Science.gov

Sample records for air ventilation rates

  1. Position paper -- Tank ventilation system design air flow rates

    SciTech Connect

    Goolsby, G.K.

    1995-01-04

    The purpose of this paper is to document a project position on required ventilation system design air flow rates for the waste storage tanks currently being designed by project W-236A, the Multi-Function Waste Tank Facility (MWTF). The Title 1 design primary tank heat removal system consists of two systems: a primary tank vapor space ventilation system; and an annulus ventilation system. At the conclusion of Title 1 design, air flow rates for the primary and annulus ventilation systems were 960 scfm and 4,400 scfm, respectively, per tank. These design flow rates were capable of removing 1,250,000 Btu/hr from each tank. However, recently completed and ongoing studies have resulted in a design change to reduce the extreme case heat load to 700,000 Btu/hr. This revision of the extreme case heat load, coupled with results of scale model evaporative testing performed by WHC Thermal Hydraulics, allow for a reduction of the design air flow rates for both primary and annulus ventilation systems. Based on the preceding discussion, ICF Kaiser Hanford Co. concludes that the design should incorporate the following design air flow rates: Primary ventilation system--500 scfm maximum and Annulus ventilation system--1,100 scfm maximum. In addition, the minimum air flow rates in the primary and annulus ventilation systems will be investigated during Title 2 design. The results of the Title 2 investigation will determine the range of available temperature control using variable air flows to both ventilation systems.

  2. Ventilating-air change rate versus particulate contaminant spread

    SciTech Connect

    Langer, G.; Deitesfeld, C.A.

    1987-11-13

    This study provides information on the spread of particulate contamination from glovebox leaks in plutonium manufacturing facilities, with emphasis on the effect of ventilating-air change rate on contaminated spread. A new, very sensitive aerosol tracer technique was developed to simulate plutonium aerosol leaks and its dispersion in a room. The tracer, a submicron aerosol of phloroglucinol, does not interfere with work activity and is detected by its ability to form ice crystals in a supercooled cloud. This technique was applied in Buildings 371 and 707 plutonium production areas. The tracer spread throughout the rooms in a few minutes and reached its equilibrium concentration in 10 to 25 min. Also, to clear the room of all tracer took about the same time. In one room, tracer concentration decreased proportionally to the air change rate, while in the second one, air change rate had no effect. This points out the need for air velocity data. Also, future work must include simultaneous particle concentration measurements at several points. 4 refs., 9 figs., 2 tabs.

  3. Effect of outside air ventilation rate on VOC concentrations and emissions in a call center

    SciTech Connect

    Hodgson, A.T.; Faulkner, D.; Sullivan, D.P.; DiBartolomeo, D.L.; Russell, M.L.; Fisk, W.J.

    2002-01-01

    A study of the relationship between outside air ventilation rate and concentrations of VOCs generated indoors was conducted in a call center. Ventilation rates were manipulated in the building's four air handling units (AHUs). Concentrations of VOCs in the AHU returns were measured on 7 days during a 13-week period. Indoor minus outdoor concentrations and emission factors were calculated. The emission factor data was subjected to principal component analysis to identify groups of co-varying compounds based on source type. One vector represented emissions of solvents from cleaning products. Another vector identified occupant sources. Direct relationships between ventilation rate and concentrations were not observed for most of the abundant VOCs. This result emphasizes the importance of source control measures for limiting VOC concentrations in buildings.

  4. Transpired Air Collectors - Ventilation Preheating

    SciTech Connect

    Christensen, C.

    2006-06-22

    Many commercial and industrial buildings have high ventilation rates. Although all that fresh air is great for indoor air quality, heating it can be very expensive. This short (2-page) fact sheet describes a technology available to use solar energy to preheat ventilation air and dramatically reduce utility bills.

  5. Evaluation of the indoor air quality minimum ventilation rate procedure for use in California retail buildings.

    PubMed

    Dutton, S M; Mendell, M J; Chan, W R; Barrios, M; Sidheswaran, M A; Sullivan, D P; Eliseeva, E A; Fisk, W J

    2015-02-01

    This research assesses benefits of adding to California Title-24 ventilation rate (VR) standards a performance-based option, similar to the American Society of Heating, Refrigerating, and Air Conditioning Engineers 'Indoor Air Quality Procedure' (IAQP) for retail spaces. Ventilation rates and concentrations of contaminants of concern (CoC) were measured in 13 stores. Mass balance models were used to estimate 'IAQP-based' VRs that would maintain concentrations of all CoCs below health- or odor-based reference concentration limits. An intervention study in a 'big box' store assessed how the current VR, the Title 24-prescribed VR, and the IAQP-based VR (0.24, 0.69, and 1.51 air changes per hour) influenced measured IAQ and perceived of IAQ. Neither current VRs nor Title 24-prescribed VRs would maintain all CoCs below reference limits in 12 of 13 stores. In the big box store, the IAQP-based VR kept all CoCs below limits. More than 80% of subjects reported acceptable air quality at all three VRs. In 11 of 13 buildings, saving energy through lower VRs while maintaining acceptable IAQ would require source reduction or gas-phase air cleaning for CoCs. In only one of the 13 retail stores surveyed, application of the IAQP would have allowed reduced VRs without additional contaminant-reduction strategies.

  6. Ventilating Air-Conditioner

    NASA Technical Reports Server (NTRS)

    Dinh, Khanh

    1994-01-01

    Air-conditioner provides ventilation designed to be used alone or incorporated into cooling or heating system operates efficiently only by recirculating stale air within building. Energy needed to operate overall ventilating cooling or heating system slightly greater than operating nonventilating cooling or heating system. Helps to preserve energy efficiency while satisfying need for increased forced ventilation to prevent accumulation of undesired gases like radon and formaldehyde. Provides fresh treated air to variety of confined spaces: hospital surgeries, laboratories, clean rooms, and printing shops and other places where solvents used. In mobile homes and portable classrooms, eliminates irritant chemicals exuded by carpets, panels, and other materials, ensuring healthy indoor environment for occupants.

  7. Equivalence in Ventilation and Indoor Air Quality

    SciTech Connect

    Sherman, Max; Walker, Iain; Logue, Jennifer

    2011-08-01

    We ventilate buildings to provide acceptable indoor air quality (IAQ). Ventilation standards (such as American Society of Heating, Refrigerating, and Air-Conditioning Enginners [ASHRAE] Standard 62) specify minimum ventilation rates without taking into account the impact of those rates on IAQ. Innovative ventilation management is often a desirable element of reducing energy consumption or improving IAQ or comfort. Variable ventilation is one innovative strategy. To use variable ventilation in a way that meets standards, it is necessary to have a method for determining equivalence in terms of either ventilation or indoor air quality. This study develops methods to calculate either equivalent ventilation or equivalent IAQ. We demonstrate that equivalent ventilation can be used as the basis for dynamic ventilation control, reducing peak load and infiltration of outdoor contaminants. We also show that equivalent IAQ could allow some contaminants to exceed current standards if other contaminants are more stringently controlled.

  8. Modeling exposure close to air pollution sources in naturally ventilated residences: association of turbulent diffusion coefficient with air change rate.

    PubMed

    Cheng, Kai-Chung; Acevedo-Bolton, Viviana; Jiang, Ruo-Ting; Klepeis, Neil E; Ott, Wayne R; Fringer, Oliver B; Hildemann, Lynn M

    2011-05-01

    For modeling exposure close to an indoor air pollution source, an isotropic turbulent diffusion coefficient is used to represent the average spread of emissions. However, its magnitude indoors has been difficult to assess experimentally due to limitations in the number of monitors available. We used 30-37 real-time monitors to simultaneously measure CO at different angles and distances from a continuous indoor point source. For 11 experiments involving two houses, with natural ventilation conditions ranging from <0.2 to >5 air changes per h, an eddy diffusion model was used to estimate the turbulent diffusion coefficients, which ranged from 0.001 to 0.013 m² s⁻¹. The model reproduced observed concentrations with reasonable accuracy over radial distances of 0.25-5.0 m. The air change rate, as measured using a SF₆ tracer gas release, showed a significant positive linear correlation with the air mixing rate, defined as the turbulent diffusion coefficient divided by a squared length scale representing the room size. The ability to estimate the indoor turbulent diffusion coefficient using two readily measurable parameters (air change rate and room dimensions) is useful for accurately modeling exposures in close proximity to an indoor pollution source.

  9. Effects of Temperature, Humidity and Air Flow on Fungal Growth Rate on Loaded Ventilation Filters.

    PubMed

    Tang, W; Kuehn, T H; Simcik, Matt F

    2015-01-01

    This study compares the fungal growth ratio on loaded ventilation filters under various temperature, relative humidity (RH), and air flow conditions in a controlled laboratory setting. A new full-size commercial building ventilation filter was loaded with malt extract nutrients and conidia of Cladosporium sphaerospermum in an ASHRAE Standard 52.2 filter test facility. Small sections cut from this filter were incubated under the following conditions: constant room temperature and a high RH of 97%; sinusoidal temperature (with an amplitude of 10°C, an average of 23°C, and a period of 24 hr) and a mean RH of 97%; room temperature and step changes between 97% and 75% RH, 97% and 43% RH, and 97% and 11% RH every 12 hr. The biomass on the filter sections was measured using both an elution-culture method and by ergosterol assay immediately after loading and every 2 days up to 10 days after loading. Fungal growth was detected earlier using ergosterol content than with the elution-culture method. A student's t-test indicated that Cladosporium sphaerospermum grew better at the constant room temperature condition than at the sinusoidal temperature condition. By part-time exposure to dry environments, the fungal growth was reduced (75% and 43% RH) or even inhibited (11% RH). Additional loaded filters were installed in the wind tunnel at room temperature and an RH greater than 95% under one of two air flow test conditions: continuous air flow or air flow only 9 hr/day with a flow rate of 0.7 m(3)/s (filter media velocity 0.15 m/s). Swab tests and a tease mount method were used to detect fungal growth on the filters at day 0, 5, and 10. Fungal growth was detected for both test conditions, which indicates that when temperature and relative humidity are optimum, controlling the air flow alone cannot prevent fungal growth. In real applications where nutrients are less sufficient than in this laboratory study, fungal growth rate may be reduced under the same operating conditions.

  10. Whole house particle removal and clean air delivery rates for in-duct and portable ventilation systems.

    PubMed

    Macintosh, David L; Myatt, Theodore A; Ludwig, Jerry F; Baker, Brian J; Suh, Helen H; Spengler, John D

    2008-11-01

    A novel method for determining whole house particle removal and clean air delivery rates attributable to central and portable ventilation/air cleaning systems is described. The method is used to characterize total and air-cleaner-specific particle removal rates during operation of four in-duct air cleaners and two portable air-cleaning devices in a fully instrumented test home. Operation of in-duct and portable air cleaners typically increased particle removal rates over the baseline rates determined in the absence of operating a central fan or an indoor air cleaner. Removal rates of 0.3- to 0.5-microm particles ranged from 1.5 hr(-1) during operation of an in-duct, 5-in. pleated media filter to 7.2 hr(-1) for an in-duct electrostatic air cleaner in comparison to a baseline rate of 0 hr(-1) when the air handler was operating without a filter. Removal rates for total particulate matter less than 2.5 microm in aerodynamic diameter (PM2.5) mass concentrations were 0.5 hr(-1) under baseline conditions, 0.5 hr(-1) during operation of three portable ionic air cleaners, 1 hr(-1) for an in-duct 1-in. media filter, 2.4 hr(-1) for a single high-efficiency particle arrestance (HEPA) portable air cleaner, 4.6 hr(-1) for an in-duct 5-in. media filter, 4.7 hr(-1) during operation of five portable HEPA filters, 6.1 hr(-1) for a conventional in-duct electronic air cleaner, and 7.5 hr(-1) for a high efficiency in-duct electrostatic air cleaner. Corresponding whole house clean air delivery rates for PM2.5 attributable to the air cleaner independent of losses within the central ventilation system ranged from 2 m3/min for the conventional media filter to 32 m3/min for the high efficiency in-duct electrostatic device. Except for the portable ionic air cleaner, the devices considered here increased particle removal indoors over baseline deposition rates. PMID:19044163

  11. VENTILATION RESEARCH: A REVIEW OF RECENT INDOOR AIR QUALITY LITERATURE

    EPA Science Inventory

    The report gives results of a literature review, conducted to survey and summarize recent and ongoing engineering research into building ventilation, air exchange rate, pollutant distribution and dispersion, and other effects of heating, ventilation, and air-conditioning (HVAC) s...

  12. Final Report Balancing energy conservation and occupant needs in ventilation rate standards for Big Box stores in California. Predicted indoor air quality and energy consumption using a matrix of ventilation scenarios

    SciTech Connect

    Apte, Michael G.; Mendell, Mark J.; Sohn, Michael D.; Dutton, Spencer M.; Berkeley, Pam M.; Spears, Michael

    2011-02-01

    Through mass-balance modeling of various ventilation scenarios that might satisfy the ASHRAE 62.1 Indoor Air Quality (IAQ) Procedure, we estimate indoor concentrations of contaminants of concern (COCs) in California “big box” stores, compare estimates to available thresholds, and for selected scenarios estimate differences in energy consumption. Findings are intended to inform decisions on adding performance-based approaches to ventilation rate (VR) standards for commercial buildings. Using multi-zone mass-balance models and available contaminant source rates, we estimated concentrations of 34 COCs for multiple ventilation scenarios: VRmin (0.04 cfm/ft2 ), VRmax (0.24 cfm/ft2 ), and VRmid (0.14 cfm/ft2 ). We compared COC concentrations with available health, olfactory, and irritant thresholds. We estimated building energy consumption at different VRs using a previously developed EnergyPlus model. VRmax did control all contaminants adequately, but VRmin did not, and VRmid did so only marginally. Air cleaning and local ventilation near strong sources both showed promise. Higher VRs increased indoor concentrations of outdoor air pollutants. Lowering VRs in big box stores in California from VRmax to VRmid would reduce total energy use by an estimated 6.6% and energy costs by 2.5%. Reducing the required VRs in California’s big box stores could reduce energy use and costs, but poses challenges for health and comfort of occupants. Source removal, air cleaning, and local ventilation may be needed at reduced VRs, and even at current recommended VRs. Also, alternative ventilation strategies taking climate and season into account in ventilation schedules may provide greater energy cost savings than constant ventilation rates, while improving IAQ.

  13. Building ventilation and indoor air quality

    SciTech Connect

    Hollowell, C.D.; Berk, J.V.; Boegel, M.L.; Miksch, R.R.; Nazaroff, W.W.; Traynor, G.W.

    1980-01-01

    Rising energy prices, among other factors, have generated an incentive to reduce ventilation rates and thereby reduce the cost of heating and cooling buildings. Reduced infiltration and ventilation in buildings may significantly increase exposure to indoor contaminants and perhaps have adverse effects on occupant health and comfort. Four indoor air contaminants - carbon monoxide and nitrogen dioxide from gas appliances; formaldehyde from particleboard, plywood, urea-formaldehyde foam insulation, and gas appliances; and radon from building materials, soil, and ground water - are currently receiving considerable attention in the context of potential health risks associated with reduced infiltration and ventilation rates. These air contaminants in conventional and energy efficient buildings were measured and analyzed with a view to assessing their potential health risks and various control strategies capable of lowering pollutant concentrations. Preliminary findings suggest that further intensive studies are needed in order to develop criteria for maintaining acceptable indoor air quality without compromising energy efficiency.

  14. Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    SciTech Connect

    Rudd, Armin; Bergey, Daniel

    2014-02-01

    In this project, Building America research team Building Science Corporation tested the effectiveness of ventilation systems at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy. This was because the source of outside air was not direct from outside, the ventilation air was not distributed, and no provision existed for air filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four system factor categories: balance, distribution, outside air source, and recirculation filtration. Recommended system factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year.

  15. Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    SciTech Connect

    Rudd, A.; Bergey, D.

    2014-02-01

    Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy. It was inferior because the source of outside air was not direct from outside, the ventilation air was not distributed, and no provision existed for air filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four System Factor Categories: Balance, Distribution, Outside Air Source, and Recirculation Filtration. Recommended System Factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year.

  16. New Air Cleaning Strategies for Reduced Commercial Building Ventilation Energy

    SciTech Connect

    Sidheswaran, Meera; Destaillats, Hugo; Sullivan, Douglas P.; Fisk, William J.

    2010-10-27

    Approximately ten percent of the energy consumed in U.S. commercial buildings is used by HVAC systems to condition outdoor ventilation air. Reducing ventilation rates would be a simple and broadly-applicable energy retrofit option, if practical counter measures were available that maintained acceptable concentrations of indoor-generated air pollutants. The two general categories of countermeasures are: 1) indoor pollutant source control, and 2) air cleaning. Although pollutant source control should be used to the degree possible, source control is complicated by the large number and changing nature of indoor pollutant sources. Particle air cleaning is already routinely applied in commercial buildings. Previous calculations indicate that particle filtration consumes only 10percent to 25percent of the energy that would otherwise be required to achieve an equivalent amount of particle removal with ventilation. If cost-effective air cleaning technologies for volatile organic compounds (VOCs) were also available, outdoor air ventilation rates could be reduced substantially and broadly in the commercial building stock to save energy. The research carried out in this project focuses on developing novel VOC air cleaning technologies needed to enable energy-saving reductions in ventilation rates. The minimum required VOC removal efficiency to counteract a 50percent reduction in ventilation rate for air cleaning systems installed in the HVAC supply airstream is modest (generally 20percent or less).

  17. Nozzle for discharging ventilation air from a ventilation system

    SciTech Connect

    Elfverson, S.E.

    1986-09-30

    This patent describes a nozzle for discharging ventilation air from a ventilation system, preferably arranged in a vehicle, including at least one outlet housing with a through-flow duct for ventilation air, a fixed plate transverse to the flow duct and rigidly attached to the outlet housing, and a plurality of plates parallel to the fixed plate. These plates are mutually displaceable in a direction transverse to the flow duct under the action of a control lever passing through the plates, the plates being formed with perforation patterns, which in coaction form ventilation ducts through which the ventilation air can flow and in response to the setting of the control lever cause deviation of the flow direction of the ventilation air. Each displaceable plate is formed with a grid cross comprising at least two intersecting bars, of which one bar has a substantially circular cross section, while the other bar has a substantially elliptical cross section and wherein the control lever is adapted to grip round a grid cross, the control lever having two pairs of longitudinal slots. One pair of the slots is adapted to grip without play one of the intersecting bars in each respective grid cross. The other pair of slots comprises a first slot adapted to grip without play the other of the intersecting bars, and a second slot formed with a width disabling engagement with the other of the intersecting bars.

  18. Evaluation of methods for determining air exchange rate in a naturally ventilated dairy cattle building with large openings using computational fluid dynamics (CFD)

    NASA Astrophysics Data System (ADS)

    Wu, Wentao; Zhai, John; Zhang, Guoqiang; Nielsen, Peter V.

    2012-12-01

    Naturally ventilated dairy cattle buildings are a major source of ammonia and greenhouse gas emissions. Accurate estimation in gas emissions constitutes the first step towards reducing the negative impact of emissions on the local environment. The greatest uncertainty in the emission estimation from a naturally ventilated livestock building with large openings is the determination of the air exchange rate (AER) and the choice of the gas sampling positions for representative outlet gas concentration. To reduce the uncertainties in the emission estimation, the performances of three techniques - integrating volume flow rates (VFR), tracer gas decay (TGD) and constant tracer gas (CTG) for determination of ventilation rates were assessed in this paper by Computational fluid dynamics (CFD). In the developed CFD model, the animal occupied zone (AOZ) was treated as porous media and the resistance coefficient of porous zone was derived by pressure drops across AOZ using a sub-CFD model. The results showed that AERs predicted by VFR and TGD were in good agreement with each other within a large range of wind speeds. The large difference in AER estimation using CTG and VFR indicates that the mean CO2 concentration of the entire room may not represent the concentration at the air exit. It may be not suitable to calculate AER using mean concentration of internal sampling positions. When wind became stronger, the accuracy of CTG decreased. The gas sampling positions should be close to the openings or even in the openings; the gas sampling positions should be located adjacent to the openings or even in the openings. To reduce the uncertain introduced by wind direction, all the openings especially of different azimuths should possess sampling tubes. The maximum gas concentrations in the different openings could be the optimum value to represent the concentration in the exit air.

  19. Characteristics of coal mine ventilation air flows.

    PubMed

    Su, Shi; Chen, Hongwei; Teakle, Philip; Xue, Sheng

    2008-01-01

    Coal mine methane (CMM) is not only a greenhouse gas but also a wasted energy resource if not utilised. Underground coal mining is by far the most important source of fugitive methane emissions, and approximately 70% of all coal mining related methane is emitted to the atmosphere through mine ventilation air. Therefore, research and development on mine methane mitigation and utilisation now focuses on methane emitted from underground coal mines, in particular ventilation air methane (VAM) capture and utilisation. To date, most work has focused on the oxidation of very low concentration methane. These processes may be classified based on their combustion kinetic mechanisms into thermal oxidation and catalytic oxidation. VAM mitigation/utilisation technologies are generally divided into two basic categories: ancillary uses and principal uses. However, it is possible that the characteristics of ventilation air flows, for example the variations in methane concentration and the presence of certain compounds, which have not been reported so far, could make some potential VAM mitigation and utilisation technologies unfeasible if they cannot cope with the characteristics of mine site ventilation air flows. Therefore, it is important to understand the characteristics of mine ventilation air flows. Moreover, dust, hydrogen sulphide, sulphur dioxide, and other possible compounds emitted through mine ventilation air into the atmosphere are also pollutants. Therefore, this paper presents mine-site experimental results on the characteristics of mine ventilation air flows, including methane concentration and its variations, dust loadings, particle size, mineral matter of the dust, and other compounds in the ventilation air flows. The paper also discusses possible correlations between ventilation air characteristics and underground mining activities.

  20. EFFECT OF VENTILATION SYSTEMS AND AIR FILTERS ON DECAY RATES OF PARTICLES PRODUCED BY INDOOR SOURCES IN AN OCCUPIED TOWNHOUSE

    EPA Science Inventory

    Several studies have shown the importance of particle losses in real homes due to deposition and filtration; however, none have quantitatively shown the impact of using a central forced air fan and in-duct filter on particle loss rates. In an attempt to provide such data, we me...

  1. Passive ventilation for residential air quality control

    SciTech Connect

    Axley, J.

    1999-07-01

    Infiltration has long served the residential ventilation needs in North America. In Northern Europe it has been augmented by purpose-provided natural ventilation systems--so-called passive ventilation systems--to better control moisture problems in dwellings smaller than their North American counterparts and in a generally wetter climate. The growing concern for energy consumption, and the environmental impacts associated with it, has however led to tighter residential construction standards on both continents and as a result problems associated with insufficient background ventilation have surfaced. Can European passive ventilation systems be adapted for use in North American dwellings to provide general background ventilation for air quality control? This paper attempts to answer this question. The configuration, specifications and performance of the preferred European passive ventilation system--the passive stack ventilation (PSV) system--will be reviewed; innovative components and system design strategies recently developed to improve the traditional PSV system performance will be outlined; and alternative system configurations will be presented that may better serve the climatic extremes and more urban contexts of North America. While these innovative and alternative passive ventilation systems hold great promise for the future, a rational method to size the components of these systems to achieve the control and precision needed to meet the conflicting constraints of new ventilation and air tightness standards has not been forthcoming. Such a method will be introduced in this paper and an application of this method will be presented.

  2. Waste tank ventilation rates measured with a tracer gas method

    SciTech Connect

    Huckaby, J.L.; Evans, J.C.; Sklarew, D.S.; Mitroshkov, A.V.

    1998-08-01

    Passive ventilation with the atmosphere is used to prevent accumulation of waste gases and vapors in the headspaces of 132 of the 177 high-level radioactive waste Tanks at the Hanford Site in Southeastern Washington State. Measurements of the passive ventilation rates are needed for the resolution of two key safety issues associated with the rates of flammable gas production and accumulation and the rates at which organic salt-nitrate salt mixtures dry out. Direct measurement of passive ventilation rates using mass flow meters is not feasible because ventilation occurs va multiple pathways to the atmosphere (i.e., via the filtered breather riser and unsealed tank risers and pits), as well as via underground connections to other tanks, junction boxes, and inactive ventilation systems. The tracer gas method discussed in this report provides a direct measurement of the rate at which gases are removed by ventilation and an indirect measurement of the ventilation rate. The tracer gas behaves as a surrogate of the waste-generated gases, but it is only diminished via ventilation, whereas the waste gases are continuously released by the waste and may be subject to depletion mechanisms other than ventilation. The fiscal year 1998 tracer studies provide new evidence that significant exchange of air occurs between tanks via the underground cascade pipes. Most of the single-shell waste tanks are connected via 7.6-cm diameter cascade pipes to one or two adjacent tanks. Tracer gas studies of the Tank U-102/U-103 system indicated that the ventilation occurring via the cascade line could be a significant fraction of the total ventilation. In this two-tank cascade, air evidently flowed from Tank U-103 to Tank U-102 for a time and then was observed to flow from Tank U-102 to Tank U-103.

  3. Quantitative relationship of sick building syndrome symptoms with ventilation rates

    SciTech Connect

    Fisk, William J.; Mirer, Anna G.; Mendell, Mark J.

    2009-01-01

    Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence in office workers with ventilation rate. For each study, slopes were calculated, representing the fractional change in SBS symptom prevalence per unit change in ventilation rate per person. Values of ventilation rate, associated with each value of slope, were also calculated. Linear regression equations were fitted to the resulting data points, after weighting by study size. Integration of the slope-ventilation rate equations yielded curves of relative SBS symptom prevalence versus ventilation rate. Based on these analyses, as the ventilation rate drops from 10 to 5 L/s-person, relative SBS symptom prevalence increases approximately 23percent (12percent to 32percent), and as ventilation rate increases from 10 to 25 L/s-person, relative prevalence decreases approximately 29percent (15percent to 42percent). Variations in SBS symptom types, building features, and outdoor air quality may cause the relationship ofSBS symptom prevalence with ventilation rate in specific situations to differ from the average relationship predicted in this paper.

  4. Effect of ventilation systems and air filters on decay rates of particles produced by indoor sources in an occupied townhouse

    NASA Astrophysics Data System (ADS)

    Howard-Reed, Cynthia; Wallace, Lance A.; Emmerich, Steven J.

    Several studies have shown the importance of particle losses in real homes due to deposition and filtration; however, none have quantitatively shown the impact of using a central forced air fan and in-duct filter on particle loss rates. In an attempt to provide such data, we measured the deposition of particles ranging from 0.3 to 10 μm in an occupied townhouse and also in an unoccupied test house. Experiments were run with three different sources (cooking with a gas stove, citronella candle, pouring kitty litter), with the central heating and air conditioning (HAC) fan on or off, and with two different types of in-duct filters (electrostatic precipitator and ordinary furnace filter). Particle size, HAC fan operation, and the electrostatic precipitator had significant effects on particle loss rates. The standard furnace filter had no effect. Surprisingly, the type of source (combustion vs. mechanical generation) and the type of furnishings (fully furnished including carpet vs. largely unfurnished including mostly bare floor) also had no measurable effect on the deposition rates of particles of comparable size. With the HAC fan off, average deposition rates varied from 0.3 h -1 for the smallest particle range (0.3-0.5 μm) to 5.2 h -1 for particles greater than 10 μm. Operation of the central HAC fan approximately doubled these rates for particles <5 μm, and increased rates by 2 h -1 for the larger particles. An in-duct electrostatic precipitator increased the loss rates compared to the fan-off condition by factors of 5-10 for particles <2.5 μm, and by a factor of 3 for 2.5-5.0 μm particles. In practical terms, use of the central fan alone could reduce indoor particle concentrations by 25-50%, and use of an in-duct ESP could reduce particle concentrations by 55-85% compared to fan-off conditions.

  5. Formaldehyde as a basis for residential ventilation rates

    SciTech Connect

    Sherman, M.H.; Hodgson, A.T.

    2002-04-28

    Traditionally, houses in the U.S. have been ventilated by passive infiltration in combination with active window opening. However in recent years, the construction quality of residential building envelopes has been improved to reduce infiltration, and the use of windows for ventilation also may have decreased due to a number of factors. Thus, there has been increased interest in engineered ventilation systems for residences. The amount of ventilation provided by an engineered system should be set to protect occupants from unhealthy or objectionable exposures to indoor pollutants, while minimizing energy costs for conditioning incoming air. Determining the correct ventilation rate is a complex task, as there are numerous pollutants of potential concern, each having poorly characterized emission rates, and poorly defined acceptable levels of exposure. One ubiquitous pollutant in residences is formaldehyde. The sources of formaldehyde in new houses are reasonably understood, and there is a large body of literature on human health effects. This report examines the use of formaldehyde as a means of determining ventilation rates and uses existing data on emission rates of formaldehyde in new houses to derive recommended levels. Based on current, widely accepted concentration guidelines for formaldehyde, the minimum and guideline ventilation rates for most new houses are 0.28 and 0.5 air changes per hour, respectively.

  6. Air flow in snake ventilation.

    PubMed

    Clark, B D; Gans, C; Rosenberg, H I

    1978-02-01

    Ventilation in resting, unrestrained Boa constrictor, Python regius and Thanmophis s. sirtalis was monitored using various combinations of a closed Kopfkappe (head chamber), intratracheal pressure catheters, strain gauges around the trunk, and a flow meter connected to one of the nostrils. Records of intratracheal pressure with and without closing the Kopfkappe show that the latter device induces artifacts in the normal ventilatory pattern. Flow meter readings from quiescent snakes indicate that ventilation is biphasic (outflow-inflow-pause) rather than triphasic (outflow-inflow-outflow-pause), while simultaneous pressure and strain gauge records are variably tri- or quadriphasic.

  7. Indoor Air Quality: Is Increased Ventilation the Answer?

    ERIC Educational Resources Information Center

    Hansen, Shirley

    1989-01-01

    Explains how indoor air quality is affected by pollutants in the air and also by temperature, humidity, and ventilation. Increased ventilation alone seldom solves the "sick building syndrome." Lists ways to improve indoor air quality and optimize energy efficiency. (MLF)

  8. Balancing energy conservation and occupant needs in ventilation rate standards for Big Box stores and other commercial buildings in California. Issues related to the ASHRAE 62.1 Indoor Air Quality Procedure

    SciTech Connect

    Mendell, Mark J.; Apte, Mike G.

    2010-10-31

    This report considers the question of whether the California Energy Commission should incorporate the ASHRAE 62.1 ventilation standard into the Title 24 ventilation rate (VR) standards, thus allowing buildings to follow the Indoor Air Quality Procedure. This, in contrast to the current prescriptive standard, allows the option of using ventilation rate as one of several strategies, which might include source reduction and air cleaning, to meet specified targets of indoor air concentrations and occupant acceptability. The research findings reviewed in this report suggest that a revised approach to a ventilation standard for commercial buildings is necessary, because the current prescriptive ASHRAE 62.1 Ventilation Rate Procedure (VRP) apparently does not provide occupants with either sufficiently acceptable or sufficiently healthprotective air quality. One possible solution would be a dramatic increase in the minimum ventilation rates (VRs) prescribed by a VRP. This solution, however, is not feasible for at least three reasons: the current need to reduce energy use rather than increase it further, the problem of polluted outdoor air in many cities, and the apparent limited ability of increasing VRs to reduce all indoor airborne contaminants of concern (per Hodgson (2003)). Any feasible solution is thus likely to include methods of pollutant reduction other than increased outdoor air ventilation; e.g., source reduction or air cleaning. The alternative 62.1 Indoor Air Quality Procedure (IAQP) offers multiple possible benefits in this direction over the VRP, but seems too limited by insufficient specifications and inadequate available data to provide adequate protection for occupants. Ventilation system designers rarely choose to use it, finding it too arbitrary and requiring use of much non-engineering judgment and information that is not readily available. This report suggests strategies to revise the current ASHRAE IAQP to reduce its current limitations. These

  9. The Influence of Fuel Moisture, Charge Size, Burning Rate and Air Ventilation Conditions on Emissions of PM, OC, EC, Parent PAHs, and Their Derivatives from Residential Wood Combustion

    PubMed Central

    Shen, Guofeng; Xue, Miao; Wei, Siye; Chen, Yuanchen; Wang, Bin; Wang, Rong; Lv, Yan; Shen, Huizhong; Li, Wei; Zhang, Yanyan; Huang, Ye; Chen, Han; Wei, Wen; Zhao, Qiuyue; Li, Bin; Wu, Haisuo; TAO, Shu

    2014-01-01

    Controlled combustion experiments were conducted to investigate the influence of fuel charge size, moisture, air ventilation and burning rate on the emission factors (EFs) of carbonaceous particulate matter, parent polycyclic aromatic hydrocarbons (pPAHs) and their derivatives from residential wood combustion in a typical brick cooking stove. Measured EFs were found to be independent of fuel charge size, but increased with increasing fuel moisture. Pollution emissions from a normal burning under an adequate air supply condition were the lowest for most pollutants, while more pollutants were emitted when the oxygen deficient atmosphere was formed in stove chamber during fast burning. The impact of these 4 factors on particulate matter size distribution was also studied. Modified combustion efficiency and the four investigated factors explained 68, 72, and 64% of total variations in EFs of PM, organic carbon, and oxygenated PAHs, respectively, but only 36, 38 and 42% of the total variations in EFs of elemental carbon, pPAHs and nitro-PAHs, respectively. PMID:24520723

  10. Technology Solutions Case Study: Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    SciTech Connect

    A. Rudd and D. Bergey

    2015-08-01

    Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs.

  11. Effect of Room Ventilation Rates in Rodent Rooms with Direct-Exhaust IVC Systems

    PubMed Central

    Geertsema, Roger S; Lindsell, Claire E

    2015-01-01

    When IVC are directly exhausted from a rodent housing room, the air quality of the room can become independent of the intracage air quality and may reduce the need for high room ventilation rates. This study assessed the effect of decreasing the ventilation rate in rodent rooms using direct-exhaust IVC systems. The study was conducted over 16 wk and compared conditions in 8 rodent rooms that had ventilation rates of 5 to 6 air changes per hour (ACH) with those in rooms at 10 to 12 ACH. At the low ventilation rate, rooms had higher CO2 concentrations, higher dew point temperature, and lower particulate levels and spent a greater percentage of time above the temperature set point than did rooms at the high rate. The levels of allergens and endotoxins in room air were the same regardless of the ventilation rate. Differences seen in parameters within cages at the 2 ventilation rates were operationally irrelevant. We detected no total volatile organic compounds in the room that were attributable to ammonia, regardless of the ventilation rate. Clearing the air of ethanol after a spill took longer at the low compared with high rate. However, ethanol clearance was faster at the low rate when the demand-control system was activated than at the high ventilation rate alone. Air quality in the room and in the cages were acceptable with room ventilation rates of 5 to 6 ACH in rodent rooms that use direct-exhaust IVC systems. PMID:26424250

  12. Rate of uptake of endogenous cortisol by the left ventricle of the anaesthetized dog during ventilation with ambient air and during hypoxia

    PubMed Central

    Kolanowski, J.; Lammerant, J.

    1973-01-01

    1. The rate of uptake of endogenous cortisol by the left ventricle was determined in eight dogs as the product of the left ventricular myocardial plasma flow and the coronary arteriovenous difference in plasma cortisol concentration. The arteriovenous difference in hormone concentration in resting skeletal muscle (M. gracilis) was also measured. The values given are means ± S.E. 2. During ventilation with ambient air (arterial PO2: 85 ± 2 mm Hg), the rate of cortisol uptake by the left ventricle averaged 382 ± 92 ng/100 g.min. The arteriovenous difference in hormone concentration in the vessels of the M. gracilis was more than twice that in the coronary vessels. Assuming a value of 3-4 ml./100 g.min for the blood flow in this muscle, the corresponding rate of cortisol uptake would be in the range of 25-33 ng/100 g.min. 3. During hypoxia (arterial PO2: 35 ± 1 mm Hg), the rate of cortisol uptake by the left ventricle was not significant, averaging 26 ± 113 ng/100 g.min. By contrast, the skeletal muscle still extracted significant amounts of cortisol from the plasma. It is inferred that the suppression of a significant uptake of the hormone by the left ventricle was related, at least in part, to the changes in the mechanical and associated metabolic activity of the heart muscle elicited by the lowering of the arterial PO2. 4. Hypoxia depressed the net uptake of cortisol by the left ventricle rather than the uptake mechanism itself. Indeed, bi-directional movements of cortisol between the plasma and the heart muscle, with rates of release up to 1150 ng/100 g.min, were observed. PMID:4754871

  13. [Air quality control systems: heating, ventilating, and air conditioning (HVAC)].

    PubMed

    Bellucci Sessa, R; Riccio, G

    2004-01-01

    After a brief illustration of the principal layout schemes of Heating, Ventilating, and Air Conditioning (HVAC), the first part of this paper summarizes the standards, both voluntary and compulsory, regulating HVAC facilities design and installation with regard to the question of Indoor Air Quality (IAQ). The paper then examines the problem of ventilation systems maintenance and the essential hygienistic requirements in whose absence HVAC facilities may become a risk factor for people working or living in the building. Lastly, the paper deals with HVAC design strategies and methods, which aim not only to satisfy comfort and air quality requirements, but also to ensure easy and effective maintenance procedures.

  14. Measured Air Distribution Effectiveness for Residential Mechanical Ventilation Systems

    SciTech Connect

    Sherman, Max; Sherman, Max H.; Walker, Iain S.

    2008-05-01

    The purpose of ventilation is dilute or remove indoor contaminants that an occupant is exposed to. In a multi-zone environment such as a house, there will be different dilution rates and different source strengths in every zone. Most US homes have central HVAC systems, which tend to mix the air thus the indoor conditions between zones. Different types of ventilation systems will provide different amounts of exposure depending on the effectiveness of their air distribution systems and the location of sources and occupants. This paper will report on field measurements using a unique multi-tracer measurement system that has the capacity to measure not only the flow of outdoor air to each zone, but zone-to-zone transport. The paper will derive seven different metrics for the evaluation of air distribution. Measured data from two homes with different levels of natural infiltration will be used to evaluate these metrics for three different ASHRAE Standard 62.2 compliant ventilation systems. Such information can be used to determine the effectiveness of different systems so that appropriate adjustments can be made in residential ventilation standards such as ASHRAE Standard 62.2.

  15. Air flow and particle control with different ventilation systems in a classroom.

    PubMed

    Holmberg, S; Chen, Q

    2003-06-01

    Most ventilation and air conditioning systems are designed without much concern about how settling particles behave in ventilation air flows. For displacement ventilation systems, designers normally assume that all pollutants follow the buoyant air flow into an upper zone, where they are evacuated. This is, however, not always true. Previous studies show that high concentrations of settling respirable particles can be found in the breathing zone, and that the exposure rates can be a health hazard to occupants. The emphasis here is on how ventilation systems should be designed to minimize respirable airborne particles in the breathing zone. The supply and exhaust conditions of the ventilation air flow are shown to play an important role in the control of air quality. Computer simulation programs of computational fluid dynamics (CFD) type are used. Particle concentrations, thermal conditions and modified ventilation system solutions are reported.

  16. Heating, ventilation and air conditioning systems

    SciTech Connect

    Kyle, D.M.; Sullivan, R.A.

    1993-02-01

    A study is made of several outstanding issues concerning the commercial development of environmental control systems for electric vehicles (EVs). Engineering design constraints such as federal regulations and consumer requirements are first identified. Next, heating and cooling loads in a sample automobile are calculated using a computer model available from the literature. The heating and cooling loads are then used as a basis for estimating the electrical consumption that is to be expected for heat pumps installed in EVs. The heat pump performance is evaluated using an automobile heat pump computer model which has been developed recently at Oak Ridge National Laboratory (ORNL). The heat pump design used as input to the model consists of typical finned-tube heat exchangers and a hermetic compressor driven by a variable-speed brushless dc motor. The simulations suggest that to attain reasonable system efficiencies, the interior heat exchangers that are currently installed as automobile air conditioning will need to be enlarged. Regarding the thermal envelope of the automobile itself, calculations are made which show that considerable energy savings will result if steps are taken to reduce {open_quote}hot soak{close_quote} temperatures and if the outdoor air ventilation rate is well controlled. When these changes are made, heating and cooling should consume less than 10% of the total stored electrical energy for steady driving in most U.S. climates. However, this result depends strongly upon the type of driving: The fraction of total power for heating and cooling ({open_quote}range penalty{close_quote}) increases sharply for driving scenarios having low average propulsion power, such as stop-and-go driving.

  17. Building America Case Study: Ventilation System Effectiveness and Tested Indoor Air Quality Impacts, Tyler, Texas

    SciTech Connect

    2015-08-01

    ?Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four System Factor Categories: Balance, Distribution, Outside Air Source, and Recirculation Filtration. Recommended System Factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy.

  18. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a) Adequate ventilation shall be provided. (b) Equipment for adequate control over air pressure, micro-organisms, dust... 21 Food and Drugs 4 2013-04-01 2013-04-01 false Ventilation, air filtration, air heating...

  19. Energy and air quality implications of passive stack ventilation in residential buildings

    SciTech Connect

    Mortensen, Dorthe Kragsig; Walker, Iain S.; Sherman, Max

    2011-01-01

    Ventilation requires energy to transport and condition the incoming air. The energy consumption for ventilation in residential buildings depends on the ventilation rate required to maintain an acceptable indoor air quality. Historically, U.S. residential buildings relied on natural infiltration to provide sufficient ventilation, but as homes get tighter, designed ventilation systems are more frequently required particularly for new energy efficient homes and retrofitted homes. ASHRAE Standard 62.2 is used to specify the minimum ventilation rate required in residential buildings and compliance is normally achieved with fully mechanical whole-house systems; however, alternative methods may be used to provide the required ventilation when their air quality equivalency has been proven. One appealing method is the use of passive stack ventilation systems. They have been used for centuries to ventilate buildings and are often used in ventilation regulations in other countries. Passive stacks are appealing because they require no fans or electrical supply (which could lead to lower cost) and do not require maintenance (thus being more robust and reliable). The downside to passive stacks is that there is little control of ventilation air flow rates because they rely on stack and wind effects that depend on local time-varying weather. In this study we looked at how passive stacks might be used in different California climates and investigated control methods that can be used to optimize indoor air quality and energy use. The results showed that passive stacks can be used to provide acceptable indoor air quality per ASHRAE 62.2 with the potential to save energy provided that they are sized appropriately and flow controllers are used to limit over-ventilation.

  20. Ventilation research: A review of recent indoor air quality literature. Final report, October 1993-March 1994

    SciTech Connect

    Van Osdell, D.W.

    1994-09-01

    Building ventilation and air conditioning systems have traditionally been designed and controlled to maintain occupant thermal comfort at acceptable capital and operating costs, an indoor air quality (IAQ) has not been a primary concern. A literature review was conducted to survey and summarize recent and on-going engineering research into building ventilation, air exchange rate, pollutant distribution and dispersion, and other effects of heating, ventilation, and air conditioning (HVAC) systems on IAQ. The ventilation-related engineering literature was divided into seven major categories: (1) pollutant transport to and into the building envelope; (2) air cleaning systems; (3) flow and pollutant dispersion, (4) room and building flow/dispersion research; (5) HVAC/building design, operation, and control strategies; (6) applied microbial research; and (7) building performance. The significance and status of ventilation-related IAQ research was summarized by research category, and research opportunities were identified within each category.

  1. Indoor Air Quality and Ventilation in Residential Deep Energy Retrofits

    SciTech Connect

    Less, Brennan; Walker, Iain

    2014-06-01

    Because airtightening is a significant part of Deep Energy Retrofits (DERs), concerns about ventilation and Indoor Air Quality (IAQ) have emerged. To investigate this, ventilation and IAQ were assessed in 17 non-smoking California Deep Energy Retrofit homes. Inspections and surveys were used to assess household activities and ventilation systems. Pollutant sampling performed in 12 homes included six-day passive samples of nitrogen dioxide (NO2), formaldehyde and air exchange rate (AER); time-resolved data loggers were used to measure particle counts. Half of the homes provided continuous mechanical ventilation. Despite these homes being twice as airtight (3.0 and 7.6 ACH50, respectively), their median AER was indistinguishable from naturally vented homes (0.36 versus 0.37 hr-1). Numerous problems were found with ventilation systems; however, pollutant levels did not reach levels of concern in most homes. Ambient NO2 standards were exceeded in some gas cooking homes that used legacy ranges with standing pilots, and in Passive House-style homes without range hoods exhausted to outside. Cooking exhaust systems were installed and used inconsistently. The majority of homes reported using low-emitting materials, and formaldehyde levels were approximately half those in conventional new CA homes (19.7 versus 36 μg/m3), with emissions rates nearly 40percent less (12.3 versus 20.6 μg/m2/hr.). Presence of air filtration systems led to lower indoor particle number concentrations (PN>0.5: 8.80E+06 PN/m3 versus 2.99E+06; PN>2.5: 5.46E+0.5 PN/m3 versus 2.59E+05). The results indicate that DERs can provide adequate ventilation and IAQ, and that DERs should prioritize source control, particle filtration and well-designed local exhaust systems, while still providing adequate continuous ventilation.

  2. Short-term airing by natural ventilation - implication on IAQ and thermal comfort.

    PubMed

    Heiselberg, P; Perino, M

    2010-04-01

    The need to improve the energy efficiency of buildings requires new and more efficient ventilation systems. It has been demonstrated that innovative operating concepts that make use of natural ventilation seem to be more appreciated by occupants. Among the available ventilation strategies that are currently available, buoyancy driven, single-sided natural ventilation has proved to be very effective and can provide high air change rates for temperature and Indoor Air Quality (IAQ) control. However, to promote a wider distribution of these systems an improvement in the knowledge of their working principles is necessary. The present study analyses and presents the results of an experimental evaluation of airing performance in terms of ventilation characteristics, IAQ and thermal comfort. It includes investigations of the consequences of opening time, opening frequency, opening area and expected airflow rate, ventilation efficiency, thermal comfort and dynamic temperature conditions. A suitable laboratory test rig was developed to perform extensive experimental analyses of the phenomenon under controlled and repeatable conditions. The results showed that short-term window airing is very effective and can provide both acceptable IAQ and thermal comfort conditions in buildings. Practical Implications This study gives the necessary background and in-depth knowledge of the performance of window airing by single-sided natural ventilation necessary for the development of control strategies for window airing (length of opening period and opening frequency) for optimum IAQ and thermal comfort in naturally ventilated buildings.

  3. Assessment of ventilation and indoor air pollutants in nursery and elementary schools in France.

    PubMed

    Canha, N; Mandin, C; Ramalho, O; Wyart, G; Ribéron, J; Dassonville, C; Hänninen, O; Almeida, S M; Derbez, M

    2016-06-01

    The aim of this study was to characterize the relationship between Indoor Air Quality (IAQ) and ventilation in French classrooms. Various parameters were measured over one school week, including volatile organic compounds, aldehydes, particulate matter (PM2.5 mass concentration and number concentration), carbon dioxide (CO2 ), air temperature, and relative humidity in 51 classrooms at 17 schools. The ventilation was characterized by several indicators, such as the air exchange rate, ventilation rate (VR), and air stuffiness index (ICONE), that are linked to indoor CO2 concentration. The influences of the season (heating or non-heating), type of school (nursery or elementary), and ventilation on the IAQ were studied. Based on the minimum value of 4.2 l/s per person required by the French legislation for mechanically ventilated classrooms, 91% of the classrooms had insufficient ventilation. The VR was significantly higher in mechanically ventilated classrooms compared with naturally ventilated rooms. The correlations between IAQ and ventilation vary according to the location of the primary source of each pollutant (outdoor vs. indoor), and for an indoor source, whether it is associated with occupant activity or continuous emission.

  4. Transpired Solar Collector at NREL's Waste Handling Facility Uses Solar Energy to Heat Ventilation Air

    SciTech Connect

    2010-09-08

    The transpired solar collector was installed on NREL's Waste handling Facility (WHF) in 1990 to preheat ventilation air. The electrically heated WHF was an ideal candidate for the this technology - requiring a ventilation rate of 3,000 cubic feet per meter to maintain safe indoor conditions.

  5. Energy Efficiency for Heating, Ventilating, Air-Conditioning Instructors.

    ERIC Educational Resources Information Center

    Scharmann, Larry, Ed.; Lay, Gary, Ed.

    Intended primarily but not solely for use at the postsecondary level, this curriculum guide contains five units on energy efficiency that were designed to be incorporated into an existing program in heating, ventilating, and air-conditioning. The following topics are examined: how energy conservation pays, heating, ventilation, air-conditioning,…

  6. New Air Cleaning Strategies for Reduced Commercial Building Ventilation Energy ? FY11 Final Report

    SciTech Connect

    Sidheswaran, Meera; Destaillats, Hugo; Cohn, Sebastian; Sullivan, Douglas P.; Fisk, William J.

    2011-10-31

    The research carried out in this project focuses on developing novel volatile organic compounds (VOCs) air cleaning technologies needed to enable energy-saving reductions in ventilation rates. we targeted a VOC air cleaning system that could enable a 50% reduction in ventilation rates. In a typical commercial HVAC system that provides a mixture of recirculated and outdoor air, a VOC air cleaner in the supply airstream must have a 15% to 20% VOC removal efficiency to counteract a 50% reduction in outdoor air supply.

  7. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1... 45 times per hour and discharge no less than 4 m (approx. 13.1 ft) above the deck. Cargo Pumprooms...

  8. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... 21 Food and Drugs 4 2010-04-01 2010-04-01 false Ventilation, air filtration, air heating and cooling. 211.46 Section 211.46 Food and Drugs FOOD AND DRUG ADMINISTRATION, DEPARTMENT OF HEALTH AND HUMAN... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a)...

  9. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... 21 Food and Drugs 4 2011-04-01 2011-04-01 false Ventilation, air filtration, air heating and cooling. 211.46 Section 211.46 Food and Drugs FOOD AND DRUG ADMINISTRATION, DEPARTMENT OF HEALTH AND HUMAN... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a)...

  10. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... 21 Food and Drugs 4 2014-04-01 2014-04-01 false Ventilation, air filtration, air heating and cooling. 211.46 Section 211.46 Food and Drugs FOOD AND DRUG ADMINISTRATION, DEPARTMENT OF HEALTH AND HUMAN... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a)...

  11. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... 21 Food and Drugs 4 2012-04-01 2012-04-01 false Ventilation, air filtration, air heating and cooling. 211.46 Section 211.46 Food and Drugs FOOD AND DRUG ADMINISTRATION, DEPARTMENT OF HEALTH AND HUMAN... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a)...

  12. 4. VENTILATION FAN SHOWING RELATIVE POSITION IN THE AIR TUNNEL. ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    4. VENTILATION FAN SHOWING RELATIVE POSITION IN THE AIR TUNNEL. - Hot Springs National Park, Bathhouse Row, Ozark Bathhouse: Mechanical & Piping Systems, State Highway 7, 1 mile north of U.S. Highway 70, Hot Springs, Garland County, AR

  13. Enrichment of ventilation air methane (VAM) with carbon fiber composites.

    PubMed

    Bae, Jun-Seok; Su, Shi; Yu, Xin Xiang

    2014-05-20

    Treatment of ventilation air methane (VAM) with cost-effective technologies has been an ongoing challenge due to its high volumetric flow rate with low and variable methane concentrations. In this work, honeycomb monolithic carbon fiber composites were developed and employed to capture VAM with a large-scale test unit at various conditions such as VAM concentration, ventilation air (VA) flow rate, temperature, and purging fluids. Regardless of inlet VAM concentrations, methane was captured at almost 100%. To regenerate the composites, the initial vacuum swing followed by combined temperature and vacuum swing adsorption (TVSA) was applied. It was found that initial vacuum swing is a control step for the final methane concentration having 5 or 11 times the VAM enrichment by one-step adsorption, which is, to our knowledge, the best performance achieved in VAM enrichment technologies worldwide. Five-time enriched VAM can be utilized as a principle fuel for lean burn turbine. Also, it can be further enriched by second step adsorption to more than 25% which then can be used for commercially available gas engines. In this way, the final product can be out of the methane explosive range (5-15%). PMID:24787090

  14. Economizer system cost effectiveness: Accounting for the influence of ventilation rate on sick leave

    SciTech Connect

    Fisk, William J.; Seppanen, Olli; Faulkner, David; Huang, Joe

    2003-06-01

    This study estimated the health, energy, and economic benefits of an economizer ventilation control system that increases outside air supply during mild weather to save energy. A model of the influence of ventilation rate on airborne transmission of respiratory illnesses was used to extend the limited data relating ventilation rate with illness and sick leave. An energy simulation model calculated ventilation rates and energy use versus time for an office building in Washington, DC with fixed minimum outdoor air supply rates, with and without an economizer. Sick leave rates were estimated with the disease transmission model. In the modeled 72-person office building, our analyses indicate that the economizer reduces energy costs by approximately $2000 and, in addition, reduces sick leave. The financial benefit of the decrease in sick leave is estimated to be between $6,000 and $16,000. This modelling suggests that economizers are much more cost effective than currently recognized.

  15. Using a Ventilation Controller to Optimize Residential Passive Ventilation For Energy and Indoor Air Quality

    SciTech Connect

    Turner, William; Walker, Iain

    2014-08-01

    One way to reduce the energy impact of providing residential ventilation is to use passive and hybrid systems. However, these passive and hybrid (sometimes called mixed-mode) systems must still meet chronic and acute health standards for ventilation. This study uses a computer simulation approach to examine the energy and indoor air quality (IAQ) implications of passive and hybrid ventilation systems, in 16 California climate zones. Both uncontrolled and flow controlled passive stacks are assessed. A new hybrid ventilation system is outlined that uses an intelligent ventilation controller to minimise energy use, while ensuring chronic and acute IAQ standards are met. ASHRAE Standard 62.2-2010 – the United States standard for residential ventilation - is used as the chronic standard, and exposure limits for PM2.5, formaldehyde and NO2 are used as the acute standards.The results show that controlled passive ventilation and hybrid ventilation can be used in homes to provide equivalent IAQ to continuous mechanical ventilation, for less use of energy.

  16. The influence of air duct geometry on air jet direction in aircraft cabin ventilated by mixing ventilation.

    NASA Astrophysics Data System (ADS)

    Fišer, J.; Jícha, M.

    2013-04-01

    The paper deals with instigation of influence of air duct geometry on air jet direction in aircraft cabin ventilated by mixing ventilation. CFD approach was used for investigation and model geometry was based on small aircraft cabin mock-up geometry. Model was also equipped by nine seats and five manikins that represent passengers. The air jet direction was observed for selected ambient environment parameters and several types of air duct geometry and influence of main air duct geometry on jets direction is discussed. The model was created in StarCCM+ ver. 6.04.014 software and polyhedral mesh was used.

  17. Minute ventilation at different compression to ventilation ratios, different ventilation rates, and continuous chest compressions with asynchronous ventilation in a newborn manikin

    PubMed Central

    2012-01-01

    Background In newborn resuscitation the recommended rate of chest compressions should be 90 per minute and 30 ventilations should be delivered each minute, aiming at achieving a total of 120 events per minute. However, this recommendation is based on physiological plausibility and consensus rather than scientific evidence. With focus on minute ventilation (Mv), we aimed to compare today’s standard to alternative chest compression to ventilation (C:V) ratios and different ventilation rates, as well as to continuous chest compressions with asynchronous ventilation. Methods Two investigators performed cardiopulmonary resuscitation on a newborn manikin with a T-piece resuscitator and manual chest compressions. The C:V ratios 3:1, 9:3 and 15:2, as well as continuous chest compressions with asynchronous ventilation (120 compressions and 40 ventilations per minute) were performed in a randomised fashion in series of 10 × 2 minutes. In addition, ventilation only was performed at three different rates (40, 60 and 120 ventilations per minute, respectively). A respiratory function monitor measured inspiration time, tidal volume and ventilation rate. Mv was calculated for the different interventions and the Mann–Whitney test was used for comparisons between groups. Results Median Mv per kg in ml (interquartile range) was significantly lower at the C:V ratios of 9:3 (140 (134–144)) and 15:2 (77 (74–83)) as compared to 3:1 (191(183–199)). With ventilation only, there was a correlation between ventilation rate and Mv despite a negative correlation between ventilation rate and tidal volumes. Continuous chest compressions with asynchronous ventilation gave higher Mv as compared to coordinated compressions and ventilations at a C:V ratio of 3:1. Conclusions In this study, higher C:V ratios than 3:1 compromised ventilation dynamics in a newborn manikin. However, higher ventilation rates, as well as continuous chest compressions with asynchronous ventilation gave higher Mv

  18. Capture and Use of Coal Mine Ventilation Air Methane

    SciTech Connect

    Deborah Kosmack

    2008-10-31

    CONSOL Energy Inc., in conjunction with MEGTEC Systems, Inc., and the U.S. Department of Energy with the U.S. Environmental Protection Agency, designed, built, and operated a commercial-size thermal flow reversal reactor (TFRR) to evaluate its suitability to oxidize coal mine ventilation air methane (VAM). Coal mining, and particularly coal mine ventilation air, is a major source of anthropogenic methane emissions, a greenhouse gas. Ventilation air volumes are large and the concentration of methane in the ventilation air is low; thus making it difficult to use or abate these emissions. This test program was conducted with simulated coal mine VAM in advance of deploying the technology on active coal mine ventilation fans. The demonstration project team installed and operated a 30,000 cfm MEGTEC VOCSIDIZER oxidation system on an inactive coal mine in West Liberty, WV. The performance of the unit was monitored and evaluated during months of unmanned operation at mostly constant conditions. The operating and maintenance history and how it impacts the implementation of the technology on mine fans were investigated. Emission tests showed very low levels of all criteria pollutants at the stack. Parametric studies showed that the equipment can successfully operate at the design specification limits. The results verified the ability of the TFRR to oxidize {ge}95% of the low and variable concentration of methane in the ventilation air. This technology provides new opportunities to reduce greenhouse gas emissions by the reduction of methane emissions from coal mine ventilation air. A large commercial-size installation (180,000 cfm) on a single typical mine ventilation bleeder fan would reduce methane emissions by 11,000 to 22,100 short tons per year (the equivalent of 183,000 to 366,000 metric tonnes carbon dioxide).

  19. Air Distribution Effectiveness for Residential Mechanical Ventilation: Simulation and Comparison of Normalized Exposures

    SciTech Connect

    Petithuguenin, T.D.P.; Sherman, M.H.

    2009-05-01

    The purpose of ventilation is to dilute indoor contaminants that an occupant is exposed to. Even when providing the same nominal rate of outdoor air, different ventilation systems may distribute air in different ways, affecting occupants' exposure to household contaminants. Exposure ultimately depends on the home being considered, on source disposition and strength, on occupants' behavior, on the ventilation strategy, and on operation of forced air heating and cooling systems. In any multi-zone environment dilution rates and source strengths may be different in every zone and change in time, resulting in exposure being tied to occupancy patterns.This paper will report on simulations that compare ventilation systems by assessing their impact on exposure by examining common house geometries, contaminant generation profiles, and occupancy scenarios. These simulations take into account the unsteady, occupancy-tied aspect of ventilation such as bathroom and kitchen exhaust fans. As most US homes have central HVAC systems, the simulation results will be used to make appropriate recommendations and adjustments for distribution and mixing to residential ventilation standards such as ASHRAE Standard 62.2.This paper will report on work being done to model multizone airflow systems that are unsteady and elaborate the concept of distribution matrix. It will examine several metrics for evaluating the effect of air distribution on exposure to pollutants, based on previous work by Sherman et al. (2006).

  20. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... manufactured home. (d) Venting system terminations shall be not less than three feet from any motor-driven air... HOUSING AND URBAN DEVELOPMENT MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS Heating, Cooling and Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required...

  1. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... manufactured home. (d) Venting system terminations shall be not less than three feet from any motor-driven air... HOUSING AND URBAN DEVELOPMENT MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS Heating, Cooling and Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required...

  2. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... manufactured home. (d) Venting system terminations shall be not less than three feet from any motor-driven air... HOUSING AND URBAN DEVELOPMENT MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS Heating, Cooling and Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required...

  3. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... manufactured home. (d) Venting system terminations shall be not less than three feet from any motor-driven air... HOUSING AND URBAN DEVELOPMENT MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS Heating, Cooling and Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required...

  4. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... manufactured home. (d) Venting system terminations shall be not less than three feet from any motor-driven air... HOUSING AND URBAN DEVELOPMENT MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS Heating, Cooling and Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required...

  5. Heating, Ventilation, and Air Conditioning Series. Duty Task List.

    ERIC Educational Resources Information Center

    Oklahoma State Dept. of Vocational and Technical Education, Stillwater. Curriculum and Instructional Materials Center.

    This task list is intended for use in planning and/or evaluating a competency-based course in heating, ventilation, and air conditioning. The guide outlines the tasks entailed in eight different duties typically required of employees in the following occupations: residential installer, domestic refrigeration technician, air conditioning and…

  6. Feasibility of cooling emplacement drifts by ventilation air and effects of pre-cooling intake air by refrigeration

    SciTech Connect

    Yang, Hang; Bhattacharyya, K.K.

    1995-12-01

    This study evaluates effects of applying refrigerated air to cool emplacement drifts and provides a preliminary basis for future design analyses. Evaluations include impacts of airflow rates, intake air temperature, ventilation systems capability, and effectiveness of pre-cooling. Representative results provided from this study include the heat removal capability of ventilation air, effects of refrigerating intake air on continuous cooling, and effects of refrigerating intake air on rapid (blast cooling). It is possible to cool emplacement drifts within a reasonable time period, using airflow at ambient temperature is reasonable quantity. Refrigerating intake air can significantly reduce required cooling time or airflow rate, but it is inefficient as far as power consumption is concerned.

  7. Heat Recovery Ventilation for Housing: Air-to-Air Heat Exchangers.

    ERIC Educational Resources Information Center

    Corbett, Robert J.; Miller, Barbara

    The air-to-air heat exchanger (a fan powered ventilation device that recovers heat from stale outgoing air) is explained in this six-part publication. Topic areas addressed are: (1) the nature of air-to-air heat exchangers and how they work; (2) choosing and sizing the system; (3) installation, control, and maintenance of the system; (4) heat…

  8. Are Ventilation Filters Degrading Indoor Air Quality in California Classrooms?

    SciTech Connect

    Fisk, William J.; Destaillats, H.; Apte, M.G.; Destaillats,, Hugo; Fisk, Michael G. Apte and William J.

    2008-10-01

    Heating, ventilating, and cooling classrooms in California consume substantial electrical energy. Indoor air quality (IAQ) in classrooms affects studenthealth and performance. In addition to airborne pollutants that are emitted directly by indoor sources and those generated outdoors, secondary pollutants can be formed indoors by chemical reaction of ozone with other chemicals and materials. Filters are used in nearly all classroom heating, ventilation and air?conditioning (HVAC) systems to maintain energy-efficient HVAC performance and improve indoor air quality; however, recent evidence indicates that ozone reactions with filters may, in fact, be a source of secondary pollutants. This project quantitatively evaluated ozone deposition in HVAC filters and byproduct formation, and provided a preliminary assessment of the extent towhich filter systems are degrading indoor air quality. The preliminary information obtained will contribute to the design of subsequent research efforts and the identification of energy efficient solutions that improve indoor air quality in classrooms and the health and performance of students.

  9. Ventilation Rates and Airflow Pathways in Patient Rooms: A Case Study of Bioaerosol Containment and Removal.

    PubMed

    Mousavi, Ehsan S; Grosskopf, Kevin R

    2015-11-01

    Most studies on the transmission of infectious airborne disease have focused on patient room air changes per hour (ACH) and how ACH provides pathogen dilution and removal. The logical but mostly unproven premise is that greater air change rates reduce the concentration of infectious particles and thus, the probability of airborne disease transmission. Recently, a growing body of research suggests pathways between pathogenic source (patient) and control (exhaust) may be the dominant environmental factor. While increases in airborne disease transmission have been associated with ventilation rates below 2 ACH, comparatively less data are available to quantify the benefits of higher air change rates in clinical spaces. As a result, a series of tests were conducted in an actual hospital to observe the containment and removal of respirable aerosols (0.5-10 µm) with respect to ventilation rate and directional airflow in a general patient room, and, an airborne infectious isolation room. Higher ventilation rates were not found to be proportionately effective in reducing aerosol concentrations. Specifically, increasing mechanical ventilation from 2.5 to 5.5 ACH reduced aerosol concentrations only 30% on average. However, particle concentrations were more than 40% higher in pathways between the source and exhaust as was the suspension and migration of larger particles (3-10 µm) throughout the patient room(s). Computational analyses were used to validate the experimental results, and, to further quantify the effect of ventilation rate on exhaust and deposition removal in patient rooms as well as other particle transport phenomena.

  10. Transpired Solar Collector at NREL's Waste Handling Facility Uses Solar Energy to Heat Ventilation Air (Fact Sheet)

    SciTech Connect

    Not Available

    2010-09-01

    The transpired solar collector was installed on NREL's Waste handling Facility (WHF) in 1990 to preheat ventilation air. The electrically heated WHF was an ideal candidate for the this technology - requiring a ventilation rate of 3,000 cubic feet per meter to maintain safe indoor conditions.

  11. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... 30 Mineral Resources 1 2013-07-01 2013-07-01 false Quantity of ventilating air. 36.45 Section 36.45 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR TESTING, EVALUATION, AND APPROVAL OF MINING PRODUCTS APPROVAL REQUIREMENTS FOR PERMISSIBLE MOBILE DIESEL-POWERED TRANSPORTATION EQUIPMENT Test Requirements §...

  12. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... 30 Mineral Resources 1 2014-07-01 2014-07-01 false Quantity of ventilating air. 36.45 Section 36.45 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR TESTING, EVALUATION... constituents in the diluted mixture shall not exceed: 0.25 percent, by volume, of carbon dioxide (CO2)....

  13. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... removed. It must be conducted as part of a miner's 30 CFR part 48 new miner training (§ 48.5), experienced... 30 Mineral Resources 1 2014-07-01 2014-07-01 false Belt air course ventilation. 75.350 Section 75.350 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR COAL MINE SAFETY...

  14. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... 30 Mineral Resources 1 2012-07-01 2012-07-01 false Quantity of ventilating air. 36.45 Section 36.45 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR TESTING, EVALUATION, AND APPROVAL OF MINING PRODUCTS APPROVAL REQUIREMENTS FOR PERMISSIBLE MOBILE DIESEL-POWERED TRANSPORTATION EQUIPMENT Test Requirements §...

