of the current pulse train generated from a single carbon fiber field emission cathode using the same technique. PMID:23277977

  1. Nonlinear transmission line based electron beam driver

    NASA Astrophysics Data System (ADS)

    French, David M.; Hoff, Brad W.; Tang, Wilkin; Heidger, Susan; Allen-Flowers, Jordan; Shiffler, Don

    2012-12-01

    Gated field emission cathodes can provide short electron pulses without the requirement of laser systems or cathode heating required by photoemission or thermionic cathodes. The large electric field requirement for field emission to take place can be achieved by using a high aspect ratio cathode with a large field enhancement factor which reduces the voltage requirement for emission. In this paper, a cathode gate driver based on the output pulse train from a nonlinear transmission line is experimentally demonstrated. The application of the pulse train to a tufted carbon fiber field emission cathode generates short electron pulses. The pulses are approximately 2 ns in duration with emission currents of several mA, and the train contains up to 6 pulses at a frequency of 100 MHz. Particle-in-cell simulation is used to predict the characteristic of the current pulse train generated from a single carbon fiber field emission cathode using the same technique.

  2. Complex magnetically insulated transmission line oscillator

    NASA Astrophysics Data System (ADS)

    Fan, Yu-Wei; Zhong, Hui-Huang; Shu, Ting; Li, Zhi-Qiang

    2008-08-01

    A magnetically insulated transmission line oscillator (MILO) is a crossed-field device designed specifically to generate microwave power at the gigawatt level, which is a major hotspot in the field of high-power microwaves (HPM) research at present. It is one of the major thrust for MILO development to improve the power conversion efficiency. In order to improve the power conversion efficiency of MILO, a complex MILO is presented and investigated theoretically and numerically, which comprises the MILO-1 and MILO-2. The MILO-2 is used as the load of the MILO-1. The theoretical analyses show that the maximum power conversion efficiency of the complex MILO has an increase of about 50% over the conventional load-limited MILO. The complex MILO is optimized with KARAT code (V. P. Tarakanov, Berkeley Research Associates, Inc., 1992), and the simulation results agree with the theoretical results.

  3. Nonlinear transmission line based electron beam driver

    SciTech Connect

    French, David M.; Hoff, Brad W.; Tang Wilkin; Heidger, Susan; Shiffler, Don; Allen-Flowers, Jordan

    2012-12-15

    Gated field emission cathodes can provide short electron pulses without the requirement of laser systems or cathode heating required by photoemission or thermionic cathodes. The large electric field requirement for field emission to take place can be achieved by using a high aspect ratio cathode with a large field enhancement factor which reduces the voltage requirement for emission. In this paper, a cathode gate driver based on the output pulse train from a nonlinear transmission line is experimentally demonstrated. The application of the pulse train to a tufted carbon fiber field emission cathode generates short electron pulses. The pulses are approximately 2 ns in duration with emission currents of several mA, and the train contains up to 6 pulses at a frequency of 100 MHz. Particle-in-cell simulation is used to predict the characteristic of the current pulse train generated from a single carbon fiber field emission cathode using the same technique.

  4. 49 CFR 192.709 - Transmission lines: Record keeping.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 49 Transportation 3 2012-10-01 2012-10-01 false Transmission lines: Record keeping. 192.709 Section 192.709 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Record keeping. Each operator shall maintain the following records for transmission...

  5. 49 CFR 192.709 - Transmission lines: Record keeping.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... 49 Transportation 3 2013-10-01 2013-10-01 false Transmission lines: Record keeping. 192.709 Section 192.709 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Record keeping. Each operator shall maintain the following records for transmission...

  6. 49 CFR 192.709 - Transmission lines: Record keeping.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 49 Transportation 3 2011-10-01 2011-10-01 false Transmission lines: Record keeping. 192.709 Section 192.709 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Record keeping. Each operator shall maintain the following records for transmission...

  7. 49 CFR 192.709 - Transmission lines: Record keeping.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... 49 Transportation 3 2014-10-01 2014-10-01 false Transmission lines: Record keeping. 192.709 Section 192.709 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Record keeping. Each operator shall maintain the following records for transmission...

  8. 49 CFR 192.709 - Transmission lines: Record keeping.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 49 Transportation 3 2010-10-01 2010-10-01 false Transmission lines: Record keeping. 192.709 Section 192.709 Transportation Other Regulations Relating to Transportation (Continued) PIPELINE AND... Transmission lines: Record keeping. Each operator shall maintain the following records for transmission...

  9. Big Creek Hydroelectric System, East & West Transmission Line, 241mile ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    Big Creek Hydroelectric System, East & West Transmission Line, 241-mile transmission corridor extending between the Big Creek Hydroelectric System in the Sierra National Forest in Fresno County and the Eagle Rock Substation in Los Angeles, California, Visalia, Tulare County, CA

  10. Radio frequency communication system utilizing radiating transmission lines

    DOEpatents

    Struven, Warren C.

    1984-01-01

    A radio communication system for use in tunnels, mines, buildings or other shielded locations in which a pair of radiating transmission lines (30), (31) extend through such location in spaced coextensive relation to each other. Each transmission line (30), (31) has at least one unidirectional amplifier (32), (33) interposed therein with the sense of the unidirectional amplifier (32) of one transmission line (30) being opposite to the sense of the unidirectional amplifier (33) of the other transmission line (31). Each of the amplifiers (32), (33) has a gain which is less than the coupling loss between the transmission lines (30), (31). Two or more mobile transceivers (35) in the location served by the system are coupled to the transmission lines (30), (31) by electromagnetic wave propagation in space in order to communicate directly with each other at a given radio frequency within the frequency range of the system.

  11. A Poynting vector transducer for transmission line monitoring and protection

    SciTech Connect

    Fam, W.Z. )

    1994-01-01

    A new type of transducer is described which enables the continuous monitoring of transmission line current voltage, real and reactive power, and which can also be used to operate the relays necessary for the protection of the line. The new transducer is designed as an integrated unit containing both the current and voltage sensors, thus eliminating the need for conventional current transformers and voltage transformers. The signals from the two sensors are processed using a simple electronic circuit which brings them to a level suitable for metering and relaying purposes. An analogue to digital interface enables the transducer to be connected to a computer for continuous data acquisition storage and monitoring. Due to its geometry and its simple structure, the transducer is ideally suitable for integration into a gas-insulated busbar duct system.

  12. 75 FR 66750 - Albany-Eugene Transmission Line Rebuild Project

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-10-29

    ... Bonneville Power Administration Albany-Eugene Transmission Line Rebuild Project AGENCY: Bonneville Power... Transmission Line Rebuild Project EIS and requesting comments about the potential environmental impacts it should consider as it prepares the EIS for the proposed project. DATES: Written comments are due to...

  13. Transmission line switch design for the investigation of sub-nanosecond electrical breakdown

    NASA Astrophysics Data System (ADS)

    Dick, A. R.; MacGregor, S. J.; Pate, R. C.

    2002-04-01

    Ultrafast plasma closing switches rely on sub-nanosecond electrical breakdown of the insulating gas. Until recently, little information was available on gas breakdown occurring within this timescale, because of the difficulties in designing an experimental system for such a study. Recently published papers have reported on the results of studies carried out using two devices designed specifically for the investigation of fast (sub-nanosecond) electrical breakdown processes. The devices are essentially modified transmission line plasma closing switches, and in this paper we describe their structure and operation. Because electromagnetic wave behaviour plays a significant role in sub-nanosecond switching, especially reflections from impedance mismatches, the design of the devices is based on transmission line concepts, rather than those of lumped parameters. One of the switches has a conical transmission line topology and is designed for the study of fast switch closure at insulating gas pressures less than 0.6 MPa. The second has a hybrid radial transmission line/conical transmission line topology and is designed for the study of fast switch closure at pressures up to 10 MPa. The paper also includes details of the D-dot monitors used to investigate sub-nanosecond processes in the two transmission line plasma devices.

  14. 77 FR 74659 - Algonquin Gas Transmission; Notice of Technical Conference

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-12-17

    ... From the Federal Register Online via the Government Publishing Office ] DEPARTMENT OF ENERGY Federal Energy Regulatory Commission Algonquin Gas Transmission; Notice of Technical Conference Take... Algonquin Gas Transmission's (Algonquin) Fuel Reimbursement proceedings in Docket Nos. RP13-238-000,...

