Sample records for air ventilation rates

  1. Effect of ventilation rate on air cleanliness and energy consumption in operation rooms at rest.

    PubMed

    Lee, Shih-Tseng; Liang, Ching-Chieh; Chien, Tsung-Yi; Wu, Feng-Jen; Fan, Kuang-Chung; Wan, Gwo-Hwa

    2018-02-27

    The interrelationships between ventilation rate, indoor air quality, and energy consumption in operation rooms at rest are yet to be understood. We investigate the effect of ventilation rate on indoor air quality indices and energy consumption in ORs at rest. The study investigates the air temperature, relative humidity, concentrations of carbon dioxide, particulate matter (PM), and airborne bacteria at different ventilation rates in operation rooms at rest of a medical center. The energy consumption and cost analysis of the heating, ventilating, and air conditioning (HVAC) system in the operation rooms at rest were also evaluated for all ventilation rates. No air-conditioned operation rooms had very highest PM and airborne bacterial concentrations in the operation areas. The bacterial concentration in the operation areas with 6-30 air changes per hour (ACH) was below the suggested level set by the United Kingdom (UK) for an empty operation room. A 70% of reduction in annual energy cost by reducing the ventilation rate from 30 to 6 ACH was found in the operation rooms at rest. Maintenance of operation rooms at ventilation rate of 6 ACH could save considerable amounts of energy and achieve the goal of air cleanliness.

  2. Determining the ventilation and aerosol deposition rates from routine indoor-air measurements.

    PubMed

    Halios, Christos H; Helmis, Costas G; Deligianni, Katerina; Vratolis, Sterios; Eleftheriadis, Konstantinos

    2014-01-01

    Measurement of air exchange rate provides critical information in energy and indoor-air quality studies. Continuous measurement of ventilation rates is a rather costly exercise and requires specific instrumentation. In this work, an alternative methodology is proposed and tested, where the air exchange rate is calculated by utilizing indoor and outdoor routine measurements of a common pollutant such as SO2, whereas the uncertainties induced in the calculations are analytically determined. The application of this methodology is demonstrated, for three residential microenvironments in Athens, Greece, and the results are also compared against ventilation rates calculated from differential pressure measurements. The calculated time resolved ventilation rates were applied to the mass balance equation to estimate the particle loss rate which was found to agree with literature values at an average of 0.50 h(-1). The proposed method was further evaluated by applying a mass balance numerical model for the calculation of the indoor aerosol number concentrations, using the previously calculated ventilation rate, the outdoor measured number concentrations and the particle loss rates as input values. The model results for the indoors' concentrations were found to be compared well with the experimentally measured values.

  3. [The effect of the ventilation rate on air particle and air microbe concentration in operating rooms with conventional ventilation. 1. Measurement without surgical activity].

    PubMed

    Kruppa, B; Rüden, H

    1993-05-01

    The question was if a reduction of airborne particles and bacteria in conventionally (turbulently), ventilated operating theatres in comparison to Laminar-Airflow (LAF) operating theatres does occur at high air-exchange-rates. Within the framework of energy consumption measures the influence of air-exchange-rates on airborne particle and bacteria concentrations was determined in two identical operating theatres with conventional ventilation (wall diffusor panel) at the air-exchange-rates 7.5, 10, 15 and 20/h without surgical activity. This was established by means of the statistical procedure of analysis of variance. Especially for the comparison of the air-exchange-rates 7.5 and 15/h statistical differences were found for airborne particle concentrations in supply and ambient air. Concerning airborne bacteria concentrations no differences were found among the various air-exchange-rates. Explanation of variance is quite high for non-viable particles (supply air: 37%, ambient air: 81%) but negligible for viable particles (bacteria) with values below 15%.

  4. Impact of Room Ventilation Rates on Mouse Cage Ventilation and Microenvironment.

    PubMed

    Reeb, Carolyn K.; Jones, Robert B.; Bearg, David W.; Bedigian, Hendrick; Paigen, Beverly

    1997-01-01

    To assess the impact of room ventilation on animal cage microenvironment, intracage ventilation rate, temperature, humidity, and concentrations of carbon dioxide and ammonia were monitored in nonpressurized, bonnet-topped mouse cages. Cages on the top, middle, and bottom rows of a mouse rack were monitored at room ventilation rates of 0, 5, 10, and 20 air changes/h (ACH). Ventilation inside the animal cage increased somewhat from 12.8 to 18.9 ACH as room ventilation rate in- creased from 0 to 20 ACH, but the differences were not statistically significant, and most of the increase occurred in cages in the top row nearest to the fresh air supply. Cages containing mice had ventilation rate between 10 and 15 ACH even when room ventilation was reduced to 0 ACH; this ventilation is a result of the thermal heat load of the mice. After 6 days of soiled bedding, intracage ammonia concentration was c 3 ppm at all room ventilation rates and was not affected by increasing room ventilation. Temperature inside cages did not change with increasing ventilation. Humidity inside cages significantly decreased with increasing ventilation, from 55% relative humidity at 5 ACH to 36% relative humidity at 20 ACH. Carbon dioxide concentration decreased from 2,500 ppm to 1,900 ppm when ventilation rate increased from 5 ACH to 10 ACH, but no further significant decrease was observed at 20 ACH. In conclusion, increasing the room ventilation rate higher than 5 ACH did not result in significant improvements in the cage microenvironment.

  5. Effect of outside air ventilation rate on VOC concentrations and emissions in a call center

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Hodgson, A.T.; Faulkner, D.; Sullivan, D.P.

    2002-01-01

    A study of the relationship between outside air ventilation rate and concentrations of VOCs generated indoors was conducted in a call center. Ventilation rates were manipulated in the building's four air handling units (AHUs). Concentrations of VOCs in the AHU returns were measured on 7 days during a 13-week period. Indoor minus outdoor concentrations and emission factors were calculated. The emission factor data was subjected to principal component analysis to identify groups of co-varying compounds based on source type. One vector represented emissions of solvents from cleaning products. Another vector identified occupant sources. Direct relationships between ventilation rate and concentrationsmore » were not observed for most of the abundant VOCs. This result emphasizes the importance of source control measures for limiting VOC concentrations in buildings.« less

  6. Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Rudd, Armin; Bergey, Daniel

    Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy. It was inferior because the source of outside air was not direct from outside, themore » ventilation air was not distributed, and no provision existed for air filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four System Factor Categories: Balance, Distribution, Outside Air Source, and Recirculation Filtration. Recommended System Factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year.« less

  7. Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Rudd, Armin; Bergey, Daniel

    In this project, Building America research team Building Science Corporation tested the effectiveness of ventilation systems at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy. This was because the sourcemore » of outside air was not direct from outside, the ventilation air was not distributed, and no provision existed for air filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four system factor categories: balance, distribution, outside air source, and recirculation filtration. Recommended system factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year.« less

  8. Whole house particle removal and clean air delivery rates for in-duct and portable ventilation systems.

    PubMed

    Macintosh, David L; Myatt, Theodore A; Ludwig, Jerry F; Baker, Brian J; Suh, Helen H; Spengler, John D

    2008-11-01

    A novel method for determining whole house particle removal and clean air delivery rates attributable to central and portable ventilation/air cleaning systems is described. The method is used to characterize total and air-cleaner-specific particle removal rates during operation of four in-duct air cleaners and two portable air-cleaning devices in a fully instrumented test home. Operation of in-duct and portable air cleaners typically increased particle removal rates over the baseline rates determined in the absence of operating a central fan or an indoor air cleaner. Removal rates of 0.3- to 0.5-microm particles ranged from 1.5 hr(-1) during operation of an in-duct, 5-in. pleated media filter to 7.2 hr(-1) for an in-duct electrostatic air cleaner in comparison to a baseline rate of 0 hr(-1) when the air handler was operating without a filter. Removal rates for total particulate matter less than 2.5 microm in aerodynamic diameter (PM2.5) mass concentrations were 0.5 hr(-1) under baseline conditions, 0.5 hr(-1) during operation of three portable ionic air cleaners, 1 hr(-1) for an in-duct 1-in. media filter, 2.4 hr(-1) for a single high-efficiency particle arrestance (HEPA) portable air cleaner, 4.6 hr(-1) for an in-duct 5-in. media filter, 4.7 hr(-1) during operation of five portable HEPA filters, 6.1 hr(-1) for a conventional in-duct electronic air cleaner, and 7.5 hr(-1) for a high efficiency in-duct electrostatic air cleaner. Corresponding whole house clean air delivery rates for PM2.5 attributable to the air cleaner independent of losses within the central ventilation system ranged from 2 m3/min for the conventional media filter to 32 m3/min for the high efficiency in-duct electrostatic device. Except for the portable ionic air cleaner, the devices considered here increased particle removal indoors over baseline deposition rates.

  9. Ventilating Air-Conditioner

    NASA Technical Reports Server (NTRS)

    Dinh, Khanh

    1994-01-01

    Air-conditioner provides ventilation designed to be used alone or incorporated into cooling or heating system operates efficiently only by recirculating stale air within building. Energy needed to operate overall ventilating cooling or heating system slightly greater than operating nonventilating cooling or heating system. Helps to preserve energy efficiency while satisfying need for increased forced ventilation to prevent accumulation of undesired gases like radon and formaldehyde. Provides fresh treated air to variety of confined spaces: hospital surgeries, laboratories, clean rooms, and printing shops and other places where solvents used. In mobile homes and portable classrooms, eliminates irritant chemicals exuded by carpets, panels, and other materials, ensuring healthy indoor environment for occupants.

  10. Emission of formaldehyde by particleboard : effect of ventilation rate and loading on air-contamination levels

    Treesearch

    George E. Myers; Muneo Nagaoka

    1981-01-01

    Dynamic tests for determining the formaldehyde emission behavior of UF-bonded boards involve the measurement of formaldehyde concentration in the air within a vessel which contains a specified board loading L (m2 of board area per m3 of vessel free volume) and is being ventilated at a specified air exchange rate N (hr.-1). Such tests constitute a primary...

  11. VENTILATION RESEARCH: A REVIEW OF RECENT INDOOR AIR QUALITY LITERATURE

    EPA Science Inventory

    The report gives results of a literature review, conducted to survey and summarize recent and ongoing engineering research into building ventilation, air exchange rate, pollutant distribution and dispersion, and other effects of heating, ventilation, and air-conditioning (HVAC) s...

  12. An approach to using heart rate monitoring to estimate the ventilation and load of air pollution exposure.

    PubMed

    Cozza, Izabela Campos; Zanetta, Dirce Maria Trevisan; Fernandes, Frederico Leon Arrabal; da Rocha, Francisco Marcelo Monteiro; de Andre, Paulo Afonso; Garcia, Maria Lúcia Bueno; Paceli, Renato Batista; Prado, Gustavo Faibischew; Terra-Filho, Mario; do Nascimento Saldiva, Paulo Hilário; de Paula Santos, Ubiratan

    2015-07-01

    The effects of air pollution on health are associated with the amount of pollutants inhaled which depends on the environmental concentration and the inhaled air volume. It has not been clear whether statistical models of the relationship between heart rate and ventilation obtained using laboratory cardiopulmonary exercise test (CPET) can be applied to an external group to estimate ventilation. To develop and evaluate a model to estimate respiratory ventilation based on heart rate for inhaled load of pollutant assessment in field studies. Sixty non-smoking men; 43 public street workers (public street group) and 17 employees of the Forest Institute (park group) performed a maximum cardiopulmonary exercise test (CPET). Regression equation models were constructed with the heart rate and natural logarithmic of minute ventilation data obtained on CPET. Ten individuals were chosen randomly (public street group) and were used for external validation of the models (test group). All subjects also underwent heart rate register, and particulate matter (PM2.5) monitoring for a 24-hour period. For the public street group, the median difference between estimated and observed data was 0.5 (CI 95% -0.2 to 1.4) l/min and for the park group was 0.2 (CI 95% -0.2 to 1.2) l/min. In the test group, estimated values were smaller than the ones observed in the CPET, with a median difference of -2.4 (CI 95% -4.2 to -1.8) l/min. The mixed model estimated values suggest that this model is suitable for situations in which heart rate is around 120-140bpm. The mixed effect model is suitable for ventilation estimate, with good accuracy when applied to homogeneous groups, suggesting that, in this case, the model could be used in field studies to estimate ventilation. A small but significant difference in the median of external validation estimates was observed, suggesting that the applicability of the model to external groups needs further evaluation. Copyright © 2015 Elsevier B.V. All rights

  13. Effect of varying the pressurisation rate during noninvasive pressure support ventilation.

    PubMed

    Prinianakis, G; Delmastro, M; Carlucci, A; Ceriana, P; Nava, S

    2004-02-01

    The aim of the study was to assess the effects of varying the pressurisation rate during noninvasive pressure support ventilation on patients' breathing pattern, inspiratory effort, arterial blood gases, tolerance to ventilation and amount of air leakage. A total of 15 chronic obstructive pulmonary disease patients recovering from an acute episode of hypercapnic acute respiratory failure were studied during four randomised trials with different levels of pressurisation rate. No significant changes were observed in breathing pattern and arterial blood gases between the different runs. The pressure time product of the diaphragm, an estimate of its metabolic consumption, was significantly lower with all pressurisation rates than with spontaneous breathing, but was significantly lowest with the fastest rate. However, air leak, assessed by the ratio between expired and inspired tidal volumes, increased and the patients' tolerance of ventilation, measured using a standardised scale, was significantly poorer with the fastest pressurisation rate. In chronic obstructive pulmonary disease patients recovering from an episode of acute hypercapnic respiratory failure and ventilated with noninvasive pressure support ventilation, different pressurisation rates resulted in different reductions in the pressure time product of the diaphragm; this reduction was greater with the fastest rate, but was accompanied by significant air leaks and poor tolerance.

  14. Technology Solutions Case Study: Ventilation System Effectiveness and Tested Indoor Air Quality Impacts

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    A. Rudd and D. Bergey

    Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, andmore » filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs.« less

  15. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... 21 Food and Drugs 4 2014-04-01 2014-04-01 false Ventilation, air filtration, air heating and... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a) Adequate ventilation shall be provided. (b) Equipment for adequate control over air pressure, micro-organisms, dust...

  16. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... 21 Food and Drugs 4 2013-04-01 2013-04-01 false Ventilation, air filtration, air heating and... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a) Adequate ventilation shall be provided. (b) Equipment for adequate control over air pressure, micro-organisms, dust...

  17. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... 21 Food and Drugs 4 2012-04-01 2012-04-01 false Ventilation, air filtration, air heating and... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a) Adequate ventilation shall be provided. (b) Equipment for adequate control over air pressure, micro-organisms, dust...

  18. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... 21 Food and Drugs 4 2011-04-01 2011-04-01 false Ventilation, air filtration, air heating and... Buildings and Facilities § 211.46 Ventilation, air filtration, air heating and cooling. (a) Adequate ventilation shall be provided. (b) Equipment for adequate control over air pressure, micro-organisms, dust...

  19. Short-term airing by natural ventilation - implication on IAQ and thermal comfort.

    PubMed

    Heiselberg, P; Perino, M

    2010-04-01

    The need to improve the energy efficiency of buildings requires new and more efficient ventilation systems. It has been demonstrated that innovative operating concepts that make use of natural ventilation seem to be more appreciated by occupants. Among the available ventilation strategies that are currently available, buoyancy driven, single-sided natural ventilation has proved to be very effective and can provide high air change rates for temperature and Indoor Air Quality (IAQ) control. However, to promote a wider distribution of these systems an improvement in the knowledge of their working principles is necessary. The present study analyses and presents the results of an experimental evaluation of airing performance in terms of ventilation characteristics, IAQ and thermal comfort. It includes investigations of the consequences of opening time, opening frequency, opening area and expected airflow rate, ventilation efficiency, thermal comfort and dynamic temperature conditions. A suitable laboratory test rig was developed to perform extensive experimental analyses of the phenomenon under controlled and repeatable conditions. The results showed that short-term window airing is very effective and can provide both acceptable IAQ and thermal comfort conditions in buildings. Practical Implications This study gives the necessary background and in-depth knowledge of the performance of window airing by single-sided natural ventilation necessary for the development of control strategies for window airing (length of opening period and opening frequency) for optimum IAQ and thermal comfort in naturally ventilated buildings.

  20. Characteristics of coal mine ventilation air flows.

    PubMed

    Su, Shi; Chen, Hongwei; Teakle, Philip; Xue, Sheng

    2008-01-01

    Coal mine methane (CMM) is not only a greenhouse gas but also a wasted energy resource if not utilised. Underground coal mining is by far the most important source of fugitive methane emissions, and approximately 70% of all coal mining related methane is emitted to the atmosphere through mine ventilation air. Therefore, research and development on mine methane mitigation and utilisation now focuses on methane emitted from underground coal mines, in particular ventilation air methane (VAM) capture and utilisation. To date, most work has focused on the oxidation of very low concentration methane. These processes may be classified based on their combustion kinetic mechanisms into thermal oxidation and catalytic oxidation. VAM mitigation/utilisation technologies are generally divided into two basic categories: ancillary uses and principal uses. However, it is possible that the characteristics of ventilation air flows, for example the variations in methane concentration and the presence of certain compounds, which have not been reported so far, could make some potential VAM mitigation and utilisation technologies unfeasible if they cannot cope with the characteristics of mine site ventilation air flows. Therefore, it is important to understand the characteristics of mine ventilation air flows. Moreover, dust, hydrogen sulphide, sulphur dioxide, and other possible compounds emitted through mine ventilation air into the atmosphere are also pollutants. Therefore, this paper presents mine-site experimental results on the characteristics of mine ventilation air flows, including methane concentration and its variations, dust loadings, particle size, mineral matter of the dust, and other compounds in the ventilation air flows. The paper also discusses possible correlations between ventilation air characteristics and underground mining activities.

  1. Evaluation of the indoor air quality minimum ventilation rate procedure for use in California retail buildings.

    PubMed

    Dutton, S M; Mendell, M J; Chan, W R; Barrios, M; Sidheswaran, M A; Sullivan, D P; Eliseeva, E A; Fisk, W J

    2015-02-01

    This research assesses benefits of adding to California Title-24 ventilation rate (VR) standards a performance-based option, similar to the American Society of Heating, Refrigerating, and Air Conditioning Engineers 'Indoor Air Quality Procedure' (IAQP) for retail spaces. Ventilation rates and concentrations of contaminants of concern (CoC) were measured in 13 stores. Mass balance models were used to estimate 'IAQP-based' VRs that would maintain concentrations of all CoCs below health- or odor-based reference concentration limits. An intervention study in a 'big box' store assessed how the current VR, the Title 24-prescribed VR, and the IAQP-based VR (0.24, 0.69, and 1.51 air changes per hour) influenced measured IAQ and perceived of IAQ. Neither current VRs nor Title 24-prescribed VRs would maintain all CoCs below reference limits in 12 of 13 stores. In the big box store, the IAQP-based VR kept all CoCs below limits. More than 80% of subjects reported acceptable air quality at all three VRs. In 11 of 13 buildings, saving energy through lower VRs while maintaining acceptable IAQ would require source reduction or gas-phase air cleaning for CoCs. In only one of the 13 retail stores surveyed, application of the IAQP would have allowed reduced VRs without additional contaminant-reduction strategies. Published 2014. This article is a U.S. Government work and is in the public domain in the USA.

  2. Neonatal air leak syndrome and the role of high-frequency ventilation in its prevention.

    PubMed

    Jeng, Mei-Jy; Lee, Yu-Sheng; Tsao, Pei-Chen; Soong, Wen-Jue

    2012-11-01

    Air leak syndrome includes pulmonary interstitial emphysema, pneumothorax, pneumomediastinum, pneumopericardium, pneumoperitoneum, subcutaneous emphysema, and systemic air embolism. The most common cause of air leak syndrome in neonates is inadequate mechanical ventilation of the fragile and immature lungs. The incidence of air leaks in newborns is inversely related to the birth weight of the infants, especially in very-low-birth-weight and meconium-aspirated infants. When the air leak is asymptomatic and the infant is not mechanically ventilated, there is usually no specific treatment. Emergent needle aspiration and/or tube drainage are necessary in managing tension pneumothorax or pneumopericardium with cardiac tamponade. To prevent air leak syndrome, gentle ventilation with low pressure, low tidal volume, low inspiratory time, high rate, and judicious use of positive end expiratory pressure are the keys to caring for mechanically ventilated infants. Both high-frequency oscillatory ventilation (HFOV) and high-frequency jet ventilation (HFJV) can provide adequate gas exchange using extremely low tidal volume and supraphysiologic rate in neonates with acute pulmonary dysfunction, and they are considered to have the potential to reduce the risks of air leak syndrome in neonates. However, there is still no conclusive evidence that HFOV or HFJV can help to reduce new air leaks in published neonatal clinical trials. In conclusion, neonatal air leaks may present as a thoracic emergency requiring emergent intervention. To prevent air leak syndrome, gentle ventilations are key to caring for ventilated infants. There is insufficient evidence showing the role of HFOV and HFJV in the prevention or reduction of new air leaks in newborn infants, so further investigation will be necessary for future applications. Copyright © 2012. Published by Elsevier B.V.

  3. Building America Case Study: Ventilation System Effectiveness and Tested Indoor Air Quality Impacts, Tyler, Texas

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    ?Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, andmore » filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four System Factor Categories: Balance, Distribution, Outside Air Source, and Recirculation Filtration. Recommended System Factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy.« less

  4. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... 30 Mineral Resources 1 2014-07-01 2014-07-01 false Belt air course ventilation. 75.350 Section 75... HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Ventilation § 75.350 Belt air course ventilation. (a) The belt air course must not be used as a return air course; and except as provided in paragraph...

  5. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... 30 Mineral Resources 1 2012-07-01 2012-07-01 false Belt air course ventilation. 75.350 Section 75... HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Ventilation § 75.350 Belt air course ventilation. (a) The belt air course must not be used as a return air course; and except as provided in paragraph...

  6. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2011 CFR

    2011-07-01

    ... 30 Mineral Resources 1 2011-07-01 2011-07-01 false Belt air course ventilation. 75.350 Section 75... HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Ventilation § 75.350 Belt air course ventilation. (a) The belt air course must not be used as a return air course; and except as provided in paragraph...

  7. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... 30 Mineral Resources 1 2013-07-01 2013-07-01 false Belt air course ventilation. 75.350 Section 75... HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Ventilation § 75.350 Belt air course ventilation. (a) The belt air course must not be used as a return air course; and except as provided in paragraph...

  8. Assessment of ventilation and indoor air pollutants in nursery and elementary schools in France.

    PubMed

    Canha, N; Mandin, C; Ramalho, O; Wyart, G; Ribéron, J; Dassonville, C; Hänninen, O; Almeida, S M; Derbez, M

    2016-06-01

    The aim of this study was to characterize the relationship between Indoor Air Quality (IAQ) and ventilation in French classrooms. Various parameters were measured over one school week, including volatile organic compounds, aldehydes, particulate matter (PM2.5 mass concentration and number concentration), carbon dioxide (CO2 ), air temperature, and relative humidity in 51 classrooms at 17 schools. The ventilation was characterized by several indicators, such as the air exchange rate, ventilation rate (VR), and air stuffiness index (ICONE), that are linked to indoor CO2 concentration. The influences of the season (heating or non-heating), type of school (nursery or elementary), and ventilation on the IAQ were studied. Based on the minimum value of 4.2 l/s per person required by the French legislation for mechanically ventilated classrooms, 91% of the classrooms had insufficient ventilation. The VR was significantly higher in mechanically ventilated classrooms compared with naturally ventilated rooms. The correlations between IAQ and ventilation vary according to the location of the primary source of each pollutant (outdoor vs. indoor), and for an indoor source, whether it is associated with occupant activity or continuous emission. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  9. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... 30 Mineral Resources 1 2014-07-01 2014-07-01 false Quantity of ventilating air. 36.45 Section 36... TRANSPORTATION EQUIPMENT Test Requirements § 36.45 Quantity of ventilating air. (a) Results of the engine tests shall be used to calculate ventilation (cubic feet of air per minute) that shall be supplied by positive...

  10. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... 30 Mineral Resources 1 2012-07-01 2012-07-01 false Quantity of ventilating air. 36.45 Section 36... TRANSPORTATION EQUIPMENT Test Requirements § 36.45 Quantity of ventilating air. (a) Results of the engine tests shall be used to calculate ventilation (cubic feet of air per minute) that shall be supplied by positive...

  11. 30 CFR 36.45 - Quantity of ventilating air.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... 30 Mineral Resources 1 2013-07-01 2013-07-01 false Quantity of ventilating air. 36.45 Section 36... TRANSPORTATION EQUIPMENT Test Requirements § 36.45 Quantity of ventilating air. (a) Results of the engine tests shall be used to calculate ventilation (cubic feet of air per minute) that shall be supplied by positive...

  12. Effects of air ventilation during stationary exercise testing.

    PubMed

    Van Schuylenbergh, R; Vanden Eynde, B; Hespel, P

    2004-07-01

    The impact of air ventilation on performance and physiological responses during stationary exercise in the laboratory was studied. Fourteen well-trained cyclists performed three exercise tests on a cycle ergometer, each separated by a 1-week interval. The first test was a graded test to determine the power output corresponding with the 4-mmol l(-1) lactate level. Tests 2 and 3 were 30-min constant-load tests at a power output corresponding with this 4-mmol l(-1) lactate threshold. One constant-load test was performed in the absence (NAV), whilst the other was performed in the presence (AV) of air ventilation (3 m s(-1)). During the constant-load tests, heart rate, tympanic temperature, blood lactate concentration and oxygen uptake (VO2) were measured at 10-min intervals and at the end of the test. Differences between the two test conditions were evaluated using paired t-tests. During NAV, 12 subjects interrupted the test due to premature exhaustion (exercise duration <30 min), versus only seven in AV ( P<0.05). At the end of the test tympanic temperature was 35.9 (0.2) degrees C in AV and was higher in NAV [36.7 (0.2) degrees C, P<0.05]. Exercise heart rate increased at a faster rate during NAV [+2.2 (0.3) beats min(-1)] than during AV [+1.5 (0.2) beats min(-1), P<0.05]. Blood lactate concentration and VO2 were similar between conditions. Air ventilation is essential to prevent an upward shift in the lactate:heart rate as well as the power output:heart rate relationship during laboratory exercise testing and indoor exercise training.

  13. High tidal volume ventilation induces NOS2 and impairs cAMP- dependent air space fluid clearance.

    PubMed

    Frank, James A; Pittet, Jean-Francois; Lee, Hyon; Godzich, Micaela; Matthay, Michael A

    2003-05-01

    Tidal volume reduction during mechanical ventilation reduces mortality in patients with acute lung injury and the acute respiratory distress syndrome. To determine the mechanisms underlying the protective effect of low tidal volume ventilation, we studied the time course and reversibility of ventilator-induced changes in permeability and distal air space edema fluid clearance in a rat model of ventilator-induced lung injury. Anesthetized rats were ventilated with a high tidal volume (30 ml/kg) or with a high tidal volume followed by ventilation with a low tidal volume of 6 ml/kg. Endothelial and epithelial protein permeability were significantly increased after high tidal volume ventilation but returned to baseline levels when tidal volume was reduced. The basal distal air space fluid clearance (AFC) rate decreased by 43% (P < 0.05) after 1 h of high tidal volume but returned to the preventilation rate 2 h after tidal volume was reduced. Not all of the effects of high tidal volume ventilation were reversible. The cAMP-dependent AFC rate after 1 h of 30 ml/kg ventilation was significantly reduced and was not restored when tidal volume was reduced. High tidal volume ventilation also increased lung inducible nitric oxide synthase (NOS2) expression and air space total nitrite at 3 h. Inhibition of NOS2 activity preserved cAMP-dependent AFC. Because air space edema fluid inactivates surfactant and reduces ventilated lung volume, the reduction of cAMP-dependent AFC by reactive nitrogen species may be an important mechanism of clinical ventilator-associated lung injury.

  14. 30 CFR 75.350 - Belt air course ventilation.

    Code of Federal Regulations, 2010 CFR

    2010-07-01

    ... HEALTH MANDATORY SAFETY STANDARDS-UNDERGROUND COAL MINES Ventilation § 75.350 Belt air course ventilation... manager may approve lower velocities in the ventilation plan based on specific mine conditions. Air... or alarm signal. This training must be conducted prior to working underground in a mine that uses...

  15. Indoor Air Quality: Is Increased Ventilation the Answer?

    ERIC Educational Resources Information Center

    Hansen, Shirley

    1989-01-01

    Explains how indoor air quality is affected by pollutants in the air and also by temperature, humidity, and ventilation. Increased ventilation alone seldom solves the "sick building syndrome." Lists ways to improve indoor air quality and optimize energy efficiency. (MLF)

  16. Effectiveness of in-room air filtration and dilution ventilation for tuberculosis infection control.

    PubMed

    Miller-Leiden, S; Lobascio, C; Nazaroff, W W; Macher, J M

    1996-09-01

    Tuberculosis (TB) is a public health problem that may pose substantial risks to health care workers and others. TB infection occurs by inhalation of airborne bacteria emitted by persons with active disease. We experimentally evaluated the effectiveness of in-room air filtration systems, specifically portable air filters (PAFs) and ceiling-mounted air filters (CMAFs), in conjunction with dilution ventilation, for controlling TB exposure in high-risk settings. For each experiment, a test aerosol was continuously generated and released into a full-sized room. With the in-room air filter and room ventilation system operating, time-averaged airborne particle concentrations were measured at several points. The effectiveness of in-room air filtration plus ventilation was determined by comparing particle concentrations with and without device operation. The four PAFs and three CMAFs we evaluated reduced room-average particle concentrations, typically by 30% to 90%, relative to a baseline scenario with two air-changes per hour of ventilation (outside air) only. Increasing the rate of air flow recirculating through the filter and/or air flow from the ventilation did not always increase effectiveness. Concentrations were generally higher near the emission source than elsewhere in the room. Both the air flow configuration of the filter and its placement within the room were important, influencing room air flow patterns and the spatial distribution of concentrations. Air filters containing efficient, but non-high efficiency particulate air (HEPA) filter media were as effective as air filters containing HEPA filter media.

  17. Effectiveness of In-Room Air Filtration and Dilution Ventilation for Tuberculosis Infection Control.

    PubMed

    Miller-Leiden, S; Lohascio, C; Nazaroff, W W; Macher, J M

    1996-09-01

    Tuberculosis (TB) is a public health problem that may pose substantial risks to health care workers and others. TB infection occurs by inhalation of airborne bacteria emitted by persons with active disease. We experimentally evaluated the effectiveness of in-room air filtration systems, specifically portable air filters (PAFs) and ceiling-mounted air filters (CMAFs), in conjunction with dilution ventilation, for controlling TB exposure in high-risk settings. For each experiment, a test aerosol was continuously generated and released into a full-sized room. With the in-room air filter and room ventilation system operating, time-averaged airborne particle concentrations were measured at several points. The effectiveness of in-room air filtration plus ventilation was determined by comparing particle concentrations with and without device operation. The four PAFs and three CMAFs we evaluated reduced room-average particle concentrations, typically by 30% to 90%, relative to a baseline scenario with two air-changes per hour of ventilation (outside air) only. Increasing the rate of air flow recirculating through the filter and/or air flow from the ventilation did not always increase effectiveness. Concentrations were generally higher near the emission source than elsewhere in the room. Both the air flow configuration of the filter and its placement within the room were important, influencing room air flow patterns and the spatial distribution of concentrations. Air filters containing efficient, but non-high efficiency particulate air (HEPA) filter media were as effective as air filters containing HEPA filter media.

  18. Indoor air pollutants, ventilation rate determinants and potential control strategies in Chinese dwellings: A literature review.

    PubMed

    Ye, Wei; Zhang, Xu; Gao, Jun; Cao, Guangyu; Zhou, Xiang; Su, Xing

    2017-05-15

    After nearly twenty years of rapid modernization and urbanization in China, huge achievements have transformed the daily lives of the Chinese people. However, unprecedented environmental consequences in both indoor and outdoor environments have accompanied this progress and have triggered public awareness and demands for improved living standards, especially in residential environments. Indoor pollution data measured for >7000 dwellings (approximately 1/3 were newly decorated and were tested for volatile organic compound (VOC) measurements, while the rest were tested for particles, phthalates and other semi-volatile organic compounds (SVOCs), moisture/mold, inorganic gases and radon) in China within the last ten years were reviewed, summarized and compared with indoor concentration recommendations based on sensory or health end-points. Ubiquitous pollutants that exceed the concentration recommendations, including particulate matter, formaldehyde, benzene and other VOCs, moisture/mold, inorganic gases and radon, were found, indicating a common indoor air quality (IAQ) issue in Chinese dwellings. With very little prevention, oral, inhalation and dermal exposure to those pollutants at unhealthy concentration levels is almost inevitable. CO 2 , VOCs, humidity and radon can serve as ventilation determinants, each with different ventilation demands and strategies, at typical occupant densities in China; and particle reduction should be a prerequisite for determining ventilation requirements. Two directional ventilation modes would have profound impacts on improving IAQ for Chinese residences are: 1) natural (or window) ventilation with an air cleaner and 2) mechanical ventilation with an air filtration unit, these two modes were reviewed and compared for their applicability and advantages and disadvantages for reducing human exposure to indoor air pollutants. In general, mode 2 can more reliably ensure good IAQ for occupants; while mode 1 is more applicable due to its

  19. Winter ventilation rates at primary schools: comparison between Portugal and Finland.

    PubMed

    Canha, N; Almeida, S M; Freitas, M C; Täubel, M; Hänninen, O

    2013-01-01

    This study focused on examination of ventilation rates in classrooms with two different types of ventilation systems: natural and mechanical. Carbon dioxide (CO2) measurements were conducted in primary schools of Portugal characterized by natural ventilation and compared to Finland where mechanical ventilation is the norm. The winter period was selected since this season exerts a great influence in naturally ventilated classrooms, where opening of windows and doors occurs due to outdoor atmospheric conditions. The ventilation rates were calculated by monitoring CO2 concentrations generated by the occupants (used as a tracer gas) and application of the buildup phase method. A comparison between both countries' results was conducted with respect to ventilation rates and how these levels corresponded to national regulatory standards. Finnish primary schools (n = 2) registered a mean ventilation rate of 13.3 L/s per person, which is higher than the recommended ventilation standards. However, the Finnish classroom that presented the lowest ventilation rate (7.2 L/s per person) displayed short-term CO2 levels above 1200 ppm, which is the threshold limit value (TLV) recommended by national guidelines. The Portuguese classrooms (n = 2) showed low ventilation rates with mean values of 2.4 L/s per person, which is markedly lower than the minimum recommended value of 7 L/s per person as defined by ASHRAE and 20% less than the REHVA minimum of 3 L/s per person. Carbon dioxide levels of 1000 ppm, close to the TLV of 1200 ppm, were also reached in both Portuguese classrooms studied. The situation in Portugal indicates a potentially serious indoor air quality problem and strengthens the need for intervention to improve ventilation rates in naturally ventilated classrooms.

  20. Contaminant levels, source strengths, and ventilation rates in California retail stores.

    PubMed

    Chan, W R; Cohn, S; Sidheswaran, M; Sullivan, D P; Fisk, W J

    2015-08-01

    This field study measured ventilation rates and indoor air quality in 21 visits to retail stores in California. Three types of stores, such as grocery, furniture/hardware stores, and apparel, were sampled. Ventilation rates measured using a tracer gas decay method exceeded the minimum requirement of California's Title 24 Standard in all but one store. Concentrations of volatile organic compounds (VOCs), ozone, and carbon dioxide measured indoors and outdoors were analyzed. Even though there was adequate ventilation according to standard, concentrations of formaldehyde and acetaldehyde exceeded the most stringent chronic health guidelines in many of the sampled stores. The whole-building emission rates of VOCs were estimated from the measured ventilation rates and the concentrations measured indoor and outdoor. Estimated formaldehyde emission rates suggest that retail stores would need to ventilate at levels far exceeding the current Title 24 requirement to lower indoor concentrations below California's stringent formaldehyde reference level. Given the high costs of providing ventilation, effective source control is an attractive alternative. Field measurements suggest that California retail stores were well ventilated relative to the minimum ventilation rate requirement specified in the Building Energy Efficiency Standards Title 24. Concentrations of formaldehyde found in retail stores were low relative to levels found in homes but exceeded the most stringent chronic health guideline. Looking ahead, California is mandating zero energy commercial buildings by 2030. To reduce the energy use from building ventilation while maintaining or even lowering formaldehyde in retail stores, effective formaldehyde source control measures are vitally important. Published 2014. This article is a U.S. Government work and is in the public domain in the USA.