  15. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2011 CFR

    2011-07-01

    ... 30 Mineral Resources 1 2011-07-01 2011-07-01 false Quantity of ventilating air. 36.45 Section 36.45 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR TESTING, EVALUATION... constituents in the diluted mixture shall not exceed: 0.25 percent, by volume, of carbon dioxide (CO2)....

  16. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2010 CFR

    2010-07-01

    ... 30 Mineral Resources 1 2010-07-01 2010-07-01 false Quantity of ventilating air. 36.45 Section 36.45 Mineral Resources MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR TESTING, EVALUATION... constituents in the diluted mixture shall not exceed: 0.25 percent, by volume, of carbon dioxide (CO2)....

  17. State Skill Standards: Heating, Ventilation, Air Conditioning, and Refrigeration

    ERIC Educational Resources Information Center

    Ball, Larry; Soukup, Dennis

    2006-01-01

    The Department of Education has undertaken an ambitious effort to develop statewide career and technical education skill standards. The standards in this document are for Heating, Ventilation, Air Conditioning and Refrigeration (HVAC&R) programs and are designed to clearly state what the student should know and be able to do upon completion of an…

  18. Heating, Ventilating, and Air Conditioning. Energy Technology Series.

    ERIC Educational Resources Information Center

    Center for Occupational Research and Development, Inc., Waco, TX.

    This course in heating, ventilating, and air conditioning is one of 16 courses in the Energy Technology Series developed for an Energy Conservation-and-Use Technology curriculum. Intended for use in two-year postsecondary technical institutions to prepare technicians for employment, the courses are also useful in industry for updating employees in…

  19. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... removed. It must be conducted as part of a miner's 30 CFR part 48 new miner training (§ 48.5), experienced... except as provided in paragraph (c) of this section. (2) Effective December 31, 2009, the air velocity in... manager may approve lower velocities in the ventilation plan based on specific mine conditions....

  20. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... removed. It must be conducted as part of a miner's 30 CFR part 48 new miner training (§ 48.5), experienced... except as provided in paragraph (c) of this section. (2) Effective December 31, 2009, the air velocity in... manager may approve lower velocities in the ventilation plan based on specific mine conditions....

  1. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2010 CFR

    2010-07-01

    ... removed. It must be conducted as part of a miner's 30 CFR part 48 new miner training (§ 48.5), experienced... except as provided in paragraph (c) of this section. (2) Effective December 31, 2009, the air velocity in... manager may approve lower velocities in the ventilation plan based on specific mine conditions....

  2. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2011 CFR

    2011-07-01

    ... removed. It must be conducted as part of a miner's 30 CFR part 48 new miner training (§ 48.5), experienced... except as provided in paragraph (c) of this section. (2) Effective December 31, 2009, the air velocity in... manager may approve lower velocities in the ventilation plan based on specific mine conditions....

  3. Building America Top Innovations 2012: Outside Air Ventilation Controller

    SciTech Connect

    none,

    2013-01-01

    venThis Building America Top Innovations profile describes Building America research showing how automated night ventilation can reduce cooling energy costs up to 40% and peak demand up to 50% in California’s hot-dry central valley climates and can eliminate the need for air conditioning altogether in the coastal marine climate.

  4. Assessment of a carbon dioxide controller for residential ventilation and indoor air quality management. Final report

    SciTech Connect

    Koontz, M.D.; Burruss, R.P.; Cade, D.R.

    1995-05-01

    Indoor air quality can be adversely affected by combinations of building materials, furniture, consumer products, and by such activities as cooking. Acceptable indoor air quality (IAQ) can be achieved by management of pollutant sources or by various modes of controlled or uncontrolled ventilation. Control of pollutant sources can often be difficult to achieve; however, increased ventilation can generally reduce concentrations of all indoor pollutants, usually to levels established by ASHRAE Standard 62-1989 which specifies acceptable levels of major indoor pollutants as well as ventilation rates for specific types of occupied spaces. Increased ventilation, however, is often done at a penalty of increased domestic energy use for heating and cooling. Ventilation systems which can satisfy the ASHRAE standard can save energy if they do not operate when the house is vacant. Among possible ventilation control methods are carbon dioxide based sensors which can detect human presence. Carbon dioxide (CO{sub 2}) can also be used as a surrogate indicator of general IAQ. Tests of a CO{sub 2}-controlled energy recovery ventilator (ERV) were performed in two houses (one in Florida, one in Maryland) to evaluate the effectiveness of CO{sub 2} as the triggering parameter for controlling an ERV. Concentrations of selected indoor air pollutants were examined as a function of ERV operation. Effects of ERV-forced air exchange rates on energy consumption for heating or cooling were also monitored. Simulated occupancy of each house was achieved by programmed injection of CO{sub 2}. Indoor and outdoor concentrations of such pollutants as formaldehyde, volatile organic compounds and radon were also monitored. Domestic heating (or cooling) energy consumption was monitored. Patterns of energy use and indoor pollutant concentrations were compared during periods of ERV use to periods of ERV non-use.

  5. Should Title 24 Ventilation Requirements Be Amended to include an Indoor Air Quality Procedure?

    SciTech Connect

    Dutton, Spencer M.; Mendell, Mark J.; Chan, Wanyu R.

    2013-05-13

    Minimum outdoor air ventilation rates (VRs) for buildings are specified in standards, including California?s Title 24 standards. The ASHRAE ventilation standard includes two options for mechanically-ventilated buildings ? a prescriptive ventilation rate procedure (VRP) that specifies minimum VRs that vary among occupancy classes, and a performance-based indoor air quality procedure (IAQP) that may result in lower VRs than the VRP, with associated energy savings, if IAQ meeting specified criteria can be demonstrated. The California Energy Commission has been considering the addition of an IAQP to the Title 24 standards. This paper, based on a review of prior data and new analyses of the IAQP, evaluates four future options for Title 24: no IAQP; adding an alternate VRP, adding an equivalent indoor air quality procedure (EIAQP), and adding an improved ASHRAE-like IAQP. Criteria were established for selecting among options, and feedback was obtained in a workshop of stakeholders. Based on this review, the addition of an alternate VRP is recommended. This procedure would allow lower minimum VRs if a specified set of actions were taken to maintain acceptable IAQ. An alternate VRP could also be a valuable supplement to ASHRAE?s ventilation standard.

  6. 10 CFR 429.43 - Commercial heating, ventilating, air conditioning (HVAC) equipment.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... 10 Energy 3 2012-01-01 2012-01-01 false Commercial heating, ventilating, air conditioning (HVAC... Commercial heating, ventilating, air conditioning (HVAC) equipment. (a) Sampling plan for selection of units... each basic model of commercial heating, ventilating, air conditioning (HVAC) equipment, efficiency...

  7. 10 CFR 429.43 - Commercial heating, ventilating, air conditioning (HVAC) equipment.

    Code of Federal Regulations, 2013 CFR

    2013-01-01

    ... 10 Energy 3 2013-01-01 2013-01-01 false Commercial heating, ventilating, air conditioning (HVAC... Commercial heating, ventilating, air conditioning (HVAC) equipment. (a) Sampling plan for selection of units... each basic model of commercial heating, ventilating, air conditioning (HVAC) equipment, efficiency...

  8. Worker productivity and ventilation rate in a call center: Analyses of time-series data for a group of workers

    SciTech Connect

    Fisk, William J.; Price, Phillip; Faulkner, David; Sullivan, Douglas; Dibartolomeo, Dennis; Federspiel, Cliff; Liu, Gang; Lahiff, Maureen

    2002-01-01

    In previous studies, increased ventilation rates and reduced indoor carbon dioxide concentrations have been associated with improvements in health at work and increased performance in work-related tasks. Very few studies have assessed whether ventilation rates influence performance of real work. This paper describes part one of a two-part analysis from a productivity study performed in a call center operated by a health maintenance organization. Outside air ventilation rates were manipulated, indoor air temperatures, humidities, and carbon dioxide concentrations were monitored, and worker performance data for advice nurses, with 30-minute resolution, were analyzed via multivariate linear regression to look for an association of performance with building ventilation rate, or with indoor carbon dioxide concentration (which is related to ventilation rate per worker). Results suggest that the effect of ventilation rate on worker performance in this call center was very small (probably less than 1%) or nil, over most of the range of ventilation rate experienced during the study (roughly 12 L s{sup -1} to 48 L s{sup -1} per person). However, there is some evidence suggesting performance improvements of 2% or more when the ventilation rate per person is very high, as indicated by indoor CO{sub 2} concentrations exceeding outdoor concentrations by less than 75 ppm.

  9. Metabolically Derived human ventilation rates: A revised approach based upon oxygen consumption rates (Final Report) 2009

    EPA Science Inventory

    The purpose of this report is to provide a revised approach for calculating an individual's ventilation rate directly from their oxygen consumption rate. This revised approach will be used to update the ventilation rate information in the Exposure Factors Handbook, which serve as...

  10. [New operating rooms: problems related with ventilation and air quality].

    PubMed

    Sabbadini, M; Verga, M; Boglioni, R; Zotti, A

    2002-01-01

    Realizing the project of the new operating theatres, We bring out the importance of creating bright environments, rational and wide ways, a good indoor air quality, thermal comfort and occupational hygiene. Therefore for the first time We've installed an automatic system for permanent monitoring of gases, vapours and particles, associated with the study of ventilation, to evaluate the real condition of the mantenance and of staff behaviour.

  11. Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information.

    PubMed

    Daisey, J M; Angell, W J; Apte, M G

    2003-03-01

    We reviewed the literature on Indoor Air Quality (IAQ), ventilation, and building-related health problems in schools and identified commonly reported building-related health symptoms involving schools until 1999. We collected existing data on ventilation rates, carbon dioxide (CO2) concentrations and symptom-relevant indoor air contaminants, and evaluated information on causal relationships between pollutant exposures and health symptoms. Reported ventilation and CO2 data strongly indicate that ventilation is inadequate in many classrooms, possibly leading to health symptoms. Adequate ventilation should be a major focus of design or remediation efforts. Total volatile organic compounds, formaldehyde (HCHO) and microbiological contaminants are reported. Low HCHO concentrations were unlikely to cause acute irritant symptoms (<0.05 ppm), but possibly increased risks for allergen sensitivities, chronic irritation, and cancer. Reported microbiological contaminants included allergens in deposited dust, fungi, and bacteria. Levels of specific allergens were sufficient to cause symptoms in allergic occupants. Measurements of airborne bacteria and airborne and surface fungal spores were reported in schoolrooms. Asthma and 'sick building syndrome' symptoms are commonly reported. The few studies investigating causal relationships between health symptoms and exposures to specific pollutants suggest that such symptoms in schools are related to exposures to volatile organic compounds (VOCs), molds and microbial VOCs, and allergens. PMID:12608926

  12. 1. LEPLEY VENTILATOR FROM WEST. AEROVANE FAN AND AIR/MANWAY SHAFT ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    1. LEPLEY VENTILATOR FROM WEST. AEROVANE FAN AND AIR/MANWAY SHAFT AT LEFT, CIRCULAR SHAFT AND SCAFFOLD AT RIGHT REAR. - Consolidation Coal Company Mine No. 11, Lepley Ventilator, East side of State Route 936, Midlothian, Allegany County, MD

  13. Optimization of Ventilation Energy Demands and Indoor Air Quality in High-Performance Homes

    SciTech Connect

    Hun, Diana E; Jackson, Mark C; Shrestha, Som S

    2014-01-01

    High-performance homes require that ventilation energy demands and indoor air quality (IAQ) be simultaneously optimized. We attempted to bridge these two areas by conducting tests in a research house located in Oak Ridge, TN, that was 20 months old, energy-efficient (i.e., expected to consume 50% less energy than a house built per the 2006 IRC), tightly-built (i.e., natural ventilation rate ~0.02 h-1), unoccupied, and unfurnished. We identified air pollutants of concern in the test home that could generally serve as indicators of IAQ, and conduced field experiments and computer simulations to determine the effectiveness and energy required by various techniques that lessened the concentration of these contaminants. Formaldehyde was selected as the main pollutant of concern among the contaminants that were sampled in the initial survey because it was the only compound that showed concentrations that were greater than the recommended exposure levels. Field data indicate that concentrations were higher during the summer primarily because emissions from sources rise with increases in temperature. Furthermore, supply ventilation and gas-phase filtration were effective means to reduce formaldehyde concentrations; however, exhaust ventilation had minimal influence on this pollutant. Results from simulations suggest that formaldehyde concentrations obtained while ventilating per ASHRAE 62.2-2010 could be decreased by about 20% from May through September through three strategies: 1) increasing ASHRAE supply ventilation by a factor of two, 2) reducing the thermostat setpoint from 76 to 74 F, or 3) running a gas-phase filtration system while decreasing supply ventilation per ASHRAE by half. In the mixed-humid climate of Oak Ridge, these strategies caused increases in electricity cost of ~$5 to ~$15/month depending on outdoor conditions.

  14. Indoor ozone concentrations: Ventilation rate impacts and mechanisms of outdoor concentration attenuation

    SciTech Connect

    Cano-Ruiz, J.A.; Modera, M.P.; Nazaroff, W.W.

    1992-07-01

    The classification of outdoor (ambient) air as fresh for the purposes of ventilation is not always appropriate, particularly in urban areas. In many cities of the world, urban air frequently violates health-based air quality standards due to high ozone concentrations. The degree of protection from exposure to ozone offered by the indoor environment depends on the relationship between indoor and outdoor ozone levels. Existing concentration data indicates that indoor/outdoor ozone ratios range between 10 and 80%. This paper analyzes several of the key issues influencing indoor ozone concentrations, including: (1) the degree of penetration of outdoor ozone indoors, (2) removal within the indoor environment (removal at surfaces and within air distribution systems), and (3) the correlation in time between outdoor ozone levels and ventilation rates. A model for calculating the degree of ozone removal in typical building leaks and air distribution systems is described and applied to a range of typical cases. This model indicates that the degree of removal is minimal for most wooden building cracks, but could be significant in leaks in concrete or brick structures, and is strongly dependent on the lining material for air distribution systems. Indoor ozone exposure estimates based on hourly outdoor ozone monitoring data and hour-by-hour weather-based simulations of infiltration rates and building operation are reported for a few residential scenarios. These estimates serve as a basis for exploring the impact of energy-efficient ventilation strategies on indoor ozone exposures.

  15. Simulation of air quality and cost to ventilate swine farrowing facilities in winter

    PubMed Central

    Park, Jae Hong; Peters, Thomas M.; Altmaier, Ralph; Sawvel, Russell A.; Anthony, T. Renée

    2016-01-01

    We developed a simulation model to study the effect of ventilation airflow rate with and without filtered recirculation on airborne contaminant concentrations (dust, NH3, CO, and CO2) for swine farrowing facilities. Energy and mass balance equations were used to simulate the indoor air quality and operational cost for a variety of ventilation conditions over a 3-month winter period, using time-varied outdoor temperature. The sensitivity of input and output parameters on indoor air quality and operational cost were evaluated. Significant factors affecting model output included mean winter temperature, generation rate of contaminants, pit-air-exchange ratio, and recirculation ratio. As mean outdoor temperature was decreased from −2.5 °C to −12.5 °C, total operational costs were increased from $872 to $1304. Dust generation rate affected dust concentrations linearly. When dust generation rates changed −50% and +100% from baseline, indoor dust concentrations were changed −50% and +100%, respectively. The selection of a pit-air-exchange ratio was found critical to NH3 concentration, but has little impact on other contaminants or cost. As the pit-air-exchange ratio was increased from 0.1 to 0.3, the NH3 concentration was increased by a factor of 1.5. The recirculation ratio affected both IAQ factors and total operational cost. As the recirculation ratio decreased to 0, inhalable and respirable dust concentrations, humidity, NH3 and CO2 concentrations decreased and total operational cost ($2216) was 104% more than with pit-fan-only ventilation ($1088). When the recirculation ratio was 1, the total operational cost was increased by $573 (53%) compared to pit-fan-only. Simulation provides a useful tool for examining the costs and benefits to installing common ventilation technology to CAFO and, ultimately, making sound management decisions. PMID:26937062

  16. Quantitative relationship of sick building syndrome symptoms with ventilation rates

    EPA Science Inventory

    Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence in office workers with ventilation rate. For each study, slopes were calculated, representing the fractional...

  17. CAN SORBENT-BASED GAS PHASE AIR CLEANING FOR VOCS SUBSTITUTE FOR VENTILATION IN COMMERCIAL BUILDINGS?

    SciTech Connect

    Fisk, William; Fisk, William J.

    2007-08-01

    This paper reviews current knowledge about the suitability of sorbent-based air cleaning for removing volatile organic compounds (VOCs) from the air in commercial buildings, as needed to enable reductions in ventilation rates and associated energy savings. The principles of sorbent air cleaning are introduced, criteria are suggested for sorbent systems that can counteract indoor VOC concentration increases from reduced ventilation, major findings from research on sorbent performance for this application are summarized, and related priority research needs are identified. Major conclusions include: sorbent systems can remove a broad range of VOCs with moderate to high efficiency, sorbent technologies perform effectively when challenged with VOCs at the low concentrations present indoors, and there is a large uncertainty about the lifetime and associated costs of sorbent air cleaning systems when used in commercial buildings for indoor VOC control. Suggested priority research includes: experiments to determine sorbent system VOC removal efficiencies and lifetimes considering the broad range and low concentration of VOCs indoors; evaluations of in-situ regeneration of sorbents; and an updated analysis of the cost of sorbent air cleaning relative to the cost of ventilation.

  18. Development of an air-bearing fan for space extravehicular activity (EVA) suit ventilation

    NASA Technical Reports Server (NTRS)

    Fukumoto, Paul; Allen, Norman; Stonesifer, Greg

    1992-01-01

    A high-speed/variable flow fan has been developed for EVA suit ventilation which combines air bearings with a two-pole, toothless permanent-magnet motor. The fan has demonstrated quiet and vibration-free operation and a 2:1 range in flow rate variation. System weight is 0.9 kg, and input powers range from 12.4 to 42 W.

  19. Circulatory effects of fast ventilator rates in preterm infants.

    PubMed Central

    Fenton, A C; Field, D J; Woods, K L; Evans, D H; Levene, M I

    1990-01-01

    High frequency positive pressure ventilation has been suggested to result in a lower incidence of respiratory complications in preterm infants with idiopathic respiratory distress syndrome compared with ventilation at conventional rates. A possible disadvantage is compromise of the infant's cardiovascular condition secondary to inadvertent positive end expiratory pressure (PEEP). In a group of 20 such infants treated with high frequency positive pressure ventilation (rates of up to 100/minute) and analysed, changes in arterial blood pressure and cerebral blood flow velocity were largely influenced by changes in arterial blood gases, and no effect could be attributed to inadvertent PEEP. In addition, the observed fall in both arterial carbon dioxide and oxygen tensions could be readily predicted for theoretical reasons. Under certain conditions at the fastest rates used, cerebral blood flow velocity was significantly influenced by changes in blood pressure, which may indicate impaired cerebrovascular regulation. Though other factors (such as the severity of the infants' illness or the use of paralysis) may have been responsible for this apparent blood pressure passivity, the role of high frequency positive pressure ventilation in such infants warrants further study. PMID:2117423

  20. Evaluation of thermal formation and air ventilation inside footwear during gait: The role of gait and fitting.

    PubMed

    Shimazaki, Yasuhiro; Matsutani, Toshiki; Satsumoto, Yayoi

    2016-07-01

    Comfort is an important concept in footwear design. The microclimate inside footwear contributes to the perception of thermal comfort. To investigate the effect of ventilation on microclimate formation inside footwear, experiments with subjects were conducted at four gait speeds with three different footwear sizes. Skin temperature, metabolism, and body mass were measured at approximately 25 °C and 50% relative humidity, with no solar radiation and a calm wind. The footwear occupancy and ventilation rate were also estimated, with the latter determined using the tracer gas method. The experimental results revealed that foot movement, metabolism, evaporation, radiation, convection, and ventilation were the main factors influencing the energy balance for temperature formation on the surface of the foot. The cooling effect of ventilation on the arch temperature was observed during gait. The significance of the amount of air space and ventilation on the improvement in the thermal comfort of footwear was clarified.

  1. Evaluation of thermal formation and air ventilation inside footwear during gait: The role of gait and fitting.

    PubMed

    Shimazaki, Yasuhiro; Matsutani, Toshiki; Satsumoto, Yayoi

    2016-07-01

    Comfort is an important concept in footwear design. The microclimate inside footwear contributes to the perception of thermal comfort. To investigate the effect of ventilation on microclimate formation inside footwear, experiments with subjects were conducted at four gait speeds with three different footwear sizes. Skin temperature, metabolism, and body mass were measured at approximately 25 °C and 50% relative humidity, with no solar radiation and a calm wind. The footwear occupancy and ventilation rate were also estimated, with the latter determined using the tracer gas method. The experimental results revealed that foot movement, metabolism, evaporation, radiation, convection, and ventilation were the main factors influencing the energy balance for temperature formation on the surface of the foot. The cooling effect of ventilation on the arch temperature was observed during gait. The significance of the amount of air space and ventilation on the improvement in the thermal comfort of footwear was clarified. PMID:26611985

  2. A simplified model for estimating population-scale energy impacts of building envelope air-tightening and mechanical ventilation retrofits

    SciTech Connect

    Logue, J. M.; Turner, W. J.N.; Walker, I. S.; Singer, B. C.

    2015-07-01

    Changing the air exchange rate of a home (the sum of the infiltration and mechanical ventilation airflow rates) affects the annual thermal conditioning energy. Large-scale changes to air exchange rates of the housing stock can significantly alter the residential sector’s energy consumption. However, the complexity of existing residential energy models is a barrier to the accurate quantification of the impact of policy changes on a state or national level.

  3. Air compressor battery duration with mechanical ventilation in a field anesthesia machine.

    PubMed

    Szpisjak, Dale F; Giberman, Anthony A

    2015-05-01

    Compressed air to power field anesthesia machine ventilators may be supplied by air compressor with battery backup. This study determined the battery duration when the compPAC ventilator's air compressor was powered by NiCd battery to ventilate the Vent Aid Training Test Lung modeling high (HC = 0.100 L/cm H2O) and low (LC = 0.020 L/cm H2O) pulmonary compliance. Target tidal volumes (VT) were 500, 750, and 1,000 mL. Respiratory rate = 10 bpm, inspiratory-to-expiratory time ratio = 1:2, and fresh gas flow = 1 L/min air. N = 5 in each group. Control limits were determined from the first 150 minutes of battery power for each run and lower control limit = mean VT - 3SD. Battery depletion occurred when VT was below the lower control limit. Battery duration ranged from 185.8 (±3.2) minutes in the LC-1000 group to 233.3 (±3.6) minutes in the HC-750 group. Battery duration of the LC-1000 group was less than all others (p = 0.027). The differences among the non-LC-1000 groups were not clinically significant.

  4. Effect of cabin ventilation rate on ultrafine particle exposure inside automobiles.

    PubMed

    Knibbs, Luke D; de Dear, Richard J; Morawska, Lidia

    2010-05-01

    We alternately measured on-road and in-vehicle ultrafine (<100 nm) particle (UFP) concentration for 5 passenger vehicles that comprised an age range of 18 years. A range of cabin ventilation settings were assessed during 301 trips through a 4 km road tunnel in Sydney, Australia. Outdoor air flow (ventilation) rates under these settings were quantified on open roads using tracer gas techniques. Significant variability in tunnel trip average median in-cabin/on-road (I/O) UFP ratios was observed (0.08 to approximately 1.0). Based on data spanning all test automobiles and ventilation settings, a positive linear relationship was found between outdoor air flow rate and I/O ratio, with the former accounting for a substantial proportion of variation in the latter (R(2) = 0.81). UFP concentrations recorded in-cabin during tunnel travel were significantly higher than those reported by comparable studies performed on open roadways. A simple mathematical model afforded the ability to predict tunnel trip average in-cabin UFP concentrations with good accuracy. Our data indicate that under certain conditions, in-cabin UFP exposures incurred during tunnel travel may contribute significantly to daily exposure. The UFP exposure of automobile occupants appears strongly related to their choice of ventilation setting and vehicle. PMID:20369882

  5. Reduction of sound in ventilation and similar air distribution systems

    NASA Astrophysics Data System (ADS)

    1982-07-01

    This Data Item is available as part of the ESDU Sub-series on Fluid Mechanics Internal Flow. A means of estimating the attenuation of sound in lined plenum chambers and ducts, and through silencers of the types used in ventilation and air-conditioning systems is given. Data are provided in graphical or tabular form for the estimation of typical silencer insertion loss, airflow generated noise and pressure loss. Both rectangular splitter silencers and cylindrical silencers are considered. The data may be used in the initial design of a system or to investigate the appropriate remedial action for an installed air distribution system that is found to be too noisy. The location of silencers in the duct system is considered, and an example is given to illustrate the use of the data provided in the selection and sizing of a silencer for a particular application.

  6. Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings.

    PubMed

    Seppänen, O A; Fisk, W J; Mendell, M J

    1999-12-01

    This paper reviews current literature on the associations of ventilation rates and carbon dioxide concentrations in non-residential and non-industrial buildings (primarily offices) with health and other human outcomes. Twenty studies, with close to 30,000 subjects, investigated the association of ventilation rates with human responses, and 21 studies, with over 30,000 subjects, investigated the association of carbon dioxide concentration with these responses. Almost all studies found that ventilation rates below 10 Ls-1 per person in all building types were associated with statistically significant worsening in one or more health or perceived air quality outcomes. Some studies determined that increases in ventilation rates above 10 Ls-1 per person, up to approximately 20 Ls-1 per person, were associated with further significant decreases in the prevalence of sick building syndrome (SBS) symptoms or with further significant improvements in perceived air quality. The carbon dioxide studies support these findings. About half of the carbon dioxide studies suggest that the risk of sick building syndrome symptoms continued to decrease significantly with decreasing carbon dioxide concentrations below 800 ppm. The ventilation studies reported relative risks of 1.5-2 for respiratory illnesses and 1.1-6 for sick building syndrome symptoms for low compared to high low ventilation rates. PMID:10649857

  7. Ventilation or filtration? The use of gas-phase air filtration for compliance with ASHRAE Standard 62

    SciTech Connect

    Muller, C.O.; Friedman, A.B.

    1997-09-01

    ASHRAE Standard 62, in its current form, employs two procedures to provide acceptable indoor air quality (IAQ) in buildings. These are the Ventilation Rate and Indoor Air Quality (IAQ) Procedures. This standard further endeavors to achieve the necessary balance between IAQ and energy consumption by specifying minimum ventilation rates and IAQ that will be acceptable to human occupants. The Ventilation Rate Procedure provides only an indirect solution for the control of indoor contaminants. While it does allow for the use of cleaned, recirculated air, it does not allow the use of this air is to be used to reduce the amount of outdoor air required, or for the implementation of energy conservation measures, the IAQ Procedure must be used. The IAQ Procedure provides a direct solution by reducing and controlling the concentrations of air contaminants, through air cleaning, to specified levels. This procedure allows for both quantitative and subjective evaluation of the effectiveness of the air cleaning method(s) employed. The standard acknowledges that air cleaning, along with recirculation, is an effective means for controlling contaminants when using the IAQ Procedure.

  8. 10 CFR 429.43 - Commercial heating, ventilating, air conditioning (HVAC) equipment.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... 10 Energy 3 2014-01-01 2014-01-01 false Commercial heating, ventilating, air conditioning (HVAC... Commercial heating, ventilating, air conditioning (HVAC) equipment. Link to an amendment published at 78 FR... § 429.11 are applicable to commercial HVAC equipment; and (2) For each basic model of commercial...

  9. Influence of Ventilation Ratio on Desiccant Air Conditioning System's Efficiency Performance

    NASA Astrophysics Data System (ADS)

    Tran, Thien Nha; Akisawa, Atsushi; Kashiwagi, Takao; Hamamoto, Yoshinori

    Ventilation air is a concern for engineers since ventilated air controls indoor air contamination; additional ventilation, however, increases the energy consumption of buildings. The study investigates the energy efficiency performance of the desiccant dehumidification air conditioning system in the context of ventilation for a hot-humid climate such as summer in Japan. The investigation focuses on the variable ratio of ventilation air as required by the application of air conditioning system. The COP of the desiccant air conditioning system is determined. The evaluation is subsequently performed by comparing the desiccant based system with the conventional absorption cooling system and the vapor compression cooling system. Based on 12 desiccant rotor simulations, it is found that the desiccant regeneration temperature required varies between 47°C to 85°C as ventilation ratio increases from 0. 0 to 100%, and up to 52. 5°C as the ventilation ratio achieves 14%. The heat required for regenerating desiccant accounts for 55% and higher of the system's total heat consumption; the system is expected to be energy efficient by using wasted heat from the absorption chiller for desiccant regeneration; and its energy efficiency expands as the ratio of ventilation air rises above 15% compared with the conventional absorption cooling system. The energy efficiency also benefits as the ratio rises beyond 70% against the conventional vapor compression cooling system.

  10. Field Test of Room-to-Room Uniformity of Ventilation Air Distribution in Two New Houses

    SciTech Connect

    Hendron, Robert; Anderson, Ren; Barley, Dennis; Rudd, Armin; Townsend, Aaron; Hancock, Ed

    2006-12-01

    This report describes a field test to characterize the uniformity of room-to-room ventilation air distribution under various operating conditions by examining multi-zone tracer gas decay curves and calculating local age-of-air.

  11. An evaluation of ventilation system flow rates and levels of carbon dioxide, ambient temperature, and relative humidity in restaurants.

    PubMed

    Akbar-Khanzadeh, Farhang; Tan, Yin; Brown, Eric N; Akbar-Khanzadeh, Mahboubeh

    2002-09-01

    Studies of the indoor air quality of restaurants have rarely focused on ventilation system performance in relation to air pollutants and climatic factors. This study was conducted in eight restaurants to examine this issue by determining the ventilation flow rates and the levels of carbon dioxide (CO2), ambient temperature, and relative humidity during at least one complete shift of serving a meal. The mean values of number of dining patrons, ventilation flow rates, and the levels of CO2, ambient temperature, and relative humidity were not significantly different in the nonsmoking dining rooms and the smoking dining rooms. The mean ventilation flow rates in individual restaurants ranged from 42-113 cubic feet per minute per person (cfm/person), overall exceeding the recommended lower limit of 30 cfm/person. The mean levels of CO2 in two restaurants (646 and 819 ppm) were below, and in the other six restaurants (ranging 1,012-1,820 ppm) were above the recommended upper limit of 1000 ppm. The levels of CO2 in each restaurant significantly correlated with the number of dining patrons and in four restaurants accumulated gradually over time. In the nonsmoking dining rooms, the levels of CO2 increased significantly as the ventilation How rates decreased. The mean ambient temperature in restaurants (ranging from 22 degrees C - 24 degrees C) were within the recommended range of 20 degrees C - 26 degrees C. The mean relative humidity in six restaurants (ranging from 46%-59%) were within the recommended upper limit of 60 percent, and in two restaurants (62% and 71%) were slightly higher than this recommended limit. It was concluded that although the mean ventilation flow rates in all restaurants exceeded the recommended value, the design of the ventilation system or the distribution of air flow rate in some sections of restaurants were not appropriate to keep the levels of CO2 and relative humidity at some measurement locations below the recommended limits. PMID:12216594

  12. Modeled Effectiveness of Ventilation with Contaminant Control Devices on Indoor Air Quality in a Swine Farrowing Facility

    PubMed Central

    Anthony, T. Renée; Altmaier, Ralph; Park, Jae Hong; Peters, Thomas M.

    2016-01-01

    Because adverse health effects experienced by swine farm workers in concentrated animal feeding operations (CAFOs) have been associated with exposure to dust and gases, efforts to reduce exposures are warranted, particularly in winter seasons when exposures increase due to decreased ventilation. Simulation of air quality and operating costs for ventilating swine CAFO, including treating and recirculating air through a farrowing room, was performed using mass and energy balance equations over a 90-day winter season. System operation required controlling heater operation to achieve room temperatures optimal to ensure animal health (20 to 22.5°C). Five air pollution control devices, four room ventilation rates, and five recirculation patterns were examined. Inhalable dust concentrations were easily reduced using standard industrial air pollution control devices, including a cyclone, filtration, and electrostatic precipitator. Operating ventilation systems at 0.94 m3 s−1 (2000 cfm) with 75 to 100% recirculation of treated air from cyclone, electrostatic precipitator, and shaker dust filtration system achieves adequate particle control with operating costs under $1.00 per pig produced ($0.22 to 0.54), although carbon dioxide (CO2) concentrations approach 2000 ppm using in-room ventilated gas fired heaters. In no simulation were CO2 concentrations below industry recommended concentrations (1540 ppm), but alternative heating devices could reduce CO2 to acceptable concentrations. While this investigation does not represent all production swine farrowing barns, which differ in characteristics including room dimensions and swine occupancy, the simulation model and ventilation optimization methods can be applied to other production sites. This work shows that ventilation may be a cost-effective control option in the swine industry to reduce exposures. PMID:24433305

  13. Modeled effectiveness of ventilation with contaminant control devices on indoor air quality in a swine farrowing facility.

    PubMed

    Anthony, T Renée; Altmaier, Ralph; Park, Jae Hong; Peters, Thomas M

    2014-01-01

    Because adverse health effects experienced by swine farm workers in concentrated animal feeding operations (CAFOs) have been associated with exposure to dust and gases, efforts to reduce exposures are warranted, particularly in winter seasons when exposures increase due to decreased ventilation. Simulation of air quality and operating costs for ventilating swine CAFO, including treating and recirculating air through a farrowing room, was performed using mass and energy balance equations over a 90-day winter season. System operation required controlling heater operation to achieve room temperatures optimal to ensure animal health (20 to 22.5 °C). Five air pollution control devices, four room ventilation rates, and five recirculation patterns were examined. Inhalable dust concentrations were easily reduced using standard industrial air pollution control devices, including a cyclone, filtration, and electrostatic precipitator. Operating ventilation systems at 0.94 m3 s(-1) (2000 cfm) with 75 to 100% recirculation of treated air from cyclone, electrostatic precipitator, and shaker dust filtration system achieves adequate particle control with operating costs under $1.00 per pig produced ($0.22 to 0.54), although carbon dioxide (CO2) concentrations approach 2000 ppm using in-room ventilated gas fired heaters. In no simulation were CO2 concentrations below industry recommended concentrations (1540 ppm), but alternative heating devices could reduce CO2 to acceptable concentrations. While this investigation does not represent all production swine farrowing barns, which differ in characteristics including room dimensions and swine occupancy, the simulation model and ventilation optimization methods can be applied to other production sites. This work shows that ventilation may be a cost-effective control option in the swine industry to reduce exposures. PMID:24433305

  14. Modeled effectiveness of ventilation with contaminant control devices on indoor air quality in a swine farrowing facility.

    PubMed

    Anthony, T Renée; Altmaier, Ralph; Park, Jae Hong; Peters, Thomas M

    2014-01-01

    Because adverse health effects experienced by swine farm workers in concentrated animal feeding operations (CAFOs) have been associated with exposure to dust and gases, efforts to reduce exposures are warranted, particularly in winter seasons when exposures increase due to decreased ventilation. Simulation of air quality and operating costs for ventilating swine CAFO, including treating and recirculating air through a farrowing room, was performed using mass and energy balance equations over a 90-day winter season. System operation required controlling heater operation to achieve room temperatures optimal to ensure animal health (20 to 22.5 °C). Five air pollution control devices, four room ventilation rates, and five recirculation patterns were examined. Inhalable dust concentrations were easily reduced using standard industrial air pollution control devices, including a cyclone, filtration, and electrostatic precipitator. Operating ventilation systems at 0.94 m3 s(-1) (2000 cfm) with 75 to 100% recirculation of treated air from cyclone, electrostatic precipitator, and shaker dust filtration system achieves adequate particle control with operating costs under $1.00 per pig produced ($0.22 to 0.54), although carbon dioxide (CO2) concentrations approach 2000 ppm using in-room ventilated gas fired heaters. In no simulation were CO2 concentrations below industry recommended concentrations (1540 ppm), but alternative heating devices could reduce CO2 to acceptable concentrations. While this investigation does not represent all production swine farrowing barns, which differ in characteristics including room dimensions and swine occupancy, the simulation model and ventilation optimization methods can be applied to other production sites. This work shows that ventilation may be a cost-effective control option in the swine industry to reduce exposures.

  15. ALGORITHMS FOR ESTIMATING RESTING METABOLIC RATE AND ACTIVITY SPECIFIC VENTILATION RATES FOR USE IN COMPLEX EXPOSURE AND INTAKE DOSE MODELS

    EPA Science Inventory

    This work summarizes advancements made that allow for better estimation of resting metabolic rate (RMR) and subsequent estimation of ventilation rates (i.e., total ventilation (VE) and alveolar ventilation (VA)) for individuals of both genders and all ages. ...

  16. Hospital ventilation standards and energy conservation: chemical contamination of hospital air. Final report

    SciTech Connect

    Rainer, D.; Michaelsen, G.S.

    1980-03-01

    In an era of increasing energy conservation consciousness, a critical reassessment of the validity of hospital ventilation and thermal standards is made. If current standards are found to be excessively conservative, major energy conservation measures could be undertaken by rebalancing and/or modification of current HVAC systems. To establish whether or not reducing ventilation rates would increase airborne chemical contamination to unacceptable levels, a field survey was conducted to develop an inventory and dosage estimates of hospital generated airborne chemical contaminants to which patients, staff, and visitors are exposed. The results of the study are presented. Emphasis is on patient exposure, but an examination of occupational exposure was also made. An in-depth assessment of the laboratory air environment is documented. Housekeeping products used in survey hospitals, hazardous properties of housekeeping chemicals and probable product composition are discussed in the appendices.

  17. Quantification of the association of ventilation rates with sick building syndrome symptoms

    SciTech Connect

    Fisk, William J.; Mirer, Anna G.; Mendell, Mark J.

    2009-06-01

    Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence with ventilation rate. For each study, slopes were calculated, representing the fractional change in SBS symptom prevalence per unit change in ventilation rate per person. Values of ventilation rate, associated with each value of slope, were also calculated. Linear regression equations were fit to the resulting data points, after weighting by study size. Integration of the slope-ventilation rate equations yielded curves of relative SBS symptom prevalence versus ventilation rate. Based on these analyses, relative SBS symptom prevalence increases approximately 23percent (12percent to 32percent) as the ventilation rate drops from 10 to 5 L/s-person and relative prevalence decreases approximately 29percent (15percent to 42percent) as ventilation rate increases from 10 to 25 L/s-person.

  18. Greater physical fitness is associated with better air ventilation efficiency in firefighters.

    PubMed

    Gendron, P; Freiberger, E; Laurencelle, L; Trudeau, F; Lajoie, C

    2015-03-01

    Firefighting is a hazardous task associated with a heavy workload where task duration may be limited by air cylinder capacity. Increased fitness may lead to better air ventilation efficiency and task duration at a given heavy work intensity. This study compared performance, air ventilation and skeletal muscle oxygen extraction during a maximal graded walking test (GWT), a 10 METS (metabolic equivalent) treadmill test (T10) and a simulated work circuit (SWC). Participants (n = 13) who performed the SWC in a shorter time had significantly lower air cylinder ventilation values on the T10 (r = -0.495), better peak oxygen consumption (r = -0.924) during the GWT and significantly greater skeletal muscle oxygen extraction during the SWC (HbDiff, r = 0.768). These results demonstrate that the fastest participants on the SWC had better air ventilation efficiency that could prolong interventions in difficult situations requiring air cylinder use. PMID:25479992

  19. Optimization of Sampling Positions for Measuring Ventilation Rates in Naturally Ventilated Buildings Using Tracer Gas

    PubMed Central

    Shen, Xiong; Zong, Chao; Zhang, Guoqiang

    2012-01-01

    Finding out the optimal sampling positions for measurement of ventilation rates in a naturally ventilated building using tracer gas is a challenge. Affected by the wind and the opening status, the representative positions inside the building may change dynamically at any time. An optimization procedure using the Response Surface Methodology (RSM) was conducted. In this method, the concentration field inside the building was estimated by a three-order RSM polynomial model. The experimental sampling positions to develop the model were chosen from the cross-section area of a pitched-roof building. The Optimal Design method which can decrease the bias of the model was adopted to select these sampling positions. Experiments with a scale model building were conducted in a wind tunnel to achieve observed values of those positions. Finally, the models in different cases of opening states and wind conditions were established and the optimum sampling position was obtained with a desirability level up to 92% inside the model building. The optimization was further confirmed by another round of experiments.

  20. Improving microbial air quality in air-conditioned mass transport buses by opening the bus exhaust ventilation fans.

    PubMed

    Luksamijarulkul, Pipat; Arunchai, Nongphon; Luksamijarulkul, Soavalug; Kaewboonchoo, Orawan

    2005-07-01

    The air quality in air-conditioned mass transport buses may affect bus drivers' health. In-bus air quality improvement with the voluntary participation of bus drivers by opening the exhaust ventilation fans in the bus was implemented in the Seventh Bus Zone of Bangkok Mass Transit Authority. Four bus numbers, including bus numbers 16, 63, 67 and 166, were randomly selected to investigate microbial air quality and to observe the effect of opening the exhaust ventilation fans in the bus. With each bus number, 9 to 10 air-conditioned buses (total, 39 air-conditioned buses) were included. In-bus air samples were collected at 5 points in each studied bus using the Millipore Air Tester. A total of 195 air samples were cultured for bacterial and fungal counts. The results reveal that the exhaust ventilation fans of 17 air-conditioned buses (43.6%) were opened to ventilate in-bus air during the cycle of the bus route. The means +/- SD of bacterial counts and fungal counts in the studied buses with opened exhaust ventilation fans (83.8 +/- 70.7 and 38.0 +/- 42.8 cfu/m3) were significantly lower than those in the studied buses without opened exhaust ventilation fans (199.6 +/- 138.8 and 294.1 +/- 178.7 cfu/m3), p < 0.0005. All the air samples collected from the studied buses with opened exhaust ventilation fans were at acceptable levels (< 500 cfu/m3) compared with 4.6% of the air samples collected from the studied buses without opened exhaust ventilation fans, which had high levels (> 500 cfu/m3). Of the studied buses with opened exhaust ventilation fans (17 buses), the bacterial and fungal counts after opening the exhaust ventilation fans (68.3 +/- 33.8 and 28.3 +/- 19.3 cfu/m3) were significantly lower than those before opening the exhaust ventilation fans (158.3 +/- 116.9 and 85.3 +/- 71.2 cfu/m3), p < 0.005.

  1. Air exchange rates from atmospheric CO2 daily cycle

    PubMed Central

    Carrilho, João Dias; Mateus, Mário; Batterman, Stuart; da Silva, Manuel Gameiro

    2015-01-01

    We propose a new approach for measuring ventilation air exchange rates (AERs). The method belongs to the class of tracer gas techniques, but is formulated in the light of systems theory and signal processing. Unlike conventional CO2 based methods that assume the outdoor ambient CO2 concentration is constant, the proposed method recognizes that photosynthesis and respiration cycle of plants and processes associated with fuel combustion produce daily, quasi-periodic, variations in the ambient CO2 concentrations. These daily variations, which are within the detection range of existing monitoring equipment, are utilized for estimating ventilation rates without the need of a source of CO2 in the building. Using a naturally-ventilated residential apartment, AERs obtained using the new method compared favorably (within 10%) to those obtained using the conventional CO2 decay fitting technique. The new method has the advantages that no tracer gas injection is needed, and high time resolution results are obtained. PMID:26236090

  2. Carbon fibre composite for ventilation air methane (VAM) capture.

    PubMed

    Thiruvenkatachari, Ramesh; Su, Shi; Yu, Xin Xiang

    2009-12-30

    Coal mine methane (CMM) is not only a hazardous greenhouse gas but is also a wasted energy resource, if not utilised. This paper evaluates a novel adsorbent material developed for capturing methane from ventilation air methane (VAM) gas in underground coal mines. The adsorbent material is a honeycomb monolithic carbon fibre composite (HMCFC) consisting of multiple parallel flow-through channels and the material exhibits unique features including low pressure drop, good mechanical properties, ability to handle dust-containing gas streams, good thermal and electrical conductivity and selective adsorption of gases. During this study, a series of HMCFC adsorbents (using different types of carbon fibres) were successfully fabricated. Experimental data demonstrated the proof-of-concept of using the HMCFC adsorbent to capture methane from VAM gas. The adsorption capacity of the HMCFC adsorbent was twice that of commercial activated carbon. Methane concentration of 0.56% in the inlet VAM gas stream is reduced to about 0.011% after it passes through the novel carbon fibre composite adsorbent material at ambient temperature and atmospheric pressure. This amounts to a maximum capture efficiency of 98%. These encouraging laboratory scale studies have prompted further large scale trials and economic assessment.

  3. Carbon fibre composite for ventilation air methane (VAM) capture.

    PubMed

    Thiruvenkatachari, Ramesh; Su, Shi; Yu, Xin Xiang

    2009-12-30

    Coal mine methane (CMM) is not only a hazardous greenhouse gas but is also a wasted energy resource, if not utilised. This paper evaluates a novel adsorbent material developed for capturing methane from ventilation air methane (VAM) gas in underground coal mines. The adsorbent material is a honeycomb monolithic carbon fibre composite (HMCFC) consisting of multiple parallel flow-through channels and the material exhibits unique features including low pressure drop, good mechanical properties, ability to handle dust-containing gas streams, good thermal and electrical conductivity and selective adsorption of gases. During this study, a series of HMCFC adsorbents (using different types of carbon fibres) were successfully fabricated. Experimental data demonstrated the proof-of-concept of using the HMCFC adsorbent to capture methane from VAM gas. The adsorption capacity of the HMCFC adsorbent was twice that of commercial activated carbon. Methane concentration of 0.56% in the inlet VAM gas stream is reduced to about 0.011% after it passes through the novel carbon fibre composite adsorbent material at ambient temperature and atmospheric pressure. This amounts to a maximum capture efficiency of 98%. These encouraging laboratory scale studies have prompted further large scale trials and economic assessment. PMID:19733967

  4. Air leaking through the mouth during nocturnal nasal ventilation: effect on sleep quality.

    PubMed

    Meyer, T J; Pressman, M R; Benditt, J; McCool, F D; Millman, R P; Natarajan, R; Hill, N S

    1997-07-01

    Air leaking through the mouth has been reported in kyphoscoliotic patients receiving nasal ventilation via volume-limited ventilators. This study accessed the frequency of occurrence and effect on sleep quality of air leaking through the mouth during nocturnal nasal ventilation in patients with chest wall and neuromuscular disease using pressure-limited ventilation. Overnight and daytime polysomnography was performed in six stable experienced users of nocturnal nasal noninvasive positive-pressure ventilation (NPPV) who had chronic respiratory failure due to neuromuscular disease or chest wall deformity. All patients used the BiPAP S/T-D ventilatory support system (Respironics, Inc., Murrysville, PA). Measures included sleep scoring, leak quantitation, diaphragm and submental electromyograms (EMGs), and tidal and leak volumes. All patients had air leaking through the mouth for the majority of sleep. Sleep quality was diminished because of poor sleep efficiency and reduced percentages of slow-wave and rapid eye movement (REM) sleep. Air leaking through the mouth was associated with frequent arousals during stages 1 and 2 and REM sleep that contributed to sleep fragmentation, but arousals were infrequent during slow-wave sleep. Despite prevalent leaking, oxygenation was well maintained in all but one patient. Patients used a-combination of passive and active mechanisms to control air leaking. Although nasal ventilation improves nocturnal hypoventilation and symptoms in patients with restrictive thoracic disorders, air leaking through the mouth is very common during use. The leaking is associated with frequent arousals during lighter stages of sleep that interfere with progression to deeper stages, compromising sleep quality. Portable pressure-limited ventilators compensate for leaks, maintaining ventilation and oxygenation, but further studies are needed to determine which interfaces and ventilator techniques best control air leaking and optimize sleep quality.

  5. Comparison of Indoor Air Quality between 2 Ventilation Strategies in a Facility Housing Rhesus Macaques (Macaca mulatta)

    PubMed Central

    Monts de Oca, Nicole A; Laughlin, Mitzi; Jenkins, John; Lockworth, Cynthia R; Bolton, Iris D; Brammer, David W

    2015-01-01

    Adequate indoor-air quality (IAQ)—defined by the temperature, relative humidity, and the levels of carbon dioxide, small particles, and total volatile organic compounds (TVOC)—is crucial in laboratory animal facilities. The ventilation standards for controlling these parameters are not well defined. This study assessed the effect of 2 ventilation strategies on IAQ in 2 rooms housing rhesus macaques (Macaca mulatta). We hypothesized that using a demand-controlled ventilation (DCV) system with a baseline ventilation rate of less than 3 fresh-air changes per hour (ACH) would maintain IAQ comparable to or better than the traditional constant flow rate (CFR) system at 12 fresh ACH. During a 60-d study period, each of the 2 rooms operated 30 d on DCV and 30 d on CFR ventilation. In both rooms, temperatures remained more consistently within the established setpoint during the DCV phase than during the CFR phase. Relative humidity did not differ significantly between rooms or strategies. CO2 was lower during the CFR phase than DCV phase. Small-particle and TVOC levels were lower during CFR in the larger (3060 ft3) room but not the smaller (2340 ft3) room. During the DCV phase, the larger room was at the baseline airflow rate over 99% of the time and the smaller room over 96% of the time. The DCV strategy resulted in a baseline airflow rate of less than 3 ACH, which in turn provided acceptable IAQ over 96% of the time; higher ventilation rates were warranted only during sanitation periods. PMID:26424251

  6. Comparison of Indoor Air Quality between 2 Ventilation Strategies in a Facility Housing Rhesus Macaques (Macaca mulatta).

    PubMed

    Monts de Oca, Nicole A; Laughlin, Mitzi; Jenkins, John; Lockworth, Cynthia R; Bolton, Iris D; Brammer, David W

    2015-09-01

    Adequate indoor-air quality (IAQ)--defined by the temperature, relative humidity, and the levels of carbon dioxide, small particles, and total volatile organic compounds (TVOC)--is crucial in laboratory animal facilities. The ventilation standards for controlling these parameters are not well defined. This study assessed the effect of 2 ventilation strategies on IAQ in 2 rooms housing rhesus macaques (Macaca mulatta). We hypothesized that using a demand-controlled ventilation (DCV) system with a baseline ventilation rate of less than 3 fresh-air changes per hour (ACH) would maintain IAQ comparable to or better than the traditional constant flow rate (CFR) system at 12 fresh ACH. During a 60-d study period, each of the 2 rooms operated 30 d on DCV and 30 d on CFR ventilation. In both rooms, temperatures remained more consistently within the established setpoint during the DCV phase than during the CFR phase. Relative humidity did not differ significantly between rooms or strategies. CO₂ was lower during the CFR phase than DCV phase. Small-particle and TVOC levels were lower during CFR in the larger (3060 ft(3)) room but not the smaller (2340 ft(3)) room. During the DCV phase, the larger room was at the baseline airflow rate over 99% of the time and the smaller room over 96% of the time. The DCV strategy resulted in a baseline airflow rate of less than 3 ACH, which in turn provided acceptable IAQ over 96% of the time; higher ventilation rates were warranted only during sanitation periods.

  7. 1. AEROVANE FAN FROM NORTHWEST. AIR/MANWAY SHAFT AND LEPLEY VENTILATOR ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    1. AEROVANE FAN FROM NORTHWEST. AIR/MANWAY SHAFT AND LEPLEY VENTILATOR AT RIGHT, CIRCULAR SHAFT AND SCAFFOLD AT RIGHT REAR. - Consolidation Coal Company Mine No. 11, Aerovane Fan, East side of State Route 936, Midlothian, Allegany County, MD

  8. The role of the US Department of Energy in indoor air quality and building ventilation policy development

    SciTech Connect

    Traynor, G.W.; Talbott, J.M.; Moses, D.O.

    1993-07-01

    Building ventilation consumes about 5.8 exajoules of energy each year in the US The annual cost of this energy, used for commercial building fans (1.6 exajoules) and the heating and cooling of outside air (4.2 exajoules), is about $US 33 billion per year. Energy conservation measures that reduce heating and cooling season ventilation rates 15 to 35% in commercial and residential buildings can result in a national savings of about 0.6 to 1.5 exajoules ($US 3-8 billion) per year assuming no reduction of commercial building fan energy use. The most significant adverse environmental impact of reduced ventilation and infiltration is the potential degradation of the buildings indoor air quality. Potential benefits to the US from the implementation of sound indoor air quality and building ventilation reduction policies include reduced building-sector energy consumption; reduced indoor, outdoor, and global air pollution; reduced product costs; reduced worker absenteeism; reduced health care costs; reduced litigation; increased worker well-being and productivity; and increased product quality and competitiveness.

  9. Shared Air: A Renewed Focus on Ventilation for the Prevention of Tuberculosis Transmission

    PubMed Central

    Richardson, Eugene T.; Morrow, Carl D.; Kalil, Darryl B.; Bekker, Linda-Gail; Wood, Robin

    2014-01-01

    Background Despite an improvement in the overall TB cure rate from 40–74% between 1995 and 2011, TB incidence in South Africa continues to increase. The epidemic is notably disquieting in schools because the vulnerable population is compelled to be present. Older learners (age 15–19) are at particular risk given a smear-positive rate of 427 per 100,000 per year and the significant amount of time they spend indoors. High schools are therefore important locations for potential TB infection and thus prevention efforts. Methods and Findings Using portable carbon dioxide monitors, we measured CO2 in classrooms under non-steady state conditions. The threshold for tuberculosis transmission was estimated using a carbon dioxide-based risk equation. We determined a critical rebreathed fraction of carbon dioxide () of 1·6%, which correlates with an indoor CO2 concentration of 1000 ppm. These values correspond with a ventilation rate of 8·6 l/s per person or 12 air exchanges per hour (ACH) for standard classrooms of 180 m3. Conclusions Given the high smear positive rate of high-school adolescents in South Africa, the proposal to achieve CO2 levels of 1000ppm through natural ventilation (in the amount 12 ACH) will not only help achieve WHO guidelines for providing children with healthy indoor environments, it will also provide a low-cost intervention for helping control the TB epidemic in areas of high prevalence. PMID:24804707

  10. Impact of reduced exhaust and ventilation rates at ``no-load`` cooking conditions in a commercial kitchen during winter operation

    SciTech Connect

    Spata, A.J.; Turgeon, S.M.

    1995-12-31

    While previous studies have examined the effect of reduced exhaust and ventilation rates on comfort levels and air-conditioning requirements in commercial kitchens when cooling of this space was required, no investigation had been performed to document energy savings that may be obtainable by a similar technique during periods when heating of make-up air was dictated. In addition, these prior studies examined the resultant kitchen conditions with lower exhaust and ventilation rates applied while the hooded appliances were actively being used for cooking. This paper presents the field evaluation findings by a major quick-service restaurant chain. These findings resulted from the reduction of exhaust and make-up air quantities during periods when heating of kitchen make-up air was required and no cooking was occurring on the grills. The initial results indicate that these reductions yield significant utility savings, with no detrimental effect on the environment within the kitchen, by minimizing the amount of outside air tempered by the heating, ventilating, and air-conditioning (HVAC) equipment during ``no load`` cooking conditions.

  11. Indoor-outdoor air quality relationships in vehicle: effect of driving environment and ventilation modes

    NASA Astrophysics Data System (ADS)

    Chan, Andy T.; Chung, Michael W.

    Nitrogen oxides and carbon monoxide concentration were measured inside and outside of a light-goods-vehicle at different locations and driving conditions for a 6-month period. To investigate the exposure of the vehicle passenger to the specified outdoor pollutant, the indoor-outdoor air quality (IO) relationships under various driving conditions, namely traffic density, ventilation modes and type of roadway were studied. Four main types of driving environments were selected: highway, countryside, urban street and tunnel. The vehicle was driven under the three main types of ventilation conditions: air-conditioning with air-recirculation, air-conditioning with fresh air intake and natural ventilation. It is found that the IO ratio is not specific only to the mode of ventilation but also depends on the driving environment. The IO value can vary drastically even using the same ventilation mode when the vehicle is travelling in a different environment. It is found that using fresh-air ventilation mode, the IO can change from approximately 0.5-3 as it commutes from a highway to the countryside. The results also indicate that indoor NO level increased as the traffic density increases. The fluctuation of indoor NO level of naturally ventilated vehicle followed the variation of outdoor NO concentration with the IO value varying from 0.5 to 5. The results also show that even in an air-conditioned van, the indoor NO and CO concentration is significantly affected by that outdoor. It suggests the use of different ventilation mode when commuting in different environment.

  12. Early ventilation-heart rate breakpoint during incremental cycling exercise.

    PubMed

    Gravier, G; Delliaux, S; Ba, A; Delpierre, S; Guieu, R; Jammes, Y

    2014-03-01

    Previous observations having reported a transient hypoxia at the onset of incremental exercise, we investigated the existence of concomitant ventilatory and heart rate (HR) breakpoints.33 subjects executed a maximal cycling exercise with averaging for successive 5-s periods of HR, ventilation, tidal volume (VT), mean inspiratory flow rate (VT/Ti), and end-tidal partial pressures of O2 (PETO2) and CO2. In 10 subjects, the transcutaneous partial pressure of O2 (PtcO2) was recorded and the venous blood lactic acid (LA) concentration measured.At the beginning of exercise, PETO2 decreased, reaching a nadir, then progressively increased until the exercise ended. PtcO2 varied in parallel. Whether or not a 0-W cycling period preceded the incremental exercise, the rate of changes in VE, VT, VT/Ti and HR significantly increased when the nadir PO2 was reached. The ventilatory/ HR breakpoint was measured at 33±4% of VO2max, whereas the ventilatory threshold (VTh) was detected at 67±4% of VO2max and LA began to increase at 45 to 50% of VO2max.During incremental cycling exercise, we identified the existence of HR and ventilatory breakpoints in advance of both lactate and ventilatory thresholds which coincided with modest hypoxia and hypercapnia.

  13. Applied patent RFID systems for building reacting HEPA air ventilation system in hospital operation rooms.

    PubMed

    Lin, Jesun; Pai, Jar-Yuan; Chen, Chih-Cheng

    2012-12-01

    RFID technology, an automatic identification and data capture technology to provide identification, tracing, security and so on, was widely applied to healthcare industry in these years. Employing HEPA ventilation system in hospital is a way to ensure healthful indoor air quality to protect patients and healthcare workers against hospital-acquired infections. However, the system consumes lots of electricity which cost a lot. This study aims to apply the RFID technology to offer a unique medical staff and patient identification, and reacting HEPA air ventilation system in order to reduce the cost, save energy and prevent the prevalence of hospital-acquired infection. The system, reacting HEPA air ventilation system, contains RFID tags (for medical staffs and patients), sensor, and reacting system which receives the information regarding the number of medical staff and the status of the surgery, and controls the air volume of the HEPA air ventilation system accordingly. A pilot program was carried out in a unit of operation rooms of a medical center with 1,500 beds located in central Taiwan from Jan to Aug 2010. The results found the air ventilation system was able to function much more efficiently with less energy consumed. Furthermore, the indoor air quality could still keep qualified and hospital-acquired infection or other occupational diseases could be prevented.

  14. Ventilation patterns of the songbird lung/air sac system during different behaviors

    PubMed Central

    Mackelprang, Rebecca; Goller, Franz

    2013-01-01

    SUMMARY Unidirectional, continuous airflow through the avian lung is achieved through an elaborate air sac system with a sequential, posterior to anterior ventilation pattern. This classical model was established through various approaches spanning passively ventilated systems to mass spectrometry analysis of tracer gas flow into various air sacs during spontaneous breathing in restrained ducks. Information on flow patterns in other bird taxa is missing, and these techniques do not permit direct tests of whether the basic flow pattern can change during different behaviors. Here we use thermistors implanted into various locations of the respiratory system to detect small pulses of tracer gas (helium) to reconstruct airflow patterns in quietly breathing and behaving (calling, wing flapping) songbirds (zebra finch and yellow-headed blackbird). The results illustrate that the basic pattern of airflow in these two species is largely consistent with the model. However, two notable differences emerged. First, some tracer gas arrived in the anterior set of air sacs during the inspiration during which it was inhaled, suggesting a more rapid throughput through the lung than previously assumed. Second, differences in ventilation between the two anterior air sacs emerged during calling and wing flapping, indicating that adjustments in the flow pattern occur during dynamic behaviors. It is unclear whether this modulation in ventilation pattern is passive or active. This technique for studying ventilation patterns during dynamic behaviors proves useful for establishing detailed timing of airflow and modulation of ventilation in the avian respiratory system. PMID:23788706

  15. Ventilation patterns of the songbird lung/air sac system during different behaviors.

    PubMed

    Mackelprang, Rebecca; Goller, Franz

    2013-10-01

    Unidirectional, continuous airflow through the avian lung is achieved through an elaborate air sac system with a sequential, posterior to anterior ventilation pattern. This classical model was established through various approaches spanning passively ventilated systems to mass spectrometry analysis of tracer gas flow into various air sacs during spontaneous breathing in restrained ducks. Information on flow patterns in other bird taxa is missing, and these techniques do not permit direct tests of whether the basic flow pattern can change during different behaviors. Here we use thermistors implanted into various locations of the respiratory system to detect small pulses of tracer gas (helium) to reconstruct airflow patterns in quietly breathing and behaving (calling, wing flapping) songbirds (zebra finch and yellow-headed blackbird). The results illustrate that the basic pattern of airflow in these two species is largely consistent with the model. However, two notable differences emerged. First, some tracer gas arrived in the anterior set of air sacs during the inspiration during which it was inhaled, suggesting a more rapid throughput through the lung than previously assumed. Second, differences in ventilation between the two anterior air sacs emerged during calling and wing flapping, indicating that adjustments in the flow pattern occur during dynamic behaviors. It is unclear whether this modulation in ventilation pattern is passive or active. This technique for studying ventilation patterns during dynamic behaviors proves useful for establishing detailed timing of airflow and modulation of ventilation in the avian respiratory system.

  16. Indoor airborne bacterial communities are influenced by ventilation, occupancy, and outdoor air source.

    PubMed

    Meadow, J F; Altrichter, A E; Kembel, S W; Kline, J; Mhuireach, G; Moriyama, M; Northcutt, D; O'Connor, T K; Womack, A M; Brown, G Z; Green, J L; Bohannan, B J M

    2014-02-01

    Architects and engineers are beginning to consider a new dimension of indoor air: the structure and composition of airborne microbial communities. A first step in this emerging field is to understand the forces that shape the diversity of bioaerosols across space and time within the built environment. In an effort to elucidate the relative influences of three likely drivers of indoor bioaerosol diversity - variation in outdoor bioaerosols, ventilation strategy, and occupancy load - we conducted an intensive temporal study of indoor airborne bacterial communities in a high-traffic university building with a hybrid HVAC (mechanically and naturally ventilated) system. Indoor air communities closely tracked outdoor air communities, but human-associated bacterial genera were more than twice as abundant in indoor air compared with outdoor air. Ventilation had a demonstrated effect on indoor airborne bacterial community composition; changes in outdoor air communities were detected inside following a time lag associated with differing ventilation strategies relevant to modern building design. Our results indicate that both occupancy patterns and ventilation strategies are important for understanding airborne microbial community dynamics in the built environment. PMID:23621155

  17. Indoor airborne bacterial communities are influenced by ventilation, occupancy, and outdoor air source

    PubMed Central

    Meadow, J F; Altrichter, A E; Kembel, S W; Kline, J; Mhuireach, G; Moriyama, M; Northcutt, D; O'Connor, T K; Womack, A M; Brown, G Z; Green, J L ; Bohannan, B J M

    2014-01-01

    Architects and engineers are beginning to consider a new dimension of indoor air: the structure and composition of airborne microbial communities. A first step in this emerging field is to understand the forces that shape the diversity of bioaerosols across space and time within the built environment. In an effort to elucidate the relative influences of three likely drivers of indoor bioaerosol diversity – variation in outdoor bioaerosols, ventilation strategy, and occupancy load – we conducted an intensive temporal study of indoor airborne bacterial communities in a high-traffic university building with a hybrid HVAC (mechanically and naturally ventilated) system. Indoor air communities closely tracked outdoor air communities, but human-associated bacterial genera were more than twice as abundant in indoor air compared with outdoor air. Ventilation had a demonstrated effect on indoor airborne bacterial community composition; changes in outdoor air communities were detected inside following a time lag associated with differing ventilation strategies relevant to modern building design. Our results indicate that both occupancy patterns and ventilation strategies are important for understanding airborne microbial community dynamics in the built environment. PMID:23621155

  18. Forced-air warming and ultra-clean ventilation do not mix: an investigation of theatre ventilation, patient warming and joint replacement infection in orthopaedics.

    PubMed

    McGovern, P D; Albrecht, M; Belani, K G; Nachtsheim, C; Partington, P F; Carluke, I; Reed, M R

    2011-11-01

    We investigated the capacity of patient warming devices to disrupt the ultra-clean airflow system. We compared the effects of two patient warming technologies, forced-air and conductive fabric, on operating theatre ventilation during simulated hip replacement and lumbar spinal procedures using a mannequin as a patient. Infection data were reviewed to determine whether joint infection rates were associated with the type of patient warming device that was used. Neutral-buoyancy detergent bubbles were released adjacent to the mannequin's head and at floor level to assess the movement of non-sterile air into the clean airflow over the surgical site. During simulated hip replacement, bubble counts over the surgical site were greater for forced-air than for conductive fabric warming when the anaesthesia/surgery drape was laid down (p = 0.010) and at half-height (p < 0.001). For lumbar surgery, forced-air warming generated convection currents that mobilised floor air into the surgical site area. Conductive fabric warming had no such effect. A significant increase in deep joint infection, as demonstrated by an elevated infection odds ratio (3.8, p = 0.024), was identified during a period when forced-air warming was used compared to a period when conductive fabric warming was used. Air-free warming is, therefore, recommended over forced-air warming for orthopaedic procedures.

  19. A simplified model for estimating population-scale energy impacts of building envelope air-tightening and mechanical ventilation retrofits

    SciTech Connect

    Logue, Jennifer M.; Turner, William J. N.; Walker, Iain S.; Singer, Brett C.

    2015-01-19

    Changing the air exchange rate of a home (the sum of the infiltration and mechanical ventilation airflow rates) affects the annual thermal conditioning energy. Large-scale changes to air exchange rates of the housing stock can significantly alter the residential sector's energy consumption. However, the complexity of existing residential energy models is a barrier to the accurate quantification of the impact of policy changes on a state or national level. The Incremental Ventilation Energy (IVE) model developed in this study combines the output of simple air exchange models with a limited set of housing characteristics to estimate the associated change in energy demand of homes. The IVE model was designed specifically to enable modellers to use existing databases of housing characteristics to determine the impact of ventilation policy change on a population scale. The IVE model estimates of energy change when applied to US homes with limited parameterisation are shown to be comparable to the estimates of a well-validated, complex residential energy model.