  15. 75 FR 55324 - Columbia Gas Transmission, LLC; Notice of Request Under Blanket Authorization

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-09-10

    ... designated as Line SLW-9297 and appurtenances; and (2) the Lucas Storage Well No. 10572 together with the... the application should be directed to Fredic J. George, Senior Counsel, Columbia Gas Transmission,...

  16. Heat resistant process gas line

    SciTech Connect

    Venable, C.R. Jr.

    1987-05-12

    A method is described of forming a heat resistant gas transfer line comprising a tubular metal outer shell, a tubular inner liner formed of prefired refractory rings joined together by shiplap joints having expansion gaps, and an intermediate liner comprising bubble alumina concrete filing the annular space between the inner liner and the outer shell. The method comprises placing on the inside lower surface of the outershell bubble alumina concrete forms capable of supporting the refractory rings in the desired location within the outer shell, securing decomposable rings to the refractory rings in the area where the shiplap joints are to be so that a suitable expansion gap will be provided in the shiplap joints when the combustible rings are destroyed.

  17. Trends of Environmental Technology of Overhead Transmission Line

    NASA Astrophysics Data System (ADS)

    Kubokawa, Hiroshi

    Movement toward extra high voltage and large capacity of overhead transmission line induces problems of wind noise and corona noise to the peripheral areas. Accordingly, environmental concern has become a critical issue of overhead transmission line construction. To reduce environmental impact, low noise overhead conductors have been developed. Meanwhile, as the environmental impact of transmission lines, there is a problem of corrosion due to intrusion of sea salt and acid rain to the inside of the wire. To reduce the environmental impact, corrosion-resistant conductors have been developed. This paper presents various environmental technologies applied to the site and future trends.

  18. 76 FR 36526 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-06-22

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on May 20, 2011, Columbia Gas Transmission, LLC (Columbia), filed an application pursuant to section 7(c..., Columbia Gas Transmission, LLC, P.O. Box 1273, Charleston, West Virginia 25325-1273; telephone...

  19. 75 FR 6371 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-02-09

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application February 2, 2010. Take notice that on January 20, 2010, Columbia Gas Transmission, LLC (Columbia), 5151 San Felipe, Suite 2500..., Fredric J. George, Senior Counsel, Columbia Gas Transmission, LLC, P.O. Box 1273, Charleston,...

  20. 75 FR 57012 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-09-17

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application September 9, 2010. Take notice that on August 26, 2010, Columbia Gas Transmission, LLC (Columbia), 1700 MacCorkle Avenue... Counsel, Columbia Gas Transmission, LLC, P.O. Box 1273, Charleston, West Virginia 25325-1273;...

  1. 78 FR 76603 - Enable Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-12-18

    ... Energy Regulatory Commission Enable Gas Transmission, LLC; Notice of Application Take notice that on November 26, 2013, Enable Gas Transmission, LLC (Enable) 1111 Louisiana Street, Houston, Texas 77002, filed... Gas Transmission, LLC, P.O. Box 21734 Shreveport, LA 71151 at (318) 429- 3708. Specifically,...

  2. 77 FR 3764 - Kinder Morgan Interstate Gas Transmission LLC

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-01-25

    ... Energy Regulatory Commission Kinder Morgan Interstate Gas Transmission LLC Notice of Request Under Blanket Authorization Take notice that on January 6, 2012, Kinder Morgan Interstate Gas Transmission LLC... Robert F. Harrington, Vice President, Regulatory, Kinder Morgan Interstate Gas Transmission LLC, P.O....

  3. 78 FR 33399 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-06-04

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on May 10, 2013, Columbia Gas Transmission, LLC. (Columbia) filed with the Federal Energy Regulatory..., Senior Counsel, Columbia Gas Transmission, LLC, P.O. Box 1273, Charleston, West Virginia, 25325-1273,...

  4. 78 FR 33400 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-06-04

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on May 10, 2013, Columbia Gas Transmission, LLC (Columbia) filed with the Federal Energy Regulatory..., Senior Counsel, Columbia Gas Transmission, LLC, P.O. Box 1273, Charleston, West Virginia 25325-1273,...

  5. 77 FR 66825 - Columbia Gas Transmission, LLC.; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-11-07

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC.; Notice of Application Take notice that on October 22, 2012, Columbia Gas Transmission, LLC. (Columbia) filed with the Federal Energy Regulatory... application should be directed to Michael Walker, Manager, FERC Certificates, Columbia Gas Transmission,...

  6. 78 FR 69845 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-11-21

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on November 1, 2013, Columbia Gas Transmission, LLC (Columbia), 1700 MacCorkle Avenue SE., Charleston, West... Gas Transmission, LLC, P.O. Box 1273, Charleston, West Virginia 25325-1273 or at (304) 357-2359...

  7. 76 FR 28967 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-05-19

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on May 11, 2011, Columbia Gas Transmission, LLC (Columbia), 5151 San Felipe, Suite 2500, Houston, Texas..., Columbia Gas Transmission Corporation, PO Box 1273, Charleston, West Virginia 25325 at (304) 357- 2359...

  8. 77 FR 48132 - Gas Transmission Northwest, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-08-13

    ... Energy Regulatory Commission Gas Transmission Northwest, LLC; Notice of Application Take notice that on July 31, 2012, Gas Transmission Northwest, LLC (GTN), filed in Docket No. CP12-494-000, an application... directed to Mr. Richard Parke, Manager, Certificates, Gas Transmission Northwest, LLC, 717 Texas...

  9. 75 FR 33289 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-06-11

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application June 4, 2010. Take notice that on May 28, 2010, Columbia Gas Transmission, LLC (Columbia) 5151 San Felipe, Suite 2500... should be directed to Fredric J. George, Lead Counsel, Columbia Gas Transmission Corporation, P.O....

  10. Nanostructure Sensing and Transmission of Gas Data

    NASA Technical Reports Server (NTRS)

    Li, Jing (Inventor)

    2011-01-01

    A system for receiving, analyzing and communicating results of sensing chemical and/or physical parameter values, using wireless transmission of the data. Presence or absence of one or more of a group of selected chemicals in a gas or vapor is determined, using suitably functionalized carbon nanostructures that are exposed to the gas. One or more physical parameter values, such as temperature, vapor pressure, relative humidity and distance from a reference location, are also sensed for the gas, using nanostructures and/or microstructures. All parameter values are transmitted wirelessly to a data processing site or to a control site, using an interleaving pattern for data received from different sensor groups, using I.E.E.E. 802.11 or 802.15 protocol, for example. Methods for estimating chemical concentration are discussed.

  11. Citizens, farmers fight huge transmission lines

    SciTech Connect

    Brummer, J.

    1982-02-01

    Opposition to high tension power lines with a 20-story towers is growing as coalitions of farmers and advocates of safe energy respond with legal intervention and sabotage, and sometimes with success. Examples of citizen action are the efforts opposing a 450 kilovolt direct current line connecting the US with Quebec Hydro and another opposing a 500 kilovolt alternating current line from Georgia Power Co.'s nuclear plants to Florida. The opposition derives partly from evidence of health hazards to humans and adverse effects on livestock. High voltage lines are felt to symbolize a utility and regulatory failure to assess the recent decline in power demand. It is stated that administration efforts to outlaw organized resistence will not deter the opposition, which cites instances of ground shock, aborted and stillborn cattle, physical irritants, and other phenomena. The General Assembly to Stop the Powerline (GASP) objects to the guinea pig position forced upon residents by the utilities. 6 references. (DCK)

  12. Africa planned gas lines will meet future demand

    SciTech Connect

    Not Available

    1991-11-01

    The burgeoning European market for natural gas is expected to create major gas line construction. The potential for North Africa looks particularly promising in 1991. Italy's ENI has proposed a 6,000-km (3,728-mi) gas network in North Africa to connect gas-rich Libya and Algeria with Morocco and Mauritania, making large volumes available to the European market. According to the proposal, a gas line would run from the Sirte Basin in Libya west to Mauritania. Extending the line eastward through Egypt and on to the Arabian Peninsula would provide export access. In this paper initial studies are examine reserve projections for the next 20 years, then based on results, a transmission/distribution network will be designed, including an offshore gathering system.