  1. Ventilation rates in recently constructed U.S. school classrooms.

    PubMed

    Batterman, S; Su, F-C; Wald, A; Watkins, F; Godwin, C; Thun, G

    2017-09-01

    Low ventilation rates (VRs) in schools have been associated with absenteeism, poorer academic performance, and teacher dissatisfaction. We measured VRs in 37 recently constructed or renovated and mechanically ventilated U.S. schools, including LEED and EnergyStar-certified buildings, using CO 2 and the steady-state, build-up, decay, and transient mass balance methods. The transient mass balance method better matched conditions (specifically, changes in occupancy) and minimized biases seen in the other methods. During the school day, air change rates (ACRs) averaged 2.0±1.3 hour -1 , and only 22% of classrooms met recommended minimum ventilation rates. HVAC systems were shut off at the school day close, and ACRs dropped to 0.21±0.19 hour -1 . VRs did not differ by building type, although cost-cutting and comfort measures resulted in low VRs and potentially impaired IAQ. VRs were lower in schools that used unit ventilators or radiant heating, in smaller schools and in larger classrooms. The steady-state, build-up, and decay methods had significant limitations and biases, showing the need to confirm that these methods are appropriate. Findings highlight the need to increase VRs and to ensure that energy saving and comfort measures do not compromise ventilation and IAQ. © 2017 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  2. Short-term airing by natural ventilation - modeling and control strategies.

    PubMed

    Perino, M; Heiselberg, P

    2009-10-01

    The need to improve the energy efficiency of buildings requires new and more efficient ventilation systems. It has been demonstrated that innovative operating concepts that make use of natural ventilation seem to be more appreciated by occupants. This kind of system frequently integrates traditional mechanical ventilation components with natural ventilation devices, such as motorized windows and louvers. Among the various ventilation strategies that are currently available, buoyancy driven single-sided natural ventilation has proved to be very effective and can provide high air change rates for temperature and IAQ control. However, in order to promote a wider applications of these systems, an improvement in the knowledge of their working principles and the availability of new design and simulation tools is necessary. In this context, the paper analyses and presents the results of a research that was aimed at developing and validating numerical models for the analysis of buoyancy driven single-sided natural ventilation systems. Once validated, these models can be used to optimize control strategies in order to achieve satisfactory indoor comfort conditions and IAQ. Practical Implications Numerical and experimental analyses have proved that short-term airing by intermittent ventilation is an effective measure to satisfactorily control IAQ. Different control strategies have been investigated to optimize the capabilities of the systems. The proposed zonal model has provided good performances and could be adopted as a design tool, while CFD simulations can be profitably used for detailed studies of the pollutant concentration distribution in a room and to address local discomfort problems.

  3. Should Title 24 Ventilation Requirements Be Amended to include an Indoor Air Quality Procedure?

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Dutton, Spencer M.; Mendell, Mark J.; Chan, Wanyu R.

    Minimum outdoor air ventilation rates (VRs) for buildings are specified in standards, including California?s Title 24 standards. The ASHRAE ventilation standard includes two options for mechanically-ventilated buildings ? a prescriptive ventilation rate procedure (VRP) that specifies minimum VRs that vary among occupancy classes, and a performance-based indoor air quality procedure (IAQP) that may result in lower VRs than the VRP, with associated energy savings, if IAQ meeting specified criteria can be demonstrated. The California Energy Commission has been considering the addition of an IAQP to the Title 24 standards. This paper, based on a review of prior data and newmore » analyses of the IAQP, evaluates four future options for Title 24: no IAQP; adding an alternate VRP, adding an equivalent indoor air quality procedure (EIAQP), and adding an improved ASHRAE-like IAQP. Criteria were established for selecting among options, and feedback was obtained in a workshop of stakeholders. Based on this review, the addition of an alternate VRP is recommended. This procedure would allow lower minimum VRs if a specified set of actions were taken to maintain acceptable IAQ. An alternate VRP could also be a valuable supplement to ASHRAE?s ventilation standard.« less

  4. [Air quality control systems: heating, ventilating, and air conditioning (HVAC)].

    PubMed

    Bellucci Sessa, R; Riccio, G

    2004-01-01

    After a brief illustration of the principal layout schemes of Heating, Ventilating, and Air Conditioning (HVAC), the first part of this paper summarizes the standards, both voluntary and compulsory, regulating HVAC facilities design and installation with regard to the question of Indoor Air Quality (IAQ). The paper then examines the problem of ventilation systems maintenance and the essential hygienistic requirements in whose absence HVAC facilities may become a risk factor for people working or living in the building. Lastly, the paper deals with HVAC design strategies and methods, which aim not only to satisfy comfort and air quality requirements, but also to ensure easy and effective maintenance procedures.

  5. Heat Recovery Ventilation for Housing: Air-to-Air Heat Exchangers.

    ERIC Educational Resources Information Center

    Corbett, Robert J.; Miller, Barbara

    The air-to-air heat exchanger (a fan powered ventilation device that recovers heat from stale outgoing air) is explained in this six-part publication. Topic areas addressed are: (1) the nature of air-to-air heat exchangers and how they work; (2) choosing and sizing the system; (3) installation, control, and maintenance of the system; (4) heat…

  6. Effect of cabin ventilation rate on ultrafine particle exposure inside automobiles.

    PubMed

    Knibbs, Luke D; de Dear, Richard J; Morawska, Lidia

    2010-05-01

    We alternately measured on-road and in-vehicle ultrafine (<100 nm) particle (UFP) concentration for 5 passenger vehicles that comprised an age range of 18 years. A range of cabin ventilation settings were assessed during 301 trips through a 4 km road tunnel in Sydney, Australia. Outdoor air flow (ventilation) rates under these settings were quantified on open roads using tracer gas techniques. Significant variability in tunnel trip average median in-cabin/on-road (I/O) UFP ratios was observed (0.08 to approximately 1.0). Based on data spanning all test automobiles and ventilation settings, a positive linear relationship was found between outdoor air flow rate and I/O ratio, with the former accounting for a substantial proportion of variation in the latter (R(2) = 0.81). UFP concentrations recorded in-cabin during tunnel travel were significantly higher than those reported by comparable studies performed on open roadways. A simple mathematical model afforded the ability to predict tunnel trip average in-cabin UFP concentrations with good accuracy. Our data indicate that under certain conditions, in-cabin UFP exposures incurred during tunnel travel may contribute significantly to daily exposure. The UFP exposure of automobile occupants appears strongly related to their choice of ventilation setting and vehicle.

  7. A review of air exchange rate models for air pollution exposure assessments.

    PubMed

    Breen, Michael S; Schultz, Bradley D; Sohn, Michael D; Long, Thomas; Langstaff, John; Williams, Ronald; Isaacs, Kristin; Meng, Qing Yu; Stallings, Casson; Smith, Luther

    2014-11-01

    A critical aspect of air pollution exposure assessments is estimation of the air exchange rate (AER) for various buildings where people spend their time. The AER, which is the rate of exchange of indoor air with outdoor air, is an important determinant for entry of outdoor air pollutants and for removal of indoor-emitted air pollutants. This paper presents an overview and critical analysis of the scientific literature on empirical and physically based AER models for residential and commercial buildings; the models highlighted here are feasible for exposure assessments as extensive inputs are not required. Models are included for the three types of airflows that can occur across building envelopes: leakage, natural ventilation, and mechanical ventilation. Guidance is provided to select the preferable AER model based on available data, desired temporal resolution, types of airflows, and types of buildings included in the exposure assessment. For exposure assessments with some limited building leakage or AER measurements, strategies are described to reduce AER model uncertainty. This review will facilitate the selection of AER models in support of air pollution exposure assessments.

  8. Measured removal rates of chrysotile asbestos fibers from air and comparison with theoretical estimates based on gravitational settling and dilution ventilation.

    PubMed

    Sahmel, J; Avens, H J; Scott, P K; Unice, K; Burns, A; Barlow, C A; Madl, A K; Henshaw, J; Paustenbach, D J

    2015-01-01

    Industrial hygiene assessments often focus on activity-based airborne asbestos concentration measurements, but few empirical data exist regarding the fiber removal rate from air after activities cease. Grade 7T chrysotile indoor fiber settling (FS) rates were characterized using air sampling (NIOSH Method 7402). Six replicate events were conducted in a 58 m(3) study chamber (ventilation 3.5 ACH), in which chrysotile-contaminated work clothing was manipulated for 15 min followed by 30 min of no activity. The fiber concentration decay constant and removal rate were characterized using an exponential decay model based on the measurements. Breathing zone airborne chrysotile concentrations decreased by 86% within 15-30 min after fiber disturbance, compared to concentrations during active disturbance (p < 0.05). Estimated mean time required for 99% of the phase contrast microscopy-equivalent (PCME) fibers to be removed from air was approximately 30 min (95% CI: 22-57 min). The observed effective FS velocity was 0.0034 m/s. This settling velocity was between 4.5-fold and 180-fold faster than predicted by two different particulate gravitational settling models. Additionally, PCME concentrations decreased approximately 2.5-fold faster than predicted due to air exchange alone (32 versus 79 min to 99% decrease in concentration). Other measurement studies have reported similar airborne fiber removal rates, supporting the finding that factors other than gravitational settling and dilution ventilation contribute measurably to PCM fiber removal from air (e.g. impaction, agglomeration). Overall, the scientific weight of evidence indicates that the time necessary for removal of 99% of fibers greater than 5 μm in length (with aspect ratios greater than 3:1) is approximately 20-80 min.

  9. ETS levels in hospitality environments satisfying ASHRAE standard 62-1989: "ventilation for acceptable indoor air quality"

    NASA Astrophysics Data System (ADS)

    Moschandreas, D. J.; Vuilleumier, K. L.

    Prior to this study, indoor air constituent levels and ventilation rates of hospitality environments had not been measured simultaneously. This investigation measured indoor Environmental Tobacco Smoke-related (ETS-related) constituent levels in two restaurants, a billiard hall and a casino. The objective of this study was to characterize ETS-related constituent levels inside hospitality environments when the ventilation rates satisfy the requirements of the ASHRAE 62-1989 Ventilation Standard. The ventilation rate of each selected hospitality environment was measured and adjusted. The study advanced only if the requirements of the ASHRAE 62-1989 Ventilation Standard - the pertinent standard of the American Society of Heating, Refrigeration and Air Conditioning Engineers - were satisfied. The supply rates of outdoor air and occupant density were measured intermittently to assure that the ventilation rate of each facility satisfied the standard under occupied conditions. Six ETS-related constituents were measured: respirable suspended particulate (RSP) matter, fluorescent particulate matter (FPM, an estimate of the ETS particle concentrations), ultraviolet particulate matter (UVPM, a second estimate of the ETS particle concentrations), solanesol, nicotine and 3-ethenylpyridine (3-EP). ETS-related constituent levels in smoking sections, non-smoking sections and outdoors were sampled daily for eight consecutive days at each hospitality environment. This study found that the difference between the concentrations of ETS-related constituents in indoor smoking and non-smoking sections was statistically significant. Differences between indoor non-smoking sections and outdoor ETS-related constituent levels were identified but were not statistically significant. Similarly, differences between weekday and weekend evenings were identified but were not statistically significant. The difference between indoor smoking sections and outdoors was statistically significant. Most

  10. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... 24 Housing and Urban Development 5 2010-04-01 2010-04-01 false Venting, ventilation and combustion... Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required by... appliance listing and the appliance manufacturer's instructions. (b) Venting and combustion air systems...

  11. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... 24 Housing and Urban Development 5 2014-04-01 2014-04-01 false Venting, ventilation and combustion... Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required by... appliance listing and the appliance manufacturer's instructions. (b) Venting and combustion air systems...

  12. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... 24 Housing and Urban Development 5 2012-04-01 2012-04-01 false Venting, ventilation and combustion... Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required by... appliance listing and the appliance manufacturer's instructions. (b) Venting and combustion air systems...

  13. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... 24 Housing and Urban Development 5 2011-04-01 2011-04-01 false Venting, ventilation and combustion... Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required by... appliance listing and the appliance manufacturer's instructions. (b) Venting and combustion air systems...

  14. 24 CFR 3280.710 - Venting, ventilation and combustion air.

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... 24 Housing and Urban Development 5 2013-04-01 2013-04-01 false Venting, ventilation and combustion... Fuel Burning Systems § 3280.710 Venting, ventilation and combustion air. (a) The venting as required by... appliance listing and the appliance manufacturer's instructions. (b) Venting and combustion air systems...

  15. Metabolically Derived Human Ventilation Rates: A Revised ...

    EPA Pesticide Factsheets

    EPA announced the availability of the final report, Metabolically Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates. This report provides a revised approach for calculating an individual's ventilation rate directly from their oxygen consumption rate. This approach will be used to update the ventilation rate information in the Exposure Factors Handbook, which serve as a resources for exposure assessors for calculating inhalation and other exposures. In this report, EPA presents a revised approach in which ventilation rate is calculated directly from an individual's oxygen consumption rate.

  16. Estimation of uncertainty in tracer gas measurement of air change rates.

    PubMed

    Iizuka, Atsushi; Okuizumi, Yumiko; Yanagisawa, Yukio

    2010-12-01

    Simple and economical measurement of air change rates can be achieved with a passive-type tracer gas doser and sampler. However, this is made more complex by the fact many buildings are not a single fully mixed zone. This means many measurements are required to obtain information on ventilation conditions. In this study, we evaluated the uncertainty of tracer gas measurement of air change rate in n completely mixed zones. A single measurement with one tracer gas could be used to simply estimate the air change rate when n = 2. Accurate air change rates could not be obtained for n ≥ 2 due to a lack of information. However, the proposed method can be used to estimate an air change rate with an accuracy of <33%. Using this method, overestimation of air change rate can be avoided. The proposed estimation method will be useful in practical ventilation measurements.

  17. Ventilation, indoor air quality, and health in homes undergoing weatherization.

    PubMed

    Francisco, P W; Jacobs, D E; Targos, L; Dixon, S L; Breysse, J; Rose, W; Cali, S

    2017-03-01

    Ventilation standards, health, and indoor air quality have not been adequately examined for residential weatherization. This randomized trial showed how ASHRAE 62-1989 (n=39 houses) and ASHRAE 62.2-2010 (n=42 houses) influenced ventilation rates, moisture balance, indoor air quality, and self-reported physical and mental health outcomes. Average total airflow was nearly twice as high for ASHRAE 62.2-2010 (79 vs. 39 cfm). Volatile organic compounds, formaldehyde and carbon dioxide were all significantly reduced for the newer standard and first-floor radon was marginally lower, but for the older standard, only formaldehyde significantly decreased. Humidity in the ASHRAE 62.2-2010 group was only about half that of the ASHRAE 62-1989 group using the moisture balance metric. Radon was higher in the basement but lower on the first floor for ASHRAE 62.2-2010. Children in each group had fewer headaches, eczema, and skin allergies after weatherization and adults had improvements in psychological distress. Indoor air quality and health improve when weatherization is accompanied by an ASHRAE residential ventilation standard, and the 2010 ASHRAE standard has greater improvements in certain outcomes compared to the 1989 standard. Weatherization, home repair, and energy conservation projects should use the newer ASHRAE standard to improve indoor air quality and health. © 2016 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  18. Comparison of freezing control strategies for residential air-to-air heat recovery ventilators

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Phillips, E.G.; Bradley, L.C.; Chant, R.E.

    1989-01-01

    A comparison of the energy performance of defrost and frost control strategies for residential air-to-air heat recovery ventilators (HRV) has been carried out by using computer simulations for various climatic conditions. This paper discusses the results and conclusions from the comparisons and their implications for the heat recovery ventilator manufacturers and system designers.

  19. Methods to reduce the CO(2) concentration of educational buildings utilizing internal ventilation by transferred air.

    PubMed

    Kalema, T; Viot, M

    2014-02-01

    The aim of this study is to develop internal ventilation by transferred air to achieve a good indoor climate with low energy consumption in educational buildings with constant air volume (CAV) ventilation. Both measurements of CO2 concentration and a multi-room calculation model are presented. The study analyzes how to use more efficiently the available spaces and the capacity of CAV ventilation systems in existing buildings and the impact this has on the indoor air quality and the energy consumption of the ventilation. The temperature differences can be used to create natural ventilation airflows between neighboring spaces. The behavior of temperature-driven airflows between rooms was studied and included in the calculation model. The effect of openings between neighboring spaces, such as doors or large apertures in the walls, on the CO2 concentration was studied in different classrooms. The air temperatures and CO2 concentrations were measured using a wireless, internet-based measurement system. The multi-room calculation model predicted the CO2 concentration in the rooms, which was then compared with the measured ones. Using transferred air between occupied and unoccupied spaces can noticeably reduce the total mechanical ventilation rates needed to keep a low CO2 concentration. © 2013 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  20. Heating, Ventilation and Air-Conditioning Systems, Part of Indoor Air Quality Design Tools for Schools

    EPA Pesticide Factsheets

    The main purposes of a Heating, Ventilation, and Air-Conditioning system are to help maintain good indoor air quality through adequate ventilation with filtration and provide thermal comfort. HVAC systems are among the largest energy consumers in schools.

  1. Healthy Zero Energy Buildings (HZEB) Program - Cross-Sectional Study of Contaminant Levels, Source, Strengths, and Ventilation Rates in Retail Stores

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Chan, Wanyu R.; Sidheswaran, Meera; Cohn, Sebastian

    2014-02-01

    This field study measured ventilation rates and indoor air quality parameters in 21 visits to retail stores in California. The data was collected to guide the development of new, science-based commercial building ventilation rate standards that balance the dual objectives of increasing energy efficiency and maintaining acceptable indoor air quality. Data collection occurred between September 2011 and March 2013. Three types of stores participated in this study: grocery stores, furniture/hardware stores, and apparel stores. Ventilation rates and indoor air contaminant concentrations were measured on a weekday, typically between 9 am and 6 pm. Ventilation rates measured using a tracer gasmore » decay method exceeded the minimum requirement of California’s Title 24 Standard in all but one store. Even though there was adequate ventilation according to Title 24, concentrations of formaldehyde, acetaldehyde, and acrolein exceeded the most stringent chronic health guidelines. Other indoor air contaminants measured included carbon dioxide (CO{sub 2}), carbon monoxide (CO), ozone (O{sub 3}), and particulate matter (PM). Concentrations of CO{sub 2} were kept low by adequate ventilation, and were assumed low also because the sampling occurred on a weekday when retail stores were less busy. CO concentrations were also low. The indoor-outdoor ratios of O{sub 3} showed that the first-order loss rate may vary by store trade types and also by ventilation mode (mechanical versus natural). Analysis of fine and ultrafine PM measurements showed that a substantial portion of the particle mass in grocery stores with cooking-related emissions was in particles less than 0.3 μm. Stores without cooking as an indoor source had PM size distributions that were more similar indoors and outdoors. The whole-building emission rates of volatile organic compounds (VOCs) and PM were estimated from the measured ventilation rates and indoor and outdoor contaminant concentrations. Mass balance

  2. Cost-benefit analysis of different air change rates in an operating room environment.

    PubMed

    Gormley, Thomas; Markel, Troy A; Jones, Howard; Greeley, Damon; Ostojic, John; Clarke, James H; Abkowitz, Mark; Wagner, Jennifer

    2017-12-01

    Hospitals face growing pressure to meet the dual but often competing goals of providing a safe environment while controlling operating costs. Evidence-based data are needed to provide insight for facility management practices to support these goals. The quality of the air in 3 operating rooms was measured at different ventilation rates. The energy cost to provide the heating, ventilation, and air conditioning to the rooms was estimated to provide a cost-benefit comparison of the effectiveness of different ventilation rates currently used in the health care industry. Simply increasing air change rates in the operating rooms tested did not necessarily provide an overall cleaner environment, but did substantially increase energy consumption and costs. Additionally, and unexpectedly, significant differences in microbial load and air velocity were detected between the sterile fields and back instrument tables. Increasing the ventilation rates in operating rooms in an effort to improve clinical outcomes and potentially reduce surgical site infections does not necessarily provide cleaner air, but does typically increase operating costs. Efficient distribution or management of the air can improve quality indicators and potentially reduce the number of air changes required. Measurable environmental quality indicators could be used in lieu of or in addition to air change rate requirements to optimize cost and quality for an operating room and other critical environments. Copyright © 2017 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.

  3. The effect of ventilation strategies of child care centers on indoor air quality and respiratory health of children in Singapore.

    PubMed

    Zuraimi, M S; Tham, K W; Chew, F T; Ooi, P L

    2007-08-01

    This paper reports the effects of ventilation strategies on indoor air quality (IAQ) and respiratory health of children within 104 child care centers (CCCs) in a hot and humid climate. The CCCs were categorized by ventilation strategies: natural (NV), air-conditioned and mechanically ventilated (ACMV), air-conditioned using split units (AC), and hybrid (NV and AC operated intermittently). The concentration levels of IAQ parameters in NV CCCs are characterized by the influence of the outdoors and good dilution of indoor pollutants. The lower ventilation rates in air-conditioned CCCs result in higher concentrations of occupant-related pollutants but lower outdoor pollutant ingress. This study also revealed lower prevalence for most asthma and allergy, and respiratory symptoms in children attending NV CCCs. In multivariate analyses controlled for the effects of confounders, the risk of current rhinitis among children is significantly higher if they attend mechanically ventilated CCCs compared to NV CCCs. Air-conditioned CCCs were also associated with higher adjusted prevalence ratio of severe phlegm and cough symptoms and lower respiratory illness. Finally, children attending CCCs with hybrid ventilation are at high risk for almost all the respiratory symptoms studied. This large field study indicates that different ventilation strategies employed by child care centers can cause significant variations in the indoor air quality and prevalence of asthma, allergies and respiratory symptoms of attending children. The higher prevalence rates of allergic and respiratory symptoms among young children, whose immune system is still under-developed, in child care centers, whether fully or partially air-conditioned, suggest that ventilation and plausible growth and propagation mechanisms of allergens and infectious agents be further investigated.

  4. Ventilation Rates and Airflow Pathways in Patient Rooms: A Case Study of Bioaerosol Containment and Removal.

    PubMed

    Mousavi, Ehsan S; Grosskopf, Kevin R

    2015-11-01

    Most studies on the transmission of infectious airborne disease have focused on patient room air changes per hour (ACH) and how ACH provides pathogen dilution and removal. The logical but mostly unproven premise is that greater air change rates reduce the concentration of infectious particles and thus, the probability of airborne disease transmission. Recently, a growing body of research suggests pathways between pathogenic source (patient) and control (exhaust) may be the dominant environmental factor. While increases in airborne disease transmission have been associated with ventilation rates below 2 ACH, comparatively less data are available to quantify the benefits of higher air change rates in clinical spaces. As a result, a series of tests were conducted in an actual hospital to observe the containment and removal of respirable aerosols (0.5-10 µm) with respect to ventilation rate and directional airflow in a general patient room, and, an airborne infectious isolation room. Higher ventilation rates were not found to be proportionately effective in reducing aerosol concentrations. Specifically, increasing mechanical ventilation from 2.5 to 5.5 ACH reduced aerosol concentrations only 30% on average. However, particle concentrations were more than 40% higher in pathways between the source and exhaust as was the suspension and migration of larger particles (3-10 µm) throughout the patient room(s). Computational analyses were used to validate the experimental results, and, to further quantify the effect of ventilation rate on exhaust and deposition removal in patient rooms as well as other particle transport phenomena. © The Author 2015. Published by Oxford University Press on behalf of the British Occupational Hygiene Society.

  5. Classroom ventilation and indoor air quality-results from the FRESH intervention study.

    PubMed

    Rosbach, J; Krop, E; Vonk, M; van Ginkel, J; Meliefste, C; de Wind, S; Gehring, U; Brunekreef, B

    2016-08-01

    Inadequate ventilation of classrooms may lead to increased concentrations of pollutants generated indoors in schools. The FRESH study, on the effects of increased classroom ventilation on indoor air quality, was performed in 18 naturally ventilated classrooms of 17 primary schools in the Netherlands during the heating seasons of 2010-2012. In 12 classrooms, ventilation was increased to targeted CO2 concentrations of 800 or 1200 ppm, using a temporary CO2 controlled mechanical ventilation system. Six classrooms were included as controls. In each classroom, data on endotoxin, β(1,3)-glucans, and particles with diameters of <10 μm (PM10 ) and <2.5 μm (PM2.5 ) and nitrogen dioxide (NO2 ) were collected during three consecutive weeks. Associations between the intervention and these measured indoor air pollution levels were assessed using mixed models, with random classroom effects. The intervention lowered endotoxin and β(1,3)-glucan levels and PM10 concentrations significantly. PM10 for instance was reduced by 25 μg/m³ (95% confidence interval 13-38 μg/m³) from 54 μg/m³ at maximum ventilation rate. No significant differences were found between the two ventilation settings. Concentrations of PM2.5 and NO2 were not affected by the intervention. Our results provide evidence that increasing classroom ventilation is effective in decreasing the concentrations of some indoor-generated pollutants. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  6. Sensor-based demand controlled ventilation

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    De Almeida, A.T.; Fisk, W.J.

    In most buildings, occupancy and indoor pollutant emission rates vary with time. With sensor-based demand-controlled ventilation (SBDCV), the rate of ventilation (i.e., rate of outside air supply) also varies with time to compensate for the changes in pollutant generation. In other words, SBDCV involves the application of sensing, feedback and control to modulate ventilation. Compared to ventilation without feedback, SBDCV offers two potential advantages: (1) better control of indoor pollutant concentrations; and (2) lower energy use and peak energy demand. SBDCV has the potential to improve indoor air quality by increasing the rate of ventilation when indoor pollutant generation ratesmore » are high and occupants are present. SBDCV can also save energy by decreasing the rate of ventilation when indoor pollutant generation rates are low or occupants are absent. After providing background information on indoor air quality and ventilation, this report provides a relatively comprehensive discussion of SBDCV. Topics covered in the report include basic principles of SBDCV, sensor technologies, technologies for controlling air flow rates, case studies of SBDCV, application of SBDCV to laboratory buildings, and research needs. SBDCV appears to be an increasingly attractive technology option. Based on the review of literature and theoretical considerations, the application of SBDCV has the potential to be cost-effective in applications with the following characteristics: (a) a single or small number of dominant pollutants, so that ventilation sufficient to control the concentration of the dominant pollutants provides effective control of all other pollutants; (b) large buildings or rooms with unpredictable temporally variable occupancy or pollutant emission; and (c) climates with high heating or cooling loads or locations with expensive energy.« less

  7. Air compressor battery duration with mechanical ventilation in a field anesthesia machine.

    PubMed

    Szpisjak, Dale F; Giberman, Anthony A

    2015-05-01

    Compressed air to power field anesthesia machine ventilators may be supplied by air compressor with battery backup. This study determined the battery duration when the compPAC ventilator's air compressor was powered by NiCd battery to ventilate the Vent Aid Training Test Lung modeling high (HC = 0.100 L/cm H2O) and low (LC = 0.020 L/cm H2O) pulmonary compliance. Target tidal volumes (VT) were 500, 750, and 1,000 mL. Respiratory rate = 10 bpm, inspiratory-to-expiratory time ratio = 1:2, and fresh gas flow = 1 L/min air. N = 5 in each group. Control limits were determined from the first 150 minutes of battery power for each run and lower control limit = mean VT - 3SD. Battery depletion occurred when VT was below the lower control limit. Battery duration ranged from 185.8 (±3.2) minutes in the LC-1000 group to 233.3 (±3.6) minutes in the HC-750 group. Battery duration of the LC-1000 group was less than all others (p = 0.027). The differences among the non-LC-1000 groups were not clinically significant. Reprint & Copyright © 2015 Association of Military Surgeons of the U.S.

  8. Influence of ventilation structure on air flow distribution of large turbo-generator

    NASA Astrophysics Data System (ADS)

    Zhang, Liying; Ding, Shuye; Zhao, Zhijun; Yang, Jingmo

    2018-04-01

    For the 350 MW air - cooled turbo—generator, the rotor body is ventilated by sub -slots and 94 radial ventilation ducts and the end adopts arc segment and the straight section to acquire the wind. The stator is ventilated with five inlets and eight outlet air branches. In order to analyze the cooling effect of different ventilation schemes, a global physical model including the stator, rotor, casing and fan is established, and the assumptions and boundary conditions of the solution domain are given. the finite volume method is used to solve the problem, and the air flow distribution characteristics of each part of the motor under different ventilation schemes are obtained. The results show that the baffle at the end of the rotor can eliminate the eddy current at the end of the rotor, and make the flow distribution of cooling air more uniform and reasonable. The conclusions can provide reference for the design of motor ventilation structure.

  9. Heart rate and leukocytes after air and ground transportation in artificially ventilated neonates: a prospective observational study.

    PubMed

    Grosek, Stefan; Mlakar, Gorazd; Vidmar, Ivan; Ihan, Alojz; Primozic, Janez

    2009-01-01

    To evaluate the effect of interhospital air and ground transportation of artificially ventilated neonates on heart rate and peripheral blood leukocyte counts. Prospective, observational study. Level III multidisciplinary Neonatal and Pediatric Intensive Care Unit. Fifty-eight near-term artificially ventilated transported neonates between May 2006 and April 2007. Day-helicopter, day- and night-ground transportation. Heart rate at retrieval, on admission to the ICU and 1 h later, and peripheral blood leukocyte counts on admission and 1 d later were compared. Fifteen neonates were transported by helicopter during the daytime (D-HEL), 20 by daytime ground and 23 by nighttime ground transportation (D-GROUND, N-GROUND). No differences in delivery mode, birth weight, gestational age, gender, primary diagnoses for transportation, response time and duration of transportation were found between the groups. Similarly, no differences in pH, pCO(2), blood pressure and skin temperature at retrieval and on admission to the ICU were found between the three groups. The mean heart rate at retrieval did not differ significantly, while on arrival in the ICU and 1 h later the D-GROUND group of patients showed a significantly higher mean heart rate compared to the D-HEL and N-GROUND groups. Moreover, leukocyte counts on arrival in the ICU showed significantly higher leukocyte counts in the D-GROUND group of patients compared to the D-HEL group of patients. These results demonstrate that there is an association between daytime ground transportation and higher heart rate and peripheral blood leukocytes.

  10. Exhaust ventilation in attached garages improves residential indoor air quality.

    PubMed

    Mallach, G; St-Jean, M; MacNeill, M; Aubin, D; Wallace, L; Shin, T; Van Ryswyk, K; Kulka, R; You, H; Fugler, D; Lavigne, E; Wheeler, A J

    2017-03-01

    Previous research has shown that indoor benzene levels in homes with attached garages are higher than homes without attached garages. Exhaust ventilation in attached garages is one possible intervention to reduce these concentrations. To evaluate the effectiveness of this intervention, a randomized crossover study was conducted in 33 Ottawa homes in winter 2014. VOCs including benzene, toluene, ethylbenzene, and xylenes, nitrogen dioxide, carbon monoxide, and air exchange rates were measured over four 48-hour periods when a garage exhaust fan was turned on or off. A blower door test conducted in each garage was used to determine the required exhaust fan flow rate to provide a depressurization of 5 Pa in each garage relative to the home. When corrected for ambient concentrations, the fan decreased geometric mean indoor benzene concentrations from 1.04 to 0.40 μg/m 3 , or by 62% (P<.05). The garage exhaust fan also significantly reduced outdoor-corrected geometric mean indoor concentrations of other pollutants, including toluene (53%), ethylbenzene (47%), m,p-xylene (45%), o-xylene (43%), and carbon monoxide (23%) (P<.05) while having no impact on the home air exchange rate. This study provides evidence that mechanical exhaust ventilation in attached garages can reduce indoor concentrations of pollutants originating from within attached garages. © 2016 Her Majesty the Queen in Right of Canada. Indoor Air published by John Wiley & Sons Ltd.

  11. Technical Note: A proposal of air ventilation system design criteria for a clinical room in a heavy-ion medical facility.

    PubMed

    Kum, Oyeon

    2018-06-01

    An optimized air ventilation system design for a treatment room in Heavy-ion Medical Facility is an important issue in the aspects of nuclear safety because the activated air produced in a treatment room can directly affect the medical staff and the general public in the radiation-free area. Optimized design criteria of air ventilation system for a clinical room in 430 MeV/u carbon ion beam medical accelerator facility was performed by using a combination of MCNPX2.7.0 and CINDER'90 codes. Effective dose rate and its accumulated effective dose by inhalation and residual gamma were calculated for a normal treatment scenario (2 min irradiation for one fraction) as a function of decay time. Natural doses around the site were measured before construction and used as reference data. With no air ventilation system, the maximum effective dose rate was about 3 μSv/h (total dose of 90 mSv/y) and minimum 0.2 μSv/h (total dose of 6 mSv/y), which are over the legal limits for medical staff and for the general public. Although inhalation dose contribution was relatively small, it was considered seriously because of its long-lasting effects in the body. The integrated dose per year was 1.8 mSv/y in the radiation-free area with the 20-min rate of air ventilation system. An optimal air ventilation rate of 20 min is proposed for a clinical room, which also agrees with the best mechanical design value. © 2018 American Association of Physicists in Medicine.

  12. Summary of human responses to ventilation.

    PubMed

    Seppänen, O A; Fisk, W J

    2004-01-01

    It is known that ventilation is necessary to remove indoor-generated pollutants from indoor air or dilute their concentration to acceptable levels. But as the limit values of all pollutants are not known the exact determination of required ventilation rates based on pollutant concentrations is seldom possible. The selection of ventilation rates has to be based also on epidemiological research, laboratory and field experiments and experience. The existing literature indicates that ventilation has a significant impact on several important human outcomes including: (1) communicable respiratory illnesses; (2) sick building syndrome symptoms; (3) task performance and productivity, and (4) perceived air quality (PAQ) among occupants or sensory panels (5) respiratory allergies and asthma. In many studies, prevalence of sick building syndrome symptoms has also been associated with characteristics of HVAC-systems. Often the prevalence of SBS symptoms is higher in air-conditioned buildings than in naturally ventilated buildings. The evidence suggests that better hygiene, commissioning, operation and maintenance of air handling systems may be particularly important for reducing the negative effects of HVAC systems. Ventilation may also have harmful effects on indoor air quality and climate if not properly designed, installed, maintained and operated. Ventilation may bring indoors harmful substances or deteriorate indoor environment. Ventilation interacts also with the building envelope and may deteriorate the structures of the building. Ventilation changes the pressure differences across the structures of building and may cause or prevent infiltration of pollutants from structures or adjacent spaces. Ventilation is also in many cases used to control the thermal environment or humidity in buildings. The paper summarises the current knowledge on positive and negative effects of ventilation on health and other human responses. The focus is on office-type working environment and

  13. 21 CFR 211.46 - Ventilation, air filtration, air heating and cooling.

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... 21 Food and Drugs 4 2010-04-01 2010-04-01 false Ventilation, air filtration, air heating and cooling. 211.46 Section 211.46 Food and Drugs FOOD AND DRUG ADMINISTRATION, DEPARTMENT OF HEALTH AND HUMAN SERVICES (CONTINUED) DRUGS: GENERAL CURRENT GOOD MANUFACTURING PRACTICE FOR FINISHED PHARMACEUTICALS...