  20. Residential ventilation with heat recovery: Improving indoor air quality and saving energy

    NASA Astrophysics Data System (ADS)

    Roseme, G. D.; Berk, J. V.; Boegel, M. L.; Halsey, H. I.; Hollowell, C. D.; Rosenfeld, A. H.; Turiel, I.

    1980-05-01

    Residential air quality measurements were made and the use of mechanical ventilation systems with air-to-air heat exchangers is discussed as a promising means of pollutant control. A particular advantage of this control strategy is that the heat exchanger permits recovery of a large portion of the heat that would normally be lost in a simple exhaust ventilation system, and therefore maintains the energy efficiency of the house. An economic analysis is presented showing that installation of these systems in newly constructed homes is cost effective in most regions of the country.

  1. Air Conditioning, Heating, and Ventilating: Construction, Supervision, and Inspection. Course of Study.

    ERIC Educational Resources Information Center

    Messer, John D.

    This course of study on air conditioning, heating, and ventilating is part of a construction, supervision, and inspection series, which provides instructional materials for community or junior college technical courses in the inspection program. Material covered pertains to: piping and piping systems; air movers; boilers; heat exchangers; cooling…

  2. Test Protocol for Room-to-Room Distribution of Outside Air by Residential Ventilation Systems

    SciTech Connect

    Barley, C. D.; Anderson, R.; Hendron, B.; Hancock, E.

    2007-12-01

    This test and analysis protocol has been developed as a practical approach for measuring outside air distribution in homes. It has been used successfully in field tests and has led to significant insights on ventilation design issues. Performance advantages of more sophisticated ventilation systems over simpler, less-costly designs have been verified, and specific problems, such as airflow short-circuiting, have been identified.

  3. A Prospective Study of Ventilation Rates and Illness Absence in California Office Buildings

    SciTech Connect

    Eliseeva, Ekaterina A.; Spears, Michael; Chan, Wanyu R.; Cohn, Sebastian; Sullivan, Douglas P.; Fisk, William J.

    2014-10-07

    Background – This study investigated the associations of ventilation rates (VRs), estimated from indoor CO2 concentrations, in offices with the amount of respiratory infections, illness absences, and building-related health symptoms in occupants. Methods – Office buildings were recruited from three California climate zones. In one or more study spaces within each building, real-time logging sensors measured carbon dioxide, temperature, and relative humidity for one year. Ventilation rates were estimated using daily peak CO2 levels, and also using an alternative metric. Data on occupants and health outcomes were collected through web-based surveys every three months. Multivariate models were used to assess relationships between metrics of ventilation rate or CO2 and occupant outcomes. For all outcomes, negative associations were hypothesized with VR metrics, and positive associations with CO2 metrics. Results – Difficulty recruiting buildings and low survey response limited sample size and study power. In 16 studied spaces within 9 office buildings, VRs were uniformly high over the year, from twice to over nine times the California office VR standard (7 L/s or 15 cfm per person). VR and CO2 metrics had no statistically significant relationships with occupant outcomes, except for a small significantly positive association of the alternative VR metric with respiratory illness-related absence, contrary to hypotheses. Conclusions– The very high time-averaged VRs in the California office buildings studied presumably resulted from “economizer cycles” bringing in large volumes of outdoor air; however, in almost all buildings even the estimated minimum VRs supplied (without the economizer) substantially exceeded the minimum required VR. These high VRs may explain the absence of hypothesized relationships with occupant outcomes. Among uniformly high VRs, little variation in contaminant concentration and occupant effects would be expected. These findings may

  4. VERIFICATION TESTING OF TECHNOLOGIES TO CLEAN OR FILTER VENTILATION AIR

    EPA Science Inventory

    Because of the importance of indoor air quality, Research Triangle Institute's Air Pollution Control Technology is adding indoor air products as a new technology category available for testing. This paper discusses RTI's participation in previous Environmental Technology Verifica...

  5. Ventilation or filtration? The use of gas-phase air filtration for compliance with ASRAE Standard 62

    SciTech Connect

    Muller, C.O.

    1996-05-01

    ASHRAE Standard 62, in its current form, employs two procedures to provide acceptable indoor air quality (IAQ) in buildings. These are the Ventilation Rate and Indoor Air Quality (IAQ) Procedures. This standard further endeavors to achieve the necessary balance between IAQ and energy consumption by specifying minimum ventilation rates and IAQ that will be acceptable to human occupants. The standard acknowledges that air cleaning, along with recirculation, is an effective means for controlling contaminants when using the IAQ Procedure. Employing this procedure allows the amount of outside ventilation air to be reduced below standard levels if it can be demonstrated that the resulting air quality meets the required criteria. More buildings are using, or will be using, gas-phase air filtration as part of their overall design for providing and maintaining acceptable IAQ. This trend is being seen in retrofit applications as well as new construction. Among the driving forces behind this are the increased awareness of people to their environment and how it may affect their well-being, legislative actions which are in effect or have been proposed, and, of course, that members of the legal community litigating complaints of sick building syndrome (SBS) and building-related illness (BRI). This paper will focus on the use of gas-phase air filtration for compliance with ASHRAE Standard 62 by using the IAQ Procedure. It will cover the requirements of using this procedure, the information required, and will describe several projects where this procedure was successfully used to realize both acceptable IAQ and energy savings.

  6. Utilization of ventilation air methane as a supplementary fuel at a circulating fluidized bed combustion boiler.

    PubMed

    You, Changfu; Xu, Xuchang

    2008-04-01

    Ventilation air methane (VAM) accounts for 60-80% of the total emissions from coal mining activities in China, which is of serious greenhouse gas concerns as well as a waste of valuable fuel sources. This contribution evaluates the use of the VAM utilization methods as a supplementary fuel at a circulating fluidized bed combustion boiler. The paper describes the system design and discusses some potential technical challenges such as methane oxidation rate, corrosion, and efficiency. Laboratory experimentation has shown that the VAM can be burnt completely in circulated fluidized bed furnaces, and the VAM oxidation does not obviously affect the boiler operation when the methane concentration is less than 0.6%. The VAM decreased the incomplete combustion loss for the circulating fluidized bed combustion furnace. The economic benefit from the coal saving insures that the proposed system is more economically feasible.

  7. Test Plan for Measuring Ventilation Rates and Combustible Gas Levels in TWRS Active Catch Tanks

    SciTech Connect

    NGUYEN, D.M.

    1999-10-25

    The purpose of this sampling activity is to obtain data to support an initial evaluation of potential hazards due to the presence of combustible gas in catch tanks that are currently operated by the River Protection Project (RPP). Results of the hazard analysis will be used to support closure of the flammable gas unreviewed safety question for these facilities. The data collection will be conducted in accordance with the Tank Safety Screening Data Quality Objective (Dukelow et al. 1995). Combustible gas, ammonia, and organic vapor levels in the headspace of the catch tanks will be field-measured using hand-held instruments. If a combustible gas level measurement in a tank exceeds an established threshold, gas samples will he collected in SUMMA' canisters for more extensive laboratory analysis. In addition, ventilation rates of some catch tanks will be measured to evaluate removal of flammable gas by air flowing through the tanks. This test plan identifies the sample collection, laboratory analysis, quality assurance, and reporting objectives for this data collection effort. The plan also provides the procedures for field measurement of combustible gas concentrations and ventilation rates.

  8. A study of energy use for ventilation and air-conditioning systems in Hong Kong

    NASA Astrophysics Data System (ADS)

    Yu, Chung Hoi Philip

    Most of the local modern buildings are high-rise with enclosed structure. Mechanical ventilation and air conditioning (MVAC) systems are installed for thermal comfort. Various types of MVAC systems found in Hong Kong were critically reviewed with comments on their characteristics in energy efficiency as well as application. The major design considerations were also discussed. Besides MVAC, other energy-consuming components in commercial buildings were also identified, such as lighting, lifts and escalators, office equipment, information technology facilities, etc. A practical approach has been adopted throughout this study in order that the end results will have pragmatic value to the heating, ventilating and air-conditioning (HVAC) industry in Hong Kong. Indoor Air Quality (IAQ) has become a major issue in commercial buildings worldwide including Hong Kong. Ventilation rate is no doubt a critical element in the design of HVAC systems, which can be realized more obviously in railway train compartments where the carbon dioxide level will be built up quickly when the compartments are crowded during rush hours. A study was carried out based on a simplified model using a train compartment that is equipped with an MVAC system. Overall Thermal Transfer Value (OTTV) is a single-value parameter for controlling building energy use and is relatively simple to implement legislatively. The local government has taken a first step in reacting to the worldwide concern of energy conservation and environmental protection since 1995. Different methods of OTTV calculation were studied and the computation results were compared. It gives a clear picture of the advantages and limitations for each method to the building designers. However, due to the limitations of using OTTV as the only parameter for building energy control, some new approaches to a total control of building energy use were discussed and they might be considered for future revision of the building energy codes in Hong

  9. An air bearing fan for EVA suit ventilation

    NASA Technical Reports Server (NTRS)

    Murry, Roger P.

    1990-01-01

    The portable life-support system (PLSS) ventilation requirements are outlined, along with the application of a high-speed axial fan technology for extravehicular-activity (EVA) space-suit ventilation. Focus is placed on a mechanical design employing high-speed gas bearings, permanent magnet rotor, and current-fed chopper/inverter electronics. The operational characteristics of the fan unit and its applicability for use in a pure-oxygen environment are discussed. It delivers a nominal 0.17 cu m/min at 1.24 kPa pressure rise using 13.8 w of input power. It is shown that the overall selection of materials for all major component meets the NASA requirements.

  10. Healthy Zero Energy Buildings (HZEB) Program - Cross-Sectional Study of Contaminant Levels, Source, Strengths, and Ventilation Rates in Retail Stores

    SciTech Connect

    Chan, Wanyu R.; Sidheswaran, Meera; Cohn, Sebastian; Sullivan, Douglas P.; Fisk, William

    2014-02-01

    This field study measured ventilation rates and indoor air quality parameters in 21 visits to retail stores in California. The data was collected to guide the development of new, science-based commercial building ventilation rate standards that balance the dual objectives of increasing energy efficiency and maintaining acceptable indoor air quality. Data collection occurred between September 2011 and March 2013. Three types of stores participated in this study: grocery stores, furniture/hardware stores, and apparel stores. Ventilation rates and indoor air contaminant concentrations were measured on a weekday, typically between 9 am and 6 pm. Ventilation rates measured using a tracer gas decay method exceeded the minimum requirement of California’s Title 24 Standard in all but one store. Even though there was adequate ventilation according to Title 24, concentrations of formaldehyde, acetaldehyde, and acrolein exceeded the most stringent chronic health guidelines. Other indoor air contaminants measured included carbon dioxide (CO{sub 2}), carbon monoxide (CO), ozone (O{sub 3}), and particulate matter (PM). Concentrations of CO{sub 2} were kept low by adequate ventilation, and were assumed low also because the sampling occurred on a weekday when retail stores were less busy. CO concentrations were also low. The indoor-outdoor ratios of O{sub 3} showed that the first-order loss rate may vary by store trade types and also by ventilation mode (mechanical versus natural). Analysis of fine and ultrafine PM measurements showed that a substantial portion of the particle mass in grocery stores with cooking-related emissions was in particles less than 0.3 μm. Stores without cooking as an indoor source had PM size distributions that were more similar indoors and outdoors. The whole-building emission rates of volatile organic compounds (VOCs) and PM were estimated from the measured ventilation rates and indoor and outdoor contaminant concentrations. Mass balance models were

  11. Test plan for measuring ventilation rates and combustible gas levels in RPP active catch tanks

    SciTech Connect

    NGUYEN, D.M.

    1999-06-03

    The purpose of this test is to provide an initial screening of combustible gas concentrations in catch tanks that currently are operated by River Protection Project (RPP). The data will be used to determine whether or not additional data will be needed for closure of the flammable gas unreviewed safety question for these facilities. This test will involve field measurements of ammonia, organic vapor, and total combustible gas levels in the headspace of the catch tanks. If combustible gas level in a tank exceeds an established threshold, gas samples will be collected in SUMMA canisters for more extensive laboratory analysis. In addition, ventilation rates of some catch tanks will be measured to evaluate removal of flammable gas by air flow through the tanks.

  12. Test plan for measuring ventilation rates and combustible gas levels in TWRS active catch tanks

    SciTech Connect

    NGUYEN, D.M.

    1999-05-20

    The purpose of this test is to provide an initial screening of combustible gas concentrations in catch tanks that currently are operated by Tank Waste Remediation System (TWRS). The data will be used to determine whether or not additional data will be needed for closure of the flammable gas unreviewed safety question for these facilities. This test will involve field measurements of ammonia, organic vapor, and total combustible gas levels in the headspace of the catch tanks. If combustible gas level in a tank exceeds an established threshold, gas samples will be collected in SUMMA canisters for more extensive laboratory analysis. In addition, ventilation rates of some catch tanks will be measured to evaluate removal of flammable gas by air flow through the tanks.

  13. Assessment of Indoor Air Quality Benefits and Energy Costs of Mechanical Ventilation

    SciTech Connect

    Logue, J.M.; Price, P.N.; Sherman, M.H.; Singer, B.C.

    2011-07-01

    Intake of chemical air pollutants in residences represents an important and substantial health hazard. Sealing homes to reduce air infiltration can save space conditioning energy, but can also increase indoor pollutant concentrations. Mechanical ventilation ensures a minimum amount of outdoor airflow that helps reduce concentrations of indoor emitted pollutants while requiring some energy for fan(s) and thermal conditioning of the added airflow. This work demonstrates a physics based, data driven modeling framework for comparing the costs and benefits of whole-house mechanical ventilation and applied the framework to new California homes. The results indicate that, on a population basis, the health benefits from reduced exposure to indoor pollutants in New California homes are worth the energy costs of adding mechanical ventilation as specified by ASHRAE Standard 62.2.This study determines the health burden for a subset of pollutants in indoor air and the costs and benefits of ASHRAE's mechanical ventilation standard (62.2) for new California homes. Results indicate that, on a population basis, the health benefits of new home mechanical ventilation justify the energy costs.

  14. Energy and IAQ Implications of Alternative Minimum Ventilation Rates in California Retail and School Buildings

    SciTech Connect

    Dutton, Spencer M.; Fisk, William J.

    2015-01-01

    For a stand-alone retail building, a primary school, and a secondary school in each of the 16 California climate zones, the EnergyPlus building energy simulation model was used to estimate how minimum mechanical ventilation rates (VRs) affect energy use and indoor air concentrations of an indoor-generated contaminant. The modeling indicates large changes in heating energy use, but only moderate changes in total building energy use, as minimum VRs in the retail building are changed. For example, predicted state-wide heating energy consumption in the retail building decreases by more than 50% and total building energy consumption decreases by approximately 10% as the minimum VR decreases from the Title 24 requirement to no mechanical ventilation. The primary and secondary schools have notably higher internal heat gains than in the retail building models, resulting in significantly reduced demand for heating. The school heating energy use was correspondingly less sensitive to changes in the minimum VR. The modeling indicates that minimum VRs influence HVAC energy and total energy use in schools by only a few percent. For both the retail building and the school buildings, minimum VRs substantially affected the predicted annual-average indoor concentrations of an indoor generated contaminant, with larger effects in schools. The shape of the curves relating contaminant concentrations with VRs illustrate the importance of avoiding particularly low VRs.

  15. Environmental Technology Verification: Supplement to Test/QA Plan for Biological and Aerosol Testing of General Ventilation Air Cleaners; Bioaerosol Inactivation Efficiency by HVAC In-Duct Ultraviolet Light Air Cleaners

    EPA Science Inventory

    The Air Pollution Control Technology Verification Center has selected general ventilation air cleaners as a technology area. The Generic Verification Protocol for Biological and Aerosol Testing of General Ventilation Air Cleaners is on the Environmental Technology Verification we...

  16. Design and optimization of personalized ventilation for overall improvement of thermal comfort, air quality, and energy efficiency

    NASA Astrophysics Data System (ADS)

    Metzger, Ian Dominic

    This paper presents a simple and repeatable CFD-based method that can accurately predict the optimal operating conditions of personalized ventilation systems. In contrast to previous studies, the optimal performance of the PV system includes the influences of various operation characteristics (supply air velocity, PV flow rate, PV temperature, PV distance from face, turbulence intensity, relative humidity, central system flow rate, central system temperature, central system type, and PV on/off operation) on three critical performance factors: thermal comfort, indoor air quality, and energy savings. This method is able to predict more achievable and comprehensive operating performance of PV systems. It is found for the computer perimeter grill air terminal device that supply temperatures, central flow rate, and PV flow rate are the most influential factors on performance in terms of thermal comfort, IAQ, and energy. Using the Taguchi design of experiment and optimal performance prediction method, the computer perimeter grill personalized ventilation system is optimized in conjunction with under-floor and overhead central systems, separately.

  17. Helium:oxygen versus air:oxygen noninvasive positive-pressure ventilation in patients exposed to sulfur mustard.

    PubMed

    Ghanei, Mostafa; Rajaeinejad, Mohsen; Motiei-Langroudi, Rouzbeh; Alaeddini, Farshid; Aslani, Jafar

    2011-01-01

    Exposure to sulfur mustard (SM) causes a variety of respiratory symptoms, such as chronic bronchitis and constrictive bronchiolitis. This study assessed the effectiveness of noninvasive positive-pressure ventilation, adjunct with 79:21 helium:oxygen instead of 79:21 air:oxygen, in 24 patients with a previous exposure to SM presenting with acute respiratory failure. Both air:oxygen and helium:oxygen significantly decreased systolic blood pressure, diastolic blood pressure, mean arterial pressure, pulse rate, respiratory rate, dyspnea, and increased oxygen saturation (P values: .007, .029, .002, <.001, <.001, <.001, and .002 for air:oxygen, respectively, and <.001, .020, .001, <.001, <.001, <.001, and .002, for helium:oxygen, respectively). Moreover, helium:oxygen more potently improved systolic pressure, mean arterial pressure, pulse rate, respiratory rate, and dyspnea (P values: .012, .048, <.001, <.001, and .012, respectively). The results of our study support the benefit of using helium:oxygen adjunct with noninvasive positive-pressure ventilation in patients exposed to SM with acute respiratory decompensation.

  18. Control strategies for sub-micrometer particles indoors: model study of air filtration and ventilation.

    PubMed

    Jamriska, M; Morawska, L; Ensor, D S

    2003-06-01

    The effects of air filtration and ventilation on indoor particles were investigated using a single-zone mathematical model. Particle concentration indoors was predicted for several I/O conditions representing scenarios likely to occur in naturally and mechanically ventilated buildings. The effects were studied for static and dynamic conditions in a hypothetical office building. The input parameters were based on real-world data. For conditions with high particle concentrations outdoors, it is recommended to reduce the amount of outdoor air delivered indoors and the necessary reduction level can be quantified by the model simulation. Consideration should also be given to the thermal comfort and minimum outdoor air required for occupants. For conditions dominated by an indoor source, it is recommended to increase the amount of outdoor air delivered indoors and to reduce the amount of return air. Air filtration and ventilation reduce particle concentrations indoors, with the overall effect depending on efficiency, location and the number of filters applied. The assessment of indoor air quality for specific conditions could be easily calculated by the model using user-defined input parameters.

  19. Ultrafine particle removal by residential heating, ventilating, and air-conditioning filters.

    PubMed

    Stephens, B; Siegel, J A

    2013-12-01

    This work uses an in situ filter test method to measure the size-resolved removal efficiency of indoor-generated ultrafine particles (approximately 7-100 nm) for six new commercially available filters installed in a recirculating heating, ventilating, and air-conditioning (HVAC) system in an unoccupied test house. The fibrous HVAC filters were previously rated by the manufacturers according to ASHRAE Standard 52.2 and ranged from shallow (2.5 cm) fiberglass panel filters (MERV 4) to deep-bed (12.7 cm) electrostatically charged synthetic media filters (MERV 16). Measured removal efficiency ranged from 0 to 10% for most ultrafine particles (UFP) sizes with the lowest rated filters (MERV 4 and 6) to 60-80% for most UFP sizes with the highest rated filter (MERV 16). The deeper bed filters generally achieved higher removal efficiencies than the panel filters, while maintaining a low pressure drop and higher airflow rate in the operating HVAC system. Assuming constant efficiency, a modeling effort using these measured values for new filters and other inputs from real buildings shows that MERV 13-16 filters could reduce the indoor proportion of outdoor UFPs (in the absence of indoor sources) by as much as a factor of 2-3 in a typical single-family residence relative to the lowest efficiency filters, depending in part on particle size. PMID:23590456

  20. Ultrafine particle removal by residential heating, ventilating, and air-conditioning filters.

    PubMed

    Stephens, B; Siegel, J A

    2013-12-01

    This work uses an in situ filter test method to measure the size-resolved removal efficiency of indoor-generated ultrafine particles (approximately 7-100 nm) for six new commercially available filters installed in a recirculating heating, ventilating, and air-conditioning (HVAC) system in an unoccupied test house. The fibrous HVAC filters were previously rated by the manufacturers according to ASHRAE Standard 52.2 and ranged from shallow (2.5 cm) fiberglass panel filters (MERV 4) to deep-bed (12.7 cm) electrostatically charged synthetic media filters (MERV 16). Measured removal efficiency ranged from 0 to 10% for most ultrafine particles (UFP) sizes with the lowest rated filters (MERV 4 and 6) to 60-80% for most UFP sizes with the highest rated filter (MERV 16). The deeper bed filters generally achieved higher removal efficiencies than the panel filters, while maintaining a low pressure drop and higher airflow rate in the operating HVAC system. Assuming constant efficiency, a modeling effort using these measured values for new filters and other inputs from real buildings shows that MERV 13-16 filters could reduce the indoor proportion of outdoor UFPs (in the absence of indoor sources) by as much as a factor of 2-3 in a typical single-family residence relative to the lowest efficiency filters, depending in part on particle size.

  1. Heating, Ventilation, Air Conditioning. Resource Manual for Custodial Training Course #3.

    ERIC Educational Resources Information Center

    Florida State Dept. of Education, Tallahassee. School Plant Management Section.

    Intended as a manual to provide school custodians with some understanding of basic functions of heating, ventilating, and air conditioning equipment for safe, efficient operation. Contains general rules and specifications for providing custodians with a more complete awareness of their equipment and the field of "Climate Control" within the…

  2. FRACTIONAL AEROSOL FILTRATION EFFICIENCY OF IN-DUCT VENTILATION AIR CLEANERS

    EPA Science Inventory

    The filtration efficiency of ventilation air cleaners is highly particle-size dependent over the 0.01 to 3 μm diameter size range. Current standardized test methods, which determine only overall efficiencies for ambient aerosol or other test aerosols, provide data of limited util...

  3. Heating, Ventilation, Air-conditioning, and Refrigeration. Ohio's Competency Analysis Profile.

    ERIC Educational Resources Information Center

    Ohio State Univ., Columbus. Vocational Instructional Materials Lab.

    Developed through a modified DACUM (Developing a Curriculum) process involving business, industry, labor, and community agency representatives in Ohio, this document is a comprehensive and verified employer competency profile for heating, ventilation, air conditioning, and refrigeration occupations. The list contains units (with and without…

  4. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Instructor Edition. Introduction to Construction Series.

    ERIC Educational Resources Information Center

    Oklahoma State Dept. of Vocational and Technical Education, Stillwater. Curriculum and Instructional Materials Center.

    This instructor's guide contains the materials required to teach a competency-based introductory course in heating, ventilating, and air conditioning (HVAC) to students who have chosen to explore careers in construction. It contains three units: HVAC materials, HVAC tools, and applied skills. Each instructional unit includes some or all of the…

  5. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Introduction to Construction Series. Instructor Edition.

    ERIC Educational Resources Information Center

    Associated General Contractors of America, Washington, DC.

    This module on introductory heating, ventilating, and air conditioning (HVAC) is one of a series of modules designed to teach basic skills necessary for entry-level employment in this field. The module contains four instructional units that cover the following topics: (1) HVAC materials; (2) HVAC tools; (3) HVAC layout; and (4) HVAC basic skills.…

  6. Technology evaluation of heating, ventilation, and air conditioning for MIUS application

    NASA Technical Reports Server (NTRS)

    Gill, W. L.; Keough, M. B.; Rippey, J. O.

    1974-01-01

    Potential ways of providing heating, ventilation, and air conditioning for a building complex serviced by a modular integrated utility system (MIUS) are examined. Literature surveys were conducted to investigate both conventional and unusual systems to serve this purpose. The advantages and disadvantages of the systems most compatible with MIUS are discussed.

  7. Optimization of Ventilation Energy Demands and Indoor Air Quality in the ZEBRAlliance Homes

    SciTech Connect

    Hun, D.; Jackson, M.; Shrestha, S.

    2013-09-01

    High-performance homes require that ventilation energy demands and indoor air quality (IAQ) be simultaneously optimized. In this project, Oak Ridge National Laboratory researchers attempted to bridge these two areas by conducting tests in research houses located in Oak Ridge, TN, that were less than 2 years old, energy-efficient (i.e., expected to consume 50% less energy than a house built per the 2006 IRC), tightly-built, unoccupied, and unfurnished. The team identified air pollutants of concern in the test homes that could generally serve as indicators of IAQ, and conduced field experiments and computer simulations to determine the effectiveness and energy required by various techniques that lessened the concentration of these contaminants. Formaldehyde was selected as the main pollutant of concern from initial air sampling surveys. Field data indicate that concentrations were higher during the summer primarily because emissions from sources rise with increases in temperature. Furthermore, supply ventilation and gas-phase filtration were effective means to reduce formaldehyde concentrations; however, exhaust ventilation had minimal influence on this pollutant. Results from simulations suggest that formaldehyde concentrations obtained while ventilating per ASHRAE 62.2-2010 could be decreased by about 20% from May through September through three strategies: 1) increasing ASHRAE supply ventilation by a factor of two, 2) reducing the thermostat setpoint from 76 to 74°F, or 3) running a gas-phase filtration system while decreasing supply ventilation per ASHRAE by half. In the mixed-humid climate of Oak Ridge, these strategies caused minimal to modest increases in electricity cost of ~$5 to ~$15/month depending on outdoor conditions.

  8. Changing ventilation rates in U.S. offices: Implications for health, work performance, energy, and associated economics

    SciTech Connect

    Fisk, William; Black, Douglas; Brunner, Gregory

    2011-07-01

    This paper provides quantitative estimates of benefits and costs of providing different amounts of outdoor air ventilation in U.S. offices. For four scenarios that modify ventilation rates, we estimated changes in sick building syndrome (SBS) symptoms, work performance, short-term absence, and building energy consumption. The estimated annual economic benefits were $13 billion from increasing minimum ventilation rates (VRs) from 8 to 10 L/s per person, $38 billion from increasing minimum VRs from 8 to 15 L/s per person, and $33 billion from increasing VRs by adding outdoor air economizers for the 50% of the office floor area that currently lacks economizers. The estimated $0.04 billion in annual energy-related benefits of decreasing minimum VRs from 8 to 6.5 L/s per person are very small compared to the projected annual costs of $12 billion. Benefits of increasing minimum VRs far exceeded energy costs while adding economizers yielded health, performance, and absence benefits with energy savings.

  9. Laboratory study on the effects of temperature and three ventilation rates on infestations of Varroa destructor in clusters of honey bees (Hymenoptera: Apidae).

    PubMed

    Kozak, Paul R; Currie, Robert W

    2011-12-01

    In this study, reduced levels of ventilation were applied to small clusters of bees under controlled conditions to determine whether lowered ventilation rates and the resulting increased levels of CO2 could increase the mortality rates of varroa. Two experiments were performed at two different temperatures (10 degrees C and 25 degrees C). Both experiments compared varroa mortality among high (360 liters/h), medium (42.5 liters/h), and low (14 liters/h) rates of ventilation. The clusters of bees (approximately 300 worker bees) in bioassay cages with 40 introduced varroa mites were placed into self-contained glass chambers and were randomly assigned to one of the three ventilation treatments within incubators set at either of the two temperatures. Bee and varroa mortality and the levels of CO2 concentration were measured in each of the experimental chambers. In both experiments, CO2 levels within the chamber increased, with a decrease in ventilation with CO2 reaching a maximum of 1.2 +/- 0.45% at 10 degrees C and 2.13 +/- 0.2% at 25 degrees C under low ventilation. At high ventilation rates, CO2 concentration in chamber air was similar at 10 degrees C (1.1 +/- 1.5%) and 25 degrees C (1.9 +/- 1.1%). Both humidity and CO2 concentration were higher at 25 degrees C than at 10 degrees C. Bee mortality was similar within all ventilation rate treatments at either 10 degrees C (11.5 +/- 2.7-19.3 +/- 3.8%) or 25 degrees C (15.2 +/- 1.9-20.7 +/- 3.5%). At 10 degrees C, varroa mortality (percentage dead) was greatest in the high ventilation treatment (12.2 +/- 2.1%), but only slightly higher than under low (3.7 +/- 1.7%) and medium ventilation (4.9 +/- 1.6%). At 25 degrees C, varroa mortality was greatest under low ventilation at 46.12 +/- 7.7% and significantly greater than at either medium (29.7 +/- 7.4%) or low ventilation (9.5 +/- 1.6.1%). This study demonstrates that at 25 degrees C, restricted ventilation, resulting in high levels of CO2 in the surrounding environment of

  10. Desiccant outdoor air preconditioners maximize heat recovery ventilation potentials

    SciTech Connect

    Meckler, M.

    1995-12-31

    Microorganisms are well protected indoors by the moisture surrounding them if the relative humidity is above 70%. They can cause many acute diseases, infections, and allergies. Humidity also has an effect on air cleanliness and causes the building structure and its contents to deteriorate. Therefore, controlling humidity is a very important factor to human health and comfort and the structural longevity of a building. To date, a great deal of research has been done, and is continuing, in the use of both solid and liquid desiccants. This paper introduces a desiccant-assisted system that combines dehumidification and mechanical refrigeration by means of a desiccant preconditioning module that can serve two or more conventional air-conditioning units. It will be demonstrated that the proposed system, also having indirect evaporative cooling within the preconditioning module, can reduce energy consumption and provide significant cost savings, independent humidity and temperature control, and, therefore, improved indoor air quality and enhanced occupant comfort.

  11. Aerodynamic characteristics of the ventilated design for flapping wing micro air vehicle.

    PubMed

    Zhang, G Q; Yu, S C M

    2014-01-01

    Inspired by superior flight performance of natural flight masters like birds and insects and based on the ventilating flaps that can be opened and closed by the changing air pressure around the wing, a new flapping wing type has been proposed. It is known that the net lift force generated by a solid wing in a flapping cycle is nearly zero. However, for the case of the ventilated wing, results for the net lift force are positive which is due to the effect created by the "ventilation" in reducing negative lift force during the upstroke. The presence of moving flaps can serve as the variable in which, through careful control of the areas, a correlation with the decrease in negative lift can be generated. The corresponding aerodynamic characteristics have been investigated numerically by using different flapping frequencies and forward flight speeds. PMID:24683339

  12. Measuring Outdoor Air Intake Rates into Existing Building

    SciTech Connect

    Fisk, William; Sullivan, Douglas; Cohen, Sebastian; Han, Hwataik

    2009-04-16

    Practical and accurate technologies are needed for continuously measuring and controlling outdoor air (OA) intake rates in commercial building heating, ventilating, and air conditioning (HVAC) systems. This project evaluated two new measurement approaches. Laboratory experiments determined that OA flow rates were measurable with errors generally less than 10 percent using electronic air velocity probes installed between OA intake louver blades or at the outlet face of louvers. High accuracy was maintained with OA flow rates as low as 15 percent of the maximum for the louvers. Thus, with this measurement approach HVAC systems do not need separate OA intakes for minimum OA supply. System calibration parameters are required for each unique combination of louver type and velocity sensor location but calibrations are not necessary for each system installation. The research also determined that the accuracy of measuring OA flow rates with velocity probes located in the duct downstream of the intake louver was not improved by installing honeycomb airflow straighteners upstream of the probes. Errors varied with type of upstream louver, were as high as 100 percent, and were often greater than 25 percent. In conclusion, use of electronic air velocity probes between the blades of OA intake louvers or at the outlet face of louvers is a highly promising means of accurately measuring rates of OA flow into HVAC systems. The use of electronic velocity probes downstream of airflow straighteners is less promising, at least with the relatively small OA HVAC inlet systems employed in this research.

  13. Developing evidence-based prescriptive ventilation rate standards for commercial buildings in California: a proposed framework

    SciTech Connect

    Mendell, Mark J.; Fisk, William J.

    2014-02-01

    Background - The goal of this project, with a focus on commercial buildings in California, was to develop a new framework for evidence-based minimum ventilation rate (MVR) standards that protect occupants in buildings while also considering energy use and cost. This was motivated by research findings suggesting that current prescriptive MVRs in commercial buildings do not provide occupants with fully safe and satisfactory indoor environments. Methods - The project began with a broad review in several areas ? the diverse strategies now used for standards or guidelines for MVRs or for environmental contaminant exposures, current knowledge about adverse human effects associated with VRs, and current knowledge about contaminants in commercial buildings, including their their presence, their adverse human effects, and their relationships with VRs. Based on a synthesis of the reviewed information, new principles and approaches are proposed for setting evidence-based VRs standards for commercial buildings, considering a range of human effects including health, performance, and acceptability of air. Results ? A review and evaluation is first presented of current approaches to setting prescriptive building ventilation standards and setting acceptable limits for human contaminant exposures in outdoor air and occupational settings. Recent research on approaches to setting acceptable levels of environmental exposures in evidence-based MVR standards is also described. From a synthesis and critique of these materials, a set of principles for setting MVRs is presented, along with an example approach based on these principles. The approach combines two sequential strategies. In a first step, an acceptable threshold is set for each adverse outcome that has a demonstrated relationship to VRs, as an increase from a (low) outcome level at a high reference ventilation rate (RVR, the VR needed to attain the best achievable levels of the adverse outcome); MVRs required to meet each

  14. Air Controlman 1 & C: Rate Training Manual.

    ERIC Educational Resources Information Center

    Naval Training Command, Pensacola, FL.

    The manual is designed for use in preparing for advancement within the Navy Air Controlman rating, which designates a professional air traffic controller, unlike the more specialized center or tower controllers. However, minimum qualifications for the rating include completion of the Federal Aviation Administration (FAA) written examination for…

  15. Response of direct thoron progeny sensors (DTPS) to various aerosol concentrations and ventilation rates

    NASA Astrophysics Data System (ADS)

    Mishra, Rosaline; Prajith, R.; Sapra, B. K.; Mayya, Y. S.

    2010-03-01

    Direct thoron/radon progeny sensors (DTPS/DRPS) are absorber mounted LR115 type track detectors for measuring the time-averaged progeny concentrations. Through a large number of experiments, the sensitivity factor of these sensors in natural indoor environment was found to be nearly constant at a value of 0.94 Tr cm -2 d -1/EETC (Bq m -3) for DTPS and 0.09 Tr cm -2 d -1/EERC (Bq m -3) for DRPS. The constancy of the sensitivity factor in the natural environments is attributed primarily to the presence of large aerosol concentrations and relatively low ventilation rates in time-averaged measurements. However, detailed model calculations suggest that in extreme scenario i.e. at high ventilation rate and low aerosol concentrations, the sensitivity factor can be quite different. Such situations are likely to occur in occupational plant areas. Therefore systematic chamber experiments were carried out to using DTPS, to estimate the variability of the sensitivity factor in these extreme conditions. In the first set, the sensitivity factor of DTPS was measured in 6 different aerosol concentrations at zero ventilation rates. The sensitivity factor showed a steep decrease as the aerosol concentration increased to about 8554 particle cm -3, after which it remained almost constant with increase in aerosol concentration. The second set of experiments was conducted at ˜5000 particles cm -3 at three different ventilation rates. The sensitivity factor was found to increase with increase in ventilation rate. The results are further discussed.

  16. Prototype Systems for Measuring Outdoor Air Intake Rates in Rooftop Air Handlers

    SciTech Connect

    Fisk, William J.; Chan, Wanyu R.; Hotchi, Toshifumi

    2015-01-01

    The widespread absence of systems for real-time measurement and feedback control, of minimum outdoor air intake rates in HVAC systems contributes to the poor control of ventilation rates in commercial buildings. Ventilation rates affect building energy consumption and influence occupant health. The project designed fabricated and tested four prototypes of systems for measuring rates of outdoor air intake into roof top air handlers. All prototypes met the ±20% accuracy target at low wind speeds, with all prototypes accurate within approximately ±10% after application of calibration equations. One prototype met the accuracy target without a calibration. With two of four prototype measurement systems, there was no evidence that wind speed or direction affected accuracy; however, winds speeds were generally below usually 3.5 m s-1 (12.6 km h-1) and further testing is desirable. The airflow resistance of the prototypes was generally less than 35 Pa at maximum RTU air flow rates. A pressure drop of this magnitude will increase fan energy consumption by approximately 4%. The project did not have resources necessary to estimate costs of mass produced systems. The retail cost of components and materials used to construct prototypes ranged from approximately $1,200 to $1,700. The test data indicate that the basic designs developed in this project, particularly the designs of two of the prototypes, have considerable merit. Further design refinement, testing, and cost analysis would be necessary to fully assess commercial potential. The designs and test results will be communicated to the HVAC manufacturing community.

  17. Effects of Classroom Ventilation Rate and Temperature on Students’ Test Scores

    PubMed Central

    2015-01-01

    Using a multilevel approach, we estimated the effects of classroom ventilation rate and temperature on academic achievement. The analysis is based on measurement data from a 70 elementary school district (140 fifth grade classrooms) from Southwestern United States, and student level data (N = 3109) on socioeconomic variables and standardized test scores. There was a statistically significant association between ventilation rates and mathematics scores, and it was stronger when the six classrooms with high ventilation rates that were indicated as outliers were filtered (> 7.1 l/s per person). The association remained significant when prior year test scores were included in the model, resulting in less unexplained variability. Students’ mean mathematics scores (average 2286 points) were increased by up to eleven points (0.5%) per each liter per second per person increase in ventilation rate within the range of 0.9–7.1 l/s per person (estimated effect size 74 points). There was an additional increase of 12–13 points per each 1°C decrease in temperature within the observed range of 20–25°C (estimated effect size 67 points). Effects of similar magnitude but higher variability were observed for reading and science scores. In conclusion, maintaining adequate ventilation and thermal comfort in classrooms could significantly improve academic achievement of students. PMID:26317643

  18. Metabolically-Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates (External Review Draft)

    EPA Science Inventory

    EPA has released a draft report entitled, Metabolically-Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates, for independent external peer review and public comment. NCEA published the Exposure Factors Handbook in 1997. This comprehens...

  19. Application information on typical hygrometers used in heating, ventilating and air conditioning (HVAC) systems

    SciTech Connect

    Kao, J.Y.; Snyder, W.J.

    1982-01-01

    Hygrometer selection information is provided for application in heating, ventilating and air-conditioning (HVAC) systems. A general review of hygrometer literature has been provided and the most commonly used ones for HVAC are discussed. Typical hygrometer parameters are listed to indicate the type of performance that can be expected. Laboratory test results of self-regulating, salt-phase transition hygrometers are presented and discussed in detail.

  20. Heating, Ventilating, and Air-Conditioning: Recent Advances in Diagnostics and Controls to Improve Air-Handling System Performance

    NASA Astrophysics Data System (ADS)

    Wray, C. P.; Sherman, M. H.; Walker, I. S.; Dickerhoff, D. J.; Federspiel, C. C.

    2008-09-01

    The performance of air-handling systems in buildings needs to be improved. Many of the deficiencies result from myths and lore and a lack of understanding about the non-linear physical principles embedded in the associated technologies. By incorporating these principles, a few important efforts related to diagnostics and controls have already begun to solve some of the problems. This paper illustrates three novel solutions: one rapidly assesses duct leakage, the second configures ad hoc duct-static-pressure reset strategies, and the third identifies useful intermittent ventilation strategies. By highlighting these efforts, this paper seeks to stimulate new research and technology developments that could further improve air-handling systems.

  1. THE EFFECT OF VENTILATION ON EMISSION RATES OF WOOD FINISHING MATERIALS

    EPA Science Inventory

    The rate of emission of organic compounds from building materials varies according to: type of material, material loading (area of material/volume of room), compound emitted, temperature, humidity, and ventilation rate. For some compounds and materials (e.g., formaldehyde from pa...

  2. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique.

    PubMed

    Battista, L; Sciuto, S A; Scorza, A

    2013-03-01

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it; the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 × 10(-4) m(3)∕s (18.0 l∕min) for the mono-directional sensor and a measurement range of ±3.00 × 10(-4) m(3)∕s (±18.0 l∕min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed theoretical model: for the mono

  3. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique

    SciTech Connect

    Battista, L.; Sciuto, S. A.; Scorza, A.

    2013-03-15

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it; the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 Multiplication-Sign 10{sup -4} m{sup 3}/s (18.0 l/min) for the mono-directional sensor and a measurement range of {+-}3.00 Multiplication-Sign 10{sup -4} m{sup 3}/s ({+-}18.0 l/min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed

  4. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique

    NASA Astrophysics Data System (ADS)

    Battista, L.; Sciuto, S. A.; Scorza, A.

    2013-03-01

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it; the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 × 10-4 m3/s (18.0 l/min) for the mono-directional sensor and a measurement range of ±3.00 × 10-4 m3/s (±18.0 l/min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed theoretical model: for the mono-directional configuration, the

  5. Talaromyces rubrifaciens, a new species discovered from heating, ventilation and air conditioning systems in China.

    PubMed

    Luo, Yi; Lu, Xiaohong; Bi, Wu; Liu, Fan; Gao, Weiwei

    2016-01-01

    A new Talaromyces species, T. rubrifaciens, was isolated from supply air outlets of heating, ventilation and air conditioning (HVAC) systems in three kinds of public building in Beijing and Nanjing, China. Morphologically it exhibits many characters of section Trachyspermi but is distinguished from other species of this section by restricted growth and broad and strictly biverticillate conidiophores. Phylogenetic analyses based on the internal transcribed spacer rDNA (ITS), β-tubulin (BenA), calmodulin (CaM) and RNA polymerase second largest subunit (RPB2) genes reveal that T. rubrifaciens is a distinct species in section Trachyspermi. PMID:27055570

  6. Talaromyces rubrifaciens, a new species discovered from heating, ventilation and air conditioning systems in China.

    PubMed

    Luo, Yi; Lu, Xiaohong; Bi, Wu; Liu, Fan; Gao, Weiwei

    2016-01-01

    A new Talaromyces species, T. rubrifaciens, was isolated from supply air outlets of heating, ventilation and air conditioning (HVAC) systems in three kinds of public building in Beijing and Nanjing, China. Morphologically it exhibits many characters of section Trachyspermi but is distinguished from other species of this section by restricted growth and broad and strictly biverticillate conidiophores. Phylogenetic analyses based on the internal transcribed spacer rDNA (ITS), β-tubulin (BenA), calmodulin (CaM) and RNA polymerase second largest subunit (RPB2) genes reveal that T. rubrifaciens is a distinct species in section Trachyspermi.

  7. Effectiveness of photocatalytic filter for removing volatile organic compounds in the heating, ventilation, and air conditioning system.

    PubMed

    Yu, Kuo-Pin; Lee, Grace Whei-May; Huang, Wei-Ming; Wu, Chih-Cheng; Lou, Chia-ling; Yang, Shinhao

    2006-05-01

    Nowadays, the heating, ventilation, and air conditioning (HVAC) system has been an important facility for maintaining indoor air quality. However, the primary function of typical HVAC systems is to control the temperature and humidity of the supply air. Most indoor air pollutants, such as volatile organic compounds (VOCs), cannot be removed by typical HVAC systems. Thus, some air handling units for removing VOCs should be added in typical HVAC systems. Among all of the air cleaning techniques used to remove indoor VOCs, photocatalytic oxidation is an attractive alternative technique for indoor air purification and deodorization. The objective of this research is to investigate the VOC removal efficiency of the photocatalytic filter in a HVAC system. Toluene and formaldehyde were chosen as the target pollutants. The experiments were conducted in a stainless steel chamber equipped with a simplified HVAC system. A mechanical filter coated with Degussa P25 titania photocatalyst and two commercial photocatalytic filters were used as the photocatalytic filters in this simplified HVAC system. The total air change rates were controlled at 0.5, 0.75, 1, 1.25, and 1.5 hr(-1), and the relative humidity (RH) was controlled at 30%, 50%, and 70%. The ultraviolet lamp used was a 4-W, ultraviolet-C (central wavelength at 254 nm) strip light bulb. The first-order decay constant of toluene and formaldehyde found in this study ranged from 0.381 to 1.01 hr(-1) under different total air change rates, from 0.34 to 0.433 hr(-1) under different RH, and from 0.381 to 0.433 hr(-1) for different photocatalytic filters.

  8. Capability of air filters to retain airborne bacteria and molds in heating, ventilating and air-conditioning (HVAC) systems.

    PubMed

    Möritz, M; Peters, H; Nipko, B; Rüden, H

    2001-07-01

    The capability of air filters (filterclass: F6, F7) to retain airborne outdoor microorganisms was examined in field experiments in two heating, ventilating and air conditioning (HVAC) systems. At the beginning of the 15-month investigation period, the first filter stages of both HVAC systems were equipped with new unused air filters. The number of airborne bacteria and molds before and behind the filters were determined simultaneously in 14 days-intervals using 6-stage Andersen cascade impactors. Under relatively dry (< 80% R. H.) and warm (> 12 degrees C) outdoor air conditions air filters led to a marked reduction of airborne microorganism concentrations (bacteria by approximately 70% and molds by > 80%). However, during long periods of high relative humidity (> 80% R. H.) a proliferation of bacteria on air filters with subsequent release into the filtered air occurred. These microorganisms were mainly smaller than 1.1 microns therefore being part of the respirable fraction. The results showed furthermore that one possibility to avoid microbial proliferation is to limit the relative humidity in the area of the air filters to 80% R. H. (mean of 3 days), e.g. by using preheaters in front of air filters in HVAC-systems.

  9. Effect of car speed on amount of air supplied by ventilation system to the space of car cabin

    NASA Astrophysics Data System (ADS)

    Fišer, Jan; Pokorný, Jan

    2014-03-01

    The amount of air supplied by ventilation system (HVAC system) of a car into a cabin is one of the main parameters for the correct simulation and prediction of a car cabin heat load. This amount is not based only on the current setting of the HVAC system, but also on the actual operating conditions and speed of the car. The authors therefore carried out experiments in the cabin of a passenger car in real traffic, while observing the amount of air on the speed of the car and setting of flap in mixing chamber. In a subsequent analysis the authors defined dependence of the airflow rate supplied by HVAC system on the speed of the car. Obtained empirical formulas were then used as a part of the code which calculates the data for the HVAC boundary conditions in the simulation of the car cabin environment.

  10. Dispersal of exhaled air and personal exposure in displacement ventilated rooms.

    PubMed

    Bjørn, E; Nielsen, P V

    2002-09-01

    The influence of the human exhalation on flow fields, contaminant distributions, and personal exposure in displacement ventilated rooms is studied together with the effects of physical movement. Experiments are conducted in full-scale test rooms with life-sized breathing thermal manikins. Numerical simulations support the experiments. Air exhaled through the mouth can lock in a thermally stratified layer, if the vertical temperature gradient in breathing zone height is sufficiently large. With exhalation through the nose, exhaled air flows to the upper part of the room. The exhalation flow from both nose and mouth is able to penetrate the breathing zone of another person standing nearby. The stratification of exhaled air breaks down if there is physical movement in the room. As movement increases, the concentration distribution in the room will move towards a fully mixed situation. The protective effect of the boundary layer flow around the body of a moving person disappears at low speed, and is reduced for a seated person placed nearby due to horizontal air movements, which can also cause rebreathing of exhaled air for the seated person. The results indicate that the effect of the exhalation flow is no acute problem in most normal ventilation applications. However, exhalation and local effects caused by movement may be worth considering if one wishes to contain contaminants in certain areas, as in the case of tobacco smoking, in hospitals and clinics, or in certain industries.

  11. Effect of central ventilation and air conditioner system on the concentration and health risk from airborne polycyclic aromatic hydrocarbons.

    PubMed

    Lv, Jinze; Zhu, Lizhong

    2013-03-01

    Central ventilation and air conditioner systems are widely utilized nowadays in public places for air exchange and temperature control, which significantly influences the transfer of pollutants between indoors and outdoors. To study the effect of central ventilation and air conditioner systems on the concentration and health risk from airborne pollutants, a spatial and temporal survey was carried out using polycyclic aromatic hydrocarbons (PAHs) as agent pollutants. During the period when the central ventilation system operated without air conditioning (AC-off period), concentrations of 2-4 ring PAHs in the model supermarket were dominated by outdoor levels, due to the good linearity between indoor air and outdoor air (r(p) > 0.769, p < 0.05), and the slopes (1.2-4.54) indicated that ventilating like the model supermarket increased the potential health risks from low molecular weight PAHs. During the period when the central ventilation and air conditioner systems were working simultaneously (AC-on period), although the total levels of PAHs were increased, the concentrations and percentage of the particulate PAHs indoors declined significantly. The BaP equivalency (BaPeq) concentration indicated that utilization of air conditioning reduced the health risks from PAHs in the model supermarket. PMID:23923426

  12. Aerodynamic Characteristics of the Ventilated Design for Flapping Wing Micro Air Vehicle

    PubMed Central

    Zhang, G. Q.; Yu, S. C. M.

    2014-01-01

    Inspired by superior flight performance of natural flight masters like birds and insects and based on the ventilating flaps that can be opened and closed by the changing air pressure around the wing, a new flapping wing type has been proposed. It is known that the net lift force generated by a solid wing in a flapping cycle is nearly zero. However, for the case of the ventilated wing, results for the net lift force are positive which is due to the effect created by the “ventilation” in reducing negative lift force during the upstroke. The presence of moving flaps can serve as the variable in which, through careful control of the areas, a correlation with the decrease in negative lift can be generated. The corresponding aerodynamic characteristics have been investigated numerically by using different flapping frequencies and forward flight speeds. PMID:24683339

  13. Effects of animal activity and air temperature on methane and ammonia emissions from a naturally ventilated building for dairy cows

    NASA Astrophysics Data System (ADS)

    Ngwabie, N. M.; Jeppsson, K.-H.; Gustafsson, G.; Nimmermark, S.

    2011-12-01

    Knowledge of how different factors affect gas emissions from animal buildings can be useful for emission prediction purposes and for the improvement of emission abatement techniques. In this study, the effects of dairy cow activity and indoor air temperature on gas emissions were examined. The concentrations of CH 4, NH 3, CO 2 and N 2O inside and outside a dairy cow building were measured continuously between February and May together with animal activity and air temperature. The building was naturally ventilated and had a solid concrete floor which sloped towards a central urine gutter. Manure was scraped from the floor once every hour in the daytime and once every second hour at night into a partly covered indoor pit which was emptied daily at 6 a.m. and at 5 p.m. Gas emissions were calculated from the measured gas concentrations and ventilation rates estimated by the CO 2 balance method. The animal activity and emission rates of CH 4 and NH 3 showed significant diurnal variations with two peaks which were probably related to the feeding routine. On an average day, CH 4 emissions ranged from 7 to 15 g LU -1 h -1 and NH 3 emissions ranged from 0.4 to 1.5 g LU -1 h -1 (1 LU = 500 kg animal weight). Mean emissions of CH 4 and NH 3 were 10.8 g LU -1 h -1 and 0.81 g LU -1 h -1, respectively. The NH 3 emissions were comparable to emissions from tied stall buildings and represented a 4% loss in manure nitrogen. At moderate levels, temperature seems to affect the behaviour of dairy cows and in this study where the daily indoor air temperature ranged from about 5 up to about 20 °C, the daily activity of the cows decreased with increasing indoor air temperature ( r = -0.78). Results suggest that enteric fermentation is the main source of CH 4 emissions from systems of the type in this study, while NH 3 is mainly emitted from the manure. Daily CH 4 emissions increased significantly with the activity of the cows ( r = 0.61) while daily NH 3 emissions increased

  14. Quantifying the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building.

    PubMed

    Tong, Zheming; Chen, Yujiao; Malkawi, Ali; Adamkiewicz, Gary; Spengler, John D

    2016-01-01

    Improper natural ventilation practices may deteriorate indoor air quality when in close proximity to roadways, although the intention is often to reduce energy consumption. In this study, we employed a CFD-based air quality model to quantify the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building. Our study found that the building envelope restricts dispersion and dilution of particulate matter. The indoor concentration in the baseline condition located 10m away from the roadway is roughly 16-21% greater than that at the edge of the roadway. The indoor flow recirculation creates a well-mixed zone with little variation in fine particle concentration (i.e., 253nm). For ultrafine particles (<100nm), a noticeable decrease in particle concentrations indoors with increasing distance from the road is observed due to Brownian and turbulent diffusion. In addition, the indoor concentration strongly depends on the distance between the roadway and building, particle size, wind condition, and window size and location. A break-even point is observed at D'~2.1 (normalized distance from the roadway by the width of the road). The indoor particle concentration is greater than that at the highway where D'<2.1, and vice versa. For new building planning, the distance from the roadway and the ambient wind condition need to be considered at the early design stage whereas the size and location of the window openings, the interior layout, and the placement of fresh air intakes are important to the indoor air quality of existing buildings adjacent to roadways. PMID:26829764

  15. Quantifying the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building.

    PubMed

    Tong, Zheming; Chen, Yujiao; Malkawi, Ali; Adamkiewicz, Gary; Spengler, John D

    2016-01-01

    Improper natural ventilation practices may deteriorate indoor air quality when in close proximity to roadways, although the intention is often to reduce energy consumption. In this study, we employed a CFD-based air quality model to quantify the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building. Our study found that the building envelope restricts dispersion and dilution of particulate matter. The indoor concentration in the baseline condition located 10m away from the roadway is roughly 16-21% greater than that at the edge of the roadway. The indoor flow recirculation creates a well-mixed zone with little variation in fine particle concentration (i.e., 253nm). For ultrafine particles (<100nm), a noticeable decrease in particle concentrations indoors with increasing distance from the road is observed due to Brownian and turbulent diffusion. In addition, the indoor concentration strongly depends on the distance between the roadway and building, particle size, wind condition, and window size and location. A break-even point is observed at D'~2.1 (normalized distance from the roadway by the width of the road). The indoor particle concentration is greater than that at the highway where D'<2.1, and vice versa. For new building planning, the distance from the roadway and the ambient wind condition need to be considered at the early design stage whereas the size and location of the window openings, the interior layout, and the placement of fresh air intakes are important to the indoor air quality of existing buildings adjacent to roadways.

  16. Rebound in ventilator-associated pneumonia rates during a prevention checklist washout period.

    PubMed

    Cheema, Ali A; Scott, Annette M; Shambaugh, Karen J; Shaffer-Hartman, Jacqueline N; Dechert, Ronald E; Hieber, Susan M; Gosbee, John W; Niedner, Matthew F

    2011-09-01

    OBJECTIVE To describe the washout effect after stopping a prevention checklist for ventilator-associated pneumonia (VAP). METHODS VAP rates were prospectively monitored for special cause variation over 42 months in a paediatric intensive care unit. A VAP prevention bundle was implemented, consisting of head of bed elevation, oral care, suctioning device management, ventilator tubing care, and standard infection control precautions. Key practices of the bundle were implemented with a checklist and subsequently incorporated into the nursing and respiratory care bedside flow sheets to achieve long-term sustainability. Compliance with the VAP bundle was monitored throughout. The timeline for the project was retrospectively categorised into the benchmark phase, the checklist phase (implementation), the checklist washout phase, and the flowsheet phase (cues in the flowsheet). RESULTS During the checklist phase (12 months), VAP bundle compliance rose from <50% to >75% and the VAP rate fell from 4.2 to 0.7 infections per 1000 ventilator days (p<0.059). Unsolicited qualitative feedback from frontline staff described overburdensome documentation requirements, form fatigue, and checklist burnout. During the checklist washout phase (4 months), VAP rates rose to 4.8 infections per 1000 ventilator days (p<0.042). In the flowsheet phase, the VAP rate dropped to 0.8 infections per 1000 ventilator days (p<0.047). CONCLUSIONS Salient cues to drive provider behaviour towards best practice are helpful to sustain process improvement, and cessation of such cues should be approached warily. Initial education, year-long habit formation, and effective early implementation demonstrated no appreciable effect on the VAP rate during the checklist washout period.

  17. The effect of increased classroom ventilation rate indicated by reduced CO2 concentration on the performance of schoolwork by children.

    PubMed

    Petersen, S; Jensen, K L; Pedersen, A L S; Rasmussen, H S

    2016-06-01

    The article reports on an experiment which investigated the effect of increased classroom ventilation rate on the performance of children aged 10-12 years. The experiment was executed at two different schools (two classrooms at each school) as a double-blind 2 × 2 crossover intervention where four different performance tests were used as surrogates for short-term concentration and logical thinking. Only complete pairs of test responses were included in the within-subject comparisons of performance, and data were not corrected for learning and fatigue effects. Analysis of the total sample suggested the number of correct answers was improved significantly in four of four performance test, addition (6.3%), number comparison (4.8%), grammatical reasoning (3.2%), and reading and comprehension (7.4%), when the outdoor air supply rate was increased from an average of 1.7 (1.4-2.0) to 6.6 l/s per person. The increased outdoor air supply rate did not have any significant effect on the number of errors in any of the performance tests. Results from questionnaires regarding pupil perception of the indoor environment, reported Sick Building Syndrome symptoms, and motivation suggested that the study classroom air was perceived more still and pupil were experiencing less pain in the eyes in the recirculation condition compared to the fresh air condition. PMID:25866236

  18. Development and Evaluation of a New Air Exchange Rate Algorithm for the Stochastic Human Exposure and Dose Simulation Model (ISES Presentation)

    EPA Science Inventory

    Previous exposure assessment panel studies have observed considerable seasonal, between-home and between-city variability in residential pollutant infiltration. This is likely a result of differences in home ventilation, or air exchange rates (AER). The Stochastic Human Exposure ...

  19. Control of pacemaker rate by impedance-based respiratory minute ventilation.

    PubMed

    Alt, E; Heinz, M; Hirgstetter, C; Emslander, H P; Daum, S; Blömer, H

    1987-08-01

    Several studies have shown that the capability for exercise can be increased in patients with pacemakers by means of adjusting the rate. Respiration is one of the parameters considered for rate control. The aim of our study was to determine how respiratory parameters such as ventilation, tidal volume, and respiratory rate are capable of controlling the pacemaker rate, especially when measured indirectly by means of impedance plethysmography. We examined four volunteers and eight patients with implanted cardiac pacemakers using bicycle ergometry at increasing work loads. We recorded heart rate, uptake of oxygen, and ventilation directly (by pneumotachygraphy) and indirectly (by chest wall impedance plethysmography). A good correlation of directly to indirectly measured ventilation (r = 0.8687) was found. Our study suggests that respiratory minute volume is more appropriate for rate control of physiologic pacemakers than tidal volume or respiratory rate alone. Measurement by means of impedance plethysmography is sufficiently precise to be used for this purpose. Further studies must be conducted as to the optimum realization within an implantable device.

  20. Ventilation, air confinement and high radon level in an underground gallery studied from profiles measurements.

    NASA Astrophysics Data System (ADS)

    Richon, P.; Perrier, F.; Sabroux, J.-C.; Pili, E.; Ferry, C.; Dezayes, C.; Voisin, V.

    2003-04-01

    An horizontal closed-end tunnel, 128 m long and 2 m in diameter, located within the eastern margin of the Belledonne crystalline basement, French Alps, near the west shore of the Roselend artificial lake, 600 m NE of the dam, has been instrumented since 1995 for radon emanation and deformation measurements. Radon bursts are repeatedly associated with transient deformation events induced by variations in lake levels (Trique et al., 1999). This high radon anomalies (up to 30,000 Bq.m-3) in the air of the tunnel result from its particular geometry, its excellent confinement, the water and radium-226 contents of rocks, and the crossing of several faults. We calculated the equilibrium factor F, directly proportional to air ventilation, from the ratios of radon-222 gas activity measured with an AlphaGUARDTM, and the Potential Alpha Energy Concentration (PAEC, in μJ.m-3) of its short-lived daughters measured with a TracerlabTM, simultaneously in five locations along the tunnel. The calculated equilibrium factors of 0.60 to 0.78 show that confinement is very good all along the tunnel. Fast Fourier Transform of the radon-222 signals measured during six months simultaneously with six BarasolTM distributed along the tunnel shows also the poor ventilation and the weak influence of atmospheric pressure and air temperature.

  1. Towards energy efficient operation of Heating, Ventilation and Air Conditioning systems via advanced supervisory control design

    NASA Astrophysics Data System (ADS)

    Oswiecinska, A.; Hibbs, J.; Zajic, I.; Burnham, K. J.

    2015-11-01

    This paper presents conceptual control solution for reliable and energy efficient operation of heating, ventilation and air conditioning (HVAC) systems used in large volume building applications, e.g. warehouse facilities or exhibition centres. Advanced two-level scalable control solution, designed to extend capabilities of the existing low-level control strategies via remote internet connection, is presented. The high-level, supervisory controller is based on Model Predictive Control (MPC) architecture, which is the state-of-the-art for indoor climate control systems. The innovative approach benefits from using passive heating and cooling control strategies for reducing the HVAC system operational costs, while ensuring that required environmental conditions are met.

  2. Scuba tanks as a compressed air source in positive-pressure ventilation.

    PubMed

    Stewart, T

    1992-06-01

    Throughout the developing world there is a general problem of ensuring regular deliveries of medical supplies to hospitals. This includes the supply of compressed gases. At one regional hospital in Vanuatu, we were faced with the problem of how to provide economically a source of compressed gas at regulated pressure to drive an anaesthetic ventilator. We eventually adapted the output from a Scuba cylinder for this purpose. This paper describes the simple modifications necessary and suggests other uses for this source of compressed air that could be implemented in hospitals with small to medium case loads and access to a diving compressor.

  3. Continuous Distributions of Ventilation-Perfusion Ratios in Normal Subjects Breathing Air and 100% O2

    PubMed Central

    Wagner, Peter D.; Laravuso, Raymond B.; Uhi, Richard R.; West, John B.

    1974-01-01

    A new method has been developed for measuring virtually continuous distributions of ventilation-perfusion ratios (V̇A/Q̇) based on the steadystate elimination of six gases of different solubilities. The method is applied here to 12 normal subjects, aged 21—60. In nine, the distributions were compared breathing air and 100% oxygen, while in the remaining three, effects of changes in posture were examined. In four young semirecumbent subjects (ages 21—24) the distributions of blood flow and ventilation with respect to V̇A/Q̇ were virtually log-normal with little dispersion (mean log standard deviations 0.43 and 0.35, respectively). The 95.5% range of both blood flow and ventilation was from V̇A/Q̇ ratios of 0.3—2.1, and there was no intrapulmonary shunt (V̇A/Q̇ of 0). On breathing oxygen, a shunt developed in three of these subjects, the mean value being 0.5% of the cardiac output. The five older subjects (ages 39—60) had broader distributions (mean log standard deviations, 0.76 and 0.44) containing areas with V̇A/Q ratios in the range 0.01—0.1 in three subjects. As for the young subjects, there was no shunt breathing air, but all five developed a shunt breathing oxygen (mean value 3.2%), and in one the value was 10.7%. Postural changes were generally those expected from the known effects of gravity, with more ventilation to high VA/Q areas when the subjects were erect than supine. Measurements of the shunt while breathing oxygen, the Bohr CO2 dead space, and the alveolar-arterial oxygen difference were all consistent with the observed distributions. Since the method involves only a short infusion of dissolved inert gases, sampling of arterial blood and expired gas, and measurement of cardiac output and minute ventilation, we conclude that it is well suited to the investigation of pulmonary gas exchange in man. PMID:4601004

  4. Estimation of the respiratory ventilation rate of preschool children in daily life using accelerometers.

    PubMed

    Kawahara, Junko; Tanaka, Shigeho; Tanaka, Chiaki; Hikihara, Yuki; Aoki, Yasunobu; Yonemoto, Junzo

    2011-01-01

    Inhalation rate is an essential factor for determining the inhaled dose of air pollutants. Here, accelerometers were used to develop regression equations for predicting the minute ventilation rate (V(E)) to estimate the daily inhalation rate in young children. Body acceleration and heart rate were measured in 29 Japanese preschool children (6 yr of age) during nine different levels of activities (lying down, sitting, standing, playing with plastic bricks, walking, building with blocks, climbing stairs, ball tossing, and running) using the Actical omnidirectional accelerometer, the ActivTracer triaxial accelerometer, and a heart rate monitor. Measurements were calibrated against the V(E) measured by the Douglas bag method. ActivTracer accelerometer measurements gave a strong correlation with V(E) (Pearson's r = 0.913), which was marginally stronger than that for the Actical counts (r = 0.886) and comparable to the correlation between heart rate and logarithmic V(E) (r = 0.909). According to the linear regression equation, the V(E) for lying down, sitting, standing, playing with plastic bricks, walking, and running was overestimated by 14-60% by the Actical and by 14-37% by the ActivTracer. By comparison, for building with blocks, climbing stairs, and ball tossing, the V(E) was underestimated by 19-23% by the Actical and by 13-18% by the ActivTracer. When these three activities were excluded, a stronger correlation was found between the V(E) and ActivTracer measurements (r = 0.949); this correlation was 0.761 for the three excluded activities. Discriminant analysis showed that the ratio between vertical and horizontal acceleration obtained by the ActivTracer could discriminate walking from building with blocks, climbing stairs, and ball tossing with a sensitivity of 75%. The error in estimating V(E) was considerably improved for the ActivTracer measurements by the use of two regression equations developed for each type of activity. PMID:21305887

  5. Summary of human responses to ventilation

    SciTech Connect

    Seppanen, Olli A.; Fisk, William J.