  13. A novel transmission line characterisation based on measurement data reconfirmation

    NASA Astrophysics Data System (ADS)

    Kim, Dongchul; Kim, Hyewon; Eo, Yungseon

    2014-04-01

    Due to inherent resonance effects and frequency-variant dielectric properties, it is very difficult to experimentally determine the stable and accurate circuit model parameters of thin film transmission line structures over a broad frequency band. In this article, a new, simple and straightforward frequency-variant transmission line circuit model parameter determination method is presented. Experimental test patterns for high-frequency transmission line characterisations are designed and fabricated using a package process. The S-parameters for the test patterns are measured using a vector network analyzer (VNA) from 100 MHz to 26.5 GHz. The parasitic effects due to contact pads are de-embedded. The frequency-variant complex permittivity and resonance-effect-free transmission line parameters (i.e., the propagation constant and characteristic impedance) are then determined in a broad frequency band.

  14. Single transmission line interrogated multiple channel data acquisition system

    DOEpatents

    Fasching, George E.; Keech, Jr., Thomas W.

    1980-01-01

    A single transmission line interrogated multiple channel data acquisition system is provided in which a plurality of remote station/sensor circuits each monitors a specific process variable and each transmits measurement values over a single transmission line to a master interrogating station when addressed by said master interrogating station. Typically, as many as 330 remote stations may be parallel connected to the transmission line which may exceed 7,000 feet. The interrogation rate is typically 330 stations/second. The master interrogating station samples each station according to a shared, charging transmit-receive cycle. All remote station address signals, all data signals from the remote stations/sensors and all power for all of the remote station/sensors are transmitted via a single continuous terminated coaxial cable. A means is provided for periodically and remotely calibrating all remote sensors for zero and span. A provision is available to remotely disconnect any selected sensor station from the main transmission line.

  15. Electrical and Biological Effects of Transmission Lines: A Review.

    SciTech Connect

    Lee, Jack M.

    1989-06-01

    This review describes the electrical properties of a-c and d-c transmission lines and the resulting effects on plants, animals, and people. Methods used by BPA to mitigate undesirable effects are also discussed. Although much of the information in this review pertains to high-voltage transmission lines, information on distribution lines and electrical appliances is included. The electrical properties discussed are electric and magnetic fields and corona: first for alternating-current (a-c) lines, then for direct current (d-c).

  16. ANALYSIS AND SIMULATION OF MAIN MAGNET TRANSMISSION LINE EFFECT

    SciTech Connect

    ZHANG,W.; MARNERIS, I.; SANDBERG, J.

    2007-06-25

    A main magnet chain forms a pair of transmission lines. Pulse-reflection-caused voltage and current differentiation throughout the magnet chain can have adverse effect on main magnet field quality. This effect is associated with magnet system configuration, coupling efficiency, and parasitic parameters. A better understanding of this phenomenon will help us in new design and existing system upgrade. In this paper, we exam the transmission line effect due to different input functions as well as configuration, coupling, and other parameters.

  17. Five Mass Power Transmission Line of a Ship Computer Modelling

    NASA Astrophysics Data System (ADS)

    Kazakoff, Alexander Borisoff; Marinov, Boycho Ivanov

    2016-03-01

    The work, presented in this paper, appears to be a natural continuation of the work presented and reported before, on the design of power transmission line of a ship, but with different multi-mass model. Some data from the previous investigations are used as a reference data, mainly from the analytical investigations, for the developed in the previ- ous study, frequency and modal analysis of a five mass model of a power transmission line of a ship. In the paper, a profound dynamic analysis of a concrete five mass dynamic model of the power transmission line of a ship is performed using Finite Element Analysis (FEA), based on the previously recommended model, investigated in the previous research and reported before. Thus, the partially validated by frequency analysis five mass model of a power transmission line of a ship is subjected to dynamic analysis. The objective of the work presented in this paper is dynamic modelling of a five mass transmission line of a ship, partial validation of the model and von Mises stress analysis calculation with the help of Finite Element Analysis (FEA) and comparison of the derived results with the analytically calculated values. The partially validated five mass power transmission line of a ship can be used for definition of many dy- namic parameters, particularly amplitude of displacement, velocity and acceleration, respectively in time and frequency domain. The frequency behaviour of the model parameters is investigated in frequency domain and it corresponds to the predicted one.

  18. 75 FR 61461 - Texas Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2010-10-05

    ... Federal Energy Regulatory Commission Texas Gas Transmission, LLC; Notice of Application September 28, 2010. Take notice that on September 22, 2010, Texas Gas Transmission, LLC (Texas Gas), 3800 Frederica Street... Act and Part 157 of the Commission's Regulations. Specifically, Texas Gas requests authorization...

  19. 78 FR 36178 - Texas Gas Transmission, LLC; Notice Of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-06-17

    ... Energy Regulatory Commission Texas Gas Transmission, LLC; Notice Of Application Take notice that on May 29, 2013, Texas Gas Transmission, LLC (Texas Gas), 9 Greenway Plaza, Suite 2800, Houston, Texas 77046... application for authorization to abandon certain mainline facilities. Texas Gas requests authority to...

  20. 78 FR 26340 - Texas Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-05-06

    ... Energy Regulatory Commission Texas Gas Transmission, LLC; Notice of Application Take notice that on April 15, 2013, Texas Gas Transmission, LLC (Texas Gas), 9 Greenway Plaza, Suite 2800, Houston, Texas 77046... Apache Corporation. Texas Gas also request authorization that the facilities, upon abandonment, will...

  1. A Generalized Lossy Transmission-Line Model for Tunable Graphene-Based Transmission Lines with Attenuation Phenomenon.

    PubMed

    Wu, Yongle; Qu, Meijun; Liu, Yuanan

    2016-01-01

    To investigate the frequency shift phenomenon by inserting graphene, a generalized lossy transmission-line model and the related electrical parameter-extraction theory are proposed in this paper. Three kinds of graphene-based transmission lines with attenuation phenomenon including microstrip line, double-side parallel strip line, and uniplanar coplanar waveguide are analyzed under the common conditions where different chemical potentials are loaded on graphene. The values of attenuation constant and phase constant, and the real and imaginary parts of the characteristic impedance of transmission lines are extracted to analyze in details. When the attenuation constant and the reactance part of the characteristic impedance are approximately equal to zero, this kind of transmission line has low or zero insertion loss. On the contrary, the transmission line is under the radiation mode with obvious insertion loss. The phase constant changes linearly under the transmission mode and can be varied with changing of chemical potentials which attributes to the property of frequency tunability. Furthermore, a bandwidth reconfigurable uniplanar coplanar waveguide power divider is simulated to demonstrate that this theory can be applied to the design of three-port devices. In summary, this work provides a strong potential approach and design theory to help design other kinds of terahertz and mid-infrared reconfigurable devices. PMID:27553759

  2. A Generalized Lossy Transmission-Line Model for Tunable Graphene-Based Transmission Lines with Attenuation Phenomenon

    PubMed Central

    Wu, Yongle; Qu, Meijun; Liu, Yuanan

    2016-01-01

    To investigate the frequency shift phenomenon by inserting graphene, a generalized lossy transmission-line model and the related electrical parameter-extraction theory are proposed in this paper. Three kinds of graphene-based transmission lines with attenuation phenomenon including microstrip line, double-side parallel strip line, and uniplanar coplanar waveguide are analyzed under the common conditions where different chemical potentials are loaded on graphene. The values of attenuation constant and phase constant, and the real and imaginary parts of the characteristic impedance of transmission lines are extracted to analyze in details. When the attenuation constant and the reactance part of the characteristic impedance are approximately equal to zero, this kind of transmission line has low or zero insertion loss. On the contrary, the transmission line is under the radiation mode with obvious insertion loss. The phase constant changes linearly under the transmission mode and can be varied with changing of chemical potentials which attributes to the property of frequency tunability. Furthermore, a bandwidth reconfigurable uniplanar coplanar waveguide power divider is simulated to demonstrate that this theory can be applied to the design of three-port devices. In summary, this work provides a strong potential approach and design theory to help design other kinds of terahertz and mid-infrared reconfigurable devices. PMID:27553759

  3. Tailoring of electron flow current in magnetically insulated transmission lines

    NASA Astrophysics Data System (ADS)

    Martin, J. P.; Savage, M. E.; Pointon, T. D.; Gilmore, M. A.