  14. Influence of Applying Additional Forcing Fans for the Air Distribution in Ventilation Network

    NASA Astrophysics Data System (ADS)

    Szlązak, Nikodem; Obracaj, Dariusz; Korzec, Marek

    2016-09-01

    Mining progress in underground mines cause the ongoing movement of working areas. Consequently, it becomes necessary to adapt the ventilation network of a mine to direct airflow into newly-opened districts. For economic reasons, opening new fields is often achieved via underground workings. Length of primary intake and return routes increases and also increases the total resistance of a complex ventilation network. The development of a subsurface structure can make it necessary to change the air distribution in a ventilation network. Increasing airflow into newly-opened districts is necessary. In mines where extraction does not entail gas-related hazards, there is possibility of implementing a push-pull ventilation system in order to supplement airflows to newly developed mining fields. This is achieved by installing subsurface fan stations with forcing fans at the bottom of downcast shaft. In push-pull systems with multiple main fans, it is vital to select forcing fans with characteristic curves matching those of the existing exhaust fans to prevent undesirable mutual interaction. In complex ventilation networks it is necessary to calculate distribution of airflow (especially in networks with a large number of installed fans). In the article the influence of applying additional forcing fans for the air distribution in ventilation network for underground mine were considered. There are also analysed the extent of overpressure caused by the additional forcing fan in branches of the ventilation network (the operating range of additional forcing fan). Possibilities of increasing airflow rate in working areas were conducted.

  15. The effect of low ventilation rate with elevated bioeffluent concentration on work performance, perceived indoor air quality, and health symptoms.

    PubMed

    Maula, H; Hongisto, V; Naatula, V; Haapakangas, A; Koskela, H

    2017-11-01

    The aim of this laboratory experiment was to study the effects of ventilation rate, and related changes in air quality, predominantly bioeffluents, on work performance, perceived indoor air quality, and health symptoms in a typical conditions of modern open-plan office with low material and equipment emissions. In Condition A, outdoor air flow rate of 28.2 l/s person (CO 2 level 540 ppm) was applied and in Condition B, outdoor air flow rate was 2.3 l/s person (CO 2 level 2260 ppm). CO 2 concentration level was used as an indicator of bioeffluents. Performance was measured with seven different tasks which measure different cognitive processes. Thirty-six subjects participated in the experiment. The exposure time was 4 hours. Condition B had a weak negative effect on performance only in the information retrieval tasks. Condition B increased slightly subjective workload and perceived fatigue. No effects on health symptoms were found. The intensity of symptoms was low in both conditions. The experimental condition had an effect on perceived air quality and observed odor intensity only in the beginning of the session. Although the room temperature was controlled in both conditions, the heat was perceived to impair the performance more in Condition B. © 2017 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  16. Infiltration as Ventilation: Weather-Induced Dilution

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Sherman, Max H.; Turner, William J.N.; Walker, Iain S.

    The purpose of outdoor air ventilation is to dilute or remove indoor contaminants to which occupants are exposed. It can be provided by mechanical or natural means. In most homes, especially older homes, weather-driven infiltration provides the dominant fraction of the total ventilation. As we seek to provide good indoor air quality at minimum energy cost, it is important to neither over-ventilate nor under-ventilate. Thus, it becomes critically important to evaluate correctly the contribution infiltration makes to the total outdoor air ventilation rate. Because weather-driven infiltration is dependent on building air leakage and weather-induced pressure differences, a given amount ofmore » air leakage will provide different amounts of infiltration. Varying rates of infiltration will provide different levels of contaminant dilution and hence effective ventilation. This paper derives these interactions and then calculates the impact of weather-driven infiltration for different climates. A new “N-factor” is introduced to provide a convenient method for calculating the ventilation contribution of infiltration for over 1,000 locations across North America. The results of this work could be used in indoor air quality standards (specifically ASHRAE 62.2) to account for the contribution of weather-driven infiltration towards the dilution of indoor pollutants.« less

  17. [Assessment of the air quality improment of cleaning and disinfection on central air-conditioning ventilation system].

    PubMed

    Liu, Hongliang; Zhang, Lei; Feng, Lihong; Wang, Fei; Xue, Zhiming

    2009-09-01

    To assess the effect of air quality of cleaning and disinfection on central air-conditioning ventilation systems. 102 air-conditioning ventilation systems in 46 public facilities were sampled and investigated based on Hygienic assessment criterion of cleaning and disinfection of public central air-conditioning systems. Median dust volume decreased from 41.8 g/m2 to 0.4 g/m2, and the percentage of pipes meeting the national standard for dust decreased from 17.3% (13/60) to 100% (62/62). In the dust, median aerobic bacterial count decreased from 14 cfu/cm2 to 1 cfu/cm2. Median aerobic fungus count decreased from 10 cfu/cm2 to 0 cfu/cm2. The percentage of pipes with bacterial and fungus counts meeting the national standard increased from 92.4% (171/185) and 82.2% (152/185) to 99.4% (165/166) and 100% (166/166), respectively. In the ventilation air, median aerobic bacterial count decreased from 756 cfu/m3 to 229 cfu/m3. Median aerobic fungus count decreased from 382 cfu/m3 to 120 cfu/m3. The percentage of pipes meeting the national standard for ventilation air increased from 33.3% (81/243) and 62.1% (151/243) to 79.8% (292/366) and 87.7% (242/276), respectively. But PM10 rose from 0.060 mg/m3 to 0.068 mg/m3, and the percentage of pipes meeting the national standard for PM10 increased from 74.2% (13/60) to 90.2% (46/51). The cleaning and disinfection of central air-conditioning ventilation systems could have a beneficial effect of air quality.

  18. Indoor air quality in a middle school, Part I: Use of CO2 as a tracer for effective ventilation.

    PubMed

    Scheff, P A; Paulius, V K; Huang, S W; Conroy, L M

    2000-11-01

    The overall objective of the study was to evaluate the indoor air quality at a middle school with an emphasis on characterizing baseline conditions. The focus of this article is on the relationship between occupancy and measured concentrations of carbon dioxide, and an evaluation of the use of carbon dioxide as a tracer for ventilation in the school. The school was characterized as having no health complaints, good maintenance schedules, no carpeting within the classrooms or hallways, and no significant remodeling, and its officials had agreed to allow the sampling to take place during school hours. Monitoring followed the guidelines recommended in the "Preliminary Draft: Conceptual Standardized EPA Protocol For Characterizing Indoor Air Quality in School Buildings." Four indoor locations including the cafeteria, a science classroom, an art classroom, and the lobby outside the main office, and one outdoor location were sampled for various environmental comfort and pollutant parameters for one week in February 1997. A consistent relationship between hourly occupancy and corresponding carbon dioxide concentrations was seen. Carbon dioxide concentrations in the cafeteria, art room, and lobby were within specified American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) guidelines for comfort (< 1000 ppm). The science room had the highest concentrations (frequently exceeding 1000 ppm) due to high occupancy and non-functioning unit ventilators. Measured ventilation rates were within specified ASHRAE guidelines for the art room, cafeteria, and lobby. The science room, which relied on natural ventilation only, was not able to meet the ASHRAE guideline on one of the three days studied. The use of a completely mixed space, one compartment mass balance model with estimated CO2 generation rates and measured CO2 concentrations is shown to be a useful method for evaluating ventilation. Modeled effective ventilation, air changes per hour, and mixing

  19. Indoor airborne bacterial communities are influenced by ventilation, occupancy, and outdoor air source.

    PubMed

    Meadow, J F; Altrichter, A E; Kembel, S W; Kline, J; Mhuireach, G; Moriyama, M; Northcutt, D; O'Connor, T K; Womack, A M; Brown, G Z; Green, J L; Bohannan, B J M

    2014-02-01

    Architects and engineers are beginning to consider a new dimension of indoor air: the structure and composition of airborne microbial communities. A first step in this emerging field is to understand the forces that shape the diversity of bioaerosols across space and time within the built environment. In an effort to elucidate the relative influences of three likely drivers of indoor bioaerosol diversity - variation in outdoor bioaerosols, ventilation strategy, and occupancy load - we conducted an intensive temporal study of indoor airborne bacterial communities in a high-traffic university building with a hybrid HVAC (mechanically and naturally ventilated) system. Indoor air communities closely tracked outdoor air communities, but human-associated bacterial genera were more than twice as abundant in indoor air compared with outdoor air. Ventilation had a demonstrated effect on indoor airborne bacterial community composition; changes in outdoor air communities were detected inside following a time lag associated with differing ventilation strategies relevant to modern building design. Our results indicate that both occupancy patterns and ventilation strategies are important for understanding airborne microbial community dynamics in the built environment. © 2013 The Authors. Indoor Air published by John Wiley & Sons Ltd.

  20. Quantifying air distribution, ventilation effectiveness and airborne pollutant transport in an aircraft cabin mockup

    NASA Astrophysics Data System (ADS)

    Wang, Aijun

    The health, safety and comfort of passengers during flight inspired this research into cabin air quality, which is closely related to its airflow distribution, ventilation effectiveness and airborne pollutant transport. The experimental facility is a full-scale aircraft cabin mockup. A volumetric particle tracking velocimetry (VPTV) technique was enhanced by incorporating a self-developed streak recognition algorithm. Two stable recirculation regions, the reverse flows above the seats and the main air jets from the air supply inlets formed the complicated airflow patterns inside the cabin mockup. The primary air flow was parallel to the passenger rows. The small velocity component in the direction of the cabin depth caused less net air exchange between the passenger rows than that parallel to the passenger rows. Different total air supply rate changed the developing behaviors of the main air jets, leading to different local air distribution patterns. Two indices, Local mean age of air and ventilation effectiveness factor (VEF), were measured at five levels of air supply rate and two levels of heating load. Local mean age of air decreased linearly with an increase in the air supply rate, while the VEF remained consistent when the air supply rate varied. The thermal buoyancy force from the thermal plume generated the upside plume flow, opposite to the main jet flow above the boundary seats and thus lowered the local net air exchange. The airborne transport dynamics depends on the distance between the source and the receptors, the relative location of pollutant source, and air supply rate. Exposure risk was significantly reduced with increased distance between source and receptors. Another possible way to decrease the exposure risk was to position the release source close to the exhaust outlets. Increasing the air supply rate could be an effective solution under some emergency situations. The large volume of data regarding the three-dimensional air velocities was

  1. Using a Ventilation Controller to Optimize Residential Passive Ventilation For Energy and Indoor Air Quality

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Turner, William; Walker, Iain

    One way to reduce the energy impact of providing residential ventilation is to use passive and hybrid systems. However, these passive and hybrid (sometimes called mixed-mode) systems must still meet chronic and acute health standards for ventilation. This study uses a computer simulation approach to examine the energy and indoor air quality (IAQ) implications of passive and hybrid ventilation systems, in 16 California climate zones. Both uncontrolled and flow controlled passive stacks are assessed. A new hybrid ventilation system is outlined that uses an intelligent ventilation controller to minimise energy use, while ensuring chronic and acute IAQ standards are met.more » ASHRAE Standard 62.2-2010 – the United States standard for residential ventilation - is used as the chronic standard, and exposure limits for PM 2.5, formaldehyde and NO 2 are used as the acute standards.The results show that controlled passive ventilation and hybrid ventilation can be used in homes to provide equivalent IAQ to continuous mechanical ventilation, for less use of energy.« less

  2. Modeled Effectiveness of Ventilation with Contaminant Control Devices on Indoor Air Quality in a Swine Farrowing Facility

    PubMed Central

    Anthony, T. Renée; Altmaier, Ralph; Park, Jae Hong; Peters, Thomas M.

    2016-01-01

    Because adverse health effects experienced by swine farm workers in concentrated animal feeding operations (CAFOs) have been associated with exposure to dust and gases, efforts to reduce exposures are warranted, particularly in winter seasons when exposures increase due to decreased ventilation. Simulation of air quality and operating costs for ventilating swine CAFO, including treating and recirculating air through a farrowing room, was performed using mass and energy balance equations over a 90-day winter season. System operation required controlling heater operation to achieve room temperatures optimal to ensure animal health (20 to 22.5°C). Five air pollution control devices, four room ventilation rates, and five recirculation patterns were examined. Inhalable dust concentrations were easily reduced using standard industrial air pollution control devices, including a cyclone, filtration, and electrostatic precipitator. Operating ventilation systems at 0.94 m3 s−1 (2000 cfm) with 75 to 100% recirculation of treated air from cyclone, electrostatic precipitator, and shaker dust filtration system achieves adequate particle control with operating costs under $1.00 per pig produced ($0.22 to 0.54), although carbon dioxide (CO2) concentrations approach 2000 ppm using in-room ventilated gas fired heaters. In no simulation were CO2 concentrations below industry recommended concentrations (1540 ppm), but alternative heating devices could reduce CO2 to acceptable concentrations. While this investigation does not represent all production swine farrowing barns, which differ in characteristics including room dimensions and swine occupancy, the simulation model and ventilation optimization methods can be applied to other production sites. This work shows that ventilation may be a cost-effective control option in the swine industry to reduce exposures. PMID:24433305

  3. Modeled effectiveness of ventilation with contaminant control devices on indoor air quality in a swine farrowing facility.

    PubMed

    Anthony, T Renée; Altmaier, Ralph; Park, Jae Hong; Peters, Thomas M

    2014-01-01

    Because adverse health effects experienced by swine farm workers in concentrated animal feeding operations (CAFOs) have been associated with exposure to dust and gases, efforts to reduce exposures are warranted, particularly in winter seasons when exposures increase due to decreased ventilation. Simulation of air quality and operating costs for ventilating swine CAFO, including treating and recirculating air through a farrowing room, was performed using mass and energy balance equations over a 90-day winter season. System operation required controlling heater operation to achieve room temperatures optimal to ensure animal health (20 to 22.5 °C). Five air pollution control devices, four room ventilation rates, and five recirculation patterns were examined. Inhalable dust concentrations were easily reduced using standard industrial air pollution control devices, including a cyclone, filtration, and electrostatic precipitator. Operating ventilation systems at 0.94 m3 s(-1) (2000 cfm) with 75 to 100% recirculation of treated air from cyclone, electrostatic precipitator, and shaker dust filtration system achieves adequate particle control with operating costs under $1.00 per pig produced ($0.22 to 0.54), although carbon dioxide (CO2) concentrations approach 2000 ppm using in-room ventilated gas fired heaters. In no simulation were CO2 concentrations below industry recommended concentrations (1540 ppm), but alternative heating devices could reduce CO2 to acceptable concentrations. While this investigation does not represent all production swine farrowing barns, which differ in characteristics including room dimensions and swine occupancy, the simulation model and ventilation optimization methods can be applied to other production sites. This work shows that ventilation may be a cost-effective control option in the swine industry to reduce exposures.

  4. Ventilation.

    PubMed

    Turner, W A; Bearg, D W; Brennan, T

    1995-01-01

    This chapter begins with an overview of the history of ventilation guidelines, which has led to the guidelines that are in effect today. Of particular interest is the most recent return in the past 5 years to ventilation rates that more closely reflect a mean or average of the range of guidelines that have existed over the past century. OSHA's and the EPA's recognition of the need to operate ventilation systems in buildings in an accountable manner is also of note. Of even more interest is the resurgence of the concept of minimum mixing and once-through ventilation air that has been pursued in parts of Northern Europe for the past 10 years, and in a school that is being designed with this concept in New Hampshire. In addition, the design concept of equipping office buildings with low pressure drop high efficiency particle filtration to remove fine particles from all of the air that is supplied to the occupants is being used increasingly in the U.S. This chapter also presents an overview of the various types of ventilation systems found in homes and commercial office buildings and the common indoor air quality problems that may be associated with them. It also offers an overview of common HVAC evaluation techniques that can be used to determine if a ventilation system is performing in a manner that makes sense for the use of the space and the needs of the occupants. Are the occupants receiving a reasonable supply of outdoor air? Is the air that they receive of reasonable quality? Are obvious pollutants being exhausted? Ventilation systems have become extremely complex and more difficult to run and maintain over the past 40 years. This trend will continue to drive the need for professionally maintained HVAC equipment that is serviced and run by individuals who are accountable for the quality of the air that the system delivers.

  5. Prototype Systems for Measuring Outdoor Air Intake Rates in Rooftop Air Handlers

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Fisk, William J.; Chan, Wanyu R.; Hotchi, Toshifumi

    2015-01-01

    The widespread absence of systems for real-time measurement and feedback control, of minimum outdoor air intake rates in HVAC systems contributes to the poor control of ventilation rates in commercial buildings. Ventilation rates affect building energy consumption and influence occupant health. The project designed fabricated and tested four prototypes of systems for measuring rates of outdoor air intake into roof top air handlers. All prototypes met the ±20% accuracy target at low wind speeds, with all prototypes accurate within approximately ±10% after application of calibration equations. One prototype met the accuracy target without a calibration. With two of four prototypemore » measurement systems, there was no evidence that wind speed or direction affected accuracy; however, winds speeds were generally below usually 3.5 m s -1 (12.6 km h -1) and further testing is desirable. The airflow resistance of the prototypes was generally less than 35 Pa at maximum RTU air flow rates. A pressure drop of this magnitude will increase fan energy consumption by approximately 4%. The project did not have resources necessary to estimate costs of mass produced systems. The retail cost of components and materials used to construct prototypes ranged from approximately $1,200 to $1,700. The test data indicate that the basic designs developed in this project, particularly the designs of two of the prototypes, have considerable merit. Further design refinement, testing, and cost analysis would be necessary to fully assess commercial potential. The designs and test results will be communicated to the HVAC manufacturing community.« less

  6. Smart ventilation energy and indoor air quality performance in residential buildings: A review

    DOE PAGES

    Guyot, Gaelle; Sherman, Max H.; Walker, Iain S.

    2017-12-30

    To better address energy and indoor air quality issues, ventilation needs to become smarter. A key smart ventilation concept is to use controls to ventilate more at times it provides either an energy or indoor air quality (IAQ) advantage (or both) and less when it provides a disadvantage. A favorable context exists in many countries to include some of the existing smart ventilation strategies in codes and standards. As a result, demand-controlled ventilation (DCV) systems are widely and easily available on the market, with more than 20 DCV systems approved and available in countries such as Belgium, France and themore » Netherlands. This paper provides a literature review on smart ventilation used in residential buildings, based on energy and indoor air quality performance. This meta-analysis includes 38 studies of various smart ventilation systems with control based on CO 2, humidity, combined CO 2 and total volatile organic compounds (TVOC), occupancy, or outdoor temperature. In conclusion, these studies show that ventilation energy savings up to 60% can be obtained without compromising IAQ, even sometimes improving it. However, the meta-analysis included some less than favorable results, with 26% energy overconsumption in some cases.« less

  7. Smart ventilation energy and indoor air quality performance in residential buildings: A review

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Guyot, Gaelle; Sherman, Max H.; Walker, Iain S.

    To better address energy and indoor air quality issues, ventilation needs to become smarter. A key smart ventilation concept is to use controls to ventilate more at times it provides either an energy or indoor air quality (IAQ) advantage (or both) and less when it provides a disadvantage. A favorable context exists in many countries to include some of the existing smart ventilation strategies in codes and standards. As a result, demand-controlled ventilation (DCV) systems are widely and easily available on the market, with more than 20 DCV systems approved and available in countries such as Belgium, France and themore » Netherlands. This paper provides a literature review on smart ventilation used in residential buildings, based on energy and indoor air quality performance. This meta-analysis includes 38 studies of various smart ventilation systems with control based on CO 2, humidity, combined CO 2 and total volatile organic compounds (TVOC), occupancy, or outdoor temperature. In conclusion, these studies show that ventilation energy savings up to 60% can be obtained without compromising IAQ, even sometimes improving it. However, the meta-analysis included some less than favorable results, with 26% energy overconsumption in some cases.« less

  8. A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study

    PubMed Central

    2013-01-01

    Background Classroom ventilation rates often do not meet building standards, although it is considered to be important to improve indoor air quality. Poor indoor air quality is thought to influence both children’s health and performance. Poor ventilation in The Netherlands most often occurs in the heating season. To improve classroom ventilation a tailor made mechanical ventilation device was developed to improve outdoor air supply. This paper studies the effect of this intervention. Methods The FRESH study (Forced-ventilation Related Environmental School Health) was designed to investigate the effect of a CO2 controlled mechanical ventilation intervention on classroom CO2 levels using a longitudinal cross-over design. Target CO2 concentrations were 800 and 1200 parts per million (ppm), respectively. The study included 18 classrooms from 17 schools from the north-eastern part of The Netherlands, 12 experimental classrooms and 6 control classrooms. Data on indoor levels of CO2, temperature and relative humidity were collected during three consecutive weeks per school during the heating seasons of 2010–2012. Associations between the intervention and weekly average indoor CO2 levels, classroom temperature and relative humidity were assessed by means of mixed models with random school-effects. Results At baseline, mean CO2 concentration for all schools was 1335 ppm (range: 763–2000 ppm). The intervention was able to significantly decrease CO2 levels in the intervention classrooms (F (2,10) = 17.59, p < 0.001), with a mean decrease of 491 ppm. With the target set at 800 ppm, mean CO2 was 841 ppm (range: 743–925 ppm); with the target set at 1200 ppm, mean CO2 was 975 ppm (range: 887–1077 ppm). Conclusions Although the device was not capable of precisely achieving the two predefined levels of CO2, our study showed that classroom CO2 levels can be reduced by intervening on classroom ventilation using a CO2 controlled mechanical ventilation system

  9. A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study.

    PubMed

    Rosbach, Jeannette T M; Vonk, Machiel; Duijm, Frans; van Ginkel, Jan T; Gehring, Ulrike; Brunekreef, Bert

    2013-12-17

    Classroom ventilation rates often do not meet building standards, although it is considered to be important to improve indoor air quality. Poor indoor air quality is thought to influence both children's health and performance. Poor ventilation in The Netherlands most often occurs in the heating season. To improve classroom ventilation a tailor made mechanical ventilation device was developed to improve outdoor air supply. This paper studies the effect of this intervention. The FRESH study (Forced-ventilation Related Environmental School Health) was designed to investigate the effect of a CO2 controlled mechanical ventilation intervention on classroom CO2 levels using a longitudinal cross-over design. Target CO2 concentrations were 800 and 1200 parts per million (ppm), respectively. The study included 18 classrooms from 17 schools from the north-eastern part of The Netherlands, 12 experimental classrooms and 6 control classrooms. Data on indoor levels of CO2, temperature and relative humidity were collected during three consecutive weeks per school during the heating seasons of 2010-2012. Associations between the intervention and weekly average indoor CO2 levels, classroom temperature and relative humidity were assessed by means of mixed models with random school-effects. At baseline, mean CO2 concentration for all schools was 1335 ppm (range: 763-2000 ppm). The intervention was able to significantly decrease CO2 levels in the intervention classrooms (F (2,10) = 17.59, p < 0.001), with a mean decrease of 491 ppm. With the target set at 800 ppm, mean CO2 was 841 ppm (range: 743-925 ppm); with the target set at 1200 ppm, mean CO2 was 975 ppm (range: 887-1077 ppm). Although the device was not capable of precisely achieving the two predefined levels of CO2, our study showed that classroom CO2 levels can be reduced by intervening on classroom ventilation using a CO2 controlled mechanical ventilation system.

  10. Constructing a generalized network design model to study air distribution in ventilation networks in subway with a single-track tunnel

    NASA Astrophysics Data System (ADS)

    Lugin, IV

    2018-03-01

    In focus are the features of construction of the generalized design model for the network method to study air distribution in ventilation system in subway with the single-track tunnel. The generalizations, assumptions and simplifications included in the model are specified. The air distribution is calculated with regard to the influence of topology and air resistances of the ventilation network sections. The author studies two variants of the subway line: half-open and closed with dead end on the both sides. It is found that the total air exchange at a subway station depends on the station location within the line. The operating mode of fans remains unaltered in this case. The article shows that elimination of air leakage in the station ventilation room allows an increase in the air flow rate by 7–8% at the same energy consumption by fans. The influence of the stop of a train in the tunnel on the air distribution is illustrated.

  11. The influence of opening windows and doors on the natural ventilation rate of a residential building

    EPA Science Inventory

    An analysis of air exchange rates due to intentional window and door openings in a research test house located in a residential environment is presented. These data inform the development of ventilation rate control strategies as building envelopes are tightened to improve the e...

  12. High Resolution Time Series Cave Ventilation Processes and the Effects on Cave Air Chemistry and Drip Waters: Speleoclimatology and Proxy Calibration

    NASA Astrophysics Data System (ADS)

    Kowalczk, A. J.; Froelich, P. N.; Gaffka, C.; Tremaine, D.

    2008-12-01

    Continuous high resolution (sub-hourly), long-term (Nov 2007-present) monitoring of cave air chemistry (Temperature, Relative Humidity, Barometric Pressure, Radon-222, CO2, Air flow, Wind speed and direction) in a shallow subtropical cave (Hollow Ridge) in N Florida reveals two major ventilation mechanisms: 1) ventilation driven by winds across the cave entrances, and 2) ventilation driven by density differences between atmospheric and cave air. The degree and type of ventilation strongly influence the 222Rn and CO2 of cave air, which in turn affects the timing and extent of calcite deposition in speleothems. The degree of ventilation is estimated using a cave air CO2-δ13CO2 Keeling Plot, or a simple radon deficiency model. Results show cave air has an atmospheric component ranging from 10-90%. During fall and winter, average CO2 (700 ppmv) and 222Rn (50-100 dpm/L) are lower than in spring and summer (CO2 = 1200 ppmv; 222Rn = 1000 dpm/L) due to increased winter ventilation. Decreased ventilation during the summer allows CO2 and 222Rn levels to rise. Winter daily ventilation is primarily a function of density gradients between cave air and atmospheric air, while summer daily ventilation is primarily a function of late morning NW-NE winds above the cave. Stable isotope analyses of drip water (fracture drip and pore flow drip) and aquifer water from Hollow Ridge agree with previous isotope studies of drip water at Florida Caverns State Park, 2 km to the NE. During summer, isotopic composition of pore flow drip water (δ18O -3.8 to -4.0 per mil; δD -17.3 to -20.2 per mil VSMOW) and aquifer water (δ18O -4.0 per mil; δD -18.0 to -21.1 per mil) are similar to average annual weighted isotopic composition of precipitation (δ18O -3.6 per mil) while fracture drip waters (δ18O -3 to -3.4 per mil; δD -11.9 to -14.3 per mil) likely reflect the isotopic composition of individual precipitation events. Pore flow drip waters δ18O are weakly correlated with drip rates

  13. Optimization of Ventilation Energy Demands and Indoor Air Quality in High-Performance Homes

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Hun, Diana E; Jackson, Mark C; Shrestha, Som S

    2014-01-01

    High-performance homes require that ventilation energy demands and indoor air quality (IAQ) be simultaneously optimized. We attempted to bridge these two areas by conducting tests in a research house located in Oak Ridge, TN, that was 20 months old, energy-efficient (i.e., expected to consume 50% less energy than a house built per the 2006 IRC), tightly-built (i.e., natural ventilation rate ~0.02 h-1), unoccupied, and unfurnished. We identified air pollutants of concern in the test home that could generally serve as indicators of IAQ, and conduced field experiments and computer simulations to determine the effectiveness and energy required by various techniquesmore » that lessened the concentration of these contaminants. Formaldehyde was selected as the main pollutant of concern among the contaminants that were sampled in the initial survey because it was the only compound that showed concentrations that were greater than the recommended exposure levels. Field data indicate that concentrations were higher during the summer primarily because emissions from sources rise with increases in temperature. Furthermore, supply ventilation and gas-phase filtration were effective means to reduce formaldehyde concentrations; however, exhaust ventilation had minimal influence on this pollutant. Results from simulations suggest that formaldehyde concentrations obtained while ventilating per ASHRAE 62.2-2010 could be decreased by about 20% from May through September through three strategies: 1) increasing ASHRAE supply ventilation by a factor of two, 2) reducing the thermostat setpoint from 76 to 74 F, or 3) running a gas-phase filtration system while decreasing supply ventilation per ASHRAE by half. In the mixed-humid climate of Oak Ridge, these strategies caused increases in electricity cost of ~$5 to ~$15/month depending on outdoor conditions.« less

  14. Association between substandard classroom ventilation rates and students' academic achievement.

    PubMed

    Haverinen-Shaughnessy, U; Moschandreas, D J; Shaughnessy, R J

    2011-04-01

    This study focuses on the relationship between classroom ventilation rates and academic achievement. One hundred elementary schools of two school districts in the southwest United States were included in the study. Ventilation rates were estimated from fifth-grade classrooms (one per school) using CO(2) concentrations measured during occupied school days. In addition, standardized test scores and background data related to students in the classrooms studied were obtained from the districts. Of 100 classrooms, 87 had ventilation rates below recommended guidelines based on ASHRAE Standard 62 as of 2004. There is a linear association between classroom ventilation rates and students' academic achievement within the range of 0.9-7.1 l/s per person. For every unit (1 l/s per person) increase in the ventilation rate within that range, the proportion of students passing standardized test (i.e., scoring satisfactory or above) is expected to increase by 2.9% (95%CI 0.9-4.8%) for math and 2.7% (0.5-4.9%) for reading. The linear relationship observed may level off or change direction with higher ventilation rates, but given the limited number of observations, we were unable to test this hypothesis. A larger sample size is needed for estimating the effect of classroom ventilation rates higher than 7.1 l/s per person on academic achievement. The results of this study suggest that increasing the ventilation rates toward recommended guideline ventilation rates in classrooms should translate into improved academic achievement of students. More studies are needed to fully understand the relationships between ventilation rate, other indoor environmental quality parameters, and their effects on students' health and achievement. Achieving the recommended guidelines and pursuing better understanding of the underlying relationships would ultimately support both sustainable and productive school environments for students and personnel. © 2010 John Wiley & Sons A/S.

  15. Air change rates of motor vehicles and in-vehicle pollutant concentrations from secondhand smoke.

    PubMed

    Ott, Wayne; Klepeis, Neil; Switzer, Paul

    2008-05-01

    The air change rates of motor vehicles are relevant to the sheltering effect from air pollutants entering from outside a vehicle and also to the interior concentrations from any sources inside its passenger compartment. We made more than 100 air change rate measurements on four motor vehicles under moving and stationary conditions; we also measured the carbon monoxide (CO) and fine particle (PM(2.5)) decay rates from 14 cigarettes smoked inside the vehicle. With the vehicle stationary and the fan off, the ventilation rate in air changes per hour (ACH) was less than 1 h(-1) with the windows closed and increased to 6.5 h(-1) with one window fully opened. The vehicle speed, window position, ventilation system, and air conditioner setting was found to affect the ACH. For closed windows and passive ventilation (fan off and no recirculation), the ACH was linearly related to the vehicle speed over the range from 15 to 72 mph (25 to 116 km h(-1)). With a vehicle moving, windows closed, and the ventilation system off (or the air conditioner set to AC Max), the ACH was less than 6.6 h(-1) for speeds ranging from 20 to 72 mph (32 to 116 km h(-1)). Opening a single window by 3'' (7.6 cm) increased the ACH by 8-16 times. For the 14 cigarettes smoked in vehicles, the deposition rate k and the air change rate a were correlated, following the equation k=1.3a (R(2)=82%; n=14). With recirculation on (or AC Max) and closed windows, the interior PM(2.5) concentration exceeded 2000 microg m(-3) momentarily for all cigarettes tested, regardless of speed. The concentration time series measured inside the vehicle followed the mathematical solutions of the indoor mass balance model, and the 24-h average personal exposure to PM(2.5) could exceed 35 microg m(-3) for just two cigarettes smoked inside the vehicle.

  16. Energy and Cost Associated with Ventilating Office Buildings in a Tropical Climate

    PubMed Central

    Rim, Donghyun; Schiavon, Stefano; Nazaroff, William W.

    2015-01-01

    Providing sufficient amounts of outdoor air to occupants is a critical building function for supporting occupant health, well-being and productivity. In tropical climates, high ventilation rates require substantial amounts of energy to cool and dehumidify supply air. This study evaluates the energy consumption and associated cost for thermally conditioning outdoor air provided for building ventilation in tropical climates, considering Singapore as an example locale. We investigated the influence on energy consumption and cost of the following factors: outdoor air temperature and humidity, ventilation rate (L/s per person), indoor air temperature and humidity, air conditioning system coefficient of performance (COP), and cost of electricity. Results show that dehumidification of outdoor air accounts for more than 80% of the energy needed for building ventilation in Singapore’s tropical climate. Improved system performance and/or a small increase in the indoor temperature set point would permit relatively large ventilation rates (such as 25 L/s per person) at modest or no cost increment. Overall, even in a thermally demanding tropical climate, the energy cost associated with increasing ventilation rate up to 25 L/s per person is less than 1% of the wages of an office worker in an advanced economy like Singapore’s. This result implies that the benefits of increasing outdoor air ventilation rate up to 25 L/s per person — which is suggested to provide for productivity increases, lower sick building syndrome symptom prevalence, and reduced sick leave — can be much larger than the incremental cost of ventilation. PMID:25822504

  17. Energy and cost associated with ventilating office buildings in a tropical climate.

    PubMed

    Rim, Donghyun; Schiavon, Stefano; Nazaroff, William W

    2015-01-01

    Providing sufficient amounts of outdoor air to occupants is a critical building function for supporting occupant health, well-being and productivity. In tropical climates, high ventilation rates require substantial amounts of energy to cool and dehumidify supply air. This study evaluates the energy consumption and associated cost for thermally conditioning outdoor air provided for building ventilation in tropical climates, considering Singapore as an example locale. We investigated the influence on energy consumption and cost of the following factors: outdoor air temperature and humidity, ventilation rate (L/s per person), indoor air temperature and humidity, air conditioning system coefficient of performance (COP), and cost of electricity. Results show that dehumidification of outdoor air accounts for more than 80% of the energy needed for building ventilation in Singapore's tropical climate. Improved system performance and/or a small increase in the indoor temperature set point would permit relatively large ventilation rates (such as 25 L/s per person) at modest or no cost increment. Overall, even in a thermally demanding tropical climate, the energy cost associated with increasing ventilation rate up to 25 L/s per person is less than 1% of the wages of an office worker in an advanced economy like Singapore's. This result implies that the benefits of increasing outdoor air ventilation rate up to 25 L/s per person--which is suggested to provide for productivity increases, lower sick building syndrome symptom prevalence, and reduced sick leave--can be much larger than the incremental cost of ventilation.

  18. Heating, Ventilation, and Air Conditioning Series. Duty Task List.

    ERIC Educational Resources Information Center

    Oklahoma State Dept. of Vocational and Technical Education, Stillwater. Curriculum and Instructional Materials Center.

    This task list is intended for use in planning and/or evaluating a competency-based course in heating, ventilation, and air conditioning. The guide outlines the tasks entailed in eight different duties typically required of employees in the following occupations: residential installer, domestic refrigeration technician, air conditioning and…

  19. Review and Extension of CO₂-Based Methods to Determine Ventilation Rates with Application to School Classrooms.

    PubMed

    Batterman, Stuart

    2017-02-04

    The ventilation rate (VR) is a key parameter affecting indoor environmental quality (IEQ) and the energy consumption of buildings. This paper reviews the use of CO₂ as a "natural" tracer gas for estimating VRs, focusing on applications in school classrooms. It provides details and guidance for the steady-state, build-up, decay and transient mass balance methods. An extension to the build-up method and an analysis of the post-exercise recovery period that can increase CO₂ generation rates are presented. Measurements in four mechanically-ventilated school buildings demonstrate the methods and highlight issues affecting their applicability. VRs during the school day fell below recommended minimum levels, and VRs during evening and early morning were on the order of 0.1 h -1 , reflecting shutdown of the ventilation systems. The transient mass balance method was the most flexible and advantageous method given the low air change rates and dynamic occupancy patterns observed in the classrooms. While the extension to the build-up method improved stability and consistency, the accuracy of this and the steady-state method may be limited. Decay-based methods did not reflect the VR during the school day due to heating, ventilation and air conditioning (HVAC) system shutdown. Since the number of occupants in classrooms changes over the day, the VR expressed on a per person basis (e.g., L·s -1 ·person -1 ) depends on the occupancy metric. If occupancy measurements can be obtained, then the transient mass balance method likely will provide the most consistent and accurate results among the CO₂-based methods. Improved VR measurements can benefit many applications, including research examining the linkage between ventilation and health.