    2004-06-01

    The effects of ventilation on indoor air quality and health is a complex issue. It is known that ventilation is necessary to remove indoor generated pollutants from indoor air or dilute their concentration to acceptable levels. But, as the limit values of all pollutants are not known, the exact determination of required ventilation rates based on pollutant concentrations and associated risks is seldom possible. The selection of ventilation rates has to be based also on epidemiological research (e.g. Seppanen et al., 1999), laboratory and field experiments (e.g. CEN 1996, Wargocki et al., 2002a) and experience (e.g. ECA 2003). Ventilation may also have harmful effects on indoor air quality and climate if not properly designed, installed, maintained and operated as summarized by Seppdnen (2003). Ventilation may bring indoors harmful substances that deteriorate the indoor environment. Ventilation also affects air and moisture flow through the building envelope and may lead to moisture problems that deteriorate the structures of the building. Ventilation changes the pressure differences over the structures of building and may cause or prevent the infiltration of pollutants from structures or adjacent spaces. Ventilation is also in many cases used to control the thermal environment or humidity in buildings. Ventilation can be implemented with various methods which may also affect health (e.g. Seppdnen and Fisk, 2002, Wargocki et al., 2002a). In non residential buildings and hot climates, ventilation is often integrated with air-conditioning which makes the operation of ventilation system more complex. As ventilation is used for many purposes its health effects are also various and complex. This paper summarizes the current knowledge on positive and negative effects of ventilation on health and other human responses. The focus of the paper is on office-type working environment and residential buildings. In the industrial premises the problems of air quality are usually

  6. A survey and critical review of the literature on indoor air quality, ventilation and health symptoms in schools

    SciTech Connect

    Daisey, J.M.; Angell, W.J.

    1998-03-01

    A survey and critical review were undertaken of existing published literature and reports on indoor air quality (IAQ), ventilation, and IAQ- and building-related health problems in schools, including California schools. Over 450 relevant publications were obtained and reviewed, including papers published in the archival peer-reviewed scientific literature, proceedings of scientific meetings, government reports, 77 NIOSH Health Hazard Evaluation Reports (HHER) and 70 reports on investigations of problem schools in California. Most of the reviewed literature was for complaint or problem schools. The types of health symptoms reported in schools were very similar to those defined as sick building syndrome (SBS) symptoms, although this may be due, at least in part, to the type of health symptom questionnaires used. Some of the symptoms, e.g., wheezing, are indicative of asthma. In the studies in which complaint and noncomplaint buildings or areas were compared, complaint buildings generally had higher rates of health symptoms.

  7. The Maintenance of Heating, Ventilating and Air-Conditioning Systems and Indoor Air Quality in Schools: A Guide for School Facility Managers. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.

    To help maintain good indoor air quality (IAQ) in schools, guidance for the development and implementation of an effective program for maintenance and operation of heating, ventilating, and air-conditioning (HVAC) systems are discussed. Frequently, a building's occupants will complain about IAQ when the temperature or humidity are at uncomfortable…

  8. Ventilation during air breathing and in response to hypercapnia in 5 and 16 month-old mdx and C57 mice

    PubMed Central

    Gayraud, Jérome; Matécki, Stefan; Hnia, Karim; Mornet, Dominique; Préfaut, Christian; Mercier, Jacques; Michel, Alain; Ramonatxo, Michèle

    2007-01-01

    Previous studies have shown a blunted ventilatory response to hypercapnia in mdx mice older than 7 months. We test the hypothesis that in the mdx mice ventilatory response changes with age, concomitantly with the increased functional impairment of the respiratory muscles. We thus studied the ventilatory response to CO2 in 5 and 16 month-old mdx and C57BL10 mice (n = 8 for each group). Respiratory rate (RR), tidal volume (VT), and minute ventilation (VE) were measured, using whole-body plethysmography, during air breathing and in response to hypercapnia (3, 5 and 8% CO2). The ventilatory protocol was completed by histological analysis of the diaphragm and intercostals muscles. During air breathing, the 16 month-old mdx mice showed higher RR and, during hypercapnia (at 8% CO2 breathing), significantly lower RR (226 ± 26 vs. 270 ± 21 breaths/min) and VE (1.81 ± 0.35 vs. 3.96 ± 0.59 ml min−1 g−1)(P < 0.001) in comparison to C57BL10 controls. On the other hand, 5 month-old C57BL10 and mdx mice did not present any difference in their ventilatory response to air breathing and to hypercapnia. In conclusion, this study shows similar ventilation during air breathing and in response to hypercapnia in the 5 month-old mdx and control mice, in spite of significant pathological structural changes in the respiratory muscles of the mdx mice. However in the 16 month-old mdx mice we observed altered ventilation under air and blunted ventilation response to hypercapnia compared to age-matched control mice. Ventilatory response to hypercapnia thus changes with age in mdx mice, in line with the increased histological damage of their respiratory muscles. PMID:17431804

  9. Measuring Infiltration Rates in Homes as a Basis for Understanding Indoor Air Quality

    NASA Astrophysics Data System (ADS)

    Jerz, G. G.; Lamb, B. K.; Pressley, S. N.; O'Keeffe, P.; Fuchs, M.; Kirk, M.

    2015-12-01

    Infiltration rates, or the rate of air exchange, of houses are important to understand because ventilation can be a dominate factor in determining indoor air quality. There are chemicals that are emitted from surfaces or point sources inside the home which are harmful to humans; these chemicals come from various objects including furniture, cleaning supplies, building materials, gas stoves, and the surrounding environment. The use of proper ventilation to cycle cleaner outdoor air into the house can be crucial for maintaining healthy living conditions in the home. At the same time, there can also be outdoor pollutants which infiltrate the house and contribute to poor indoor air quality. In either case, it is important to determine infiltration rates as a function of outdoor weather conditions, the house structure properties and indoor heating and cooling systems. In this work, the objective is to measure ventilation rates using periodic releases of a tracer gas and measuring how quickly the tracer concentration decays. CO2 will be used as the tracer gas because it is inert and harmless at low levels. An Arduino timer is connected to a release valve which controls the release of 9.00 SLPM of CO2 into the uptake vent within the test home. CO2 will be released until there is at least a 200 to 300 ppm increase above ambient indoor levels. Computers with CO2 sensors and temperature/pressure sensors attached will be used to record data from different locations within the home which will continuously record data up to a week. The results from these periodic ventilation measurements will be analyzed with respect to outdoor wind and temperature conditions and house structure properties. The data will be used to evaluate an established indoor air quality model.

  10. [Disinfectants and main sanitary and preventive measures for protection of ventilation and air-conditioning systems from Legionella contamination].

    PubMed

    Gerasimov, V N; Golov, E A; Khramov, M V; Diatlov, I A

    2008-01-01

    The study was devoted to selection and assessment of disinfecting preparations for prevention of contamination by Legionella. Using system of criteria for quality assessment of disinfectants, seven newdomestic ones belonging to quaternary ammonium compounds class or to oxygen-containing preparations and designed for disinfecting of air-conditioning and ventilation systems were selected. Antibacterial and disinfecting activities of working solutions of disinfectants were tested in laboratory on the test-surfaces and test-objects of premises' air-conditioning and ventilation systems contaminated with Legionella. High antimicrobial and disinfecting activity of new preparations "Dezactiv-M", "ExtraDez", "Emital-Garant", "Aquasept Plus", "Samarovka", "Freesept", and "Ecobreeze Oxy" during their exposure on objects and materials contaminated with Legionella was shown. Main sanitary and preventive measures for defending of air-conditioning and ventilation systems from contamination by Legionella species were presented.

  11. Ventilation measurements in large office buildings

    SciTech Connect

    Persily, A.K.; Grot, R.A.

    1985-01-01

    Ventilation rates were measured in nine office buildings using an automated tracer gas measuring system. The buildings range in size from a two-story federal building with a floor area of about 20,000 ft/sup 2/ (1900 m/sup 2/) to a 26-story office building with a floor area of 700,000 ft/sup 2/ (65,000 m/sup 2/). The ventilation rates were measured for about 100 hours in each building over a range of weather conditions. The results are presented and examined for variation with time and weather. In most cases, the ventilation rate of a building is similar for hot and cold weather. In mild weather, outdoor air is used to cool the building and the ventilation rate increases. In the buildings where infiltration is a significant portion of the total ventilation rate, this total rate exhibits a dependence on weather conditions. The measured ventilation rates are discussed in relation to the outdoor air intake strategy in each building. The ventilation rates are also compared to the design rates in the buildings and ventilation rates based on the ASHRAE Standard 62-81. Some of the buildings are at times operated at lower ventilation rates than recommended in Standard 62-81.

  12. DEMAND CONTROLLED VENTILATION AND CLASSROOM VENTILATION

    SciTech Connect

    Fisk, William J.; Mendell, Mark J.; Davies, Molly; Eliseeva, Ekaterina; Faulkner, David; Hong, Tienzen; Sullivan, Douglas P.

    2014-01-06

    This document summarizes a research effort on demand controlled ventilation and classroom ventilation. The research on demand controlled ventilation included field studies and building energy modeling. Major findings included: ? The single-location carbon dioxide sensors widely used for demand controlled ventilation frequently have large errors and will fail to effectively control ventilation rates (VRs).? Multi-location carbon dioxide measurement systems with more expensive sensors connected to multi-location sampling systems may measure carbon dioxide more accurately.? Currently-available optical people counting systems work well much of the time but have large counting errors in some situations. ? In meeting rooms, measurements of carbon dioxide at return-air grilles appear to be a better choice than wall-mounted sensors.? In California, demand controlled ventilation in general office spaces is projected to save significant energy and be cost effective only if typical VRs without demand controlled ventilation are very high relative to VRs in codes. Based on the research, several recommendations were developed for demand controlled ventilation specifications in the California Title 24 Building Energy Efficiency Standards.The research on classroom ventilation collected data over two years on California elementary school classrooms to investigate associations between VRs and student illness absence (IA). Major findings included: ? Median classroom VRs in all studied climate zones were below the California guideline, and 40percent lower in portable than permanent buildings.? Overall, one additional L/s per person of VR was associated with 1.6percent less IA. ? Increasing average VRs in California K-12 classrooms from the current average to the required level is estimated to decrease IA by 3.4percent, increasing State attendance-based funding to school districts by $33M, with $6.2 M in increased energy costs. Further VR increases would provide additional benefits

  13. Direct measurement technique for determining ventilation rate in the deposit-feeding clam Macoma nasuta (bivalvia, tellinaceae)

    SciTech Connect

    Specht, D.T.; Lee, H.

    1989-01-01

    An exposure chamber, the 'clambox', was developed to measure ventilation rate, sediment processing rate, and efficiency of pollutant uptake by Macoma nasuta, Conrad, a surface-deposit-feeding clam. Clams, collected from Yaquina Bay, Oregon, USA, were cemented into a hole in a piece of rubber dental dam so that the inhalant siphons were separated by a membrane. The dental dam was then clamped between two glass chambers. The inhalant and exhalant siphons were thus diirected into separate chambers of the device so that the amount of water or feces discharged into the exhalant camber provided direct measure ventilation rate and sediment processing rate, respectively. The short-term pattern was for ventilation to be intermittently interrupted, essentially ceasing for 12 to 120 min, followed by a short period of active ventilation and then a resumption of the normal rate.

  14. HVAC (heating, ventilation, air conditioning) literature in Japan: A critical review

    SciTech Connect

    Hane, G.J.

    1988-02-01

    Japanese businessmen in the heating, ventilation, air conditioning, and refrigeration (HVACandR) industry consider the monitoring of technical and market developments in the United States to be a normal part of their business. In contrast, efforts by US businessmen to monitor Japanese HVAC and R developments are poorly developed. To begin to redress this imbalance, this report establishes the groundwork for a more effective system for use in monitoring Japanese HVAC and R literature. Discussions of a review of the principal HVAC and R publications in Japan and descriptions of the type of information contained in each of those publications are included in this report. Since the Japanese HVAC and R literature is abundant, this report also provides practical suggestions on how a researcher or research manager can limit the monitoring effort to the publications and type of information that would most likely be of greatest value.

  15. Bio-inspired, efficient, artificial lung employing air as the ventilating gas.

    PubMed

    Potkay, Joseph A; Magnetta, Michael; Vinson, Abigail; Cmolik, Brian

    2011-09-01

    Artificial lungs have recently been utilized to rehabilitate patients suffering from lung diseases. However, significant advances in gas exchange, biocompatibility, and portability are required to realize their full clinical potential. Here, we have focused on the issues of gas exchange and portability and report a small-scale, microfabricated artificial lung that uses new mathematical modeling and a bio-inspired design to achieve oxygen exchange efficiencies much larger than current devices, thereby enabling air to be utilized as the ventilating gas. This advancement eliminates the need for pure oxygen required by conventional artificial lung systems and is achieved through a device with feature sizes and structure similar to that in the natural lung. This advancement represents a significant step towards creating the first truly portable and implantable artificial lung systems for the ambulatory care of patients suffering from lung diseases.

  16. Brain Cooling With Ventilation of Cold Air Over Respiratory Tract in Newborn Piglets: An Experimental and Numerical Study

    PubMed Central

    Bakhsheshi, Mohammad Fazel; Moradi, Hadi Vafadar; Stewart, Errol E.; Keenliside, Lynn; Lee, Ting-Yim

    2015-01-01

    We investigate thermal effects of pulmonary cooling which was induced by cold air through an endotracheal tube via a ventilator on newborn piglets. A mathematical model was initially employed to compare the thermal impact of two different gas mixtures, O2-medical air (1:2) and O2-Xe (1:2), across the respiratory tract and within the brain. Following mathematical simulations, we examined the theoretical predictions with O2-medical air condition on nine anesthetized piglets which were randomized to two treatment groups: 1) control group (\\documentclass[12pt]{minimal} \\usepackage{amsmath} \\usepackage{wasysym} \\usepackage{amsfonts} \\usepackage{amssymb} \\usepackage{amsbsy} \\usepackage{upgreek} \\usepackage{mathrsfs} \\setlength{\\oddsidemargin}{-69pt} \\begin{document} }{}$n = 4$ \\end{document}) and 2) pulmonary cooling group (\\documentclass[12pt]{minimal} \\usepackage{amsmath} \\usepackage{wasysym} \\usepackage{amsfonts} \\usepackage{amssymb} \\usepackage{amsbsy} \\usepackage{upgreek} \\usepackage{mathrsfs} \\setlength{\\oddsidemargin}{-69pt} \\begin{document} }{}$n = 5$ \\end{document}). Numerical and experimental results using O2-medical air mixture show that brain temperature fell from 38.5 °C and 38.3 °C ± 0.3 °C to 35.7 °C ± 0.9 °C and 36.5 °C ± 0.6 °C during 3 h cooling which corresponded to a mean cooling rate of 0.9 °C/h ± 0.2 °C/h and 0.6 °C/h ± 0.1 °C/h, respectively. According to the numerical results, decreasing the metabolic rate and increasing air velocity are helpful to maximize the cooling effect. We demonstrated that pulmonary cooling by cooling of inhalation gases immediately before they enter the trachea can slowly reduce brain and core body temperature of newborn piglets. Numerical simulations show no significant differences between two different inhaled conditions, i.e., O2-medical air (1:2) and O2-Xe (1:2) with respect to cooling rate. PMID:27170888

  17. Derivation of cardiac output and alveolar ventilation rate based on energy expenditure measurements in healthy males and females.

    PubMed

    Brochu, Pierre; Brodeur, Jules; Krishnan, Kannan

    2012-08-01

    Physiologically based pharmacokinetic modeling and occupational exposure assessment studies often use minute ventilation rates (VE), alveolar ventilation rates (VA) and cardiac outputs (Q) that are not reflective of the physiological variations encountered during the aggregate daytime activities of individuals from childhood to adulthood. These variations of VE, VA and Q values were determined for healthy normal-weight individuals aged 5-96 years by using two types of published individual data that were measured in the same subjects (n = 902), namely indirect calorimetry measurements and the disappearance rates of oral doses of deuterium (²H) and heavy-oxygen (¹⁸O) in urine monitored by gas-isotope-ratio mass spectrometry. Arteriovenous oxygen content differences (0.051-0.082 ml of O₂ consumed ml⁻¹ of blood) and ratios of the physiological dead space to the tidal volume (0.232-0.419) were determined for oxygen consumption rates (0.157-0.806 l min⁻¹) required by minute energy expenditures ranging from 0.76 to 3.91 kcal min⁻¹. Generally higher values for the 2.5th up to the 99th percentile for VE (0.132-0.774 l kg⁻¹ min⁻¹, 4.42-21.69 l m⁻² min⁻¹), VA (0.093-0.553 l kg⁻¹ min⁻¹, 3.09-15.53 l m⁻² min⁻¹), Q (0.065-0.330 l kg⁻¹ min⁻¹, 2.17 to 9.46 l m⁻² min⁻¹) and ventilation-perfusion ratios (1.12-2.16) were found in children and teenagers aged 5-<16.5 years compared with older individuals. The distributions of cardiopulmonary parameters developed in this study should be useful in facilitating a scientifically sound characterization of the inter-individual differences in the uptake and health risks of lipophilic air pollutants, particularly as they relate to younger children.

  18. Indoor air quality, ventilation and respiratory health in elderly residents living in nursing homes in Europe.

    PubMed

    Bentayeb, Malek; Norback, Dan; Bednarek, Micha; Bernard, Alfred; Cai, Guihong; Cerrai, Sonia; Eleftheriou, Konstantinos Kostas; Gratziou, Christina; Holst, Gitte Juel; Lavaud, François; Nasilowski, Jacek; Sestini, Piersante; Sarno, Giuseppe; Sigsgaard, Torben; Wieslander, Gunilla; Zielinski, Jan; Viegi, Giovanni; Annesi-Maesano, Isabella

    2015-05-01

    Few data exist on respiratory effects of indoor air quality and comfort parameters in the elderly. In the context of the GERIE study, we investigated for the first time the relationships of these factors to respiratory morbidity among elderly people permanently living in nursing homes in seven European countries. 600 elderly people from 50 nursing homes underwent a medical examination and completed a standardised questionnaire. Air quality and comfort parameters were objectively assessed in situ in the nursing home. Mean concentrations of air pollutants did not exceed the existing standards. Forced expiratory volume in 1 s/forced vital capacity ratio was highly significantly related to elevated levels of particles with a 50% cut-off aerodynamic diameter of <0.1 µm (PM0.1) (adjusted OR 8.16, 95% CI 2.24-29.3) and nitrogen dioxide (aOR 3.74, 95% CI 1.06-13.1). Excess risks for usual breathlessness and cough were found with elevated PM10 (aOR 1.53 (95% CI 1.15-2.07) and aOR 1.73 (95% CI 1.17-10.3), respectively) and nitrogen dioxide (aOR 1.58 (95% CI 1.15-2.20) and aOR 1.56 (95% CI 1.03-2.41), respectively). Excess risks for wheeze in the past year were found with PM0.1 (aOR 2.82, 95% CI 1.15-7.02) and for chronic obstructive pulmonary disease and exhaled carbon monoxide with formaldehyde (aOR 3.49 (95% CI 1.17-10.3) and aOR 1.25 (95% CI 1.02-1.55), respectively). Breathlessness and cough were associated with higher carbon dioxide. Relative humidity was inversely related to wheeze in the past year and usual cough. Elderly subjects aged ≥80 years were at higher risk. Pollutant effects were more pronounced in the case of poor ventilation. Even at low levels, indoor air quality affected respiratory health in elderly people permanently living in nursing homes, with frailty increasing with age. The effects were modulated by ventilation. PMID:25766977

  19. Development and Evaluation of a New Air Exchange Rate Algorithm for the Stochastic Human Exposure and Dose Simulation Model

    EPA Science Inventory

    between-home and between-city variability in residential pollutant infiltration. This is likely a result of differences in home ventilation, or air exchange rates (AER). The Stochastic Human Exposure and Dose Simulation (SHEDS) model is a population exposure model that uses a pro...

  20. Review of low-energy construction, air tightness, ventilation strategies and indoor radon: results from Finnish houses and apartments.

    PubMed

    Arvela, H; Holmgren, O; Reisbacka, H; Vinha, J

    2014-12-01

    Low-energy and passive house construction practices are characterised by increased insulation, high air tightness of the building shell and controlled mechanical ventilation with heat recovery. As a result of the interaction of mechanical ventilation and high air tightness, the pressure difference in a building can be markedly enhanced. This may lead to elevated indoor radon levels. Minor leakages in the foundation can affect the radon concentration, even in the case where such leaks do not markedly reduce the total air tightness. The potential for high pressures to affect indoor radon concentrations markedly increases when the air tightness ACH50, i.e. the air change per hour induced by a pressure difference of 50 Pa, is <1.0 h(-1). Pressure differences in Finnish low-rise residential houses having mechanical supply and exhaust ventilation with heat recovery (MSEV) are typically 2-3 Pa, clearly lower than the values of 5-9 Pa in houses with only mechanical exhaust ventilation (MEV). In MSEV houses, radon concentrations are typically 30% lower than in MEV houses. In new MSEV houses with an ACH50 of 0.6 h(-1), the limit for passive construction, the analytical estimates predict an increase of 100% in the radon concentration compared with older houses with an ACH50 of 4.0 h(-1). This poses a challenge for efficient radon prevention in new construction. Radon concentrations are typically 30% lower in houses with two storeys compared with only one storey. The introduction of an MSEV ventilation strategy in typically very airtight apartments has markedly reduced pressure differences and radon concentrations.

  1. Fungal colonization of air filters for use in heating, ventilating, and air conditioning (HVAC) systems.

    PubMed

    Simmons, R B; Crow, S A

    1995-01-01

    New and used cellulosic air filters for HVAC systems including those treated with antimicrobials were suspended in vessels with a range of relative humidities (55-99%) and containing non-sterile potting soil which stimulates fungal growth. Most filters yielded fungi prior to suspension in the chambers but only two of 14 nontreated filters demonstrated fungal colonization following use in HVAC systems. Filters treated with antimicrobials, particularly a phosphated amine complex, demonstrated markedly less fungal colonization than nontreated filters. In comparison with nontreated cellulosic filters, fungal colonization of antimicrobial-treated cellulosic filters was selective and delayed.

  2. Liquid Ventilation

    PubMed Central

    Tawfic, Qutaiba A.; Kausalya, Rajini

    2011-01-01

    Mammals have lungs to breathe air and they have no gills to breath liquids. When the surface tension at the air-liquid interface of the lung increases, as in acute lung injury, scientists started to think about filling the lung with fluid instead of air to reduce the surface tension and facilitate ventilation. Liquid ventilation (LV) is a technique of mechanical ventilation in which the lungs are insufflated with an oxygenated perfluorochemical liquid rather than an oxygen-containing gas mixture. The use of perfluorochemicals, rather than nitrogen, as the inert carrier of oxygen and carbon dioxide offers a number of theoretical advantages for the treatment of acute lung injury. In addition, there are non-respiratory applications with expanding potential including pulmonary drug delivery and radiographic imaging. The potential for multiple clinical applications for liquid-assisted ventilation will be clarified and optimized in future. PMID:22043370

  3. Coal-packed methane biofilter for mitigation of green house gas emissions from coal mine ventilation air.

    PubMed

    Limbri, Hendy; Gunawan, Cindy; Thomas, Torsten; Smith, Andrew; Scott, Jason; Rosche, Bettina

    2014-01-01

    Methane emitted by coal mine ventilation air (MVA) is a significant greenhouse gas. A mitigation strategy is the oxidation of methane to carbon dioxide, which is approximately twenty-one times less effective at global warming than methane on a mass-basis. The low non-combustible methane concentrations at high MVA flow rates call for a catalytic strategy of oxidation. A laboratory-scale coal-packed biofilter was designed and partially removed methane from humidified air at flow rates between 0.2 and 2.4 L min-1 at 30°C with nutrient solution added every three days. Methane oxidation was catalysed by a complex community of naturally-occurring microorganisms, with the most abundant member being identified by 16S rRNA gene sequence as belonging to the methanotrophic genus Methylocystis. Additional inoculation with a laboratory-grown culture of Methylosinus sporium, as investigated in a parallel run, only enhanced methane consumption during the initial 12 weeks. The greatest level of methane removal of 27.2±0.66 g methane m-3 empty bed h-1 was attained for the non-inoculated system, which was equivalent to removing 19.7±2.9% methane from an inlet concentration of 1% v/v at an inlet gas flow rate of 1.6 L min-1 (2.4 min empty bed residence time). These results show that low-cost coal packing holds promising potential as a suitable growth surface and contains methanotrophic microorganisms for the catalytic oxidative removal of methane. PMID:24743729

  4. Coal-Packed Methane Biofilter for Mitigation of Green House Gas Emissions from Coal Mine Ventilation Air

    PubMed Central

    Limbri, Hendy; Gunawan, Cindy; Thomas, Torsten; Smith, Andrew; Scott, Jason; Rosche, Bettina

    2014-01-01

    Methane emitted by coal mine ventilation air (MVA) is a significant greenhouse gas. A mitigation strategy is the oxidation of methane to carbon dioxide, which is approximately twenty-one times less effective at global warming than methane on a mass-basis. The low non-combustible methane concentrations at high MVA flow rates call for a catalytic strategy of oxidation. A laboratory-scale coal-packed biofilter was designed and partially removed methane from humidified air at flow rates between 0.2 and 2.4 L min−1 at 30°C with nutrient solution added every three days. Methane oxidation was catalysed by a complex community of naturally-occurring microorganisms, with the most abundant member being identified by 16S rRNA gene sequence as belonging to the methanotrophic genus Methylocystis. Additional inoculation with a laboratory-grown culture of Methylosinus sporium, as investigated in a parallel run, only enhanced methane consumption during the initial 12 weeks. The greatest level of methane removal of 27.2±0.66 g methane m−3 empty bed h−1 was attained for the non-inoculated system, which was equivalent to removing 19.7±2.9% methane from an inlet concentration of 1% v/v at an inlet gas flow rate of 1.6 L min−1 (2.4 min empty bed residence time). These results show that low-cost coal packing holds promising potential as a suitable growth surface and contains methanotrophic microorganisms for the catalytic oxidative removal of methane. PMID:24743729

  5. Coal-packed methane biofilter for mitigation of green house gas emissions from coal mine ventilation air.

    PubMed

    Limbri, Hendy; Gunawan, Cindy; Thomas, Torsten; Smith, Andrew; Scott, Jason; Rosche, Bettina

    2014-01-01

    Methane emitted by coal mine ventilation air (MVA) is a significant greenhouse gas. A mitigation strategy is the oxidation of methane to carbon dioxide, which is approximately twenty-one times less effective at global warming than methane on a mass-basis. The low non-combustible methane concentrations at high MVA flow rates call for a catalytic strategy of oxidation. A laboratory-scale coal-packed biofilter was designed and partially removed methane from humidified air at flow rates between 0.2 and 2.4 L min-1 at 30°C with nutrient solution added every three days. Methane oxidation was catalysed by a complex community of naturally-occurring microorganisms, with the most abundant member being identified by 16S rRNA gene sequence as belonging to the methanotrophic genus Methylocystis. Additional inoculation with a laboratory-grown culture of Methylosinus sporium, as investigated in a parallel run, only enhanced methane consumption during the initial 12 weeks. The greatest level of methane removal of 27.2±0.66 g methane m-3 empty bed h-1 was attained for the non-inoculated system, which was equivalent to removing 19.7±2.9% methane from an inlet concentration of 1% v/v at an inlet gas flow rate of 1.6 L min-1 (2.4 min empty bed residence time). These results show that low-cost coal packing holds promising potential as a suitable growth surface and contains methanotrophic microorganisms for the catalytic oxidative removal of methane.

  6. Experimental and theoretical study of the oxidation of ventilation air methane over Fe2O3 and CuO.

    PubMed

    Jin, Yonggang; Sun, Chenghua; Su, Shi

    2015-07-01

    Coal mine ventilation air methane (VAM) is an important contributor to methane emissions from the energy sector. Although various technologies are under development, treatment of the VAM with an efficient and cost-effective approach has been an ongoing challenge due to massive flow rates of the ventilation air and low and variable methane concentrations. Recently a new concept based on the principle of chemical looping combustion (CLC) has been proposed for VAM abatement (Appl. Energy, 2014, 113, 1916), in which oxidation of low-concentration CH4 balanced by N2 with Fe2O3 or CuO as the oxygen carrier was studied. Here, we thoroughly examined the feasibility of CLC of VAM based on experimental study and theoretical calculations. Reduction of Fe2O3 and CuO and evolution of gas products during CH4 oxidation were investigated using TGA-MS under two reaction atmospheres: 1 vol% CH4 balanced by N2 and the simulated VAM containing 1 vol% CH4, 20 vol% O2, 0.4 vol% CO2 and balance N2. It was found that the CLC of VAM is fundamentally infeasible because the reduced phase of Fe2O3 and CuO cannot be formed for chemical looping when reacting with the simulated VAM containing abundant oxygen. Theoretical calculations revealed that Fe2O3 and CuO remain stable without the transition to the reduced phase as the generated oxygen vacancy on the surface of metal oxides during CH4 oxidation can recover quickly with O2 adsorption and dissociation. Calculations confirmed that both Fe2O3 and CuO play a role of surface catalyst in VAM oxidation. More importantly, it was found that the low-coordinated metal atoms and oxygen vacancies can stabilize CHx radicals to promote the dissociation of CH4, which is generally the rate-determining step for CH4 oxidation. Such findings are useful for new development and understanding of high-performance and low-cost metal oxide catalysts for CH4 oxidation. PMID:26028316

  7. Dynamics of ventilation, heart rate, and gas exchange: sinusoidal and impulse work loads in man.

    PubMed

    Bakker, H K; Struikenkamp, R S; De Vries, G A

    1980-02-01

    Dynamic characteristics of ventilation, heart rate, and gas exchange in response to sinusoidally varying work loads were analyzed in four male subjects, exercising in the upright position on a bicycle ergometer. Mean work-load and sinusoidal amplitude were about 1.5 and 0.9 W/kg, fat-free mass), respectively. Seven different frequencies were used, the periods ranging from 12 to 0.75 min. To further investigate the linearity of the variables under study, 10-s impulse loads were also applied to three of the four subjects. Harmonic analysis of the sine-wave data and comparison of the sine-wave fundamental responses with the impulse frequency responses showed that only O2 uptake behaves in a linear fashion. Ventilation and CO2 production showed quasi- to nonlinear behaviors, whereas the responses of heart rate and alveolar partial pressures were clearly dependent on the type of forcing used. By means of mathematical parameter identification techniques, it was found that the individual frequency responses of O2 uptake could be almost completely described by a four-parameter transfer function with parameter values showing second-order underdamped to critically damped dynamics.

  8. Review of Air Exchange Rate Models for Air Pollution Exposure Assessments

    EPA Science Inventory

    A critical aspect of air pollution exposure assessments is estimation of the air exchange rate (AER) for various buildings, where people spend their time. The AER, which is rate the exchange of indoor air with outdoor air, is an important determinant for entry of outdoor air pol...

  9. Modelica Library for Building Heating, Ventilation and Air-Conditioning Systems

    SciTech Connect

    Wetter, Michael

    2009-06-17

    This paper presents a freely available Modelica library for building heating, ventilation and air conditioning systems. The library is based on the Modelica.Fluid library. It has been developed to support research and development of integrated building energy and control systems. The primary applications are controls design, energy analysis and model-based operation. The library contains dynamic and steady-state component models that are applicable for analyzing fast transients when designing control algorithms and for conducting annual simulations when assessing energy performance. For most models, dimensional analysis is used to compute the performance for operating points that differ from nominal conditions. This allows parameterizing models in the absence of detailed geometrical information which is often impractical to obtain during the conceptual design phase of building systems. In the first part of this paper, the library architecture and the main classes are described. In the second part, an example is presented in which we implemented a model of a hydronic heating system with thermostatic radiator valves and thermal energy storage.

  10. Energy-Efficient Supermarket Heating, Ventilation, and Air Conditioning in Humid Climates in the United States

    SciTech Connect

    Clark, J.

    2015-03-01

    Supermarkets are energy-intensive buildings that consume the greatest amount of electricity per square foot of building of any building type in the United States and represent 5% of total U.S. commercial building primary energy use (EIA 2005). Refrigeration and heating, ventilation, and air-conditioning (HVAC) systems are responsible for a large proportion of supermarkets’ total energy use. These two systems sometimes work together and sometimes compete, but the performance of one system always affects the performance of the other. To better understand these challenges and opportunities, the Commercial Buildings team at the National Renewable Energy Laboratory investigated several of the most promising strategies for providing energy-efficient HVAC for supermarkets and quantified the resulting energy use and costs using detailed simulations. This research effort was conducted on behalf of the U.S. Department of Energy (DOE) Commercial Building Partnerships (CBP) (Baechler et al. 2012; Parrish et al. 2013; Antonopoulos et al. 2014; Hirsch et al. 2014). The goal of CBP was to reduce energy use in the commercial building sector by creating, testing, and validating design concepts on the pathway to net zero energy commercial buildings. Several CBP partners owned or operated buildings containing supermarkets and were interested in optimizing the energy efficiency of supermarket HVAC systems in hot-humid climates. These partners included Walmart, Target, Whole Foods Market, SUPERVALU, and the Defense Commissary Agency.

  11. Worker productivity and ventilation rate in a call center: Analyses of time-series data for a group of registered nurses

    SciTech Connect

    Fisk, William J.; Price, Phillip; Faulkner, David; Sullivan, Douglas; Dibartolomeo, Dennis

    2003-08-01

    We investigated the relationship of ventilation rates with the performance of advice nurses working in a call center. Ventilation rates were manipulated; temperatures, humidities, and CO{sub 2} concentrations were monitored; and worker performance data, with 30-minute resolution, were collected. Multivariate linear regression was used to investigate the association of worker performance with indoor minus outdoor CO{sub 2} concentration (which increases with decreasing ventilation rate per worker) and with building ventilation rate. Results suggest that the effect of ventilation rate on worker performance in this call center was very small (probably less than 1%) or nil, over most of the range of ventilation rate (roughly 12 L s{sup -1} to 48 L s{sup -1} per person). However, there is some evidence of worker performance improvements of 2% or more when the indoor CO{sub 2} concentration exceeded the outdoor concentration by less than 75 ppm.

  12. Innovative ventilation system for animal anatomy laboratory

    SciTech Connect

    Lacey, D.R.; Smith, D.C.

    1997-04-01

    A unique ventilation system was designed and built to reduce formaldehyde fumes in the large animal anatomy lab at the Vet Medical Center at Cornell University. The laboratory includes four rooms totaling 5,500 ft{sup 2}. The main room has 2,300 ft{sup 2} and houses the laboratory where up to 60 students dissect as many as 12 horses at a time. Other rooms are a cold storage locker, an animal preparation room and a smaller lab for specialized instruction. The large animal anatomy laboratory has a history of air quality complaints despite a fairly high ventilation rate of over 10 air changes/hour. The horses are embalmed, creating a voluminous source of formaldehyde and phenol vapors. Budget constraints and increasingly stringent exposure limits for formaldehyde presented a great challenge to design a ventilation system that yields acceptable air quality. The design solution included two innovative elements: air-to-air heat recovery, and focused ventilation.

  13. Energy Code Enforcement Training Manual : Covering the Washington State Energy Code and the Ventilation and Indoor Air Quality Code.

    SciTech Connect

    Washington State Energy Code Program

    1992-05-01

    This manual is designed to provide building department personnel with specific inspection and plan review skills and information on provisions of the 1991 edition of the Washington State Energy Code (WSEC). It also provides information on provisions of the new stand-alone Ventilation and Indoor Air Quality (VIAQ) Code.The intent of the WSEC is to reduce the amount of energy used by requiring energy-efficient construction. Such conservation reduces energy requirements, and, as a result, reduces the use of finite resources, such as gas or oil. Lowering energy demand helps everyone by keeping electricity costs down. (It is less expensive to use existing electrical capacity efficiently than it is to develop new and additional capacity needed to heat or cool inefficient buildings.) The new VIAQ Code (effective July, 1991) is a natural companion to the energy code. Whether energy-efficient or not, an homes have potential indoor air quality problems. Studies have shown that indoor air is often more polluted than outdoor air. The VIAQ Code provides a means of exchanging stale air for fresh, without compromising energy savings, by setting standards for a controlled ventilation system. It also offers requirements meant to prevent indoor air pollution from building products or radon.

  14. Evaluating the Accuracy of Sampling Strategies for Estimation of Compliance Rate for Ventilator-Associated Pneumonia Process Measures.

    PubMed

    Diehl, Adam; Yang, Ting; Speck, Kathleen; Battles, James; Cosgrove, Sara E; Berenholtz, Sean; Klompas, Michael

    2016-09-01

    BACKGROUND Measuring processes of care performance rates is an invaluable tool for quality improvement; however, collecting daily process measure data is time-consuming and burdensome. OBJECTIVE To evaluate the accuracy of sampling strategies to estimate monthly compliance rates with ventilator-associated pneumonia prevention measures. SETTING AND PARTICIPANTS A total of 37 intensive care units affiliated with 29 hospitals participating in a 2-state 35-month ventilator-associated pneumonia prevention collaborative. Analysis was limited to 325 unit-months with complete data entry rates. METHODS We calculated unit-month level actual and sample monthly compliance rates for 6 ventilator-associated pneumonia prevention measures, using 4 sampling strategies: sample 1 day per month, sample 1 day per week, sample 7 consecutive days per month, and sample 7 consecutive days per month plus additional consecutive days as necessary to obtain at least 30 ventilator-days for that month whenever possible. We compared sample versus actual rates using paired t test and χ2 test. RESULTS Mean sampling accuracy ranged 84%-97% for 1 day per month, 91%-98% for 1 day per week, 92%-98% for 7 consecutive days per month, and 96%-99% for 7 consecutive days with at least 30 days per month if possible. The most accurate sampling strategy was to sample 7 consecutive days with at least 30 ventilator-days per month if possible. With this strategy, sample rates were within 10% of actual rates in 88%-99% of unit-months and within 5% of actual rates in 74%-97% of unit-months. CONCLUSION Sampling process measures intermittently rather than continually can yield accurate estimates of process measure performance rates. Infect Control Hosp Epidemiol 2016;37:1037-1043.

  15. Ventilation efficiencies and thermal comfort results of a desk-edge-mounted task ventilation system

    SciTech Connect

    Faulkner, D.; Fisk, W.J.; Sullivan, D.P.; Lee, S.M.

    2003-09-01

    In chamber experiments, we investigated the ventilation effectiveness and thermal comfort of a task ventilation system with an air supply nozzle located underneath the front edge of a desk and directing air toward a heated mannequin or a human volunteer seated at the desk. The task ventilation system provided outside air, while another ventilation system provided additional space cooling but no outside air. Test variables included the vertical angle of air supply (-15{sup o} to 45{sup o} from horizontal), and the supply flow rate of (3.5 to 6.5 L s{sup -1}). Using the tracer gas step-up and step-down procedures, the measured air change effectiveness (i.e., exhaust air age divided by age of air in the breathing zone) in experiments with the mannequin ranged from 1.4 to 2.7 (median, 1.8), whereas with human subjects the air change effectiveness ranged from 1.3 to 2.3 (median, 1.6). The majority of the air change effectiveness values with the human subjects were less than values with the mannequin at comparable tests. Similarly, the tests run with supply air temperature equal to the room air temperature had lower air change effectiveness values than comparable tests with the supply air temperature lower ({approx}5 C) than the room air temperature. The air change effectiveness values are higher than typically reported for commercially available task ventilation or displacement ventilation systems. Based on surveys completed by the subjects, operation of the task ventilation system did not cause thermal discomfort.

  16. The influence of opening windows and doors on the natural ventilation rate of a residential building

    EPA Science Inventory

    Increased building energy efficiency is important in reducing national energy use and greenhouse gas emissions. An analysis of air change rates due to door and window openings in a research test house located in a residential environment are presented. These data inform developme...

  17. Reducing patients’ exposures to asthma and allergy triggers in their homes: an evaluation of effectiveness of grades of forced air ventilation filters

    PubMed Central

    Minegishi, Taeko; Allen, Joseph G.; McCarthy, John F.; Spengler, John D.; MacIntosh, David L.

    2014-01-01

    Objective Many interventions to reduce allergen levels in the home are recommended to asthma and allergy patients. One that is readily available and can be highly effective is the use of high performing filters in forced air ventilation systems. Methods We conducted a modeling analysis of the effectiveness of filter-based interventions in the home to reduce airborne asthma and allergy triggers. This work used “each pass removal efficiency” applied to health-relevant size fractions of particles to assess filter performance. We assessed effectiveness for key allergy and asthma triggers based on applicable particle sizes for cat allergen, indoor and outdoor sources of particles <2.5 µm in diameter (PM2.5), and airborne influenza and rhinovirus. Results Our analysis finds that higher performing filters can have significant impacts on indoor particle pollutant levels. Filters with removal efficiencies of >70% for cat dander particles, fine particulate matter (PM2.5) and respiratory virus can lower concentrations of those asthma triggers and allergens in indoor air of the home by >50%. Very high removal efficiency filters, such as those rated a 16 on the nationally recognized Minimum Efficiency Removal Value (MERV) rating system, tend to be only marginally more effective than MERV12 or 13 rated filters. Conclusions The results of this analysis indicate that use of a MERV12 or higher performing air filter in home ventilation systems can effectively reduce indoor levels of these common asthma and allergy triggers. These reductions in airborne allergens in turn may help reduce allergy and asthma symptoms, especially if employed in conjunction with other environmental management measures recommended for allergy and asthma patients. PMID:24555523

  18. 46 CFR 108.437 - Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 46 Shipping 4 2012-10-01 2012-10-01 false Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment. 108.437 Section 108.437 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) A-MOBILE OFFSHORE DRILLING UNITS DESIGN AND EQUIPMENT Fire Extinguishing Systems Fixed Carbon Dioxide...

  19. 46 CFR 108.437 - Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment. 108.437 Section 108.437 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) A-MOBILE OFFSHORE DRILLING UNITS DESIGN AND EQUIPMENT Fire Extinguishing Systems Fixed Carbon Dioxide...

  20. 46 CFR 108.437 - Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 46 Shipping 4 2011-10-01 2011-10-01 false Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment. 108.437 Section 108.437 Shipping COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) A-MOBILE OFFSHORE DRILLING UNITS DESIGN AND EQUIPMENT Fire Extinguishing Systems Fixed Carbon Dioxide...

  1. Comparison of ventilation threshold and heart rate deflection point in fast and standard treadmill test protocols.

    PubMed

    Vucetić, Vlatko; Sentija, Davor; Sporis, Goran; Trajković, Nebojsa; Milanović, Zoran

    2014-06-01

    The purpose of this study was to compare two methods for determination of anaerobic threshold from two different treadmill protocols. Forty-eight Croatian runners of national rank (ten sprinters, fifteen 400-m runners, ten middle distance runners and thirteen long distance runners), mean age 21.7 +/- 5.1 years, participated in the study. They performed two graded maximal exercise tests on a treadmill, a standard ramp treadmill test (T(SR), speed increments of 1 km x h(-1) every 60 seconds) and a fast ramp treadmill test (T(FR), speed increments of 1 km x h(-1) every 30 seconds) to determine and compare the parameters at peak values and at heart rate at the deflection point (HR(DP)) and ventilation threshold (VT). There were no significant differences between protocols (p > 0.05) for peak values of oxygen uptake (VO(2max), 4.48 +/- 0.43 and 4.44 +/- 0.45 L x min(-1)), weight related VO(2max) (62.5 +/- 6.2 and 62.0 +/- 6.0 mL x kg(-1) x min(-1)), pulmonary ventilation (VE(max), 163.1 +/- 18.7 and 161.3 +/- 19.9 L x min(-1)) and heart rate (HR(max), 192.3 +/- 8.5 and 194.4 +/- 8.7 bpm) (T(FR) and T(SR), respectively). Moreover, no significant differences between T(FR) and T(SR) where found for VT and HR(DP) when expressed as VO2 and HR. However, there was a significant effect of ramp slope on running speed at VO(2max) and at the anaerobic threshold (AnT), independent of the method used (VT: 16.0 +/- 2.2 vs 14.9 +/- 2.2 km x h(-1);HR(DP): 16.5 +/- 1.9 vs 14.9 +/- 2.0 km x h(-1) for T(FR) and T(SR) respectively). Linear regression analysis revealed high between-test and between-method correlations for VO2, HR and running speed parameters (r = 0.78-0.89, p < 0.01). The present study has indicated that the VT and HR(DP) for running (VO2, ventilation, and heart rate at VT/HR(DP)) are independent of test protocol, while there is a significant effect of ramp slope on VT and HR(DP) when expressed as running speed. Moreover, this study demonstrates that the point of deflection

  2. Liquid ventilation

    PubMed Central

    Sarkar, Suman; Paswan, Anil; Prakas, S.

    2014-01-01

    Human have lungs to breathe air and they have no gills to breath liquids like fish. When the surface tension at the air-liquid interface of the lung increases as in acute lung injury, scientists started to think about filling the lung with fluid instead of air to reduce the surface tension and facilitate ventilation. Liquid ventilation (LV) is a technique of mechanical ventilation in which the lungs are insufflated with an oxygenated perfluorochemical liquid rather than an oxygen-containing gas mixture. The use of perfluorochemicals, rather than nitrogen as the inert carrier of oxygen and carbon dioxide offers a number of advantages for the treatment of acute lung injury. In addition, there are non-respiratory applications with expanding potential including pulmonary drug delivery and radiographic imaging. It is well-known that respiratory diseases are one of the most common causes of morbidity and mortality in intensive care unit. During the past few years several new modalities of treatment have been introduced. One of them and probably the most fascinating, is of LV. Partial LV, on which much of the existing research has concentrated, requires partial filling of lungs with perfluorocarbons (PFC's) and ventilation with gas tidal volumes using conventional mechanical ventilators. Various physico-chemical properties of PFC's make them the ideal media. It results in a dramatic improvement in lung compliance and oxygenation and decline in mean airway pressure and oxygen requirements. No long-term side-effect reported. PMID:25886321

  3. Sensor-based demand controlled ventilation

    SciTech Connect

    De Almeida, A.T.; Fisk, W.J.

    1997-07-01

    In most buildings, occupancy and indoor pollutant emission rates vary with time. With sensor-based demand-controlled ventilation (SBDCV), the rate of ventilation (i.e., rate of outside air supply) also varies with time to compensate for the changes in pollutant generation. In other words, SBDCV involves the application of sensing, feedback and control to modulate ventilation. Compared to ventilation without feedback, SBDCV offers two potential advantages: (1) better control of indoor pollutant concentrations; and (2) lower energy use and peak energy demand. SBDCV has the potential to improve indoor air quality by increasing the rate of ventilation when indoor pollutant generation rates are high and occupants are present. SBDCV can also save energy by decreasing the rate of ventilation when indoor pollutant generation rates are low or occupants are absent. After providing background information on indoor air quality and ventilation, this report provides a relatively comprehensive discussion of SBDCV. Topics covered in the report include basic principles of SBDCV, sensor technologies, technologies for controlling air flow rates, case studies of SBDCV, application of SBDCV to laboratory buildings, and research needs. SBDCV appears to be an increasingly attractive technology option. Based on the review of literature and theoretical considerations, the application of SBDCV has the potential to be cost-effective in applications with the following characteristics: (a) a single or small number of dominant pollutants, so that ventilation sufficient to control the concentration of the dominant pollutants provides effective control of all other pollutants; (b) large buildings or rooms with unpredictable temporally variable occupancy or pollutant emission; and (c) climates with high heating or cooling loads or locations with expensive energy.

  4. VENTILATION TECHNOLOGY SYSTEMS ANALYSIS

    EPA Science Inventory

    The report gives results of a project to develop a systems analysis of ventilation technology and provide a state-of-the-art assessment of ventilation and indoor air quality (IAQ) research needs. (NOTE: Ventilation technology is defined as the hardware necessary to bring outdoor ...

  5. Air velocity distributions from a variable-rate air-assisted sprayer for tree applications

    Technology Transfer Automated Retrieval System (TEKTRAN)

    A capability that implements tree structure to control liquid and air flow rates is the preferential design in the development of variable-rate orchard and nursery sprayers. Air jet velocity distributions from an air assisted, five-port sprayer which was under the development to achieve variable-rat...

  6. Ventilation and Heart Rate Monitoring in Drivers using a Contactless Electrical Bioimpedance System

    NASA Astrophysics Data System (ADS)

    Macías, R.; García, M. A.; Ramos, J.; Bragós, R.; Fernández, M.

    2013-04-01

    Nowadays, the road safety is one of the most important priorities in the automotive industry. Many times, this safety is jeopardized because of driving under inappropriate states, e.g. drowsiness, drugs and/or alcohol. Therefore several systems for monitoring the behavior of subjects during driving are researched. In this paper, a device based on a contactless electrical bioimpedance system is shown. Using the four-wire technique, this system is capable of obtaining the heart rate and the ventilation of the driver through multiple textile electrodes. These textile electrodes are placed on the car seat and the steering wheel. Moreover, it is also reported several measurements done in a controlled environment, i.e. a test room where there are no artifacts due to the car vibrations or the road state. In the mentioned measurements, the system response can be observed depending on several parameters such as the placement of the electrodes or the number of clothing layers worn by the driver.

  7. Energy Savings Potential and Research, Development, & Demonstration Opportunities for Commercial Building Heating, Ventilation, and Air Conditioning Systems

    SciTech Connect

    none,

    2011-09-01

    This report covers an assessment of 182 different heating, ventilation, and air-conditioning (HVAC) technologies for U.S. commercial buildings to identify and provide analysis on 17 priority technology options in various stages of development. The analyses include an estimation of technical energy-savings potential, description of technical maturity, description of non-energy benefits, description of current barriers for market adoption, and description of the technology’s applicability to different building or HVAC equipment types. From these technology descriptions, are suggestions for potential research, development and demonstration (RD&D) initiatives that would support further development of the priority technology options.

  8. Energy Savings Potential and Research, Development, & Demonstration Opportunities for Residential Building Heating, Ventilation, and Air Conditioning Systems

    SciTech Connect

    Goetzler, William; Zogg, Robert; Young, Jim; Schmidt, Justin

    2012-10-01

    This report is an assessment of 135 different heating, ventilation, and air-conditioning (HVAC) technologies for U.S. residential buildings to identify and provide analysis on 19 priority technology options in various stages of development. The analyses include an estimation of technical energy-savings potential, descriptions of technical maturity, descriptions of non-energy benefits, descriptions of current barriers for market adoption, and descriptions of the technology's applicability to different building or HVAC equipment types. From these technology descriptions, are suggestions for potential research, development and demonstration (RD&D) initiatives that would support further development of the priority technology options.

  9. Odor and volatile organic compound removal from wastewater treatment plant headworks ventilation air using a biofilter.

    PubMed

    Converse, B M; Schroeder, E D; Iranpour, R; Cox, H H J; Deshusses, M A

    2003-01-01

    Laboratory-scale experiments and field studies were performed to evaluate the feasibility of biofilters for sequential removal of hydrogen sulfide and volatile organic compounds (VOCs) from wastewater treatment plant waste air. The biofilter was designed for spatially separated removal of pollutants to mitigate the effects of acid production resulting from hydrogen sulfide oxidation. The inlet section of the upflow units was designated for hydrogen sulfide removal and the second section was designated for VOC removal. Complete removal of hydrogen sulfide (H2S) and methyl tert-butyl ether (MTBE) was accomplished at loading rates of 8.3 g H2S/(m3 x h) (15-second empty bed retention time [EBRT]) and 33 g MTBE/(m3 x h) (60-second EBRT), respectively. In field studies performed at the Hyperion Treatment Plant in Los Angeles, California, excellent removal of hydrogen sulfide, moderate removal of nonchlorinated VOCs such as toluene and benzene, and poor removal of chlorinated VOCs were observed in treating the headworks waste air. During spiking experiments on the headworks waste air, the percentage removals were similar to the unspiked removals when nonchlorinated VOCs were spiked; however, feeding high concentrations of chlorinated VOCs reduced the removal percentages for all VOCs. Thus, biofilters offer a distinct advantage over chemical scrubbers currently used at publicly owned treatment works in that they not only remove odor and hydrogen sulfide efficiently at low cost, but also reduce overall toxicity by partially removing VOCs and avoiding the use of hazardous chemicals.

  10. Continuous distributions of ventilation-perfusion ratios in normal subjects breathing air and 100 per cent O2.

    PubMed

    Wagner, P D; Laravuso, R B; Uhl, R R; West, J B

    1974-07-01

    A new method has been developed for measuring virtually continuous distributions of ventilation-perfusion ratios (V(A)/Q) based on the steadystate elimination of six gases of different solubilities. The method is applied here to 12 normal subjects, aged 21-60. In nine, the distributions were compared breathing air and 100% oxygen, while in the remaining three, effects of changes in posture were examined. In four young semirecumbent subjects (ages 21-24) the distributions of blood flow and ventilation with respect to V(A)/Q were virtually log-normal with little dispersion (mean log standard deviations 0.43 and 0.35, respectively). The 95.5% range of both blood flow and ventilation was from V(A)/Q ratios of 0.3-2.1, and there was no intrapulmonary shunt (V(A)/Q of 0). On breathing oxygen, a shunt developed in three of these subjects, the mean value being 0.5% of the cardiac output. The five older subjects (ages 39-60) had broader distributions (mean log standard deviations, 0.76 and 0.44) containing areas with V(A)/Q ratios in the range 0.01-0.1 in three subjects. As for the young subjects, there was no shunt breathing air, but all five developed a shunt breathing oxygen (mean value 3.2%), and in one the value was 10.7%. Postural changes were generally those expected from the known effects of gravity, with more ventilation to high V(A)/Q areas when the subjects were erect than supine. Measurements of the shunt while breathing oxygen, the Bohr CO(2) dead space, and the alveolar-arterial oxygen difference were all consistent with the observed distributions. Since the method involves only a short infusion of dissolved inert gases, sampling of arterial blood and expired gas, and measurement of cardiac output and minute ventilation, we conclude that it is well suited to the investigation of pulmonary gas exchange in man.

  11. Ammonia emissions from two mechanically ventilated UK livestock buildings

    NASA Astrophysics Data System (ADS)

    Demmers, T. G. M.; Burgess, L. R.; Short, J. L.; Phillips, V. R.; Clark, J. A.; Wathes, C. M.

    Ammonia emission rates from livestock buildings are required to construct an accurate emission inventory for the UK. Ventilation and ammonia emission rates from a fattening pig unit and a broiler house, both mechanically ventilated, were estimated using fan wheel anemometers and thermal converters with a chemiluminescence NO x-analyser to measure the ventilation rate and the ammonia concentration, respectively. The estimated ammonia emission factors were 46.9 and 16.6 kg lu -1 a -1 for the fattening pig unit and the broiler house, respectively. Both emission factors were within the range reported in the literature. A tracer gas (CO) method, based on a constant tracer release rate, was validated for measuring ventilation rates from naturally ventilated livestock buildings. Air inlets and outlets were identified using the air temperature or tracer concentration in the opening. Tracer concentration was found to be a more suitable criterion than temperature. In both houses, a significant correlation between the estimated ventilation rate using the tracer method and the measured ventilation rate using fan wheel anemometers was found. The ventilation rate was underestimated by 12 and 6% for the piggery and broiler house, respectively. The instantaneous ammonia emission derived from the tracer gas method was lower than the ammonia emission derived from the fan wheel anemometer method by 14 and 16% for the piggery and broiler house, respectively. The ventilation and ammonia emission estimates using the tracer method were within acceptable range from the ventilation and emission rates measured using measuring fans, but because of its accuracy and simplicity the fan wheel anemometer method is preferred for long-term measurements of ventilation rate in mechanically ventilated buildings.

  12. Potential model for single-sided naturally ventilated buildings in China

    SciTech Connect

    Wei, Yin; Guo-qiang, Zhang; Jing, Liu; San-xian, Xia; Xiao, Wang

    2010-09-15

    The paper investigates a single-sided naturally ventilated buildings potential model considering number of factors in China. This model can be used to estimate potential of natural ventilation via local climate data and building parameters. The main goal of the model is to predict natural ventilation hours and hourly ventilation flow rate. In fluid model, formula of single-sided natural ventilation by coupling wind pressure and temperature difference was used to calculate air flow rate. Accordingly, the paper analyzed four typical cities in different climate region in China and calculated pressure difference Pascal hours (PDPH). The results show that single-sided ventilation has fewer adaptive comfort hours than two-sided ventilation and much less ventilation volume. This model provided quantitative information for early stage architectural natural ventilation design and building energy efficiency evaluation. (author)

  13. Use of Recirculating Ventilation With Dust Filtration to Improve Wintertime Air Quality in a Swine Farrowing Room.

    PubMed

    Anthony, T Renée; Altmaier, Ralph; Jones, Samuel; Gassman, Rich; Park, Jae Hong; Peters, Thomas M

    2015-01-01

    The performance of a recirculating ventilation system with dust filtration was evaluated to determine its effectiveness to improve the air quality in a swine farrowing room of a concentrated animal feeding operation (CAFO). Air was exhausted from the room (0.47 m(3) sec(-1); 1000 cfm), treated with a filtration unit (Shaker-Dust Collector), and returned to the farrowing room to reduce dust concentrations while retaining heat necessary for livestock health. The air quality in the room was assessed over a winter, during which time limited fresh air is traditionally brought into the building. Over the study period, dust concentrations ranged from 0.005-0.31 mg m(-3) (respirable) and 0.17-2.09 mg m(-3) (inhalable). In-room dust concentrations were reduced (41% for respirable and 33% for inhalable) with the system in operation, while gas concentrations (ammonia [NH3], hydrogen sulfide [H2S], carbon monoxide [CO], carbon dioxide [CO2]) were unchanged. The position of the exhaust and return air systems provided reasonably uniform contaminant distributions, although the respirable dust concentrations nearest one of the exhaust ducts was statistically higher than other locations in the room, with differences averaging only 0.05 mg m(-3). Throughout the study, CO2 concentrations consistently exceeded 1540 ppm (industry recommendations) and on eight of the 18 study days it exceeded 2500 ppm (50% of the ACGIH TLV), with significantly higher concentrations near a door to a temperature-controlled hallway that was typically often left open. Alternative heaters are recommended to reduce CO2 concentrations in the room. Contaminant concentrations were modeled using production and environmental factors, with NH3 related to the number of sow in the room and outdoor temperatures and CO2 related to the number of piglets and outdoor temperatures. The recirculating ventilation system provided dust reduction without increasing concentrations of hazardous gases.

  14. Use of Recirculating Ventilation With Dust Filtration to Improve Wintertime Air Quality in a Swine Farrowing Room.

    PubMed

    Anthony, T Renée; Altmaier, Ralph; Jones, Samuel; Gassman, Rich; Park, Jae Hong; Peters, Thomas M

    2015-01-01

    The performance of a recirculating ventilation system with dust filtration was evaluated to determine its effectiveness to improve the air quality in a swine farrowing room of a concentrated animal feeding operation (CAFO). Air was exhausted from the room (0.47 m(3) sec(-1); 1000 cfm), treated with a filtration unit (Shaker-Dust Collector), and returned to the farrowing room to reduce dust concentrations while retaining heat necessary for livestock health. The air quality in the room was assessed over a winter, during which time limited fresh air is traditionally brought into the building. Over the study period, dust concentrations ranged from 0.005-0.31 mg m(-3) (respirable) and 0.17-2.09 mg m(-3) (inhalable). In-room dust concentrations were reduced (41% for respirable and 33% for inhalable) with the system in operation, while gas concentrations (ammonia [NH3], hydrogen sulfide [H2S], carbon monoxide [CO], carbon dioxide [CO2]) were unchanged. The position of the exhaust and return air systems provided reasonably uniform contaminant distributions, although the respirable dust concentrations nearest one of the exhaust ducts was statistically higher than other locations in the room, with differences averaging only 0.05 mg m(-3). Throughout the study, CO2 concentrations consistently exceeded 1540 ppm (industry recommendations) and on eight of the 18 study days it exceeded 2500 ppm (50% of the ACGIH TLV), with significantly higher concentrations near a door to a temperature-controlled hallway that was typically often left open. Alternative heaters are recommended to reduce CO2 concentrations in the room. Contaminant concentrations were modeled using production and environmental factors, with NH3 related to the number of sow in the room and outdoor temperatures and CO2 related to the number of piglets and outdoor temperatures. The recirculating ventilation system provided dust reduction without increasing concentrations of hazardous gases. PMID:25950713

  15. Use of Recirculating Ventilation with Dust Filtration to Improve Wintertime Air Quality in a Swine Farrowing Room

    PubMed Central

    Anthony, T. Renée; Altmaier, Ralph; Jones, Samuel; Gassman, Rich; Park, Jae Hong; Peters, Thomas M.

    2016-01-01

    The performance of a recirculating ventilation system with dust filtration was evaluated to determine its effectiveness to improve the air quality in a swine farrowing room of a concentrated animal feeding operation (CAFO). Air was exhausted from the room (0.47 m3sec−1; 1000 cfm), treated with a filtration unit (Shaker-Dust Collector), and returned to the farrowing room to reduce dust concentrations while retaining heat necessary for livestock health. The air quality in the room was assessed over a winter, during which time limited fresh air is traditionally brought into the building. Over the study period, dust concentrations ranged from 0.005 to 0.31 mg m−3 (respirable) and 0.17 to 2.09 mg m−3 (inhalable). In-room dust concentrations were reduced (41% for respirable and 33% for inhalable) with the system in operation, while gas concentrations (ammonia [NH3], hydrogen sulfide [H2S], carbon monoxide [CO], carbon dioxide [CO2]) were unchanged. The position of the exhaust and return air systems provided reasonably uniform contaminant distributions, although the respirable dust concentrations nearest one of the exhaust ducts was statistically higher than other locations in the room, with differences averaging only 0.05 mg m−3. Throughout the study, CO2 concentrations consistently exceeded 1540 ppm (industry recommendations) and on eight of the 18 study days it exceeded 2500 ppm (50% of the ACGIH TLV), with significantly higher concentrations near a door to a temperature-controlled hallway that was typically often left open. Alternative heaters are recommended to reduce CO2 concentrations in the room. Contaminant concentrations were modeled using production and environmental factors, with NH3 related to the number of sow in the room and outdoor temperatures and CO2 related to the number of piglets and outdoor temperatures. The recirculating ventilation system provided dust reduction without increasing concentrations of hazardous gases. PMID:25950713

  16. A direct method of measuring gaseous emissions from naturally ventilated dairy barns

    NASA Astrophysics Data System (ADS)

    Joo, H. S.; Ndegwa, P. M.; Heber, A. J.; Bogan, B. W.; Ni, J.-Q.; Cortus, E. L.; Ramirez-Dorronsoro, J. C.

    2014-04-01

    Air pollutant emission rates from mechanically ventilated (MV) dairy barns are determined from the product of the differences in concentrations of pollutants in air at the inlet and exhaust points and the corresponding ventilation rates. In contrast to well defined entry and exit points in MV barns, large area air inlets or outlets characterize naturally ventilated (NV) freestall dairy barns. Complicating this scenario even more, pertinent airflow characteristics (velocity and direction) necessary for determining ventilation rates vary continuously, both temporally and spatially. This paper describes implementation of a direct method, generally equivalent to the approach used for MV barns, for determining air emission rates of NV barns. Ultrasonic anemometers (sonics) located at salient points in the barn openings mapped air inflow and outflow velocities necessary to calculate ventilation rates. Pollutant concentrations in the air entering or leaving the barn during a given period were measured at sampling points located next to the anemometers. The air inflow rates were, in general, higher than the air outflow rates from the barns, but diurnal profiles were similar. The observed ventilation characteristics were consistent with prevailing wind directions. Air inflows were observed predominantly at windward openings of the barn, while the outflows were mainly at the barn's leeward openings. Results indicated that either: (i) the average of the air inflow and outflow rates (averaging approach), or (ii) the air inflow rates (inflow-only approach) were credible representations of ventilation rates. Results also revealed use of an on-site weather station and one sonic mounted in the middle of each wall of the barn as a possible approach for determining barn ventilation rates. The suggested use of ventilation rates for interpolating missing concentrations from intermittent gas measurements could potentially increase the integrity of emission rates at significantly lower

  17. Ventilation Model

    SciTech Connect

    V. Chipman

    2002-10-05

    The purpose of the Ventilation Model is to simulate the heat transfer processes in and around waste emplacement drifts during periods of forced ventilation. The model evaluates the effects of emplacement drift ventilation on the thermal conditions in the emplacement drifts and surrounding rock mass, and calculates the heat removal by ventilation as a measure of the viability of ventilation to delay the onset of peak repository temperature and reduce its magnitude. The heat removal by ventilation is temporally and spatially dependent, and is expressed as the fraction of heat carried away by the ventilation air compared to the fraction of heat produced by radionuclide decay. One minus the heat removal is called the wall heat fraction, or the remaining amount of heat that is transferred via conduction to the surrounding rock mass. Downstream models, such as the ''Multiscale Thermohydrologic Model'' (BSC 2001), use the wall heat fractions as outputted from the Ventilation Model to initialize their post-closure analyses. The Ventilation Model report was initially developed to analyze the effects of preclosure continuous ventilation in the Engineered Barrier System (EBS) emplacement drifts, and to provide heat removal data to support EBS design. Revision 00 of the Ventilation Model included documentation of the modeling results from the ANSYS-based heat transfer model. The purposes of Revision 01 of the Ventilation Model are: (1) To validate the conceptual model for preclosure ventilation of emplacement drifts and verify its numerical application in accordance with new procedural requirements as outlined in AP-SIII-10Q, Models (Section 7.0). (2) To satisfy technical issues posed in KTI agreement RDTME 3.14 (Reamer and Williams 2001a). Specifically to demonstrate, with respect to the ANSYS ventilation model, the adequacy of the discretization (Section 6.2.3.1), and the downstream applicability of the model results (i.e. wall heat fractions) to initialize post

  18. Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System.

    PubMed

    Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P; Sax, Hugo

    2016-06-01

    Heater-cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices.

  19. Transmission of Mycobacterium chimaera from Heater–Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System

    PubMed Central

    Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P.

    2016-01-01

    Heater–cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices. PMID:27070958

  20. Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System.