    2009-03-01

    It is desirable to optimize (minimizing both the inductance and electron flow) the magnetically insulated vacuum sections of low impedance pulsed-power drivers. The goal of low inductance is understandable from basic efficiency arguments. The goal of low electron flow results from two observations: (1) flowing electrons generally do not deliver energy to (or even reach) most loads, and thus constitute a loss mechanism; (2) energetic electrons deposited in a small area can cause anode damage and anode plasma formation. Low inductance and low electron flow are competing goals; an optimized system requires a balance of the two. While magnetically insulated systems are generally forgiving, there are times when optimization is crucial. For example, in large pulsed-power drivers used to energize high energy density physics loads, the electron flow as a fraction of total current is small, but that flow often reaches the anode in relatively small regions. If the anode temperature becomes high enough to desorb gas, the resulting plasma initiates a gap closure process that can impact system performance. Magnetic-pressure driven (z pinches and material equation of state) loads behave like a fixed inductor for much of the drive pulse. It is clear that neither fixed gap nor constant-impedance transmission lines are optimal for driving inductive loads. This work shows a technique for developing the optimal impedance profile for the magnetically insulated section of a high-current driver. Particle-in-cell calculations are used to validate the impedance profiles developed in a radial disk magnetically insulated transmission line geometry. The input parameters are the spacing and location of the minimum gap, the effective load inductance, and the desired electron flow profile. The radial electron flow profiles from these simulations are in good agreement with theoretical predictions when driven at relatively high voltage (i.e., V≥2MV).

  4. Flexible gas insulated cable for high power transmission

    NASA Astrophysics Data System (ADS)

    Artbauer, J.; Renftel, W.

    1982-07-01

    The dielectric losses which increase as the square of voltage and limit power transmission capacity of paper/oil impregnated isolated cables were studied. This limitation disappears by using gas insulation. Tube transmission lines isolated with SF6 gas were developed. Their conception was paired with a lot of inconveniences: short length, numerous connections, special curved sections and necessity of dilation joints. A test cable was fabricated from Al wire conductors, epoxy resin spacer insulators, and an external sheath of 3 mm thick Al-Mn alloy strip. A special high tension testing device was also constructed. The development of such a cable for 220 kV and of its components involved electric field computations, electrical, mechanical, and thermal measurements, elaboration of test and calculation methods, manufacture and testing of cable samples. Tests show that the transmission capacity of the cable in air surpasses 1000 MVA. Due to the limits set by the sheath diameter and the gas pressure, the 380 kV level cannot be attained with the design.

  5. Experimental Analysis of Reduced-Sized Coplanar Waveguide Transmission Lines

    NASA Technical Reports Server (NTRS)

    Ponchak, George E.

    2002-01-01

    An experimental investigation of the use of capacitive loading of coplanar waveguides to reduce their line length and, thus the size, of monolithic microwave integrated circuits is presented. The reduced sized coplanar waveguides are compared to unloaded transmission lines and to lumped element transmission line segments. The phase bandwidth, defined by 2 percent error in S(sub 21), and the return loss bandwidth, defined by a return loss greater than 15 dB, of coplanar waveguides reduced from 0 to 90 percent are compared, and the insertion loss as a function of the size reduction is presented.

  6. Stand-off transmission lines and method for making same

    DOEpatents

    Tuckerman, David B.

    1991-01-01

    Standoff transmission lines in an integrated circuit structure are formed by etching away or removing the portion of the dielectric layer separating the microstrip metal lines and the ground plane from the regions that are not under the lines. The microstrip lines can be fabricated by a subtractive process of etching a metal layer, an additive process of direct laser writing fine lines followed by plating up the lines or a subtractive/additive process in which a trench is etched over a nucleation layer and the wire is electrolytically deposited. Microstrip lines supported on freestanding posts of dielectric material surrounded by air gaps are produced. The average dielectric constant between the lines and ground plane is reduced, resulting in higher characteristic impedance, less crosstalk between lines, increased signal propagation velocities, and reduced wafer stress.

  7. NOVEL SIGNAL PROCESSING WITH NONLINEAR TRANSMISSION LINES

    SciTech Connect

    D. REAGOR; ET AL

    2000-08-01

    Nonlinear dielectrics offer uniquely strong and tunable nonlinearities that make them attractive for current devices (for example, frequency-agile microwave filters) and for future signal-processing technologies. The goal of this project is to understand pulse propagation on nonlinear coplanar waveguide prototype devices. We have performed time-domain and frequency-domain experimental studies of simple waveguide structures and pursued a theoretical understanding of the propagation of signals on these nonlinear waveguides. To realistically assess the potential applications, we used a time-domain measurement and analysis technique developed during this project to perform a broadband electrodynamics characterization in terms of nonlinear, dispersive, and dissipative effects. We completed a comprehensive study of coplanar waveguides made from high-temperature superconducting thin-film YBa{sub 2}Cu{sub 3}O{sub 7{minus}{delta}} electrodes on nonlinear dielectric single-crystal SrTiO{sub 3} substrates. By using parameters determined from small-signal (linear) transmission characteristics of the waveguides, we develop a model equation that successfully predicts and describes large-signal (nonlinear) behavior.

  8. Electric transmission line flashover prediction system

    NASA Astrophysics Data System (ADS)

    Amarh, Felix

    Near industrial, agricultural, or coastal areas, contamination is a frequent cause of insulator flashover, most cases of which result in lengthy service interruptions. Utilities spend significant amounts of money on insulator washing and cleaning before the restoration of the service. Laboratory studies and industrial experience have shown that both contamination and wetting of insulator surfaces, which initiate the flow of leakage current, are required for insulator flashover. The leakage current leading to flashover has distinctive stages of development. Flashover is preceded by dry-band arcing and extension of the arc to bridge the insulator. This combination significantly modifies both the magnitude and shape of the leakage current. A condition-based monitoring (CBM) system that monitors the easily measurable insulator leakage current as a means of assessing pollution severity and would possibly predict an approaching flashover could prove beneficial to utilities. The overall aim of this project is the development of a system that monitors pollution build-up through the signature changes in the leakage current and alerts an operator when there is a danger of flashover. The operator can, in turn, order maintenance personnel to wash the insulators. This will safeguard against unforeseen flashovers, since the system is constantly being monitored and diagnosed. Additionally, the washing cycles of insulators will be optimized, saving money and eventually rendering the power transmission system more reliable.

  9. 78 FR 25068 - Columbia Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-04-29

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Application Take notice that on April 5, 2013, Columbia Gas Transmission, LLC (Columbia), 5151 San Felipe, Suite 2500, Houston, Texas... 12.6 miles of 8-inch diameter looping pipeline connected to its existing transmission system...

  10. Effect of asphaltene deposition on the internal corrosion in transmission lines

    SciTech Connect

    Morales, J.L.; Viloria, A.; Palacios T, C.A.

    1996-12-31

    Crude oil from Norte de Monagas field, in Venezuela, contains large amounts of asphaltenes, some of them are very unstable with tendency to precipitate. Because liquid is carried over from the separation process in the flow stations, asphaltenes are also present in the gas gathering and transmission lines, precipitating on inner wall of pipelines. The gas gathering and transmission lines contain gas with high partial pressures of CO{sub 2}, some H{sub 2}S and are water saturated; therefore inhibitors are used to control the internal corrosion. There is uncertainty on how inhibitors perform in the presence of asphaltene deposition. To protect the pipelines from external corrosion, cathodic protection is used. Since asphaltenes have polar properties, there exists an uncertainty on whether it enhances asphaltene precipitation and deposition. The purpose of this paper to describe the causes that enhance asphaltene deposition on gas and some of the preliminary result from an ongoing research project carried out by Intevep and Corpoven.

  11. Transmission line component testing for the ITER Ion Cyclotron Heating and Current Drive System

    NASA Astrophysics Data System (ADS)

    Goulding, Richard; Bell, G. L.; Deibele, C. E.; McCarthy, M. P.; Rasmussen, D. A.; Swain, D. W.; Barber, G. C.; Barbier, C. N.; Cambell, I. H.; Moon, R. L.; Pesavento, P. V.; Fredd, E.; Greenough, N.; Kung, C.

    2014-10-01

    High power RF testing is underway to evaluate transmission line components for the ITER Ion Cyclotron Heating and Current Drive System. The transmission line has a characteristic impedance Z0 = 50 Ω and a nominal outer diameter of 305 mm. It is specified to carry up to 6 MW at VSWR = 1.5 for 3600 s pulses, with transient voltages up to 40 kV. The transmission line is actively cooled, with turbulent gas flow (N2) used to transfer heat from the inner to outer conductor, which is water cooled. High voltage and high current testing of components has been performed using resonant lines generating steady state voltages of 35 kV and transient voltages up to 60 kV. A resonant ring, which has operated with circulating power of 6 MW for 1 hr pulses, is being used to test high power, low VSWR operation. Components tested to date include gas barriers, straight sections of various lengths, and 90 degree elbows. Designs tested include gas barriers fabricated from quartz and aluminum nitride, and transmission lines with quartz and alumina inner conductor supports. The latest results will be presented. This manuscript has been authored by UT-Battelle, LLC, under Contract No. DE-AC05-00OR22725 with the U.S. Department of Energy.