  20. Measuring Infiltration Rates in Homes as a Basis for Understanding Indoor Air Quality

    NASA Astrophysics Data System (ADS)

    Jerz, G. G.; Lamb, B. K.; Pressley, S. N.; O'Keeffe, P.; Fuchs, M.; Kirk, M.

    2015-12-01

    Infiltration rates, or the rate of air exchange, of houses are important to understand because ventilation can be a dominate factor in determining indoor air quality. There are chemicals that are emitted from surfaces or point sources inside the home which are harmful to humans; these chemicals come from various objects including furniture, cleaning supplies, building materials, gas stoves, and the surrounding environment. The use of proper ventilation to cycle cleaner outdoor air into the house can be crucial for maintaining healthy living conditions in the home. At the same time, there can also be outdoor pollutants which infiltrate the house and contribute to poor indoor air quality. In either case, it is important to determine infiltration rates as a function of outdoor weather conditions, the house structure properties and indoor heating and cooling systems. In this work, the objective is to measure ventilation rates using periodic releases of a tracer gas and measuring how quickly the tracer concentration decays. CO2 will be used as the tracer gas because it is inert and harmless at low levels. An Arduino timer is connected to a release valve which controls the release of 9.00 SLPM of CO2 into the uptake vent within the test home. CO2 will be released until there is at least a 200 to 300 ppm increase above ambient indoor levels. Computers with CO2 sensors and temperature/pressure sensors attached will be used to record data from different locations within the home which will continuously record data up to a week. The results from these periodic ventilation measurements will be analyzed with respect to outdoor wind and temperature conditions and house structure properties. The data will be used to evaluate an established indoor air quality model.

  1. Thermal comfort in naturally ventilated and air-conditioned buildings in humid subtropical climate zone in China

    NASA Astrophysics Data System (ADS)

    Yang, Wei; Zhang, Guoqiang

    2008-05-01

    A thermal comfort field study has been carried out in five cities in the humid subtropical climate zone in China. The survey was performed in naturally ventilated and air-conditioned buildings during the summer season in 2006. There were 229 occupants from 111 buildings who participated in this study and 229 questionnaire responses were collected. Thermal acceptability assessment reveals that the indoor environment in naturally ventilated buildings could not meet the 80% acceptability criteria prescribed by ASHRAE Standard 55, and people tended to feel more comfortable in air-conditioned buildings with the air-conditioned occupants voting with higher acceptability (89%) than the naturally ventilated occupants (58%). The neutral temperatures in naturally ventilated and air-conditioned buildings were 28.3°C and 27.7°C, respectively. The range of accepted temperature in naturally ventilated buildings (25.0˜31.6°C) was wider than that in air-conditioned buildings (25.1˜30.3°C), which suggests that occupants in naturally ventilated buildings seemed to be more tolerant of higher temperatures. Preferred temperatures were 27.9°C and 27.3°C in naturally ventilated and air-conditioned buildings, respectively, both of which were 0.4°C cooler than neutral temperatures. This result suggests that people of hot climates may use words like “slightly cool” to describe their preferred thermal state. The relationship between draught sensation and indoor air velocity at different temperature ranges indicates that indoor air velocity had a significant influence over the occupants’ comfort sensation, and air velocities required by occupants increased with the increasing of operative temperatures. Thus, an effective way of natural ventilation which can create the preferred higher air movement is called for. Finally, the indoor set-point temperature of 26°C or even higher in air-conditioned buildings was confirmed as making people comfortable, which supports the regulation

  2. Safety in the Chemical Laboratory: Laboratory Air Quality: Part II. Measurements of Ventilation Rates.

    ERIC Educational Resources Information Center

    Butcher, Samuel S.; And Others

    1985-01-01

    Part I of this paper (SE 538 295) described a simple model for estimating laboratory concentrations of gas phase pollutants. In this part, the measurement of ventilation rates and applications of the model are discussed. The model can provide a useful starting point in planning for safer instructional laboratories. (JN)

  3. The effect of natural ventilation strategy on indoor air quality in schools.

    PubMed

    Stabile, Luca; Dell'Isola, Marco; Russi, Aldo; Massimo, Angelamaria; Buonanno, Giorgio

    2017-10-01

    In order to reduce children's exposure to pollutants in classrooms a proper ventilation strategy need to be adopted. Such strategy is even more important in naturally ventilated schools where the air exchange rate is only based on the manual airing of classrooms. The present work aimed to evaluate the effect of the manual airing strategy on indoor air quality in Italian classrooms. For this aim, schools located in the Central Italy were investigated. Indoor air quality was studied in terms of CO 2 , particle number and PM concentrations and compared to corresponding outdoor levels. In particular two experimental analyses were performed: i) a comparison between heating and non heating season in different schools; ii) an evaluation of the effect of scheduled airing periods on the dilution of indoor-generated pollutants and the penetration of outdoor-generated ones. In particular, different airing procedures, i.e. different window opening periods (5 to 20min per hour) were imposed and controlled through contacts installed on classroom windows and doors. Results revealed that the airing strategy differently affect the several pollutants detected in indoors depending on their size, origin and dynamics. Longer airing periods may result in reduced indoor CO 2 concentrations and, similarly, other gaseous indoor-generated pollutants. Simultaneously, higher ultrafine particle (and other vehicular-related pollutants) levels in indoors were measured due to infiltration from outdoors. Finally, a negligible effect of the manual airing on PM levels in classroom was detected. Therefore, a simultaneous reduction in concentration levels for all the pollutant metrics in classrooms cannot be obtained just relying upon air permeability of the building envelope and manual airing of the classrooms. Copyright © 2017 Elsevier B.V. All rights reserved.

  4. Control of airborne infectious diseases in ventilated spaces

    PubMed Central

    Nielsen, Peter V.

    2009-01-01

    We protect ourselves from airborne cross-infection in the indoor environment by supplying fresh air to a room by natural or mechanical ventilation. The air is distributed in the room according to different principles: mixing ventilation, displacement ventilation, etc. A large amount of air is supplied to the room to ensure a dilution of airborne infection. Analyses of the flow in the room show that there are a number of parameters that play an important role in minimizing airborne cross-infection. The air flow rate to the room must be high, and the air distribution pattern can be designed to have high ventilation effectiveness. Furthermore, personalized ventilation may reduce the risk of cross-infection, and in some cases, it can also reduce the source of infection. Personalized ventilation can especially be used in hospital wards, aircraft cabins and, in general, where people are in fixed positions. PMID:19740921

  5. Applied patent RFID systems for building reacting HEPA air ventilation system in hospital operation rooms.

    PubMed

    Lin, Jesun; Pai, Jar-Yuan; Chen, Chih-Cheng

    2012-12-01

    RFID technology, an automatic identification and data capture technology to provide identification, tracing, security and so on, was widely applied to healthcare industry in these years. Employing HEPA ventilation system in hospital is a way to ensure healthful indoor air quality to protect patients and healthcare workers against hospital-acquired infections. However, the system consumes lots of electricity which cost a lot. This study aims to apply the RFID technology to offer a unique medical staff and patient identification, and reacting HEPA air ventilation system in order to reduce the cost, save energy and prevent the prevalence of hospital-acquired infection. The system, reacting HEPA air ventilation system, contains RFID tags (for medical staffs and patients), sensor, and reacting system which receives the information regarding the number of medical staff and the status of the surgery, and controls the air volume of the HEPA air ventilation system accordingly. A pilot program was carried out in a unit of operation rooms of a medical center with 1,500 beds located in central Taiwan from Jan to Aug 2010. The results found the air ventilation system was able to function much more efficiently with less energy consumed. Furthermore, the indoor air quality could still keep qualified and hospital-acquired infection or other occupational diseases could be prevented.

  6. A preliminary study on the association between ventilation rates in classrooms and student performance.

    PubMed

    Shaughnessy, R J; Haverinen-Shaughnessy, U; Nevalainen, A; Moschandreas, D

    2006-12-01

    Poor conditions leading to substandard indoor air quality (IAQ) in classrooms have been frequently cited in the literature over the past two decades. However, there is limited data linking poor IAQ in the classrooms to student performance. Whereas, it is assumed that poor IAQ results in reduced attendance and learning potential, and subsequent poor student performance, validating this hypothesis presents a challenge in today's school environment. This study explores the association between student performance on standardized aptitude tests that are administered to students on a yearly basis, to classroom carbon dioxide (CO2) concentrations, which provide a surrogate of ventilation being provided to each room. Data on classroom CO2 concentrations (over a 4-5 h time span within a typical school day) were recorded in fifth grade classrooms in 54 elementary schools within a school district in the USA. Results from this preliminary study yield a significant (P < 0.10) association between classroom-level ventilation rate and test results in math. They also indicate that non-linear effects may need to be considered for better representation of the association. A larger sample size is required in order to draw more definitive conclusions. Practical Implications Future studies could focus on (1) gathering more evidence on the possible association between classroom ventilation rates and students' academic performance; (2) the linear/non-linear nature of the association; and (3) whether it is possible to detect 'no observed adverse effect level' for adequate ventilation with respect to academic performance in schools. All of this information could be used to improve guidance and take regulatory actions to ensure adequate ventilation in schools. The high prevalence of low ventilation rates, combined with the growing evidence of the positive impact that sufficient ventilation has on human performance, suggests an opportunity for improving design and management of school

  7. Field study of air change and flow rate in six automobiles.

    PubMed

    Knibbs, L D; de Dear, R J; Atkinson, S E

    2009-08-01

    For many people, a relatively large proportion of daily exposure to a multitude of pollutants may occur inside an automobile. A key determinant of exposure is the amount of outdoor air entering the cabin (i.e. air change or flow rate). We have quantified this parameter in six passenger vehicles ranging in age from 18 years to <1 year, at three vehicle speeds and under four different ventilation settings. Average infiltration into the cabin with all operable air entry pathways closed was between 1 and 33.1 air changes per hour (ACH) at a vehicle speed of 60 km/h, and between 2.6 and 47.3 ACH at 110 km/h, with these results representing the most (2005 Volkswagen Golf) and least air-tight (1989 Mazda 121) vehicles, respectively. Average infiltration into stationary vehicles parked outdoors varied between approximately 0 and 1.4 ACH and was moderately related to wind speed. Measurements were also performed under an air recirculation setting with low fan speed, while airflow rate measurements were conducted under two non-recirculate ventilation settings with low and high fan speeds. The windows were closed in all cases, and over 200 measurements were performed. The results can be applied to estimate pollutant exposure inside vehicles. There is increasing recognition of the often disproportionately large contribution of in-vehicle pollutant exposures to overall measures. This has highlighted the need for accurate and representative quantification of determinant factors to facilitate exposure estimation and mitigation. The ventilation rate in a vehicle cabin is a key parameter affecting the transfer of pollutants from outdoors to the cabin interior, and vice-versa. New data regarding this variable are presented here, and the results indicate substantial variability in outdoor air infiltration into vehicles of differing age. The efficacy of simple measures to reduce outdoor air infiltration into 'leaky' vehicles to increase occupant protection would be a worthwhile avenue

  8. Feasibility of the capnogram to monitor ventilation rate during cardiopulmonary resuscitation.

    PubMed

    Aramendi, Elisabete; Elola, Andoni; Alonso, Erik; Irusta, Unai; Daya, Mohamud; Russell, James K; Hubner, Pia; Sterz, Fritz

    2017-01-01

    The rates of chest compressions (CCs) and ventilations are both important metrics to monitor the quality of cardiopulmonary resuscitation (CPR). Capnography permits monitoring ventilation, but the CCs provided during CPR corrupt the capnogram and compromise the accuracy of automatic ventilation detectors. The aim of this study was to evaluate the feasibility of an automatic algorithm based on the capnogram to detect ventilations and provide feedback on ventilation rate during CPR, specifically addressing intervals where CCs are delivered. The dataset used to develop and test the algorithm contained in-hospital and out-of-hospital cardiac arrest episodes. The method relies on adaptive thresholding to detect ventilations in the first derivative of the capnogram. The performance of the detector was reported in terms of sensitivity (SE) and Positive Predictive Value (PPV). The overall performance was reported in terms of the rate error and errors in the hyperventilation alarms. Results were given separately for the intervals with CCs. A total of 83 episodes were considered, resulting in 4880min and 46,740 ventilations (8741 during CCs). The method showed an overall SE/PPV above 99% and 97% respectively, even in intervals with CCs. The error for the ventilation rate was below 1.8min -1 in any group, and >99% of the ventilation alarms were correctly detected. A method to provide accurate feedback on ventilation rate using only the capnogram is proposed. Its accuracy was proven even in intervals where canpography signal was severely corrupted by CCs. This algorithm could be integrated into monitor/defibrillators to provide reliable feedback on ventilation rate during CPR. Copyright © 2016 Elsevier Ireland Ltd. All rights reserved.

  9. Pretest Predictions for Ventilation Tests

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Y. Sun; H. Yang; H.N. Kalia

    The objective of this calculation is to predict the temperatures of the ventilating air, waste package surface, concrete pipe walls, and insulation that will be developed during the ventilation tests involving various test conditions. The results will be used as input to the following three areas: (1) Decisions regarding testing set-up and performance. (2) Assessing how best to scale the test phenomena measured. (3) Validating numerical approach for modeling continuous ventilation. The scope of the calculation is to identify the physical mechanisms and parameters related to thermal response in the ventilation tests, and develop and describe numerical methods that canmore » be used to calculate the effects of continuous ventilation. Sensitivity studies to assess the impact of variation of linear power densities (linear heat loads) and ventilation air flow rates are included. The calculation is limited to thermal effect only.« less

  10. Comparison of ventilator-associated pneumonia (VAP) rates between different ICUs: Implications of a zero VAP rate.

    PubMed

    Sundar, Krishna M; Nielsen, David; Sperry, Paul

    2012-02-01

    Ventilator-associated pneumonia (VAP) is associated with significant morbidity and mortality. Measures to reduce the incidence of VAP have resulted in institutions reporting a zero or near-zero VAP rates. The implications of zero VAP rates are unclear. This study was done to compare outcomes between two intensive care units (ICU) with one of them reporting a zero VAP rate. This study retrospectively compared VAP rates between two ICUs: Utah Valley Regional Medical Center (UVRMC) with 25 ICU beds and American Fork Hospital (AFH) with 9 ICU beds. Both facilities are under the same management and attended by a single group of intensivists. Both ICUs have similar nursing and respiratory staffing patterns. Both ICUs use the same intensive care program for reduction of VAP rates. ICU outcomes between AFH (reporting zero VAP rate) and UVRMC (VAP rate of 2.41/1000 ventilator days) were compared for the years 2007-2008. UVRMC VAP rates during 2007 and 2008 were 2.31/1000 ventilator days and 2.5/1000 ventilator days respectively compared to a zero VAP rate at AFH. The total days of ventilation, mean days of ventilation per patient and mean duration of ICU stay per patient was higher in the UVRMC group as compared to AFH ICU group. There was no significant difference in mean age and APACHE II score between ICU patients at UVRMC and AFH. There was no statistical difference in rates of VAP and mortality between UVRMC and AFH. During comparisons of VAP rate between institutions, a zero VAP rate needs to be considered in the context of overall ventilator days, mean durations of ventilator stay and ICU mortality. Copyright © 2012 Elsevier Inc. All rights reserved.

  11. Review and Extension of CO2-Based Methods to Determine Ventilation Rates with Application to School Classrooms

    PubMed Central

    Batterman, Stuart

    2017-01-01

    The ventilation rate (VR) is a key parameter affecting indoor environmental quality (IEQ) and the energy consumption of buildings. This paper reviews the use of CO2 as a “natural” tracer gas for estimating VRs, focusing on applications in school classrooms. It provides details and guidance for the steady-state, build-up, decay and transient mass balance methods. An extension to the build-up method and an analysis of the post-exercise recovery period that can increase CO2 generation rates are presented. Measurements in four mechanically-ventilated school buildings demonstrate the methods and highlight issues affecting their applicability. VRs during the school day fell below recommended minimum levels, and VRs during evening and early morning were on the order of 0.1 h−1, reflecting shutdown of the ventilation systems. The transient mass balance method was the most flexible and advantageous method given the low air change rates and dynamic occupancy patterns observed in the classrooms. While the extension to the build-up method improved stability and consistency, the accuracy of this and the steady-state method may be limited. Decay-based methods did not reflect the VR during the school day due to heating, ventilation and air conditioning (HVAC) system shutdown. Since the number of occupants in classrooms changes over the day, the VR expressed on a per person basis (e.g., L·s−1·person−1) depends on the occupancy metric. If occupancy measurements can be obtained, then the transient mass balance method likely will provide the most consistent and accurate results among the CO2-based methods. Improved VR measurements can benefit many applications, including research examining the linkage between ventilation and health. PMID:28165398

  12. Inadequate ventilation for nosocomial tuberculosis prevention in public hospitals in Central Thailand.

    PubMed

    Jiamjarasrangsi, W; Bualert, S; Chongthaleong, A; Chaindamporn, A; Udomsantisuk, N; Euasamarnjit, W

    2009-04-01

    Forty-two community and general hospitals in central Thailand. To examine the adequacy of indoor ventilation for nosocomial tuberculosis (TB) prevention in public hospitals in central Thailand. A cross-sectional survey was conducted among 323 patient care and ancillary areas in the target hospitals. Data on indoor ventilation rate were collected by the tracer gas method and reported as air changes per hour (ACH). The adequacy of the measured ventilation rates were then determined by comparison with the international recommended standard values. Indoor ventilation rates were inadequate in almost half of the studied areas (144/323, 44.6%). The inadequacy was particularly serious in the emergency rooms (ERs) and radiological areas, where 73.8% (31/42 each) of the rooms had ACH below the recommended standards. Detailed analysis showed that most of the rooms with natural ventilation had air exchange rates that exceeded the recommended standards, while the opposite was the case for rooms with air-conditioning, particularly the window or wall-mount type. Indoor ventilation in high-risk nosocomial TB areas in public hospitals in Thailand was inadequate due to the installation of air-conditioning systems in modern buildings.

  13. Experiments to Evaluate and Implement Passive Tracer Gas Methods to Measure Ventilation Rates in Homes

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Lunden, Melissa; Faulkner, David; Heredia, Elizabeth

    2012-10-01

    This report documents experiments performed in three homes to assess the methodology used to determine air exchange rates using passive tracer techniques. The experiments used four different tracer gases emitted simultaneously but implemented with different spatial coverage in the home. Two different tracer gas sampling methods were used. The results characterize the factors of the execution and analysis of the passive tracer technique that affect the uncertainty in the calculated air exchange rates. These factors include uncertainties in tracer gas emission rates, differences in measured concentrations for different tracer gases, temporal and spatial variability of the concentrations, the comparison betweenmore » different gas sampling methods, and the effect of different ventilation conditions.« less

  14. Sustained Reduction of Ventilator-Associated Pneumonia Rates Using Real-Time Course Correction With a Ventilator Bundle Compliance Dashboard.

    PubMed

    Talbot, Thomas R; Carr, Devin; Parmley, C Lee; Martin, Barbara J; Gray, Barbara; Ambrose, Anna; Starmer, Jack

    2015-11-01

    The effectiveness of practice bundles on reducing ventilator-associated pneumonia (VAP) has been questioned. To implement a comprehensive program that included a real-time bundle compliance dashboard to improve compliance and reduce ventilator-associated complications. DESIGN Before-and-after quasi-experimental study with interrupted time-series analysis. SETTING Academic medical center. In 2007 a comprehensive institutional ventilator bundle program was developed. To assess bundle compliance and stimulate instant course correction of noncompliant parameters, a real-time computerized dashboard was developed. Program impact in 6 adult intensive care units (ICUs) was assessed. Bundle compliance was noted as an overall cumulative bundle adherence assessment, reflecting the percentage of time all elements were concurrently in compliance for all patients. The VAP rate in all ICUs combined decreased from 19.5 to 9.2 VAPs per 1,000 ventilator-days following program implementation (P<.001). Bundle compliance significantly increased (Z100 score of 23% in August 2007 to 83% in June 2011 [P<.001]). The implementation resulted in a significant monthly decrease in the overall ICU VAP rate of 3.28/1,000 ventilator-days (95% CI, 2.64-3.92/1,000 ventilator-days). Following the intervention, the VAP rate decreased significantly at a rate of 0.20/1,000 ventilator-days per month (95% CI, 0.14-0.30/1,000 ventilator-days per month). Among all adult ICUs combined, improved bundle compliance was moderately correlated with monthly VAP rate reductions (Pearson correlation coefficient, -0.32). A prevention program using a real-time bundle adherence dashboard was associated with significant sustained decreases in VAP rates and an increase in bundle compliance among adult ICU patients.

  15. The IVAIRE project--a randomized controlled study of the impact of ventilation on indoor air quality and the respiratory symptoms of asthmatic children in single family homes.

    PubMed

    Lajoie, P; Aubin, D; Gingras, V; Daigneault, P; Ducharme, F; Gauvin, D; Fugler, D; Leclerc, J-M; Won, D; Courteau, M; Gingras, S; Héroux, M-È; Yang, W; Schleibinger, H

    2015-12-01

    A randomized controlled trial was carried out to measure the impact of an intervention on ventilation, indoor air contaminants, and asthma symptoms of children. Eighty-three asthmatic children living in low-ventilated homes were followed over 2 years. Several environmental parameters were measured during the summer, fall, and winter. The children were randomized after Year 1 (43 Intervention; 40 Control). The intervention included the installation of either a Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV). During the fall and winter seasons, there was a significant increase in the mean ventilation rate in the homes of the intervention group. A statistically significant reduction in mean formaldehyde, airborne mold spores, toluene, styrene, limonene, and α-pinene concentrations was observed in the intervention group. There was no significant group difference in change in the number of days with symptoms per 14 days. However, there was a significant decrease in the proportion of children who experienced any wheezing (≥1 episode) and those with ≥4 episodes in the 12-month period in the intervention group. This study indicates that improved ventilation reduces air contaminants and may prevent wheezing. Due to lack of power, a bigger study is needed. Positive findings from this study include the fact that, upon recruitment, most of the single family homes with asthmatic children were already equipped with a mechanical ventilation system and had relatively good indoor air quality. However, the 8-h indoor guideline for formaldehyde (50 μg/m3) was frequently exceeded and the ventilation rates were low in most of the homes, even those with a ventilation system. Both ERVs and HRVs were equally effective at increasing air exchange rates above 0.30 ACH and at preventing formaldehyde concentrations from exceeding the 50 μg/m3 guideline during the fall and winter seasons. Furthermore, the ERVs were effective at preventing excessively low relative

  16. Characteristics of rain penetration through a gravity ventilator used for natural ventilation.

    PubMed

    Kim, Taehyeung; Lee, Dong Ho; Ahn, Kwangseog; Ha, Hyunchul; Park, Heechang; Piao, Cheng Xu; Li, Xiaoyu; Seo, Jeoungyoon

    2008-01-01

    Gravity ventilators rely simply on air buoyancy to extract air and are widely used to exhaust air contaminants and heat from workplaces using minimal energy. They are designed to maximize the exhaust flow rate, but the rain penetration sometimes causes malfunctioning. In this study, the characteristics of rain penetration through a ventilator were examined as a preliminary study to develop a ventilator with the maximum exhaust capacity while minimizing rain penetration. A model ventilator was built and exposed to artificial rain and wind. The paths, intensities and amounts of penetration through the ventilator were observed and measured in qualitative and quantitative fashions. In the first phase, the pathways and intensities of rain penetration were visually observed. In the second phase, the amounts of rain penetration were quantitatively measured under the different configurations of ventilator components that were installed based on the information obtained in the first-phase experiment. The effects of wind speed, grill direction, rain drainage width, outer wall height, neck height and leaning angle of the outer wall from the vertical position were analyzed. Wind speed significantly affected rain penetration. Under the low crosswind conditions, the rain penetration intensities were under the limit of detection. Under the high crosswind conditions, grill direction and neck height were the most significant factors in reducing rain penetration. The installation of rain drainage was also important in reducing rain penetration. The experimental results suggest that, with proper configurations of its components, a gravity ventilator can be used for natural ventilation without significant rain penetration problems.

  17. Ventilation and infiltration in high-rise apartment buildings

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Diamond, R.C.; Feustel, H.E.; Dickerhoff, D.J.

    1996-03-01

    Air flow, air leakage measurements and numerical simulations were made on a 13-story apartment building to characterize the ventilation rates for the individual apartments. Parametric simulations were performed for specific conditions, e.g., height, orientation, outside temperature and wind speed. Our analysis of the air flow simulations suggest that the ventilation to the individual units varies considerably. With the mechanical ventilation system disabled and no wind, units at the lower level of the building have adequate ventilation only on days with high temperature differences, while units on higher floors have no ventilation at all. Units facing the windward side will bemore » over-ventilated when the building experiences wind directions between west and north. At the same time, leeward apartments did not experience any fresh air-because, in these cases, air flows enter the apartments from the corridor and exit through the exhaust shafts and the cracks in the facade. Even with the mechanical ventilation system operating, we found wide variation in the air flows to the individual apartments. In addition to the specific case presented here, these findings have more general implications for energy retrofits and health and comfort of occupants in high-rise apartment buildings.« less

  18. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... CARGOES SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS Design and Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1...

  19. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... CARGOES SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS Design and Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1...

  20. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... CARGOES SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS Design and Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1...

  1. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... CARGOES SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS Design and Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1...

  2. 46 CFR 153.316 - Special cargo pumproom ventilation rate.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... CARGOES SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS Design and Equipment Cargo Handling Space Ventilation § 153.316 Special cargo pumproom ventilation rate. When Table 1...

  3. Evaluation of thermal formation and air ventilation inside footwear during gait: The role of gait and fitting.

    PubMed

    Shimazaki, Yasuhiro; Matsutani, Toshiki; Satsumoto, Yayoi

    2016-07-01

    Comfort is an important concept in footwear design. The microclimate inside footwear contributes to the perception of thermal comfort. To investigate the effect of ventilation on microclimate formation inside footwear, experiments with subjects were conducted at four gait speeds with three different footwear sizes. Skin temperature, metabolism, and body mass were measured at approximately 25 °C and 50% relative humidity, with no solar radiation and a calm wind. The footwear occupancy and ventilation rate were also estimated, with the latter determined using the tracer gas method. The experimental results revealed that foot movement, metabolism, evaporation, radiation, convection, and ventilation were the main factors influencing the energy balance for temperature formation on the surface of the foot. The cooling effect of ventilation on the arch temperature was observed during gait. The significance of the amount of air space and ventilation on the improvement in the thermal comfort of footwear was clarified. Copyright © 2015 Elsevier Ltd and The Ergonomics Society. All rights reserved.

  4. The ventilation problem in schools: literature review

    DOE PAGES

    Fisk, W. J.

    2017-07-06

    Based on a review of literature published in refereed archival journals, ventilation rates in classrooms often fall far short of the minimum ventilation rates specified in standards. We report that there is compelling evidence, from both cross-sectional and intervention studies, of an association of increased student performance with increased ventilation rates. There is evidence that reduced respiratory health effects and reduced student absence are associated with increased ventilation rates. Increasing ventilation rates in schools imposes energy costs and can increase heating, ventilating, and air-conditioning system capital costs. The net annual costs, ranging from a few dollars to about 10 dollarsmore » per person, are less than 0.1% of typical public spending on elementary and secondary education in the United States. Finally, such expenditures seem like a small price to pay given the evidence of health and performance benefits.« less

  5. The ventilation problem in schools: literature review

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Fisk, W. J.

    Based on a review of literature published in refereed archival journals, ventilation rates in classrooms often fall far short of the minimum ventilation rates specified in standards. We report that there is compelling evidence, from both cross-sectional and intervention studies, of an association of increased student performance with increased ventilation rates. There is evidence that reduced respiratory health effects and reduced student absence are associated with increased ventilation rates. Increasing ventilation rates in schools imposes energy costs and can increase heating, ventilating, and air-conditioning system capital costs. The net annual costs, ranging from a few dollars to about 10 dollarsmore » per person, are less than 0.1% of typical public spending on elementary and secondary education in the United States. Finally, such expenditures seem like a small price to pay given the evidence of health and performance benefits.« less

  6. Heating, Ventilating, and Air Conditioning. Energy Technology Series.

    ERIC Educational Resources Information Center

    Center for Occupational Research and Development, Inc., Waco, TX.

    This course in heating, ventilating, and air conditioning is one of 16 courses in the Energy Technology Series developed for an Energy Conservation-and-Use Technology curriculum. Intended for use in two-year postsecondary technical institutions to prepare technicians for employment, the courses are also useful in industry for updating employees in…

  7. Building Component Maintenance and Repair Data Base: Heating, Ventilating, and Air Conditioning (HVAC) Systems

    DTIC Science & Technology

    1991-05-01

    Building Component Maintenance and Repair Data Base: Heating, Ventilating, and Air Conditioning (HVAC) Systems by Edgar S. Neely Robert D. Neathammer...Repair Data Base: Heating, Ventilating, and Air Conditioning (HVAC) Systems RDTE dated 1980EIMB 1984 - 1989 6. AUTHOR(S) Edgar S. Neely, Robert D...Laboratory (USACERL). The Principal Investigators were Dr. Edgar Neely and Mr. Robert Neathammer (USACERL-FS). The primary contractor for much of the

  8. Control of gill ventilation and air-breathing in the bowfin amia calva

    PubMed

    Hedrick; Jones

    1999-01-01

    The purpose of this study was to investigate the roles of branchial and gas bladder reflex pathways in the control of gill ventilation and air-breathing in the bowfin Amia calva. We have previously determined that bowfin use two distinct air-breathing mechanisms to ventilate the gas bladder: type I air breaths are characterized by exhalation followed by inhalation, are stimulated by aquatic or aerial hypoxia and appear to regulate O2 gas exchange; type II air breaths are characterized by inhalation alone and possibly regulate gas bladder volume and buoyancy. In the present study, we test the hypotheses (1) that gill ventilation and type I air breaths are controlled by O2-sensitive chemoreceptors located in the branchial region, and (2) that type II air breaths are controlled by gas bladder mechanosensitive stretch receptors. Hypothesis 1 was tested by examining the effects of partial or complete branchial denervation of cranial nerves IX and X to the gill arches on gill ventilation frequency (fg) and the proportion of type I air breaths during normoxia and hypoxia; hypothesis II was tested by gas bladder inflation and deflation. Following complete bilateral branchial denervation, fg did not differ from that of sham-operated control fish; in addition, fg was not significantly affected by aquatic hypoxia in sham-operated or denervated fish. In sham-operated fish, aquatic hypoxia significantly increased overall air-breathing frequency (fab) and the percentage of type I breaths. In fish with complete IX-X branchial denervation, fab was also significantly increased during aquatic hypoxia, but there were equal percentages of type I and type II air breaths. Branchial denervation did not affect the frequency of type I air breaths during aquatic hypoxia. Gas bladder deflation via an indwelling catheter resulted in type II breaths almost exclusively; furthermore, fab was significantly correlated with the volume removed from the gas bladder, suggesting a volume

  9. Metabolically Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates (Final Report, 2009)

    EPA Science Inventory

    EPA announced the availability of the final report, Metabolically Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates. This report provides a revised approach for calculating an individual's ventilation rate directly from their oxygen c...

  10. A Chemical-Biological-Radio-Nuclear (CBRN) Filter can be Added to the Air-Outflow Port of a Ventilator to Protect a Home Ventilated Patient From Inhalation of Toxic Industrial Compounds.

    PubMed

    Be'eri, Eliezer; Owen, Simon; Beeri, Maurit; Millis, Scott R; Eisenkraft, Arik

    2018-02-21

    Chemical-biological-radio-nuclear (CBRN) gas masks are the standard means for protecting the general population from inhalation of toxic industrial compounds (TICs), for example after industrial accidents or terrorist attacks. However, such gas masks would not protect patients on home mechanical ventilation, as ventilator airflow would bypass the CBRN filter. We therefore evaluated in vivo the safety of adding a standard-issue CBRN filter to the air-outflow port of a home ventilator, as a method for providing TIC protection to such patients. Eight adult patients were included in the study. All had been on stable, chronic ventilation via a tracheostomy for at least 3 months before the study. Each patient was ventilated for a period of 1 hour with a standard-issue CBRN filter canister attached to the air-outflow port of their ventilator. Physiological and airflow measurements were made before, during, and after using the filter, and the patients reported their subjective sensation of ventilation continuously during the trial. For all patients, and throughout the entire study, no deterioration in any of the measured physiological parameters and no changes in measured airflow parameters were detected. All patients felt no subjective difference in the sensation of ventilation with the CBRN filter canister in situ, as compared with ventilation without it. This was true even for those patients who were breathing spontaneously and thus activating the ventilator's trigger/sensitivity function. No technical malfunctions of the ventilators occurred after addition of the CBRN filter canister to the air-outflow ports of the ventilators. A CBRN filter canister can be added to the air-outflow port of chronically ventilated patients, without causing an objective or subjective deterioration in the quality of the patients' mechanical ventilation. (Disaster Med Public Health Preparedness. 2018;page 1 of 5).

  11. Innovative ventilation system for animal anatomy laboratory

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Lacey, D.R.; Smith, D.C.

    1997-04-01

    A unique ventilation system was designed and built to reduce formaldehyde fumes in the large animal anatomy lab at the Vet Medical Center at Cornell University. The laboratory includes four rooms totaling 5,500 ft{sup 2}. The main room has 2,300 ft{sup 2} and houses the laboratory where up to 60 students dissect as many as 12 horses at a time. Other rooms are a cold storage locker, an animal preparation room and a smaller lab for specialized instruction. The large animal anatomy laboratory has a history of air quality complaints despite a fairly high ventilation rate of over 10 airmore » changes/hour. The horses are embalmed, creating a voluminous source of formaldehyde and phenol vapors. Budget constraints and increasingly stringent exposure limits for formaldehyde presented a great challenge to design a ventilation system that yields acceptable air quality. The design solution included two innovative elements: air-to-air heat recovery, and focused ventilation.« less

  12. Effect of central ventilation and air conditioner system on the concentration and health risk from airborne polycyclic aromatic hydrocarbons.

    PubMed

    Lv, Jinze; Zhu, Lizhong

    2013-03-01

    Central ventilation and air conditioner systems are widely utilized nowadays in public places for air exchange and temperature control, which significantly influences the transfer of pollutants between indoors and outdoors. To study the effect of central ventilation and air conditioner systems on the concentration and health risk from airborne pollutants, a spatial and temporal survey was carried out using polycyclic aromatic hydrocarbons (PAHs) as agent pollutants. During the period when the central ventilation system operated without air conditioning (AC-off period), concentrations of 2-4 ring PAHs in the model supermarket were dominated by outdoor levels, due to the good linearity between indoor air and outdoor air (r(p) > 0.769, p < 0.05), and the slopes (1.2-4.54) indicated that ventilating like the model supermarket increased the potential health risks from low molecular weight PAHs. During the period when the central ventilation and air conditioner systems were working simultaneously (AC-on period), although the total levels of PAHs were increased, the concentrations and percentage of the particulate PAHs indoors declined significantly. The BaP equivalency (BaPeq) concentration indicated that utilization of air conditioning reduced the health risks from PAHs in the model supermarket.

  13. 4. VENTILATION FAN SHOWING RELATIVE POSITION IN THE AIR TUNNEL. ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    4. VENTILATION FAN SHOWING RELATIVE POSITION IN THE AIR TUNNEL. - Hot Springs National Park, Bathhouse Row, Ozark Bathhouse: Mechanical & Piping Systems, State Highway 7, 1 mile north of U.S. Highway 70, Hot Springs, Garland County, AR

  14. Effect of frequency of ventilator circuit changes (3 vs 7 days) on the rate of ventilator-associated pneumonia in PICU.