    PubMed

    Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P; Sax, Hugo

    2016-06-01

    Heater-cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices. PMID:27070958

  1. Household Ventilation May Reduce Effects of Indoor Air Pollutants for Prevention of Lung Cancer: A Case-Control Study in a Chinese Population

    PubMed Central

    Han, Ren-Qiang; Zhang, Xiao-Feng; Wang, Xu-Shan; Liu, Ai-Ming; Zhou, Jin-Yi; Lu, Qing-Yi; Kim, Claire H.; Mu, Lina; Zhang, Zuo-Feng; Zhao, Jin-Kou

    2014-01-01

    Background Although the International Agency for Research on Cancer (IARC) has classified various indoor air pollutants as carcinogenic to humans, few studies evaluated the role of household ventilation in reducing the impact of indoor air pollutants on lung cancer risk. Objectives To explore the association between household ventilation and lung cancer. Methods A population-based case-control study was conducted in a Chinese population from 2003 to 2010. Epidemiologic and household ventilation data were collected using a standardized questionnaire. Unconditional logistic regression was employed to estimate adjusted odds ratios (ORadj) and their 95% confidence intervals (CI). Results Among 1,424 lung cancer cases and 4,543 healthy controls, inverse associations were observed for good ventilation in the kitchen (ORadj = 0.86, 95% CI: 0.75, 0.98), bedroom (ORadj = 0.90, 95% CI: 0.79, 1.03), and both kitchen and bedroom (ORadj = 0.87, 95% CI: 0.75, 1.00). Stratified analyses showed lung cancer inversely associated with good ventilation among active smokers (ORadj = 0.85, 95% CI: 0.72, 1.00), secondhand smokers at home (ORadj = 0.77, 95% CI: 0.63, 0.94), and those exposed to high-temperature cooking oil fumes (ORadj = 0.82, 95% CI: 0.68, 0.99). Additive interactions were found between household ventilation and secondhand smoke at home as well as number of household pollutant sources. Conclusions A protective association was observed between good ventilation of households and lung cancer, most likely through the reduction of exposure to indoor air pollutants, indicating ventilation may serve as one of the preventive measures for lung cancer, in addition to tobacco cessation. PMID:25019554

  2. Energy and cost associated with ventilating office buildings in a tropical climate.

    PubMed

    Rim, Donghyun; Schiavon, Stefano; Nazaroff, William W

    2015-01-01

    Providing sufficient amounts of outdoor air to occupants is a critical building function for supporting occupant health, well-being and productivity. In tropical climates, high ventilation rates require substantial amounts of energy to cool and dehumidify supply air. This study evaluates the energy consumption and associated cost for thermally conditioning outdoor air provided for building ventilation in tropical climates, considering Singapore as an example locale. We investigated the influence on energy consumption and cost of the following factors: outdoor air temperature and humidity, ventilation rate (L/s per person), indoor air temperature and humidity, air conditioning system coefficient of performance (COP), and cost of electricity. Results show that dehumidification of outdoor air accounts for more than 80% of the energy needed for building ventilation in Singapore's tropical climate. Improved system performance and/or a small increase in the indoor temperature set point would permit relatively large ventilation rates (such as 25 L/s per person) at modest or no cost increment. Overall, even in a thermally demanding tropical climate, the energy cost associated with increasing ventilation rate up to 25 L/s per person is less than 1% of the wages of an office worker in an advanced economy like Singapore's. This result implies that the benefits of increasing outdoor air ventilation rate up to 25 L/s per person--which is suggested to provide for productivity increases, lower sick building syndrome symptom prevalence, and reduced sick leave--can be much larger than the incremental cost of ventilation.

  3. Characteristics of rain penetration through a gravity ventilator used for natural ventilation.

    PubMed

    Kim, Taehyeung; Lee, Dong Ho; Ahn, Kwangseog; Ha, Hyunchul; Park, Heechang; Piao, Cheng Xu; Li, Xiaoyu; Seo, Jeoungyoon

    2008-01-01

    Gravity ventilators rely simply on air buoyancy to extract air and are widely used to exhaust air contaminants and heat from workplaces using minimal energy. They are designed to maximize the exhaust flow rate, but the rain penetration sometimes causes malfunctioning. In this study, the characteristics of rain penetration through a ventilator were examined as a preliminary study to develop a ventilator with the maximum exhaust capacity while minimizing rain penetration. A model ventilator was built and exposed to artificial rain and wind. The paths, intensities and amounts of penetration through the ventilator were observed and measured in qualitative and quantitative fashions. In the first phase, the pathways and intensities of rain penetration were visually observed. In the second phase, the amounts of rain penetration were quantitatively measured under the different configurations of ventilator components that were installed based on the information obtained in the first-phase experiment. The effects of wind speed, grill direction, rain drainage width, outer wall height, neck height and leaning angle of the outer wall from the vertical position were analyzed. Wind speed significantly affected rain penetration. Under the low crosswind conditions, the rain penetration intensities were under the limit of detection. Under the high crosswind conditions, grill direction and neck height were the most significant factors in reducing rain penetration. The installation of rain drainage was also important in reducing rain penetration. The experimental results suggest that, with proper configurations of its components, a gravity ventilator can be used for natural ventilation without significant rain penetration problems.

  4. ASME N511-19XX, Standard for periodic in-service testing of nuclear air treatment, heating, ventilating and air conditioning systems

    SciTech Connect

    1997-08-01

    A draft version of the Standard is presented in this document. The Standard covers the requirements for periodic in-service testing of nuclear safety-related air treatment, heating, ventilating, and air conditioning systems in nuclear facilities. The Standard provides a basis for the development of test programs and does not include acceptance criteria, except in cases where the results of one test influence the performance of other tests. The Standard covers general inspection and test requirements, reference values, inspection and test requirements, generic tests, acceptance criteria, in-service test requirements, testing following an abnormal incident, corrective action requirements, and quality assurance. Mandatory appendices provide a visual inspection checklist and four test procedures. Non-mandatory appendices provide additional information and guidance on mounting frame pressure leak test procedure, corrective action, challenge gas substitute selection criteria, and test program development. 8 refs., 10 tabs.

  5. A comparison of ventilator-associated pneumonia rates determined by different scoring systems in four intensive care units in the North West of England.

    PubMed

    Wallace, F A; Alexander, P D G; Spencer, C; Naisbitt, J; Moore, J A; McGrath, B A

    2015-11-01

    Ventilator-associated pneumonia is a common healthcare-associated infection with significant mortality, morbidity and healthcare cost, and rates have been proposed as a potential quality indicator. We examined ventilator-associated pneumonia rates as determined by different diagnostic scoring systems across four adult intensive care units in the North West of England. We also collected clinical opinions as to whether patients had ventilator-associated pneumonia, and whether patients were receiving antibiotics as treatment. Pooled ventilator-associated pneumonia rates were 36.3, 22.2, 15.2 and 1.1 per 1000 ventilator-bed days depending on the scoring system used. There was significant within-unit heterogeneity for ventilator-associated pneumonia rates calculated by the various scoring systems (all p < 0.001). Clinical opinion and antibiotic use did not correlate well with the scoring systems (k = 0.23 and k = 0.17, respectively). We therefore question whether the ventilator-associated pneumonia rate as measured by existing tools is either useful or desirable as a quality indicator.

  6. VENTILATION MODEL REPORT

    SciTech Connect

    V. Chipman

    2002-10-31

    The purpose of the Ventilation Model is to simulate the heat transfer processes in and around waste emplacement drifts during periods of forced ventilation. The model evaluates the effects of emplacement drift ventilation on the thermal conditions in the emplacement drifts and surrounding rock mass, and calculates the heat removal by ventilation as a measure of the viability of ventilation to delay the onset of peak repository temperature and reduce its magnitude. The heat removal by ventilation is temporally and spatially dependent, and is expressed as the fraction of heat carried away by the ventilation air compared to the fraction of heat produced by radionuclide decay. One minus the heat removal is called the wall heat fraction, or the remaining amount of heat that is transferred via conduction to the surrounding rock mass. Downstream models, such as the ''Multiscale Thermohydrologic Model'' (BSC 2001), use the wall heat fractions as outputted from the Ventilation Model to initialize their postclosure analyses.

  7. Performance of passively automatic ventilation inlets for agricultural buildings

    SciTech Connect

    Kaiser, K.J.; Hosni, M.H.; Heber, A.J.

    1995-08-01

    Good air distribution is needed in livestock buildings to remove moisture and pollutants without chilling animals during cold weather and to assist in evaporative and convective cooling during warm weather. Passively automatic inlets are intended to provide nearly constant air velocity into buildings as ventilation airflow rates are automatically adjusted. The airflow rate, average exit air velocity, and velocity profile of eight commercially available ceiling and wall ventilation inlets were tested under various configurations and static pressures. Only one inlet supplied the airflow rate claimed by the manufacturer, and only one wall inlet developed a nearly constant exit air velocity.

  8. Experiments probing the influence of air exchange rates on secondary organic aerosols derived from indoor chemistry

    NASA Astrophysics Data System (ADS)

    Weschler, Charles J.; Shields, Helen C.

    Reactions between ozone and terpenes have been shown to increase the concentrations of submicron particles in indoor settings. The present study was designed to examine the influence of air exchange rates on the concentrations of these secondary organic aerosols as well as on the evolution of their particle size distributions. The experiments were performed in a manipulated office setting containing a constant source of d-limonene and an ozone generator that was remotely turned "on" or "off" at 6 h intervals. The particle number concentrations were monitored using an optical particle counter with eight-channels ranging from 0.1-0.2 to>2.0 μm diameter. The air exchange rates during the experiments were either high (working hours) or low (non-working hours) and ranged from 1.6 to>12 h -1, with intermediate exchange rates. Given the emission rates of ozone and d-limonene used in these studies, at an air exchange rate of 1.6 h -1 particle number concentration in the 0.1-0.2 μm size-range peaked 1.2 h after the ozone generator was switched on. In the ensuing 4.8 h particle counts increased in successive size-ranges up to the 0.5-0.7 μm diameter range. At higher air exchange rates, the resulting concentrations of total particles and particle mass (calculated from particle counts) were smaller, and at exchange rates exceeding 12 h -1, no excess particle formation was detectable with the instrument used in this study. Particle size evolved through accretion and, in some cases, coagulation. There was evidence for coagulation among particles in the smallest size-range at low air exchange rates (high particle concentrations) but no evidence of coagulation was apparent at higher air exchange rates (lower particle concentrations). At higher air exchange rates the particle count or size distributions were shifted towards smaller particle diameters and less time was required to achieve the maximum concentration in each of the size-ranges where discernable particle growth

  9. Impact of surface disinfection and sterile draping of furniture on room air quality in a cardiac procedure room with a ventilation and air-conditioning system (extrusion airflow, cleanroom class 1b (DIN 1946-4)).

    PubMed

    Below, Harald; Ryll, Sylvia; Empen, Klaus; Dornquast, Tina; Felix, Stefan; Rosenau, Heike; Kramer, Sebastian; Kramer, Axel

    2010-09-21

    In a cardiac procedure room, ventilated by a ventilation and air-conditioning system with turbulent mixed airflow, a protection zone in the operating area could be defined through visualization of airflows. Within this protection zone, no turbulence was detectable in the room air.Under the given conditions, disinfection of all surfaces including all furniture and equipment after the last operation and subsequent draping of furniture and all equipment that could not be removed from the room with sterile surgical drapes improved the indoor room air quality from cleanroom class C to cleanroom class B. This also allows procedures with elevated requirements to be performed in room class 1b.

  10. Safety management of nuclear medicine personnel with visualisation of air dose rate.

    PubMed

    Kawase, S; Ohno, K; Nakamoto, Y; Miyatake, H

    2015-07-01

    Many people are anxious about radiation exposure for the reason that radiation cannot be seen. With the aim of devising a way for medical personnel to perform their medical duties without worry about radiation exposure, we attempted safety management using a system that displays the air dose of radiation in real time. Measurements were made in a lung ventilation scintigraphy examination room with the use of Xe-133. An SCI-type RI detector from Hamamatsu Photonics, which displays the air dose rate in real time, was used for the measurements. These radiation measurements were continued from the start to finish of the examination. The measurements were made in two locations, on the patient inhalation tube side and on the opposite side. Measurements were made on the patient tube side in 24 tests and on the opposite side in 12 tests. The maximum air dose rate was 3.7 ± 2.1 μSv/h on the patient tube side and 1.1 ± 0.5 μSv/h on the opposite side. Thus, the level on the opposite side was about 1/5 that of the tube side. To accurately perform lung ventilation scintigraphy, a medical worker needs to observe the patient's breathing status up close. Because of this, some medical workers are worried about radiation exposure during tests. The simplest way to reduce exposure would be to maintain a distance from the examination tube that is the source of radiation. The measurements in this study were made to encourage medical workers' recognition of this fact. Displaying specific numbers not only serves as basic data for managing staff operations, but is also thought to reassure workers through visualization.

  11. Ventilation and ventilators.

    PubMed

    Hayes, B

    1982-01-01

    The history of ventilation is reviewed briefly and recent developments in techniques of ventilation are discussed. Operating features of ventilators have changed in the past few years, partly as the result of clinical progress; yet, technology appears to have outstripped the clinician's ability to harness it most effectively. Clinical discipline and training of medical staff in the use of ventilators could be improved. The future is promising if clinician and designer can work together closely. Ergonomics of ventilators and their controls and the provision of alarms need special attention. Microprocessors are likely to feature prominently in the next generation of designs.

  12. Ventilation and ventilators.

    PubMed

    Hayes, B

    1982-01-01

    The history of ventilation is reviewed briefly and recent developments in techniques of ventilation are discussed. Operating features of ventilators have changed in the past few years, partly as the result of clinical progress; yet, technology appears to have outstripped the clinician's ability to harness it most effectively. Clinical discipline and training of medical staff in the use of ventilators could be improved. The future is promising if clinician and designer can work together closely. Ergonomics of ventilators and their controls and the provision of alarms need special attention. Microprocessors are likely to feature prominently in the next generation of designs. PMID:6754938

  13. Extreme variations of air dose rates in east Fukushima.

    PubMed

    Akimoto, Kazuhiro

    2015-11-01

    This report analyses the data of air (ambient) dose rates measured at 164 points in eastern Fukushima during a period of half a year after 10 June 2011. It is found that at some locations the values decreased or increased extraordinarily although on average the overall dose rates decreased significantly faster than the theoretically predicted rate. Among them the nine most extreme points are selected and analysed. It is found that behind these extraordinary behaviours of air dose rates there exists the combination of wind/rain and artificial structures such as sloped pavements.

  14. Optimization of Occupancy Based Demand Controlled Ventilation in Residences

    SciTech Connect

    Mortensen, Dorthe K.; Walker, Iain S.; Sherman, Max H.

    2011-05-01

    Although it has been used for many years in commercial buildings, the application of demand controlled ventilation in residences is limited. In this study we used occupant exposure to pollutants integrated over time (referred to as 'dose') as the metric to evaluate the effectiveness and air quality implications of demand controlled ventilation in residences. We looked at air quality for two situations. The first is that typically used in ventilation standards: the exposure over a long term. The second is to look at peak exposures that are associated with time variations in ventilation rates and pollutant generation. The pollutant generation had two components: a background rate associated with the building materials and furnishings and a second component related to occupants. The demand controlled ventilation system operated at a low airflow rate when the residence was unoccupied and at a high airflow rate when occupied. We used analytical solutions to the continuity equation to determine the ventilation effectiveness and the long-term chronic dose and peak acute exposure for a representative range of occupancy periods, pollutant generation rates and airflow rates. The results of the study showed that we can optimize the demand controlled airflow rates to reduce the quantity of air used for ventilation without introducing problematic acute conditions.

  15. Sulfide toxicity: Mechanical ventilation and hypotension determine survival rate and brain necrosis

    SciTech Connect

    Baldelli, R.J.; Green, F.H.Y.; Auer, R.N. )

    1993-09-01

    Occupational exposure to hydrogen sulfide is one of the leading causes of sudden death in the workplace, especially in the oil and gas industry. High-dose exposure causes immediate neurogenic apnea and death; lower doses cause [open quotes]knockdown[close quotes] (transient loss of consciousness, with apnea). Because permanent neurological sequelae have been reported, the authors sought to determine whether sulfide can directly kill central nervous system neurons. Ventilated and unventilated rats were studied to allow administration of higher doses of sulfide and to facilitate physiological monitoring. It was extremely difficult to produce cerebral necrosis with sulfide. Only one of eight surviving unventilated rats given high-dose sulfide (a dose that was lethal in [ge]50% of animals) showed cerebral necrosis. Mechanical ventilation shifted the dose that was lethal in 50% of the animals to 190 mg/kg from 94 mg/kg in the unventilated rats. Sulfide was found to potently depress blood pressure. Cerebral necrosis was absent in the ventilated rats (n = 11), except in one rat that showed profound and sustained hypotension to [le]35 Torr. Electroencephalogram activity ceased during exposure but recovered when the animals regained consciousness. The authors conclude that very-high-dose sulfide is incapable of producing cerebral necrosis by a direct histotoxic effect. 32 refs., 5 figs.

  16. Central Fan Integrated Ventilation Systems

    SciTech Connect

    2009-05-12

    This information sheet describes one example of a ventilation system design, a central fan integrated supply (CFIS) system, a mechanical ventilation and pollutant source control to ensure that there is reasonable indoor air quality inside the house.

  17. Semi-volatile organic compounds in heating, ventilation, and air-conditioning filter dust in retail stores.

    PubMed

    Xu, Y; Liang, Y; Urquidi, J R; Siegel, J A

    2015-02-01

    Retail stores contain a wide range of products that can emit a variety of indoor pollutants. Among these chemicals, phthalate esters and polybrominated diphenyl ethers (PBDEs) are two important categories of semi-volatile organic compounds (SVOCs). Filters in heating, ventilation, and air-conditioning (HVAC) system collect particles from large volumes of air and thus potentially provide spatially and temporally integrated SVOC concentrations. This study measured six phthalate and 14 PBDE compounds in HVAC filter dust in 14 retail stores in Texas and Pennsylvania, United States. Phthalates and PBDEs were widely found in the HVAC filter dust in retail environment, indicating that they are ubiquitous indoor pollutants. The potential co-occurrence of phthalates and PBDEs was not strong, suggesting that their indoor sources are diverse. The levels of phthalates and PBDEs measured in HVAC filter dust are comparable to concentrations found in previous investigations of settled dust in residential buildings. Significant correlations between indoor air and filter dust concentrations were found for diethyl phthalate, di-n-butyl phthalate, and benzyl butyl phthalate. Reasonable agreement between measurements and an equilibrium model to describe SVOC partitioning between dust and gas-phase is achieved.

  18. Semi-volatile organic compounds in heating, ventilation, and air-conditioning filter dust in retail stores.

    PubMed

    Xu, Y; Liang, Y; Urquidi, J R; Siegel, J A

    2015-02-01

    Retail stores contain a wide range of products that can emit a variety of indoor pollutants. Among these chemicals, phthalate esters and polybrominated diphenyl ethers (PBDEs) are two important categories of semi-volatile organic compounds (SVOCs). Filters in heating, ventilation, and air-conditioning (HVAC) system collect particles from large volumes of air and thus potentially provide spatially and temporally integrated SVOC concentrations. This study measured six phthalate and 14 PBDE compounds in HVAC filter dust in 14 retail stores in Texas and Pennsylvania, United States. Phthalates and PBDEs were widely found in the HVAC filter dust in retail environment, indicating that they are ubiquitous indoor pollutants. The potential co-occurrence of phthalates and PBDEs was not strong, suggesting that their indoor sources are diverse. The levels of phthalates and PBDEs measured in HVAC filter dust are comparable to concentrations found in previous investigations of settled dust in residential buildings. Significant correlations between indoor air and filter dust concentrations were found for diethyl phthalate, di-n-butyl phthalate, and benzyl butyl phthalate. Reasonable agreement between measurements and an equilibrium model to describe SVOC partitioning between dust and gas-phase is achieved. PMID:24766478

  19. Application of local exhaust ventilation system and integrated collectors for control of air pollutants in mining company.

    PubMed

    Ghorbani Shahna, Farshid; Bahrami, Abdulrahman; Farasati, Farhad

    2012-01-01

    Local exhaust ventilation (LEV) systems and integrated collectors were designed and implemented in a mining company in order to control emitted air pollutant from furnaces. The LEV was designed for capture and transition of air pollutants emitted from furnaces to the integrated collectors. The integrated collectors including four high efficiency Stairmand model cyclones for control of particulate matter, a venturi scrubber for control of the fine particles, SO(2) and a part of H(2)S to follow them, and a packed scrubber for treatment of the residual H(2)S and SO(2) were designed. Pollutants concentration were measured to determine system effectiveness. The results showed that the effectiveness of LEV for reducing workplace pollution is 91.83%, 96.32% and 83.67% for dust, SO(2) and H(2)S, respectively. Average removal efficiency of particles by combination of cyclone and venturi scrubber was 98.72%. Average removal efficiency of SO(2) and H(2)S were 95.85% and 47.13% for the venturi scrubber and 68.45% and 92.7% for the packed bed scrubber. The average removal efficiency of SO(2) and H(2)S were increased to 99.1% and 95.95% by the combination of venturi and packed bed scrubbers. According to the results, integrated collectors are a good air pollution control option for industries with economic constraints and ancient technologies. PMID:22878358

  20. A Survey and Critical Review of the Literature on Indoor Air Quality, Ventilation and Health Symptoms in Schools. IEQ Strategies[TM].

    ERIC Educational Resources Information Center

    Daisey, Joan M.; Angell, William J.

    This report presents detailed results from a survey and critical review of existing published literature and reports on indoor air quality (IAQ), ventilation, and IAQ- and building-related health problems in schools, particularly California schools. The findings: (1) identify the most commonly reported building-related health symtoms involving…

  1. Advanced Controls for Residential Whole-House Ventilation Systems

    SciTech Connect

    Turner, William; Walker, Iain; Sherman, Max

    2014-08-01

    Whole-house ventilation systems are becoming commonplace in new construction, remodeling/renovation, and weatherization projects, driven by combinations of specific requirements for indoor air quality (IAQ), health and compliance with standards, such as ASHRAE 62.2. Ventilation systems incur an energy penalty on the home via fan power used to drive the airflow, and the additional space-conditioning load associated with heating or cooling the ventilation air. Finding a balance between IAQ and energy use is important if homes are to be adequately ventilated while not increasing the energy burden. This study used computer simulations to examine RIVEC the Residential Integrated Ventilation Controller - a prototype ventilation controller that aims to deliver whole-house ventilation rates that comply with ventilation standards, for the minimum use of energy. Four different whole-house ventilation systems were simulated, both with and without RIVEC, so that the energy and IAQ results could be compared. Simulations were conducted for 13 US climate zones, three house designs, and three envelope leakage values. The results showed that the RIVEC controller could typically return ventilation energy savings greater than 40percent without compromising long-term chronic or short-term acute exposures to relevant indoor contaminants. Critical and average peak power loads were also reduced as a consequence of using RIVEC.

  2. Predicting residential air exchange rates from questionnaires and meteorology: model evaluation in central North Carolina.

    PubMed

    Breen, Michael S; Breen, Miyuki; Williams, Ronald W; Schultz, Bradley D

    2010-12-15

    A critical aspect of air pollution exposure models is the estimation of the air exchange rate (AER) of individual homes, where people spend most of their time. The AER, which is the airflow into and out of a building, is a primary mechanism for entry of outdoor air pollutants and removal of indoor source emissions. The mechanistic Lawrence Berkeley Laboratory (LBL) AER model was linked to a leakage area model to predict AER from questionnaires and meteorology. The LBL model was also extended to include natural ventilation (LBLX). Using literature-reported parameter values, AER predictions from LBL and LBLX models were compared to data from 642 daily AER measurements across 31 detached homes in central North Carolina, with corresponding questionnaires and meteorological observations. Data was collected on seven consecutive days during each of four consecutive seasons. For the individual model-predicted and measured AER, the median absolute difference was 43% (0.17 h(-1)) and 40% (0.17 h(-1)) for the LBL and LBLX models, respectively. Additionally, a literature-reported empirical scale factor (SF) AER model was evaluated, which showed a median absolute difference of 50% (0.25 h(-1)). The capability of the LBL, LBLX, and SF models could help reduce the AER uncertainty in air pollution exposure models used to develop exposure metrics for health studies.

  3. Ventilation Systems Operating Experience Review for Fusion Applications

    SciTech Connect

    Cadwallader, Lee Charles

    1999-12-01

    This report is a collection and review of system operation and failure experiences for air ventilation systems in nuclear facilities. These experiences are applicable for magnetic and inertial fusion facilities since air ventilation systems are support systems that can be considered generic to nuclear facilities. The report contains descriptions of ventilation system components, operating experiences with these systems, component failure rates, and component repair times. Since ventilation systems have a role in mitigating accident releases in nuclear facilities, these data are useful in safety analysis and risk assessment of public safety. An effort has also been given to identifying any safety issues with personnel operating or maintaining ventilation systems. Finally, the recommended failure data were compared to an independent data set to determine the accuracy of individual values. This comparison is useful for the International Energy Agency task on fusion component failure rate data collection.

  4. Design and Implementation of Automatic Air Flow Rate Control System

    NASA Astrophysics Data System (ADS)

    Akbar, A.; Saputra, C.; Munir, M. M.; Khairurrijal

    2016-08-01

    Venturimeter is an apparatus that can be used to measure the air flow rate. In this experiment we designed a venturimeter which equipped with a valve that is used to control the air flow rate. The difference of pressure between the cross sections was measured with the differential pressure sensor GA 100-015WD which can calculate the difference of pressures from 0 to 3737.33 Pa. A 42M048C Z36 stepper motor was used to control the valve. The precision of this motor rotation is about 0.15 °. A Graphical User Interface (GUI) was developed to monitor and set the value of flow rate then an 8-bit microcontroller was used to process the control system In this experiment- the venturimeter has been examined to get the optimal parameter of controller. The results show that the controller can set the stable output air flow rate.

  5. The influence of broiler activity, growth rate, and litter on carbon dioxide balances for the determination of ventilation flow rates in broiler production.

    PubMed

    Calvet, S; Estellés, F; Cambra-López, M; Torres, A G; Van den Weghe, H F A

    2011-11-01

    Carbon dioxide balances are useful in determining ventilation rates in livestock buildings. These balances need an accurate estimation of the CO(2) produced by animals and their litter to determine the ventilation flows. To estimate the daily variation in ventilation flow, it is necessary to precisely know the daily variation pattern of CO(2) production, which mainly depends on animal activity. The objective of this study was to explore the applicability of CO(2) balances for determining ventilation flows in broiler buildings. More specifically, this work aimed to quantify the amount of CO(2) produced by the litter, as well as the amount of CO(2) produced by the broilers, as a function of productive parameters, and to analyze the influence of broiler activity on CO(2) emissions. Gas concentrations and ventilation flows were simultaneously measured in 3 trials, with 1 under experimental conditions and the other 2 in a commercial broiler farm. In the experimental assay, broiler activity was also determined. At the end of the experimental trial, on the day after the removal of the broilers, the litter accounted for 20% of the total CO(2) produced, and the broilers produced 3.71 L/h of CO(2) per kg of metabolic weight. On the commercial farm, CO(2) production was the same for the 2 cycles (2.60 L/h per kg of metabolic weight, P > 0.05). However, substantial differences were found between CO(2) and broiler activity patterns after changes in light status. A regression model was used to explain these differences (R(2) = 0.52). Carbon dioxide increased with bird activity, being on average 3.02 L/h per kg of metabolic weight for inactive birds and 4.73 L/h per kg of metabolic weight when bird activity was highest. Overall, CO(2) balances are robust tools for determining the daily average ventilation flows in broiler farms. These balances could also be applied at more frequent intervals, but in this case, particular care is necessary after light status changes because of

  6. Oxygen and carbon dioxide sensitivity of ventilation in amphibious crabs, Cardisoma guanhumi, breathing air and water.

    PubMed

    Gannon, Andrew T; Henry, Raymond P

    2004-05-01

    Amphibious crabs, Cardisoma guanhumi, were acclimated to breathing either air or water and exposed to altered levels of oxygen and/or carbon dioxide in the medium. Hypercapnia (22, 36 and 73 torr CO(2)) stimulated a significant hypercapnic ventilatory response (HCVR) in both groups of crabs, with a much greater effect on scaphognathite frequency (Deltaf(SC)=+700%) in air-breathing crabs than water-breathing crabs (Deltaf(SC)=+100%). In contrast, hyperoxia induced significant hypoventilation in both sets of crabs. However, simultaneous hyperoxia and hypercapnia triggered a greater than 10-fold increase in f(SC) in air-breathing crabs but no change in water-breathing crabs. For water-breathing crabs hypoxia simultaneous with hypercapnia triggered the same response as hypoxia alone-bradycardia (-50%), and a significant increase in f(SC) at moderate exposures but not at the more extreme levels. The response of air-breathing crabs to hypoxia concurrent with hypercapnia was proportionally closer to the response to hypercapnia alone than to hypoxia. Thus, C. guanhumi were more sensitive to ambient CO(2) than O(2) when breathing air, characteristic of fully terrestrial species, and more sensitive to ambient O(2) when breathing water, characteristic of fully aquatic species. C. guanhumi possesses both an O(2)- and a CO(2)-based ventilatory drive whether breathing air or water, but the relative importance switches when the respiratory medium is altered.

  7. Demonstration of split-flow ventilation and recirculation as flow-reduction methods in an Air Force paint spray booth. Final technical report, February 1991-October 1992

    SciTech Connect

    Hughes, S.; Ayer, J.; Sutay, R.

    1994-07-01

    During a series of painting operations in a horizontal-flow paint spray booth at Travis AFB, CA, baseline concentrations of four classes of toxic airborne pollutants were measured at 24 locations across a plane immediately forward of the exhaust filters, in the exhaust duct, and inside and outside the respirator in the painter`s breathing zone (BZ). The resulting data were analyzed and used to design a modified ventilation system that (1) separates a portion of the exhaust exiting the lower portion of the booth, which contains a concentration of toxic pollutants greater than the average at the exhaust plane (split-flow); and (2) provides an option to return the flow from the upper portion of the exhaust to the intake plenum for mixing with fresh air and recirculation through the booth (recirculation). After critical review by cognizant Air Force offices and an experimental demonstration showing that a flame ionization detector monitoring the air entering the booth is able to detect excursions above the equivalent exposure limit for the solvents in the paint, the exhaust duct was reconfigured for split-flow and recirculating ventilation. A volunteer painter was briefed on the increased risk of exposure during recirculation, and on the purposes and possible benefits of this study. He then signed an informed consent form before participating in the recirculation tests. A series of tests generally equivalent to the baseline series was conducted during split-flow and recirculating ventilation, and three tests were performed during only split-flow ventilation.

  8. Occupant Interactions and Effectiveness of Natural Ventilation Strategies in Contemporary New Housing in Scotland, UK.

    PubMed

    Sharpe, Tim; Farren, Paul; Howieson, Stirling; Tuohy, Paul; McQuillan, Jonathan

    2015-07-01

    The need to reduce carbon emissions and fuel poverty has led to increased building envelope air tightness, intended to reduce uncontrolled ventilation heat losses. Ventilation strategies in dwellings still allow the use of trickle ventilators in window frames for background ventilation. The extent to which this results in "healthy" Indoor Air Quality (IAQ) in recently constructed dwellings was a concern of regulators in Scotland. This paper describes research to explore this. First a review of literature was conducted, then data on occupant interactions with ventilation provisions (windows, doors, trickle vents) gathered through an interview-based survey of 200 recently constructed dwellings, and measurements made on a sample of 40 of these. The main measured parameter discussed here is CO2 concentration. It was concluded after the literature review that 1000 ppm absolute was a reasonable threshold to use for "adequate" ventilation. The occupant survey found that there was very little occupant interaction with the trickle ventilators e.g., in bedrooms 63% were always closed, 28% always open, and in only 9% of cases occupants intervened to make occasional adjustments. In the measured dwellings average bedroom CO2 levels of 1520 ppm during occupied (night time) hours were observed. Where windows were open the average bedroom CO2 levels were 972 ppm. With windows closed, the combination of "trickle ventilators open plus doors open" gave an average of 1021 ppm. "Trickle ventilators open" gave an average of 1571 ppm. All other combinations gave averages of 1550 to 2000 ppm. Ventilation rates and air change rates were estimated from measured CO2 levels, for all dwellings calculated ventilation rate was less than 8 L/s/p, in 42% of cases calculated air change rate was less than 0.5 ach. It was concluded that trickle ventilation as installed and used is ineffective in meeting desired ventilation rates, evidenced by high CO2 levels reported across the sampled dwellings

  9. Occupant Interactions and Effectiveness of Natural Ventilation Strategies in Contemporary New Housing in Scotland, UK.

    PubMed

    Sharpe, Tim; Farren, Paul; Howieson, Stirling; Tuohy, Paul; McQuillan, Jonathan

    2015-07-21

    The need to reduce carbon emissions and fuel poverty has led to increased building envelope air tightness, intended to reduce uncontrolled ventilation heat losses. Ventilation strategies in dwellings still allow the use of trickle ventilators in window frames for background ventilation. The extent to which this results in "healthy" Indoor Air Quality (IAQ) in recently constructed dwellings was a concern of regulators in Scotland. This paper describes research to explore this. First a review of literature was conducted, then data on occupant interactions with ventilation provisions (windows, doors, trickle vents) gathered through an interview-based survey of 200 recently constructed dwellings, and measurements made on a sample of 40 of these. The main measured parameter discussed here is CO2 concentration. It was concluded after the literature review that 1000 ppm absolute was a reasonable threshold to use for "adequate" ventilation. The occupant survey found that there was very little occupant interaction with the trickle ventilators e.g., in bedrooms 63% were always closed, 28% always open, and in only 9% of cases occupants intervened to make occasional adjustments. In the measured dwellings average bedroom CO2 levels of 1520 ppm during occupied (night time) hours were observed. Where windows were open the average bedroom CO2 levels were 972 ppm. With windows closed, the combination of "trickle ventilators open plus doors open" gave an average of 1021 ppm. "Trickle ventilators open" gave an average of 1571 ppm. All other combinations gave averages of 1550 to 2000 ppm. Ventilation rates and air change rates were estimated from measured CO2 levels, for all dwellings calculated ventilation rate was less than 8 L/s/p, in 42% of cases calculated air change rate was less than 0.5 ach. It was concluded that trickle ventilation as installed and used is ineffective in meeting desired ventilation rates, evidenced by high CO2 levels reported across the sampled dwellings

  10. Measurement of air exchange rate of stationary vehicles and estimation of in-vehicle exposure.

    PubMed

    Park, J H; Spengler, J D; Yoon, D W; Dumyahn, T; Lee, K; Ozkaynak, H

    1998-01-01

    The air exchange rates or air changes per hour (ACH) were measured under 4 conditions in 3 stationary automobiles. The ACH ranged between 1.0 and 3.0 h-1 with windows closed and no mechanical ventilation, between 1.8 and 3.7 h-1 for windows closed with fan set on recirculation, between 13.3 and 26.1 h-1 for window open with no mechanical ventilation, and between 36.2 and 47.5 h-1 for window closed with the fan set on fresh air. ACHs for windows closed with no ventilation were higher for the older automobile than for the newer automobiles. With the windows closed and fan turned off, ACH was not influenced by wind speed (p > 0.05). When the window was open, ACH appeared to be greatly affected by wind speed (R2 = 0.86). These measurements are relevant to understanding exposures inside automobiles to sources such as dry-cleaned clothes, cigarettes and airbags. Therefore, to understand the in-vehicle exposure to these internal sources, perchloroethylene (PCE) emitted from dry-cleaned clothes and environmental tobacco smoke (ETS) inside a vehicle were modeled for simulated driving cycles. Airbag deployment was also modeled for estimating exposure level to alkaline particulate and carbon monoxide (CO). Average exposure to PCE inside a vehicle for 30 minutes period was high (approximately 780 micrograms/m3); however, this is only 6% of the two-week exposure that is influenced by the storage of dry cleaned clothing at home. On the other hand, the exposure levels of respirable suspended particulate (RSP) and formaldehyde due to ETS could reach 2.1 mg/m3 and 0.11 ppm, respectively, when a person smokes inside a driving car even with the window open. In modeling the in-vehicle concentrations following airbag deployment, the average CO level over 20 minutes would not appear to present problem (less than 28 ppm). The peak concentration of respirable particulate would have exceeded 140 mg/m3. Since most of the particle mass is composed of alkaline material, these high levels

  11. Low air exchange rate causes high indoor radon concentration in energy-efficient buildings.

    PubMed

    Vasilyev, A V; Yarmoshenko, I V; Zhukovsky, M V

    2015-06-01

    Since 1995, requirements on energy-efficient building construction were established in Russian Building Codes. In the course of time, utilisation of such technologies became prevailing, especially in multi-storey building construction. According to the results of radon survey in buildings constructed meeting new requirements on energy efficiency, radon concentration exceeds the average level in early-constructed buildings. Preponderance of the diffusion mechanism of radon entry in modern multi-storey buildings has been experimentally established. The experimental technique of the assessment of ventilation rate in dwellings under real conditions was developed. Based on estimates of average ventilation rate, it was approved that measures to increase energy efficiency lead to reduction in ventilation rate and accumulation of higher radon concentrations indoors. Obtained ventilation rate values have to be considered as extremely low.

  12. Flammable gas cloud build up in a ventilated enclosure.

    PubMed

    Ivings, M J; Gant, S E; Saunders, C J; Pocock, D J

    2010-12-15

    Ventilation is frequently used as a means for preventing the build up of flammable or toxic gases in enclosed spaces. The effectiveness of the ventilation often has to be considered as part of a safety case or risk assessment. In this paper methods for assessing ventilation effectiveness for hazardous area classification are examined. The analysis uses data produced from Computational Fluid Dynamics (CFD) simulations of low-pressure jet releases of flammable gas in a ventilated enclosure. The CFD model is validated against experimental measurements of gas releases in a ventilation-controlled test chamber. Good agreement is found between the model predictions and the experimental data. Analysis of the CFD results shows that the flammable gas cloud volume resulting from a leak is largely dependent on the mass release rate of flammable gas and the ventilation rate of the enclosure. The effectiveness of the ventilation for preventing the build up of flammable gas can therefore be assessed by considering the average gas concentration at the enclosure outlet(s). It is found that the ventilation rate of the enclosure provides a more useful measure of ventilation effectiveness than considering the enclosure air change rate.

  13. Flammable gas cloud build up in a ventilated enclosure.

    PubMed

    Ivings, M J; Gant, S E; Saunders, C J; Pocock, D J

    2010-12-15

    Ventilation is frequently used as a means for preventing the build up of flammable or toxic gases in enclosed spaces. The effectiveness of the ventilation often has to be considered as part of a safety case or risk assessment. In this paper methods for assessing ventilation effectiveness for hazardous area classification are examined. The analysis uses data produced from Computational Fluid Dynamics (CFD) simulations of low-pressure jet releases of flammable gas in a ventilated enclosure. The CFD model is validated against experimental measurements of gas releases in a ventilation-controlled test chamber. Good agreement is found between the model predictions and the experimental data. Analysis of the CFD results shows that the flammable gas cloud volume resulting from a leak is largely dependent on the mass release rate of flammable gas and the ventilation rate of the enclosure. The effectiveness of the ventilation for preventing the build up of flammable gas can therefore be assessed by considering the average gas concentration at the enclosure outlet(s). It is found that the ventilation rate of the enclosure provides a more useful measure of ventilation effectiveness than considering the enclosure air change rate. PMID:20855156

  14. Impacts of cave air ventilation and in-cave prior calcite precipitation on Golgotha Cave dripwater chemistry, southwest Australia

    NASA Astrophysics Data System (ADS)

    Treble, Pauline C.; Fairchild, Ian J.; Griffiths, Alan; Baker, Andy; Meredith, Karina T.; Wood, Anne; McGuire, Elizabeth

    2015-11-01

    Speleothem trace element chemistry is an important component of multi-proxy records of environmental change but a thorough understanding of hydrochemical processes is essential for its interpretation. We present a dripwater chemistry dataset (PCO2, alkalinity, Ca, SIcc, Mg and Sr) from an eight-year monitoring study from Golgotha Cave, building on a previous study of hydrology and dripwater oxygen isotopes (Treble et al., 2013). Golgotha Cave is developed in Quaternary aeolianite and located in a forested catchment in the Mediterranean-type climate of southwest Western Australia. All dripwaters from each of the five monitored sites become supersaturated with respect to calcite during most of the year when cave ventilation lowers PCO2 in cave air. In this winter ventilation mode, prior calcite precipitation (PCP) signals of increased Mg/Ca and Sr/Ca in dripwater are attributed to stalactite deposition. A fast-dripping site displays less-evolved carbonate chemistry, implying minimal stalactite growth, phenomena which are attributed to minimal degassing because of the short drip interval (30 s). We employ hydrochemical mass-balance modelling techniques to quantitatively investigate the impact of PCP and CO2 degassing on our dripwater. Initially, we reverse-modelled dripwater solutions to demonstrate that PCP is dominating the dripwater chemistry at our low-flow site and predict that PCP becomes enhanced in underlying stalagmites. Secondly, we forward-modelled the ranges of solution Mg/Ca variation that potentially can be caused by degassing and calcite precipitation to serve as a guide to interpreting the resulting stalagmite chemistry. We predict that stalagmite trace element data from our high-flow sites will reflect trends in original dripwater solutes, preserving information on biogeochemical fluxes within our system. By contrast, stalagmites from our low-flow sites will be dominated by PCP effects driven by cave ventilation. Our poorly karstified system allows us

  15. High Lapse Rates in AIRS Retrieved Temperatures in Cold Air Outbreaks

    NASA Technical Reports Server (NTRS)

    Fetzer, Eric J.; Kahn, Brian; Olsen, Edward T.; Fishbein, Evan

    2004-01-01

    The Atmospheric Infrared Sounder (AIRS) experiment, on NASA's Aqua spacecraft, uses a combination of infrared and microwave observations to retrieve cloud and surface properties, plus temperature and water vapor profiles comparable to radiosondes throughout the troposphere, for cloud cover up to 70%. The high spectral resolution of AIRS provides sensitivity to important information about the near-surface atmosphere and underlying surface. A preliminary analysis of AIRS temperature retrievals taken during January 2003 reveals extensive areas of superadiabatic lapse rates in the lowest kilometer of the atmosphere. These areas are found predominantly east of North America over the Gulf Stream, and, off East Asia over the Kuroshio Current. Accompanying the high lapse rates are low air temperatures, large sea-air temperature differences, and low relative humidities. Imagery from a Visible / Near Infrared instrument on the AIRS experiment shows accompanying clouds. These lines of evidence all point to shallow convection in the bottom layer of a cold air mass overlying warm water, with overturning driven by heat flow from ocean to atmosphere. An examination of operational radiosondes at six coastal stations in Japan shows AIRS to be oversensitive to lower tropospheric lapse rates due to systematically warm near-surface air temperatures. The bias in near-surface air temperature is seen to be independent of sea surface temperature, however. AIRS is therefore sensitive to air-sea temperature difference, but with a warm atmospheric bias. A regression fit to radiosondes is used to correct AIRS near-surface retrieved temperatures, and thereby obtain an estimate of the true atmosphere-ocean thermal contrast in five subtropical regions across the north Pacific. Moving eastward, we show a systematic shift in this air-sea temperature differences toward more isothermal conditions. These results, while preliminary, have implications for our understanding of heat flow from ocean to

  16. Measuring and modeling air exchange rates inside taxi cabs in Los Angeles, California

    NASA Astrophysics Data System (ADS)

    Shu, Shi; Yu, Nu; Wang, Yueyan; Zhu, Yifang

    2015-12-01

    Air exchange rates (AERs) have a direct impact on traffic-related air pollutant (TRAP) levels inside vehicles. Taxi drivers are occupationally exposed to TRAP on a daily basis, yet there is limited measurement of AERs in taxi cabs. To fill this gap, AERs were quantified in 22 representative Los Angeles taxi cabs including 10 Prius, 5 Crown Victoria, 3 Camry, 3 Caravan, and 1 Uplander under realistic driving (RD) conditions. To further study the impacts of window position and ventilation settings on taxi AERs, additional tests were conducted on 14 taxis with windows closed (WC) and on the other 8 taxis with not only windows closed but also medium fan speed (WC-MFS) under outdoor air mode. Under RD conditions, the AERs in all 22 cabs had a mean of 63 h-1 with a median of 38 h-1. Similar AERs were observed under WC condition when compared to those measured under RD condition. Under WC-MFS condition, AERs were significantly increased in all taxi cabs, when compared with those measured under RD condition. A General Estimating Equation (GEE) model was developed and the modeling results showed that vehicle model was a significant factor in determining the AERs in taxi cabs under RD condition. Driving speed and car age were positively associated with AERs but not statistically significant. Overall, AERs measured in taxi cabs were much higher than typical AERs people usually encounter in indoor environments such as homes, offices, and even regular passenger vehicles.

  17. Guide to Home Ventilation

    SciTech Connect

    2010-10-01

    A fact sheet from the U.S. Department of Energy's Office of Energy Efficiency and Renewable Energy: Ventilation refers to the exchange of indoor and outdoor air. Without proper ventilation, an otherwise insulated and airtight house will seal in harmful pollutants, such as carbon monoxide, and moisture that can damage a house.

  18. Multifamily Ventilation Retrofit Strategies

    SciTech Connect

    Ueno, K.; Lstiburek, J.; Bergey, D.

    2012-12-01

    In multifamily buildings, central ventilation systems often have poor performance, overventilating some portions of the building (causing excess energy use), while simultaneously underventilating other portions (causing diminished indoor air quality). BSC and Innova Services Corporation performed a series of field tests at a mid-rise test building undergoing a major energy audit and retrofit, which included ventilation system upgrades.

  19. Heating, ventilating, and air conditioning deactivation thermal analysis of PUREX Plant

    SciTech Connect

    Chen, W.W.; Gregonis, R.A.

    1997-08-01

    Thermal analysis was performed for the proposed Plutonium Uranium Extraction Plant exhaust system after deactivation. The purpose of the analysis was to determine if enough condensation will occur to plug or damage the filtration components. A heat transfer and fluid flow analysis was performed to evaluate the thermal characteristics of the underground duct system, the deep-bed glass fiber filter No. 2, and the high-efficiency particulate air filters in the fourth filter building. The analysis is based on extreme variations of air temperature, relative humidity, and dew point temperature using 15 years of Hanford Site weather data as a basis. The results will be used to evaluate the need for the electric heaters proposed for the canyon exhaust to prevent condensation. Results of the analysis indicate that a condition may exist in the underground ductwork where the duct temperature can lead or lag changes in the ambient air temperature. This condition may contribute to condensation on the inside surfaces of the underground exhaust duct. A worst case conservative analysis was performed assuming that all of the water is removed from the moist air over the inside surface of the concrete duct area in the fully developed turbulent boundary layer while the moist air in the free stream will not condense. The total moisture accumulated in 24 hours is negligible. Water puddling would not be expected. The results of the analyses agree with plant operating experiences. The filters were designed to resist high humidity and direct wetting, filter plugging caused by slight condensation in the upstream duct is not a concern. 19 refs., 2 figs.

  20. An optimized method for the estimation of the respiratory rate from electrocardiographic signals: implications for estimating minute ventilation.

    PubMed

    Weiss, Eric H; Sayadi, Omid; Ramaswamy, Priya; Merchant, Faisal M; Sajja, Naveen; Foley, Lori; Laferriere, Shawna; Armoundas, Antonis A

    2014-08-01

    It is well-known that respiratory activity influences electrocardiographic (ECG) morphology. In this article we present a new algorithm for the extraction of respiratory rate from either intracardiac or body surface electrograms. The algorithm optimizes selection of ECG leads for respiratory analysis, as validated in a swine model. The algorithm estimates the respiratory rate from any two ECG leads by finding the power spectral peak of the derived ratio of the estimated root-mean-squared amplitude of the QRS complexes on a beat-by-beat basis across a 32-beat window and automatically selects the lead combination with the highest power spectral signal-to-noise ratio. In 12 mechanically ventilated swine, we collected intracardiac electrograms from catheters in the right ventricle, coronary sinus, left ventricle, and epicardial surface, as well as body surface electrograms, while the ventilation rate was varied between 7 and 13 breaths/min at tidal volumes of 500 and 750 ml. We found excellent agreement between the estimated and true respiratory rate for right ventricular (R(2) = 0.97), coronary sinus (R(2) = 0.96), left ventricular (R(2) = 0.96), and epicardial (R(2) = 0.97) intracardiac leads referenced to surface lead ECGII. When applied to intracardiac right ventricular-coronary sinus bipolar leads, the algorithm exhibited an accuracy of 99.1% (R(2) = 0.97). When applied to 12-lead body surface ECGs collected in 4 swine, the algorithm exhibited an accuracy of 100% (R(2) = 0.93). In conclusion, the proposed algorithm provides an accurate estimation of the respiratory rate using either intracardiac or body surface signals without the need for additional hardware.

  1. 46 CFR 153.312 - Ventilation system standards.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... ventilation system must be sized to change the air in the ventilated space at least 30 times per hour. (f) A... Handling Space Ventilation § 153.312 Ventilation system standards. A cargo handling space ventilation... (approx. 32.8 ft) from openings into or ventilation intakes for, accommodation or service spaces. (b)...

  2. 46 CFR 153.312 - Ventilation system standards.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... ventilation system must be sized to change the air in the ventilated space at least 30 times per hour. (f) A... Handling Space Ventilation § 153.312 Ventilation system standards. A cargo handling space ventilation... (approx. 32.8 ft) from openings into or ventilation intakes for, accommodation or service spaces. (b)...

  3. Does Mixing Make Residential Ventilation More Effective?

    SciTech Connect

    Sherman, Max; Walker, Iain

    2010-08-16

    Ventilation dilutes or removes indoor contaminants to reduce occupant exposure. In a multi-zone environment such as a house, there will be different dilution rates and different source strengths in every zone. The total ventilation rate is the most important factor in determining the exposure of occupants to given sources, but the zone- specific distribution of exhaust and supply air, and the mixing of ventilation air can have significant roles. Different types of ventilation systems will provide different amounts of mixing depending on several factors such as air leakage through the building envelope, air distribution systems and the location of sources and occupants. This paper reports recent results of investigations to determine the impact that air mixing has on exposures of residential occupants to prototypical contaminants of concern. Evaluations of existing field measurements and simulations reported in the literature are combined with new analyses to provide an integrated overview of the topic. The results show that for extreme cases additional mixing can be a significant factor but for typical homes looking at average exposures mixing is not helpful and can even make exposures worse.

  4. Yaw rate control of an air bearing vehicle

    NASA Technical Reports Server (NTRS)

    Walcott, Bruce L.

    1989-01-01

    The results of a 6 week project which focused on the problem of controlling the yaw (rotational) rate the air bearing vehicle used on NASA's flat floor facility are summarized. Contained within is a listing of the equipment available for task completion and an evaluation of the suitability of this equipment. The identification (modeling) process of the air bearing vehicle is detailed as well as the subsequent closed-loop control strategy. The effectiveness of the solution is discussed and further recommendations are included.

  5. A novel target-type low pressure drop bidirectional optoelectronic air flow sensor for infant artificial ventilation: Measurement principle and static calibration

    NASA Astrophysics Data System (ADS)

    Saccomandi, Paola; Schena, Emiliano; Silvestri, Sergio

    2011-02-01

    An optoelectronic target-type volumetric air flow-rate transducer for bidirectional measurements is presented. The sensor is composed of a T-shaped target and two nominally identical LED-photodiode couples which are operated in differential mode. The sensitive surfaces of the photodiodes are differentially shadowed by the deflection of the target, which in turn depends on the gas flow-rate. The principle of operation is described in mathematical terms and the design parameters have been optimized in order to obtain the highest sensitivity along with minimal pressure drop and reduced dimensions. The sensor is placed in a 20 mm diameter hose and was tested with air flow-rate in the typical temperature range of mechanical ventilation between 20 and 40 °C. The theoretical model was validated through experiments carried out in the volumetric flow range from -7.0 to +7.0 l min-1. The nonlinear behavior allows sensitivities equal to 0.6 V l-1 min for flow rates ranging from -2.0 to +2.0 l min-1, equal to 2.0 V l-1 min for flow rates ranging from -3.0 to -2.0 l min-1 and from +2.0 to +3.0 l min-1, up to 5.7 V l-1 min at higher flow rates ranging from -7.0 to -3.0 l min-1 and from +3.0 to +7.0 l min-1. The linear range extends from 3.0 to 7.0 l min-1 with constant sensitivity equal to 5.7 V l-1 min. The sensor is able to detect a flow-rate equal to 1.0 l min-1 with a sensitivity of about 400 mV l-1 min. The differential nature of the output minimizes the influence of the LEDs' power supply variations and allows to obtain a repeatability in the order of 3% of full scale output. The small pressure drop produced by the sensor placed in-line the fluid stream, of about 2.4 Pa at 7 l min-1, corresponds to a negligible fluid dynamic resistance lower than 0.34 Pa l-1 min.

  6. A novel target-type low pressure drop bidirectional optoelectronic air flow sensor for infant artificial ventilation: Measurement principle and static calibration

    SciTech Connect

    Saccomandi, Paola; Schena, Emiliano; Silvestri, Sergio

    2011-02-15

    An optoelectronic target-type volumetric air flow-rate transducer for bidirectional measurements is presented. The sensor is composed of a T-shaped target and two nominally identical LED-photodiode couples which are operated in differential mode. The sensitive surfaces of the photodiodes are differentially shadowed by the deflection of the target, which in turn depends on the gas flow-rate. The principle of operation is described in mathematical terms and the design parameters have been optimized in order to obtain the highest sensitivity along with minimal pressure drop and reduced dimensions. The sensor is placed in a 20 mm diameter hose and was tested with air flow-rate in the typical temperature range of mechanical ventilation between 20 and 40 deg. C. The theoretical model was validated through experiments carried out in the volumetric flow range from -7.0 to +7.0 l min{sup -1}. The nonlinear behavior allows sensitivities equal to 0.6 V l{sup -1} min for flow rates ranging from -2.0 to +2.0 l min{sup -1}, equal to 2.0 V l{sup -1} min for flow rates ranging from -3.0 to -2.0 l min{sup -1} and from +2.0 to +3.0 l min{sup -1}, up to 5.7 V l{sup -1} min at higher flow rates ranging from -7.0 to -3.0 l min{sup -1} and from +3.0 to +7.0 l min{sup -1}. The linear range extends from 3.0 to 7.0 l min{sup -1} with constant sensitivity equal to 5.7 V l{sup -1} min. The sensor is able to detect a flow-rate equal to 1.0 l min{sup -1} with a sensitivity of about 400 mV l{sup -1} min. The differential nature of the output minimizes the influence of the LEDs' power supply variations and allows to obtain a repeatability in the order of 3% of full scale output. The small pressure drop produced by the sensor placed in-line the fluid stream, of about 2.4 Pa at 7 l min{sup -1}, corresponds to a negligible fluid dynamic resistance lower than 0.34 Pa l{sup -1} min.

  7. A review of reaction rates in high temperature air

    NASA Technical Reports Server (NTRS)

    Park, Chul

    1989-01-01

    The existing experimental data on the rate coefficients for the chemical reactions in nonequilibrium high temperature air are reviewed and collated, and a selected set of such values is recommended for use in hypersonic flow calculations. For the reactions of neutral species, the recommended values are chosen from the experimental data that existed mostly prior to 1970, and are slightly different from those used previously. For the reactions involving ions, the recommended rate coefficients are newly chosen from the experimental data obtained more recently. The reacting environment is assumed to lack thermal equilibrium, and the rate coefficients are expressed as a function of the controlling temperature, incorporating the recent multitemperature reaction concept.

  8. Association Between Air Temperature and Cancer Death Rates in Florida

    PubMed Central

    2015-01-01

    Proponents of global warming predict adverse events due to a slight warming of the planet in the last 100 years. This ecological study tests one of the possible arguments that might support the global warming theory – that it may increase cancer death rates. Thus, average daily air temperature is compared to cancer death rates at the county level in a U.S. state, while controlling for variables of smoking, race, and land elevation. The study revealed that lower cancer death rates were associated with warmer temperatures. Further study is indicated to verify these findings. PMID:26674418

  9. Air traffic control surveillance accuracy and update rate study

    NASA Technical Reports Server (NTRS)

    Craigie, J. H.; Morrison, D. D.; Zipper, I.

    1973-01-01

    The results of an air traffic control surveillance accuracy and update rate study are presented. The objective of the study was to establish quantitative relationships between the surveillance accuracies, update rates, and the communication load associated with the tactical control of aircraft for conflict resolution. The relationships are established for typical types of aircraft, phases of flight, and types of airspace. Specific cases are analyzed to determine the surveillance accuracies and update rates required to prevent two aircraft from approaching each other too closely.

  10. Measuring OutdoorAir Intake Rates Using Electronic Velocity Sensors at Louvers and Downstream of Airflow Straighteners

    SciTech Connect

    Fisk, William; Sullivan, Douglas; Cohen, Sebastian; Han, Hwataik

    2008-10-01

    Practical and accurate technologies are needed for continuously measuring and controlling outdoor air (OA) intake rates in commercial building heating, ventilating, and air conditioning (HVAC) systems. This project evaluated two new measurement approaches. Laboratory experiments determined that OA flow rates were measurable with errors generally less than 10percent using electronic air velocity probes installed between OA intake louver blades or at the outlet face of louvers. High accuracy was maintained with OA flow rates as low as 15percent of the maximum for the louvers. Thus, with this measurement approach HVAC systems do not need separate OA intakes for minimum OA supply. System calibration parameters are required for each unique combination of louver type and velocity sensor location but calibrations are not necessary for each system installation. The research also determined that the accuracy of measuring OA flow rates with velocity probes located in the duct downstream of the intake louver was not improved by installing honeycomb airflow straighteners upstream of the probes. Errors varied with type of upstream louver, were as high as 100percent, and were often greater than 25percent. In conclusion, use of electronic air velocity probes between the blades of OA intake louvers or at the outlet face of louvers is a highly promising means of accurately measuring rates of OA flow into HVAC systems. The use of electronic velocity probes downstream of airflow straighteners is less promising, at least with the relatively small OA HVAC inlet systems employed in this research.

  11. The performance of Dräger Oxylog ventilators at simulated altitude.

    PubMed

    Flynn, J G; Singh, B

    2008-07-01

    Ventilated patients frequently require transport by air in a hypobaric environment. Previous studies have demonstrated significant changes in the performance of ventilators with changes in cabin pressure (altitude) but no studies have been published on the function of modem ventilators at altitude. This experiment set out to evaluate ventilatory parameters (tidal volume and respiratory rate) of three commonly used transport ventilators (the Dräger Oxylog 1000, 2000 and 3000) in a simulated hypobaric environment. Ventilators were assessed using either air-mix (60% oxygen) or 100% oxygen and tested against models simulating a normal lung, a low compliance (Acute Respiratory Distress Syndrome) lung and a high-resistance (asthma) lung. Ventilators were tested at a range of simulated altitudes between sea level and 3048 m. Over this range, tidal volume delivered by the Oxylog 1000 increased by 68% and respiratory rate decreased by 28%. Tidal volume delivered by the Oxylog 2000 ventilator increased by 29% over the same range of altitudes but there was no significant change in respiratory rate. Tidal volume and respiratory rate remained constant with the Oxylog 3000 over the same range of altitudes. Changes were consistent with each ventilator regardless of oxygen content or lung model. It is important that clinicians involved in critical care transport in a hypobaric environment are aware that individual ventilators perform differently at altitude and that they are aware of the characteristics of the particular ventilator that they are using. PMID:18714624

  12. Advanced control strategies for heating, ventilation, air-conditioning, and refrigeration systems—An overview: Part I: Hard control

    SciTech Connect

    D. Subbaram Naidu; Craig G. Rieger

    2011-02-01

    A chronological overview of the advanced control strategies for heating, ventilation, air-conditioning, and refrigeration (HVAC&R) is presented in this article. The overview focuses on hard-computing or control techniques, such as proportional-integral-derivative, optimal, nonlinear, adaptive, and robust; soft-computing or control techniques, such as neural networks, fuzzy logic, genetic algorithms; and on the fusion or hybrid of hard- and soft-control techniques. Thus, it is to be noted that the terminology “hard” and “soft” computing/control has nothing to do with the “hardware” and “software” that is being generally used. Part I of a two-part series focuses on hard-control strategies, and Part II focuses on softand fusion-control in addition to some future directions in HVAC&R research. This overview is not intended to be an exhaustive survey on this topic, and any omission of other works is purely unintentional.

  13. IMPACT OF HEATING AND AIR CONDITIONING SYSTEM OPERATION AND LEAKAGE ON VENTILATION AND INTERCOMPARTMENT TRANSPORT: STUDIES IN UNOCCUPIED AND OCCUPIED TENNESSEE VALLEY HOMES

    EPA Science Inventory

    Forced-air heating and air conditioning (HAC) systems caused an average and maximum increase in air infiltration rates of 1.8- and 4.3-fold, respectively, during brief whole-house studies of tracer gas decay In 39 occupied houses. An average Increase in air infiltration rate of 0...

  14. Anaesthesia ventilators

    PubMed Central

    Jain, Rajnish K; Swaminathan, Srinivasan

    2013-01-01

    Anaesthesia ventilators are an integral part of all modern anaesthesia workstations. Automatic ventilators in the operating rooms, which were very simple with few modes of ventilation when introduced, have become very sophisticated with many advanced ventilation modes. Several systems of classification of anaesthesia ventilators exist based upon various parameters. Modern anaesthesia ventilators have either a double circuit, bellow design or a single circuit piston configuration. In the bellows ventilators, ascending bellows design is safer than descending bellows. Piston ventilators have the advantage of delivering accurate tidal volume. They work with electricity as their driving force and do not require a driving gas. To enable improved patient safety, several modifications were done in circle system with the different types of anaesthesia ventilators. Fresh gas decoupling is a modification done in piston ventilators and in descending bellows ventilator to reduce th incidence of ventilator induced volutrauma. In addition to the conventional volume control mode, modern anaesthesia ventilators also provide newer modes of ventilation such as synchronised intermittent mandatory ventilation, pressure-control ventilation and pressure-support ventilation (PSV). PSV mode is particularly useful for patients maintained on spontaneous respiration with laryngeal mask airway. Along with the innumerable benefits provided by these machines, there are various inherent hazards associated with the use of the ventilators in the operating room. To use these workstations safely, it is important for every Anaesthesiologist to have a basic understanding of the mechanics of these ventilators and breathing circuits. PMID:24249886

  15. Meeting Residential Ventilation Standards Through Dynamic Control of Ventilation Systems

    SciTech Connect

    Sherman, Max H.; Walker, Iain S.

    2011-04-01

    Existing ventilation standards, including American Society of Heating, Refrigerating, and Air-conditioning Engineers (ASHRAE) Standard 62.2, specify continuous operation of a defined mechanical ventilation system to provide minimum ventilation, with time-based intermittent operation as an option. This requirement ignores several factors and concerns including: other equipment such as household exhaust fans that might incidentally provide ventilation, negative impacts of ventilation when outdoor pollutant levels are high, the importance of minimizing energy use particularly during times of peak electricity demand, and how the energy used to condition air as part of ventilation system operation changes with outdoor conditions. Dynamic control of ventilation systems can provide ventilation equivalent to or better than what is required by standards while minimizing energy costs and can also add value by shifting load during peak times and reducing intake of outdoor air contaminants. This article describes the logic that enables dynamic control of whole-house ventilation systems to meet the intent of ventilation standards and demonstrates the dynamic ventilation system control concept through simulations and field tests of the Residential Integrated Ventilation-Energy Controller (RIVEC).

  16. The Effects of Air Pollution on Ischemic Stroke Admission Rate

    PubMed Central

    Alimohammadi, Hossein; Fakhri, Sara; Derakhshanfar, Hojjat; Hosseini-Zijoud, Seyed-Mostafa; Safari, Saeed

    2016-01-01

    The present study aimed to determine the relationship between the level of air pollutants and the rate of ischemic stroke (IS) admissions to hospitals. In this retrospective cross-sectional study, stroke admissions (January-March 2012 and 2013) to an emergency department and air pollution and meteorological data were gathered. The relationship between air pollutant levels and hospital admission rates were evaluated using the generalize additive model. In all 379 patients with IS were referred to the hospital (52.5% male; mean age 68.2±13.3 years). Both transient (p<0.001) and long-term (p<0.001) rises in CO level increases the risk of IS. Increased weekly (p<0.001) and monthly (p<0.001) average O3 levels amplifies this risk, while a transient increase in NO2 (p<0.001) and SO2 (p<0.001) levels has the same effect. Long-term changes in PM10 (p<0.001) and PM2.5 (p<0.001) also increase the risk of IS. The findings showed that the level of air pollutants directly correlates with the number of stroke admissions to the emergency department. PMID:26866000

  17. High-resolution deep Northeast Pacific radiocarbon record shows little change in ventilation rate during the last deglaciation

    NASA Astrophysics Data System (ADS)

    Lund, D. C.; Mix, A. C.

    2010-12-01

    The rise in atmospheric carbon dioxide during the last deglaciation is thought to be driven by release of carbon sequestered in the abyssal ocean. This mechanism requires a poorly ventilated deep Pacific during the Last Glacial Maximum (LGM) and enhanced ventilation during the deglaciation. Here we evaluate the plausibility of this scenario using planktonic and benthic foraminiferal radiocarbon data from a high-sedimentation rate core (~25 cm/kyr) collected in the deep (2700 m) Northeast Pacific. We estimate that the mean benthic-planktonic (B-P) age was 1620±190 years during the LGM (n=10 pairs). This value is indistinguishable from the mean B-P difference for the deglaciation (1500±230; n=20 pairs) and the difference between surface and deep water 14C ages today (1560±70 years). Furthermore, our time series of benthic Δ14C parallels atmospheric Δ14C with an offset of 300±50‰ from 22 to 10 kyr BP. These data suggest the ventilation rate of the deep NE Pacific remained nearly constant during the deglaciation, consistent with lower resolution data from this region (Okazaki et al., 2010). Between 22 and 16 kyr BP, Δ14C in the deep NE Pacific varied between 0 and 100‰, well above the -200‰ values estimated at intermediate depths off of Baja California during the Mystery Interval (Marchitto et al., 2007). The deep NE Pacific apparently did not contain water of adequate age to source deglacial Δ14C anomalies shallower in the water column. Given that Antarctic Intermediate Water is also an unlikely source (de Pol-Holz et al., 2010; Rose et al., 2010), an alternative explanation is necessary for the extreme 14C depletions in the eastern tropical Pacific. De Pol-Holz, R. D., et al. 2010. No signature of abyssal carbon in intermediate waters off Chile during deglaciation. Nature Geoscience 3, 192-195. Marchitto, T., Lehman, S., Ortiz, J., Fluckiger, J. & van Geen, A. 2007. Marine radiocarbon evidence for the mechanism of deglacial atmospheric CO2 rise. Science

  18. Dependence of indoor-pollutant concentrations on sources, ventilation rates, and other removal factors

    SciTech Connect

    Nero, A.V. Jr.; Grimsrud, D.T.

    1983-08-02

    The behavior of several classes of chemical and physical pollutants include emissions from combustion appliances, radon and its progeny, formaldehyde, and other organic compounds. Current research at Lawrence Berkeley Laboratory is described and research needs in the area of indoor air quality is pointed out. (ACR)

  19. Air Controlman 3 and 2: Naval Rate Training Manual and Nonresident Career Course.

    ERIC Educational Resources Information Center

    Naval Education and Training Command, Pensacola, FL.