  12. Atlas Transmission Line/Transition Design and Fabrication Status

    SciTech Connect

    Ballard, E.O.; Baca, D.M.; Davis, H.A.; Elizondo, J.M.; Gribble, R.F.; Nielsen, K.E.; Parker, G.V.; Ricketts, R.L.; Valdez, G.

    1999-06-27

    Atlas is a pulsed-power facility under development at Los Alamos National Laboratory to drive high-energy density experiments. Design has been completed for this new generation pulsed-power machine consisting of an azimuthal array of 24, 240-kV Marx modules and transmission lines supplying current to the load region at the machine center. The transmission line consists of a cable header, load protection switch, and tri-plate assembly interfacing to the center transition section. The cable header interface to the Marx module provides a mechanism to remove the Marx module for maintenance without removing other components of the transmission line. The load protection switch provides a mechanism for protecting the load during charging of the Marx in the event of a pre-fire condition. The aluminum tri-plate is a low-inductance transmission line carries radial current flow from the Marx energy storage system at the machine periphery toward the load. All transmission line components are oil insulated except the solid-dielectric insulated power flow channel connected directly to the load. The transition region at the machine center consists of several components that enable the radial converging vertical transmission lines to interface to a horizontal disk/conical power flow channel delivering current to the load. The current carrying transition components include the high-voltage and ground conductors interfacing to the tri-plate transmission lines. The tri-plate tank attachment ring interfaces to the tri-plate tanks and the base-plate. The base-plate supports the transition components and interfaces to the center support structure of the machine. The bottom insulator also attaches to the base-plate and to the high-voltage conductor, providing an oil containment seal between the transition and vacuum vessel. Design has been completed for all Atlas components. Some prototype hardware fabrication has been completed and first article hardware is in various stages of

  13. Residential proximity to high voltage transmission lines and depressive symptomatology

    SciTech Connect

    McMahan, S.G.

    1992-01-01

    A number of epidemiological studies indicate an association between depression and proximity to high voltage transmission lines. These studies have been criticized, however, for using surrogate measures of electromagnetic fields (EMFs) and unstandardized measures of depression. In an effort to overcome these limitations, the Center for Epidemiological Studies Depression (CES-D) scale was administered to 152 women living either adjacent to a transmission line or one block away. Results indicate that homes adjacent to the transmission lines have an average EMF level of 4.86 milligauss at their front door and those one block away have an average of 0.68 milligauss. There was no significant difference in CES-D scores between the groups, controlling for demographic variables. There appeared to be an increase in other health effects, including cancer and miscarriages, but these findings were preliminary and need further investigation.

  14. Artificial neural network modeling of plasmonic transmission lines.

    PubMed

    Andrawis, Robert R; Swillam, Mohamed A; El-Gamal, Mohamed A; Soliman, Ezzeldin A

    2016-04-01

    In this paper, new models based on an artificial neural network (ANN) are developed to predict the propagation characteristics of plasmonic nanostrip and coupled nanostrips transmission lines. The trained ANNs are capable of providing the required propagation characteristics with good accuracy and almost instantaneously. The nonlinear mapping performed by the trained ANNs is written as closed-form expressions, which facilitate the direct use of the results obtained in this research. The propagation characteristics of the investigated transmission lines include the effective refractive index and the characteristic impedance. The time needed to simulate 1000 different versions of the transmission line structure is about 48 h, using a full-wave electromagnetic solver compared to 3 s using the developed ANN model. PMID:27139685

  15. Quasi-Optical Transmission Line for 94-GHz Radar

    NASA Technical Reports Server (NTRS)

    Perez, Raul M.; Veruttipong, Watt

    2008-01-01

    A quasi-optical transmission line (QOTL) has been developed as a low-loss transmission line for a spaceborne cloudobserving radar instrument that operates at a nominal frequency of 94 GHz. This QOTL could also readily be redesigned for use in terrestrial millimeter-wave radar systems and millimeter-wave imaging systems. In the absence of this or another lowloss transmission line, it would be necessary to use a waveguide transmission line in the original radar application. Unfortunately, transmission losses increase and power-handling capacities of waveguides generally decrease with frequency, such that at 94 GHz, the limitation on transmitting power and the combined transmission and reception losses (greater than 5 dB) in a waveguide transmission line previously considered for the original application would be unacceptable. The QOTL functions as a very-lowloss, three-port circulator. The QOTL includes a shaped input mirror that can be rotated to accept 94-GHz transmitter power from either of two high-power amplifiers. Inside the QOTL, the transmitter power takes the form of a linearly polarized beam radiated from a feed horn. This beam propagates through a system of mirrors, each of which refocuses the beam to minimize diffraction losses. A magnetically biased ferrite disc is placed at one of the foci to utilize the Faraday effect to rotate the polarization of the beam by 45 degrees. The beam is then transmitted via an antenna system. The radar return (scatter from clouds, and/or reflections from other objects) is collected by the same antenna and propagates through the Faraday rotator in the reverse of the direction of propagation of the transmitted beam. In the Faraday rotator, the polarization of the received signal is rotated a further 45 degrees, so that upon emerging from the Faraday rotator, the received beam is polarized at 90 with respect to the transmitted beam. The transmitted and received signals are then separated by a wire-grid polarizer.

  16. Gates to Gregg High Voltage Transmission Line Study. [California

    NASA Technical Reports Server (NTRS)

    Bergis, V.; Maw, K.; Newland, W.; Sinnott, D.; Thornbury, G.; Easterwood, P.; Bonderud, J.

    1982-01-01

    The usefulness of LANDSAT data in the planning of transmission line routes was assessed. LANDSAT digital data and image processing techniques, specifically a multi-date supervised classification aproach, were used to develop a land cover map for an agricultural area near Fresno, California. Twenty-six land cover classes were identified, of which twenty classes were agricultural crops. High classification accuracies (greater than 80%) were attained for several classes, including cotton, grain, and vineyards. The primary products generated were 1:24,000, 1:100,000 and 1:250,000 scale maps of the classification and acreage summaries for all land cover classes within four alternate transmission line routes.

  17. Self-monitoring high voltage transmission line suspension insulator

    DOEpatents

    Stemler, Gary E.; Scott, Donald N.

    1981-01-01

    A high voltage transmission line suspension insulator (18 or 22) which monitors its own dielectric integrity. A dielectric rod (10) has one larger diameter end fitting attachable to a transmission line and another larger diameter end fitting attachable to a support tower. The rod is enclosed in a dielectric tube (14) which is hermetically sealed to the rod's end fittings such that a liquidtight space (20) is formed between the rod and the tube. A pressurized dielectric liquid is placed within that space. A discoloring dye placed within this space is used to detect the loss of the pressurized liquid.

  18. Reconfigurable Wave Velocity Transmission Lines for Phased Arrays

    NASA Technical Reports Server (NTRS)

    Host, Nick; Chen, Chi-Chih; Volakis, John L.; Miranda, Felix

    2013-01-01

    Phased array antennas showcase many advantages over mechanically steered systems. However, they are also more complex, heavy and most importantly costly. This presentation paper presents a concept which overcomes these detrimental attributes by eliminating all of the phase array backend (including phase shifters). Instead, a wave velocity reconfigurable transmission line is used in a series fed array arrangement to allow phase shifting with one small (100mil) mechanical motion. Different configurations of the reconfigurable wave velocity transmission line are discussed and simulated and experimental results are presented.

  19. Prototype uhv compressed-gas-insulated transmission system

    NASA Astrophysics Data System (ADS)

    1982-02-01

    Development, manufacture, testing and installation of a 1200 kV compressed gas insulated transmission line (CGIT) and an SF6-air bushing are reported. Gas insulation studies of SF6 and mixtures with nitrogen, air or carbon dioxide were conducted. Pure SF6 at .45 MPa (50 psig) was selected for use in the prototype. Various materials and construction alternatives for the enclosure and conductor were investigated. Aluminum was chosen for both the enclosure and conductor. These provide the 5000 A 75% load factor thermal rating under standard burial and grounding conditions. Effects of alternate burial, grounding and bonding conditions are reported. For the solid support insulators low dielectric constant materials and epoxy were studied. An arc resistant epoxy formulation was developed and used for both conical and Tripost insulators. A high performance plug in contact for conductor joints was developed. Two versions of an SF6-air bushing were built and tested.