    PubMed

    Samransamruajkit, Rujipat; Jirapaiboonsuk, Suree; Siritantiwat, Sirirush; Tungsrijitdee, Ornanong; Deerojanawong, Jitladda; Sritippayawan, Suchada; Prapphal, Nuanchan

    2010-03-01

    Ventilator-associated pneumonia (VAP) is associated with significant morbidity and mortality in pediatric intensive care unit (PICU). Our purpose was to evaluate the effects of ventilator circuit change on the rate of VAP in the PICU. A prospective randomized controlled trial was conducted at a university hospital PICU. Children (younger than 18 years) who received mechanical ventilation from December 2006 to November 2007 were randomly assigned to receive ventilator circuit changes every 3 or 7 days. Of 176 patients, 88 were assigned to receive ventilator circuit every 3 days and 88 patients had a change weekly. The rate of VAP was 13.9/1000 ventilator days for the 3-day circuit change (n = 12) vs 11.5/1000 ventilator days (n = 10) for the 7-day circuit change (odds ratio, 0.8; confidence interval, 0.3-1.9; P = .6). There was a trend toward decreased PICU stay and mortality rate in 7-day change group compared to 3-day change group but did not reach statistical significance. Furthermore, switching from a 3-day to a 7-day change policy could save costs up to US $22,000/y. The 7-day ventilator circuit change did not contribute to increased rates of VAP in our PICU. Thus, it may be used as a guide to save workload and supply costs. Crown Copyright 2010. Published by Elsevier Inc. All rights reserved.

  15. A polyurethane cuffed endotracheal tube is associated with decreased rates of ventilator-associated pneumonia.

    PubMed

    Miller, Melissa A; Arndt, Jennifer L; Konkle, Mark A; Chenoweth, Carol E; Iwashyna, Theodore J; Flaherty, Kevin R; Hyzy, Robert C

    2011-06-01

    The aim of this study was to determine whether the use of a polyurethane-cuffed endotracheal tube would result in a decrease in ventilator-associated pneumonia rate. We replaced conventional endotracheal tube with a polyurethane-cuff endotracheal tube (Microcuff, Kimberly-Clark Corporation, Rosewell, Ga) in all adult mechanically ventilated patients throughout our large academic hospital from July 2007 to June 2008. We retrospectively compared the rates of ventilator-associated pneumonia before, during, and after the intervention year by interrupted time-series analysis. Ventilator-associated pneumonia rates decreased from 5.3 per 1000 ventilator days before the use of the polyurethane-cuffed endotracheal tube to 2.8 per 1000 ventilator days during the intervention year (P = .0138). During the first 3 months after return to conventional tubes, the rate of ventilator-associated pneumonia was 3.5/1000 ventilator days. Use of the polyurethane-cuffed endotracheal tube was associated with an incidence risk ratio of ventilator-associated pneumonia of 0.572 (95% confidence interval, 0.340-0.963). In statistical regression analysis controlling for other possible alterations in the hospital environment, as measured by rate of tracheostomy-ventilator-associated pneumonia, the incidence risk ratio of ventilator-associated pneumonia in patients intubated with polyurethane-cuffed endotracheal tube was 0.565 (P = .032; 95% confidence interval, 0.335-0.953). Use of a polyurethane-cuffed endotracheal tube was associated with a significant decrease in the rate of ventilator-associated pneumonia in our study. Copyright © 2011 Elsevier Inc. All rights reserved.

  16. Ventilation/odor study, field study. Final report, Volume I

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Duffee, R.A.; Jann, P.

    1981-04-01

    The results are presented of field investigations in schools, hospitals, and an office building on the relation between ventilation rate and odor within the buildings. The primary objective of the study was to determine: the reduction in ventilation rates that could be achieved in public buildings without causing adverse effects on odor; the sources of odor in public buildings; and the identity of the odorants. The variables of particular interest include: type of odor, occupant density, odorant identity and concentration, differences in impressions between occupants adapted to prevailing conditions and visitors, and the influence of temperature and humidity on bothmore » the generation and perception of common contaminants. Sensory odor measurements, chemical measurements, fresh air ventilation measurements, and acceptability evaluations via questionnaires were made. Sensory odor levels were found to be quite low in most buildings tested. A three-to-five-fold reduction in the fresh air ventilation in schools, hospitals, and office buildings can be achieved without significantly affecting perceived odor intensities or detectability. Tobacco smoking was found to be the most significant, pervasive contributor to interior odor level. Total hydrocarbon content of indoor air varies directly with ventilation rates; odor, however, does not. The complete set of reduced data are contained in Volume II. (LEW)« less

  17. State Skill Standards: Heating, Ventilation, Air Conditioning, and Refrigeration

    ERIC Educational Resources Information Center

    Ball, Larry; Soukup, Dennis

    2006-01-01

    The Department of Education has undertaken an ambitious effort to develop statewide career and technical education skill standards. The standards in this document are for Heating, Ventilation, Air Conditioning and Refrigeration (HVAC&R) programs and are designed to clearly state what the student should know and be able to do upon completion of…

  18. Minute ventilation of cyclists, car and bus passengers: an experimental study.

    PubMed

    Zuurbier, Moniek; Hoek, Gerard; van den Hazel, Peter; Brunekreef, Bert

    2009-10-27

    Differences in minute ventilation between cyclists, pedestrians and other commuters influence inhaled doses of air pollution. This study estimates minute ventilation of cyclists, car and bus passengers, as part of a study on health effects of commuters' exposure to air pollutants. Thirty-four participants performed a submaximal test on a bicycle ergometer, during which heart rate and minute ventilation were measured simultaneously at increasing cycling intensity. Individual regression equations were calculated between heart rate and the natural log of minute ventilation. Heart rates were recorded during 280 two hour trips by bicycle, bus and car and were calculated into minute ventilation levels using the individual regression coefficients. Minute ventilation during bicycle rides were on average 2.1 times higher than in the car (individual range from 1.3 to 5.3) and 2.0 times higher than in the bus (individual range from 1.3 to 5.1). The ratio of minute ventilation of cycling compared to travelling by bus or car was higher in women than in men. Substantial differences in regression equations were found between individuals. The use of individual regression equations instead of average regression equations resulted in substantially better predictions of individual minute ventilations. The comparability of the gender-specific overall regression equations linking heart rate and minute ventilation with one previous American study, supports that for studies on the group level overall equations can be used. For estimating individual doses, the use of individual regression coefficients provides more precise data. Minute ventilation levels of cyclists are on average two times higher than of bus and car passengers, consistent with the ratio found in one small previous study of young adults. The study illustrates the importance of inclusion of minute ventilation data in comparing air pollution doses between different modes of transport.

  19. Air Conditioning, Heating, and Ventilating: Construction, Supervision, and Inspection. Course of Study.

    ERIC Educational Resources Information Center

    Messer, John D.

    This course of study on air conditioning, heating, and ventilating is part of a construction, supervision, and inspection series, which provides instructional materials for community or junior college technical courses in the inspection program. Material covered pertains to: piping and piping systems; air movers; boilers; heat exchangers; cooling…

  20. Heating, Ventilation, Air-conditioning, and Refrigeration. Ohio's Competency Analysis Profile.

    ERIC Educational Resources Information Center

    Ohio State Univ., Columbus. Vocational Instructional Materials Lab.

    Developed through a modified DACUM (Developing a Curriculum) process involving business, industry, labor, and community agency representatives in Ohio, this document is a comprehensive and verified employer competency profile for heating, ventilation, air conditioning, and refrigeration occupations. The list contains units (with and without…

  1. FRACTIONAL AEROSOL FILTRATION EFFICIENCY OF IN-DUCT VENTILATION AIR CLEANERS

    EPA Science Inventory

    The filtration efficiency of ventilation air cleaners is highly particle-size dependent over the 0.01 to 3 μm diameter size range. Current standardized test methods, which determine only overall efficiencies for ambient aerosol or other test aerosols, provide data of limited util...

  2. An easy tool to assess ventilation in health facilities as part of air-borne transmission prevention: a cross-sectional survey from Uganda.

    PubMed

    Brouwer, Miranda; Katamba, Achilles; Katabira, Elly Tebasoboke; van Leth, Frank

    2017-05-03

    No guidelines exist on assessing ventilation through air changes per hour (ACH) using a vaneometer. The objective of the study was to evaluate the position and frequency for measuring air velocity using a vaneometer to assess ventilation with ACH; and to assess influence of ambient temperature and weather on ACH. Cross-sectional survey in six urban health facilities in Kampala, Uganda. Measurements consisted of taking air velocity on nine separate moments in five positions in each opening of the TB clinic, laboratory, outpatient consultation and outpatient waiting room using a vaneometer. We assessed in addition the ventilation with the "20% rule", and compared this estimation with the ventilation in ACH assessed using the vaneometer. A total of 189 measurements showed no influence on air velocity of the position and moment of the measurement. No significant influence existed of ambient temperature and a small but significant influence of sunny weather. Ventilation was adequate in 17/24 (71%) of all measurements. Using the "20% rule", ventilation was adequate in 50% of rooms assessed. Agreement between both methods existed in 13/23 (56%) of the rooms assessed. Most rooms had adequate ventilation when assessed using a vaneometer for measuring air velocity. A single vaneometer measurement of air velocity is adequate to assess ventilation in this setting. These findings provide practical input for clear guidelines on assessing ventilation using a vaneometer. Assessing ventilation with a vaneometer differs substantially from applying the "20% rule".

  3. Environmental Technology Verification: Supplement to Test/QA Plan for Biological and Aerosol Testing of General Ventilation Air Cleaners; Bioaerosol Inactivation Efficiency by HVAC In-Duct Ultraviolet Light Air Cleaners

    EPA Science Inventory

    The Air Pollution Control Technology Verification Center has selected general ventilation air cleaners as a technology area. The Generic Verification Protocol for Biological and Aerosol Testing of General Ventilation Air Cleaners is on the Environmental Technology Verification we...

  4. The use of a modified technique to reduce radioactive air contamination in aerosol lung ventilation imaging.

    PubMed

    Avison, M; Hart, G

    2001-06-01

    The aim of this study was to reduce airborne contamination resulting from the use of aerosols in lung ventilation scintigraphy. Lung ventilation imaging is frequently performed with 99mTc-diethylenetriaminepentaacetate aerosol (DTPA), derived from a commercial nebuliser. Airborne contamination is a significant problem with this procedure; it results in exposure of staff to radiation and can reduce gamma camera performance when the ventilation is performed in the camera room. We examined the level of airborne contamination resulting from the standard technique with one of the most popular nebuliser kits and tested a modification which significantly reduced airborne contamination. Air contamination was measured while ventilating 122 patients. The modified technique reduced air contamination by a mean value of 64% (p = 0.028) compared with the standard control technique. Additionally, differences in contamination were examined when a mask or mouthpiece was used as well as differences between operators. A simplified method of monitoring air contamination is presented using a commonly available surface contamination monitor. The index so derived was proportional to air contamination (r = 0.88). The problems and regulations associated with airborne contamination are discussed.

  5. Economic, Environmental and Health Implications of Enhanced Ventilation in Office Buildings.

    PubMed

    MacNaughton, Piers; Pegues, James; Satish, Usha; Santanam, Suresh; Spengler, John; Allen, Joseph

    2015-11-18

    Current building ventilation standards are based on acceptable minimums. Three decades of research demonstrates the human health benefits of increased ventilation above these minimums. Recent research also shows the benefits on human decision-making performance in office workers, which translates to increased productivity. However, adoption of enhanced ventilation strategies is lagging. We sought to evaluate two of the perceived potential barriers to more widespread adoption-Economic and environmental costs. We estimated the energy consumption and associated per building occupant costs for office buildings in seven U.S. cities, representing different climate zones for three ventilation scenarios (standard practice (20 cfm/person), 30% enhanced ventilation, and 40 cfm/person) and four different heating, ventilation and air conditioning (HVAC) system strategies (Variable Air Volume (VAV) with reheat and a Fan Coil Unit (FCU), both with and without an energy recovery ventilator). We also estimated emissions of greenhouse gases associated with this increased energy usage, and, for comparison, converted this to the equivalent number of vehicles using greenhouse gas equivalencies. Lastly, we paired results from our previous research on cognitive function and ventilation with labor statistics to estimate the economic benefit of increased productivity associated with increasing ventilation rates. Doubling the ventilation rate from the American Society of Heating, Refrigeration and Air-Conditioning Engineers minimum cost less than $40 per person per year in all climate zones investigated. Using an energy recovery ventilation system significantly reduced energy costs, and in some scenarios led to a net savings. At the highest ventilation rate, adding an ERV essentially neutralized the environmental impact of enhanced ventilation (0.03 additional cars on the road per building across all cities). The same change in ventilation improved the performance of workers by 8

  6. Economic, Environmental and Health Implications of Enhanced Ventilation in Office Buildings

    PubMed Central

    MacNaughton, Piers; Pegues, James; Satish, Usha; Santanam, Suresh; Spengler, John; Allen, Joseph

    2015-01-01

    Introduction: Current building ventilation standards are based on acceptable minimums. Three decades of research demonstrates the human health benefits of increased ventilation above these minimums. Recent research also shows the benefits on human decision-making performance in office workers, which translates to increased productivity. However, adoption of enhanced ventilation strategies is lagging. We sought to evaluate two of the perceived potential barriers to more widespread adoption—Economic and environmental costs. Methods: We estimated the energy consumption and associated per building occupant costs for office buildings in seven U.S. cities, representing different climate zones for three ventilation scenarios (standard practice (20 cfm/person), 30% enhanced ventilation, and 40 cfm/person) and four different heating, ventilation and air conditioning (HVAC) system strategies (Variable Air Volume (VAV) with reheat and a Fan Coil Unit (FCU), both with and without an energy recovery ventilator). We also estimated emissions of greenhouse gases associated with this increased energy usage, and, for comparison, converted this to the equivalent number of vehicles using greenhouse gas equivalencies. Lastly, we paired results from our previous research on cognitive function and ventilation with labor statistics to estimate the economic benefit of increased productivity associated with increasing ventilation rates. Results: Doubling the ventilation rate from the American Society of Heating, Refrigeration and Air-Conditioning Engineers minimum cost less than $40 per person per year in all climate zones investigated. Using an energy recovery ventilation system significantly reduced energy costs, and in some scenarios led to a net savings. At the highest ventilation rate, adding an ERV essentially neutralized the environmental impact of enhanced ventilation (0.03 additional cars on the road per building across all cities). The same change in ventilation improved the

  7. Air quality and ventilation fan control based on aerosol measurement in the bi-directional undersea Bømlafjord tunnel.

    PubMed

    Indrehus, Oddny; Aralt, Tor Tybring

    2005-04-01

    Aerosol, NO and CO concentration, temperature, air humidity, air flow and number of running ventilation fans were measured by continuous analysers every minute for a whole week for six different one-week periods spread over ten months in 2001 and 2002 at measuring stations in the 7860 m long tunnel. The ventilation control system was mainly based on aerosol measurements taken by optical scatter sensors. The ventilation turned out to be satisfactory according to Norwegian air quality standards for road tunnels; however, there was some uncertainty concerning the NO2 levels. The air humidity and temperature inside the tunnel were highly influenced by the outside metrological conditions. Statistical models for NO concentration were developed and tested; correlations between predicted and measured NO were 0.81 for a partial least squares regression (PLS1) model based on CO and aerosol, and 0.77 for a linear regression model based only on aerosol. Hence, the ventilation control system should not solely be based on aerosol measurements. Since NO2 is the hazardous polluter, modelling NO2 concentration rather than NO should be preferred in any further optimising of the ventilation control.

  8. Effects of Classroom Ventilation Rate and Temperature on Students' Test Scores.

    PubMed

    Haverinen-Shaughnessy, Ulla; Shaughnessy, Richard J

    2015-01-01

    Using a multilevel approach, we estimated the effects of classroom ventilation rate and temperature on academic achievement. The analysis is based on measurement data from a 70 elementary school district (140 fifth grade classrooms) from Southwestern United States, and student level data (N = 3109) on socioeconomic variables and standardized test scores. There was a statistically significant association between ventilation rates and mathematics scores, and it was stronger when the six classrooms with high ventilation rates that were indicated as outliers were filtered (> 7.1 l/s per person). The association remained significant when prior year test scores were included in the model, resulting in less unexplained variability. Students' mean mathematics scores (average 2286 points) were increased by up to eleven points (0.5%) per each liter per second per person increase in ventilation rate within the range of 0.9-7.1 l/s per person (estimated effect size 74 points). There was an additional increase of 12-13 points per each 1°C decrease in temperature within the observed range of 20-25°C (estimated effect size 67 points). Effects of similar magnitude but higher variability were observed for reading and science scores. In conclusion, maintaining adequate ventilation and thermal comfort in classrooms could significantly improve academic achievement of students.

  9. Experimental research on the indoor temperature and humidity fields in radiant ceiling air-conditioning system under natural ventilation

    NASA Astrophysics Data System (ADS)

    Huang, Tao; Xiang, Yutong; Wang, Yonghong

    2017-05-01

    In this paper, the indoor temperature and humidity fields of the air in a metal ceiling radiant panel air conditioning system with fresh air under natural ventilation were researched. The temperature and humidity distributions at different height and different position were compared. Through the computation analysis of partial pressure of water vapor, the self-recovery characteristics of humidity after the natural ventilation was discussed.

  10. Ventilation of carbon monoxide from a biomass pellet storage tank--a study of the effects of variation of temperature and cross-ventilation on the efficiency of natural ventilation.

    PubMed

    Emhofer, Waltraud; Lichtenegger, Klaus; Haslinger, Walter; Hofbauer, Hermann; Schmutzer-Roseneder, Irene; Aigenbauer, Stefan; Lienhard, Martin

    2015-01-01

    Wood pellets have been reported to emit toxic gaseous emissions during transport and storage. Carbon monoxide (CO) emission, due to the high toxicity of the gas and the possibility of it being present at high levels, is the most imminent threat to be considered before entering a pellet storage facility. For small-scale (<30 tons storage capacity) residential pellet storage facilities, ventilation, preferably natural ventilation utilizing already existing openings, has become the most favored solution to overcome the problem of high CO concentrations. However, there is little knowledge on the ventilation rates that can be reached and thus on the effectiveness of such measures. The aim of the study was to investigate ventilation rates for a specific small-scale pellet storage system depending on characteristic temperature differences. Furthermore, the influence of the implementation of a chimney and the influence of cross-ventilation on the ventilation rates were investigated. The air exchange rates observed in the experiments ranged between close to zero and up to 8 m(3) h(-1), depending largely on the existing temperature differences and the existence of cross-ventilation. The results demonstrate that implementing natural ventilation is a possible measure to enhance safety from CO emissions, but not one without limitations. © The Author 2014. Published by Oxford University Press on behalf of the British Occupational Hygiene Society.

  11. Occupant Interactions and Effectiveness of Natural Ventilation Strategies in Contemporary New Housing in Scotland, UK.

    PubMed

    Sharpe, Tim; Farren, Paul; Howieson, Stirling; Tuohy, Paul; McQuillan, Jonathan

    2015-07-21

    The need to reduce carbon emissions and fuel poverty has led to increased building envelope air tightness, intended to reduce uncontrolled ventilation heat losses. Ventilation strategies in dwellings still allow the use of trickle ventilators in window frames for background ventilation. The extent to which this results in "healthy" Indoor Air Quality (IAQ) in recently constructed dwellings was a concern of regulators in Scotland. This paper describes research to explore this. First a review of literature was conducted, then data on occupant interactions with ventilation provisions (windows, doors, trickle vents) gathered through an interview-based survey of 200 recently constructed dwellings, and measurements made on a sample of 40 of these. The main measured parameter discussed here is CO2 concentration. It was concluded after the literature review that 1000 ppm absolute was a reasonable threshold to use for "adequate" ventilation. The occupant survey found that there was very little occupant interaction with the trickle ventilators e.g., in bedrooms 63% were always closed, 28% always open, and in only 9% of cases occupants intervened to make occasional adjustments. In the measured dwellings average bedroom CO2 levels of 1520 ppm during occupied (night time) hours were observed. Where windows were open the average bedroom CO2 levels were 972 ppm. With windows closed, the combination of "trickle ventilators open plus doors open" gave an average of 1021 ppm. "Trickle ventilators open" gave an average of 1571 ppm. All other combinations gave averages of 1550 to 2000 ppm. Ventilation rates and air change rates were estimated from measured CO2 levels, for all dwellings calculated ventilation rate was less than 8 L/s/p, in 42% of cases calculated air change rate was less than 0.5 ach. It was concluded that trickle ventilation as installed and used is ineffective in meeting desired ventilation rates, evidenced by high CO2 levels reported across the sampled dwellings

  12. Subway platform air quality: Assessing the influences of tunnel ventilation, train piston effect and station design

    NASA Astrophysics Data System (ADS)

    Moreno, T.; Pérez, N.; Reche, C.; Martins, V.; de Miguel, E.; Capdevila, M.; Centelles, S.; Minguillón, M. C.; Amato, F.; Alastuey, A.; Querol, X.; Gibbons, W.

    2014-08-01

    A high resolution air quality monitoring campaign (PM, CO2 and CO) was conducted on differently designed station platforms in the Barcelona subway system under: (a) normal forced tunnel ventilation, and (b) with daytime tunnel ventilation systems shut down. PM concentrations are highly variable (6-128 μgPM1 m-3, 16-314 μgPM3 m-3, and 33-332 μgPM10 m-3, 15-min averages) depending on ventilation conditions and station design. Narrow platforms served by single-track tunnels are heavily dependent on forced tunnel ventilation and cannot rely on the train piston effect alone to reduce platform PM concentrations. In contrast PM levels in stations with spacious double-track tunnels are not greatly affected when tunnel ventilation is switched off, offering the possibility of significant energy savings without damaging air quality. Sampling at different positions along the platform reveals considerable lateral variation, with the greatest accumulation of particulates occurring at one end of the platform. Passenger accesses can dilute PM concentrations by introducing cleaner outside air, although lateral down-platform accesses are less effective than those positioned at the train entry point. CO concentrations on the platform are very low (≤1 ppm) and probably controlled by ingress of traffic-contaminated street-level air. CO2 averages range from 371 to 569 ppm, changing during the build-up and exchange of passengers with each passing train.

  13. ALGORITHMS FOR ESTIMATING RESTING METABOLIC RATE AND ACTIVITY SPECIFIC VENTILATION RATES FOR USE IN COMPLEX EXPOSURE AND INTAKE DOSE MODELS

    EPA Science Inventory

    This work summarizes advancements made that allow for better estimation of resting metabolic rate (RMR) and subsequent estimation of ventilation rates (i.e., total ventilation (VE) and alveolar ventilation (VA)) for individuals of both genders and all ages. ...

  14. Demand controlled ventilating systems: Sensor market survey. Energy conservation in buildings and community systems programme, annex 18, December 1991

    NASA Astrophysics Data System (ADS)

    Raatschen, W.; Sjoegren, M.

    The subject of indoor and outdoor air quality has generated a great deal of attention in many countries. Areas of concern include outgassing of building materials as well as occupant-generated pollutants such as carbon dioxide, moisture, and odors. Progress has also been made towards addressing issues relating to the air tightness of the building envelope. Indoor air quality studies indicate that better control of supply flow rates as well as the air distribution pattern within buildings are necessary. One method of maintaining good indoor air quality without extensive energy consumption is to control the ventilation rate according to the needs and demands of the occupants, or to preserve the building envelope. This is accomplished through the use of demand controlled ventilating (DCV) systems. The specific objective of Annex 18 is to develop guidelines for demand controlled ventilating systems based on state of the art analyses, case studies on ventilation effectiveness, and proposed ventilation rates for different users in domestic, office, and school buildings.

  15. Bias flow rate and ventilation efficiency during adult high-frequency oscillatory ventilation: a lung model study.

    PubMed

    Nagano, Osamu; Yumoto, Tetsuya; Nishimatsu, Atsunori; Kanazawa, Shunsuke; Fujita, Takahisa; Asaba, Sunao; Yamanouchi, Hideo

    2018-04-19

    Bias flow (BF) is essential to maintain mean airway pressure (MAP) and to washout carbon dioxide (CO 2 ) from the oscillator circuit during high-frequency oscillatory ventilation (HFOV). If the BF rate is inadequate, substantial CO 2 rebreathing could occur and ventilation efficiency could worsen. With lower ventilation efficiency, the required stroke volume (SV) would increase in order to obtain the same alveolar ventilation with constant frequency. The aim of this study was to assess the effect of BF rate on ventilation efficiency during adult HFOV. The R100 oscillator (Metran, Japan) was connected to an original lung model internally equipped with a simulated bronchial tree. The actual SV was measured with a flow sensor placed at the Y-piece. Carbon dioxide (CO 2 ) was continuously insufflated into the lung model ([Formula: see text]CO 2 ), and the partial pressure of CO 2 (PCO 2 ) in the lung model was monitored. Alveolar ventilation ([Formula: see text]A) was estimated as [Formula: see text]CO 2 divided by the stabilized value of PCO 2 . [Formula: see text]A was evaluated by setting SV from 80 to 180 mL (10 mL increments, n = 5) at a frequency of 8 Hz, a MAP of 25 cmH 2 O, and a BF of 10, 20, 30, and 40 L/min (study 1). Ventilation efficiency was calculated as [Formula: see text]A divided by the actual minute volume. The experiment was also performed with an actual SV of 80, 100, and 120 mL and a BF from 10 to 60 L/min (10 L/min increments: study 2). Study 1: With the same setting SV, the [Formula: see text]A with a BF of 20 L/min or more was significantly higher than that with a BF of 10 L/min. Study 2: With the same actual SV, the [Formula: see text]A and the ventilation efficiency with a BF of 30 L/min or more were significantly higher than those with a BF of 10 or 20 L/min. Increasing BF up to 30 L/min or more improved ventilation efficiency in the R100 oscillator.

  16. Effects of Classroom Ventilation Rate and Temperature on Students’ Test Scores

    PubMed Central

    2015-01-01

    Using a multilevel approach, we estimated the effects of classroom ventilation rate and temperature on academic achievement. The analysis is based on measurement data from a 70 elementary school district (140 fifth grade classrooms) from Southwestern United States, and student level data (N = 3109) on socioeconomic variables and standardized test scores. There was a statistically significant association between ventilation rates and mathematics scores, and it was stronger when the six classrooms with high ventilation rates that were indicated as outliers were filtered (> 7.1 l/s per person). The association remained significant when prior year test scores were included in the model, resulting in less unexplained variability. Students’ mean mathematics scores (average 2286 points) were increased by up to eleven points (0.5%) per each liter per second per person increase in ventilation rate within the range of 0.9–7.1 l/s per person (estimated effect size 74 points). There was an additional increase of 12–13 points per each 1°C decrease in temperature within the observed range of 20–25°C (estimated effect size 67 points). Effects of similar magnitude but higher variability were observed for reading and science scores. In conclusion, maintaining adequate ventilation and thermal comfort in classrooms could significantly improve academic achievement of students. PMID:26317643

  17. ENVIRONMENTAL TECHNOLOGY VERIFICATION--GENERIC VERIFICATION PROTOCOL FOR BIOLOGICAL AND AEROSOL TESTING OF GENERAL VENTILATION AIR CLEANERS

    EPA Science Inventory

    Under EPA's Environmental Technology Verification Program, Research Triangle Institute (RTI) will operate the Air Pollution Control Technology Center to verify the filtration efficiency and bioaerosol inactivation efficiency of heating, ventilation and air conditioning air cleane...

  18. In China, Students in Crowded Dormitories with a Low Ventilation Rate Have More Common Colds: Evidence for Airborne Transmission

    PubMed Central

    Sun, Yuexia; Wang, Zhigang; Zhang, Yufeng; Sundell, Jan

    2011-01-01

    Objective To test whether the incidence of common colds among college students in China is associated with ventilation rates and crowdedness in dormitories. Methods In Phase I of the study, a cross-sectional study, 3712 students living in 1569 dorm rooms in 13 buildings responded to a questionnaire about incidence and duration of common colds in the previous 12 months. In Phase II, air temperature, relative humidity and CO2 concentration were measured for 24 hours in 238 dorm rooms in 13 buildings, during both summer and winter. Out-to indoor air flow rates at night were calculated based on measured CO2 concentrations. Results In Phase I, 10% of college students reported an incidence of more than 6 common colds in the previous 12 months, and 15% reported that each infection usually lasted for more than 2 weeks. Students in 6-person dorm rooms were about 2 times as likely to have an incidence of common colds ≥6 times per year and a duration ≥2 weeks, compared to students in 3-person rooms. In Phase II, 90% of the measured dorm rooms had an out-to indoor air flow rate less than the Chinese standard of 8.3 L/s per person during the heating season. There was a dose-response relationship between out-to indoor air flow rate per person in dorm rooms and the proportion of occupants with annual common cold infections ≥6 times. A mean ventilation rate of 5 L/(s•person) in dorm buildings was associated with 5% of self reported common cold ≥6 times, compared to 35% at 1 L/(s•person). Conclusion Crowded dormitories with low out-to indoor airflow rates are associated with more respiratory infections among college students. PMID:22110607

  19. A comparison between tracer gas and aerosol particles distribution indoors: The impact of ventilation rate, interaction of airflows, and presence of objects.

    PubMed

    Bivolarova, M; Ondráček, J; Melikov, A; Ždímal, V

    2017-11-01

    The study investigated the separate and combined effects of ventilation rate, free convection flow produced by a thermal manikin, and the presence of objects on the distribution of tracer gas and particles in indoor air. The concentration of aerosol particles and tracer gas was measured in a test room with mixing ventilation. Three layouts were arranged: an empty room, an office room with an occupant sitting in front of a table, and a single-bed hospital room. The room occupant was simulated by a thermal manikin. Monodisperse particles of three sizes (0.07, 0.7, and 3.5 μm) and nitrous oxide tracer gas were generated simultaneously at the same location in the room. The particles and gas concentrations were measured in the bulk room air, in the breathing zone of the manikin, and in the exhaust air. Within the breathing zone of the sitting occupant, the tracer gas emerged as reliable predictor for the exposure to all different-sized test particles. A change in the ventilation rate did not affect the difference in concentration distribution between tracer gas and larger particle sizes. Increasing the room surface area did not influence the similarity in the dispersion of the aerosol particles and the tracer gas. © 2017 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  20. The impact of cage ventilation on rats housed in IVC systems.

    PubMed

    Krohn, Thomas C; Hansen, Axel Kornerup; Dragsted, Nils

    2003-04-01

    Today the use of individually ventilated cage systems (IVC systems) is common, especially for housing transgenic rodents. Typically, in each cage a ventilation rate of 40 to 50 air changes per hour is applied, but in some systems even up to 120 air changes per hour is applied. To reach this rate, the air is blown into the cage at a relatively high speed. However, at the animal's level most systems ventilate with an air speed of approximately 0.2 m/s. In the present paper, two studies were conducted, one analysing whether an air speed below 0.2 m/s or just above 0.5 m/s affects the rats, and another study analysing whether air changes of 50, 80 and 120 times per hour affect the rats. In both studies, monitoring of preferences as well as physiological parameters such as heart rate and blood pressure, was used to show the ability of the animals to register the different parameters and to avoid them if possible. Air speeds inside the cage of as high as 0.5 m/s could not be shown to affect the rats, while the number of air changes in each cage should be kept below 80 times per hour to avoid impacts on physiology (heart rate and systolic blood pressure). Also the rats prefer cages with air changes below 80 times per hour if they have the opportunity of choosing, as shown in the preference test.

  1. Carbon Dioxide Detection and Indoor Air Quality Control.

    PubMed

    Bonino, Steve

    2016-04-01

    When building ventilation is reduced, energy is saved because it is not necessary to heat or cool as much outside air. Reduced ventilation can result in higher levels of carbon dioxide, which may cause building occupants to experience symptoms. Heating or cooling for ventilation air can be enhanced by a DCV system, which can save energy while providing a comfortable environment. Carbon dioxide concentrations within a building are often used to indicate whether adequate fresh air is being supplied to the building. These DCV systems use carbon dioxide sensors in each space or in the return air and adjust the ventilation based on carbon dioxide concentration; the higher the concentration, the more people occupy the space relative to the ventilation rate. With a carbon dioxide sensor DCV system, the fresh air ventilation rate varies based on the number ofpeople in the space, saving energy while maintaining a safe and comfortable environment.

  2. Test Protocol for Room-to-Room Distribution of Outside Air by Residential Ventilation Systems

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Barley, C. D.; Anderson, R.; Hendron, B.

    2007-12-01

    This test and analysis protocol has been developed as a practical approach for measuring outside air distribution in homes. It has been used successfully in field tests and has led to significant insights on ventilation design issues. Performance advantages of more sophisticated ventilation systems over simpler, less-costly designs have been verified, and specific problems, such as airflow short-circuiting, have been identified.

  3. Shared air: a renewed focus on ventilation for the prevention of tuberculosis transmission.

    PubMed

    Richardson, Eugene T; Morrow, Carl D; Kalil, Darryl B; Ginsberg, Samuel; Bekker, Linda-Gail; Wood, Robin

    2014-01-01

    Despite an improvement in the overall TB cure rate from 40-74% between 1995 and 2011, TB incidence in South Africa continues to increase. The epidemic is notably disquieting in schools because the vulnerable population is compelled to be present. Older learners (age 15-19) are at particular risk given a smear-positive rate of 427 per 100,000 per year and the significant amount of time they spend indoors. High schools are therefore important locations for potential TB infection and thus prevention efforts. Using portable carbon dioxide monitors, we measured CO2 in classrooms under non-steady state conditions. The threshold for tuberculosis transmission was estimated using a carbon dioxide-based risk equation. We determined a critical rebreathed fraction of carbon dioxide (ƒ(c)) of 1 · 6%, which correlates with an indoor CO2 concentration of 1000 ppm. These values correspond with a ventilation rate of 8 · 6 l/s per person or 12 air exchanges per hour (ACH) for standard classrooms of 180 m(3). Given the high smear positive rate of high-school adolescents in South Africa, the proposal to achieve CO2 levels of 1000 ppm through natural ventilation (in the amount 12 ACH) will not only help achieve WHO guidelines for providing children with healthy indoor environments, it will also provide a low-cost intervention for helping control the TB epidemic in areas of high prevalence.

  4. Shared Air: A Renewed Focus on Ventilation for the Prevention of Tuberculosis Transmission

    PubMed Central

    Richardson, Eugene T.; Morrow, Carl D.; Kalil, Darryl B.; Bekker, Linda-Gail; Wood, Robin

    2014-01-01

    Background Despite an improvement in the overall TB cure rate from 40–74% between 1995 and 2011, TB incidence in South Africa continues to increase. The epidemic is notably disquieting in schools because the vulnerable population is compelled to be present. Older learners (age 15–19) are at particular risk given a smear-positive rate of 427 per 100,000 per year and the significant amount of time they spend indoors. High schools are therefore important locations for potential TB infection and thus prevention efforts. Methods and Findings Using portable carbon dioxide monitors, we measured CO2 in classrooms under non-steady state conditions. The threshold for tuberculosis transmission was estimated using a carbon dioxide-based risk equation. We determined a critical rebreathed fraction of carbon dioxide () of 1·6%, which correlates with an indoor CO2 concentration of 1000 ppm. These values correspond with a ventilation rate of 8·6 l/s per person or 12 air exchanges per hour (ACH) for standard classrooms of 180 m3. Conclusions Given the high smear positive rate of high-school adolescents in South Africa, the proposal to achieve CO2 levels of 1000ppm through natural ventilation (in the amount 12 ACH) will not only help achieve WHO guidelines for providing children with healthy indoor environments, it will also provide a low-cost intervention for helping control the TB epidemic in areas of high prevalence. PMID:24804707

  5. Operating theatre ventilation systems and microbial air contamination in total joint replacement surgery: results of the GISIO-ISChIA study.