    The Rate Training Manual is one of a series of training manuals prepared for enlisted personnel of the Navy and Naval Reserve studying for advancement in the Air Controlman (AC) rating to Air Controlman Third and Second Class. Chapter 1 discusses air controlman qualifications, the enlisted rating structure, the Air Controlman rating, references…

  20. Carbon Dioxide Detection and Indoor Air Quality Control.

    PubMed

    Bonino, Steve

    2016-04-01

    When building ventilation is reduced, energy is saved because it is not necessary to heat or cool as much outside air. Reduced ventilation can result in higher levels of carbon dioxide, which may cause building occupants to experience symptoms. Heating or cooling for ventilation air can be enhanced by a DCV system, which can save energy while providing a comfortable environment. Carbon dioxide concentrations within a building are often used to indicate whether adequate fresh air is being supplied to the building. These DCV systems use carbon dioxide sensors in each space or in the return air and adjust the ventilation based on carbon dioxide concentration; the higher the concentration, the more people occupy the space relative to the ventilation rate. With a carbon dioxide sensor DCV system, the fresh air ventilation rate varies based on the number ofpeople in the space, saving energy while maintaining a safe and comfortable environment.

  1. Minimum energy ventilation for fast food restaurant kitchens

    SciTech Connect

    Frey, D.; Nicoulin, V.; Smith, V.

    1996-09-01

    HVAC load represents 30 percent of the total energy consumed in restaurants, and up to 75% of this load can be directly attributed to the kitchen exhaust ventilation system. Over the last several years, research on kitchen exhaust hood ventilation rates has been focused on methods to reduce exhaust air because flow rates prescribed by codes are higher than necessary for capture and containment of cooking effluent. In this research, a fast food restaurant was computer modeled using weather data for five cities to assess the effects of different levels of ventilation rates and strategies on energy use and costs. It was found that decreases in kitchen exhaust flow rates resulted in improved energy and economic performance in most cases. Decreases in cookline radiant gain to space were not sufficient to make higher ventilation rates cost- effective.

  2. A Novel Method for Quantifying the Inhaled Dose of Air Pollutants Based on Heart Rate, Breathing Rate and Forced Vital Capacity.

    PubMed

    Greenwald, Roby; Hayat, Matthew J; Barton, Jerusha; Lopukhin, Anastasia

    2016-01-01

    To better understand the interaction of physical activity and air pollution exposure, it is important to quantify the change in ventilation rate incurred by activity. In this paper, we describe a method for estimating ventilation using easily-measured variables such as heart rate (HR), breathing rate (fB), and forced vital capacity (FVC). We recruited healthy adolescents to use a treadmill while we continuously measured HR, fB, and the tidal volume (VT) of each breath. Participants began at rest then walked and ran at increasing speed until HR was 160-180 beats per minute followed by a cool down period. The novel feature of this method is that minute ventilation ([Formula: see text]) was normalized by FVC. We used general linear mixed models with a random effect for subject and identified nine potential predictor variables that influence either [Formula: see text] or FVC. We assessed predictive performance with a five-fold cross-validation procedure. We used a brute force selection process to identify the best performing models based on cross-validation percent error, the Akaike Information Criterion and the p-value of parameter estimates. We found a two-predictor model including HR and fB to have the best predictive performance ([Formula: see text]/FVC = -4.247+0.0595HR+0.226fB, mean percent error = 8.1±29%); however, given the ubiquity of HR measurements, a one-predictor model including HR may also be useful ([Formula: see text]/FVC = -3.859+0.101HR, mean percent error = 11.3±36%). PMID:26809066

  3. A Novel Method for Quantifying the Inhaled Dose of Air Pollutants Based on Heart Rate, Breathing Rate and Forced Vital Capacity.

    PubMed

    Greenwald, Roby; Hayat, Matthew J; Barton, Jerusha; Lopukhin, Anastasia

    2016-01-01

    To better understand the interaction of physical activity and air pollution exposure, it is important to quantify the change in ventilation rate incurred by activity. In this paper, we describe a method for estimating ventilation using easily-measured variables such as heart rate (HR), breathing rate (fB), and forced vital capacity (FVC). We recruited healthy adolescents to use a treadmill while we continuously measured HR, fB, and the tidal volume (VT) of each breath. Participants began at rest then walked and ran at increasing speed until HR was 160-180 beats per minute followed by a cool down period. The novel feature of this method is that minute ventilation ([Formula: see text]) was normalized by FVC. We used general linear mixed models with a random effect for subject and identified nine potential predictor variables that influence either [Formula: see text] or FVC. We assessed predictive performance with a five-fold cross-validation procedure. We used a brute force selection process to identify the best performing models based on cross-validation percent error, the Akaike Information Criterion and the p-value of parameter estimates. We found a two-predictor model including HR and fB to have the best predictive performance ([Formula: see text]/FVC = -4.247+0.0595HR+0.226fB, mean percent error = 8.1±29%); however, given the ubiquity of HR measurements, a one-predictor model including HR may also be useful ([Formula: see text]/FVC = -3.859+0.101HR, mean percent error = 11.3±36%).

  4. Validation of the criteria for initiating the cleaning of heating, ventilation, and air-conditioning (HVAC) ductwork under real conditions.

    PubMed

    Lavoie, Jacques; Marchand, Geneviève; Cloutier, Yves; Lavoué, Jérôme

    2011-08-01

    Dust accumulation in the components of heating, ventilation, and air-conditioning (HVAC) systems is a potential source of contaminants. To date, very little information is available on recognized methods for assessing dust buildup in these systems. The few existing methods are either objective in nature, involving numerical values, or subjective in nature, based on experts' judgments. An earlier project aimed at assessing different methods of sampling dust in ducts was carried out in the laboratories of the Institut de recherche Robert-Sauvé en santé et en sécurité du travail (IRSST). This laboratory study showed that all the sampling methods were practicable, provided that a specific surface-dust cleaning initiation criterion was used for each method. However, these conclusions were reached on the basis of ideal conditions in a laboratory using a reference dust. The objective of this present study was to validate these laboratory results in the field. To this end, the laboratory sampling templates were replicated in real ducts and the three sampling methods (the IRSST method, the method of the U.S. organization National Air Duct Cleaner Association [NADCA] and that of the French organization Association pour la Prévention et l'Étude de la Contamination [ASPEC]) were used simultaneously in a statistically representative number of systems. The air return and supply ducts were also compared. Cleaning initiation criteria under real conditions were found to be 6.0 mg/100 cm(2) using the IRSST method, 2.0 mg/100 cm(2) using the NADCA method, and 23 mg/100 cm(2) using the ASPEC method. In the laboratory study, the criteria using the same methods were 6.0 for the IRSST method, 2.0 for the NADCA method, and 3.0 for the ASPEC method. The laboratory criteria for the IRSST and NADCA methods were therefore validated in the field. The ASPEC criterion was the only one to change. The ASPEC method therefore allows for the most accurate evaluation of dust accumulation in HVAC

  5. Validation of the criteria for initiating the cleaning of heating, ventilation, and air-conditioning (HVAC) ductwork under real conditions.

    PubMed

    Lavoie, Jacques; Marchand, Geneviève; Cloutier, Yves; Lavoué, Jérôme

    2011-08-01

    Dust accumulation in the components of heating, ventilation, and air-conditioning (HVAC) systems is a potential source of contaminants. To date, very little information is available on recognized methods for assessing dust buildup in these systems. The few existing methods are either objective in nature, involving numerical values, or subjective in nature, based on experts' judgments. An earlier project aimed at assessing different methods of sampling dust in ducts was carried out in the laboratories of the Institut de recherche Robert-Sauvé en santé et en sécurité du travail (IRSST). This laboratory study showed that all the sampling methods were practicable, provided that a specific surface-dust cleaning initiation criterion was used for each method. However, these conclusions were reached on the basis of ideal conditions in a laboratory using a reference dust. The objective of this present study was to validate these laboratory results in the field. To this end, the laboratory sampling templates were replicated in real ducts and the three sampling methods (the IRSST method, the method of the U.S. organization National Air Duct Cleaner Association [NADCA] and that of the French organization Association pour la Prévention et l'Étude de la Contamination [ASPEC]) were used simultaneously in a statistically representative number of systems. The air return and supply ducts were also compared. Cleaning initiation criteria under real conditions were found to be 6.0 mg/100 cm(2) using the IRSST method, 2.0 mg/100 cm(2) using the NADCA method, and 23 mg/100 cm(2) using the ASPEC method. In the laboratory study, the criteria using the same methods were 6.0 for the IRSST method, 2.0 for the NADCA method, and 3.0 for the ASPEC method. The laboratory criteria for the IRSST and NADCA methods were therefore validated in the field. The ASPEC criterion was the only one to change. The ASPEC method therefore allows for the most accurate evaluation of dust accumulation in HVAC

  6. Why We Ventilate

    SciTech Connect

    Logue, Jennifer M.; Sherman, Max H.; Price, Phil N.; Singer, Brett C.

    2011-09-01

    It is widely accepted that ventilation is critical for providing good indoor air quality (IAQ) in homes. However, the definition of"good" IAQ, and the most effective, energy efficient methods for delivering it are still matters of research and debate. This paper presents the results of work done at the Lawrence Berkeley National Lab to identify the air pollutants that drive the need for ventilation as part of a larger effort to develop a health-based ventilation standard. First, we present results of a hazard analysis that identified the pollutants that most commonly reach concentrations in homes that exceed health-based standards or guidelines for chronic or acute exposures. Second, we present results of an impact assessment that identified the air pollutants that cause the most harm to the U.S. population from chronic inhalation in residences. Lastly, we describe the implications of our findings for developing effective ventilation standards.

  7. Preoperational test report, vent building ventilation system

    SciTech Connect

    Clifton, F.T.

    1997-11-04

    This represents a preoperational test report for Vent Building Ventilation Systems, Project W-030. Project W-030 provides a ventilation upgrade for the four Aging Waste Facility tanks. The system provides Heating, Ventilation, and Air Conditioning (HVAC) for the W-030 Ventilation Building. The tests verify correct system operation and correct indications displayed by the central Monitor and Control System.

  8. Surveillance of a Ventilated Rack System for Corynebacterium bovis by Sampling Exhaust-Air Manifolds

    PubMed Central

    Manuel, Christopher A; Pugazhenthi, Umarani; Leszczynski, Jori K

    2016-01-01

    Corynebacterium bovis causes an opportunistic infection of nude (Foxn1, nu/nu) mice, leading to nude mouse hyperkeratotic dermatitis (scaly skin disease). Enzootic in many nude mouse colonies, C. bovis spreads rapidly to naive nude mice, despite modern husbandry practices, and is very difficult to eradicate. To facilitate rapid detection in support of eradication efforts, we investigated a surveillance method based on quantitative real-time PCR (qPCR) evaluation of swabs collected from the horizontal exhaust manifold (HEM) of an IVC rack system. We first evaluated the efficacy of rack sanitation methods for removing C. bovis DNA from the HEM of racks housing endemic colonies of infected nude mice. Pressurized water used to flush the racks’ air exhaust system followed by a standard rack-washer cycle was ineffective in eliminating C. bovis DNA. Only after autoclaving did all sanitized racks test negative for C. bovis DNA. We then measured the effects of stage of infection (early or established), cage density, and cage location on the rack on time-to-detection at the HEM. Stage of infection significantly affected time-to-detection, independent of cage location. Early infections required 7.3 ± 1.2 d whereas established infections required 1 ± 0 d for detection of C. bovis at the HEM. Cage density influenced the quantity of C. bovis DNA detected but not time-to-detection. The location of the cage on the rack affected the time-to-detection only during early C. bovis infections. We suggest that qPCR swabs of HEM are useful during the routine surveillance of nude mouse colonies for C. bovis infection. PMID:26817981

  9. New Ventilated Isolation Cage

    PubMed Central

    Cook, Reginald O.

    1968-01-01

    A multifunction lid has been developed for a commercially available transparent animal cage which permits feeding, watering, viewing, long-term holding, and local transport of laboratory rodents on experiment while isolating the surrounding environment. The cage is airtight except for its inlet and exhaust high-efficiency particulate air filters, and it is completely steam-sterilizable. Opening of the cage's feed and water ports causes an inrush of high velocity air which prevents back-migration of aerosols and permits feeding and watering while eliminating need for chemical vapor decontamination. Ventilation system design permits the holding in adjacent cages of animals infected with different organisms without danger of cross-contamination; leaves the animal room odor-free; reduces required bedding changes to twice a month or less, and provides investigators with capability to control precisely individual cage ventilation rates. Forty-eight cages can be conveniently placed on a standard NIH “shoebox” cage rack (60 inches wide × 28 inches deep × 74 inches high) fitted with a simple manifold exhaust system. The entire system is mobile, requiring only an electrical power outlet. Principal application of the caging system is in the area of preventing exposure of animal caretakers to pathogenic substances associated with the animal host, and in reducing handling of animals and their exposure to extraneous contamination. Images Fig. 1 Fig. 2 Fig. 3 Fig. 4 Fig. 5 Fig. 9 PMID:5659368

  10. Association of pneumococcal conjugate vaccination with rates of ventilation tube insertion in Denmark: population-based register study

    PubMed Central

    Groth, Christina; Thomsen, Reimar W; Ovesen, Therese

    2015-01-01

    Objective To examine if the introduction of pneumococcal conjugate vaccine (PCV) in Denmark was associated with a decrease in the rate of ventilation tube (VT) insertions performed by office-based practising ear, nose and throat (ENT) specialists. Design Population-based register study based on prospectively collected data. Setting Central Denmark Region. Data on VT insertions performed by any office-based practising ENT specialist in the region were collected from the National Health Service Registry. Participants All children below the age of 2 years with a first-time VT insertion from 2001 through 2011. Main outcome measures Age-stratified and gender-stratified standardised incidence rates of first-time VT insertion, and incidence rate ratio for PCV period 2008–2011 compared with pre-PCV period 2001–2007. Results The annual incidence rate of first-time VT insertion in small children increased steadily from 64/1000 person-years in 2001 to 100/1000 person-years in 2011. The incidence rate ratio was 1.27 (95% CI 1.24 to 1.30) in the PCV period compared with the pre-PCV period. Conclusions The introduction of PCV into the Danish childhood immunisation programme in 2007 was not associated with a subsequent decrease in the rate of VT insertions among children below the age of 2 years. Instead, the rate continued to rise, as before the introduction of PCV. Trial registration number Danish Data Protection Agency: 2007-58-0010. PMID:26048205

  11. Measurements of VOC/SVOC emission factors from burning incenses in an environmental test chamber: influence of temperature, relative humidity, and air exchange rate.

    PubMed

    Manoukian, A; Buiron, D; Temime-Roussel, B; Wortham, H; Quivet, E

    2016-04-01

    This study investigates the influence of three environmental indoor parameters (i.e., temperature, relative humidity, and air exchange rate) on the emission of 13 volatile organic compounds (VOCs) and semi-volatile organic compounds (SVOCs) during incense burning. Experiments have been carried out using an environmental test chamber. Statistical results from a classical two-level full factorial design highlight the predominant effect of ventilation on emission factors. The higher the ventilation, the higher the emission factor. Moreover, thanks to these results, an estimation of the concentration range for the compounds under study can be calculated and allows a quick look of indoor pollution induced by incense combustion. Carcinogenic substances (i.e., benzene, benzo(a)pyrene, and formaldehyde) produced from the incense combustion would be predicted in typical living indoors conditions to reach instantaneous concentration levels close to or higher than air quality exposure threshold values.

  12. Developments in longwall ventilation

    SciTech Connect

    Brune, J.F.; Aman, J.P.; Kotch, M.

    1999-07-01

    Rapid development in longwall mining technology has brought significant changes in panel layout and geometry. These changes require adaptations in the ventilation system to provide sufficient air quantities in longwall face and bleeder areas. At CONSOL, various longwall bleeder systems in the Pittsburgh No. 8 Seam have been studied with detailed ventilation surveys. Computer model network simulations were conducted from these surveys to study the effects of different bleeder configurations and ventilation adjustments. This paper examines the relationships between the longwall face air quantity and the convergence in the tailgate-to-bleeder entries, number of development entries, bleeder fan pressure and the tailgate ventilation scheme. It shows that, using conventional ventilation patterns, the face air quantity may be limited if the gob caves tightly. In such cases, modification of the ventilation pattern to an internal bleeder system, combined with appropriate tailgate ventilation and higher bleeder fan pressure may be required. Experience in CONSOL's operations has proven this method successful especially in mines that changed from four-entry to three-entry longwall development.

  13. Evaluation of retrofit crankcase ventilation controls and diesel oxidation catalysts for reducing air pollution in school buses

    NASA Astrophysics Data System (ADS)

    Trenbath, Kim; Hannigan, Michael P.; Milford, Jana B.

    2009-12-01

    This study evaluates the effect of retrofit closed crankcase ventilation filters (CCFs) and diesel oxidation catalysts (DOCs) on the in-cabin air quality in transit-style diesel school buses. In-cabin pollution levels were measured on three buses from the Pueblo, CO District 70 fleet. Monitoring was conducted while buses were driven along their regular routes, with each bus tested three times before and three times after installation of control devices. Ultrafine number concentrations in the school bus cabins were 33-41% lower, on average, after the control devices were installed. Mean mass concentrations of particulate matter less than 2.5 μm in diameter (PM2.5) were 56% lower, organic carbon (OC) 41% lower, elemental carbon (EC) 85% lower, and formaldehyde 32% lower after control devices were installed. While carbon monoxide concentrations were low in all tests, mean concentrations were higher after control devices were installed than in pre-retrofit tests. Reductions in number, OC, and formaldehyde concentrations were statistically significant, but reductions in PM2.5 mass were not. Even with control devices installed, during some runs PM2.5 and OC concentrations in the bus cabins were elevated compared to ambient concentrations observed in the area. OC concentrations inside the bus cabins ranged from 22 to 58 μg m -3 before and 13 to 33 μg m -3 after control devices were installed. OC concentrations were correlated with particle-bound organic tracers for lubricating oil emissions (hopanes) and diesel fuel and tailpipe emissions (polycyclic aromatic hydrocarbons (PAH) and aliphatic hydrocarbons). Mean concentrations of hopanes, PAH, and aliphatic hydrocarbons were lower by 37, 50, and 43%, respectively, after the control devices were installed, suggesting that both CCFs and DOCs were effective at reducing in-cabin OC concentrations.

  14. Propellant Handler's Ensemble (PHE) Aka Self-Contained Atmospheric Protective Ensemble (SCAPE), Ventilator Improvement Study Project

    NASA Technical Reports Server (NTRS)

    Oliva-Buisson, Yvette J. (Compiler)

    2014-01-01

    The overall objective for this project is to evaluate two candidate alternatives for the existing Propellant Handler's Ensemble (PHE) escape ventilator. The new candidate ventilators use newer technology with similar quantities of air at approximately half the weight of the current ventilator. Ventilators are typically used to ingress/egress a hazardous work area when hard line air is provided at the work area but the hose is not long enough to get the operator to and from the staging area to the work area. The intent of this test is to verify that the new ventilators perform as well as or better than the current ventilators in maintaining proper oxygen (O2) and carbon dioxide (CO2) levels in the PHE during a typical use for the rated time period (10 minutes). We will evaluate two new units comparing them to the existing unit. Subjects will wear the Category I version of the Propellant Handler's Ensemble with the rear suit pouch snapped.

  15. Numerical simulation of the performance of building ventilation systems

    SciTech Connect

    Fang, J.B.; Grot, R.A. )

    1990-01-01

    Mathematical modeling is performed for three-dimensional turbulent buoyant flows emerging from an air diffuser in an air-conditioned, ventilated room subject to diverse supply air velocities. The velocity and temperature distributions of air in the room are calculated, and the calculated results are found to be in reasonable agreement with published experimental observations., Calculations of the Air Diffusion Performance Index (ADPI) for a sidewall grille and a return air grille in a room with specified heating loads are carried out for different flow rates of air supply. The predicted ADPI values generally are found to be consistent with the corresponding experimental values. It is reasonable to apply the numerical modeling technique for practical use in the prediction of various air-conditioned room environments and the design of building ventilation systems.

  16. Operability of the Ventilation Continuous Air Monitor (CAM) Interlock Analysis of Proposed Upgrade to the 241AW Farm Primary Exhauster CAM System

    SciTech Connect

    GUSTAVSON, R.D.

    2002-06-19

    The Tank Farms Final Safety Analysis (FSAR) assumes that a ventilation stack Continuous Air Monitor (CAM) interlock system detects high radiation in the exhaust stream and shuts off the associated ventilation system within 10 minutes of a High-Efficiency Particulate Air (HEPA) filter system failure (CHG, 2002). Previous analysis of the as-built CAM system on the AW Farm Primary Exhauster (stack 296-A-27) showed that this system potentially required significantly longer than 10 minutes to detect a HEPA filter failure and initiate shutdown of the ventilation system (Short, 2002). The purpose of this report is to determine the CAM interlock system response time for a proposed upgrade of the 296-A-27 CAM system. The approach to be used in this analysis is essentially the same as used in RPP-10799, Rev. 0 (Short, 2002), which is to conservatively estimate the time required by the proposed upgraded CAM sampling/monitoring system to detect a FSAR-defined HEPA filter failure and automatically shutdown the exhaust fan. For the HEPA filter failure over-temperature accident scenario in the FSAR, the upgraded CAM system on the AW Farm Primary Exhauster will require significantly less than 10 minutes to detect a HEPA filter failure, actuate the CAM Interlock, and shutdown the exhauster fan. Therefore, the analyzed system is adequate to meet the operability requirements specified in the FSAR and the Tank Farms Technical Safety Requirements (CHG, 2001; CHG, 2002).

  17. Particle deposition in ventilation ducts

    SciTech Connect

    Sippola, Mark R.

    2002-09-01

    Exposure to airborne particles is detrimental to human health and indoor exposures dominate total exposures for most people. The accidental or intentional release of aerosolized chemical and biological agents within or near a building can lead to exposures of building occupants to hazardous agents and costly building remediation. Particle deposition in heating, ventilation and air-conditioning (HVAC) systems may significantly influence exposures to particles indoors, diminish HVAC performance and lead to secondary pollutant release within buildings. This dissertation advances the understanding of particle behavior in HVAC systems and the fates of indoor particles by means of experiments and modeling. Laboratory experiments were conducted to quantify particle deposition rates in horizontal ventilation ducts using real HVAC materials. Particle deposition experiments were conducted in steel and internally insulated ducts at air speeds typically found in ventilation ducts, 2-9 m/s. Behaviors of monodisperse particles with diameters in the size range 1-16 {micro}m were investigated. Deposition rates were measured in straight ducts with a fully developed turbulent flow profile, straight ducts with a developing turbulent flow profile, in duct bends and at S-connector pieces located at duct junctions. In straight ducts with fully developed turbulence, experiments showed deposition rates to be highest at duct floors, intermediate at duct walls, and lowest at duct ceilings. Deposition rates to a given surface increased with an increase in particle size or air speed. Deposition was much higher in internally insulated ducts than in uninsulated steel ducts. In most cases, deposition in straight ducts with developing turbulence, in duct bends and at S-connectors at duct junctions was higher than in straight ducts with fully developed turbulence. Measured deposition rates were generally higher than predicted by published models. A model incorporating empirical equations based on

  18. Expected rates with mini-arrays for air showers

    NASA Technical Reports Server (NTRS)

    Hazen, W. E.

    1985-01-01

    As a guide in the design of mini-arrays used to exploit the Linsley effect in the study of air showers, it is useful to calculate the expected rates. The results can aid in the choice of detectors and their placement or in predicting the utility of existing detector systems. Furthermore, the potential of the method can be appraised for the study of large showers. Specifically, we treat the case of a mini-array of dimensions small enough compared to the distance of axes of showers of interest so that it can be considered a point detector. The input information is taken from the many previous studies of air showers by other groups. The calculations will give: (1) the expected integral rate, F(sigma, rho), for disk thickness, sigma, or rise time, t sub 1/2, with local particle density, rho, as a parameter; (2) the effective detection area A(N) with sigma (min) and rho (min) and rho (min) as parameters; (3) the expected rate of collection of data F sub L (N) versus shower size, N.

  19. Realtime mine ventilation simulation

    SciTech Connect

    McDaniel, K.H.; Wallace, K.G. Jr.

    1997-04-01

    This paper describes the development of a Windows based, interactive mine ventilation simulation software program at the Waste Isolation Pilot Plant (WIPP). To enhance the operation of the underground ventilation system, Westinghouse Electric Corporation developed the program called WIPPVENT. While WIPPVENT includes most of the functions of the commercially available simulation program VNETPC and uses the same subroutine to calculate airflow distributions, the user interface has been completely rewritten as a Windows application with screen graphics. WIPPVENT is designed to interact with WIPP ventilation monitoring systems through the sitewise Central monitoring System. Data can be continuously collected from the Underground Ventilation Remote Monitoring and Control System (e.g., air quantity and differential pressure) and the Mine Weather Stations (psychrometric data). Furthermore, WIPPVENT incorporates regulator characteristic curves specific to the site. The program utilizes this data to create and continuously update a REAL-TIME ventilation model. This paper discusses the design, key features, and interactive capabilities of WIPPVENT.

  20. Percutaneous transtracheal ventilation.

    PubMed

    Smith, R B; Babinski, M; Klain, M; Pfaeffle, H

    1976-10-01

    The technique of percutaneous transtracheal ventilation (intermittent jets of oxygen under high pressure, 50 pounds per square inch [psi]) has been used for resuscitation during anesthesia and prior to tracheostomy, and has been established as an important adjunct to life-support techniques. The technical aspects are described together with experimental evidence that intermittent jet ventilation is necessary to eliminate carbon dioxide. The complications occurring with a series of 80 patients are reported along with experimental work in ventilation of dogs with compressed air sources, including truck tires. Emergency physicians should be familiar with this technique and equipment for its use should be readily available in the emergency department. The potential role of transtracheal ventilation in the mobile intensive care unit at accident sites has been explored and appears promising. Conventional airway support techniques should be applied prior to resorting to transtracheal ventilation.

  1. Spontaneous efferent activity in branches of the vagus nerve controlling heart rate and ventilation in the dogfish.

    PubMed

    Barrett, D J; Taylor, E W

    1985-07-01

    Efferent activity was recorded from cranial nerves in the decerebrate dogfish (Scyliorhinus canicula) before and after injection of paralysing drugs. The recordings were made from the mandibular (Vth) and glossopharyngeal (IXth) nerves and the branchial (respiratory) and cardiac branches of the vagus (Xth) nerve. All the respiratory branches (Vth, IXth and Xth) and both cardiac branches fired rhythmic bursts of activity, synchronous with ventilation, which continued (at a higher rate) following paralysis, indicating that they originated in the CNS rather than arising reflexly from stimulation of pharyngeal mechanoreceptors. A burst of activity in the Vth nerve was followed by a burst in the IXth then, after a 30-ms delay, simultaneous bursts in the three respiratory branches of the Xth. The bursts in the branchial cardiac branches had a fixed phase relationship with activity in the respiratory branches, the onset of each burst preceding that in the immediately adjacent branch (branchial III), whereas the bursts in the visceral cardiac branches had a variable phase relationship with all other branches. The branchial cardiac branches alone contained units which fired sporadically between the bursts and increased their rate of firing during hypoxia. Both the bursting and non-bursting units responded to mechanical stimulation of the gill area. Separate oscillatory inputs driving the Vth, IXth and Xth respiratory motoneurones and an excitatory input to the bursting cardiac vagal motoneurones from expiratory motoneurones or the respiratory rhythm generator are implied by these relationships. The sporadically firing units in the branchial cardiac nerves clearly receive non-oscillatory inputs.

  2. Oven ventilation system

    SciTech Connect

    Brewer, D.E.

    1987-02-17

    A ventilation system is described for venting an oven with external surfaces, the oven being located within an enclosed space, the system comprising: intake means for collecting air from the external environment of the enclosed space; means for forming a sheet of the air and passing the sheet across the external surfaces of the oven; and exhaust means for exhausting the sheet of the air to the external environment of the enclosed space after the air has been passed across the external surfaces.

  3. Review of Residential Ventilation Technologies

    SciTech Connect

    Russell, Marion L.; Sherman, Max H.; Rudd, Armin

    2005-03-01

    This paper reviews current and potential ventilation technologies for residential buildings in North America and a few in Europe. The major technologies reviewed include a variety of mechanical systems, natural ventilation, and passive ventilation. Key parameters that are related to each system include operating costs, installation costs, ventilation rates, heat recovery potential. It also examines related issues such as infiltration, duct systems, filtration options, noise, and construction issues. This report describes a wide variety of systems currently on the market that can be used to meet ASHRAE standard 62.2. While these systems generally fall into the categories of supply, exhaust or balanced, the specifics of each system are driven by concerns that extend beyond those in the standard and are discussed. Some of these systems go beyond the current standard by providing additional features (such as air distribution or pressurization control). The market will decide the immediate value of such features, but ASHRAE may wish to consider modifications to the standard in the future.

  4. Mechanical ventilation in children.

    PubMed

    Kendirli, Tanil; Kavaz, Asli; Yalaki, Zahide; Oztürk Hişmi, Burcu; Derelli, Emel; Ince, Erdal

    2006-01-01

    Mechanical ventilation can be lifesaving, but > 50% of complications in conditions that require intensive care are related to ventilatory support, particularly if it is prolonged. We retrospectively evaluated the medical records of patients who had mechanical ventilation in the Pediatric Intensive Care Unit (PICU) during a follow-up period between January 2002-May 2005. Medical records of 407 patients were reviewed. Ninety-one patients (22.3%) were treated with mechanical ventilation. Ages of all patients were between 1-180 (median: 8) months. The mechanical ventilation time was 18.8 +/- 14.1 days. Indication of mechanical ventilation could be divided into four groups as respiratory failure (64.8%), cardiovascular failure (19.7%), central nervous system disease (9.8%) and safety airway (5.4%). Tracheostomy was performed in four patients. The complication ratio of mechanically ventilated children was 42.8%, and diversity of complications was as follows: 26.3% atelectasia, 17.5% ventilator-associated pneumonia, 13.1% pneumothorax, 5.4% bleeding, 4.3% tracheal edema, and 2.1% chronic lung disease. The mortality rate of mechanically ventilated patients was 58.3%, but the overall mortality rate in the PICU was 12.2%. In conclusion, there are few published epidemiological data on the follow-up results and mortality in infants and children who are mechanically ventilated. PMID:17290566

  5. Energy and Cost Associated with Ventilating Office Buildings in a Tropical Climate

    PubMed Central

    Rim, Donghyun; Schiavon, Stefano; Nazaroff, William W.

    2015-01-01

    Providing sufficient amounts of outdoor air to occupants is a critical building function for supporting occupant health, well-being and productivity. In tropical climates, high ventilation rates require substantial amounts of energy to cool and dehumidify supply air. This study evaluates the energy consumption and associated cost for thermally conditioning outdoor air provided for building ventilation in tropical climates, considering Singapore as an example locale. We investigated the influence on energy consumption and cost of the following factors: outdoor air temperature and humidity, ventilation rate (L/s per person), indoor air temperature and humidity, air conditioning system coefficient of performance (COP), and cost of electricity. Results show that dehumidification of outdoor air accounts for more than 80% of the energy needed for building ventilation in Singapore’s tropical climate. Improved system performance and/or a small increase in the indoor temperature set point would permit relatively large ventilation rates (such as 25 L/s per person) at modest or no cost increment. Overall, even in a thermally demanding tropical climate, the energy cost associated with increasing ventilation rate up to 25 L/s per person is less than 1% of the wages of an office worker in an advanced economy like Singapore’s. This result implies that the benefits of increasing outdoor air ventilation rate up to 25 L/s per person — which is suggested to provide for productivity increases, lower sick building syndrome symptom prevalence, and reduced sick leave — can be much larger than the incremental cost of ventilation. PMID:25822504

  6. Laboratory Ventilation and Safety.

    ERIC Educational Resources Information Center

    Steere, Norman V.

    1965-01-01

    In order to meet the needs of both safety and economy, laboratory ventilation systems must effectively remove air-borne toxic and flammable materials and at the same time exhaust a minimum volume of air. Laboratory hoods are the most commonly used means of removing gases, dusts, mists, vapors, and fumed from laboratory operations. To be effective,…

  7. Comparison the effect of Sleep Positioning on Cardiorespiratory Rate in Noninvasive Ventilated Premature Infants

    PubMed Central

    Ghorbani, Fatemeh; Asadollahi, Maliheh; Valizadeh, Sousan

    2013-01-01

    Background: Results of several studies suggest that prone position is beneficial in improving the preterm infants’ cardio-respiratory status. Previous studies showed opposite results, and also there is not any available clear study about the effect of this position on cardio-respiratory rates of Nasal Continuous Positive Airway Pressure (N-CPAP) treating premature infants. Objectives: This study aimed at comparing supine and prone positions on cardio-respiratory rates of premature infants with respiratory distress syndrome (RDS) who were treated using N-CPAP. Patients and Methods: This was a cross over study which was performed in 2010 on 44 hospitalized 29-34 weeks gestation premature infants who were receiving N-CPAP in Neonatal Intensive Care Unit of Al-Zahra Hospital of Tabriz University of Medical Sciences. Infants were randomly assigned into two groups, and the first group was placed in prone at first and then in supine, and the position of second group was at first supine and then prone. Infants’ Heart Rate (HR) and Respiratory Rate (RR) were assessed three times in each position for 30 minutes. The data was recorded in a data-collection form, and demographic data was analyzed using t test, Chi square and Fisher exact test. Also, repeated measurement ANOVA and Tukey post-hoc tests were used. Results: There was a significant difference in HR and RR of premature infants who were similar in gestational age and clinical condition and placed in two positions. Premature infants’ HR and RR became lower at prone position than supine in both groups. So it can be concluded that prone position could decrease infants HR and RR, but supine position might increase them (P < 0.05). Conclusion: Our findings support prone positioning for premature infants. Therefore, it is advisable to NICU staff that if there is no obstacle for changing the infant’s position, prone position in infants with respiratory complications during receiving N-CPAP in NICU can be useful

  8. Characterization of air profiles impeded by plant canopies for a variable-rate air-assisted sprayer

    Technology Transfer Automated Retrieval System (TEKTRAN)

    The preferential design for variable-rate orchard and nursery sprayers relies on tree structure to control liquid and air flow rates. Demand for this advanced feature has been incremental as the public demand on reduction of pesticide use. A variable-rate, air assisted, five-port sprayer had been in...

  9. WASTE HANDLING BUILDING VENTILATION SYSTEM DESCRIPTION DOCUMENT

    SciTech Connect

    P.A. Kumar

    2000-06-21

    The Waste Handling Building Ventilation System provides heating, ventilation, and air conditioning (HVAC) for the contaminated, potentially contaminated, and uncontaminated areas of the Monitored Geologic Repository's (MGR) Waste Handling Building (WHB). In the uncontaminated areas, the non-confinement area ventilation system maintains the proper environmental conditions for equipment operation and personnel comfort. In the contaminated and potentially contaminated areas, in addition to maintaining the proper environmental conditions for equipment operation and personnel comfort, the contamination confinement area ventilation system directs potentially contaminated air away from personnel in the WHB and confines the contamination within high-efficiency particulate air (HEPA) filtration units. The contamination confinement areas ventilation system creates airflow paths and pressure zones to minimize the potential for spreading contamination within the building. The contamination confinement ventilation system also protects the environment and the public by limiting airborne releases of radioactive or other hazardous contaminants from the WHB. The Waste Handling Building Ventilation System is designed to perform its safety functions under accident conditions and other Design Basis Events (DBEs) (such as earthquakes, tornadoes, fires, and loss of the primary electric power). Additional system design features (such as compartmentalization with independent subsystems) limit the potential for cross-contamination within the WHB. The system provides status of important system parameters and equipment operation, and provides audible and/or visual indication of off-normal conditions and equipment failures. The Waste Handling Building Ventilation System confines the radioactive and hazardous material within the building such that the release rates comply with regulatory limits. The system design, operations, and maintenance activities incorporate ALARA (as low as is

  10. Speech for People with Tracheostomies or Ventilators

    MedlinePlus

    ... ventilator users may sound different. Because of the design of the ventilator, speech occurs when air is ... pathologists (SLPs) The SLP will evaluate the person's thinking and language skills, oral-motor and swallowing functioning, ...

  11. Economic, Environmental and Health Implications of Enhanced Ventilation in Office Buildings

    PubMed Central

    MacNaughton, Piers; Pegues, James; Satish, Usha; Santanam, Suresh; Spengler, John; Allen, Joseph

    2015-01-01

    Introduction: Current building ventilation standards are based on acceptable minimums. Three decades of research demonstrates the human health benefits of increased ventilation above these minimums. Recent research also shows the benefits on human decision-making performance in office workers, which translates to increased productivity. However, adoption of enhanced ventilation strategies is lagging. We sought to evaluate two of the perceived potential barriers to more widespread adoption—Economic and environmental costs. Methods: We estimated the energy consumption and associated per building occupant costs for office buildings in seven U.S. cities, representing different climate zones for three ventilation scenarios (standard practice (20 cfm/person), 30% enhanced ventilation, and 40 cfm/person) and four different heating, ventilation and air conditioning (HVAC) system strategies (Variable Air Volume (VAV) with reheat and a Fan Coil Unit (FCU), both with and without an energy recovery ventilator). We also estimated emissions of greenhouse gases associated with this increased energy usage, and, for comparison, converted this to the equivalent number of vehicles using greenhouse gas equivalencies. Lastly, we paired results from our previous research on cognitive function and ventilation with labor statistics to estimate the economic benefit of increased productivity associated with increasing ventilation rates. Results: Doubling the ventilation rate from the American Society of Heating, Refrigeration and Air-Conditioning Engineers minimum cost less than $40 per person per year in all climate zones investigated. Using an energy recovery ventilation system significantly reduced energy costs, and in some scenarios led to a net savings. At the highest ventilation rate, adding an ERV essentially neutralized the environmental impact of enhanced ventilation (0.03 additional cars on the road per building across all cities). The same change in ventilation improved the

  12. Mobile zone, spray booth ventilation system. Final report

    SciTech Connect

    Not Available

    1994-04-26

    This concept endeavors to reduce the volume of air (to be treated) from spray paint booths, thereby increasing efficiency and improving air pollution abatement (VOC emissions especially). Most of the ventilation air is recycled through the booth to maintain laminar flow; the machinery is located on the supply side of the booth rather than on the exhaust side. 60 to 95% reduction in spray booth exhaust rate should result. Although engineering and production prototypes have been made, demand is low.

  13. Hygiene guideline for the planning, installation, and operation of ventilation and air-conditioning systems in health-care settings - Guideline of the German Society for Hospital Hygiene (DGKH).

    PubMed

    Külpmann, Rüdiger; Christiansen, Bärbel; Kramer, Axel; Lüderitz, Peter; Pitten, Frank-Albert; Wille, Frank; Zastrow, Klaus-Dieter; Lemm, Friederike; Sommer, Regina; Halabi, Milo

    2016-01-01

    Since the publication of the first "Hospital Hygiene Guideline for the implementation and operation of air conditioning systems (HVAC systems) in hospitals" (http://www.krankenhaushygiene.de/informationen/fachinformationen/leitlinien/12) in 2002, it was necessary due to the increase in knowledge, new regulations, improved air-conditioning systems and advanced test methods to revise the guideline. Based on the description of the basic features of ventilation concepts, its hygienic test and the usage-based requirements for ventilation, the DGKH section "Ventilation and air conditioning technology" attempts to provide answers for the major air quality issues in the planning, design and the hygienically safe operation of HVAC systems in rooms of health care. PMID:26958457

  14. Hygiene guideline for the planning, installation, and operation of ventilation and air-conditioning systems in health-care settings - Guideline of the German Society for Hospital Hygiene (DGKH).

    PubMed

    Külpmann, Rüdiger; Christiansen, Bärbel; Kramer, Axel; Lüderitz, Peter; Pitten, Frank-Albert; Wille, Frank; Zastrow, Klaus-Dieter; Lemm, Friederike; Sommer, Regina; Halabi, Milo

    2016-01-01

    Since the publication of the first "Hospital Hygiene Guideline for the implementation and operation of air conditioning systems (HVAC systems) in hospitals" (http://www.krankenhaushygiene.de/informationen/fachinformationen/leitlinien/12) in 2002, it was necessary due to the increase in knowledge, new regulations, improved air-conditioning systems and advanced test methods to revise the guideline. Based on the description of the basic features of ventilation concepts, its hygienic test and the usage-based requirements for ventilation, the DGKH section "Ventilation and air conditioning technology" attempts to provide answers for the major air quality issues in the planning, design and the hygienically safe operation of HVAC systems in rooms of health care.

  15. Hygiene guideline for the planning, installation, and operation of ventilation and air-conditioning systems in health-care settings – Guideline of the German Society for Hospital Hygiene (DGKH)

    PubMed Central

    Külpmann, Rüdiger; Christiansen, Bärbel; Kramer, Axel; Lüderitz, Peter; Pitten, Frank-Albert; Wille, Frank; Zastrow, Klaus-Dieter; Lemm, Friederike; Sommer, Regina; Halabi, Milo

    2016-01-01

    Since the publication of the first “Hospital Hygiene Guideline for the implementation and operation of air conditioning systems (HVAC systems) in hospitals” (http://www.krankenhaushygiene.de/informationen/fachinformationen/leitlinien/12) in 2002, it was necessary due to the increase in knowledge, new regulations, improved air-conditioning systems and advanced test methods to revise the guideline. Based on the description of the basic features of ventilation concepts, its hygienic test and the usage-based requirements for ventilation, the DGKH section “Ventilation and air conditioning technology” attempts to provide answers for the major air quality issues in the planning, design and the hygienically safe operation of HVAC systems in rooms of health care. PMID:26958457

  16. 6. VIEW LOOKING SOUTHEAST AT VENTILATION EQUIPMENT IN SOUTH VENTILATION ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    6. VIEW LOOKING SOUTHEAST AT VENTILATION EQUIPMENT IN SOUTH VENTILATION HOUSE. THIS AIR CONDITIONING SYSTEM WAS INSTALLED BY PARKS-CRAMER COMPANY OF FITCHBURG, MASSACHUSETTS WHEN THE MILL WAS CONSTRUCTED IN 1923-24. ONE AIR WASHER AND FAN ROOM EXTERIOR IS VISIBLE ON THE RIGHT. THE DUCTS FROM BOTH FAN ROOMS (CURVED METAL STRUCTURES AT CENTER AND LEFT OF PHOTO) ARE CONNECTED TO A COMMON AIR SHAFT. - Stark Mill, 117 Corinth Road, Hogansville, Troup County, GA

  17. Heart-rate monitoring by air pressure and causal analysis

    NASA Astrophysics Data System (ADS)

    Tsuchiya, Naoki; Nakajima, Hiroshi; Hata, Yutaka

    2011-06-01

    Among lots of vital signals, heart-rate (HR) is an important index for diagnose human's health condition. For instance, HR provides an early stage of cardiac disease, autonomic nerve behavior, and so forth. However, currently, HR is measured only in medical checkups and clinical diagnosis during the rested state by using electrocardiograph (ECG). Thus, some serious cardiac events in daily life could be lost. Therefore, a continuous HR monitoring during 24 hours is desired. Considering the use in daily life, the monitoring should be noninvasive and low intrusive. Thus, in this paper, an HR monitoring in sleep by using air pressure sensors is proposed. The HR monitoring is realized by employing the causal analysis among air pressure and HR. The causality is described by employing fuzzy logic. According to the experiment on 7 males at age 22-25 (23 on average), the correlation coefficient against ECG is 0.73-0.97 (0.85 on average). In addition, the cause-effect structure for HR monitoring is arranged by employing causal decomposition, and the arranged causality is applied to HR monitoring in a setting posture. According to the additional experiment on 6 males, the correlation coefficient is 0.66-0.86 (0.76 on average). Therefore, the proposed method is suggested to have enough accuracy and robustness for some daily use cases.

  18. Predicting clinical physiology: a Markov chain model of heart rate recovery after spontaneous breathing trials in mechanically ventilated patients.

    PubMed

    Lu, Yan; Burykin, Anton; Deem, Michael W; Buchman, Timothy G

    2009-09-01

    Analysis of heart rate (HR) dynamics before, during, and after a physiologic stress has clinical importance. For example, the celerity of heart rate recovery (HRR) after a cardiac stress test (eg, treadmill exercise test) has been shown to be an independent predictor of all-cause mortality. Heart rate dynamics are modulated, in part, by the autonomic nervous system. These dynamics are commonly abstracted using metrics of heart rate variability (HRV), which are known to be sensitive to the influence of the autonomic nervous system on HR. The patient-specific modulators of HR should be reflected both in the response to stress as well as in the recovery from stress. We therefore hypothesized that the patient-specific HR response to stress could be used to predict the HRR after the stress. We devised a Markov chain model to predict the poststress HRR dynamics using the parameters (transition matrix) calculated from HR data during the stress. The model correctly predicts the exponential shape of poststress HRR. This model features a simple analytical relationship linking poststress HRR time constant (T(off)) with a standard measure of HRV, namely the correlation coefficient of the Poincaré plot (first return map) of the HR recorded during the stress. A corresponding relationship exists between the time constant (T(on)) of R-R interval decrease at the onset of stress and the correlation coefficient of the Poincaré plot of prestress R-R intervals. Consequently, the model can be used for the prediction of poststress HRR using the HRV measured during the stress. This direct relationship between the event-to-event microscopic fluctuations (HRV) during the stress and the macroscopic response (HRR) after the stress terminates can be interpreted as an instance of a fluctuation-dissipation relationship. We have thus applied the fluctuation-dissipation theorem to the analysis of heart rate dynamics. The approach is specific neither to cardiac physiology nor to transitions

  19. RESULTS OF EXPERIMENT TO DETERMINE CORROSION RATES FOR 304L IN HB-LINE DISSOLVER VESSEL VENTILATION SYSTEM

    SciTech Connect

    Mickalonis, J; Kathryn Counts, K

    2008-02-22

    Radioactive material being processed as part of the DE3013 program for HB-Line will result in the presence of chlorides, and in some cases fluorides, in the dissolver. Material Science and Technology developed an experimental plan to evaluate the impact of chloride on corrosion of the dissolver vessel ventilation system. The plan set test variables from the proposed operating parameters, previous test results, and a desired maximum chloride concentration for processing. The test variables included concentrations of nitric acid, fluorides and chlorides, and the presence of a welded and stressed metal coupon. Table 1 contains expected general corrosion rates in the HB-Line vessel vent system from dissolution of 3013 contents of varying nitric acid and chloride content. These general corrosion rates were measured upstream of the condenser in the experiment's offgas system near the entrance to the dissolver. However, they could apply elsewhere in the offgas system, depending on factors not simulated in the testing, including offgas system temperatures and airflow. Localized corrosion was significant in Tests One, Two, and Three. This corrosion is significant because it will probably be the first mode of penetration of the 304L steel in several places in the system. See Table 2. For Tests One and Three, the penetration rate of localized corrosion was much higher than that for general corrosion. It was approximately four times higher in Test One and at least 45 times higher in Test Three, penetrating an entire coupon thickness of 54 mils in 186 hours or less. There was no significant difference in corrosion between welded areas and un-welded areas on coupons. There was also no significant attack on stressed portions of coupons. It is probable that the lack of corrosion was because the stressed areas were facing downwards and offered no place for condensation or deposits to form. Had deposits formed, pitting may have occurred and led to stress corrosion cracking. The

  20. Modeling spatial and temporal variability of residential air exchange rates for the Near-Road Exposures and Effects of Urban Air Pollutants Study (NEXUS).

    PubMed

    Breen, Michael S; Burke, Janet M; Batterman, Stuart A; Vette, Alan F; Godwin, Christopher; Croghan, Carry W; Schultz, Bradley D; Long, Thomas C

    2014-11-07

    Air pollution health studies often use outdoor concentrations as exposure surrogates. Failure to account for variability of residential infiltration of outdoor pollutants can induce exposure errors and lead to bias and incorrect confidence intervals in health effect estimates. The residential air exchange rate (AER), which is the rate of exchange of indoor air with outdoor air, is an important determinant for house-to-house (spatial) and temporal variations of air pollution infiltration. Our goal was to evaluate and apply mechanistic models to predict AERs for 213 homes in the Near-Road Exposures and Effects of Urban Air Pollutants Study (NEXUS), a cohort study of traffic-related air pollution exposures and respiratory effects in asthmatic children living near major roads in Detroit, Michigan. We used a previously developed model (LBL), which predicts AER from meteorology and questionnaire data on building characteristics related to air leakage, and an extended version of this model (LBLX) that includes natural ventilation from open windows. As a critical and novel aspect of our AER modeling approach, we performed a cross validation, which included both parameter estimation (i.e., model calibration) and model evaluation, based on daily AER measurements from a subset of 24 study homes on five consecutive days during two seasons. The measured AER varied between 0.09 and 3.48 h(-1) with a median of 0.64 h(-1). For the individual model-predicted and measured AER, the median absolute difference was 29% (0.19 h‑1) for both the LBL and LBLX models. The LBL and LBLX models predicted 59% and 61% of the variance in the AER, respectively. Daily AER predictions for all 213 homes during the three year study (2010-2012) showed considerable house-to-house variations from building leakage differences, and temporal variations from outdoor temperature and wind speed fluctuations. Using this novel approach, NEXUS will be one of the first epidemiology studies to apply calibrated and

  1. Exposure Modeling of Residential Air Exchange Rates for NEXUS Participants

    EPA Science Inventory

    Due to cost and participant burden of personal measurements, air pollution health studies often estimate exposures using local ambient air monitors. Since outdoor levels do not necessarily reflect personal exposures, we developed the Exposure Model for Individuals (EMI) to improv...

  2. Exposure Modeling of Residential Air Exchange Rates for NEXUS Participants.

    EPA Science Inventory

    Due to cost and participant burden of personal measurements, air pollution health studies often estimate exposures using local ambient air monitors. Since outdoor levels do not necessarily reflect personal exposures, we developed the Exposure Model for Individuals (EMI) to improv...

  3. Evolution of microbial aerosol behaviour in heating, ventilating and air-conditioning systems--quantification of Staphylococcus epidermidis and Penicillium oxalicum viability.

    PubMed

    Forthomme, A; Andrès, Y; Joubert, A; Simon, X; Duquenne, P; Bemer, D; Le Coq, L

    2012-01-01

    The aim of this study was to develop an experimental set-up and a methodology to uniformly contaminate several filter samples with high concentrations of cultivable bacteria and fungi. An experimental set-up allows contaminating simultaneously up to four filters for range of velocities representative of heating, ventilating and air-conditioning systems. The test aerosol was composed of a microbial consortium of one bacterium (Staphylococcus epidermidis) and one fungus (Penicillium oxalicum) and aerosol generation was performed in wet conditions. Firstly, the experimental set-up was validated in regards to homogeneity of the air flows. The bioaerosol was also characterized in terms of the number and particle size distribution using two particle counters: optical particle counter Grimm 1.109 (optical diameters) and TSI APS 3321 (aerodynamic diameters). Moreover, stabilities of the number of particles generated were measured. Finally, concentrations of cultivable microorganisms were measured with BioSamplers SKC downstream of the four filters.

  4. Evolution of microbial aerosol behaviour in heating, ventilating and air-conditioning systems--quantification of Staphylococcus epidermidis and Penicillium oxalicum viability.

    PubMed

    Forthomme, A; Andrès, Y; Joubert, A; Simon, X; Duquenne, P; Bemer, D; Le Coq, L

    2013-01-01

    The aim of this study was to develop an experimental set-up and a methodology to uniformly contaminate several filter samples with high concentrations of cultivable bacteria and fungi. An experimental set-up allows contaminating simultaneously up to four filters for range of velocities representative of heating, ventilating and air-conditioning systems. The test aerosol was composed of a microbial consortium of one bacterium (Staphylococcus epidermidis) and one fungus (Penicillium oxalicum) and aerosol generation was performed in wet conditions. Firstly, the experimental set-up was validated in regards to homogeneity of the air flows. The bioaerosol was also characterized in terms of number and particle size distribution using two particle counters: optical particle counter Grimm 1.109 (optical diameters) and TSI APS 3321 (aerodynamic diameters). Moreover, stabilities of the number of particles generated were measured. Finally, concentrations of cultivable microorganisms were measured with BioSamplers (SKC) downstream of the four filters.

  5. Evolution of microbial aerosol behaviour in heating, ventilating and air-conditioning systems--quantification of Staphylococcus epidermidis and Penicillium oxalicum viability.

    PubMed

    Forthomme, A; Andrès, Y; Joubert, A; Simon, X; Duquenne, P; Bemer, D; Le Coq, L

    2012-01-01

    The aim of this study was to develop an experimental set-up and a methodology to uniformly contaminate several filter samples with high concentrations of cultivable bacteria and fungi. An experimental set-up allows contaminating simultaneously up to four filters for range of velocities representative of heating, ventilating and air-conditioning systems. The test aerosol was composed of a microbial consortium of one bacterium (Staphylococcus epidermidis) and one fungus (Penicillium oxalicum) and aerosol generation was performed in wet conditions. Firstly, the experimental set-up was validated in regards to homogeneity of the air flows. The bioaerosol was also characterized in terms of the number and particle size distribution using two particle counters: optical particle counter Grimm 1.109 (optical diameters) and TSI APS 3321 (aerodynamic diameters). Moreover, stabilities of the number of particles generated were measured. Finally, concentrations of cultivable microorganisms were measured with BioSamplers SKC downstream of the four filters. PMID:23393961

  6. Evolution of microbial aerosol behaviour in heating, ventilating and air-conditioning systems--quantification of Staphylococcus epidermidis and Penicillium oxalicum viability.

    PubMed

    Forthomme, A; Andrès, Y; Joubert, A; Simon, X; Duquenne, P; Bemer, D; Le Coq, L

    2013-01-01

    The aim of this study was to develop an experimental set-up and a methodology to uniformly contaminate several filter samples with high concentrations of cultivable bacteria and fungi. An experimental set-up allows contaminating simultaneously up to four filters for range of velocities representative of heating, ventilating and air-conditioning systems. The test aerosol was composed of a microbial consortium of one bacterium (Staphylococcus epidermidis) and one fungus (Penicillium oxalicum) and aerosol generation was performed in wet conditions. Firstly, the experimental set-up was validated in regards to homogeneity of the air flows. The bioaerosol was also characterized in terms of number and particle size distribution using two particle counters: optical particle counter Grimm 1.109 (optical diameters) and TSI APS 3321 (aerodynamic diameters). Moreover, stabilities of the number of particles generated were measured. Finally, concentrations of cultivable microorganisms were measured with BioSamplers (SKC) downstream of the four filters. PMID:23837350

  7. Association of ventilation with health and other responses in commercial and institutional buildings

    SciTech Connect

    Seppanen, Olli; Fisk, William J.; Mendell, Mark J.

    2000-08-01

    The paper presents a summary of a review [1] of current literature on the associations of ventilation rates in non-residential and non-industrial buildings (primarily offices) with health and other human outcomes. Twenty studies, with close to 30,000 subjects, investigated the association of ventilation rates with human responses. (Twenty one studies investigating the association of carbon dioxide with human responses, although included in the previous review, are not summarized here.) Almost all studies including ventilation rates below 10 Ls{sup -1} per person found these ventilation rates to be associated in all building types with statistically significant worsening in one or more health or perceived air quality outcomes. Some studies comparing only ventilation rates above 10 Ls{sup -1} per person determined that increases in ventilation rate above 10 Ls{sup -1} per person, up to approximately 20 Ls{sup -1} per person, were associated with further significant decreases in the prevalence of SBS symptoms or with further significant improvements in perceived air quality. The studies reported relative risks of 1.5-2 for respiratory illnesses and 1.1-6 for sick building syndrome symptoms for low compared to high ventilation rates.

  8. Ventilation of carbon monoxide from a biomass pellet storage tank--a study of the effects of variation of temperature and cross-ventilation on the efficiency of natural ventilation.

    PubMed

    Emhofer, Waltraud; Lichtenegger, Klaus; Haslinger, Walter; Hofbauer, Hermann; Schmutzer-Roseneder, Irene; Aigenbauer, Stefan; Lienhard, Martin

    2015-01-01

    Wood pellets have been reported to emit toxic gaseous emissions during transport and storage. Carbon monoxide (CO) emission, due to the high toxicity of the gas and the possibility of it being present at high levels, is the most imminent threat to be considered before entering a pellet storage facility. For small-scale (<30 tons storage capacity) residential pellet storage facilities, ventilation, preferably natural ventilation utilizing already existing openings, has become the most favored solution to overcome the problem of high CO concentrations. However, there is little knowledge on the ventilation rates that can be reached and thus on the effectiveness of such measures. The aim of the study was to investigate ventilation rates for a specific small-scale pellet storage system depending on characteristic temperature differences. Furthermore, the influence of the implementation of a chimney and the influence of cross-ventilation on the ventilation rates were investigated. The air exchange rates observed in the experiments ranged between close to zero and up to 8 m(3) h(-1), depending largely on the existing temperature differences and the existence of cross-ventilation. The results demonstrate that implementing natural ventilation is a possible measure to enhance safety from CO emissions, but not one without limitations.

  9. Lung Ventilation/Perfusion Scan

    MedlinePlus

    ... from the NHLBI on Twitter. What Is a Lung Ventilation/Perfusion Scan? A lung ventilation/perfusion scan, or VQ scan, is a ... that measures air and blood flow in your lungs. A VQ scan most often is used to ...

  10. [New potentials for monitoring the temperature and the relative and absolute humidity of the air-oxygen mixture during the prolonged artificial ventilation of newborn infants].

    PubMed

    Milenin, O B; Efimov, M S

    1998-01-01

    A new HTM-902 monitor (UCCP, Germany/Serviceinstrument, Russia) was used for continuous measurements of the temperature and relative and absolute humidity of inspired gas during prolonged mechanical ventilation in 86 neonates with respiratory failure caused by the respiratory distress syndrome (n = 42), meconium aspiration syndrome (n = 28), and congenital pneumonia (n = 16). All measurements were performed with a special probe connected to the inspiratory contour through a standard adapter close to the patient's T-piece. The monitor helped maintain the optimal values of the inspired gas conditioning during assisted ventilation of the neonates. The optimal relationships between gas temperature and humidity can be attained only with humidifiers with a servocontrol of temperature and heated wire inside the inspiratory circle tube. For maintaining adequate humidity of inspired gas after any changes in the ventilator flow rate or in the temperature inside the incubator, the heating power of the humidifier had to be corrected. However, even with servocontrolled humidifiers and humidity regulation, an increase of temperature inside the incubator over 35 degrees C made impossible the maintenance of the inspired gas humidity at the level of 96-100% with its temperature at the level of the patient's T-piece no higher than 37 degrees C.

  11. Comparison of deliverable and exhaustible pressurized air flow rates in laboratory gloveboxes

    SciTech Connect

    Compton, J.A.

    1994-10-01

    Calculations were performed to estimate the maximum credible flow rates of pressurized air into Plutonium Process Support Laboratories gloveboxes. Classical equations for compressible fluids were used to estimate the flow rates. The calculated maxima were compared to another`s estimates of glovebox exhaust flow rates and corresponding glovebox internal pressures. No credible pressurized air flow rate will pressurize a glovebox beyond normal operating limits. Unrestricted use of the pressurized air supply is recommended.

  12. Heart rate variability and stroke volume variability to detect central hypovolemia during spontaneous breathing and supported ventilation in young, healthy volunteers.

    PubMed

    Elstad, Maja; Walløe, Lars

    2015-04-01

    Cardiovascular oscillations exist in many different variables and may give important diagnostic and prognostic information in patients. Variability in cardiac stroke volume (SVV) is used in clinical practice for diagnosis of hypovolemia, but currently is limited to patients on mechanical ventilation. We investigated if SVV and heart rate variability (HRV) could detect central hypovolemia in spontaneously breathing humans: We also compared cardiovascular variability during spontaneous breathing with supported mechanical ventilation.Ten subjects underwent simulated central hypovolemia by lower body negative pressure (LBNP) with >10% reduction of cardiac stroke volume. The subjects breathed spontaneously and with supported mechanical ventilation. Heart rate, respiratory frequency and mean arterial blood pressure were measured. Stroke volume (SV) was estimated by ModelFlow (Finometer). Respiratory SVV was calculated by: 1) SVV% = (SVmax - SVmin)/SVmean during one respiratory cycle, 2) SVIntegral from the power spectra (Fourier transform) at 0.15-0.4 Hz and 3) SVV_norm = (√SVIntegral)/SVmean. HRV was calculated by the same methods.During spontaneous breathing two measures of SVV and all three measures of HRV were reduced during hypovolemia compared to baseline. During spontaneous breathing SVIntegral and HRV% were best to detect hypovolemia (area under receiver operating curve 0.81). HRV% ≤ 11% and SVIntegral ≤ 12 ml(2) differentiated between hypovolemia and baseline during spontaneous breathing.During supported mechanical ventilation, none of the three measures of SVV changed and two of the HRV measures were reduced during hypovolemia. Neither measures of SVV nor HRV were classified as a good detector of hypovolemia.We conclude that HRV% and SVIntegral detect hypovolemia during spontaneous breathing and both are candidates for further clinical testing. PMID:25799094

  13. Technology Solutions Case Study: Selecting Ventilation Systems for Existing Homes

    SciTech Connect

    2014-12-01

    In multifamily buildings, particularly in the Northeast, exhaust ventilation strategies are the norm as a means of meeting both local exhaust and whole-unit mechanical ventilation rates. The issue of where the "fresh" air is coming from is gaining significance as air-tightness standards for enclosures become more stringent, and the normal leakage paths through the building envelope disappear. Researchers from the Consortium for Advanced Residential Buildings (CARB) found that the majority of high performance, new construction, multifamily housing in the Northeast use one of four general strategies for ventilation: continuous exhaust only with no designated supply or make-up air source, continuous exhaust with ducted make-up air to apartments, continuous exhaust with supply through a make-up air device integral to the unit HVAC, and continuous exhaust with supply through a passive inlet device, such as a trickle vent. Insufficient information is available to designers on how these various systems are best applied. In this project, the CARB team evaluated the four different strategies for providing make-up air to multifamily residential buildings and developed guidelines to help contractors and building owners choose the best ventilation systems.

  14. Quantitative stove use and ventilation guidance for behavior change strategies.

    PubMed

    Johnson, Michael A; Chiang, Ranyee A

    2015-01-01

    Achieving World Health Organization air quality targets and aspirational fuel savings targets through clean cooking solutions will require high usage rates of high-performing products and low usage rates of traditional stoves. Catalyzing this shift is challenging as fuel and stove use practices associated with new technologies generally differ from those used with traditional technologies. Accompanying this shift with ventilation improvements can help further reduce exposure to emissions of health damaging pollutants. Behavior change strategies will be central to these efforts to move users to new technologies and minimize exposure to emissions. In this article, the authors show how behavior change can be linked to quantitative guidance on stove usage, household ventilation rates, and performance. The guidance provided here can help behavior change efforts in the household energy sector set and achieve quantitative goals for usage and ventilation rates. PMID:25839198

  15. Quantitative stove use and ventilation guidance for behavior change strategies.

    PubMed

    Johnson, Michael A; Chiang, Ranyee A

    2015-01-01

    Achieving World Health Organization air quality targets and aspirational fuel savings targets through clean cooking solutions will require high usage rates of high-performing products and low usage rates of traditional stoves. Catalyzing this shift is challenging as fuel and stove use practices associated with new technologies generally differ from those used with traditional technologies. Accompanying this shift with ventilation improvements can help further reduce exposure to emissions of health damaging pollutants. Behavior change strategies will be central to these efforts to move users to new technologies and minimize exposure to emissions. In this article, the authors show how behavior change can be linked to quantitative guidance on stove usage, household ventilation rates, and performance. The guidance provided here can help behavior change efforts in the household energy sector set and achieve quantitative goals for usage and ventilation rates.

  16. Evaluation of building ventilation systems

    SciTech Connect

    Hughes, R.T.; O'Brien, D.M.

    1986-04-01

    Over the past several years, NIOSH has responded to health hazard evaluation requests from workers in dozens of office environments. Typically, the employees have complained of headache, eye and upper respiratory tract irritation, dizziness, lethargy and the inability to concentrate. Most often inadequate ventilation has been blamed for these complaints. Of paramount importance in the evaluation and correction of these problems is an effective evaluation of the building's ventilation system. Heating, ventilating and air-conditioning conditions that can cause worker stresses include: migration of odors or chemical hazards between building areas; reentrainment of exhaust from building fume hoods or through heat wheels; buildup of microorganisms in the HVAC system components; and poor odor or environmental control due to insufficient fresh outdoor air or system heating or cooling malfunction. The purpose of this paper is to provide an overview of building ventilation systems, the ventilation problems associated with poorly designed or operating systems, and the methodology for effectively evaluating system performance.

  17. Peer Ratings: Scoring Strategy Development and Reliability Demonstration on Air Force Basic Trainees. Final Report.

    ERIC Educational Resources Information Center

    Borman, Walter C.; Rosse, Rodney L.