  20. Inductive gas line for pulsed lasers

    DOEpatents

    Benett, William J.; Alger, Terry W.

    1985-01-01

    A gas laser having a metal inlet gas feed line assembly shaped as a coil, to function as an electrical inductance and therefore high impedance to pulses of electric current applied to electrodes at opposite ends of a discharge tube of a laser, for example. This eliminates a discharge path for the laser through the inlet gas feed line. A ferrite core extends through the coil to increase the inductance of the coil and provide better electric isolation. By elimination of any discharge breakdown through the gas supply, efficiency is increased and a significantly longer operating lifetime of the laser is provided.

  1. Inductive gas line for pulsed lasers

    DOEpatents

    Benett, W.J.; Alger, T.W.

    1982-09-29

    A gas laser having a metal inlet gas feed line assembly shaped as a coil, to function as an electrical inductance and therefore high impedance to pulses of electric current applied to electrodes at opposite ends of a discharge tube of a laser, for example. This eliminates a discharge path for the laser through the inlet gas feed line. A ferrite core extends through the coil to increase the inductance of the coil and provide better electric isolation. By elimination of any discharge breakdown through the gas supply, efficiency is increased and a significantly longer operating lifetime of the laser is provided.

  2. Line competition in gas lasers

    SciTech Connect

    Pikulev, A A

    2000-08-31

    Simultaneous lasing on two lines having a common upper level is analysed. Within the framework of the two-level model, a formula for the gain in each line is obtained. Two possible types of line competition are found: symbiosis and quenching. It is shown that competition in the quenching regime can be used to study the rates of population of the lower levels. The results are illustrated by competition diagrams for the 2.65-{mu}m and 2.03-{mu}m of the Xe atom in the Ar-Xe mixture and the 703.2-nm and 724.5-nm lines of the Ne atom in the Ne-Ar mixture. (active media)

  3. Transmission Lines: An Overview of Electrical Properties and Environmental Effects.

    SciTech Connect

    United States. Bonneville Power Administration. Biological Studies Task Team.

    1982-03-01

    A brief overview is provided of environmental and biological effects of high-voltage power transmission lines. Paragraph length descriptions of electric fields, induced voltage and currents, biological effects, magnetic fields, corona, radio and television interference, and ozone are given. 13 figs.

  4. 77 FR 35366 - Albany-Eugene Transmission Line Rebuild Project

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-06-13

    ... Administration (BPA), Department of Energy (DOE). ACTION: Notice of Availability of Record of Decision (ROD..., based on the Albany-Eugene Transmission Line Rebuild Project (DOE/EIS-0457, March 2012). BPA has decided... will continue to operate at 115 kV. ADDRESSES: Copies of the ROD and EIS may be obtained by calling...

  5. Flow Impedance in a Uniform Magnetically-Insulated Transmission Line

    SciTech Connect

    Mendel, C.W.

    1999-03-23

    In two recent publications relativistic electron flow in cylindrical magnetically-insulated transmission lines (MITL) was analyzed and modeled under the assumption of negligible electron pressure. Cylindrical MITLs were used because of their common occurrence, and because they are the simplest case of finite width. The authors show in this report that the models apply equally to MITLs of any cross section.

  6. HIGH FREQUENCY POWER TRANSMISSION LINE FOR CYCLOTRONS AND THE LIKE

    DOEpatents

    Armstrong, W.J.

    1954-04-20

    High-frequency power transmission systems, particularly a stacked capacitance alternating power current transmission line wherein maximum utilization of the effective conductios skin of the line conductors is achieved while enabling a low impedance to be obtained are reported. The transmission line consists of a number of flat metal strips with interleaved dielectric strips. The metal dielectric strips are coiled spirally with the axis of the spiral extending along the length of the strips, and the alternating metal strips at the output end have outwardly extending aligned lugs which are directly strapped together and connected to the respective terminals on the load. At the input end of the transmission line, similarly, the alternate metal strips are directly strapped together and connected to an altereating current source. With the arrangement described each metal strip conducts on both sides, so that the metal strips are designed to have a thickness corresponding to twice the depth of the "skin effect" conducting lamina of each conductor at the source frequency.

  7. Airplane Ice Detector Based on a Microwave Transmission Line

    NASA Technical Reports Server (NTRS)

    Ngo, Phong; Arndt, G. Dickey; Carl, James R.

    2004-01-01

    An electronic instrument that could detect the potentially dangerous buildup of ice on an airplane wing is undergoing development. The instrument is based on a microwave transmission line configured as a capacitance probe: at selected spots, the transmission-line conductors are partly exposed to allow any ice and/or liquid water present at those spots to act as predominantly capacitive electrical loads on the transmission line. These loads change the input impedance of the transmission line, as measured at a suitable excitation frequency. Thus, it should be possible to infer the presence of ice and/or liquid water from measurements of the input impedance and/or electrical parameters related to the input impedance. The sensory transmission line is of the microstrip type and thus thin enough to be placed on an airplane wing without unduly disturbing airflow in flight. The sensory spots are small areas from which the upper layer of the microstrip has been removed to allow any liquid water or ice on the surface to reach the transmission line. The sensory spots are spaced at nominal open-circuit points, which are at intervals of a half wavelength (in the transmission line, not in air) at the excitation frequency. The excitation frequency used in the experiments has been 1 GHz, for which a half wavelength in the transmission line is .4 in. (.10 cm). The figure depicts a laboratory prototype of the instrument. The impedance-related quantities chosen for use in this version of the instrument are the magnitude and phase of the scattering parameter S11 as manifested in the in-phase (I ) and quadrature (Q) outputs of the phase detector. By careful layout of the transmission line (including the half-wavelength sensor spacing), one can ensure that the amplitude and phase of the input to the phase detector keep shifting in the same direction as ice forms on one or more of the sensor areas. Although only one transmission-line sensor strip is used in the laboratory version, in a

  8. Sliding backshorts for planar circuits. [strip transmission line tuning

    NASA Technical Reports Server (NTRS)

    Lubecke, Victor M.; Rutledge, David B.; Mcgrath, William R.

    1991-01-01

    An adjustable planar imbedding circuit based on coplanar transmission lines is presented to deal with the impedance mismatch associated with the use of the Superconductor-Insulator-Superconductor tunnel junction. The planar embedding circuit is developed with movable noncontacting shorting elements that consist of thin metallic plates with optimized arrangements of rectangular holes. The rectangular holes are placed along the insulated metallic transmission line to provide a periodic variation of the line impedance. A large reflection coefficient is demonstrated with a scale model of the sliding backshort, and values of more than -0.5 dB are reported. The shorting elements are incorporated into a low-frequency tuning circuit to test the practical tuning ranges. The backshort can be used to fashion tuning stubs with variable post-fabrication electrical lengths which relaxes the design constraints of planar integrated circuits.

  9. 77 FR 58371 - Discovery Gas Transmission LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-09-20

    ... From the Federal Register Online via the Government Publishing Office DEPARTMENT OF ENERGY Federal Energy Regulatory Commission Discovery Gas Transmission LLC; Notice of Application Take notice that on September 7, 2012, Discovery Gas Transmission LLC (Discovery), 2800 Post Oak Boulevard, Houston, Texas...

  10. Modeling the axial extension of a transmission line source within iterative reconstruction via multiple transmission sources.