    PubMed

    Agodi, A; Auxilia, F; Barchitta, M; Cristina, M L; D'Alessandro, D; Mura, I; Nobile, M; Pasquarella, C

    2015-07-01

    Recent studies have shown a higher rate of surgical site infections in hip prosthesis implantation using unidirectional airflow ventilation compared with turbulent ventilation. However, these studies did not measure the air microbial quality of operating theatres (OTs), and assumed it to be compliant with the recommended standards for this ventilation technique. To evaluate airborne microbial contamination in OTs during hip and knee replacement surgery, and compare the findings with values recommended for joint replacement surgery. Air samplings were performed in 28 OTs supplied with unidirectional, turbulent and mixed airflow ventilation. Samples were collected using passive sampling to determine the index of microbial air contamination (IMA). Active sampling was also performed in some of the OTs. The average number of people in the OT and the number of door openings during the sampling period were recorded. In total, 1228 elective prosthesis procedures (60.1% hip and 39.9% knee) were included in this study. Of passive samplings performed during surgical activity in unidirectional airflow ventilation OTs (U-OTs) and mixed airflow OTs (M-OTs), 58.9% and 87.6% had IMA values >2, respectively. Of samplings performed during surgical activity in turbulent airflow OTs (T-OTs) and in turbulent airflow OTs with the surgical team wearing Steri-Shield Turbo Helmets (TH-OTs), 8.6% and 60% had IMA values ≤ 2, respectively. Positive correlation was found between IMA values and the number of people in the OT and the number of door openings (P < 0.001). In addition, correlation was found between active and passive sampling (P < 0.001). These findings challenge the belief that unidirectional systems always provide acceptable airborne bacterial counts. Copyright © 2015 The Healthcare Infection Society. Published by Elsevier Ltd. All rights reserved.

  6. Heating, Ventilation, Air Conditioning. Resource Manual for Custodial Training Course #3.

    ERIC Educational Resources Information Center

    Florida State Dept. of Education, Tallahassee. School Plant Management Section.

    Intended as a manual to provide school custodians with some understanding of basic functions of heating, ventilating, and air conditioning equipment for safe, efficient operation. Contains general rules and specifications for providing custodians with a more complete awareness of their equipment and the field of "Climate Control" within the…

  7. 6. VIEW LOOKING SOUTHEAST AT VENTILATION EQUIPMENT IN SOUTH VENTILATION ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    6. VIEW LOOKING SOUTHEAST AT VENTILATION EQUIPMENT IN SOUTH VENTILATION HOUSE. THIS AIR CONDITIONING SYSTEM WAS INSTALLED BY PARKS-CRAMER COMPANY OF FITCHBURG, MASSACHUSETTS WHEN THE MILL WAS CONSTRUCTED IN 1923-24. ONE AIR WASHER AND FAN ROOM EXTERIOR IS VISIBLE ON THE RIGHT. THE DUCTS FROM BOTH FAN ROOMS (CURVED METAL STRUCTURES AT CENTER AND LEFT OF PHOTO) ARE CONNECTED TO A COMMON AIR SHAFT. - Stark Mill, 117 Corinth Road, Hogansville, Troup County, GA

  8. [Anesthesia ventilators].

    PubMed

    Otteni, J C; Beydon, L; Cazalaà, J B; Feiss, P; Nivoche, Y

    1997-01-01

    To review anaesthesia ventilators in current use in France by categories of ventilators. References were obtained from computerized bibliographic search. (Medline), recent review articles, the library of the service and personal files. Anaesthesia ventilators can be allocated into three groups, depending on whether they readminister expired gases or not or allow both modalities. Contemporary ventilators provide either constant volume ventilation, or constant pressure ventilation, with or without a pressure plateau. Ventilators readministering expired gases after CO2 absorption, or closed circuit ventilators, are either of a double- or a single-circuit design. Double-circuit ventilators, or pneumatical bag or bellows squeezers, or bag-in-bottle or bellows-in-bottle (or box) ventilators, consist of a primary, or driving circuit (bottle or box) and a secondary or patient circuit (including a bag or a bellows or membrane chambers). Bellows-in-bottle ventilators have either standing bellows ascending at expiration, or hanging bellows, descending at expiration. Ascending bellows require a positive pressure of about 2 cmH2O throughout exhalation to allow the bellows to refill. The expired gas volume is a valuable indicator for leak and disconnection. Descending bellows generate a slight negative pressure during exhalation. In case of leak or disconnection they aspirate ambient air and cannot act therefore as an indicator for integrity of the circuit and the patient connection. Closed circuit ventilators with a single-circuit (patient circuit) include a insufflating device consisting either in a bellows or a cylinder with a piston, operated by a electric or pneumatic motor. As the hanging bellows of the double circuit ventilators, they generate a slight negative pressure during exhalation and aspirate ambient air in case of leak or disconnection. Ventilators not designed for the readministration of expired gases, or open circuit ventilators, are generally stand

  9. Technology evaluation of heating, ventilation, and air conditioning for MIUS application

    NASA Technical Reports Server (NTRS)

    Gill, W. L.; Keough, M. B.; Rippey, J. O.

    1974-01-01

    Potential ways of providing heating, ventilation, and air conditioning for a building complex serviced by a modular integrated utility system (MIUS) are examined. Literature surveys were conducted to investigate both conventional and unusual systems to serve this purpose. The advantages and disadvantages of the systems most compatible with MIUS are discussed.

  10. Ventilation, temperature, and HVAC characteristics in small and medium commercial buildings in California.

    PubMed

    Bennett, D H; Fisk, W; Apte, M G; Wu, X; Trout, A; Faulkner, D; Sullivan, D

    2012-08-01

    This field study of 37 small and medium commercial buildings throughout California obtained information on ventilation rate, temperature, and heating, ventilating, and air-conditioning (HVAC) system characteristics. The study included seven retail establishments; five restaurants; eight offices; two each of gas stations, hair salons, healthcare facilities, grocery stores, dental offices, and fitness centers; and five other buildings. Fourteen (38%) of the buildings either could not or did not provide outdoor air through the HVAC system. The air exchange rate averaged 1.6 (s.d. = 1.7) exchanges per hour and was similar between buildings with and without outdoor air supplied through the HVAC system, indicating that some buildings have significant leakage or ventilation through open windows and doors. Not all buildings had sufficient air exchange to meet ASHRAE 62.1 Standards, including buildings used for fitness centers, hair salons, offices, and retail establishments. The majority of the time, buildings were within the ASHRAE temperature comfort range. Offices were frequently overcooled in the summer. All of the buildings had filters, but over half the buildings had a filter with a minimum efficiency reporting value rating of 4 or lower, which are not very effective for removing fine particles. Most U.S. commercial buildings (96%) are small- to medium-sized, using nearly 18% of the country's energy, and sheltering a large population daily. Little is known about the ventilation systems in these buildings. This study found a wide variety of ventilation conditions, with many buildings failing to meet relevant ventilation standards. Regulators may want to consider implementing more complete building inspections at commissioning and point of sale. © 2012 John Wiley & Sons A/S.

  11. Evaluation of design ventilation requirements for enclosed parking facilities

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Ayari, A.; Krarti, M.

    2000-07-01

    This paper proposes a new design approach to determine the ventilation requirements for enclosed parking garages. The design approach accounts for various factors that affect the indoor air quality within a parking facility, including the average CO emission rate, the average travel time, the number of cars, and the acceptable CO level within the parking garage. This paper first describes the results of a parametric analysis based on the design method that was developed. Then the design method is presented to explain how the ventilation flow rate can be determined for any enclosed parking facility. Finally, some suggestions are proposedmore » to save fan energy for ventilating parking garages using demand ventilation control strategies.« less

  12. [Disinfectants and main sanitary and preventive measures for protection of ventilation and air-conditioning systems from Legionella contamination].

    PubMed

    Gerasimov, V N; Golov, E A; Khramov, M V; Diatlov, I A

    2008-01-01

    The study was devoted to selection and assessment of disinfecting preparations for prevention of contamination by Legionella. Using system of criteria for quality assessment of disinfectants, seven newdomestic ones belonging to quaternary ammonium compounds class or to oxygen-containing preparations and designed for disinfecting of air-conditioning and ventilation systems were selected. Antibacterial and disinfecting activities of working solutions of disinfectants were tested in laboratory on the test-surfaces and test-objects of premises' air-conditioning and ventilation systems contaminated with Legionella. High antimicrobial and disinfecting activity of new preparations "Dezactiv-M", "ExtraDez", "Emital-Garant", "Aquasept Plus", "Samarovka", "Freesept", and "Ecobreeze Oxy" during their exposure on objects and materials contaminated with Legionella was shown. Main sanitary and preventive measures for defending of air-conditioning and ventilation systems from contamination by Legionella species were presented.

  13. The effect of ventilation on indoor exposure to semivolatile organic compounds.

    PubMed

    Liu, C; Zhang, Y; Benning, J L; Little, J C

    2015-06-01

    A mechanistic model was developed to examine how natural ventilation influences residential indoor exposure to semivolatile organic compounds (SVOCs) via inhalation, dermal sorption, and dust ingestion. The effect of ventilation on indoor particle mass concentration and mass transfer at source/sink surfaces, and the enhancing effect of particles on mass transfer at source/sink surfaces are included. When air exchange rate increases from 0.6/h to 1.8/h, the steady-state SVOC (gas-phase plus particle phase with log KOA varying from 9 to 13) concentration in the idealized model decreases by about 60%. In contrast, for the same change in ventilation, the simulated indoor formaldehyde (representing volatile organic compounds) gas-phase concentration decreases by about 70%. The effect of ventilation on exposure via each pathway has a relatively insignificant association with the KOA of the SVOCs: a change of KOA from 10(9) to 10(13) results in a change of only 2-30%. Sensitivity analysis identifies the deposition rate of PM2.5 as a primary factor influencing the relationship between ventilation and exposure for SVOCs with log KOA = 13. The relationship between ventilation rate and air speed near surfaces needs to be further substantiated. © 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  14. Exhaled air dispersion during noninvasive ventilation via helmets and a total facemask.

    PubMed

    Hui, David S; Chow, Benny K; Lo, Thomas; Ng, Susanna S; Ko, Fanny W; Gin, Tony; Chan, Matthew T V

    2015-05-01

    Noninvasive ventilation (NIV) via helmet or total facemask is an option for managing patients with respiratory infections in respiratory failure. However, the risk of nosocomial infection is unknown. We examined exhaled air dispersion during NIV using a human patient simulator reclined at 45° in a negative pressure room with 12 air changes/h by two different helmets via a ventilator and a total facemask via a bilevel positive airway pressure device. Exhaled air was marked by intrapulmonary smoke particles, illuminated by laser light sheet, and captured by a video camera for data analysis. Significant exposure was defined as where there was ≥ 20% of normalized smoke concentration. During NIV via a helmet with the simulator programmed in mild lung injury, exhaled air leaked through the neck-helmet interface with a radial distance of 150 to 230 mm when inspiratory positive airway pressure was increased from 12 to 20 cm H2O, respectively, while keeping the expiratory pressure at 10 cm H2O. During NIV via a helmet with air cushion around the neck, there was negligible air leakage. During NIV via a total facemask for mild lung injury, air leaked through the exhalation port to 618 and 812 mm when inspiratory pressure was increased from 10 to 18 cm H2O, respectively, with the expiratory pressure at 5 cm H2O. A helmet with a good seal around the neck is needed to prevent nosocomial infection during NIV for patients with respiratory infections.

  15. Adaptive support ventilation may deliver unwanted respiratory rate-tidal volume combinations in patients with acute lung injury ventilated according to an open lung concept.

    PubMed

    Dongelmans, Dave A; Paulus, Frederique; Veelo, Denise P; Binnekade, Jan M; Vroom, Margreeth B; Schultz, Marcus J

    2011-05-01

    With adaptive support ventilation, respiratory rate and tidal volume (V(T)) are a function of the Otis least work of breathing formula. We hypothesized that adaptive support ventilation in an open lung ventilator strategy would deliver higher V(T)s to patients with acute lung injury. Patients with acute lung injury were ventilated according to a local guideline advising the use of lower V(T) (6-8 ml/kg predicted body weight), high concentrations of positive end-expiratory pressure, and recruitment maneuvers. Ventilation parameters were recorded when the ventilator was switched to adaptive support ventilation, and after recruitment maneuvers. If V(T) increased more than 8 ml/kg predicted body weight, airway pressure was limited to correct for the rise of V(T). Ten patients with a mean (±SD) Pao(2)/Fio(2) of 171 ± 86 mmHg were included. After a switch from pressure-controlled ventilation to adaptive support ventilation, respiratory rate declined (from 31 ± 5 to 21 ± 6 breaths/min; difference = 10 breaths/min, 95% CI 3-17 breaths/min, P = 0.008) and V(T) increased (from 6.5 ± 0.8 to 9.0 ± 1.6 ml/kg predicted body weight; difference = 2.5 ml, 95% CI 0.4-4.6 ml/kg predicted body weight, P = 0.02). Pressure limitation corrected for the rise of V(T), but minute ventilation declined, forcing the user to switch back to pressure-controlled ventilation. Adaptive support ventilation, compared with pressure-controlled ventilation in an open lung strategy setting, delivers a lower respiratory rate-higher V(T) combination. Pressure limitation does correct for the rise of V(T), but leads to a decline in minute ventilation.

  16. The transmission characteristics of indoor particles under different ventilation conditions

    NASA Astrophysics Data System (ADS)

    Lv, Yang; Wang, Haifeng; Wei, Shanshan

    2017-11-01

    In modern society, ventilation is an important method for removing indoor particles. This study applies the parameter of attenuation index to analyze the effect of the removal of indoor particles in the two typical ventilation strategies called ceiling exhaust and slit exhaust strategy. Experiment was conducted in a chamber and riboflavin particles were used as the indoor particles source, instantaneous microbial detection (IMD) used to measure the particulate concentration. Conclusions can be found that air exchange rate is an important factor affecting the indoor particle concentration distribution. In the process of indoor free settling(air exchange rate is 0 h-1), the deposition rate were 0.086 h-1, 0.122 h-1, 0.173 h-1 for the particles of 0.5-1.0 μm, 1.0-3.0μm and 3.0-5.0 μm. When the air exchange rate increased to 2.5 h-1, the differences in the attenuation index is significant. There was also a significant linear relationship between air exchange rate and attenuation index. Furthermore, the effect of the slit exhaust strategy on the removal of coarse particles is more remarkable as the increasing air exchange rate.

  17. Forced-air warming and ultra-clean ventilation do not mix: an investigation of theatre ventilation, patient warming and joint replacement infection in orthopaedics.

    PubMed

    McGovern, P D; Albrecht, M; Belani, K G; Nachtsheim, C; Partington, P F; Carluke, I; Reed, M R

    2011-11-01

    We investigated the capacity of patient warming devices to disrupt the ultra-clean airflow system. We compared the effects of two patient warming technologies, forced-air and conductive fabric, on operating theatre ventilation during simulated hip replacement and lumbar spinal procedures using a mannequin as a patient. Infection data were reviewed to determine whether joint infection rates were associated with the type of patient warming device that was used. Neutral-buoyancy detergent bubbles were released adjacent to the mannequin's head and at floor level to assess the movement of non-sterile air into the clean airflow over the surgical site. During simulated hip replacement, bubble counts over the surgical site were greater for forced-air than for conductive fabric warming when the anaesthesia/surgery drape was laid down (p = 0.010) and at half-height (p < 0.001). For lumbar surgery, forced-air warming generated convection currents that mobilised floor air into the surgical site area. Conductive fabric warming had no such effect. A significant increase in deep joint infection, as demonstrated by an elevated infection odds ratio (3.8, p = 0.024), was identified during a period when forced-air warming was used compared to a period when conductive fabric warming was used. Air-free warming is, therefore, recommended over forced-air warming for orthopaedic procedures.

  18. Aerodynamic characteristics of the ventilated design for flapping wing micro air vehicle.

    PubMed

    Zhang, G Q; Yu, S C M

    2014-01-01

    Inspired by superior flight performance of natural flight masters like birds and insects and based on the ventilating flaps that can be opened and closed by the changing air pressure around the wing, a new flapping wing type has been proposed. It is known that the net lift force generated by a solid wing in a flapping cycle is nearly zero. However, for the case of the ventilated wing, results for the net lift force are positive which is due to the effect created by the "ventilation" in reducing negative lift force during the upstroke. The presence of moving flaps can serve as the variable in which, through careful control of the areas, a correlation with the decrease in negative lift can be generated. The corresponding aerodynamic characteristics have been investigated numerically by using different flapping frequencies and forward flight speeds.

  19. Evidence of inadequate ventilation in portable classrooms: results of a pilot study in Los Angeles County.

    PubMed

    Shendell, D G; Winer, A M; Weker, R; Colome, S D

    2004-06-01

    The prevalence of prefabricated, portable classrooms (portables) for United States public schools has increased; in California, approximately one of three students learn inside portables. Limited research has been conducted on indoor air and environmental quality in American schools, and almost none in portables. Available reports and conference proceedings suggest problems from insufficient ventilation due to poor design, operation, and/or maintenance of heating, ventilation and air conditioning (HVAC) systems; most portables have one mechanical, wall-mounted HVAC system. A pilot assessment was conducted in Los Angeles County, including measurements of integrated ventilation rates based on a perfluorocarbon tracer gas technique and continuous monitoring of temperature (T) and relative humidity (RH). Measured ventilation rates were low [mean school day integrated average 0.8 per hour (range: 0.1-2.9 per hour)]. Compared with relevant standards, results suggested adequate ventilation and associated conditioning of indoor air for occupant comfort were not always provided to these classrooms. Future school studies should include integrated and continuous measurements of T, RH, and ventilation with appropriate tracer gas methods, and other airflow measures. Adequate ventilation has the potential to mitigate concentrations of chemical pollutants, particles, carbon dioxide, and odors in portable and traditional classrooms, which should lead to a reduction in reported health outcomes, e.g., symptoms of 'sick building syndrome', allergies, asthma. Investigations of school indoor air and environmental quality should include continuous temperature and relative humidity data with inexpensive instrumentation as indicators of thermal comfort, and techniques to measure ventilation rates.

  20. Summarized Data of Test Space Heating, Ventilation and Air Conditioning Inspections from the Building Assessment Survey and Evaluation Study

    EPA Pesticide Factsheets

    Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations, and operation and maintenance issues

  1. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Battista, L.; Sciuto, S. A.; Scorza, A.

    2013-03-15

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it;more » the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 Multiplication-Sign 10{sup -4} m{sup 3}/s (18.0 l/min) for the mono-directional sensor and a measurement range of {+-}3.00 Multiplication-Sign 10{sup -4} m{sup 3}/s ({+-}18.0 l/min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed

  2. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique.

    PubMed

    Battista, L; Sciuto, S A; Scorza, A

    2013-03-01

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it; the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 × 10(-4) m(3)∕s (18.0 l∕min) for the mono-directional sensor and a measurement range of ±3.00 × 10(-4) m(3)∕s (±18.0 l∕min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed theoretical model: for the mono

  3. An air flow sensor for neonatal mechanical ventilation applications based on a novel fiber-optic sensing technique

    NASA Astrophysics Data System (ADS)

    Battista, L.; Sciuto, S. A.; Scorza, A.

    2013-03-01

    In this work, a simple and low-cost air flow sensor, based on a novel fiber-optic sensing technique has been developed for monitoring air flows rates supplied by a neonatal ventilator to support infants in intensive care units. The device is based on a fiber optic sensing technique allowing (a) the immunity to light intensity variations independent by measurand and (b) the reduction of typical shortcomings affecting all biomedical fields (electromagnetic interference and patient electrical safety). The sensing principle is based on the measurement of transversal displacement of an emitting fiber-optic cantilever due to action of air flow acting on it; the fiber tip displacement is measured by means of a photodiode linear array, placed in front of the entrance face of the emitting optical fiber in order to detect its light intensity profile. As the measurement system is based on a detection of the illumination pattern, and not on an intensity modulation technique, it results less sensitive to light intensity fluctuation independent by measurand than intensity-based sensors. The considered technique is here adopted in order to develop two different configurations for an air flow sensor suitable for the measurement of air flow rates typically occurring during mechanical ventilation of newborns: a mono-directional and a bi-directional transducer have been proposed. A mathematical model for the air flow sensor is here proposed and a static calibration of two different arrangements has been performed: a measurement range up to 3.00 × 10-4 m3/s (18.0 l/min) for the mono-directional sensor and a measurement range of ±3.00 × 10-4 m3/s (±18.0 l/min) for the bi-directional sensor are experimentally evaluated, according to the air flow rates normally encountered during tidal breathing of infants with a mass lower than 10 kg. Experimental data of static calibration result in accordance with the proposed theoretical model: for the mono-directional configuration, the

  4. Dynamic evaluation of airflow rates for a variable air volume system serving an open-plan office.

    PubMed

    Mai, Horace K W; Chan, Daniel W T; Burnett, John

    2003-09-01

    In a typical air-conditioned office, the thermal comfort and indoor air quality are sustained by delivering the amount of supply air with the correct proportion of outdoor air to the breathing zone. However, in a real office, it is not easy to measure these airflow rates supplied to space, especially when the space is served by a variable air volume (VAV) system. The most accurate method depends on what is being measured, the details of the building and types of ventilation system. The constant concentration tracer gas method as a means to determine ventilation system performance, however, this method becomes more complicated when the air, including the tracer gas is allowed to recirculate. An accurate measurement requires significant resource support in terms of instrumentation set up and also professional interpretation. This method deters regular monitoring of the performance of an airside systems by building managers, and hence the indoor environmental quality, in terms of thermal comfort and indoor air quality, may never be satisfactory. This paper proposes a space zone model for the calculation of all the airflow parameters based on tracer gas measurements, including flow rates of outdoor air, VAV supply, return space, return and exfiltration. Sulphur hexafluoride (SF6) and carbon dioxide (CO2) are used as tracer gases. After using both SF6 and CO2, the corresponding results provide a reference to justify the acceptability of using CO2 as the tracer gas. The validity of using CO2 has the significance that metabolic carbon dioxide can be used as a means to evaluate real time airflow rates. This approach provides a practical protocol for building managers to evaluate the performance of airside systems.

  5. First experiences with methods to measure ammonia emissions from naturally ventilated cattle buildings in the U.K.

    NASA Astrophysics Data System (ADS)

    Demmers, T. G. M.; Burgess, L. R.; Short, J. L.; Phillips, V. R.; Clark, J. A.; Wathes, C. M.

    A method has been developed to measure the emission rate of ammonia from naturally ventilated U.K. livestock buildings. The method is based on measurements of ammonia concentration and estimates of the ventilation rate of the building by continuous release of carbon monoxide tracer within the building. The tracer concentration is measured at nine positions in openings around the perimeter of the building, as well as around a ring sampling line. Two criteria were evaluated to decide whether, at any given time, a given opening in the building acted as an air inlet or as an air outlet. Carbon monoxide concentration difference across an opening was found to be a better criterion than the temperature difference across the opening. Ammonia concentrations were measured continuously at the sampling points using a chemiluminescence analyser. The method was applied to a straw-bedded beef unit and to a slurry-based dairy unit. Both buildings were of space-boarded construction. Ventilation rates estimated by the ring line sample were consistently higher than by the perimeter samples. During calm weather, the ventilation estimates by both samples were similar (10-20 air changes h -1). However, during windy conditions (>5 m s -1) the ventilation rate was overestimated by the ring line sample (average 100 air changes h -1) compared to the perimeter samples (average 50 air changes h -1). The difference was caused by incomplete mixing of the tracer within the building. The ventilation rate estimated from the perimeter samples was used for the calculation of the emission rate. Preliminary estimates of the ammonia emission factor were 6.0 kg NH 3 (500 kg live-weight) -1 (190 d) -1 for the slurry-based dairy unit and 3.7 for the straw-bedded beef unit.

  6. Characterization of natural ventilation in wastewater collection systems.

    PubMed

    Ward, Matthew; Corsi, Richard; Morton, Robert; Knapp, Tom; Apgar, Dirk; Quigley, Chris; Easter, Chris; Witherspoon, Jay; Pramanik, Amit; Parker, Wayne

    2011-03-01

    The purpose of the study was to characterize natural ventilation in full-scale gravity collection system components while measuring other parameters related to ventilation. Experiments were completed at four different locations in the wastewater collection systems of Los Angeles County Sanitation Districts, Los Angeles, California, and the King County Wastewater Treatment District, Seattle, Washington. The subject components were concrete gravity pipes ranging in diameter from 0.8 to 2.4 m (33 to 96 in.). Air velocity was measured in each pipe using a carbon-monoxide pulse tracer method. Air velocity was measured entering or exiting the components at vents using a standpipe and hotwire anemometer arrangement. Ambient wind speed, temperature, and relative humidity; headspace temperature and relative humidity; and wastewater flow and temperature were measured. The field experiments resulted in a large database of measured ventilation and related parameters characterizing ventilation in full-scale gravity sewers. Measured ventilation rates ranged from 23 to 840 L/s. The experimental data was used to evaluate existing ventilation models. Three models that were based upon empirical extrapolation, computational fluid dynamics, and thermodynamics, respectively, were evaluated based on predictive accuracy compared to the measured data. Strengths and weaknesses in each model were found and these observations were used to propose a concept for an improved ventilation model.

  7. Experimental study of airflow characteristics of stratum ventilation in a multi-occupant room with comparison to mixing ventilation and displacement ventilation.

    PubMed

    Cheng, Y; Lin, Z

    2015-12-01

    The motivation of this study is stimulated by a lack of knowledge about the difference of airflow characteristics between a novel air distribution method [i.e., stratum ventilation (SV)] and conventional air distribution methods [i.e., mixing ventilation (MV) and displacement ventilation (DV)]. Detailed air velocity and temperature measurements were conducted in the occupied zone of a classroom with dimensions of 8.8 m (L) × 6.1 m (W) × 2.4 m (H). Turbulence intensity and power spectrum of velocity fluctuation were calculated using the measured data. Thermal comfort and cooling efficiency were also compared. The results show that in the occupied zone, the airflow characteristics among MV, DV, and SV are different. The turbulent airflow fluctuation is enhanced in this classroom with multiple thermal manikins due to thermal buoyancy and airflow mixing effect. Thermal comfort evaluations indicate that in comparison with MV and DV, a higher supply air temperature should be adopted for SV to achieve general thermal comfort with low draft risk. Comparison of the mean air temperatures in the occupied zone reveals that SV is of highest cooling efficiency, followed by DV and then MV. This study reports the unique profiles of flow, temperature, turbulence intensity, and power spectrum of stratum ventilation, which can have a number of implications for both knowledge and understanding of the flow characteristics in a stratum-ventilated room. With respect to the former, it expounds the fundamental characteristics of this air distribution method; and with respect to the latter, it reveals the mechanism of thermal comfort and energy saving under stratum ventilation. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  8. Modelling dynamics of atmosphere ventilation and industrial city’s air pollution analysis: New approach

    NASA Astrophysics Data System (ADS)

    Glushkov, A. V.; Khetselius, O. Yu; Agayar, E. V.; Buyadzhi, V. V.; Romanova, A. V.; Mansarliysky, V. F.

    2017-10-01

    We present a new effective approach to analysis and modelling the natural air ventilation in an atmosphere of the industrial city, which is based on the Arakawa-Schubert and Glushkov models, modified to calculate the current involvement of the ensemble of clouds, and advanced mathematical methods of modelling an unsteady turbulence in the urban area. For the first time the methods of a plane complex field and spectral expansion algorithms are applied to calculate the air circulation for the cloud layer arrays, penetrating into the territory of the industrial city. We have also taken into account for the mechanisms of transformation of the cloud system advection over the territory of the urban area. The results of test computing the air ventilation characteristics are presented for the Odessa city. All above cited methods and models together with the standard monitoring and management systems can be considered as a basis for comprehensive “Green City” construction technology.

  9. International Space Station Crew Quarters Ventilation and Acoustic Design Implementation

    NASA Technical Reports Server (NTRS)

    Broyan, James L., Jr.; Cady, Scott M; Welsh, David A.

    2010-01-01

    The International Space Station (ISS) United States Operational Segment has four permanent rack sized ISS Crew Quarters (CQs) providing a private crew member space. The CQs use Node 2 cabin air for ventilation/thermal cooling, as opposed to conditioned ducted air-from the ISS Common Cabin Air Assembly (CCAA) or the ISS fluid cooling loop. Consequently, CQ can only increase the air flow rate to reduce the temperature delta between the cabin and the CQ interior. However, increasing airflow causes increased acoustic noise so efficient airflow distribution is an important design parameter. The CQ utilized a two fan push-pull configuration to ensure fresh air at the crew member's head position and reduce acoustic exposure. The CQ ventilation ducts are conduits to the louder Node 2 cabin aisle way which required significant acoustic mitigation controls. The CQ interior needs to be below noise criteria curve 40 (NC-40). The design implementation of the CQ ventilation system and acoustic mitigation are very inter-related and require consideration of crew comfort balanced with use of interior habitable volume, accommodation of fan failures, and possible crew uses that impact ventilation and acoustic performance. Each CQ required 13% of its total volume and approximately 6% of its total mass to reduce acoustic noise. This paper illustrates the types of model analysis, assumptions, vehicle interactions, and trade-offs required for CQ ventilation and acoustics. Additionally, on-orbit ventilation system performance and initial crew feedback is presented. This approach is applicable to any private enclosed space that the crew will occupy.

  10. 46 CFR 194.15-5 - Ventilation.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ....15-5 Ventilation. (a) Operations, reactions or experiments which produce toxic, noxious or corrosive...) Ventilation of air conditioning systems serving the chemical laboratory shall be designed so that air cannot...

  11. Ventilation rate in adults with a tracheal tube during cardiopulmonary resuscitation: A systematic review.

    PubMed

    Vissers, Gino; Soar, Jasmeet; Monsieurs, Koenraad G

    2017-10-01

    The optimal ventilation rate during cardiopulmonary resuscitation (CPR) with a tracheal tube is unknown. We evaluated whether in adults with cardiac arrest and a secure airway (tracheal tube), a ventilation rate of 10min -1 , compared to any other rate during CPR, improves outcomes. A systematic review up to 14 July 2016. We included both adult human and animal studies. A GRADE (Grades of Recommendation, Assessment, Development and Evaluation) approach was used to evaluate the quality of evidence for each outcome. We identified one human observational study with 67 patients and ten animal studies (234 pigs and 30 dogs). All studies carried a high risk of bias. All studies evaluated for return of spontaneous circulation (ROSC). Studies showed no improvement in ROSC with a ventilation rate of 10 min-1 compared to any other rate. The evidence for longer-term outcomes such as survival to discharge and survival with favourable neurological outcome was very limited. A ventilation rate recommendation of 10 min-1 during adult CPR with a tracheal tube and no pauses for chest compression is a very weak recommendation based on very low quality evidence. Copyright © 2017 Elsevier B.V. All rights reserved.

  12. VENTILATION TECHNOLOGY SYSTEMS ANALYSIS

    EPA Science Inventory

    The report gives results of a project to develop a systems analysis of ventilation technology and provide a state-of-the-art assessment of ventilation and indoor air quality (IAQ) research needs. (NOTE: Ventilation technology is defined as the hardware necessary to bring outdoor ...

  13. Control systems for heating, ventilating, and air conditioning

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Haines, R.W.

    1977-01-01

    Hundreds of ideas for designing and controlling sophisticated heating, ventilating and air conditioning (HVAC) systems are presented. Information is included on enthalpy control, energy conservation in HVAC systems, on solar heating, cooling and refrigeration systems, and on a self-draining water collector and heater. Computerized control systems and the economics of supervisory systems are discussed. Information is presented on computer system components, software, relevant terminology, and computerized security and fire reporting systems. Benefits of computer systems are explained, along with optimization techniques, data management, maintenance schedules, and energy consumption. A bibliography, glossaries of HVAC terminology, abbreviations, symbols, and a subject indexmore » are provided. (LCL)« less

  14. Liquid ventilation.

    PubMed

    Sarkar, Suman; Paswan, Anil; Prakas, S

    2014-01-01

    Human have lungs to breathe air and they have no gills to breath liquids like fish. When the surface tension at the air-liquid interface of the lung increases as in acute lung injury, scientists started to think about filling the lung with fluid instead of air to reduce the surface tension and facilitate ventilation. Liquid ventilation (LV) is a technique of mechanical ventilation in which the lungs are insufflated with an oxygenated perfluorochemical liquid rather than an oxygen-containing gas mixture. The use of perfluorochemicals, rather than nitrogen as the inert carrier of oxygen and carbon dioxide offers a number of advantages for the treatment of acute lung injury. In addition, there are non-respiratory applications with expanding potential including pulmonary drug delivery and radiographic imaging. It is well-known that respiratory diseases are one of the most common causes of morbidity and mortality in intensive care unit. During the past few years several new modalities of treatment have been introduced. One of them and probably the most fascinating, is of LV. Partial LV, on which much of the existing research has concentrated, requires partial filling of lungs with perfluorocarbons (PFC's) and ventilation with gas tidal volumes using conventional mechanical ventilators. Various physico-chemical properties of PFC's make them the ideal media. It results in a dramatic improvement in lung compliance and oxygenation and decline in mean airway pressure and oxygen requirements. No long-term side-effect reported.

  15. Quantifying the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building.

    PubMed

    Tong, Zheming; Chen, Yujiao; Malkawi, Ali; Adamkiewicz, Gary; Spengler, John D

    2016-01-01

    Improper natural ventilation practices may deteriorate indoor air quality when in close proximity to roadways, although the intention is often to reduce energy consumption. In this study, we employed a CFD-based air quality model to quantify the impact of traffic-related air pollution on the indoor air quality of a naturally ventilated building. Our study found that the building envelope restricts dispersion and dilution of particulate matter. The indoor concentration in the baseline condition located 10m away from the roadway is roughly 16-21% greater than that at the edge of the roadway. The indoor flow recirculation creates a well-mixed zone with little variation in fine particle concentration (i.e., 253nm). For ultrafine particles (<100nm), a noticeable decrease in particle concentrations indoors with increasing distance from the road is observed due to Brownian and turbulent diffusion. In addition, the indoor concentration strongly depends on the distance between the roadway and building, particle size, wind condition, and window size and location. A break-even point is observed at D'~2.1 (normalized distance from the roadway by the width of the road). The indoor particle concentration is greater than that at the highway where D'<2.1, and vice versa. For new building planning, the distance from the roadway and the ambient wind condition need to be considered at the early design stage whereas the size and location of the window openings, the interior layout, and the placement of fresh air intakes are important to the indoor air quality of existing buildings adjacent to roadways. Copyright © 2016 Elsevier Ltd. All rights reserved.

  16. Formaldehyde and acetaldehyde exposure mitigation in US residences: In-home measurements of ventilation control and source control

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Hult, Erin L.; Willem, Henry; Price, Phillip N.

    2014-10-01

    Measurements were taken in new US residences to assess the extent to which ventilation and source control can mitigate formaldehyde exposure. Increasing ventilation consistently lowered indoor formaldehyde concentrations. However, at a reference air exchange rate of 0.35 h -1, increasing ventilation was up to 60% less effective than would be predicted if the emission rate were constant. This is consistent with formaldehyde emission rates decreasing as air concentrations increase, as observed in chamber studies. In contrast, measurements suggest acetaldehyde emission was independent of ventilation rate. To evaluate the effectiveness of source control, formaldehyde concentrations were measured in Leadership in Energymore » and Environmental Design (LEED) certified/Indoor airPLUS homes constructed with materials certified to have low emission rates of volatile organic compounds (VOC). At a reference air exchange rate of 0.35 h -1, and adjusting for home age, temperature and relative humidity, formaldehyde concentrations in homes built with low-VOC materials were 42% lower on average than in reference new homes with conventional building materials. Without adjustment, concentrations were 27% lower in the low-VOC homes. The mean and standard deviation of formaldehyde concentration were 33 μg m-3 and 22 μg m -3 for low-VOC homes and 45 μg m -3 and 30 μg m -3 for conventional.« less

  17. Building America Case Study: Sealed Crawl Spaces with Integrated Whole-House Ventilation in a Cold Climate, Ithaca, New York

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    "9One method of code-compliance for crawlspaces is to seal and insulate the crawlspace, rather than venting to the outdoors. However, codes require mechanical ventilation; either via conditioned supply air from the HVAC system, or a continuous exhaust ventilation strategy. As the CARB's building partner, Ithaca Neighborhood Housing Services, intended to use the unvented crawlspace in a recent development, CARB was interested in investigating a hybrid ventilation method that includes the exhaust air from the crawlspace as a portion of an ASHRAE 62.2 compliant whole-house ventilation strategy. This hybrid ventilation method was evaluated through a series of long-term monitoring tests thatmore » observed temperature, humidity, and pressure conditions through the home and crawlspace. Additionally, CARB worked with NREL to perform multi-point tracer gas testing on six separate ventilation strategies - varying portions of 62.2 required flow supplied by the crawlspace fan and an upstairs bathroom fan. The intent of the tracer gas testing was to identify effective Reciprocal Age of Air (RAoA), which is equivalent to the air change rate in well-mixed zones, for each strategy while characterizing localized infiltration rates in several areas of the home.« less

  18. Selective permeation of moisture and VOCs through polymer membranes used in total heat exchangers for indoor air ventilation.