    As an alternative for or adjunct to paper-and-pencil tests for predicting personnel performance, the United States Air Force studied the use of peer ratings as an evaluative tool. Purpose of this study was to evaluate the psychometric characteristics of peer ratings among Air Force basic trainees. Peer ratings were obtained from more than 27,000…

  18. Re-inspiration of CO2 from ventilator circuit: effects of circuit flushing and aspiration of dead space up to high respiratory rate

    PubMed Central

    2010-01-01

    Introduction Dead space negatively influences carbon dioxide (CO2) elimination, particularly at high respiratory rates (RR) used at low tidal volume ventilation in acute respiratory distress syndrome (ARDS). Aspiration of dead space (ASPIDS), a known method for dead space reduction, comprises two mechanisms activated during late expiration: aspiration of gas from the tip of the tracheal tube and gas injection through the inspiratory line - circuit flushing. The objective was to study the efficiency of circuit flushing alone and of ASPIDS at wide combinations of RR and tidal volume (VT) in anaesthetized pigs. The hypothesis was tested that circuit flushing and ASPIDS are particularly efficient at high RR. Methods In Part 1 of the study, RR and VT were, with a computer-controlled ventilator, modified for one breath at a time without changing minute ventilation. Proximal dead space in a y-piece and ventilator tubing (VDaw, prox) was measured. In part two, changes in CO2 partial pressure (PaCO2) during prolonged periods of circuit flushing and ASPIDS were studied at RR 20, 40 and 60 minutes-1. Results In Part 1, VDaw, prox was 7.6 ± 0.5% of VT at RR 10 minutes-1 and 16 ± 2.5% at RR 60 minutes-1. In Part 2, circuit flushing reduced PaCO2 by 20% at RR 40 minutes-1 and by 26% at RR 60 minutes-1. ASPIDS reduced PaCO2 by 33% at RR 40 minutes-1 and by 41% at RR 60 minutes-1. Conclusions At high RR, re-breathing of CO2 from the y-piece and tubing becomes important. Circuit flushing and ASPIDS, which significantly reduce tubing dead space and PaCO2, merit further clinical studies. PMID:20420671

  19. Occupant Interactions and Effectiveness of Natural Ventilation Strategies in Contemporary New Housing in Scotland, UK

    PubMed Central

    Sharpe, Tim; Farren, Paul; Howieson, Stirling; Tuohy, Paul; McQuillan, Jonathan

    2015-01-01

    The need to reduce carbon emissions and fuel poverty has led to increased building envelope air tightness, intended to reduce uncontrolled ventilation heat losses. Ventilation strategies in dwellings still allow the use of trickle ventilators in window frames for background ventilation. The extent to which this results in “healthy” Indoor Air Quality (IAQ) in recently constructed dwellings was a concern of regulators in Scotland. This paper describes research to explore this. First a review of literature was conducted, then data on occupant interactions with ventilation provisions (windows, doors, trickle vents) gathered through an interview-based survey of 200 recently constructed dwellings, and measurements made on a sample of 40 of these. The main measured parameter discussed here is CO2 concentration. It was concluded after the literature review that 1000 ppm absolute was a reasonable threshold to use for “adequate” ventilation. The occupant survey found that there was very little occupant interaction with the trickle ventilators e.g., in bedrooms 63% were always closed, 28% always open, and in only 9% of cases occupants intervened to make occasional adjustments. In the measured dwellings average bedroom CO2 levels of 1520 ppm during occupied (night time) hours were observed. Where windows were open the average bedroom CO2 levels were 972 ppm. With windows closed, the combination of “trickle ventilators open plus doors open” gave an average of 1021 ppm. “Trickle ventilators open” gave an average of 1571 ppm. All other combinations gave averages of 1550 to 2000 ppm. Ventilation rates and air change rates were estimated from measured CO2 levels, for all dwellings calculated ventilation rate was less than 8 L/s/p, in 42% of cases calculated air change rate was less than 0.5 ach. It was concluded that trickle ventilation as installed and used is ineffective in meeting desired ventilation rates, evidenced by high CO2 levels reported across the

  20. Impact of Residential Mechanical Ventilation on Energy Cost and Humidity Control

    SciTech Connect

    Martin, E.

    2014-01-01

    The DOE Building America program has been conducting research leading to cost effective high performance homes since the early 1990's. Optimizing whole house mechanical ventilation as part of the program's systems engineered approach to constructing housing has been an important subject of the program's research. Ventilation in residential buildings is one component of an effective, comprehensive strategy for creation and maintenance of a comfortable and healthy indoor air environment. The study described in this white paper is based on building energy modeling with an important focus on the indoor humidity impacts of ventilation. The modeling tools used were EnergyPlus version 7.1 (E+) and EnergyGauge USA (EGUSA). Twelve U.S. cities and five climate zones were represented. A total of 864 simulations (2*2*3*3*12= 864) were run using two building archetypes, two building leakage rates, two building orientations, three ventilation systems, three ventilation rates, and twelve climates.

  1. Impact of Residential Mechanical Ventilation on Energy Cost and Humidity Control

    SciTech Connect

    Martin, Eric

    2014-01-01

    Optimizing whole house mechanical ventilation as part of the Building Ameerica program's systems engineered approach to constructing housing has been an important subject of the program's research. Ventilation in residential buildings is one component of an effective, comprehensive strategy for creation and maintenance of a comfortable and healthy indoor air environment. The study described in this report is based on building energy modeling with an important focus on the indoor humidity impacts of ventilation. The modeling tools used were EnergyPlus version 7.1 (E+) and EnergyGauge USA (EGUSA). Twelve U.S. cities and five climate zones were represented. A total of 864 simulations (2*2*3*3*12= 864) were run using two building archetypes, two building leakage rates, two building orientations, three ventilation systems, three ventilation rates, and twelve climates.

  2. Indoor air quality: recommendations relevant to aircraft passenger cabins.

    PubMed

    Hocking, M B

    1998-07-01

    To evaluate the human component of aircraft cabin air quality the effects of respiration of a resting adult on air quality in an enclosed space are estimated using standard equations. Results are illustrated for different air volumes per person, with zero air exchange, and with various air change rates. Calculated ventilation rates required to achieve a specified air quality for a wide range of conditions based on theory agree to within 2% of the requirements determined using a standard empirical formula. These calculations quantitatively confirm that the air changes per hour per person necessary for ventilation of an enclosed space vary inversely with the volume of the enclosed space. However, they also establish that the ventilation required to achieve a target carbon dioxide concentration in the air of an enclosed space with a resting adult remains the same regardless of the volume of the enclosed space. Concentration equilibria resulting from the interaction of the respiration of a resting adult with various ventilation conditions are compared with the rated air exchange rates of samples of current passenger aircraft, both with and without air recirculation capability. Aircraft cabin carbon dioxide concentrations calculated from the published ventilation ratings are found to be intermediate to these sets of results obtained by actual measurement. These findings are used to arrive at recommendations for aircraft builders and operators to help improve aircraft cabin air quality at minimum cost. Passenger responses are suggested to help improve their comfort and decrease their exposure to disease transmission, particularly on long flights.

  3. Ventilation Model

    SciTech Connect

    H. Yang

    1999-11-04

    The purpose of this analysis and model report (AMR) for the Ventilation Model is to analyze the effects of pre-closure continuous ventilation in the Engineered Barrier System (EBS) emplacement drifts and provide heat removal data to support EBS design. It will also provide input data (initial conditions, and time varying boundary conditions) for the EBS post-closure performance assessment and the EBS Water Distribution and Removal Process Model. The objective of the analysis is to develop, describe, and apply calculation methods and models that can be used to predict thermal conditions within emplacement drifts under forced ventilation during the pre-closure period. The scope of this analysis includes: (1) Provide a general description of effects and heat transfer process of emplacement drift ventilation. (2) Develop a modeling approach to simulate the impacts of pre-closure ventilation on the thermal conditions in emplacement drifts. (3) Identify and document inputs to be used for modeling emplacement ventilation. (4) Perform calculations of temperatures and heat removal in the emplacement drift. (5) Address general considerations of the effect of water/moisture removal by ventilation on the repository thermal conditions. The numerical modeling in this document will be limited to heat-only modeling and calculations. Only a preliminary assessment of the heat/moisture ventilation effects and modeling method will be performed in this revision. Modeling of moisture effects on heat removal and emplacement drift temperature may be performed in the future.

  4. Estimation of time-varying pollutant emission rates in a ventilated enclosure: inversion of a reduced model obtained by experimental application of the modal identification method

    NASA Astrophysics Data System (ADS)

    Girault, M.; Maillet, D.; Bonthoux, F.; Galland, B.; Martin, P.; Braconnier, R.; Fontaine, J. R.

    2008-02-01

    A method is proposed for the estimation of time-varying emission rates of pollutant sources in a ventilated enclosure, through the resolution of an inverse forced convection problem. Unsteady transport-diffusion of the pollutant is considered, with the assumption of a stationary velocity field remaining unchanged during emission (passive contaminant). The pollutant transport equation is therefore linear with respect to concentration. The source's location is also supposed to be known. As the first step, a reduced model (RM) linking concentrations at a set of control points to emission rates of sources is identified from experimental data by using the modal identification method (MIM). This parameter estimation problem uses transient contaminant concentration measurements made at control points inside the ventilated enclosure, corresponding to increasing and decreasing steps of emission rates. Such experimental modelling allows us to avoid dealing with a CFD code involving turbulence modelling and to get rid of uncertainties about sensors position. In a second step, the identified RM is used to solve an inverse forced convection problem: from contaminant concentration measured at the same control points, rates of sources emitting simultaneously are estimated with a sequential in time algorithm using future time steps.

  5. Effect of wind tunnel air velocity on VOC flux rates from CAFO manure and wastewater

    Technology Transfer Automated Retrieval System (TEKTRAN)

    Wind tunnels and flux chambers are often used to estimate volatile organic compound (VOC) emissions from animal feeding operations (AFOs) without regard to air velocity or sweep air flow rates. Laboratory experiments were conducted to evaluate the effect of wind tunnel air velocity on VOC emission ...

  6. Measurement of air temperature in the presence of a large radiant flux: an assessment of passively ventilated thermometer screens

    NASA Astrophysics Data System (ADS)

    Erell, Evyatar; Leal, Vítor; Maldonado, Eduardo

    The energy balance of small temperature sensors was modelled to illustrate the effects of sensor characteristics, particularly size, on the accuracy of readings in the presence of strong shortwave or longwave radiant loads. For all but extremely small sensors, radiant exchange may lead to unacceptable errors. The common practice of using passively ventilated instrument screens was evaluated in a series of comparative measurements. The differences resulting from the use of different models of shields may be an order of magnitude greater than the error resulting from sensor calibration. In the absence of technological innovation capable of reducing the error due to radiant exchange to negligible proportions, it is suggested that a standard methodology for calibrating and labelling the error resulting from the characteristics of the screens be adopted, to allow comparison of new data with long-established records.

  7. Evaluation of Ventilation Strategies in New Construction Multifamily Buildings

    SciTech Connect

    Maxwell, S.; Berger, D.; Zuluaga, M.

    2014-07-01

    In multifamily buildings, particularly in the Northeast, exhaust ventilation strategies are the norm as a means of meeting both local exhaust and whole-unit mechanical ventilation rates. The issue of where the "fresh" air is coming from is gaining significance as air-tightness standards for enclosures become more stringent. CARB researchers have found that most new high performance, multifamily housing in the Northeast use one of four strategies for ventilation: continuous exhaust only with no designated supply or make-up air source, continuous exhaust with ducted make-up air to apartments, continuous exhaust with supply through a make-up air device integral to the unit HVAC, and continuous exhaust with supply through a passive inlet device, such as a trickle vent. Insufficient information is available to designers on how these various systems are best applied. Product performance data are based on laboratory tests, but there is no guarantee that those conditions will exist consistently in the finished building. In this research project, CARB evaluated the four ventilation strategies in the field to validate system performance.

  8. International Space Station Crew Quarters Ventilation and Acoustic Design Implementation

    NASA Technical Reports Server (NTRS)

    Broyan, James L., Jr.; Cady, Scott M; Welsh, David A.

    2010-01-01

    The International Space Station (ISS) United States Operational Segment has four permanent rack sized ISS Crew Quarters (CQs) providing a private crew member space. The CQs use Node 2 cabin air for ventilation/thermal cooling, as opposed to conditioned ducted air-from the ISS Common Cabin Air Assembly (CCAA) or the ISS fluid cooling loop. Consequently, CQ can only increase the air flow rate to reduce the temperature delta between the cabin and the CQ interior. However, increasing airflow causes increased acoustic noise so efficient airflow distribution is an important design parameter. The CQ utilized a two fan push-pull configuration to ensure fresh air at the crew member's head position and reduce acoustic exposure. The CQ ventilation ducts are conduits to the louder Node 2 cabin aisle way which required significant acoustic mitigation controls. The CQ interior needs to be below noise criteria curve 40 (NC-40). The design implementation of the CQ ventilation system and acoustic mitigation are very inter-related and require consideration of crew comfort balanced with use of interior habitable volume, accommodation of fan failures, and possible crew uses that impact ventilation and acoustic performance. Each CQ required 13% of its total volume and approximately 6% of its total mass to reduce acoustic noise. This paper illustrates the types of model analysis, assumptions, vehicle interactions, and trade-offs required for CQ ventilation and acoustics. Additionally, on-orbit ventilation system performance and initial crew feedback is presented. This approach is applicable to any private enclosed space that the crew will occupy.

  9. Litter ammonia losses amplified by higher air flow rates

    Technology Transfer Automated Retrieval System (TEKTRAN)

    ABSTRACT Broiler litter utilization has largely been associated with land application as fertilizer. Reducing ammonia (NH3) released from litter enhances its fertilizer value and negates detrimental impacts to the environment. A laboratory study was conducted to quantify the effect of air flow var...

  10. Fuselage ventilation due to wind flow about a postcrash aircraft

    NASA Technical Reports Server (NTRS)

    Stuart, J. W.

    1980-01-01

    Postcrash aircraft fuselage fire development, dependent on the internal and external fluid dynamics is discussed. The natural ventilation rate, a major factor in the internal flow patterns and fire development is reviewed. The flow about the fuselage as affected by the wind and external fire is studied. An analysis was performend which estimated the rates of ventilation produced by the wind for a limited idealized environmental configuration. The simulation utilizes the empirical pressure coefficient distribution of an infinite circular cylinder near a wall with its boundary later flow to represent the atmospheric boundary layer. The resulting maximum ventilation rate for two door size openings, with varying circumferential location in a common 10 mph wind was an order of magnitude greater than the forced ventilation specified in full scale fire testing. The parameter discussed are: (1) fuselage size and shape, (2) fuselage orientation and proximity to the ground, (3) fuselage-openings size and location, (4) wind speed and direction, and (5) induced flow of the external fire plume is recommended. The fire testing should be conducted to a maximum ventilation rate at least an order of magnitude greater than the inflight air conditioning rates.

  11. Transient secondary organic aerosol formation from limonene ozonolysis in indoor environments: impacts of air exchange rates and initial concentration ratios.

    PubMed

    Youssefi, Somayeh; Waring, Michael S

    2014-07-15

    Secondary organic aerosol (SOA) results from the oxidation of reactive organic gases (ROGs) and is an indoor particle source. The aerosol mass fraction (AMF), a.k.a. SOA yield, quantifies the SOA forming potential of ROGs and is the ratio of generated SOA to oxidized ROG. The AMF depends on the organic aerosol concentration, as well as the prevalence of later generation reactions. AMFs have been measured in unventilated chambers or steady-state flow through chambers. However, indoor settings have outdoor air exchange, and indoor SOA formation often occurs when ROGs are transiently emitted, for instance from emissions of cleaning products. Herein, we quantify "transient AMFs" from ozonolysis of pulse-emitted limonene in a ventilated chamber, for 18 experiments at low (0.28 h(-1)), moderate (0.53 h(-1)), and high (0.96 h(-1)) air exchange rates (AER) with varying initial ozone-limonene ratios. Transient AMFs increased with the amount of ROG reacted; AMFs also increased with decreasing AERs and increasing initial ozone-limonene ratios, which together likely promoted more ozone reactions with the remaining exocyclic bond of oxidized limonene products in the SOA phase. Knowing the AER and initial ozone-limonene ratio is crucial to predict indoor transient SOA behavior accurately.

  12. Spatiotemporally‐Resolved Air Exchange Rate as a Modifier of Acute Air Pollution‐Related Morbidity in AtlantaMorbidity in Atlanta

    EPA Science Inventory

    Epidemiological studies frequently use central site concentrations as surrogates of exposure to air pollutants. Variability in air pollutant infiltration due to differential air exchange rates (AERs) is potentially a major factor affecting the relationship between central site c...

  13. Subsurface Ventilation System Description Document

    SciTech Connect

    2000-10-12

    The Subsurface Ventilation System supports the construction and operation of the subsurface repository by providing air for personnel and equipment and temperature control for the underground areas. Although the system is located underground, some equipment and features may be housed or located above ground. The system ventilates the underground by providing ambient air from the surface throughout the subsurface development and emplacement areas. The system provides fresh air for a safe work environment and supports potential retrieval operations by ventilating and cooling emplacement drifts. The system maintains compliance within the limits established for approved air quality standards. The system maintains separate ventilation between the development and waste emplacement areas. The system shall remove a portion of the heat generated by the waste packages during preclosure to support thermal goals. The system provides temperature control by reducing drift temperature to support potential retrieval operations. The ventilation system has the capability to ventilate selected drifts during emplacement and retrieval operations. The Subsurface Facility System is the main interface with the Subsurface Ventilation System. The location of the ducting, seals, filters, fans, emplacement doors, regulators, and electronic controls are within the envelope created by the Ground Control System in the Subsurface Facility System. The Subsurface Ventilation System also interfaces with the Subsurface Electrical System for power, the Monitored Geologic Repository Operations Monitoring and Control System to ensure proper and safe operation, the Safeguards and Security System for access to the emplacement drifts, the Subsurface Fire Protection System for fire safety, the Emplacement Drift System for repository performance, and the Backfill Emplacement and Subsurface Excavation Systems to support ventilation needs.

  14. Subsurface Ventilation System Description Document

    SciTech Connect

    Eric Loros

    2001-07-25

    The Subsurface Ventilation System supports the construction and operation of the subsurface repository by providing air for personnel and equipment and temperature control for the underground areas. Although the system is located underground, some equipment and features may be housed or located above ground. The system ventilates the underground by providing ambient air from the surface throughout the subsurface development and emplacement areas. The system provides fresh air for a safe work environment and supports potential retrieval operations by ventilating and cooling emplacement drifts. The system maintains compliance within the limits established for approved air quality standards. The system maintains separate ventilation between the development and waste emplacement areas. The system shall remove a portion of the heat generated by the waste packages during preclosure to support thermal goals. The system provides temperature control by reducing drift temperature to support potential retrieval operations. The ventilation system has the capability to ventilate selected drifts during emplacement and retrieval operations. The Subsurface Facility System is the main interface with the Subsurface Ventilation System. The location of the ducting, seals, filters, fans, emplacement doors, regulators, and electronic controls are within the envelope created by the Ground Control System in the Subsurface Facility System. The Subsurface Ventilation System also interfaces with the Subsurface Electrical System for power, the Monitored Geologic Repository Operations Monitoring and Control System to ensure proper and safe operation, the Safeguards and Security System for access to the emplacement drifts, the Subsurface Fire Protection System for fire safety, the Emplacement Drift System for repository performance, and the Backfill Emplacement and Subsurface Excavation Systems to support ventilation needs.

  15. Ventilation rates of the waters in the Nansen Basin of the Arctic Ocean derived from a multitracer approach

    SciTech Connect

    Schlosser, P.; Boenisch, G.; Kromer, B.; Muennich, K.O. )

    1990-03-15

    Tritium/{sup 3}He-, {sup 14}C- and helium/neon data from a station located in the central Nansen Basin of the Arctic Ocean are reported and discussed. It is demonstrated that {sup 3}He is a valuable tracer for studies of the upper water column and, together with tritium, {sup 3}He provides a rough time scale of the ventilation of these waters. The apparent tritium/{sup 3}He age is about 7 years in the surface water and about 14 years in the lower part of the halocline. Water of Atlantic origin defined by a temperature maximum shows tritium/{sup 3}He ages between 7 and 9 years. This variation of ages indicates that the circulation of the individual water layers of the upper water column is largely decoupled and occurs on different time scales. Tritium/{sup 3}He ages observed in the Arctic Intermediate Water suggest a ventilation on a time scale of 15 to 20 years (depth < 1,000 m). The mean age of the Eurasian Basin Bottom Water is estimated on the basis of {sup 14}C data to approximately 200 to 250 years. There is no indication of noble gas fractionation due to sea ice formation below the surface layer. From analysis of the {sup 3}He background it appears that there is a small primordial {sup 3}He component in Eurasian Basin Bottom Water.

  16. Demonstration of split-flow ventilation and recirculation as flow-reduction methods in an Air Force paint spray booth. Final report, 15 February 1991-9 October 1992

    SciTech Connect

    Hughes, S.; Ayer, J.; Sutay, R.

    1994-07-27

    During a series of painting operations in a horizontal-flow paint spray booth at Travis AFB, CA, baseline concentrations of four classes of toxic airborne pollutants were measured at 24 locations across a plane immediately forward of the exhaust filters, in the exhaust duct, and inside and outside the respirator in the painter`s breathing zone (BZ). The resulting data were analyzed and used to design a modified ventilation system that (1) separates a portion of the exhaust exiting the lower portion of the booth, which contains a concentration of toxic pollutants greater than the average at the exhaust plane (split-flow); and (2) provides an option to return the flow from the upper portion of the exhaust to the intake plenum for mixing with fresh air and recirculation through the booth (recirculation). After critical review by cognizant Air Force offices and an experimental demonstration showing that a flame ionization detector monitoring the air entering the booth is able to detect excursions above the equivalent exposure limit for the solvents in the paint, the exhaust duct was reconfigured for split-flow and recirculating ventilation. A volunteer painter was briefed on the increased risk of exposure during recirculation, and on the purposes and possible benefits of this study. He then signed an informed consent form before participating in the recirculation tests. A series of tests generally equivalent to the baseline series was conducted during split-flow and recirculating ventilation, and three tests were performed during only split-flow ventilation.

  17. 14 CFR 23.831 - Ventilation.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... STANDARDS: NORMAL, UTILITY, ACROBATIC, AND COMMUTER CATEGORY AIRPLANES Design and Construction Personnel and... ventilation system must also provide a sufficient amount of uncontaminated air to enable the flight crew... ventilation system must be designed to provide each occupant with at least 0.55 pounds of fresh air per...

  18. A compartment model of alveolar-capillary oxygen diffusion with ventilation-perfusion gradient and dynamics of air transport through the respiratory tract.

    PubMed

    Jaworski, Jacek; Redlarski, Grzegorz

    2014-08-01

    This paper presents a model of alveolar-capillary oxygen diffusion with dynamics of air transport through the respiratory tract. For this purpose electrical model representing the respiratory tract mechanics and differential equations representing oxygen membrane diffusion are combined. Relevant thermodynamic relations describing the mass of oxygen transported into the human body are proposed as the connection between these models, as well as the influence of ventilation-perfusion mismatch on the oxygen diffusion. The model is verified based on simulation results of varying exercise intensities and statistical calculations of the results obtained during various clinical trials. The benefit of the approach proposed is its application in simulation-based research aimed to generate quantitative data of normal and pathological conditions. Based on the model presented, taking into account many essential physiological processes and air transport dynamics, comprehensive and combined studies of the respiratory efficiency can be performed. The impact of physical exercise, precise changes in respiratory tract mechanics and alterations in breathing pattern can be analyzed together with the impact of various changes in alveolar-capillary oxygen diffusion. This may be useful in simulation of effects of many severe medical conditions and increased activity level.

  19. A practical approach to estimate emission rates of indoor air pollutants due to the use of personal combustible products based on small-chamber studies.

    PubMed

    Szulejko, Jan E; Kim, Ki-Hyun

    2016-02-01

    As emission rates of airborne pollutants are commonly measured from combusting substances placed inside small chambers, those values need to be re-evaluated for the possible significance under practical conditions. Here, a simple numerical procedure is investigated to extrapolate the chamber-based emission rates of formaldehyde that can be released from various combustible sources including e-cigarettes, conventional cigarettes, or scented candles to their concentration levels in a small room with relatively poor ventilation. This simple procedure relies on a mass balance approach by considering the masses of pollutants emitted from source and lost through ventilation under the assumption that mixing occurs instantaneously in the room without chemical reactions or surface sorption. The results of our study provide valuable insights into re-evaluation procedure of chamber data to allow comparison between extrapolated and recommended values to judge the safe use of various combustible products in confined spaces. If two scented candles with a formaldehyde emission rate of 310 µg h(-1) each were lit for 4 h in a small 20 m(3) room with an air change rate of 0.5 h(-1), then the 4-h (candle lit) and 8-h (up to 8 h after candle lighting) TWA [FA] were determined to be 28.5 and 23.5 ppb, respectively. This is clearly above the 8-h NIOSH recommended exposure limit (REL) time weighted average of 16 ppb.

  20. A practical approach to estimate emission rates of indoor air pollutants due to the use of personal combustible products based on small-chamber studies.

    PubMed

    Szulejko, Jan E; Kim, Ki-Hyun

    2016-02-01

    As emission rates of airborne pollutants are commonly measured from combusting substances placed inside small chambers, those values need to be re-evaluated for the possible significance under practical conditions. Here, a simple numerical procedure is investigated to extrapolate the chamber-based emission rates of formaldehyde that can be released from various combustible sources including e-cigarettes, conventional cigarettes, or scented candles to their concentration levels in a small room with relatively poor ventilation. This simple procedure relies on a mass balance approach by considering the masses of pollutants emitted from source and lost through ventilation under the assumption that mixing occurs instantaneously in the room without chemical reactions or surface sorption. The results of our study provide valuable insights into re-evaluation procedure of chamber data to allow comparison between extrapolated and recommended values to judge the safe use of various combustible products in confined spaces. If two scented candles with a formaldehyde emission rate of 310 µg h(-1) each were lit for 4 h in a small 20 m(3) room with an air change rate of 0.5 h(-1), then the 4-h (candle lit) and 8-h (up to 8 h after candle lighting) TWA [FA] were determined to be 28.5 and 23.5 ppb, respectively. This is clearly above the 8-h NIOSH recommended exposure limit (REL) time weighted average of 16 ppb. PMID:26495830

  1. Effect of air deflectors on fan performance in tunnel-ventilated broiler houses with a dropped ceiling

    Technology Transfer Automated Retrieval System (TEKTRAN)

    Air velocity is a critical design parameter for modern commercial broiler houses, owing to the beneficial effects of increased cooling on live performance and thermal comfort in broiler chickens. As a result, design velocities have increased over the last 15 years and broiler growers have installed ...

  2. International Space Station USOS Crew Quarters Ventilation and Acoustic Design Implementation

    NASA Technical Reports Server (NTRS)

    Broyan, James Lee, Jr.

    2009-01-01

    The International Space Station (ISS) United States Operational Segment (USOS) has four permanent rack sized ISS Crew Quarters (CQ) providing a private crewmember space. The CQ uses Node 2 cabin air for ventilation/thermal cooling, as opposed to conditioned ducted air from the ISS Temperature Humidity Control System or the ISS fluid cooling loop connections. Consequently, CQ can only increase the air flow rate to reduce the temperature delta between the cabin and the CQ interior. However, increasing airflow causes increased acoustic noise so efficient airflow distribution is an important design parameter. The CQ utilized a two fan push-pull configuration to ensure fresh air at the crewmember s head position and reduce acoustic exposure. The CQ interior needs to be below Noise Curve 40 (NC-40). The CQ ventilation ducts are open to the significantly louder Node 2 cabin aisle way which required significantly acoustic mitigation controls. The design implementation of the CQ ventilation system and acoustic mitigation are very inter-related and require consideration of crew comfort balanced with use of interior habitable volume, accommodation of fan failures, and possible crew uses that impact ventilation and acoustic performance. This paper illustrates the types of model analysis, assumptions, vehicle interactions, and trade-offs required for CQ ventilation and acoustics. Additionally, on-orbit ventilation system performance and initial crew feedback is presented. This approach is applicable to any private enclosed space that the crew will occupy.

  3. Solar chimney design: Investigating natural ventilation and cooling in offices with the aid of computer simulation

    NASA Astrophysics Data System (ADS)

    Angelis, Nikolaos

    Solar chimney design is investigated as a means of improving natural ventilation and passive cooling in office buildings. Existing scientific research and built precedents are generally limited literature review findings on various features of solar chimneys were categorised and used to develop a building simulation strategy. Using UK climatic data, simulations were performed on several computer models in order to investigate solar chimney performance during a single day period and an entire cooling season. Passive cooling with a solar chimney is possible but actual reduction in temperatures in most cases examined could be negligible. Cooling potential is increased on still, warm days, while the prospects for night cooling are further improved. A solar chimney may help reduce considerably the occurrence of resultant temperatures at or above the 25 C and 28 C thresholds. Solar chimney width, height, apertures and integral use of thermal mass are the most significant parameters for cooling. Simulation results showed that a solar chimney can increase significantly natural ventilation rates. Total ventilation rates may be increased by at least 22%. During still days a solar chimney can enhance ventilation rates by 36% or more. Stack ventilation through a solar chimney is typically 20% of cross ventilation during night time this may increase to at least 40-45% and on still days it may reach 100% of typical cross ventilation rates. Solar chimney induced stack ventilation and cross ventilation are interrelated. Resultant air flow patterns may have an important effect on convective heat transfers and thermal comfort. Climate and microclimate conditions should be an integral part of solar chimney design. Key aspects and recommendations regarding solar chimneys, passive cooling and natural ventilation are provided for design guidance and feedback in further research.

  4. Absorbed dose rate in air in metropolitan Tokyo before the Fukushima Daiichi Nuclear Power Plant accident.

    PubMed

    Inoue, K; Hosoda, M; Fukushi, M; Furukawa, M; Tokonami, S

    2015-11-01

    The monitoring of absorbed dose rate in air has been carried out continually at various locations in metropolitan Tokyo after the accident of the Fukushima Daiichi Nuclear Power Plant. While the data obtained before the accident are needed to more accurately assess the effects of radionuclide contamination from the accident, detailed data for metropolitan Tokyo obtained before the accident have not been reported. A car-borne survey of the absorbed dose rate in air in metropolitan Tokyo was carried out during August to September 2003. The average absorbed dose rate in air in metropolitan Tokyo was 49±6 nGy h(-1). The absorbed dose rate in air in western Tokyo was higher compared with that in central Tokyo. Here, if the absorbed dose rate indoors in Tokyo is equivalent to that outdoors, the annual effective dose would be calculated as 0.32 mSv y(-1).

  5. Absorbed dose rate in air in metropolitan Tokyo before the Fukushima Daiichi Nuclear Power Plant accident.

    PubMed

    Inoue, K; Hosoda, M; Fukushi, M; Furukawa, M; Tokonami, S

    2015-11-01

    The monitoring of absorbed dose rate in air has been carried out continually at various locations in metropolitan Tokyo after the accident of the Fukushima Daiichi Nuclear Power Plant. While the data obtained before the accident are needed to more accurately assess the effects of radionuclide contamination from the accident, detailed data for metropolitan Tokyo obtained before the accident have not been reported. A car-borne survey of the absorbed dose rate in air in metropolitan Tokyo was carried out during August to September 2003. The average absorbed dose rate in air in metropolitan Tokyo was 49±6 nGy h(-1). The absorbed dose rate in air in western Tokyo was higher compared with that in central Tokyo. Here, if the absorbed dose rate indoors in Tokyo is equivalent to that outdoors, the annual effective dose would be calculated as 0.32 mSv y(-1). PMID:25944962

  6. A Review of the Thermodynamic, Transport, and Chemical Reaction Rate Properties of High-temperature Air

    NASA Technical Reports Server (NTRS)

    Hansen, C Frederick; Heims, Steve P

    1958-01-01

    Thermodynamic and transport properties of high temperature air, and the reaction rates for the important chemical processes which occur in air, are reviewed. Semiempirical, analytic expressions are presented for thermodynamic and transport properties of air. Examples are given illustrating the use of these properties to evaluate (1) equilibrium conditions following shock waves, (2) stagnation region heat flux to a blunt high-speed body, and (3) some chemical relaxation lengths in stagnation region flow.

  7. Effect of air-flow rate and turning frequency on bio-drying of dewatered sludge.

    PubMed

    Zhao, Ling; Gu, Wei-Mei; He, Pin-Jing; Shao, Li-Ming

    2010-12-01

    Sludge bio-drying is an approach for biomass energy utilization, in which sludge is dried by means of the heat generated by aerobic degradation of its organic substances. The study aimed at investigating the interactive influence of air-flow rate and turning frequency on water removal and biomass energy utilization. Results showed that a higher air-flow rate (0.0909m(3)h(-1)kg(-1)) led to lower temperature than did the lower one (0.0455m(3)h(-1)kg(-1)) by 17.0% and 13.7% under turning per two days and four days. With the higher air-flow rate and lower turning frequency, temperature cumulation was almost similar to that with the lower air-flow rate and higher turning frequency. The doubled air-flow rate improved the total water removal ratio by 2.86% (19.5gkg(-1) initial water) and 11.5% (75.0gkg(-1) initial water) with turning per two days and four days respectively, indicating that there was no remarkable advantage for water removal with high air-flow rate, especially with high turning frequency. The heat used for evaporation was 60.6-72.6% of the total heat consumption (34,400-45,400kJ). The higher air-flow rate enhanced volatile solids (VS) degradation thus improving heat generation by 1.95% (800kJ) and 8.96% (3200kJ) with turning per two days and four days. With the higher air-flow rate, heat consumed by sensible heat of inlet air and heat utilization efficiency for evaporation was higher than the lower one. With the higher turning frequency, sensible heat of materials and heat consumed by turning was higher than lower one.

  8. Effect of Noninvasive Ventilation Delivered by Helmet vs Face Mask on the Rate of Endotracheal Intubation in Patients With Acute Respiratory Distress Syndrome

    PubMed Central

    Patel, Bhakti K.; Wolfe, Krysta S.; Pohlman, Anne S.; Hall, Jesse B.; Kress, John P.

    2016-01-01

    IMPORTANCE Noninvasive ventilation (NIV) with a face mask is relatively ineffective at preventing endotracheal intubation in patients with acute respiratory distress syndrome (ARDS). Delivery of NIV with a helmet may be a superior strategy for these patients. OBJECTIVE To determine whether NIV delivered by helmet improves intubation rate among patients with ARDS. DESIGN, SETTING, AND PARTICIPANTS Single-center randomized clinical trial of 83 patients with ARDS requiring NIV delivered by face mask for at least 8 hours while in the medical intensive care unit at the University of Chicago between October 3, 2012, through September 21, 2015. INTERVENTIONS Patients were randomly assigned to continue face mask NIV or switch to a helmet for NIV support for a planned enrollment of 206 patients (103 patients per group). The helmet is a transparent hood that covers the entire head of the patient and has a rubber collar neck seal. Early trial termination resulted in 44 patients randomized to the helmet group and 39 to the face mask group. MAIN OUTCOMES AND MEASURES The primary outcome was the proportion of patients who required endotracheal intubation. Secondary outcomes included 28-day invasive ventilator–free days (ie, days alive without mechanical ventilation), duration of ICU and hospital length of stay, and hospital and 90-day mortality. RESULTS Eighty-three patients (45% women; median age, 59 years; median Acute Physiology and Chronic Health Evaluation [APACHE] II score, 26) were included in the analysis after the trial was stopped early based on predefined criteria for efficacy. The intubation rate was 61.5% (n = 24) for the face mask group and 18.2% (n = 8) for the helmet group (absolute difference, −43.3%; 95% CI, −62.4%to −24.3%; P < .001). The number of ventilator-free days was significantly higher in the helmet group (28 vs 12.5, P < .001). At 90 days, 15 patients (34.1%) in the helmet group died compared with 22 patients (56.4%) in the face mask group

  9. A sewer ventilation model applying conservation of momentum.

    PubMed

    Ward, M; Hamer, G; McDonald, A; Witherspoon, J; Loh, E; Parker, W

    2011-01-01

    The work presented herein was completed in an effort to characterize the forces influencing ventilation in gravity sewers and to develop a mathematical model, based on conservation of momentum, capable of accounting for friction at the headspace/pipe interface, drag at the air/water interface, and buoyancy caused by air density differences between a sewer headspace and ambient. Experiments were completed on two full scale sewer reaches in Australia. A carbon monoxide-based tracer technique was used to measure the ventilation rate within the sewer headspaces. Additionally, measurements of pressure, relative humidity, and temperature were measured in the ambient air and sewer headspace. The first location was a five kilometre long sewer outfall beginning at a wastewater treatment plant and terminating at the ocean. The second location was a large gravity sewer reach fitted with ventilation fans. At the first location the headspace was entirely sealed except for openings that were controlled during the experiments. In this situation forces acting on the headspace air manifested mostly as a pressure distribution within the reach, effectively eliminating friction at the pipe wall. At the second location, air was forced to move near the same velocity as the wastewater, effectively eliminating drag at the air/water interface. These experiments allowed individual terms of the momentum equation to be evaluated. Experimental results were compared to the proposed mathematical model. Conclusions regarding model accuracy are provided along with model application guidance and assumptions. PMID:22214094

  10. A sewer ventilation model applying conservation of momentum.

    PubMed

    Ward, M; Hamer, G; McDonald, A; Witherspoon, J; Loh, E; Parker, W

    2011-01-01

    The work presented herein was completed in an effort to characterize the forces influencing ventilation in gravity sewers and to develop a mathematical model, based on conservation of momentum, capable of accounting for friction at the headspace/pipe interface, drag at the air/water interface, and buoyancy caused by air density differences between a sewer headspace and ambient. Experiments were completed on two full scale sewer reaches in Australia. A carbon monoxide-based tracer technique was used to measure the ventilation rate within the sewer headspaces. Additionally, measurements of pressure, relative humidity, and temperature were measured in the ambient air and sewer headspace. The first location was a five kilometre long sewer outfall beginning at a wastewater treatment plant and terminating at the ocean. The second location was a large gravity sewer reach fitted with ventilation fans. At the first location the headspace was entirely sealed except for openings that were controlled during the experiments. In this situation forces acting on the headspace air manifested mostly as a pressure distribution within the reach, effectively eliminating friction at the pipe wall. At the second location, air was forced to move near the same velocity as the wastewater, effectively eliminating drag at the air/water interface. These experiments allowed individual terms of the momentum equation to be evaluated. Experimental results were compared to the proposed mathematical model. Conclusions regarding model accuracy are provided along with model application guidance and assumptions.

  11. Evaluation of Ventilation Strategies in New Construction Multifamily Buildings

    SciTech Connect

    Maxwell, S.; Berger, D.; Zuluaga, M.

    2014-07-01

    In multifamily buildings, particularly in the Northeast, exhaust ventilation strategies are the norm as a means of meeting both local exhaust and whole-unit mechanical ventilation rates. The issue of where the 'fresh' air is coming from is gaining significance as air-tightness standards for enclosures become more stringent, and the 'normal leakage paths through the building envelope' disappear. CARB researchers have found that the majority of high performance, new construction, multifamily housing in the Northeast use one of four general strategies for ventilation: continuous exhaust only with no designated supply or make-up air source, continuous exhaust with ducted make-up air to apartments, continuous exhaust with supply through a make-up air device integral to the unit HVAC, and continuous exhaust with supply through a passive inlet device, such as a trickle vent. Insufficient information is available to designers on how these various systems are best applied. Product performance data are based on laboratory tests, and the assumption is that products will perform similarly in the field. Proper application involves matching expected performance at expected building pressures, but there is no guarantee that those conditions will exist consistently in the finished building. This research effort, which included several weeks of building pressure monitoring, sought to provide field validation of system performance. The performance of four substantially different strategies for providing make-up air to apartments was evaluated.

  12. ASHRAE and residential ventilation

    SciTech Connect

    Sherman, Max H.

    2003-10-01

    In the last quarter of a century, the western world has become increasingly aware of environmental threats to health and safety. During this period, people psychologically retreated away from outdoors hazards such as pesticides, smog, lead, oil spills, and dioxin to the seeming security of their homes. However, the indoor environment may not be healthier than the outdoor environment, as has become more apparent over the past few years with issues such as mold, formaldehyde, and sick-building syndrome. While the built human environment has changed substantially over the past 10,000 years, human biology has not; poor indoor air quality creates health risks and can be uncomfortable. The human race has found, over time, that it is essential to manage the indoor environments of their homes. ASHRAE has long been in the business of ventilation, but most of the focus of that effort has been in the area of commercial and institutional buildings. Residential ventilation was traditionally not a major concern because it was felt that, between operable windows and envelope leakage, people were getting enough outside air in their homes. In the quarter of a century since the first oil shock, houses have gotten much more energy efficient. At the same time, the kinds of materials and functions in houses changed in character in response to people's needs. People became more environmentally conscious and aware not only about the resources they were consuming but about the environment in which they lived. All of these factors contributed to an increasing level of public concern about residential indoor air quality and ventilation. Where once there was an easy feeling about the residential indoor environment, there is now a desire to define levels of acceptability and performance. Many institutions--both public and private--have interests in Indoor Air Quality (IAQ), but ASHRAE, as the professional society that has had ventilation as part of its mission for over 100 years, is the

  13. Ventilation in homes infested by house-dust mites.

    PubMed

    Sundell, J; Wickman, M; Pershagen, G; Nordvall, S L

    1995-02-01

    Thirty single-family homes with either high (> or = 2000 ng/g) or low (< or = 1000 ng/g) house-dust mite (HDM) allergen levels in mattress dust were examined for ventilation, thermal climate, and air quality (formaldehyde and total volatile organic compounds (TVOC). Elevated concentrations of HDM allergen in mattress and floor dust were associated with the difference in absolute humidity between indoor and outdoor air, as well as with low air-change rates of the home, particularly the bedroom. No correlation was found between concentration of TVOC or formaldehyde in bedroom air and HDM allergen concentration. In regions with a cold winter climate, the air-change rate of the home and the infiltration of outdoor air into the bedroom appear to be important for the infestation of HDM.

  14. Spatiotemporally-Resolved Air Exchange Rate as a Modifier of Acute Air Pollution-Related Morbidity

    EPA Science Inventory

    The National Exposure Research Laboratory (NERL) Human Exposure and Atmospheric Sciences Division (HEASD) conducts research in support of EPA mission to protect human health and the environment. HEASD research program supports Goal 1 (Clean Air) and Goal 4 (Healthy People) of EP...

  15. Risk Factors in Heating, Ventilating, and Air-Conditioning Systemsfor Occupant Symptoms in U.S. Office Buildings: the EPA BASE Study

    SciTech Connect

    Mendell, M.J.; Lei-Gomez, Q.; Mirer, A.; Seppanen, O.; Brunner, G.

    2006-10-01

    Nonspecific building-related symptoms among occupants of modern office buildings worldwide are common and may be associated with important reductions in work performance, but their etiology remains uncertain. Characteristics of heating, ventilating, and air-conditioning (HVAC) systems in office buildings that increase risk of indoor contaminants or reduce effectiveness of ventilation may cause adverse exposures and subsequent increase in these symptoms among occupants. We analyzed data collected by the U.S. EPA from a representative sample of 100 large U.S. office buildings--the Building Assessment and Survey Evaluation (BASE) study--using multivariate logistic regression models with generalized estimating equations adjusted for potential personal and building confounders. We estimated odds ratios (ORs) and 95% confidence intervals (CIs) for associations between seven building-related symptom outcomes and selected HVAC system characteristics. Among factors of HVAC design or configuration: Outdoor air intakes less than 60 m above the ground were associated with approximately doubled odds of most symptoms assessed. Sealed (non-operable) windows were associated with increases in skin and eye symptoms (ORs= 1.9, 1.3, respectively). Outdoor air intake without an intake fan was associated with an increase in eye symptoms (OR=1.7). Local cooling coils were associated with increased headache (OR=1.5). Among factors of HVAC condition, maintenance, or operation: the presence of humidification systems in good condition was associated with an increase in headache (OR=1.4), whereas the presence of humidification systems in poor condition was associated with increases in fatigue/difficulty concentrating, as well as upper respiratory symptoms (ORs=1.8, 1.5). No regularly scheduled inspections for HVAC components was associated with increased eye symptoms, cough and upper respiratory symptoms (ORs=2.2, 1.6, 1.5). Less frequent cleaning of cooling coils or drip pans was associated

  16. A novel test cage with an air ventilation system as an alternative to conventional cages for the efficacy testing of mosquito repellents.

    PubMed

    Obermayr, U; Rose, A; Geier, M

    2010-11-01

    We have developed a novel test cage and improved method for the evaluation of mosquito repellents. The method is compatible with the United States Environmental Protection Agency, 2000 draft OPPTS 810.3700 Product Performance Test Guidelines for Testing of Insect Repellents. The Biogents cages (BG-cages) require fewer test mosquitoes than conventional cages and are more comfortable for the human volunteers. The novel cage allows a section of treated forearm from a volunteer to be exposed to mosquito probing through a window. This design minimizes residual contamination of cage surfaces with repellent. In addition, an air ventilation system supplies conditioned air to the cages after each single test, to flush out and prevent any accumulation of test substances. During biting activity tests, the untreated skin surface does not receive bites because of a screen placed 150 mm above the skin. Compared with the OPPTS 810.3700 method, the BG-cage is smaller (27 liters, compared with 56 liters) and contains 30 rather than hundreds of blood-hungry female mosquitoes. We compared the performance of a proprietary repellent formulation containing 20% KBR3023 with four volunteers on Aedes aegypti (L.) (Diptera: Culicidae) in BG- and conventional cages. Repellent protection time was shorter in tests conducted with conventional cages. The average 95% protection time was 4.5 +/- 0.4 h in conventional cages and 7.5 +/- 0.6 h in the novel BG-cages. The protection times measured in BG-cages were more similar to the protection times determined with these repellents in field tests. PMID:21175061

  17. Phonation time, phonation volume and air flow rate in normal adults.

    PubMed

    Prathanee, B; Watthanathon, J; Ruangjirachuporn, P

    1994-12-01

    The purpose of this study was to determine the average phonation time, phonation volume and air flow rate, as well as the relationship between each of these parameters during two conditions (normal and deep breaths). Researchers expect to use these averages in screening of voice disorders. One hundred and three subjects, 67 males and 36 females, were studied. The instruments were a 9 liter respirometer, a tape recorder and a stop watch. The results indicated that the parameters for males were significantly greater than those for females. In addition, the findings suggested that the values of mean phonation time, phonation volume and air flow rate during deep breath were significantly greater than those during normal breath (p < 0.05). The phonation time was inversely related to the air flow rate. However, there was a positive relationship between phonation time and phonation volume, as well as between phonation volume and air flow rate. The findings supported our hypothesises.

  18. Ventilation best practices guide

    SciTech Connect

    Dorgan, C.B.; Dorgan, C.E.

    1996-07-01

    The intent of this Guide is to provide utility marketing and engineering personnel with information on how to identify indoor air quality (IAQ) problems, the current standards relating to IAQ and examples of what typically causes IAQ problems in commercial buildings. The Guide is written assuming that the reader has limited knowledge of heating, ventilating and air conditioning (HVAC) systems and that they are new to the IAQ arena. Also included in the Guide is a discussion of new electric technologies which are energy efficient and maintain a high level of IAQ.

  19. Measuring the emission rate of an aerosol source placed in a ventilated room using a tracer gas: influence of particle wall deposition.

    PubMed

    Bémer, D; Lecler, M T; Régnier, R; Hecht, G; Gerber, J M

    2002-04-01

    A method to measure the emission rate of an airborne pollutant source using a tracer gas was tested in the case of an aerosol source. The influence of particle deposition on the walls of a test room of 72 m3 was studied. The deposition rate of an aerosol of MgCl2 was determined by means of two methods: one based on measuring the aerosol concentration decay inside the ventilated room, the other based on calculation of the material mass balance. The concentration decay was monitored by optical counting and the aerosol mass concentration determined by means of sampling on a filter and analysis of the mass deposited by atomic absorption spectrometry. Four series of measurements were carried out. The curve giving the deposition rate according to the particle aerodynamic diameter (d(ae)) was established and shows deposition rates higher than those predicted using the model of Corner. The decay method gives the best results. The study carried out has shown that the phenomenon of deposition has little effect on the measurement of the aerosol source emission rate using a tracer gas for particles of aerodynamic diameter < 5 microm (underestimation < 25%). For particles of a greater diameter, wall deposition is an extremely limiting factor for the method, the influence of which can, however, be limited by using a test booth of small volume and keeping the sampling duration as short as possible.

  20. Space station ventilation study

    NASA Technical Reports Server (NTRS)

    Colombo, G. V.; Allen, G. E.

    1972-01-01

    A ventilation system design and selection method which is applicable to any manned vehicle were developed. The method was used to generate design options for the NASA 33-foot diameter space station, all of which meet the ventilation system design requirements. System characteristics such as weight, volume, and power were normalized to dollar costs for each option. Total system costs for the various options ranged from a worst case $8 million to a group of four which were all approximately $2 million. A system design was then chosen from the $2 million group and is presented in detail. A ventilation system layout was designed for the MSFC space station mockup which provided comfortable, efficient ventilation of the mockup. A conditioned air distribution system design for the 14-foot diameter modular space station, using the same techniques, is also presented. The tradeoff study resulted in the selection of a system which costs $1.9 million, as compared to the alternate configuration which would have cost $2.6 million.

  1. Using CFCs and Sulfur Hexafluoride to Improve Estimates of Ventilation Rate Changes and Anthropogenic CO2 Uptake Along CLIVAR Repeat Hydrography Sections

    NASA Astrophysics Data System (ADS)

    Bullister, J. L.; Sonnerup, R. E.; Warner, M. J.

    2008-12-01

    A number of key hydrographic sections sampled in the 1990s as part of the World Ocean Circulation Experiment (WOCE) are being re-occupied at approximately decadal intervals as part of the CLIVAR Repeat Hydrography Program. Measurements of a number of physical and chemical properties are made at full depth, closely spaced (nominally 30 nautical mile) CTD/rosette stations, with water samples collected at between 24 and 36 depths per station. Among the central goals of the program are the detection of changes in ventilation, carbon uptake and storage, dissolved oxygen and water properties on decadal time scales. Repeat measurements of dissolved chlorofluorocarbon (CFC) CFC-11 and CFC-12 concentrations show significant decadal increases. Water mass ages derived from CFCs (pCFC ages) also show substantial changes (typically increases) with time along the repeat sections. Simple models indicate that much of the observed pCFC age increases are due to the impacts of mixing in the ocean interior. Measurements of sulfur hexafluoride (SF6), a transient tracer that has been rapidly increasing in the atmosphere during the past several decades, have been included along with CFCs on some recent CLIVAR repeat sections. Because the atmospheric history of SF6 differs substantially from that of the CFCs, concurrent SF6 and CFC measurements can be used to help diagnose the impacts of mixing on pCFC ages and on decadal changes in pCFC ages. We are exploiting this twin-tracer strategy in an attempt to improve estimates of ventilation rate changes and anthropogenic CO2 uptake rates along the CLIVAR repeat sections.

  2. Dependence of lung injury on inflation rate during low-volume ventilation in normal open-chest rabbits.

    PubMed

    D'Angelo, Edgardo; Pecchiari, Matteo; Saetta, Marina; Balestro, Elisabetta; Milic-Emili, Joseph

    2004-07-01

    Lung mechanics and morphometry were assessed in two groups of nine normal open-chest rabbits mechanically ventilated (MV) for 3-4 h at zero end-expiratory pressure (ZEEP) with physiological tidal volumes (Vt; 11 ml/kg) and high (group A) or low (group B) inflation flow (44 and 6.1 ml x kg(-1) x s(-1), respectively). Relative to initial MV on positive end-expiratory pressure (PEEP; 2.3 cmH(2)O), MV on ZEEP increased quasi-static elastance and airway and viscoelastic resistance more in group A (+251, +393, and +225%, respectively) than in group B (+180, +247, and +183%, respectively), with no change in viscoelastic time constant. After restoration of PEEP, quasi-static elastance and viscoelastic resistance returned to control, whereas airway resistance, still relative to initial values, remained elevated more in group A (+86%) than in group B (+33%). In contrast, prolonged high-flow MV on PEEP had no effect on lung mechanics of seven open-chest rabbits (group C). Gas exchange on PEEP was equally preserved in all groups, and the lung wet-to-dry ratios were normal. Relative to group C, both groups A and B had an increased percentage of abnormal alveolar-bronchiolar attachments and number of polymorphonuclear leukocytes in alveolar septa, the latter being significantly larger in group A than in group B. Thus prolonged MV on ZEEP with cyclic opening-closing of peripheral airways causes alveolar-bronchiolar uncoupling and parenchymal inflammation with concurrent, persistent increase in airway resistance, which are worsened by high-inflation flow.

  3. Transpleural Ventilation via Spiracles in Severe Emphysema Increases Alveolar Ventilation.

    PubMed

    Chahla, Mayy; Larson, Christopher D; Parekh, Kalpaj R; Reed, Robert M; Terry, Peter; Schmidt, Gregory A; Eberlein, Michael

    2016-06-01

    In emphysema airway resistance can exceed collateral airflow resistance, causing air to flow preferentially through collateral pathways. In severe emphysema ventilation through openings directly through the chest wall into the parenchyma (spiracles) could bypass airway obstruction and increase alveolar ventilation via transpleural expiration. During lung transplant operations, spiracles occasionally can occur inadvertently. We observed transpleural expiration via spiracles in three subjects undergoing lung transplant for emphysema. During transpleural spiracle ventilation, inspiratory tidal volumes (TV) were unchanged; however, expiration was entirely transpleural in two patients whereas the expired TV to the ventilator circuit was reduced to 25% of the inspired TV in one. At baseline, mean PCO2 was 61 ± 5 mm Hg, which decreased to a mean PCO2 of 49 ± 5 mm Hg (P = .05) within minutes after transpleural spiracle ventilation and further decreased at 1 to 2 h (36 ± 4 mm Hg; P = .002 compared with baseline) on unchanged ventilator settings. This observation of increased alveolar ventilation supports further studies of spiracles as a possible therapy for advanced emphysema. PMID:27287591

  4. Test Plan to Evaluate the Relationship Among IAQ, Comfort, Moisture, and Ventilation in Humid Climates

    SciTech Connect

    Widder, Sarah H.; Martin, Eric

    2013-03-15

    This experimental plan describes research being conducted by Pacific Northwest National Laboratory (PNNL), in coordinatation with Florida Solar Energy Center (FSEC), Florida HERO, and Lawrence Berkeley National Laboratory (LBNL) to evaluate the impact of ventilation rate on interior moisture levels, temperature distributions, and indoor air contaminant concentrations. Specifically, the research team will measure concentrations of indoor air contaminants, ventilation system flow rates, energy consumption, and temperature and relative humidity in ten homes in Gainesville, FL to characterize indoor pollutant levels and energy consumption associated with the observed ventilation rates. PNNL and FSEC have collaboratively prepared this experimental test plan, which describes background and context for the proposed study; the experimental design; specific monitoring points, including monitoring equipment, and sampling frequency; key research questions and the associated data analysis approach; experimental logistics, including schedule, milestones, and team member contact information; and clearly identifies the roles and responsibilities of each team in support of project objectives.

  5. Experimental study of a semi-passive ventilation grille with a feedback control system

    NASA Astrophysics Data System (ADS)

    D'Orazio, A.; Fontana, L.; Salata, F.

    2011-08-01

    The diffusion of window frames with low air permeability, due to the energy saving regulations, has implied in several cases the worsening of the indoor microclimate and air quality. On the other hand, air-tight window frames imply uncontrolled and too high air change rates. The mechanical ventilation not always is a practicable solution because of economic reasons and because it implies energy waste. Various Italian and European environmental and energetic laws take into consideration and promote the use of controlled natural ventilation, though this definition is not associated to well defined and tested technical solutions. An adequate solution can be achieved by using semi-passive self adjustable ventilation devices, able to ensure controlled changes of indoor air. In this paper, a semi-passive damper with a feedback control system is proposed and its behavior is investigated by means of experimental study. The presented semi-passive grille allows to control the air flow rate, injected into the room by natural or artificial pressure gradient, more effectively than the usual passive ventilation grilles made available by the present industrial production. However, since the semi-passive grille has a one-way flow, in the natural ventilation of a flat the proper functioning of the system could be ensured with a more complex configuration, with respect to the passive self-regulating grilles, able to limit the flow of fresh air in the presence of high levels of Δp; conversely, it could have widespread use in applications requiring a more accurate control of airflow in case of mechanical ventilation plants.

  6. Experimental study of a semi-passive ventilation grille with a feedback control system.

    PubMed

    D'Orazio, A; Fontana, L; Salata, F

    2011-08-01

    The diffusion of window frames with low air permeability, due to the energy saving regulations, has implied in several cases the worsening of the indoor microclimate and air quality. On the other hand, air-tight window frames imply uncontrolled and too high air change rates. The mechanical ventilation not always is a practicable solution because of economic reasons and because it implies energy waste. Various Italian and European environmental and energetic laws take into consideration and promote the use of controlled natural ventilation, though this definition is not associated to well defined and tested technical solutions. An adequate solution can be achieved by using semi-passive self adjustable ventilation devices, able to ensure controlled changes of indoor air. In this paper, a semi-passive damper with a feedback control system is proposed and its behavior is investigated by means of experimental study. The presented semi-passive grille allows to control the air flow rate, injected into the room by natural or artificial pressure gradient, more effectively than the usual passive ventilation grilles made available by the present industrial production. However, since the semi-passive grille has a one-way flow, in the natural ventilation of a flat the proper functioning of the system could be ensured with a more complex configuration, with respect to the passive self-regulating grilles, able to limit the flow of fresh air in the presence of high levels of Δp; conversely, it could have widespread use in applications requiring a more accurate control of airflow in case of mechanical ventilation plants.

  7. Mechanical Ventilation

    MedlinePlus

    ... or husband or next of kin). It is important that you talk with your family members and your doctors about using a ventilator and what you would like to happen in different situations. The more clearly you explain your values and choices to friends, loved ones and doctors, ...

  8. Daily changes in oxygen saturation and pulse rate associated with particulate air pollution and barometric pressure.

    PubMed

    Dockery, D W; Pope, C A; Kanner, R E; Martin Villegas, G; Schwartz, J

    1999-01-01

    Epidemiologic studies have linked fine particulate air pollution with increases in morbidity and mortality rates from cardiopulmonary complications. Although the underlying biologic mechanisms responsible for this increase remain largely unknown, potential pathways include transient declines in blood oxygenation and changes in pulse rate following exposures to particulate air pollution episodes. This study evaluated potential associations between daily measures of respirable particulate matter (PM) with pulse rate and oxygen saturation of the blood. Pulse rate and oxygen saturation (Spo2) using pulse oximetry were measured daily in 90 elderly subjects living near air pollution monitors during the winter of 1995-96 in Utah Valley. We also evaluated potential associations of oxygen saturation and pulse rate with barometric pressure. Small but statistically significant positive associations between day-to-day changes in Spo2 and barometric pressure were observed. Pulse rate was inversely associated with barometric pressure. Exposure to particulate pollution was not significantly associated with Spo2 except in male participants 80 years of age or older. Increased daily pulse rate, as well as the odds of having a pulse rate 5 or 10 beats per minute (bpm) above normal (normal is defined as the individual's mean pulse rate throughout the study period), were significantly associated with exposure to particulate pollution on the previous 1 to 5 days. The medical or biologic relevance of these increases in pulse rate following exposure to particulate air pollution requires further study.

  9. Daily changes in oxygen saturation and pulse rate associated with particulate air pollution and barometric pressure.

    PubMed

    Dockery, D W; Pope, C A; Kanner, R E; Martin Villegas, G; Schwartz, J

    1999-01-01

    Epidemiologic studies have linked fine particulate air pollution with increases in morbidity and mortality rates from cardiopulmonary complications. Although the underlying biologic mechanisms responsible for this increase remain largely unknown, potential pathways include transient declines in blood oxygenation and changes in pulse rate following exposures to particulate air pollution episodes. This study evaluated potential associations between daily measures of respirable particulate matter (PM) with pulse rate and oxygen saturation of the blood. Pulse rate and oxygen saturation (Spo2) using pulse oximetry were measured daily in 90 elderly subjects living near air pollution monitors during the winter of 1995-96 in Utah Valley. We also evaluated potential associations of oxygen saturation and pulse rate with barometric pressure. Small but statistically significant positive associations between day-to-day changes in Spo2 and barometric pressure were observed. Pulse rate was inversely associated with barometric pressure. Exposure to particulate pollution was not significantly associated with Spo2 except in male participants 80 years of age or older. Increased daily pulse rate, as well as the odds of having a pulse rate 5 or 10 beats per minute (bpm) above normal (normal is defined as the individual's mean pulse rate throughout the study period), were significantly associated with exposure to particulate pollution on the previous 1 to 5 days. The medical or biologic relevance of these increases in pulse rate following exposure to particulate air pollution requires further study. PMID:10192116

  10. Building America Case Study: Sealed Crawl Spaces with Integrated Whole-House Ventilation in a Cold Climate, Ithaca, New York

    SciTech Connect

    2015-09-01

    "9One method of code-compliance for crawlspaces is to seal and insulate the crawlspace, rather than venting to the outdoors. However, codes require mechanical ventilation; either via conditioned supply air from the HVAC system, or a continuous exhaust ventilation strategy. As the CARB's building partner, Ithaca Neighborhood Housing Services, intended to use the unvented crawlspace in a recent development, CARB was interested in investigating a hybrid ventilation method that includes the exhaust air from the crawlspace as a portion of an ASHRAE 62.2 compliant whole-house ventilation strategy. This hybrid ventilation method was evaluated through a series of long-term monitoring tests that observed temperature, humidity, and pressure conditions through the home and crawlspace. Additionally, CARB worked with NREL to perform multi-point tracer gas testing on six separate ventilation strategies - varying portions of 62.2 required flow supplied by the crawlspace fan and an upstairs bathroom fan. The intent of the tracer gas testing was to identify effective Reciprocal Age of Air (RAoA), which is equivalent to the air change rate in well-mixed zones, for each strategy while characterizing localized infiltration rates in several areas of the home.

  11. Human Reliability Analysis for In-Tank Precipitation Alignment and Startup of Emergency Purge Ventilation Equipment. Revision 4

    SciTech Connect

    Shapiro, B.J.; Britt, T.E.

    1995-06-01

    This report documents the methodology used for calculating the human error probability for establishing air based ventilation using emergency purge ventilation equipment on In-Tank Precipitation (ITP) processing tanks 48 and 49 after a failure of the nitrogen purge system following a seismic event. The analyses were performed according to THERP (Technique for Human Error Rate Prediction) as describes in NUREG/CR-1278-F.

  12. A theory of ventilation estimate over hypothetical urban areas.

    PubMed

    Liu, Chun-Ho; Ng, Chi-To; Wong, Colman C C

    2015-10-15

    Urban roughness is a major factor governing the flows and scalar transport in the atmospheric boundary layer (ABL) but our understanding is rather limited. The ventilation and pollutant removal of hypothetical urban areas consisting of various types of street canyons are examined using computational fluid dynamics (CFD). The aerodynamic resistance, ventilation efficiency, and pollutant removal are measured by the friction factor f, air exchange rate (ACH), and pollutant exchange rate (PCH), respectively. Two source configurations of passive tracer, ground-level-only (Tracer 0) and all-solid-boundary (Tracer 1) are employed to contrast their transport behavior. It is found that the ventilation and pollutant removal are largely attributed to their turbulent components (over 60%). Moreover, with a consistent support from analytical solution and CFD results, the turbulent ACH is a linear function of the square root of the friction factor (ACH'∝f(1/2)) regardless of building geometry. Tracer 0 and Tracer 1 exhibit diversified removal behavior as functions of friction factor so analytical parameterizations have not yet been developed. In view of the large portion of aged air removal by turbulence, it is proposed that the aerodynamic resistance can serve as an estimate to the minimum ventilation efficiency of urban areas. PMID:25901939

  13. A theory of ventilation estimate over hypothetical urban areas.

    PubMed

    Liu, Chun-Ho; Ng, Chi-To; Wong, Colman C C

    2015-10-15

    Urban roughness is a major factor governing the flows and scalar transport in the atmospheric boundary layer (ABL) but our understanding is rather limited. The ventilation and pollutant removal of hypothetical urban areas consisting of various types of street canyons are examined using computational fluid dynamics (CFD). The aerodynamic resistance, ventilation efficiency, and pollutant removal are measured by the friction factor f, air exchange rate (ACH), and pollutant exchange rate (PCH), respectively. Two source configurations of passive tracer, ground-level-only (Tracer 0) and all-solid-boundary (Tracer 1) are employed to contrast their transport behavior. It is found that the ventilation and pollutant removal are largely attributed to their turbulent components (over 60%). Moreover, with a consistent support from analytical solution and CFD results, the turbulent ACH is a linear function of the square root of the friction factor (ACH'∝f(1/2)) regardless of building geometry. Tracer 0 and Tracer 1 exhibit diversified removal behavior as functions of friction factor so analytical parameterizations have not yet been developed. In view of the large portion of aged air removal by turbulence, it is proposed that the aerodynamic resistance can serve as an estimate to the minimum ventilation efficiency of urban areas.

  14. Preventing Airborne Disease Transmission: Review of Methods for Ventilation Design in Health Care Facilities

    PubMed Central

    Aliabadi, Amir A.; Rogak, Steven N.; Bartlett, Karen H.; Green, Sheldon I.

    2011-01-01

    Health care facility ventilation design greatly affects disease transmission by aerosols. The desire to control infection in hospitals and at the same time to reduce their carbon footprint motivates the use of unconventional solutions for building design and associated control measures. This paper considers indoor sources and types of infectious aerosols, and pathogen viability and infectivity behaviors in response to environmental conditions. Aerosol dispersion, heat and mass transfer, deposition in the respiratory tract, and infection mechanisms are discussed, with an emphasis on experimental and modeling approaches. Key building design parameters are described that include types of ventilation systems (mixing, displacement, natural and hybrid), air exchange rate, temperature and relative humidity, air flow distribution structure, occupancy, engineered disinfection of air (filtration and UV radiation), and architectural programming (source and activity management) for health care facilities. The paper describes major findings and suggests future research needs in methods for ventilation design of health care facilities to prevent airborne infection risk. PMID:22162813

  15. Development of a method for bacteria and virus recovery from heating, ventilation, and air conditioning (HVAC) filters.

    PubMed

    Farnsworth, James E; Goyal, Sagar M; Kim, Seung Won; Kuehn, Thomas H; Raynor, Peter C; Ramakrishnan, M A; Anantharaman, Senthilvelan; Tang, Weihua

    2006-10-01

    The aim of the work presented here is to study the effectiveness of building air handling units (AHUs) in serving as high volume sampling devices for airborne bacteria and viruses. An HVAC test facility constructed according to ASHRAE Standard 52.2-1999 was used for the controlled loading of HVAC filter media with aerosolized bacteria and virus. Nonpathogenic Bacillus subtilis var. niger was chosen as a surrogate for Bacillus anthracis. Three animal viruses; transmissible gastroenteritis virus (TGEV), avian pneumovirus (APV), and fowlpox virus were chosen as surrogates for three human viruses; SARS coronavirus, respiratory syncytial virus, and smallpox virus; respectively. These bacteria and viruses were nebulized in separate tests and injected into the test duct of the test facility upstream of a MERV 14 filter. SKC Biosamplers upstream and downstream of the test filter served as reference samplers. The collection efficiency of the filter media was calculated to be 96.5 +/- 1.5% for B. subtilis, however no collection efficiency was measured for the viruses as no live virus was ever recovered from the downstream samplers. Filter samples were cut from the test filter and eluted by hand-shaking. An extraction efficiency of 105 +/- 19% was calculated for B. subtilis. The viruses were extracted at much lower efficiencies (0.7-20%). Our results indicate that the airborne concentration of spore-forming bacteria in building AHUs may be determined by analyzing the material collected on HVAC filter media, however culture-based analytical techniques are impractical for virus recovery. Molecular-based identification techniques such as PCR could be used.