    PubMed

    Bowsher, J E; Tornai, M P; Peter, J; González Trotter, D E; Krol, A; Gilland, D R; Jaszczak, R J

    2002-03-01

    Reconstruction algorithms for transmission tomography have generally assumed that the photons reaching a particular detector bin at a particular angle originate from a single point source. In this paper, we highlight several cases of extended transmission sources, in which it may be useful to approach the estimation of attenuation coefficients as a problem involving multiple transmission point sources. Examined in detail is the case of a fixed transmission line source with a fan-beam collimator. This geometry can result in attenuation images that have significant axial blur. Herein it is also shown, empirically, that extended transmission sources can result in biased estimates of the average attenuation, and an explanation is proposed. The finite axial resolution of the transmission line source configuration is modeled within iterative reconstruction using an expectation-maximization algorithm that was previously derived for estimating attenuation coefficients from single photon emission computed tomography (SPECT) emission data. The same algorithm is applicable to both problems because both can be thought of as involving multiple transmission sources. It is shown that modeling axial blur within reconstruction removes the bias in the average estimated attenuation and substantially improves the axial resolution of attenuation images. PMID:11989845

  11. Wireless Sensor Network for Electric Transmission Line Monitoring

    SciTech Connect

    Alphenaar, Bruce

    2009-06-30

    Generally, federal agencies tasked to oversee power grid reliability are dependent on data from grid infrastructure owners and operators in order to obtain a basic level of situational awareness. Since there are many owners and operators involved in the day-to-day functioning of the power grid, the task of accessing, aggregating and analyzing grid information from these sources is not a trivial one. Seemingly basic tasks such as synchronizing data timestamps between many different data providers and sources can be difficult as evidenced during the post-event analysis of the August 2003 blackout. In this project we investigate the efficacy and cost effectiveness of deploying a network of wireless power line monitoring devices as a method of independently monitoring key parts of the power grid as a complement to the data which is currently available to federal agencies from grid system operators. Such a network is modeled on proprietary power line monitoring technologies and networks invented, developed and deployed by Genscape, a Louisville, Kentucky based real-time energy information provider. Genscape measures transmission line power flow using measurements of electromagnetic fields under overhead high voltage transmission power lines in the United States and Europe. Opportunities for optimization of the commercial power line monitoring technology were investigated in this project to enable lower power consumption, lower cost and improvements to measurement methodologies. These optimizations were performed in order to better enable the use of wireless transmission line monitors in large network deployments (perhaps covering several thousand power lines) for federal situational awareness needs. Power consumption and cost reduction were addressed by developing a power line monitor using a low power, low cost wireless telemetry platform known as the ''Mote''. Motes were first developed as smart sensor nodes in wireless mesh networking applications. On such a platform

  12. 77 FR 26534 - Northern Natural Gas Company, Florida Gas Transmission Company, LLC, Transcontinental Gas Pipe...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-05-04

    ..., Transcontinental Gas Pipe Line Company, LLC, Enterprise Field Services, LLC; Notice of Application Take notice that..., Transcontinental Gas Pipe Line Company, LLC, and Enterprise Field Services, LLC, filed an application in Docket No... Matagorda Island Areas in Federal offshore waters of Texas (MOPS Phase III Facilities). Any...

  13. Beam coupling impedances of fast transmission-line kickers.

    SciTech Connect

    Kurennoy, S.

    2002-01-01

    Fast transmission-line kickers contain no ferrite and consist of two long metallic parallel plates supported by insulators inside a beam pipe. A beam is deflected by both the electric and magnetic fields of a TEM wave created by a pulse propagating along the strips in the direction opposite to the beam. Computations of the beam coupling impedances for such structures are difficult because of their length. In the paper, the beam coupling impedances of transmission-line kickers are calculated by combining analytical and numerical methods: the wake potentials computed in short models are extended analytically to obtain the wakes for the long kickers, and then the corresponding beam impedances are derived. At very low frequencies the results are compared with simple analytical expressions for the coupling impedances of striplines in beam position monitors.

  14. Comparison of Transmission Line Methods for Surface Acoustic Wave Modeling

    NASA Technical Reports Server (NTRS)

    Wilson, William; Atkinson, Gary

    2009-01-01

    Surface Acoustic Wave (SAW) technology is low cost, rugged, lightweight, extremely low power and can be used to develop passive wireless sensors. For these reasons, NASA is investigating the use of SAW technology for Integrated Vehicle Health Monitoring (IVHM) of aerospace structures. To facilitate rapid prototyping of passive SAW sensors for aerospace applications, SAW models have been developed. This paper reports on the comparison of three methods of modeling SAWs. The three models are the Impulse Response Method (a first order model), and two second order matrix methods; the conventional matrix approach, and a modified matrix approach that is extended to include internal finger reflections. The second order models are based upon matrices that were originally developed for analyzing microwave circuits using transmission line theory. Results from the models are presented with measured data from devices. Keywords: Surface Acoustic Wave, SAW, transmission line models, Impulse Response Method.

  15. HTS DC Transmission Line for Megalopolis Grid Development

    NASA Astrophysics Data System (ADS)

    Kopylov, S.; Sytnikov, V.; Bemert, S.; Ivanov, Yu; Krivetskiy, I.; Romashov, M.; Shakaryan, Yu; Keilin, V.; Shikov, A.; Patrikeev, V.; Lobyntsev, V.; Shcherbakov, V.

    2014-05-01

    Using of HTS AC and DC cables in electric power grids allows increasing of the transferred power, losses diminishing, decreasing of exclusion zone areas, the enhancement of the environmental conditions and fire/explosion safety of electric power systems. However, the use of DC superconducting cable lines together with converters brings additional advantages as reduction of losses in cables and suitable lowering of refrigerating plant capacity, as well as the realization of the function of short-circuit currents limitation by means of the appropriate setting of converter equipment. Russian Federal Grid Company and its R&D Center started the construction of the DC HTS power transmission line which includes the cable itself, cryogenic equipment, AC/DC converters, terminals and cable coupling boxes. This line will connect two substations in Saint-Petersburg - 330 kV "Centralnaya" and 220 kV "RP-9". The length of this HTS transmission line will be about 2500 meters. Nowadays are developed all the elements of the line and technologies of the cable manufacturing. Two HTS cable samples, each 30 m length, have been made. This paper describes the results of cables tests.

  16. Flow impedance in a uniform magnetically insulated transmission line

    NASA Astrophysics Data System (ADS)

    Mendel, C. W.; Seidel, D. B.

    1999-12-01

    In two recent publications [C. W. Mendel, Jr. and S. E. Rosenthal, Phys. of Plasmas 2, 1332 (1995), C. W. Mendel, Jr. and S. E. Rosenthal, Phys. of Plasmas 3, 4207 (1996)] relativistic electron flow in cylindrical magnetically insulated transmission lines was analyzed and modeled under the assumption of negligible electron pressure. The model allows power flow in these lines to be accurately calculated under most conditions. The model was developed for coaxial right circular cylindrical electrodes. It is shown here that the model applies equally well to arbitrary cylindrical systems, i.e., systems consisting of electrodes of arbitrary cross section.

  17. Flow impedance in a uniform magnetically insulated transmission line

    SciTech Connect

    Mendel, C.W. Jr.; Seidel, D.B.

    1999-12-01

    In two recent publications [C. W. Mendel, Jr. and S. E. Rosenthal, Phys. of Plasmas {bold 2}, 1332 (1995), C. W. Mendel, Jr. and S. E. Rosenthal, Phys. of Plasmas {bold 3}, 4207 (1996)] relativistic electron flow in cylindrical magnetically insulated transmission lines was analyzed and modeled under the assumption of negligible electron pressure. The model allows power flow in these lines to be accurately calculated under most conditions. The model was developed for coaxial right circular cylindrical electrodes. It is shown here that the model applies equally well to arbitrary cylindrical systems, i.e., systems consisting of electrodes of arbitrary cross section. {copyright} {ital 1999 American Institute of Physics.}

  18. Reconfigurable Wave Velocity Transmission Lines for Phased Arrays

    NASA Technical Reports Server (NTRS)

    Host, Nicholas Keith; Chen, Chi-Chih; Volakis, John L.

    2012-01-01

    This presentation discussed a novel phased array with an emphasis to simplify the array feed. Specifically, we will demonstrate a simple, low cost feeding approach by mechanically controlling the substrate thickness. The array feed lines are constructed from parallel plate transmission lines whose thickness are adjusted to control their effective dielectric constant (Epsilon_eff). As a result the phase delay/excitation at each array element will be adjusted per desired beam direction. The proposed antenna elements will be overlapping dipoles operating over a 2:1 bandwidth in the Ku-Band spectrum. Preliminary simulation and experimental demonstration of such an array will be presented.

  19. Nonlinear waves propagating in the electrical transmission line

    NASA Astrophysics Data System (ADS)

    Duan, W.-S.

    2004-04-01

    A coupled Zakharov-Kuznetsov (ZK) equation is derived for a nonlinear transmission line in which the nonlinear capacitance C is of a general form C = C0(1 + k1V + k2V2 + ...). For a solitary-wave solution of the ZK equation, there is an instability region which is given numerically in this paper. It is in agreement with the analytical results for special cases.