    PubMed

    Zhang, L-Z; Zhang, X-R; Miao, Q-Z; Pei, L-X

    2012-08-01

    Fresh air ventilation is central to indoor environmental control. Total heat exchangers can be key equipment for energy conservation in ventilation. Membranes have been used for total heat exchangers for more than a decade. Much effort has been spent to achieve water vapor permeability of various membranes; however, relatively little attention has been paid to the selectivity of moisture compared with volatile organic compounds (VOCs) through such membranes. In this investigation, the most commonly used membranes, both hydrophilic and hydrophobic ones, are tested for their permeability for moisture and five VOCs (acetic acid, formaldehyde, acetaldehyde, toluene, and ethane). The selectivity of moisture vs. VOCs in these membranes is then evaluated. With a solution-diffusion model, the solubility and diffusivity of moisture and VOCs in these membranes are calculated. The resulting data could provide some reference for future material selection. Total heat exchangers are important equipment for fresh air ventilation with energy conservation. However, their implications for indoor air quality in terms of volatile organic compound permeation have not been known. The data in this article help us to clarify the impacts on indoor VOC levels of membrane-based heat exchangers. Guidelines for material selection can be obtained for future use total heat exchangers for building ventilation. © 2011 John Wiley & Sons A/S.

  19. Metronome improves compression and ventilation rates during CPR on a manikin in a randomized trial.

    PubMed

    Kern, Karl B; Stickney, Ronald E; Gallison, Leanne; Smith, Robert E

    2010-02-01

    We hypothesized that a unique tock and voice metronome could prevent both suboptimal chest compression rates and hyperventilation. A prospective, randomized, parallel design study involving 34 pairs of paid firefighter/emergency medical technicians (EMTs) performing two-rescuer CPR using a Laerdal SkillReporter Resusci Anne manikin with and without metronome guidance was performed. Each CPR session consisted of 2 min of 30:2 CPR with an unsecured airway, then 4 min of CPR with a secured airway (continuous compressions at 100 min(-1) with 8-10 ventilations/min), repeated after the rescuers switched roles. The metronome provided "tock" prompts for compressions, transition prompts between compressions and ventilations, and a spoken "ventilate" prompt. During CPR with a bag/valve/mask the target compression rate of 90-110 min(-1) was achieved in 5/34 CPR sessions (15%) for the control group and 34/34 sessions (100%) for the metronome group (p<0.001). An excessive ventilation rate was not observed in either the metronome or control group during CPR with a bag/valve/mask. During CPR with a bag/endotracheal tube, the target of both a compression rate of 90-110 min(-1) and a ventilation rate of 8-11 min(-1) was achieved in 3/34 CPR sessions (9%) for the control group and 33/34 sessions (97%) for the metronome group (p<0.001). Metronome use with the secured airway scenario significantly decreased the incidence of over-ventilation (11/34 EMT pairs vs. 0/34 EMT pairs; p<0.001). A unique combination tock and voice prompting metronome was effective at directing correct chest compression and ventilation rates both before and after intubation. Copyright 2009 Elsevier Ireland Ltd. All rights reserved.

  20. The Maintenance of Heating, Ventilating and Air-Conditioning Systems and Indoor Air Quality in Schools: A Guide for School Facility Managers. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.

    To help maintain good indoor air quality (IAQ) in schools, guidance for the development and implementation of an effective program for maintenance and operation of heating, ventilating, and air-conditioning (HVAC) systems are discussed. Frequently, a building's occupants will complain about IAQ when the temperature or humidity are at uncomfortable…

  1. Fuselage ventilation due to wind flow about a postcrash aircraft

    NASA Technical Reports Server (NTRS)

    Stuart, J. W.

    1980-01-01

    Postcrash aircraft fuselage fire development, dependent on the internal and external fluid dynamics is discussed. The natural ventilation rate, a major factor in the internal flow patterns and fire development is reviewed. The flow about the fuselage as affected by the wind and external fire is studied. An analysis was performend which estimated the rates of ventilation produced by the wind for a limited idealized environmental configuration. The simulation utilizes the empirical pressure coefficient distribution of an infinite circular cylinder near a wall with its boundary later flow to represent the atmospheric boundary layer. The resulting maximum ventilation rate for two door size openings, with varying circumferential location in a common 10 mph wind was an order of magnitude greater than the forced ventilation specified in full scale fire testing. The parameter discussed are: (1) fuselage size and shape, (2) fuselage orientation and proximity to the ground, (3) fuselage-openings size and location, (4) wind speed and direction, and (5) induced flow of the external fire plume is recommended. The fire testing should be conducted to a maximum ventilation rate at least an order of magnitude greater than the inflight air conditioning rates.

  2. International Space Station USOS Crew Quarters Ventilation and Acoustic Design Implementation

    NASA Technical Reports Server (NTRS)

    Broyan, James Lee, Jr.

    2009-01-01

    The International Space Station (ISS) United States Operational Segment (USOS) has four permanent rack sized ISS Crew Quarters (CQ) providing a private crewmember space. The CQ uses Node 2 cabin air for ventilation/thermal cooling, as opposed to conditioned ducted air from the ISS Temperature Humidity Control System or the ISS fluid cooling loop connections. Consequently, CQ can only increase the air flow rate to reduce the temperature delta between the cabin and the CQ interior. However, increasing airflow causes increased acoustic noise so efficient airflow distribution is an important design parameter. The CQ utilized a two fan push-pull configuration to ensure fresh air at the crewmember s head position and reduce acoustic exposure. The CQ interior needs to be below Noise Curve 40 (NC-40). The CQ ventilation ducts are open to the significantly louder Node 2 cabin aisle way which required significantly acoustic mitigation controls. The design implementation of the CQ ventilation system and acoustic mitigation are very inter-related and require consideration of crew comfort balanced with use of interior habitable volume, accommodation of fan failures, and possible crew uses that impact ventilation and acoustic performance. This paper illustrates the types of model analysis, assumptions, vehicle interactions, and trade-offs required for CQ ventilation and acoustics. Additionally, on-orbit ventilation system performance and initial crew feedback is presented. This approach is applicable to any private enclosed space that the crew will occupy.

  3. WASTE HANDLING BUILDING VENTILATION SYSTEM DESCRIPTION DOCUMENT

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    P.A. Kumar

    2000-06-21

    The Waste Handling Building Ventilation System provides heating, ventilation, and air conditioning (HVAC) for the contaminated, potentially contaminated, and uncontaminated areas of the Monitored Geologic Repository's (MGR) Waste Handling Building (WHB). In the uncontaminated areas, the non-confinement area ventilation system maintains the proper environmental conditions for equipment operation and personnel comfort. In the contaminated and potentially contaminated areas, in addition to maintaining the proper environmental conditions for equipment operation and personnel comfort, the contamination confinement area ventilation system directs potentially contaminated air away from personnel in the WHB and confines the contamination within high-efficiency particulate air (HEPA) filtration units. Themore » contamination confinement areas ventilation system creates airflow paths and pressure zones to minimize the potential for spreading contamination within the building. The contamination confinement ventilation system also protects the environment and the public by limiting airborne releases of radioactive or other hazardous contaminants from the WHB. The Waste Handling Building Ventilation System is designed to perform its safety functions under accident conditions and other Design Basis Events (DBEs) (such as earthquakes, tornadoes, fires, and loss of the primary electric power). Additional system design features (such as compartmentalization with independent subsystems) limit the potential for cross-contamination within the WHB. The system provides status of important system parameters and equipment operation, and provides audible and/or visual indication of off-normal conditions and equipment failures. The Waste Handling Building Ventilation System confines the radioactive and hazardous material within the building such that the release rates comply with regulatory limits. The system design, operations, and maintenance activities incorporate ALARA (as low as is

  4. Metabolically-Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates (External Review Draft)

    EPA Science Inventory

    EPA has released a draft report entitled, Metabolically-Derived Human Ventilation Rates: A Revised Approach Based Upon Oxygen Consumption Rates, for independent external peer review and public comment. NCEA published the Exposure Factors Handbook in 1997. This comprehens...

  5. THE EFFECT OF VENTILATION ON EMISSION RATES OF WOOD FINISHING MATERIALS

    EPA Science Inventory

    The rate of emission of organic compounds from building materials varies according to: type of material, material loading (area of material/volume of room), compound emitted, temperature, humidity, and ventilation rate. For some compounds and materials (e.g., formaldehyde from pa...

  6. Air Trapping on Chest CT Is Associated with Worse Ventilation Distribution in Infants with Cystic Fibrosis Diagnosed following Newborn Screening

    PubMed Central

    Hall, Graham L.; Logie, Karla M.; Parsons, Faith; Schulzke, Sven M.; Nolan, Gary; Murray, Conor; Ranganathan, Sarath; Robinson, Phil; Sly, Peter D.; Stick, Stephen M.

    2011-01-01

    Background In school-aged children with cystic fibrosis (CF) structural lung damage assessed using chest CT is associated with abnormal ventilation distribution. The primary objective of this analysis was to determine the relationships between ventilation distribution outcomes and the presence and extent of structural damage as assessed by chest CT in infants and young children with CF. Methods Data of infants and young children with CF diagnosed following newborn screening consecutively reviewed between August 2005 and December 2009 were analysed. Ventilation distribution (lung clearance index and the first and second moment ratios [LCI, M1/M0 and M2/M0, respectively]), chest CT and airway pathology from bronchoalveolar lavage were determined at diagnosis and then annually. The chest CT scans were evaluated for the presence or absence of bronchiectasis and air trapping. Results Matched lung function, chest CT and pathology outcomes were available in 49 infants (31 male) with bronchiectasis and air trapping present in 13 (27%) and 24 (49%) infants, respectively. The presence of bronchiectasis or air trapping was associated with increased M2/M0 but not LCI or M1/M0. There was a weak, but statistically significant association between the extent of air trapping and all ventilation distribution outcomes. Conclusion These findings suggest that in early CF lung disease there are weak associations between ventilation distribution and lung damage from chest CT. These finding are in contrast to those reported in older children. These findings suggest that assessments of LCI could not be used to replace a chest CT scan for the assessment of structural lung disease in the first two years of life. Further research in which both MBW and chest CT outcomes are obtained is required to assess the role of ventilation distribution in tracking the progression of lung damage in infants with CF. PMID:21886842

  7. Development and Evaluation of a New Air Exchange Rate Algorithm for the Stochastic Human Exposure and Dose Simulation Model

    EPA Science Inventory

    between-home and between-city variability in residential pollutant infiltration. This is likely a result of differences in home ventilation, or air exchange rates (AER). The Stochastic Human Exposure and Dose Simulation (SHEDS) model is a population exposure model that uses a pro...

  8. 14 CFR 125.117 - Ventilation.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 14 Aeronautics and Space 3 2010-01-01 2010-01-01 false Ventilation. 125.117 Section 125.117 Aeronautics and Space FEDERAL AVIATION ADMINISTRATION, DEPARTMENT OF TRANSPORTATION (CONTINUED) AIR CARRIERS....117 Ventilation. Each passenger or crew compartment must be suitably ventilated. Carbon monoxide...

  9. Respirator triggering of electron-beam computed tomography (EBCT): differences in dynamic changes between augmented ventilation and controlled mechanical ventilation

    NASA Astrophysics Data System (ADS)

    Recheis, Wolfgang A.; Kleinsasser, Axel; Schuster, Antonius H.; Loeckinger, Alexander; Frede, Thomas; Springer, Peter; Hoermann, Christoph; zur Nedden, Dieter

    2000-04-01

    The purpose was to evaluate differences in dynamic changes of the lung aeration (air-tissue ratio) between augmented modes of ventilation (AMV) and controlled mechanical ventilation (CMV) in normal subjects. 4 volunteers, ventilated with the different respirator protocols via face mask, were scanned using the EBCT in the 50 ms mode. A software analyzed the respirator's digitized pressure and volume signals of two subsequent ventilation phases. Using these values it was possible to calculate the onset of inspiration or expiration of the next respiratory phase. The calculated starting point was then used to trigger the EBCT. The dynamic changes of air- tissue ratios were evaluated in three separate regions: a ventral, an intermediate and a dorsal area. AMV results in increase of air-tissue ratio in the dorsal lung area due to the active contraction of the diaphragm, whereas CMV results in a more pronounced increase in air-tissue ratio of the ventral lung area. This study gives further insight into the dynamic changes of the lung's biomechanics by comparing augmented ventilation and controlled mechanical ventilation in the healthy proband.

  10. Natural ventilation without air breathing in the top openings of highway tunnels

    NASA Astrophysics Data System (ADS)

    Jin, Sike; Jin, Jiali; Gong, Yanfeng

    2017-05-01

    A number of urban shallow-buried highway tunnels have been built in China. Despite much better internal air quality compared to the traditional tunnels, there is no sufficient theoretical ground or experimental support for the construction of such tunnels. Most researchers hold that natural ventilation in such tunnels depends on air breathing in the top openings, but some others are skeptical about this conclusion. By flow visualization technology on a tunnel experiment platform, we tested the characteristics of airflow in the top openings of highway tunnels. The results showed that air always flowed from outside to inside in all top openings above a continuous traffic stream, and the openings did not breathe at all. In addition, intake air in the top openings reached its maximum velocity at the tunnel entrance, and then gradually slowed down with tunnel depth increasing.

  11. Integrated analysis of numerical weather prediction and computational fluid dynamics for estimating cross-ventilation effects on inhaled air quality inside a factory

    NASA Astrophysics Data System (ADS)

    Murga, Alicia; Sano, Yusuke; Kawamoto, Yoichi; Ito, Kazuhide

    2017-10-01

    Mechanical and passive ventilation strategies directly impact indoor air quality. Passive ventilation has recently become widespread owing to its ability to reduce energy demand in buildings, such as the case of natural or cross ventilation. To understand the effect of natural ventilation on indoor environmental quality, outdoor-indoor flow paths need to be analyzed as functions of urban atmospheric conditions, topology of the built environment, and indoor conditions. Wind-driven natural ventilation (e.g., cross ventilation) can be calculated through the wind pressure coefficient distributions of outdoor wall surfaces and openings of a building, allowing the study of indoor air parameters and airborne contaminant concentrations. Variations in outside parameters will directly impact indoor air quality and residents' health. Numerical modeling can contribute to comprehend these various parameters because it allows full control of boundary conditions and sampling points. In this study, numerical weather prediction modeling was used to calculate wind profiles/distributions at the atmospheric scale, and computational fluid dynamics was used to model detailed urban and indoor flows, which were then integrated into a dynamic downscaling analysis to predict specific urban wind parameters from the atmospheric to built-environment scale. Wind velocity and contaminant concentration distributions inside a factory building were analyzed to assess the quality of the human working environment by using a computer simulated person. The impact of cross ventilation flows and its variations on local average contaminant concentration around a factory worker, and inhaled contaminant dose, were then discussed.

  12. On the calculation of air flow rates to ventilate closed-type stations in subway with the double-track tunnel

    NASA Astrophysics Data System (ADS)

    Kiyanitsa, LA

    2018-03-01

    Metro is not only the most promising kind of public transport but also an important part of infrastructure in a modern city. As a place where large groups of people gather, subway is to ensure the required air exchange at the passenger platforms of the stations. The air flow rate for airing the stations is also determined based on the required temperature, humidity and MAC of gases. The present study estimates the required air flow rate at the passenger platform of the closed-type subway station with the double-track tunnel given the standard air temperature, humidity and gas concentration, as well as based on the condition of the specified air flow feed and air changes per hour. The article proposes the scheme of air recirculation from the double-track tunnel to the station.

  13. The correlation of Acanthamoeba from the ventilation system with other environmental parameters in commercial buildings as possible indicator for indoor air quality.

    PubMed

    Ooi, Soo Shen; Mak, Joon Wah; Chen, Donald K F; Ambu, Stephen

    2017-02-07

    The free-living protozoan Acanthamoeba is an opportunistic pathogen that is ubiquitous in our environment. However, its role in affecting indoor air quality and ill-health of indoor occupants is relatively unknown. The present study investigated the presence of Acanthamoeba from the ventilation system and its correlation with other indoor air quality parameters, used in the industry code of practice and its potential as an indicator for indoor air quality. Indoor air quality assessments were carried out in nine commercial buildings with approval from the building management, and the parameters assessed were as recommended by the Department of Occupational Safety and Health. The presence of Acanthamoeba was determined through dust swabs from the ventilation system and indoor furniture. Logistic regression was performed to study the correlation between assessed parameters and occupants' complaints. A total of 107 sampling points were assessed and 40.2% of the supplying air diffuser and blowing fan and 15% of the furniture were positive for cysts. There was a significant correlation between Acanthamoeba detected from the ventilation system with ambient total fungus count (r=0.327; p=0.01) and respirable particulates (r=0.276; p=0.01). Occupants' sick building syndrome experience also correlated with the presence of Acanthamoeba in the ventilation system (r=0.361; p=0.01) and those detected on the furniture (r=0.290; p=0.01). Logistic regression showed that there was a five-fold probability of sick building syndrome among occupants when Acanthamoeba was detected in the ventilation system.

  14. The correlation of Acanthamoeba from the ventilation system with other environmental parameters in commercial buildings as possible indicator for indoor air quality

    PubMed Central

    OOI, Soo Shen; MAK, Joon Wah; CHEN, Donald K.F.; AMBU, Stephen

    2016-01-01

    The free-living protozoan Acanthamoeba is an opportunistic pathogen that is ubiquitous in our environment. However, its role in affecting indoor air quality and ill-health of indoor occupants is relatively unknown. The present study investigated the presence of Acanthamoeba from the ventilation system and its correlation with other indoor air quality parameters, used in the industry code of practice and its potential as an indicator for indoor air quality. Indoor air quality assessments were carried out in nine commercial buildings with approval from the building management, and the parameters assessed were as recommended by the Department of Occupational Safety and Health. The presence of Acanthamoeba was determined through dust swabs from the ventilation system and indoor furniture. Logistic regression was performed to study the correlation between assessed parameters and occupants’ complaints. A total of 107 sampling points were assessed and 40.2% of the supplying air diffuser and blowing fan and 15% of the furniture were positive for cysts. There was a significant correlation between Acanthamoeba detected from the ventilation system with ambient total fungus count (r=0.327; p=0.01) and respirable particulates (r=0.276; p=0.01). Occupants’ sick building syndrome experience also correlated with the presence of Acanthamoeba in the ventilation system (r=0.361; p=0.01) and those detected on the furniture (r=0.290; p=0.01). Logistic regression showed that there was a five-fold probability of sick building syndrome among occupants when Acanthamoeba was detected in the ventilation system. PMID:27476379

  15. CFD Simulations to Improve Ventilation in Low-Income Housing

    NASA Astrophysics Data System (ADS)

    Ho, Rosemond; Gorle, Catherine

    2017-11-01

    Quality of housing plays an important role in public health. In Dhaka, Bangladesh, the leading causes of death include tuberculosis, lower respiratory infections, and chronic obstructive pulmonary disease, so improving home ventilation could potentially mitigate these negative health effects. The goal of this project is to use computational fluid dynamics (CFD) to predict the relative effectiveness of different ventilation strategies for Dhaka homes. A Reynolds-averaged Navier-Stokes CFD model of a standard Dhaka home with apertures of different sizes and locations was developed to predict air exchange rates. Our initial focus is on simulating ventilation driven by buoyancy-alone conditions, which is often considered the limiting case in natural ventilation design. We explore the relationship between ventilation rate and aperture area to determine the most promising configurations for optimal ventilation solutions. Future research will include the modeling of wind-driven conditions, and extensive uncertainty quantification studies to investigate the effect of variability in the layout of homes and neighborhoods, and in local wind and temperature conditions. The ultimate objective is to formulate robust design recommendations that can reduce risks of respiratory illness in low-income housing.

  16. Effectiveness of photocatalytic filter for removing volatile organic compounds in the heating, ventilation, and air conditioning system.

    PubMed

    Yu, Kuo-Pin; Lee, Grace Whei-May; Huang, Wei-Ming; Wu, Chih-Cheng; Lou, Chia-ling; Yang, Shinhao

    2006-05-01

    Nowadays, the heating, ventilation, and air conditioning (HVAC) system has been an important facility for maintaining indoor air quality. However, the primary function of typical HVAC systems is to control the temperature and humidity of the supply air. Most indoor air pollutants, such as volatile organic compounds (VOCs), cannot be removed by typical HVAC systems. Thus, some air handling units for removing VOCs should be added in typical HVAC systems. Among all of the air cleaning techniques used to remove indoor VOCs, photocatalytic oxidation is an attractive alternative technique for indoor air purification and deodorization. The objective of this research is to investigate the VOC removal efficiency of the photocatalytic filter in a HVAC system. Toluene and formaldehyde were chosen as the target pollutants. The experiments were conducted in a stainless steel chamber equipped with a simplified HVAC system. A mechanical filter coated with Degussa P25 titania photocatalyst and two commercial photocatalytic filters were used as the photocatalytic filters in this simplified HVAC system. The total air change rates were controlled at 0.5, 0.75, 1, 1.25, and 1.5 hr(-1), and the relative humidity (RH) was controlled at 30%, 50%, and 70%. The ultraviolet lamp used was a 4-W, ultraviolet-C (central wavelength at 254 nm) strip light bulb. The first-order decay constant of toluene and formaldehyde found in this study ranged from 0.381 to 1.01 hr(-1) under different total air change rates, from 0.34 to 0.433 hr(-1) under different RH, and from 0.381 to 0.433 hr(-1) for different photocatalytic filters.

  17. Development and Evaluation of a New Air Exchange Rate Algorithm for the Stochastic Human Exposure and Dose Simulation Model (ISES Presentation)

    EPA Science Inventory

    Previous exposure assessment panel studies have observed considerable seasonal, between-home and between-city variability in residential pollutant infiltration. This is likely a result of differences in home ventilation, or air exchange rates (AER). The Stochastic Human Exposure ...

  18. Household ventilation may reduce effects of indoor air pollutants for prevention of lung cancer: a case-control study in a Chinese population.

    PubMed

    Jin, Zi-Yi; Wu, Ming; Han, Ren-Qiang; Zhang, Xiao-Feng; Wang, Xu-Shan; Liu, Ai-Ming; Zhou, Jin-Yi; Lu, Qing-Yi; Kim, Claire H; Mu, Lina; Zhang, Zuo-Feng; Zhao, Jin-Kou

    2014-01-01

    Although the International Agency for Research on Cancer (IARC) has classified various indoor air pollutants as carcinogenic to humans, few studies evaluated the role of household ventilation in reducing the impact of indoor air pollutants on lung cancer risk. To explore the association between household ventilation and lung cancer. A population-based case-control study was conducted in a Chinese population from 2003 to 2010. Epidemiologic and household ventilation data were collected using a standardized questionnaire. Unconditional logistic regression was employed to estimate adjusted odds ratios (ORadj) and their 95% confidence intervals (CI). Among 1,424 lung cancer cases and 4,543 healthy controls, inverse associations were observed for good ventilation in the kitchen (ORadj = 0.86, 95% CI: 0.75, 0.98), bedroom (ORadj = 0.90, 95% CI: 0.79, 1.03), and both kitchen and bedroom (ORadj = 0.87, 95% CI: 0.75, 1.00). Stratified analyses showed lung cancer inversely associated with good ventilation among active smokers (ORadj = 0.85, 95% CI: 0.72, 1.00), secondhand smokers at home (ORadj = 0.77, 95% CI: 0.63, 0.94), and those exposed to high-temperature cooking oil fumes (ORadj = 0.82, 95% CI: 0.68, 0.99). Additive interactions were found between household ventilation and secondhand smoke at home as well as number of household pollutant sources. A protective association was observed between good ventilation of households and lung cancer, most likely through the reduction of exposure to indoor air pollutants, indicating ventilation may serve as one of the preventive measures for lung cancer, in addition to tobacco cessation.

  19. Quantitative relationship of sick building syndrome symptoms with ventilation rates

    EPA Science Inventory

    Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence in office workers with ventilation rate. For each study, slopes were calculated, representing the fractional...

  20. CFD and ventilation research.

    PubMed

    Li, Y; Nielsen, P V

    2011-12-01

    There has been a rapid growth of scientific literature on the application of computational fluid dynamics (CFD) in the research of ventilation and indoor air science. With a 1000-10,000 times increase in computer hardware capability in the past 20 years, CFD has become an integral part of scientific research and engineering development of complex air distribution and ventilation systems in buildings. This review discusses the major and specific challenges of CFD in terms of turbulence modelling, numerical approximation, and boundary conditions relevant to building ventilation. We emphasize the growing need for CFD verification and validation, suggest ongoing needs for analytical and experimental methods to support the numerical solutions, and discuss the growing capacity of CFD in opening up new research areas. We suggest that CFD has not become a replacement for experiment and theoretical analysis in ventilation research, rather it has become an increasingly important partner. We believe that an effective scientific approach for ventilation studies is still to combine experiments, theory, and CFD. We argue that CFD verification and validation are becoming more crucial than ever as more complex ventilation problems are solved. It is anticipated that ventilation problems at the city scale will be tackled by CFD in the next 10 years. © 2011 John Wiley & Sons A/S.

  1. Ventilation in homes infested by house-dust mites.

    PubMed

    Sundell, J; Wickman, M; Pershagen, G; Nordvall, S L

    1995-02-01

    Thirty single-family homes with either high (> or = 2000 ng/g) or low (< or = 1000 ng/g) house-dust mite (HDM) allergen levels in mattress dust were examined for ventilation, thermal climate, and air quality (formaldehyde and total volatile organic compounds (TVOC). Elevated concentrations of HDM allergen in mattress and floor dust were associated with the difference in absolute humidity between indoor and outdoor air, as well as with low air-change rates of the home, particularly the bedroom. No correlation was found between concentration of TVOC or formaldehyde in bedroom air and HDM allergen concentration. In regions with a cold winter climate, the air-change rate of the home and the infiltration of outdoor air into the bedroom appear to be important for the infestation of HDM.

  2. Capability of air filters to retain airborne bacteria and molds in heating, ventilating and air-conditioning (HVAC) systems.

    PubMed

    Möritz, M; Peters, H; Nipko, B; Rüden, H

    2001-07-01

    The capability of air filters (filterclass: F6, F7) to retain airborne outdoor microorganisms was examined in field experiments in two heating, ventilating and air conditioning (HVAC) systems. At the beginning of the 15-month investigation period, the first filter stages of both HVAC systems were equipped with new unused air filters. The number of airborne bacteria and molds before and behind the filters were determined simultaneously in 14 days-intervals using 6-stage Andersen cascade impactors. Under relatively dry (< 80% R. H.) and warm (> 12 degrees C) outdoor air conditions air filters led to a marked reduction of airborne microorganism concentrations (bacteria by approximately 70% and molds by > 80%). However, during long periods of high relative humidity (> 80% R. H.) a proliferation of bacteria on air filters with subsequent release into the filtered air occurred. These microorganisms were mainly smaller than 1.1 microns therefore being part of the respirable fraction. The results showed furthermore that one possibility to avoid microbial proliferation is to limit the relative humidity in the area of the air filters to 80% R. H. (mean of 3 days), e.g. by using preheaters in front of air filters in HVAC-systems.

  3. Effect Of Ventilation On Chronic Health Risks In Schools And Offices

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Parthasarathy, Srinandini; Fisk, William J.; McKone, Thomas E.

    This study provides a risk assessment for chronic health risks from inhalation exposure to indoor air pollutants in offices and schools with a focus how ventilation impacts exposures to, and risks from, volatile organic compounds (VOCs) and particulate matter (PM2.5). We estimate how much health risks could change with varying ventilation rates under two scenarios: (i) halving the measured ventilation rates and (ii) doubling the measured ventilation rates. For the hazard characterization we draw upon prior papers that identified pollutants potentially affecting health with indoor air concentrations responsive to changes in ventilation rates. For exposure assessment we determine representative concentrationsmore » of pollutants using data available in current literature and model changes in exposures with changes in ventilation rates. As a metric of disease burden, we use disability adjusted life years (DALYs) to address both cancer and non-cancer effects. We also compare exposures to guidelines published by regulatory agencies to assess chronic health risks. Chronic health risks are driven primarily by particulate matter exposure, with an estimated baseline disease burden of 150 DALYs per 100,000 people in offices and 140 DALYs per 100,000 people in schools. Study results show that PM2.5-related DALYs are not very sensitive to changes in ventilation rates. Filtration is more effective at controlling PM2.5 concentrations and health effects. Non-cancer health effects contribute only a small fraction of the overall chronic health burden of populations in offices and schools (<1 DALY per 100,000 people). Cancer health effects dominate the disease burden in schools (3 DALYs per 100,000) and offices (5 DALYs per 100,000), with formaldehyde being the primary risk driver. In spite of large uncertainties in toxicological data and dose-response modeling, our results support the finding that ventilation rate changes do not have significant impacts on estimated chronic

  4. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Instructor Edition. Introduction to Construction Series.

    ERIC Educational Resources Information Center

    Oklahoma State Dept. of Vocational and Technical Education, Stillwater. Curriculum and Instructional Materials Center.

    This instructor's guide contains the materials required to teach a competency-based introductory course in heating, ventilating, and air conditioning (HVAC) to students who have chosen to explore careers in construction. It contains three units: HVAC materials, HVAC tools, and applied skills. Each instructional unit includes some or all of the…

  5. Ultrafine particle removal by residential heating, ventilating, and air-conditioning filters.

    PubMed

    Stephens, B; Siegel, J A

    2013-12-01

    This work uses an in situ filter test method to measure the size-resolved removal efficiency of indoor-generated ultrafine particles (approximately 7-100 nm) for six new commercially available filters installed in a recirculating heating, ventilating, and air-conditioning (HVAC) system in an unoccupied test house. The fibrous HVAC filters were previously rated by the manufacturers according to ASHRAE Standard 52.2 and ranged from shallow (2.5 cm) fiberglass panel filters (MERV 4) to deep-bed (12.7 cm) electrostatically charged synthetic media filters (MERV 16). Measured removal efficiency ranged from 0 to 10% for most ultrafine particles (UFP) sizes with the lowest rated filters (MERV 4 and 6) to 60-80% for most UFP sizes with the highest rated filter (MERV 16). The deeper bed filters generally achieved higher removal efficiencies than the panel filters, while maintaining a low pressure drop and higher airflow rate in the operating HVAC system. Assuming constant efficiency, a modeling effort using these measured values for new filters and other inputs from real buildings shows that MERV 13-16 filters could reduce the indoor proportion of outdoor UFPs (in the absence of indoor sources) by as much as a factor of 2-3 in a typical single-family residence relative to the lowest efficiency filters, depending in part on particle size. © 2013 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  6. Indoor air quality and health in two office buildings with different ventilation systems

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Hedge, A.; Sterling, T.D.; Sterling, E.M.

    1989-01-01

    Measurements of indoor air pollutants were taken in (1) an air conditioned and (2) an adjacent, naturally ventilated office of a public sector organization. Self-administered questionnaires on the work environment and health were distributed to all workers. No differences in concentrations of carbon monoxide, carbon dioxide, ozone, and total oxidants were found between buildings. Concentrations of formaldehyde, volatile organic compounds, and respirable particulates were higher in the air conditioned offices. Symptoms of sleepiness, nasal irritation, concentration difficulties, cold/flu-like symptoms, and eye focusing problems were significantly more prevalent in the air conditioned offices. In the air conditioned offices, most symptoms weremore » significantly more prevalent among women than men. Passive smoking was associated with symptom prevalence, but alcohol, tea, and coffee consumption was unrelated. No significant correlations between pollutant concentrations and symptom prevalence were found, however, recalled reports of leaving work early because of feeling ill were significantly correlated with formaldehyde levels in the air conditioned building.« less

  7. Ventilation for an enclosure of a gas turbine and related method

    DOEpatents

    Schroeder, Troy Joseph; Leach, David; O'Toole, Michael Anthony

    2002-01-01

    A ventilation scheme for a rotary machine supported on pedestals within an enclosure having a roof, end walls and side walls with the machine arranged parallel to the side walls, includes ventilation air inlets located in a first end wall of the enclosure; a barrier wall located within the enclosure, proximate the first end wall to thereby create a plenum chamber. The barrier wall is constructed to provide a substantially annular gap between the barrier wall and a casing of the turbine to thereby direct ventilation air axially along the turbine; one or more ventilation air outlets located proximate a second, opposite end wall on the roof of the enclosure. In addition, one or more fans are provided for pulling ventilating air into said plenum chamber via the ventilation air inlets.

  8. Investigation of induced recirculation during planned ventilation system maintenance

    PubMed Central

    Pritchard, C.J.; Scott, D.F.; Noll, J.D.; Voss, B.; Leonis, D.

    2015-01-01

    The Office of Mine Safety and Health Research (OMSHR) investigated ways to increase mine airflow to underground metal/nonmetal (M/NM) mine working areas to improve miners’ health and safety. One of those areas is controlled recirculation. Because the quantity of mine air often cannot be increased, reusing part of the ventilating air can be an effective alternative, if implemented properly, until the capacity of the present system is improved. The additional airflow can be used to provide effective dilution of contaminants and higher flow velocities in the underground mine environment. Most applications of controlled recirculation involve taking a portion of the return air and passing it back into the intake to increase the air volume delivered to the desired work areas. OMSHR investigated a Nevada gold mine where shaft rehabilitation was in progress and one of the two main fans was shut down to allow reduced air velocity for safe shaft work. Underground booster fan operating pressures were kept constant to maintain airflow to work areas, inducing controlled recirculation in one work zone. Investigation into system behavior and the effects of recirculation on the working area during times of reduced primary ventilation system airflow would provide additional information on implementation of controlled recirculation into the system and how these events affect M/NM ventilation systems. The National Institute for Occupational Safety and Health monitored the ventilation district when both main fans were operating and another scenario with one of the units turned off for maintenance. Airflow and contaminants were measured to determine the exposure effects of induced recirculation on miner health. Surveys showed that 19% controlled recirculation created no change in the overall district airflow distribution and a small reduction in district fresh air intake. Total dust levels increased only modestly and respirable dust levels were also low. Diesel particulate matter

  9. Long-distance transport of ventilated patients: advantages and limitations of air medical repatriation on commercial airlines.

    PubMed

    Veldman, Alex; Diefenbach, Michael; Fischer, Doris; Benton, Alida; Bloch, Richard

    2004-01-01

    To illustrate the advantages and limitations of transporting ventilated intensive care unit patients over intercontinental distances on commercial airlines, this case series reports 8 ventilated patients repatriated by an air medical transport company. Eight ventilated patients, 3 suffering from internal and 5 from neurologic diseases. Distances ranged from 1700 to 10280 nautical miles with transport times from 04:10 hours to 21:55 hours. For 3 patients, a dedicated patient transport compartment (PTC) in the aircraft cabin was used. All patients were ventilator-dependent for a minimum of 11 days before transport (48 days median, 113 days maximum). One patient went into cardiac arrest during the flight and died. None of the other patients experienced any emergency or invasive procedures, other than peripheral venous access necessary during the flight. In all patients, ventilation was adjusted with respect to the blood gas analysis at least once during the transport. No technical failures or drop-outs occurred during the flights. None of the flights had to be diverted for technical or medical reasons. Long distance international transport of ventilated intensive care unit patients is an extremely cost intensive and logistically challenging task. In a certain subgroup of relatively stable ventilated patients, transport on commercial airlines offers advantages in terms of cost effectiveness and reduced transport time and acceleration/deceleration trauma as a result of multiple fuel stops.