  16. Early results from combined historic chlorofluorocarbon and first sulphur hexafluoride measurements in the Weddell Sea - variability of ventilation rates and anthropogenic carbon

    NASA Astrophysics Data System (ADS)

    Huhn, O.; Rhein, M.; Bulsiewicz, K.

    2012-04-01

    The Weddell Sea is a key area for the formation of deep and bottom water and, hence, a major driver of the deep part of the global ocean's conveyor belt. Furthermore, it provides an important sink for atmospheric gases like anthropogenic carbon. Its sensitivity to changing atmospheric conditions is under discussion. During the last three decades time series of anthropogenic transient tracer measurements (chlorofluorocarbons, CFCs) were obtained on a section crossing the Weddell Basin from the northern tip of the Antarctic Peninsula to Cape Norwegia and along the Prime Meridian from the Antarctic Continent to the Mid Atlantic Ridge (1984-2008). On our most recent RV POLARSTERN expedition from November 2010 to February 2011 we obtained for the first time sulphur hexafluoride (SF6) measurements in addition to CFCs in that area. The onset of the atmospheric SF6 history starts some decades after the CFCs, and the increase of SF6 in the atmosphere is steeper. The combination of CFC and SF6 may, hence, provide a better constraint for the quantification of very recently ventilated deep and bottom water and for the estimate of transport time scales or transit time distributions (TTDs). We discuss that new CFC and SF6 data set in comparison to the historic CFC data and show early results from our analysis. We use the extended CFC time series combined with the additional tracer SF6 to determine TTDs, from which we assess the ventilation rates of deep and bottom water and estimate the related content of anthropogenic carbon and their temporal variability in the Weddell Sea during the last three decades.

  17. The basis and basics of mechanical ventilation.

    PubMed

    Bone, R C; Eubanks, D H

    1991-06-01

    The development of mechanical ventilators and the procedures for their application began with the simple foot pump developed by Fell O'Dwyer in 1888. Ventilators have progressed through three generations, beginning with intermittent positive pressure breathing units such as the Bird and Bennett device in the 1960s. These were followed by second-generation units--represented by the Bennett MA-2 ventilator--in the 1970s, and the third-generation microprocessor-controlled units of today. During this evolutionary process clinicians recognized Types I and II respiratory failure as being indicators for mechanical ventilatory support. More recently investigators have expanded, clarified, and clinically applied the physiology of the work of breathing (described by Julius Comroe and other pioneers) to muscle fatigue, requiring ventilatory support. A ventilator classification system can help the clinician understand how ventilators function and under what conditions they may fail to operate as desired. Pressure-support ventilation is an example of how industry has responded to a clinical need--that is, to unload the work of breathing. All positive pressure ventilators generate tidal volumes by using power sources such as medical gas cylinders, air compressors, electrically driven turbines, or piston driven motors. Positive end-expiratory pressures, synchronized intermittent mandatory ventilation, pressure support ventilation, pressure release ventilation, and mandatory minute ventilation, are examples of the special functions available on modern ventilators. Modern third-generation ventilators use microprocessors to control operational functions and monitors. Because these units have incorporated the experience learned from earlier ventilators, it is imperative that clinicians understand basic ventilator operation and application in order to most effectively prescribe and assess their use. PMID:2036934

  18. 21 CFR 868.5955 - Intermittent mandatory ventilation attachment.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... providing mechanical ventilation at a preset rate. (b) Classification. Class II (performance standards). ... 21 Food and Drugs 8 2012-04-01 2012-04-01 false Intermittent mandatory ventilation attachment. 868... mandatory ventilation attachment. (a) Identification. An intermittent mandatory ventilation (IMV)...

  19. 21 CFR 868.5955 - Intermittent mandatory ventilation attachment.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... providing mechanical ventilation at a preset rate. (b) Classification. Class II (performance standards). ... 21 Food and Drugs 8 2014-04-01 2014-04-01 false Intermittent mandatory ventilation attachment. 868... mandatory ventilation attachment. (a) Identification. An intermittent mandatory ventilation (IMV)...

  20. 21 CFR 868.5955 - Intermittent mandatory ventilation attachment.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... providing mechanical ventilation at a preset rate. (b) Classification. Class II (performance standards). ... 21 Food and Drugs 8 2013-04-01 2013-04-01 false Intermittent mandatory ventilation attachment. 868... mandatory ventilation attachment. (a) Identification. An intermittent mandatory ventilation (IMV)...

  1. Reaction rate constant for dry air oxidation of K Basin fuel

    SciTech Connect

    Trimble, D.J.

    1998-04-29

    The rate of oxidation of spent nuclear fuel stored in the K Basin water is an important parameter when assessing the processes and accident scenarios for preparing the fuel for dry storage. The literature provides data and rate laws for the oxidation of unirradiated uranium in various environments. Measurement data for the dry air oxidation of K Basin fuel is compared to the literature data for linear oxidation in dry air. Equations for the correlations and statistical bounds to the K Basin fuel data and the literature data are selected for predicting nominal and bounding rates for the dry air oxidation of the K Basin fuel. These rate equations are intended for use in the Spent Nuclear Fuel Project Technical Data book.

  2. 46 CFR 194.20-5 - Ventilation.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... CONTROL OF EXPLOSIVES AND OTHER HAZARDOUS MATERIALS Chemical Stores and/or Storerooms § 194.20-5 Ventilation. (a) Chemical storerooms shall be equipped with a power ventilation system of exhaust type. The system shall have a capacity sufficient to effect a complete change of air in not more than 4...

  3. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... 14 Aeronautics and Space 4 2014-01-01 2014-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking...

  4. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 14 Aeronautics and Space 4 2010-01-01 2010-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking...

  5. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2013 CFR

    2013-01-01

    ... 14 Aeronautics and Space 4 2013-01-01 2013-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking...

  6. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2011 CFR

    2011-01-01

    ... 14 Aeronautics and Space 4 2011-01-01 2011-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking...

  7. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... 14 Aeronautics and Space 4 2012-01-01 2012-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking...

  8. Microprocessor control of broiler house ventilation

    SciTech Connect

    Kay, F.W.; Allison, J.M.

    1983-06-01

    An M6800 microprocessor control system for ventilation fans, supplemental heaters, and air inlet slots is presented. The control system uses inputs from temperature sensors, both inside and outside the house, along with the desired environmental conditions inside to calculate the required ventilation for heat and moisture control.

  9. Comparative study on the ventilation mode of the residential building in Beijing area in winter

    NASA Astrophysics Data System (ADS)

    Wang, G. J.; Li, Q. P.; Guo, Y.; Hu, Y. H.

    2016-08-01

    With the development of residential energy conservation technology, the air tightness requirement of the window is higher and higher. So in winter the cold penetration wind cannot satisfy the requirement of indoor personnel to fresh air. The common ventilation mode includes natural ventilation, natural inlet and mechanical exhaust, wall type ventilator with heat exchange, ventilation unit with heat exchange. Looking for energy saving, comfortable way of ventilation, the application effect of the way of ventilation is evaluated in air distribution and comfort performance and the initial investment by FLUENT software. The conclusion is that the mode of ventilation unit with heat exchange has higher superiority compared with the others.

  10. Entrainment Rate in Shallow Cumuli: Dependence on Entrained Dry Air Sources and Probability Density Functions

    NASA Astrophysics Data System (ADS)

    Lu, C.; Liu, Y.; Niu, S.; Vogelmann, A. M.

    2012-12-01

    In situ aircraft cumulus observations from the RACORO field campaign are used to estimate entrainment rate for individual clouds using a recently developed mixing fraction approach. The entrainment rate is computed based on the observed state of the cloud core and the state of the air that is laterally mixed into the cloud at its edge. The computed entrainment rate decreases when the air is entrained from increasing distance from the cloud core edge; this is because the air farther away from cloud edge is drier than the neighboring air that is within the humid shells around cumulus clouds. Probability density functions of entrainment rate are well fitted by lognormal distributions at different heights above cloud base for different dry air sources (i.e., different source distances from the cloud core edge). Such lognormal distribution functions are appropriate for inclusion into future entrainment rate parameterization in large scale models. To the authors' knowledge, this is the first time that probability density functions of entrainment rate have been obtained in shallow cumulus clouds based on in situ observations. The reason for the wide spread of entrainment rate is that the observed clouds are affected by entrainment mixing processes to different extents, which is verified by the relationships between the entrainment rate and cloud microphysics/dynamics. The entrainment rate is negatively correlated with liquid water content and cloud droplet number concentration due to the dilution and evaporation in entrainment mixing processes. The entrainment rate is positively correlated with relative dispersion (i.e., ratio of standard deviation to mean value) of liquid water content and droplet size distributions, consistent with the theoretical expectation that entrainment mixing processes are responsible for microphysics fluctuations and spectral broadening. The entrainment rate is negatively correlated with vertical velocity and dissipation rate because entrainment

  11. Value impact analysis of Generic Issue 143, Availability of Heating, Ventilation, Air Conditioning (HVAC) and Chilled Water Systems

    SciTech Connect

    Daling, P.M.; Marler, J.E.; Vo, T.V.; Phan, H.; Friley, J.R.

    1993-11-01

    This study evaluates the values (benefits) and impacts (costs) associated with potential resolutions to Generic Issue 143, ``Availability of HVAC and Chilled Water Systems.`` The study identifies vulnerabilities related to failures of HVAC, chilled water, and room cooling systems; develops estimates of room heatup rates and safety-related equipment vulnerabilities following losses of HVAC/room cooler systems; develops estimates of the core damage frequencies and public risks associated with failures of these systems; develops three proposed resolution strategies to this generic issue; and performs a value/impact analysis of the proposed resolutions. Existing probabilistic risk assessments for four representative plants, including one plant from each vendor, form the basis for the core damage frequency and public risk calculations. Both internal and external events were considered. It was concluded that all three proposed resolution strategies exceed the $1,000/person-rem cost-effectiveness ratio. Additional evaluations were performed to develop ``generic`` insights on potential design-related and configuration-related vulnerabilities and potential high-frequency ({approximately}1E-04/RY) accident sequences that involve failures of HVAC/room cooling functions. It was concluded that, although high-frequency accident sequences may exist at some plants, these high-frequency sequences are plant-specific in nature or have been resolved through hardware and/or operational changes. The plant-specific Individual Plant Examinations are an effective vehicle for identification and resolution of these plant-specific anomalies and hardware configurations.

  12. Ventilation requirements for control of occupancy odor and tobacco smoke odor: laboratory studies. Final report

    SciTech Connect

    Cain, W.S.; Isseroff, R.; Leaderer, B.P.; Lipsitt, E.D.; Huey, R.J.; Perlman, D.; Bergland, L.G.; Dunn, J.D.

    1981-04-01

    Experiments on occupancy odor addressed the question of why required ventilation rate per occupant increased progressively with increases in the number of persons in a space. In order to investigate ventilation requirements under approximately ideal conditions, we constructed an aluminum-lined environmental chamber with excellent control over environmental conditions and a ventilation system that provided rapid and uniform mixing of air. Psychophysical experiments on occupancy odor explored 47 different combinations of occupancy density, temperature and humidity, and ventilation rate. The experiments collected judgements both from visitors, who smelled air from the chamber only once every few minutes, and from occupants, who remained in the chamber for an hour at a time. The judgements of visitors revealed that occupancy odor increased only gradually over time and rarely reached very high or objectionable levels. Judgements of occupants also revealed rather minor dissatisfaction. Only during combinations of high temperature and humidity did objectionability become more than a minor issue to either group. Experiments on cigarette smoking explored rates of 4, 8, and 16 cigarettes per hour under various environmental conditions and with ventilation rates as high as 68 cfm (34 L.s/sup -1/) per occupant. As soon as occupants lit cigarettes in the chamber, the odor level increased dramatically. At ventilation rates far greater than necessary to control occupancy odor, the odor from cigarette smoking remained quite intense. In general, the odor proved impossible to control adequately even with a ventilation rate of 68 cfm (34 L.s/sup -1/) per occupant (4 occupants) and even when only one occupant smoked at a time. As in the case of occupancy odor, a combination of high temperature and humidity exacerbated the odor problem.

  13. Air

    MedlinePlus

    ... do to protect yourself from dirty air . Indoor air pollution and outdoor air pollution Air can be polluted indoors and it can ... this chart to see what things cause indoor air pollution and what things cause outdoor air pollution! Indoor ...

  14. A technique for the local measurement of air kerma rate from small Caesium-137 sources.

    PubMed

    Aukett, R J

    1991-10-01

    A method is described in which a Farmer ionization chamber is used for the direct measurement of the air kerma rate in air from small spherical Caesium-137 sources at distances of 35 to 70 mm. The calibration factor and corrections for source and ion chamber geometry are examined. For quality assurance purposes, the results obtained are in sufficient agreement with other methods of calibration.

  15. On the accuracy of the rate coefficients used in plasma fluid models for breakdown in air

    NASA Astrophysics Data System (ADS)

    Kourtzanidis, Konstantinos; Raja, Laxminarayan L.

    2016-07-01

    The electrical breakdown of air depends on the balance between creation and loss of charged particles. In fluid models, datasets of the rate coefficients used are obtained either from fits to experimental data or by solutions of the Boltzmann equation. Here, we study the accuracy of the commonly used models for ionization and attachment frequencies and their impact on the prediction of the breakdown threshold for air. We show that large errors can occur depending on the model and propose the most accurate dataset available for modeling of air breakdown phenomena.

  16. Cooling Rates of Humans in Air and in Water: An Experiment

    NASA Astrophysics Data System (ADS)

    Bohren, Craig F.

    2012-12-01

    In a previous article I analyzed in detail the physical factors resulting in greater cooling rates of objects in still water than in still air, emphasizing cooling of the human body. By cooling rate I mean the rate of decrease of core temperature uncompensated by metabolism. I concluded that the "correct ratio for humans is closer to 2 than to 10." To support this assertion I subsequently did experiments, which I report following a digression on hypothermia.

  17. [Home mechanical ventilation-tracheostomy ventilation, for the long-term and variation].

    PubMed

    Yamamoto, Makoto

    2006-12-01

    We experienced long-term ventilation for 30 patients mostly with amyotrophic lateral sclerosis (ALS). For long-term ventilation by tracheostomy positive pressure ventilation (TPPV), we must set tidal volume (TV) over 600 ml, because setting 400 ml as TV usually applied in Japan, often develops atelectasis which causes frequent or serious pneumonia. To avoid both the elevation of airway pressure and hyper ventilation, the following intervals are needed: 10 times/min for breathing frequency and 2 seconds for exhaling time. In the cases with ventilator induced lung injury (VILI), it is necessary to lower the TV and to treat with steroid pulse therapy. In the transitional stage from non-invasive positive pressure ventilation (NPPV) to TPPV, we conduct tracheostomy for suction of the sputum. In that stage, by using a cuffless tracheal canule, we can continue NPPV. As another method in that stage, we recommend biphasic management by NPPV at daytime and TPPV at nighttime with a bi-level ventilator. This method can provide certain ventilation also during sleep. When the respiratory failure proceeds further, we manage the ventilation with a bi-level ventilator on TPPV, because a bi-level ventilator is also good adapting to assist spontaneous breathing in that stage. And if the patient does not have bulbar paralysis, the patient can utter by air leakage with using bi-level ventilator and flattening the cuff of the tracheal canule. PMID:17469348

  18. Carbon dioxide and oxygen levels in disposable individually ventilated cages after removal from mechanical ventilation.

    PubMed

    Nagamine, Claude M; Long, C Tyler; McKeon, Gabriel P; Felt, Stephen A

    2012-03-01

    Disposable individually ventilated cages have lids that restrict air exchange when the cage is not mechanically ventilated. This design feature may cause intracage CO2 to increase and O2 to decrease (hypercapnic and hypoxic conditions, respectively) when the electrical supply to the ventilated rack fails, the ventilated rack malfunctions, cages are docked in the rack incorrectly, or cages are removed from the ventilated rack for extended periods of time. We investigated how quickly hypercapnic and hypoxic conditions developed within disposable individually ventilated cages after removal from mechanical ventilation and compared the data with nondisposable static cages, disposable static cages, and unventilated nondisposable individually ventilated cages. When disposable individually ventilated cages with 5 adult mice per cage were removed from mechanical ventilation, CO2 concentrations increased from less than 1% at 0 h to approximately 5% at 3 h and O2 levels dropped from more than 20% at 0 h to 11.7% at 6 h. The breathing pattern of the mice showed a prominent abdominal component (hyperventilation). Changes were similar for 4 adult mice per cage, reaching at least 5% CO2 at 4 h and 13.0% O2 at 6 h. For 3 or 2 mice per cage, values were 4.6% CO2 and 14.7% O2 and 3.04% CO2 and 17.1% O2, respectively, at 6 h. These results document that within disposable individually ventilated cages, a hypercapnic and hypoxic microenvironment develops within hours in the absence of mechanical ventilation.

  19. Night ventilation control strategies in office buildings

    SciTech Connect

    Wang, Zhaojun; Yi, Lingli; Gao, Fusheng

    2009-10-15

    In moderate climates night ventilation is an effective and energy-efficient approach to improve the indoor thermal environment for office buildings during the summer months, especially for heavyweight construction. However, is night ventilation a suitable strategy for office buildings with lightweight construction located in cold climates? In order to answer this question, the whole energy-consumption analysis software EnergyPlus was used to simulate the indoor thermal environment and energy consumption in typical office buildings with night mechanical ventilation in three cities in northern China. The summer outdoor climate data was analyzed, and three typical design days were chosen. The most important factors influencing night ventilation performance such as ventilation rates, ventilation duration, building mass and climatic conditions were evaluated. When night ventilation operation time is closer to active cooling time, the efficiency of night ventilation is higher. With night ventilation rate of 10 ach, the mean radiant temperature of the indoor surface decreased by up to 3.9 C. The longer the duration of operation, the more efficient the night ventilation strategy becomes. The control strategies for three locations are given in the paper. Based on the optimized strategies, the operation consumption and fees are calculated. The results show that more energy is saved in office buildings cooled by a night ventilation system in northern China than ones that do not employ this strategy. (author)

  20. The rate of pressure rise of gaseous propylene-air explosions in spherical and cylindrical enclosures.

    PubMed

    Razus, Domnina; Movileanua, Codina; Oancea, Dumitru

    2007-01-01

    The maximum rates of pressure rise of propylene-air explosions at various initial pressures and various fuel/oxygen ratios in three closed vessels (a spherical vessel with central ignition and two cylindrical vessels with central or with top ignition) are reported. It was found that in explosions of quiescent mixtures the maximum rates of pressure rise are linear functions on total initial pressure, at constant initial temperature and fuel/oxygen ratio. The slope and intercept of found correlations are greatly influenced by vessel's volume and shape and by the position of the ignition source--factors which determine the amount of heat losses from the burned gas in a closed vessel explosion. Similar data on propylene-air inert mixtures are discussed in comparison with those referring to propylene-air, revealing the influence of nature and amount of inert additive. The deflagration index KG of centrally ignited explosions was also calculated from maximum rates of pressure rise. PMID:16876946

  1. The rate of pressure rise of gaseous propylene-air explosions in spherical and cylindrical enclosures.

    PubMed

    Razus, Domnina; Movileanua, Codina; Oancea, Dumitru

    2007-01-01

    The maximum rates of pressure rise of propylene-air explosions at various initial pressures and various fuel/oxygen ratios in three closed vessels (a spherical vessel with central ignition and two cylindrical vessels with central or with top ignition) are reported. It was found that in explosions of quiescent mixtures the maximum rates of pressure rise are linear functions on total initial pressure, at constant initial temperature and fuel/oxygen ratio. The slope and intercept of found correlations are greatly influenced by vessel's volume and shape and by the position of the ignition source--factors which determine the amount of heat losses from the burned gas in a closed vessel explosion. Similar data on propylene-air inert mixtures are discussed in comparison with those referring to propylene-air, revealing the influence of nature and amount of inert additive. The deflagration index KG of centrally ignited explosions was also calculated from maximum rates of pressure rise.

  2. Worker performance and ventilation in a call center: Analyses of work performance data for registered nurses

    SciTech Connect

    Federspiel, C.C.; Fisk, W.J.; Price, P.N.; Liu, G.; Faulkner, D.; Dibartolomeo, D.L.; Sullivan, D.P.; Lahiff, M.

    2004-05-01

    We investigated the relationship between ventilation rates and individual work performance in a call center, and controlled for other factors of the indoor environment. We randomized the position of the outdoor air control dampers, and measured ventilation rate, differential (indoor minus outdoor) carbon dioxide ({Delta}CO{sub 2}) concentration, supply air velocity, temperature, humidity, occupant density, degree of under-staffing, shift length, time of day, and time required to complete two different work performance tasks (talking with clients and post-talk wrap-up to process information). {Delta}CO{sub 2} concentrations ranged from 13 to 611 ppm. We used multi-variable regression to model the association between the predictors and the responses. We found that agents performed talk tasks fastest when the ventilation rate was highest, but that the relationship between talk performance and ventilation was not strong or monotonic. We did not find a statistically significant association between wrap-up performance and ventilation rate. Agents were slower at the wrap-up task when the temperature was high (>25.4 C). Agents were slower at wrap-up during long shifts and when the call center was under-staffed.

  3. Effects of Methadone on the Minimum Anesthetic Concentration of Isoflurane, and Its Effects on Heart Rate, Blood Pressure and Ventilation during Isoflurane Anesthesia in Hens (Gallus gallus domesticus)

    PubMed Central

    Pypendop, Bruno Henri; Zangirolami Filho, Darcio; Sousa, Samuel Santos; Valadão, Carlos Augusto Araújo

    2016-01-01

    The aim of this study was to measure the temporal effects of intramuscular methadone administration on the minimum anesthetic concentration (MAC) of isoflurane in hens, and to evaluate the effects of the isoflurane-methadone combination on heart rate and rhythm, blood pressure and ventilation. Thirteen healthy adult hens weighing 1.7 ± 0.2 kg were used. The MAC of isoflurane was determined in each individual using the bracketing method. Subsequently, the reduction in isoflurane MAC produced by methadone (3 or 6 mg kg-1, IM) was determined by the up-and-down method. Stimulation was applied at 15 and 30 minutes, and at 45 minutes if the bird had not moved at 30 minutes. Isoflurane MAC reduction was calculated at each time point using logistic regression. After a washout period, birds were anesthetized with isoflurane and methadone, 6 mg kg-1 IM was administered. Heart rate and rhythm, respiratory rate, blood gas values and invasive blood pressure were measured at 1.0 and 0.7 isoflurane MAC, and during 45 minutes after administration of methadone once birds were anesthetized with 0.7 isoflurane MAC. Fifteen minutes after administration of 3 mg kg-1 of methadone, isoflurane MAC was reduced by 2 (-9 to 13)% [logistic regression estimate (95% Wald confidence interval)]. Administration of 6 mg kg-1 of methadone decreased isoflurane MAC by 29 (11 to 46)%, 27 (-3 to 56)% and 10 (-8 to 28)% after 15, 30 and 45 minutes, respectively. Methadone (6 mg kg-1) induced atrioventricular block in three animals and ventricular premature contractions in two. Methadone caused an increase in arterial blood pressure and arterial partial pressure of carbon dioxide, while heart rate and pH decreased. Methadone, 6 mg kg-1 IM significantly reduced isoflurane MAC by 30% in hens 15 minutes after administration. At this dose, methadone caused mild respiratory acidosis and increase in systemic blood pressure. PMID:27018890

  4. Long-term dynamics of death rates of emphysema, asthma, and pneumonia and improving air quality

    PubMed Central

    Kravchenko, Julia; Akushevich, Igor; Abernethy, Amy P; Holman, Sheila; Ross, William G; Lyerly, H Kim

    2014-01-01

    Background The respiratory tract is a major target of exposure to air pollutants, and respiratory diseases are associated with both short- and long-term exposures. We hypothesized that improved air quality in North Carolina was associated with reduced rates of death from respiratory diseases in local populations. Materials and methods We analyzed the trends of emphysema, asthma, and pneumonia mortality and changes of the levels of ozone, sulfur dioxide (SO2), nitrogen dioxide (NO2), carbon monoxide (CO), and particulate matters (PM2.5 and PM10) using monthly data measurements from air-monitoring stations in North Carolina in 1993–2010. The log-linear model was used to evaluate associations between air-pollutant levels and age-adjusted death rates (per 100,000 of population) calculated for 5-year age-groups and for standard 2000 North Carolina population. The studied associations were adjusted by age group-specific smoking prevalence and seasonal fluctuations of disease-specific respiratory deaths. Results Decline in emphysema deaths was associated with decreasing levels of SO2 and CO in the air, decline in asthma deaths–with lower SO2, CO, and PM10 levels, and decline in pneumonia deaths–with lower levels of SO2. Sensitivity analyses were performed to study potential effects of the change from International Classification of Diseases (ICD)-9 to ICD-10 codes, the effects of air pollutants on mortality during summer and winter, the impact of approach when only the underlying causes of deaths were used, and when mortality and air-quality data were analyzed on the county level. In each case, the results of sensitivity analyses demonstrated stability. The importance of analysis of pneumonia as an underlying cause of death was also highlighted. Conclusion Significant associations were observed between decreasing death rates of emphysema, asthma, and pneumonia and decreases in levels of ambient air pollutants in North Carolina. PMID:25018627

  5. Multifamily Individual Heating and Ventilation Systems, Lawrence, Massachusetts (Fact Sheet)

    SciTech Connect

    Not Available

    2013-11-01

    The conversion of an older Massachusetts building into condominiums illustrates a safe, durable, and cost-effective solution for heating and ventilation systems that can potentially benefit millions of multifamily buildings. Merrimack Valley Habitat for Humanity (MVHfH) partnered with U.S. Department of Energy Building America team Building Science Corporation (BSC) to provide high performance affordable housing for 10 families in the retrofit of an existing mass masonry building (a former convent). The original ventilation design for the project was provided by a local engineer and consisted of a single large heat recovery ventilator (HRV) located in a mechanical room in the basement with a centralized duct system providing supply air to the main living space and exhausting stale air from the single bathroom in each apartment. This design was deemed to be far too costly to install and operate for several reasons: the large central HRV was oversized and the specified flows to each apartment were much higher than the ASHRAE 62.2 rate; an extensive system of ductwork, smoke and fire dampers, and duct chases were specified; ductwork required a significant area of dropped ceilings; and the system lacked individual ventilation control in the apartments

  6. Air pollutant emission rates for sources at the Deaf Smith County repository site

    SciTech Connect

    Not Available

    1985-11-01

    This document summarizes the air-quality source terms used for the Deaf Smith County, Texas environmental assessment report and explains their derivation. The engineering data supporting these source terms appear as appendixes to this report and include summary equipment lists for the repository and detailed equipment lists for the exploratory shaft. Although substantial work has been performed in establishing the current repository design, a greater effort will be required for the final design. Consequently, the repository emission rates presented here should be considered as preliminary estimates. Another set of air pollution emission rates will be calculated after design data are more firmly established. 18 refs., 15 tabs.

  7. Infiltration in ASHRAE's Residential Ventilation Standards

    SciTech Connect

    Sherman, Max

    2008-10-01

    The purpose of ventilation is to dilute or remove indoor contaminants that an occupant could be exposed to. It can be provided by mechanical or natural means. ASHRAE Standards including standards 62, 119, and 136 have all considered the contribution of infiltration in various ways, using methods and data from 20 years ago. The vast majority of homes in the United States and indeed the world are ventilated through natural means such as infiltration caused by air leakage. Newer homes in the western world are tight and require mechanical ventilation. As we seek to provide acceptable indoor air quality at minimum energy cost, it is important to neither over-ventilate norunder-ventilate. Thus, it becomes critically important to correctly evaluate the contribution infiltration makes to both energy consumption and equivalent ventilation. ASHRAE Standard 62.2 specifies how much mechanical ventilation is considered necessary to provide acceptable indoor air quality, but that standard is weak on how infiltration can contribute towards meeting the total requirement. In the past ASHRAE Standard 136 was used to do this, but new theoretical approaches and expanded weather data have made that standard out of date. This article will describe how to properly treat infiltration as an equivalent ventilation approach and then use new data and these new approaches to demonstrate how these calculations might be done both in general and to update Standard 136.

  8. Ventilation rates and activity levels of juvenile jumbo squid under metabolic suppression in the oxygen minimum zone.

    PubMed

    Trübenbach, Katja; Pegado, Maria R; Seibel, Brad A; Rosa, Rui

    2013-02-01

    The Humboldt (jumbo) squid, Dosidicus gigas, is a part-time resident of the permanent oxygen minimum zone (OMZ) in the Eastern Tropical Pacific and, thereby, it encounters oxygen levels below its critical oxygen partial pressure. To better understand the ventilatory mechanisms that accompany the process of metabolic suppression in these top oceanic predators, we exposed juvenile D. gigas to the oxygen levels found in the OMZ (1% O(2), 1 kPa, 10 °C) and measured metabolic rate, activity cycling patterns, swimming mode, escape jet (burst) frequency, mantle contraction frequency and strength, stroke volume and oxygen extraction efficiency. In normoxia, metabolic rate varied between 14 and 29 μmol O(2) g(-1) wet mass h(-1), depending on the level of activity. The mantle contraction frequency and strength were linearly correlated and increased significantly with activity level. Additionally, an increase in stroke volume and ventilatory volume per minute was observed, followed by a mantle hyperinflation process during high activity periods. Squid metabolic rate dropped more than 75% during exposure to hypoxia. Maximum metabolic rate was not achieved under such conditions and the metabolic scope was significantly decreased. Hypoxia changed the relationship between mantle contraction strength and frequency from linear to polynomial with increasing activity, indicating that, under hypoxic conditions, the jumbo squid primarily increases the strength of mantle contraction and does not regulate its frequency. Under hypoxia, jumbo squid also showed a larger inflation period (reduced contraction frequency) and decreased relaxed mantle diameter (shortened diffusion pathway), which optimize oxygen extraction efficiency (up to 82%/34%, without/with consideration of 60% potential skin respiration). Additionally, they breathe 'deeply', with more powerful contractions and enhanced stroke volume. This deep-breathing behavior allows them to display a stable ventilatory volume per

  9. Ventilation Model and Analysis Report

    SciTech Connect

    V. Chipman

    2003-07-18

    This model and analysis report develops, validates, and implements a conceptual model for heat transfer in and around a ventilated emplacement drift. This conceptual model includes thermal radiation between the waste package and the drift wall, convection from the waste package and drift wall surfaces into the flowing air, and conduction in the surrounding host rock. These heat transfer processes are coupled and vary both temporally and spatially, so numerical and analytical methods are used to implement the mathematical equations which describe the conceptual model. These numerical and analytical methods predict the transient response of the system, at the drift scale, in terms of spatially varying temperatures and ventilation efficiencies. The ventilation efficiency describes the effectiveness of the ventilation process in removing radionuclide decay heat from the drift environment. An alternative conceptual model is also developed which evaluates the influence of water and water vapor mass transport on the ventilation efficiency. These effects are described using analytical methods which bound the contribution of latent heat to the system, quantify the effects of varying degrees of host rock saturation (and hence host rock thermal conductivity) on the ventilation efficiency, and evaluate the effects of vapor and enhanced vapor diffusion on the host rock thermal conductivity.

  10. Development of a Residential Integrated Ventilation Controller

    SciTech Connect

    Staff Scientist; Walker, Iain; Sherman, Max; Dickerhoff, Darryl

    2011-12-01

    The goal of this study was to develop a Residential Integrated Ventilation Controller (RIVEC) to reduce the energy impact of required mechanical ventilation by 20percent, maintain or improve indoor air quality and provide demand response benefits. This represents potential energy savings of about 140 GWh of electricity and 83 million therms of natural gas as well as proportional peak savings in California. The RIVEC controller is intended to meet the 2008 Title 24 requirements for residential ventilation as well as taking into account the issues of outdoor conditions, other ventilation devices (including economizers), peak demand concerns and occupant preferences. The controller is designed to manage all the residential ventilation systems that are currently available. A key innovation in this controller is the ability to implement the concept of efficacy and intermittent ventilation which allows time shifting of ventilation. Using this approach ventilation can be shifted away from times of high cost or high outdoor pollution towards times when it is cheaper and more effective. Simulations, based on the ones used to develop the new residential ventilation requirements for the California Buildings Energy code, were used to further define the specific criteria and strategies needed for the controller. These simulations provide estimates of the energy, peak power and contaminant improvement possible for different California climates for the various ventilation systems. Results from a field test of the prototype controller corroborate the predicted performance.

  11. Shut-off mechanism for ventilation hose

    SciTech Connect

    Huyett, J.D.; Meskanick, G.R.

    1989-12-07

    A shut-off mechanism to provide automatic closure of a ventilation hose when the operation of drawing air through the hose is terminated. The mechanism includes a tube of light gauge metal inside of which are mounted a plurality of louver doors positioned in the closed position due to gravity when the ventilation unit is not operational. When the unit is operational, air flowing into the unit maintains the doors in the open position. 5 figs.

  12. Diaphragmatic contraction during assisted mechanical ventilation.

    PubMed

    Flick, G R; Bellamy, P E; Simmons, D H

    1989-07-01

    Indirect evidence from airway pressure recordings in mechanically ventilated patients suggests that the diaphragm exhibits contractile activity beyond that required to trigger a ventilator-assisted breath. We used the diaphragmatic EMG to provide direct evidence of persistent contractile activity and studied the effects of alterations in ventilator-delivered flow rate and tidal volume on the duration of diaphragmatic contraction. The duration of contraction was expressed in terms of inspired volume. During a single breath, diaphragmatic force generation ceases at the point of peak electromyographic activity; hence, the inspired volume at peak EMG is the volume at the diaphragmatic off-switch (Voff). Ventilator-delivered flow rate and tidal volume were varied during assisted (patient-initiated) and controlled (ventilator-initiated) breaths while diaphragmatic EMG and inspired volume were recorded simultaneously in ten patients with a variety of illnesses requiring mechanical ventilation. Spontaneous ventilator-unassisted breaths were also recorded for comparison. We found that (1) during assisted breaths, diaphragmatic activity continued after the ventilator was triggered, (2) Voff was usually close to spontaneous tidal volume, (3) Voff increased significantly as ventilator-delivered flow rate increased, and (4) controlled breaths may also be associated with phasic electromyographic activity. The data have implications for resting patients on assisted ventilation.

  13. Contaminants in ventilated filling boxes

    NASA Astrophysics Data System (ADS)

    Bolster, D. T.; Linden, P. F.

    While energy efficiency is important, the adoption of energy-efficient ventilation systems still requires the provision of acceptable indoor air quality. Many low-energy systems, such as displacement or natural ventilation, rely on temperature stratification within the interior environment, always extracting the warmest air from the top of the room. Understanding buoyancy-driven convection in a confined ventilated space is key to understanding the flow that develops with many of these modern low-energy ventilation schemes. In this work we study the transport of an initially uniformly distributed passive contaminant in a displacement-ventilated space. Representing a heat source as an ideal sourced of buoyancy, analytical and numerical models are developed that allow us to compare the average efficiency of contaminant removal between traditional mixing and modern low-energy systems. A set of small-scale analogue laboratory experiments was also conducted to further validate our analytical and numerical solutions.We find that on average traditional and low-energy ventilation methods are similar with regard to pollutant flushing efficiency. This is because the concentration being extracted from the system at any given time is approximately the same for both systems. However, very different vertical concentration gradients exist. For the low-energy system, a peak in contaminant concentration occurs at the temperature interface that is established within the space. This interface is typically designed to sit at some intermediate height in the space. Since this peak does not coincide with the extraction point, displacement ventilation does not offer the same benefits for pollutant flushing as it does for buoyancy removal.

  14. Effects of saline-water flow rate and air speed on leakage current in RTV coatings

    SciTech Connect

    Kim, S.H.; Hackam, R.

    1995-10-01

    Room temperature vulcanizing (RTV) silicone rubber is increasingly being used to coat porcelain and glass insulators in order to improve their electrical performance in the presence of pollution and moisture. A study of the dependence of leakage current, pulse current count and total charge flowing across the surface of RTV on the flow rate of the saline water and on the compressed air pressure used to create the salt-fog is reported. The fog was directed at the insulating rods either from one or two sides. The RTV was fabricated from polydimethylsiloxane polymer, a filler of alumina trihydrate (ATH), a polymerization catalyst and fumed silica reinforcer, all dispersed in 1,1,1-trichloroethane solvent. The saline water flow rate was varied in the range 0.4 to 2.0 l/min. The compressed air pressure at the input of the fog nozzles was varied from 0.20 to 0.63 MPa. The air speed at the surface of the insulating rods was found to depend linearly on the air pressure measured at the inlet to the nozzles and varied in the range 3 to 14 km/hr. The leakage current increased with increasing flow rate and increasing air speed. This is attributed to the increased loss of hydrophobicity with a larger quantity of saline fog and a larger impact velocities of fog droplets interacting with the surface of the RTV coating.

  15. EFFECT OF AIR-POLLUTION CONTROL ON DEATH RATES IN DUBLIN, IRELAND: AN INTERVENTION STUDY. (R827353C006)

    EPA Science Inventory

    Background Particulate air pollution episodes have been associated with increased daily death. However, there is little direct evidence that diminished particulate air pollution concentrations would lead to reductions in death rates. We assessed the effect of ...

  16. Response of heart rate and cloacal ventilation in the bimodally respiring freshwater turtle, Rheodytes leukops, to experimental changes in aquatic PO2.

    PubMed

    Gordos, Matthew A; Limpus, Colin J; Franklin, Craig E

    2006-01-01

    Changes in heart rate (f(H)) and cloacal ventilation frequency (f(C)) were investigated in the Fitzroy turtle, Rheodytes leukops, under normoxic (17.85 kPa) and hypoxic (3.79 kPa) conditions at 25 degrees C. Given R. leukops' high reliance on aquatic respiration via the cloacal bursae, the objective of this study was to examine the effect of varying aquatic PO(2) levels upon the expression of a bradycardia in a freely diving, bimodally respiring turtle. In normoxia, mean diving f(H) and f(C) for R. leukops remained constant with increasing submergence length, indicating that a bradycardia failed to develop during extended dives of up to 3 days. Alternatively, exposure to aquatic hypoxia resulted in the expression of a bradycardia as recorded by a decreasing mean diving f(H) with increasing dive duration. The observed bradycardia is attributed to a hypoxic-induced metabolic depression, possibly facilitated by a concurrent decrease in f(C). Results suggest that R. leukops alters its strategy from aquatic O(2) extraction via cloacal respiration in normoxia to O(2) conservation when exposed to aquatic hypoxia for the purpose of extending dive duration. Upon surfacing, a significant tachycardia was observed for R. leukops regardless of aquatic PO(2), presumably functioning to rapidly equilibrate blood and tissue gas tensions with alveolar gas to reduce surfacing duration. PMID:16235043

  17. Research review: Indoor air quality control techniques

    SciTech Connect

    Fisk, W.J.

    1986-10-01

    Techniques for controlling the concentration of radon, formaldehyde, and combustion products in the indoor air are reviewed. The most effective techniques, which are generally based on limiting or reducing indoor pollutant source strengths, can decrease indoor pollutant concentrations by a factor of 3 to 10. Unless the initial ventilation rate is unusually low, it is difficult to reduce indoor pollutant concentrations more than approximately 50% by increasing the ventilation rate of an entire building. However, the efficiency of indoor pollutant control by ventilation can be enhanced through the use of local exhaust ventilation near concentrated sources of pollutants, by minimizing short circuiting of air from supply to exhaust when pollutant sources are dispersed and, in some situations, by promoting a displacement flow of air and pollutants toward the exhaust. Active air cleaning is also examined briefly. Filtration and electrostatic air cleaning for removal of particles from the indoor air are the most practical and effective currently available techniques of air cleaning. 49 refs., 7 figs.

  18. THE EFFECT OF OPENING WINDOWS ON AIR CHANGE RATES IN TWO HOMES

    EPA Science Inventory

    Over 300 air change rate experiments were completed in two occupied residences: a two-story detached house in Redwood City, CA and a three-story townhouse in Reston, VA. A continuous monitor was used to measure the decay of sulfur hexafluoride tracer gas over periods of 1 to 1...

  19. Formaldehyde and acetaldehyde exposure mitigation in US residences: In-home measurements of ventilation control and source control

    SciTech Connect

    Hult, Erin L.; Willem, Henry; Price, Phillip N.; Hotchi, Toshifumi; Russell, Marion L.; Singer, Brett C.

    2014-10-01

    Measurements were taken in new US residences to assess the extent to which ventilation and source control can mitigate formaldehyde exposure. Increasing ventilation consistently lowered indoor formaldehyde concentrations. However, at a reference air exchange rate of 0.35 h-1, increasing ventilation was up to 60% less effective than would be predicted if the emission rate were constant. This is consistent with formaldehyde emission rates decreasing as air concentrations increase, as observed in chamber studies. In contrast, measurements suggest acetaldehyde emission was independent of ventilation rate. To evaluate the effectiveness of source control, formaldehyde concentrations were measured in Leadership in Energy and Environmental Design (LEED) certified/Indoor airPLUS homes constructed with materials certified to have low emission rates of volatile organic compounds (VOC). At a reference air exchange rate of 0.35 h-1, and adjusting for home age, temperature and relative humidity, formaldehyde concentrations in homes built with low-VOC materials were 42% lower on average than in reference new homes with conventional building materials. Without adjustment, concentrations were 27% lower in the low-VOC homes. The mean and standard deviation of formaldehyde concentration were 33 μg m-3 and 22 μg m-3 for low-VOC homes and 45 μg m-3 and 30 μg m-3 for conventional.

  20. Maximum sustainable work rate for five protective clothing ensembles with respect to moisture vapor transmission rate and air permeability.

    PubMed

    Gonzalez, Nancy W; Bernard, Thomas E; Carroll, Nora L; Bryner, Michael A; Zeigler, James P

    2006-02-01

    The fabrics associated with protective clothing affect heat stress, which influences productivity and risks of heat-related disorders. This study compared the work limiting effects of five protective coveralls and a semiclothed condition (t-shirt and shorts). Two fabric characteristics determined from bench tests, moisture vapor transmission rate (MVTR), and air permeability were also examined as possible predictors of ensemble performance. A progressive metabolic rate protocol was used where environmentalconditions (T(db) = 32 degrees C; T(pwb) = 26 degrees C) were held constant while treadmill speed was slowly increased. The limiting metabolic rate to just maintain thermal equilibrium was the critical point. At this point, critical speed and critical metabolic rate were noted and total evaporative resistance was calculated for each ensemble. Five acclimatized subjects wore each of the six clothing conditions in a random order. Statistically significant differences were found among the five protective garments and a semiclothed ensemble for critical treadmill speed (S(crit)), critical metabolic rate (M(crit)), and total evaporative resistance (R(e-t)). The semiclothed condition (S(crit) = 1.77 m/sec; M(crit) = 580 W; R(e-t) = 0.0099 kPa m2/W) and ensembles made from spunbonded, melt blown, spunbonded polypropylene (SMS) (1.72 m/sec; 560 W; 0.0135 kPa m2/W) and spunbonded polypropylene (1.67 m/sec; 550 W; 0.0126 kPa m2/W) were able to support higher work rates than fabrics made from Tyvek 1422-A (a nonwoven spunbonded olefin) (1.48 m/sec; 470 W; 0.0183 kPa m2/W) and a microporous film supported by spunbonded polypropylene (1.34 m/sec; 420 W; 0.0231 kPa m2/W). A tightly woven polyester ensemble (1.59 m/sec; 510 W; 0.0130 kPa m2/W) had intermediate values and was not significantly different from either group. Air permeability was a better predictor of fabric work limiting performance than MVTR. An air permeability on the order of 10,000 L/min cm2 bar would have

  1. Multizone airflow and contaminant modeling: Performance of two common ventilation systems in Swedish apartment buildings

    SciTech Connect

    Herrlin, M.K.

    1999-07-01

    The goal of this work was to assess the performance of two common ventilation systems, an exhaust and an exhaust-supply system, in Swedish apartment buildings. Since correct air-exchange and interzonal airflows are important for removing contaminants and improving indoor air quality, these air flows were analyzed by systematic computer calculations when selected input parameters were varied around their default values. The research specifically involved establishing characteristics of a prototypical building, determining appropriate boundary conditions (climate and operation), developing necessary physical/mathematical models, and establishing a protocol for carrying out the parametric studies required to assess airflows in buildings of this type. The study results, though specific for the prototypical building, present useful generalities that allow substitutions to be made in working with comparable buildings. The exhaust ventilation system allows a pressure hierarchy that is beneficial for controlling interzonal airflows and exfiltration. This hierarchy, however, turns into a disadvantage when leakage levels are altered by closing ventilation slots, for example. The exhaust-supply ventilation system has the advantage of guaranteeing a minimum air-exchange rate under all conditions. A drawback of this system is that air flows from apartments on the lower levels to apartments on upper levels via the staircase. Because of this flow pattern, contaminants can be transported to upper-level apartments.

  2. Relationship between recycling rate and air pollution: Waste management in the state of Massachusetts

    SciTech Connect

    Giovanis, Eleftherios

    2015-06-15

    Highlights: • This study examines the relationship between recycling rate of solid waste and air pollution. • Fixed effects Stochastic Frontier Analysis model with panel data are employed. • The case study is a waste municipality survey in the state of Massachusetts during 2009–2012. • The findings support that a negative relationship between air pollution and recycling. - Abstract: This study examines the relationship between recycling rate of solid waste and air pollution using data from a waste municipality survey in the state of Massachusetts during the period 2009–2012. Two econometric approaches are applied. The first approach is a fixed effects model, while the second is a Stochastic Frontier Analysis (SFA) with fixed effects model. The advantage of the first approach is the ability of controlling for stable time invariant characteristics of the municipalities, thereby eliminating potentially large sources of bias. The second approach is applied in order to estimate the technical efficiency and rank of each municipality accordingly. The regressions control for various demographic, economic and recycling services, such as income per capita, population density, unemployment, trash services, Pay-as-you-throw (PAYT) program and meteorological data. The findings support that a negative relationship between particulate particles in the air 2.5 μm or less in size (PM{sub 2.5}) and recycling rate is presented. In addition, the pollution is increased with increases on income per capita up to $23,000–$26,000, while after this point income contributes positively on air quality. Finally, based on the efficiency derived by the Stochastic Frontier Analysis (SFA) model, the municipalities which provide both drop off and curbside services for trash, food and yard waste and the PAYT program present better performance regarding the air quality.

  3. Estimating the energy-saving benefit of reduced-flow and/or multi-speed commercial kitchen ventilation systems

    SciTech Connect

    Fisher, D.; Schmid, F.; Spata, A.J.

    1999-07-01

    Kitchen exhaust ventilation systems are recognized as a major energy user within commercial food service facilities and restaurants. Minimizing the design ventilation rate of an appliance/hood system by optimizing hood performance in the laboratory is a viable strategy for reducing the makeup air heating and cooling loads as well as the exhaust and supply fan energy. Cutting back the exhaust flow under conditions of noncooking (appliance idle) can further reduce the energy load associated with a kitchen ventilation system. An optimized, two-speed exhaust system was installed within the scope of an energy-efficient, quick service restaurant (QSR) design and demonstration project. This paper evaluates the energy benefit of this variable-flow strategy as well as the savings associated with reducing the design ventilation rate (compared to an off-the-shelf exhaust hood). The paper describes a new public-domain software tool for estimating heating and cooling loads associated with the makeup air requirements of commercial kitchens. This bin-based software provides ASHRAE engineers with an alternative to hand calculations or more sophisticated hour-by-hour simulation. The dramatic impact that both makeup air set point and geographic location have on the outdoor air load is illustrated. The paper concludes with an industry-wide projection of energy savings associated with optimizing the design and operation of commercial kitchen ventilation (CKV) systems.

  4. Effects of dissolved air flotation hydraulic loading rate on water treatment performance

    SciTech Connect

    Tobiason, J.E.; Edzwald, J.K.; Amato, T.; Maggi, L.J.

    1999-07-01

    The performance of dissolved air flotation (DAF) followed by granular media filtration for water treatment was evaluated via pilot-scale studies for two water sources. The study focused on short flocculation times (5--8 minutes), high DAF hydraulic loading rates (17--44 m/hr (7--18 gpm/ft{sup 2})) and rapid rate filtration (10--20 m/hr (4--8 gpm/ft{sup 2})). Excellent treatment performance was achieved in terms of DAF clarified water turbidity, filtered water turbidity, organic matter removal and filtered water production. Bubble carryover from the DAF tank was mitigated by employing either internal or external air removal strategies. Overall, the results demonstrate the effectiveness of an integrated, high rate flocculation/DAF/filtration water treatment strategy.

  5. The measurement of water vapour transfer rate through clothing system with air gap between layers

    NASA Astrophysics Data System (ADS)

    Oh, Ae-Gyeong

    2008-02-01

    The experiments described in this paper are designed to test the water vapour transfer rates through outdoor clothing system with air gap between layers under conditions more closely actual wear. It was adopted distance of 5 mm to ensure no disturbance of the air gap thickness between layers throughout the measurement period with all fabrics. The results have indicated that the water vapour transfer rates of clothing system decrease very slightly with time, it is shown that they approached nearly equilibrium state throughout the experiment. It is revealed that the water vapour transfer rates of the clothing system were ordered into groups determined by the type of waterproof breathable fabric as a shell layer being ordered.

  6. Energy and IAQ Implications of Residential Ventilation Cooling

    SciTech Connect

    Turner, William; Walker, Iain

    2014-08-01

    This study evaluates the energy, humidity and indoor air quality (IAQ) implications of residential ventilation cooling in all U.S. IECC climate zones. A computer modeling approach was adopted, using an advanced residential building simulation tool with airflow, energy and humidity models. An economizer (large supply fan) was simulated to provide ventilation cooling while outdoor air temperatures were lower than indoor air temperatures (typically at night). The simulations were performed for a full year using one-minute time steps to allow for scheduling of ventilation systems and to account for interactions between ventilation and heating/cooling systems.

  7. Rate constants for chemical reactions in high-temperature nonequilibrium air

    NASA Technical Reports Server (NTRS)

    Jaffe, R. L.

    1986-01-01

    In the nonequilibrium atmospheric chemistry regime that will be encountered by the proposed Aeroassisted Orbital Transfer Vehicle in the upper atmosphere, where air density is too low for thermal and chemical equilibrium to be maintained, the detailed high temperature air chemistry plays a critical role in defining radiative and convective heating loads. Although vibrational and electronic temperatures remain low (less than 15,000 K), rotational and translational temperatures may reach 50,000 K. Attention is presently given to the effects of multiple temperatures on the magnitudes of various chemical reaction rate constants, for the cases of both bimolecular exchange reactions and collisional excitation and dissociation reactions.

  8. Drip water electrical conductivity as an indicator of cave ventilation at the event scale.

    PubMed

    Smith, Andrew C; Wynn, Peter M; Barker, Philip A; Leng, Melanie J

    2015-11-01

    The use of speleothems to reconstruct past climatic and environmental change through chemical proxies is becoming increasingly common. Speleothem chemistry is controlled by hydrological and atmospheric processes which vary over seasonal time scales. However, as many reconstructions using speleothem carbonate are now endeavouring to acquire information about precipitation and temperature dynamics at a scale that can capture short term hydrological events, our understanding of within cave processes must match this resolution. Monitoring within Cueva de Asiul (N. Spain) has identified rapid (hourly resolution) changes in drip water electrical conductivity (EC), which is regulated by the pCO2 in the cave air. Drip water EC is therefore controlled by different modes of cave ventilation. In Cueva de Asiul a combination of density differences, and external pressure changes control ventilation patterns. Density driven changes in cave ventilation occur on a diurnal scale at this site irrespective of season, driven by fluctuations in external temperature across the cave internal temperature threshold. As external temperatures drop below those within the cave low pCO2 external air enters the void, facilitating the deposition of speleothem carbonate and causing a reduction in measured drip water EC. Additionally, decreases in external pressure related to storm activity act as a secondary ventilation mechanism. Reductions in external air pressure cause a drop in cave air pressure, enhancing karst air draw down, increasing the pCO2 of the cave and therefore the EC measured within drip waters. EC thereby serves as a first order indicator of cave ventilation, regardless of changes in speleothem drip rates and karst hydrological conditions. High resolution monitoring of cave drip water electrical conductivity reveals the highly sensitive nature of ventilation dynamics within cave environments, and highlights the importance of this for understanding trace element incorporation into

  9. Building America Top Innovations 2014 Profile: ASHRAE Standard 62.2. Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings

    SciTech Connect

    none,

    2014-11-01

    This 2014 Top Innovations profile describes Building America research and support in developing and gaining adoption of ASHRAE 62.2, a residential ventilation standard that is critical to transforming the U.S. housing industry to high-performance homes.

  10. Computational fluid dynamic modelling of the effect of ventilation mode and tracheal tube position on air flow in the large airways.

    PubMed

    Lumb, A B; Burns, A D; Figueroa Rosette, J A; Gradzik, K B; Ingham, D B; Pourkashanian, M

    2015-05-01

    We have used computational fluid dynamic modelling to study the effects of tracheal tube size and position on regional gas flow in the large airways. Using a three-dimensional mathematical model, we simulated flow with and without a tracheal tube, replicating both physiological and artificial breathing. Ventilation through a tracheal tube increased proportional flow to the left lung from 39.5% with no tube to 43.1-47.2%, depending on tube position. Ventilation mode and tube distance from the carina had no effect on flow. Lateral displacement and deflection of the tube increased ventilation to the ipsilateral lung; for example, when deflected 10° to the left of centre, flow to the left lung increased from 43.8 to 53.7%. Because of the small diameter of a tracheal tube relative to the trachea, gas exits a tube at high velocity such that regional ventilation may be affected by changes in the position and angle of the tube. PMID:25581493

  11. The utility of heart rate and minute ventilation as predictors of whole-body metabolic rate during occupational simulations involving load carriage.

    PubMed

    Notley, Sean R; Peoples, Gregory E; Taylor, Nigel A S

    2015-01-01

    The utility of cardiac and ventilatory predictors of metabolic rate derived under temperate and heated laboratory conditions was evaluated during three fire-fighting simulations (70-mm hose drag, Hazmat recovery, bushfire hose drag; N = 16 per simulation). The limits of agreement for cardiac (temperate: - 0.54 to 1.77; heated: - 1.39 to 0.80 l min(- 1)) and ventilatory surrogates (temperate: - 0.19 to 1.27; heated: - 0.26 to 1.16 l min(- 1)) revealed an over-estimation of oxygen consumption that exceeded the acceptable limits required by occupational physiologists (N = 25; ± 0.24 l min(- 1)). Although ventilatory predictions offered superior precision during low-intensity work (P < 0.05), a cardiac prediction was superior during more demanding work (P < 0.05). Deriving those equations under heated conditions failed to improve precision, with the exception of the cardiac surrogate during low-intensity work (P < 0.05). These observations imply that individualised prediction curves are necessary for valid estimations of metabolic demand in the field.

  12. The utility of heart rate and minute ventilation as predictors of whole-body metabolic rate during occupational simulations involving load carriage.

    PubMed

    Notley, Sean R; Peoples, Gregory E; Taylor, Nigel A S

    2015-01-01

    The utility of cardiac and ventilatory predictors of metabolic rate derived under temperate and heated laboratory conditions was evaluated during three fire-fighting simulations (70-mm hose drag, Hazmat recovery, bushfire hose drag; N = 16 per simulation). The limits of agreement for cardiac (temperate: - 0.54 to 1.77; heated: - 1.39 to 0.80 l min(- 1)) and ventilatory surrogates (temperate: - 0.19 to 1.27; heated: - 0.26 to 1.16 l min(- 1)) revealed an over-estimation of oxygen consumption that exceeded the acceptable limits required by occupational physiologists (N = 25; ± 0.24 l min(- 1)). Although ventilatory predictions offered superior precision during low-intensity work (P < 0.05), a cardiac prediction was superior during more demanding work (P < 0.05). Deriving those equations under heated conditions failed to improve precision, with the exception of the cardiac surrogate during low-intensity work (P < 0.05). These observations imply that individualised prediction curves are necessary for valid estimations of metabolic demand in the field. PMID:25746518

  13. Prevention of ventilator-associated pneumonia.

    PubMed

    Lau, Arthur C W; So, H M; Tang, S L; Yeung, Alwin; Lam, S M; Yan, W W

    2015-02-01

    Ventilator-associated pneumonia is the commonest, yet mostly preventable, infection in mechanically ventilated patients. Successful control of ventilator-associated pneumonia can save hospitalisation cost, and is possible by using a multidisciplinary clinical and administrative approach. The ventilator-associated pneumonia rate should be expressed as the number of ventilator-associated pneumonia days per 1000 ventilator days to take into account the device-utilisation duration for meaningful comparison. Various strategies address the issue, including general infection control measures, body positioning, intubation and mechanical ventilation, oral and gastro-intestinal tract, endotracheal tube, airway pressure, cuff pressure, selective digestive and/or oropharyngeal decontamination, and probiotic or early antibiotic treatment, as well as overall administration at a policy level. The rationale and controversy of these approaches are discussed in this article. The authors suggest that all units treating mechanically ventilated patients should have a ventilator-associated pneumonia prevention protocol in place, and ventilator-associated pneumonia should be seriously considered as a key performance indicator in local intensive care units.

  14. Influence of ventilation strategies on indoor radon concentrations based on a semiempirical model for Florida-style houses

    SciTech Connect

    Hintenlang, D.E.; Al-Ahmady, K.K.

    1994-04-01

    Measurements in a full-scale experimental facility are used to benchmark a semiempirical model for predicting indoor radon concentrations for Florida-style houses built using slab-on-grade construction. The model is developed to provide time-averaged indoor radon concentrations from quantitative relationships between the time-dependent radon entry and elimination mechanisms that have been demonstrated to be important for this style of residential construction. The model successfully predicts indoor radon concentrations in the research structure for several pressure and ventilation conditions. Parametric studies using the model illustrate how different ventilation strategies affect indoor radon concentrations. It is demonstrated that increasing house ventilation rates by increasing the effective leakage area of the house shell does not reduce indoor radon concentrations as effectively as increasing house ventilation rates by controlled duct ventilation associated with the heating, ventilating, and air conditioning system. The latter strategy provides the potential to minimize indoor radon concentrations while providing positive control over the quality of infiltration air. 9 refs., 5 figs.

  15. Smoking, air pollution, and the high rates of lung cancer in Shenyang, China

    SciTech Connect

    Xu, Z.Y.; Blot, W.J.; Xiao, H.P.; Wu, A.; Feng, Y.P.; Stone, B.J.; Sun, J.; Ershow, A.G.; Henderson, B.E.; Fraumeni, J.F. Jr. )

    1989-12-06

    A case-control study involving interviews with 1,249 patients with lung cancer and 1,345 population-based controls was conducted in Shenyang, an industrial city in northeastern China, where mortality rates are high among men and women. Cigarette smoking was found to be the principal cause of lung cancer in this population, accounting for 55% of the lung cancers in males and 37% in females. The attributable risk percentage among females is high compared to elsewhere in China, largely because of a higher prevalence of smoking among women. After adjustment for smoking, there were also significant increases in lung cancer risk associated with several measures of exposure to air pollutants. Risks were twice as high among those who reported smoky outdoor environments, and increased in proportion to years of sleeping on beds heated by coal-burning stoves (kang), and to an overall index of indoor air pollution. Threefold increases in lung cancer risk were found among men who worked in the nonferrous smelting industry, where heavy exposures to inorganic arsenic have been reported. The associations with both smoking and indoor air pollution were stronger for squamous cell and small cell carcinomas than for adenocarcinoma of the lung. Risks due to smoking or air pollution were not greatly altered by adjustment for consumption of fresh vegetables or sources of beta carotene or retinol, prior chronic lung diseases, or education level. The findings suggest that smoking and environmental pollution combine to account for the elevated rates of lung cancer mortality in Shenyang.

  16. Relationship between recycling rate and air pollution: Waste management in the state of Massachusetts.

    PubMed

    Giovanis, Eleftherios

    2015-06-01

    This study examines the relationship between recycling rate of solid waste and air pollution using data from a waste municipality survey in the state of Massachusetts during the period 2009-2012. Two econometric approaches are applied. The first approach is a fixed effects model, while the second is a Stochastic Frontier Analysis (SFA) with fixed effects model. The advantage of the first approach is the ability of controlling for stable time invariant characteristics of the municipalities, thereby eliminating potentially large sources of bias. The second approach is applied in order to estimate the technical efficiency and rank of each municipality accordingly. The regressions control for various demographic, economic and recycling services, such as income per capita, population density, unemployment, trash services, Pay-as-you-throw (PAYT) program and meteorological data. The findings support that a negative relationship between particulate particles in the air 2.5 μm or less in size (PM2.5) and recycling rate is presented. In addition, the pollution is increased with increases on income per capita up to $23,000-$26,000, while after this point income contributes positively on air quality. Finally, based on the efficiency derived by the Stochastic Frontier Analysis (SFA) model, the municipalities which provide both drop off and curbside services for trash, food and yard waste and the PAYT program present better performance regarding the air quality.

  17. Relationship between recycling rate and air pollution: Waste management in the state of Massachusetts.

    PubMed

    Giovanis, Eleftherios

    2015-06-01

    This study examines the relationship between recycling rate of solid waste and air pollution using data from a waste municipality survey in the state of Massachusetts during the period 2009-2012. Two econometric approaches are applied. The first approach is a fixed effects model, while the second is a Stochastic Frontier Analysis (SFA) with fixed effects model. The advantage of the first approach is the ability of controlling for stable time invariant characteristics of the municipalities, thereby eliminating potentially large sources of bias. The second approach is applied in order to estimate the technical efficiency and rank of each municipality accordingly. The regressions control for various demographic, economic and recycling services, such as income per capita, population density, unemployment, trash services, Pay-as-you-throw (PAYT) program and meteorological data. The findings support that a negative relationship between particulate particles in the air 2.5 μm or less in size (PM2.5) and recycling rate is presented. In addition, the pollution is increased with increases on income per capita up to $23,000-$26,000, while after this point income contributes positively on air quality. Finally, based on the efficiency derived by the Stochastic Frontier Analysis (SFA) model, the municipalities which provide both drop off and curbside services for trash, food and yard waste and the PAYT program present better performance regarding the air quality. PMID:25827258

  18. VENTILATION NEEDS DURING CONSTRUCTION

    SciTech Connect

    C.R. Gorrell

    1998-07-23

    The purpose of this analysis is to determine ventilation needs during construction and development of the subsurface repository and develop systems to satisfy those needs. For this analysis, construction is defined as pre-emplacement excavation and development is excavation that takes place simultaneously with emplacement. The three options presented in the ''Overall Development and Emplacement Ventilation Systems'' analysis (Reference 5.5) for development ventilation will be applied to construction ventilation in this analysis as well as adding new and updated ventilation factors to each option for both construction and development. The objective of this analysis is to develop a preferred ventilation system to support License Application Design. The scope of this analysis includes: (1) Description of ventilation conditions; (2) Ventilation factors (fire hazards, dust control, construction logistics, and monitoring and control systems); (3) Local ventilation alternatives; (4) Global ventilation options; and (5) Evaluation of options.

  19. Mathematical Modeling of Radiocesium Migration and Air Dose Rate Changes in Eastern Fukushima Prefecture

    NASA Astrophysics Data System (ADS)

    Kitamura, A.; Sakuma, K.; Kurikami, H.; Malins, A.; Okumura, M.; Itakura, M.; Yamada, S.; Machida, M.

    2015-12-01

    Radioactive cesium that was deposited over Fukushima Prefecture after the accident at the Fukushima Daiichi nuclear power plant station is one of the major concerns regarding health physics today. Its migration is primarily by soil erosion and sediment transport within surface water during times of heavy rainfall and flooding. In order to predict the future distribution of radioactive cesium and resulting air dose rate at any location in Fukushima, we have integrated a number of mathematical models covering different time and spatial scales. In this presentation we report our overall scheme of prediction starting from sediment and radioactive cesium movement and resulting long term air dose rate changes. Specifically, we present simulation results of sediment movement and radioactive cesium migration using semi-empirical and physics based watershed models, and that of sediment and radioactive cesium behavior in a dam reservoir using one and two dimensional river simulation models. The model's results are compared with ongoing field monitoring.

  20. Indoor air quality modeling for PM 10, PM 2.5, and PM 1.0 in naturally ventilated classrooms of an urban Indian school building.

    PubMed

    Goyal, Radha; Khare, Mukesh

    2011-05-01

    Assessment of indoor air quality (IAQ) in classrooms of school buildings is of prime concern due to its potential effects on student's health and performance as they spend a substantial amount of their time (6-7 h per day) in schools. A number of airborne contaminants may be present in urban school environment. However, respirable suspended particulate matter (RSPM) is of great significance as they may significantly affect occupants' health. The objectives of the present study are twofold, one, to measure the concentrations of PM(10) (<10 microm), PM(2.5) (<2.5 microm), and PM(1.0) (<1.0 microm) in naturally ventilated classrooms of a school building located near a heavy-traffic roadway (9,755 and 4,296 vehicles/hour during weekdays and weekends, respectively); and second, to develop single compartment mass balance-based IAQ models for PM(10) (NVIAQM(pm10)), PM(2.5) (NVIAQM(pm2.5)), and PM(1.0) (NVIAQM(pm1.0)) for predicting their indoor concentrations. Outdoor RSPM levels and classroom characteristics, such as size, occupancy level, temperature, relative humidity, and CO(2) concentrations have also been monitored during school hours. Predicted indoor PM(10) concentrations show poor correlations with observed indoor PM(10) concentrations (R (2) = 0.028 for weekdays, and 0.47 for weekends). However, a fair degree of agreement (d) has been found between observed and predicted concentrations, i.e., 0.42 for weekdays and 0.59 for weekends. Furthermore, NVIAQM(pm2.5) and NVIAQM(pm1.0) results show good correlations with observed concentrations of PM(2.5) (R(2) = 0.87 for weekdays and 0.9 for weekends) and PM(1.0) (R(2) = 0.86 for weekdays and 0.87 for weekends). NVIAQM(pm10) shows the tendency to underpredict indoor PM(10) concentrations during weekdays as it does not take into account the occupant's activities and its effects on the indoor concentrations during the class hours. Intense occupant's activities cause resuspension or delayed deposition of PM(10). The model