  20. Parameters of lossless transmission lines with spherical T-waves

    NASA Astrophysics Data System (ADS)

    Kniaz, A. I.; Draganov, V. M.

    1983-04-01

    The analogy between plane-parallel and spherical-parallel fields is used to derive a unified formula for the parameters (capacitance and wave resistance) of a cylindrical system of conductors with a plane transverse wave and of a system of conical conductors with a spherical transverse wave. This makes it possible to transform previously developed formulas into formulas for determining the parameters of lossless transmission lines with spherical transverse waves. Some examples of the application of the proposed approach are considered.

  1. Gas Research Institute's research and development program on in-line inspection of natural gas pipelines

    NASA Astrophysics Data System (ADS)

    Haines, Harvey H.; Bubenik, Tom A.; Nestleroth, J. Bruce

    1995-05-01

    The Gas Research Institute (GRI) has been supporting a comprehensive research and development program on in-line inspection techniques for natural gas transmission pipelines. This program contains assessments of state-of-the-art nondestructive evaluation methods, improvements in current approaches, and developments of advanced inspection technologies. The elements of the GRI Nondestructive Evaluation Program range from laboratory evaluations of the capabilities of inspection technologies to large-scale measurements in simulated pipeline settings. Each level of research stresses a quantification of both the limits of detection and the accuracy of characterization of pipeline imperfections that are found by in- line inspection tools. The overall goal of GRI's Nondestructive Evaluation Program is to develop and improve technologies that will help gas pipeline companies maintain the physical integrity of their transmission systems, prevent pipeline shutdowns, and reduce maintenance costs. This paper summarizes the results of the GRI program to date in relationship to their direct application to in-line inspection of gas transmission pipelines. The program consists of three main elements: facilities development, research on current inspection technologies, and research on future inspection technologies. The facilities development is centered around the Pipeline Simulation Facility; the research on current inspection technologies is aimed at improving magnetic flux leakage analyses; and the research on future inspection technologies is centered on stress-corrosion crack detection and characterization.

  2. Mitigation of bird collisions with transmission lines: Final report

    SciTech Connect

    Beaulaurier, D.L.

    1981-09-11

    In this study removal of overhead groundwires was evaluated as a technique for mitigating bird collisions with transmission lines. Groundwires were removed by BPA from a 500 kV double circuit line at Bybee Lake in Portland, Oregon. Earlier studies at these sites had documented small but measurable collision rates (i.e., No. collisions/No. flights) attributed primarily to collisions with groundwires. Observations of bird flights and searches for dead birds in the vicinity of the lines constituted the primary methods of data collection during pre- and post-removal studies. Field work was conducted from October 1980 through March 1981. A total of seven dead birds and eight feather spots were found after groundwire removal. Species found were green-winged teal, pintail, greater scaup, American wigeon, glaucous-winged gull, starling, red-winged blackbird and song sparrow. No collisions with transmission lines were observed. During pre-removal studies at these two sites, a total of 53 dead birds and 22 feather spots were found over two years of study. It was necessary to document flight intensity (No. flights/day) during pre- and post-removal studies, in order to determine if the number of dead birds found changed because of groundwire removal or simply because of changes in flight intensity. 41 refs., 18 figs., 22 tabs.

  3. Dynamic modeling of magnetically insulated transmission line systems

    SciTech Connect

    Mendel, C.W. Jr.; Rosenthal, S.E.

    1996-11-01

    Negative conductors in vacuum transmission lines used in multiterrawatt applications emit electrons freely. These lines are efficient only because the self-magnetic field of the power flow forces the electrons to flow parallel to the electrodes. Excepting numerical simulations, dynamic modeling of systems of these transmission lines has generally either ignored electron flow, or has included only those electrons that cross immediately to the anode at the front of the forward wave. In this paper we describe an analytic model that includes flowing electrons and the effects of these flows on line voltage and on the reduction of magnetic flux. Axial electron currents are modeled using simple, measurable, and calculable parameters. Transverse electron currents are modeled using general patterns found empirically from simulation data. These currents are in turn related by an expanded set of Telegrapher equations. An example of the use of the model is compared to two-dimensional, time-dependent particle-in-cell simulations. {copyright} {ital 1996 American Institute of Physics.}

  4. 78 FR 48153 - Tallgrass Interstate Gas Transmission, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2013-08-07

    ... Energy Regulatory Commission Tallgrass Interstate Gas Transmission, LLC; Notice of Application Take notice that on July 22, 2013, Tallgrass Interstate Gas Transmission, LLC (Tallgrass) 370 Van Gordon..., Manager of Regulatory, Tallgrass Interstate Gas Transmission, LLC, 370 Van Gordon Street,...

  5. 77 FR 26544 - Columbia Gas Transmission, LLC; Notice of Request Under Blanket Authorization

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-05-04

    ... Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Request Under Blanket Authorization Take notice that on April 18, 2012 Columbia Gas Transmission, LLC (Columbia), 5151 San Felipe... authorization to construct and operate certain natural gas transmission facilities in Chesterfield...

  6. 76 FR 20653 - Florida Gas Transmission Company, LLC; Notice of Application

    Federal Register 2010, 2011, 2012, 2013, 2014

    2011-04-13

    ... Energy Regulatory Commission Florida Gas Transmission Company, LLC; Notice of Application Take notice that on March 24, 2011, Florida Gas Transmission Company, LLC (FGT), 5444 Westheimer Road, Houston... directed to Stephen Veatch, Senior Director of Certificates & Tariffs, Florida Gas Transmission...

  7. Radiofrequency transmission line for bioluminescent Vibrio sp. irradiation

    NASA Astrophysics Data System (ADS)

    Nassisi, V.; Alifano, P.; Talà, A.; Velardi, L.

    2012-07-01

    We present the study and the analyses of a transmission line for radiofrequency (RF) irradiation of bacteria belonging to Vibrio harveyi-related strain PS1, a bioluminescent bacterium living in symbiosis with many marine organisms. The bioluminescence represents a new biologic indicator which is useful for studying the behaviour of living samples in the presence of RF waves due to the modern communication systems. A suitable transmission line, used as an irradiating cell and tested up to the maximum frequency used by the global system for mobile communications and universal mobile telecommunications system transmissions, was characterized. In this experiment, the RF voltage applied to the transmission line was 1 V. Due to short dimensions of the line and the applied high frequencies, standing waves were produced in addition to progressing waves and the electric field strength varies particularly along the longitudinal direction. The magnetic field map was not strongly linked to the electric one due to the presence of standing waves and of the outgoing irradiation. RF fields were measured by two homemade suitable probes able to diagnostic fields of high frequency. The field measurements were performed without any specimens inside the line. Being our sample made of living matter, the real field was modified and its value was estimated by a simulation code. The bioluminescence experiments were performed only at 900 MHz for two different measured electric fields, 53 and 140 V/m. The light emission was measured right from the beginning and after 7 and 25 h. Under RF irradiation, we found that the bioluminescence activity decreased. Compared with the control sample, the diminution was 6.8% and 44% after 7 and 25 h of irradiation, respectively, both with the low or high field. No changes of the survival factor for all the samples were observed. Besides, to understand the emission processes, we operated the deconvolution of the spectra by two Gaussian curves. The Gaussian

  8. 77 FR 50098 - Columbia Gas Transmission, LLC; Supplemental Notice of Intent To Prepare an Environmental...

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-08-20

    ... Environmental Assessment for the Planned Line MB Loop Extension Project and Request for Comments on Environmental Issues On August 1, 2012, Columbia Gas Transmission, LLC (Columbia) filed its intent to modify the... important environmental issues. By this notice, the Commission requests public comments on the scope of...

  9. 77 FR 32628 - Columbia Gas Transmission, LLC; Notice of Environmental Onsite Review

    Federal Register 2010, 2011, 2012, 2013, 2014

    2012-06-01

    ... From the Federal Register Online via the Government Publishing Office DEPARTMENT OF ENERGY Federal Energy Regulatory Commission Columbia Gas Transmission, LLC; Notice of Environmental Onsite Review On June 13 and 14, 2012, the Office of Energy Projects (OEP) staff will conduct site visits of the proposed Line MB Loop Extension Project....

  10. View facing north (30°) of Transmission Line entering Teton River ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    View facing north (30°) of Transmission Line entering Teton River Valley, near Structure 40-7 - Havre Rainbow Transmission Line, Havre City to Great Falls vicinity, Montana, Great Falls, Cascade County, MT