  10. Use of ventilator associated pneumonia bundle and statistical process control chart to decrease VAP rate in Syria.

    PubMed

    Alsadat, Reem; Al-Bardan, Hussam; Mazloum, Mona N; Shamah, Asem A; Eltayeb, Mohamed F E; Marie, Ali; Dakkak, Abdulrahman; Naes, Ola; Esber, Faten; Betelmal, Ibrahim; Kherallah, Mazen

    2012-10-01

    Implementation of ventilator associated pneumonia (VAP) bundle as a performance improvement project in the critical care units for all mechanically ventilated patients aiming to decrease the VAP rates. VAP bundle was implemented in 4 teaching hospitals after educational sessions and compliance rates along with VAP rates were monitored using statistical process control charts. VAP bundle compliance rates were steadily increasing from 33 to 80% in hospital 1, from 33 to 86% in hospital 2 and from 83 to 100% in hospital 3 during the study period. The VAP bundle was not applied in hospital 4 therefore no data was available. A target level of 95% was reached only in hospital 3. This correlated with a decrease in VAP rates from 30 to 6.4 per 1000 ventilator days in hospital 1, from 12 to 4.9 per 1000 ventilator days in hospital 3, whereas VAP rate failed to decrease in hospital 2 (despite better compliance) and it remained high around 33 per 1000 ventilator days in hospital 4 where VAP bundle was not implemented. VAP bundle has performed differently in different hospitals in our study. Prevention of VAP requires a multidimensional strategy that includes strict infection control interventions, VAP bundle implementation, process and outcome surveillance and education.

  11. Ventilation requirements for control of occupancy odor and tobacco smoke odor: laboratory studies. Final report

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Cain, W.S.; Isseroff, R.; Leaderer, B.P.

    1981-04-01

    Experiments on occupancy odor addressed the question of why required ventilation rate per occupant increased progressively with increases in the number of persons in a space. In order to investigate ventilation requirements under approximately ideal conditions, we constructed an aluminum-lined environmental chamber with excellent control over environmental conditions and a ventilation system that provided rapid and uniform mixing of air. Psychophysical experiments on occupancy odor explored 47 different combinations of occupancy density, temperature and humidity, and ventilation rate. The experiments collected judgements both from visitors, who smelled air from the chamber only once every few minutes, and from occupants, whomore » remained in the chamber for an hour at a time. The judgements of visitors revealed that occupancy odor increased only gradually over time and rarely reached very high or objectionable levels. Judgements of occupants also revealed rather minor dissatisfaction. Only during combinations of high temperature and humidity did objectionability become more than a minor issue to either group. Experiments on cigarette smoking explored rates of 4, 8, and 16 cigarettes per hour under various environmental conditions and with ventilation rates as high as 68 cfm (34 L.s/sup -1/) per occupant. As soon as occupants lit cigarettes in the chamber, the odor level increased dramatically. At ventilation rates far greater than necessary to control occupancy odor, the odor from cigarette smoking remained quite intense. In general, the odor proved impossible to control adequately even with a ventilation rate of 68 cfm (34 L.s/sup -1/) per occupant (4 occupants) and even when only one occupant smoked at a time. As in the case of occupancy odor, a combination of high temperature and humidity exacerbated the odor problem.« less

  12. Vocal Ergonomics in the Workplace: Heating, Ventilation, and Air-Conditioning Method Influences on Vocal Comfort and Function

    ERIC Educational Resources Information Center

    Sandage, Mary J.; Rahn, Keith A.; Smith, Audrey G.

    2017-01-01

    Purpose: The purpose of this study was to examine the influence of the heating, ventilation, and air-conditioning method on voice function following a voicing task using ecologically valid offices, one with radiant HVAC and one with forced air. Method: A total of 12 consented participants (6 women, 6 men) narrated a video in each of 4…

  13. Hygiene guideline for the planning, installation, and operation of ventilation and air-conditioning systems in health-care settings - Guideline of the German Society for Hospital Hygiene (DGKH).

    PubMed

    Külpmann, Rüdiger; Christiansen, Bärbel; Kramer, Axel; Lüderitz, Peter; Pitten, Frank-Albert; Wille, Frank; Zastrow, Klaus-Dieter; Lemm, Friederike; Sommer, Regina; Halabi, Milo

    2016-01-01

    Since the publication of the first "Hospital Hygiene Guideline for the implementation and operation of air conditioning systems (HVAC systems) in hospitals" (http://www.krankenhaushygiene.de/informationen/fachinformationen/leitlinien/12) in 2002, it was necessary due to the increase in knowledge, new regulations, improved air-conditioning systems and advanced test methods to revise the guideline. Based on the description of the basic features of ventilation concepts, its hygienic test and the usage-based requirements for ventilation, the DGKH section "Ventilation and air conditioning technology" attempts to provide answers for the major air quality issues in the planning, design and the hygienically safe operation of HVAC systems in rooms of health care.

  14. Propellant Handler's Ensemble (PHE) Aka Self-Contained Atmospheric Protective Ensemble (SCAPE), Ventilator Improvement Study Project

    NASA Technical Reports Server (NTRS)

    Oliva-Buisson, Yvette J. (Compiler)

    2014-01-01

    The overall objective for this project is to evaluate two candidate alternatives for the existing Propellant Handler's Ensemble (PHE) escape ventilator. The new candidate ventilators use newer technology with similar quantities of air at approximately half the weight of the current ventilator. Ventilators are typically used to ingress/egress a hazardous work area when hard line air is provided at the work area but the hose is not long enough to get the operator to and from the staging area to the work area. The intent of this test is to verify that the new ventilators perform as well as or better than the current ventilators in maintaining proper oxygen (O2) and carbon dioxide (CO2) levels in the PHE during a typical use for the rated time period (10 minutes). We will evaluate two new units comparing them to the existing unit. Subjects will wear the Category I version of the Propellant Handler's Ensemble with the rear suit pouch snapped.

  15. Analysis of hybrid interface cooling system using air ventilation and nanofluid

    NASA Astrophysics Data System (ADS)

    Rani, M. F. H.; Razlan, Z. M.; Bakar, S. A.; Desa, H.; Wan, W. K.; Ibrahim, I.; Kamarrudin, N. S.; Bin-Abdun, Nazih A.

    2017-09-01

    The hybrid interface cooling system needs to be designed for maintaining the electric vehicle's battery cell temperature at 25°C. The hybrid interface cooling system is a combination of two individual systems, where the primary cooling system (R-134a) and the secondary cooling system (CuO + Water) will be used to absorb the heat generated by the battery cells. The ventilation system is designed using air as the medium to transfer the heat from the batteries to the refrigeration system (R-134a). Research will focus on determining the suitable compressor displacement, the heat exchanger volume and the expansion valve resistance value. The analysis for the secondary cooling system is focused on the cooling coil where low temperature nanofluid is passing through each interval of the battery cells. For analysing purposes, the thermal properties of the mixture of 50 grams, Copper (II) Oxide and the base fluid have been determined. The hybrid interface cooling system are able to achieve 57.82% increments in term of rate of heat transfer as compared to the individual refrigeration system.

  16. Reducing patients' exposures to asthma and allergy triggers in their homes: an evaluation of effectiveness of grades of forced air ventilation filters.

    PubMed

    Brown, Kathleen Ward; Minegishi, Taeko; Allen, Joseph G; McCarthy, John F; Spengler, John D; MacIntosh, David L

    2014-08-01

    Many interventions to reduce allergen levels in the home are recommended to asthma and allergy patients. One that is readily available and can be highly effective is the use of high performing filters in forced air ventilation systems. We conducted a modeling analysis of the effectiveness of filter-based interventions in the home to reduce airborne asthma and allergy triggers. This work used "each pass removal efficiency" applied to health-relevant size fractions of particles to assess filter performance. We assessed effectiveness for key allergy and asthma triggers based on applicable particle sizes for cat allergen, indoor and outdoor sources of particles <2.5 µm in diameter (PM2.5), and airborne influenza and rhinovirus. Our analysis finds that higher performing filters can have significant impacts on indoor particle pollutant levels. Filters with removal efficiencies of >70% for cat dander particles, fine particulate matter (PM2.5) and respiratory virus can lower concentrations of those asthma triggers and allergens in indoor air of the home by >50%. Very high removal efficiency filters, such as those rated a 16 on the nationally recognized Minimum Efficiency Removal Value (MERV) rating system, tend to be only marginally more effective than MERV12 or 13 rated filters. The results of this analysis indicate that use of a MERV12 or higher performing air filter in home ventilation systems can effectively reduce indoor levels of these common asthma and allergy triggers. These reductions in airborne allergens in turn may help reduce allergy and asthma symptoms, especially if employed in conjunction with other environmental management measures recommended for allergy and asthma patients.

  17. Reducing patients’ exposures to asthma and allergy triggers in their homes: an evaluation of effectiveness of grades of forced air ventilation filters

    PubMed Central

    Minegishi, Taeko; Allen, Joseph G.; McCarthy, John F.; Spengler, John D.; MacIntosh, David L.

    2014-01-01

    Objective Many interventions to reduce allergen levels in the home are recommended to asthma and allergy patients. One that is readily available and can be highly effective is the use of high performing filters in forced air ventilation systems. Methods We conducted a modeling analysis of the effectiveness of filter-based interventions in the home to reduce airborne asthma and allergy triggers. This work used “each pass removal efficiency” applied to health-relevant size fractions of particles to assess filter performance. We assessed effectiveness for key allergy and asthma triggers based on applicable particle sizes for cat allergen, indoor and outdoor sources of particles <2.5 µm in diameter (PM2.5), and airborne influenza and rhinovirus. Results Our analysis finds that higher performing filters can have significant impacts on indoor particle pollutant levels. Filters with removal efficiencies of >70% for cat dander particles, fine particulate matter (PM2.5) and respiratory virus can lower concentrations of those asthma triggers and allergens in indoor air of the home by >50%. Very high removal efficiency filters, such as those rated a 16 on the nationally recognized Minimum Efficiency Removal Value (MERV) rating system, tend to be only marginally more effective than MERV12 or 13 rated filters. Conclusions The results of this analysis indicate that use of a MERV12 or higher performing air filter in home ventilation systems can effectively reduce indoor levels of these common asthma and allergy triggers. These reductions in airborne allergens in turn may help reduce allergy and asthma symptoms, especially if employed in conjunction with other environmental management measures recommended for allergy and asthma patients. PMID:24555523

  18. Comparative Performance of Two Ventilation Strategies in a Hot-Humid Climate

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Widder, Sarah; Martin, Eric; Chasar, Dave

    2017-02-01

    In fiscal year 2013, Pacific Northwest National Laboratory (PNNL), Florida Solar Energy Center (FSEC), and Florida Home Energy and Resources Organization (Florida HERO) began a collaborative effort to evaluate the impact of ventilation rate on interior comfort conditions, space-conditioning energy use, and indoor air contaminant concentrations. Relevant parameters were measured in 10 homes in Gainesville, Florida, along with corresponding outdoor conditions, to characterize the impact of differing ventilation rates. This report provides information about the data collection method and results from more than 1 year of data collection during a period from summer 2013 through summer 2014. Indoor air qualitymore » was sampled in three discrete periods with the first occurring in August/September 2013, the second occurring in March/April 2014, and the third occurring in August 2014.« less

  19. Comparative Performance of Two Ventilation Strategies in a Hot-Humid Climate

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Widder, Sarah; Martin, Eric; Chasar, Dave

    In fiscal year 2013, Pacific Northwest National Laboratory (PNNL), Florida Solar Energy Center (FSEC), and Florida Home Energy and Resources Organization (Florida HERO) began a collaborative effort to evaluate the impact of ventilation rate on interior comfort conditions, space-conditioning energy use, and indoor air contaminant concentrations. Relevant parameters were measured in 10 homes in Gainesville, Florida, along with corresponding outdoor conditions, to characterize the impact of differing ventilation rates. This report provides information about the data collection method and results from more than 1 year of data collection during a period from summer 2013 through summer 2014. Indoor air qualitymore » was sampled in three discrete periods with the first occurring in August/September 2013, the second occurring in March/April 2014, and the third occurring in August 2014.« less

  20. A study of energy use for ventilation and air-conditioning systems in Hong Kong

    NASA Astrophysics Data System (ADS)

    Yu, Chung Hoi Philip

    Most of the local modern buildings are high-rise with enclosed structure. Mechanical ventilation and air conditioning (MVAC) systems are installed for thermal comfort. Various types of MVAC systems found in Hong Kong were critically reviewed with comments on their characteristics in energy efficiency as well as application. The major design considerations were also discussed. Besides MVAC, other energy-consuming components in commercial buildings were also identified, such as lighting, lifts and escalators, office equipment, information technology facilities, etc. A practical approach has been adopted throughout this study in order that the end results will have pragmatic value to the heating, ventilating and air-conditioning (HVAC) industry in Hong Kong. Indoor Air Quality (IAQ) has become a major issue in commercial buildings worldwide including Hong Kong. Ventilation rate is no doubt a critical element in the design of HVAC systems, which can be realized more obviously in railway train compartments where the carbon dioxide level will be built up quickly when the compartments are crowded during rush hours. A study was carried out based on a simplified model using a train compartment that is equipped with an MVAC system. Overall Thermal Transfer Value (OTTV) is a single-value parameter for controlling building energy use and is relatively simple to implement legislatively. The local government has taken a first step in reacting to the worldwide concern of energy conservation and environmental protection since 1995. Different methods of OTTV calculation were studied and the computation results were compared. It gives a clear picture of the advantages and limitations for each method to the building designers. However, due to the limitations of using OTTV as the only parameter for building energy control, some new approaches to a total control of building energy use were discussed and they might be considered for future revision of the building energy codes in Hong

  1. Effect of Ventilation Strategies on Residential Ozone Levels

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Walker, Iain S.; Sherman, Max H.

    Elevated outdoor ozone levels are associated with adverse health effects. Because people spend the vast majority of their time indoors, reduction in indoor levels of ozone of outdoor origin would lower population exposures and might also lead to a reduction in ozone-associated adverse health effects. In most buildings, indoor ozone levels are diminished with respect to outdoor levels to an extent that depends on surface reactions and on the degree to which ozone penetrates the building envelope. Ozone enters buildings from outdoors together with the airflows that are driven by natural and mechanical means, including deliberate ventilation used to reducemore » concentrations of indoor-generated pollutants. When assessing the effect of deliberate ventilation on occupant health one should consider not only the positive effects on removing pollutants of indoor origin but also the possibility that enhanced ventilation might increase indoor levels of pollutants originating outdoors. This study considers how changes in residential ventilation that are designed to comply with ASHRAE Standard 62.2 might influence indoor levels of ozone. Simulation results show that the building envelope can contribute significantly to filtration of ozone. Consequently, the use of exhaust ventilation systems is predicted to produce lower indoor ozone concentrations than would occur with balanced ventilation systems operating at the same air-­exchange rate. We also investigated a strategy for reducing exposure to ozone that would deliberately reduce ventilation rates during times of high outdoor ozone concentration while still meeting daily average ventilation requirements.« less

  2. Aerodynamic Characteristics of the Ventilated Design for Flapping Wing Micro Air Vehicle

    PubMed Central

    Zhang, G. Q.; Yu, S. C. M.

    2014-01-01

    Inspired by superior flight performance of natural flight masters like birds and insects and based on the ventilating flaps that can be opened and closed by the changing air pressure around the wing, a new flapping wing type has been proposed. It is known that the net lift force generated by a solid wing in a flapping cycle is nearly zero. However, for the case of the ventilated wing, results for the net lift force are positive which is due to the effect created by the “ventilation” in reducing negative lift force during the upstroke. The presence of moving flaps can serve as the variable in which, through careful control of the areas, a correlation with the decrease in negative lift can be generated. The corresponding aerodynamic characteristics have been investigated numerically by using different flapping frequencies and forward flight speeds. PMID:24683339

  3. Impact of ventilation systems and energy savings in a building on the mechanisms governing the indoor radon activity concentration.

    PubMed

    Collignan, Bernard; Powaga, Emilie

    2017-11-23

    For a given radon potential in the ground and a given building, the parameters affecting the indoor radon activity concentration (IRnAC) are indoor depressurization of a building and its air change rate. These parameters depend mainly on the building characteristics, such as airtightness, and on the nature and performances of the ventilation system. This study involves a numerical sensitivity assessment of the indoor environmental conditions on the IRnAC in buildings. A numerical ventilation model has been adapted to take into account the effects of variations in the indoor environmental conditions (depressurization and air change rate) on the radon entry rate and on the IRnAC. In the context of the development of a policy to reduce energy consumption in a building, the results obtained showed that IRnAC could be strongly affected by variations in the air permeability of the building associated with the ventilation regime. Copyright © 2017 Elsevier Ltd. All rights reserved.

  4. AIR CLEANING FOR ACCEPTABLE INDOOR AIR QUALITY

    EPA Science Inventory

    The paper discusses air cleaning for acceptable indoor air quality. ir cleaning has performed an important role in heating, ventilation, and air-conditioning systems for many years. raditionally, general ventilation air-filtration equipment has been used to protect cooling coils ...

  5. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Introduction to Construction Series. Instructor Edition.

    ERIC Educational Resources Information Center

    Associated General Contractors of America, Washington, DC.

    This module on introductory heating, ventilating, and air conditioning (HVAC) is one of a series of modules designed to teach basic skills necessary for entry-level employment in this field. The module contains four instructional units that cover the following topics: (1) HVAC materials; (2) HVAC tools; (3) HVAC layout; and (4) HVAC basic skills.…

  6. The fluid mechanics of natural ventilation

    NASA Astrophysics Data System (ADS)

    Linden, Paul

    1999-11-01

    Natural ventilation of buildings is the flow generated by temperature differences and by the wind. Modern buildings have extreme designs with large, tall open plan spaces and large cooling requirements. Natural ventilation offers a means of cooling these buildings and providing good indoor air quality. The essential feature of ventilation is an exchange between an interior space and the external ambient. Recent work shows that in many circumstances temperature variations play a controlling feature on the ventilation since the directional buoyancy force has a large influence on the flow patterns within the space and on the nature of the exchange with the outside. Two forms of buoyancy-driven ventilation are discussed: mixing ventilation in which the interior is at approximately uniform temperature and displacement ventilation where there is strong internal stratification. The dynamics of these flows are considered and the effects of wind on them are examined both experimentally and theoretically. The aim behind this work is to give designers rules and intuition on how air moves within a building and the research shows a fascinating branch of fluid mechanics.

  7. 46 CFR 108.437 - Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 46 Shipping 4 2011-10-01 2011-10-01 false Pipe sizes and discharge rates for enclosed ventilation... Systems Fixed Carbon Dioxide Fire Extinguishing Systems § 108.437 Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment. (a) The minimum pipe size for the initial...

  8. Mobile zoned/exponential LAF screen: a new concept in ultra-clean air technology for additional operating room ventilation.

    PubMed

    Friberg, B; Lindgren, M; Karlsson, C; Bergström, A; Friberg, S

    2002-04-01

    A mobile screen (0.5 x 0.4 m) producing ultra-clean exponential LAF (air-flow central zone 0.6 m/s and peripheral zone 0.4 m/s) was investigated as an addition to conventional turbulent/mixing operating room ventilation. The evaluation was performed during strictly standardized sham operations reflecting conditions during major surgery. The study consisted of a pilot experiment designed to give high counts of sedimenting aerobic colony forming units (cfu). In a second main study, recording dust particles, air-borne and sedimenting aerobic cfu, the screen was associated with optimal operating room clothing. In the pilot experiment the use of the screen resulted in a substantial reduction of sedimenting bacteria from 3835-4940 to 0-390 cfu/m(2)/h. In the main study, the use of the additional LAF reduced the surface contamination from 416-329 to 7-78 cfu/m(2)/h up to 1.6 m from the screen (P=0.001-0.0001). Measured in the wound area the screen reduced the air counts of bacteria from 9-14 to 0.2-0.4 cfu/m(3) (P=0.008-0.0001) and a marked reduction of air-borne dust particles was recorded (P=0.007-0.009). In conclusion, the additional mobile LAF screen reduced the counts of aerobic air-borne and sedimenting bacteria-carrying particles as well as dust particles to the levels gained with complete ultra-clean LAF room ventilation. Thus, the screen might prove a valuable addition to operating room ventilation as well as in other areas where asepsis is essential. Copyright 2002 The Hospital Infection Society.

  9. Cumulative ventilation air drying potential as an indication of dry mass content in wastewater sludge in a thin-layer solar drying facility

    NASA Astrophysics Data System (ADS)

    Krawczyk, Piotr

    2013-12-01

    Controlling low-temperature drying facilities which utilise nonprepared air is quite difficult, due to very large variability of ventilation air parameters - both in daily and seasonal cycles. The paper defines the concept of cumulative drying potential of ventilation air and presents experimental evidence that there is a relation between this parameter and condition of the dried matter (sewage sludge). Knowledge on current dry mass content in the dried matter (sewage sludge) provides new possibilities for controlling such systems. Experimental data analysed in the paper was collected in early 2012 during operation of a test solar drying facility in a sewage treatment plant in Błonie near Warsaw, Poland.

  10. Experimental and numerical investigation of hydro power generator ventilation

    NASA Astrophysics Data System (ADS)

    Jamshidi, H.; Nilsson, H.; Chernoray, V.

    2014-03-01

    Improvements in ventilation and cooling offer means to run hydro power generators at higher power output and at varying operating conditions. The electromagnetic, frictional and windage losses generate heat. The heat is removed by an air flow that is driven by fans and/or the rotor itself. The air flow goes through ventilation channels in the stator, to limit the electrical insulation temperatures. The temperature should be kept limited and uniform in both time and space, avoiding thermal stresses and hot-spots. For that purpose it is important that the flow of cooling air is distributed uniformly, and that flow separation and recirculation are minimized. Improvements of the air flow properties also lead to an improvement of the overall efficiency of the machine. A significant part of the windage losses occurs at the entrance of the stator ventilation channels, where the air flow turns abruptly from tangential to radial. The present work focuses exclusively on the air flow inside a generator model, and in particular on the flow inside the stator channels. The generator model design of the present work is based on a real generator that was previously studied. The model is manufactured taking into consideration the needs of both the experimental and numerical methodologies. Computational Fluid Dynamics (CFD) results have been used in the process of designing the experimental setup. The rotor and stator are manufactured using rapid-prototyping and plexi-glass, yielding a high geometrical accuracy, and optical experimental access. A special inlet section is designed for accurate air flow rate and inlet velocity profile measurements. The experimental measurements include Particle Image Velocimetry (PIV) and total pressure measurements inside the generator. The CFD simulations are performed based on the OpenFOAM CFD toolbox, and the steady-state frozen rotor approach. Specific studies are performed, on the effect of adding "pick-up" to spacers, and the effects of the

  11. Wind-driven roof turbines: a novel way to improve ventilation for TB infection control in health facilities.

    PubMed

    Cox, Helen; Escombe, Rod; McDermid, Cheryl; Mtshemla, Yolanda; Spelman, Tim; Azevedo, Virginia; London, Leslie

    2012-01-01

    Tuberculosis transmission in healthcare facilities contributes significantly to the TB epidemic, particularly in high HIV settings. Although improving ventilation may reduce transmission, there is a lack of evidence to support low-cost practical interventions. We assessed the efficacy of wind-driven roof turbines to achieve recommended ventilation rates, compared to current recommended practices for natural ventilation (opening windows), in primary care clinic rooms in Khayelitsha, South Africa. Room ventilation was assessed (CO₂ gas tracer technique) in 4 rooms where roof turbines and air-intake grates were installed, across three scenarios: turbine, grate and window closed, only window open, and only turbine and grate open, with concurrent wind speed measurement. 332 measurements were conducted over 24 months. For all 4 rooms combined, median air changes per hour (ACH) increased with wind speed quartiles across all scenarios. Higher median ACH were recorded with open roof turbines and grates, compared to open windows across all wind speed quartiles. Ventilation with open turbine and grate exceeded WHO-recommended levels (60 Litres/second/patient) for 95% or more of measurements in 3 of the 4 rooms; 47% in the remaining room, where wind speeds were lower and a smaller diameter turbine was installed. High room ventilation rates, meeting recommended thresholds, may be achieved using wind-driven roof turbines and grates, even at low wind speeds. Roof turbines and air-intake grates are not easily closed by staff, allowing continued ventilation through colder periods. This simple, low-cost technology represents an important addition to our tools for TB infection control.

  12. Wind-Driven Roof Turbines: A Novel Way to Improve Ventilation for TB Infection Control in Health Facilities

    PubMed Central

    Cox, Helen; Escombe, Rod; McDermid, Cheryl; Mtshemla, Yolanda; Spelman, Tim; Azevedo, Virginia; London, Leslie

    2012-01-01

    Objective Tuberculosis transmission in healthcare facilities contributes significantly to the TB epidemic, particularly in high HIV settings. Although improving ventilation may reduce transmission, there is a lack of evidence to support low-cost practical interventions. We assessed the efficacy of wind-driven roof turbines to achieve recommended ventilation rates, compared to current recommended practices for natural ventilation (opening windows), in primary care clinic rooms in Khayelitsha, South Africa. Methods Room ventilation was assessed (CO2 gas tracer technique) in 4 rooms where roof turbines and air-intake grates were installed, across three scenarios: turbine, grate and window closed, only window open, and only turbine and grate open, with concurrent wind speed measurement. 332 measurements were conducted over 24 months. Findings For all 4 rooms combined, median air changes per hour (ACH) increased with wind speed quartiles across all scenarios. Higher median ACH were recorded with open roof turbines and grates, compared to open windows across all wind speed quartiles. Ventilation with open turbine and grate exceeded WHO-recommended levels (60 Litres/second/patient) for 95% or more of measurements in 3 of the 4 rooms; 47% in the remaining room, where wind speeds were lower and a smaller diameter turbine was installed. Conclusion High room ventilation rates, meeting recommended thresholds, may be achieved using wind-driven roof turbines and grates, even at low wind speeds. Roof turbines and air-intake grates are not easily closed by staff, allowing continued ventilation through colder periods. This simple, low-cost technology represents an important addition to our tools for TB infection control. PMID:22253742

  13. Ceiling-mounted personalized ventilation system integrated with a secondary air distribution system--a human response study in hot and humid climate.

    PubMed

    Yang, B; Sekhar, S C; Melikov, A K

    2010-08-01

    The benefits of thermal comfort and indoor air quality with personalized ventilation (PV) systems have been demonstrated in recent studies. One of the barriers for wide spread acceptance by architects and HVAC designers has been attributed to challenges and constraints faced in the integration of PV systems with the work station. A newly developed ceiling-mounted PV system addresses these challenges and provides a practical solution while retaining much of the apparent benefits of PV systems. Assessments of thermal environment, air movement, and air quality for ceiling-mounted PV system were performed with tropically acclimatized subjects in a Field Environmental Chamber. Thirty-two subjects performed normal office work and could choose to be exposed to four different PV airflow rates (4, 8, 12, and 16 L/s), thus offering themselves a reasonable degree of individual control. Ambient temperatures of 26 and 23.5 degrees C and PV air temperatures of 26, 23.5, and 21 degrees C were employed. The local and whole body thermal sensations were reduced when PV airflow rates were increased. Inhaled air temperature was perceived cooler and perceived air quality and air freshness improved when PV airflow rate was increased or temperature was reduced. The newly developed ceiling-mounted PV system offers a practical solution to the integration of PV air terminal devices (ATDs) in the vicinity of the workstation. By remotely locating the PV ATDs on the ceiling directly above the occupants and under their control, the conditioned outdoor air is now provided to the occupants through the downward momentum of the air. A secondary air-conditioning and air distribution system offers additional cooling in the room and maintains a higher ambient temperature, thus offering significant benefits in conserving energy. The results of this study provide designers and consultants with needed knowledge for design of PV systems.

  14. Causes Of Low Efficiency Of Combined Ventilation System In Coal Mines In Resolving The Problem Of Air Leaks (Inflows) Between Levels And Surface

    NASA Astrophysics Data System (ADS)

    Popov, Valeriy; Filatov, Yuriy; Lee, Hee; Golik, Anatoliy

    2017-11-01

    The paper discusses the problem of the underground mining safety control. The long-term air intake to coal accumulations is reviewed as one of the reasons of endogenous fires during mining. The methods of combating air leaks (inflows) in order to prevent endogenous fires are analyzed. The calculations showing the discrepancy between the design calculations for the mine ventilation, disregarding a number of mining-andgeological and mining-engineering factors, and the actual conditions of mining are given. It is proved that the conversion of operating mines to combined (pressure and exhaust) ventilation system in order to reduce the endogenous fire hazard of underground mining is unreasonable due to impossibility of providing an optimal distribution of aerodynamic pressure in mines. The conversion does not exclude the entry of air into potentially hazardous zones of endogenous fires. The essence of the combined application of positive and negative control methods for the distribution of air pressure is revealed. It consists of air doors installation in easily ventilated airways and installation of pressure equalization chambers equipped with auxiliary fans near the stoppings, working sections and in parallel airways.The effectiveness of the combined application of negative and positive control methods for the air pressure distribution in order to reduce endogenous fire hazard of mining operations is proved.

  15. A novel fiber-optic measurement system for the evaluation of performances of neonatal pulmonary ventilators

    NASA Astrophysics Data System (ADS)

    Battista, L.; Scorza, A.; Botta, F.; Sciuto, S. A.

    2016-02-01

    Published standards for the performance evaluation of pulmonary ventilators are mainly directed to manufacturers rather than to end-users and often considered inadequate or not comprehensive. In order to contribute to overcome the problems above, a novel measurement system was proposed and tested with waveforms of mechanical ventilation by means of experimental trials carried out with infant ventilators typically used in neonatal intensive care units: the main quantities of mechanical ventilation in newborns are monitored, i.e. air flow rate, differential pressure and volume from infant ventilator are measured by means of two novel fiber-optic sensors (OFSs) developed and characterized by the authors, while temperature and relative humidity of air mass are obtained by two commercial transducers. The proposed fiber-optic sensors (flow sensor Q-OFS, pressure sensor P-OFS) showed measurement ranges of air flow and pressure typically encountered in neonatal mechanical ventilation, i.e. the air flow rate Q ranged from 3 l min-1 to 18 l min-1 (inspiratory) and from  -3 l min-1 to  -18 l min-1 (expiratory), the differential pressure ΔP ranged from  -15 cmH2O to 15 cmH2O. In each experimental trial carried out with different settings of the ventilator, outputs of the OFSs are compared with data from two reference sensors (reference flow sensor RF, reference pressure sensor RP) and results are found consistent: flow rate Q showed a maximum error between Q-OFS and RF up to 13 percent, with an output ratio Q RF/Q OFS of not more than 1.06  ±  0.09 (least square estimation, 95 percent confidence level, R 2 between 0.9822 and 0.9931). On the other hand the maximum error between P-OFS and RP on differential pressure ΔP was lower than 10 percent, with an output ratio ΔP RP/ΔP OFS between 0.977  ±  0.022 and 1.0  ±  0.8 (least square estimation, 95 percent confidence level, R 2 between 0.9864 and 0.9876). Despite the possible improvements

  16. A pilot study using scripted ventilation conditions to identify key factors affecting indoor pollutant concentration and air exchange rate in a residence.

    PubMed

    Johnson, Ted; Myers, Jeffrey; Kelly, Thomas; Wisbith, Anthony; Ollison, Will

    2004-01-01

    A pilot study was conducted using an occupied, single-family test house in Columbus, OH, to determine whether a script-based protocol could be used to obtain data useful in identifying the key factors affecting air-exchange rate (AER) and the relationship between indoor and outdoor concentrations of selected traffic-related air pollutants. The test script called for hourly changes to elements of the test house considered likely to influence air flow and AER, including the position (open or closed) of each window and door and the operation (on/off) of the furnace, air conditioner, and ceiling fans. The script was implemented over a 3-day period (January 30-February 1, 2002) during which technicians collected hourly-average data for AER, indoor, and outdoor air concentrations for six pollutants (benzene, formaldehyde (HCHO), polycyclic aromatic hydrocarbons (PAH), carbon monoxide (CO), nitric oxide (NO), and nitrogen oxides (NO(x))), and selected meteorological variables. Consistent with expectations, AER tended to increase with the number of open exterior windows and doors. The 39 AER values measured during the study when all exterior doors and windows were closed varied from 0.36 to 2.29 h(-1) with a geometric mean (GM) of 0.77 h(-1) and a geometric standard deviation (GSD) of 1.435. The 27 AER values measured when at least one exterior door or window was opened varied from 0.50 to 15.8 h(-1) with a GM of 1.98 h(-1) and a GSD of 1.902. AER was also affected by temperature and wind speed, most noticeably when exterior windows and doors were closed. Results of a series of stepwise linear regression analyses suggest that (1) outdoor pollutant concentration and (2) indoor pollutant concentration during the preceding hour were the "variables of choice" for predicting indoor pollutant concentration in the test house under the conditions of this study. Depending on the pollutant and ventilation conditions, one or more of the following variables produced a small, but

  17. Analysis of the dust particles distribution and ventilation as a way to improve indoor air quality

    NASA Astrophysics Data System (ADS)

    Kozlovtseva, E. Yu; Azarov, V. N.; Stefanenko, I. V.

    2017-10-01

    The indoor air pollution is analyzed in the article. The subject of the research is the presence and composition of the dust particles taken into “traps” in the working space of the public building (Volgograd State Technical University, Volgograd, the Russian Federation). The research has established the range of sizes of the particulate matter (fractional composition) for the dust in the air of the working space in the form of integral curves for the mass distribution of particles with to their diameters, it also provides the scheme of the air flows movement in the ventilation system of the room.

  18. 14 CFR 121.219 - Ventilation.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 14 Aeronautics and Space 3 2010-01-01 2010-01-01 false Ventilation. 121.219 Section 121.219 Aeronautics and Space FEDERAL AVIATION ADMINISTRATION, DEPARTMENT OF TRANSPORTATION (CONTINUED) AIR CARRIERS... passenger or crew compartment must be suitably ventilated. Carbon monoxide concentration may not be more...

  19. Ventilation Control of Volatile Organic Compounds in New U.S. Homes: Results of a Controlled Field Study in Nine Residential Units

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Willem, Henry; Hult, Erin L.; Hotchi, Toshifumi

    2013-01-01

    In order to optimize strategies to remove airborne contaminants in residences, it is necessary to determine how contaminant concentrations respond to changes in the air exchange rate. The impact of air exchange rate on the indoor concentrations of 39 target volatile organic compounds (VOCs) was assessed by measuring air exchange rates and VOC concentrations at three ventilation settings in nine residences. Active sampling methods were used for VOC concentration measurements, and passive perfluorocarbon tracer gas emitters with active sampling were used to determine the overall air exchange rate corresponding to the VOC measurements at each ventilation setting. The concentration levelsmore » and emission rates of the target VOCs varied by as much as two orders of magnitude across sites. Aldehyde and terpene compounds were typically the chemical classes with highest concentrations, followed by alkanes, aromatics, and siloxanes. For each home, VOC concentrations tended to decrease as the air exchange rate was increased, however, measurement uncertainty was significant. The indoor concentration was inversely proportional to air exchange rate for most compounds. For a subset of compounds including formaldehyde, however, the indoor concentration exhibited a non-linear dependence on the timescale for air exchange« less

  20. Ventilation Control of Volatile Organic Compounds in New U.S. Homes: Results of a Controlled Field Study in Nine Residential Units

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Willem, Henry; Hult, Erin L.; Hotchi, Toshifumi

    2013-01-23

    In order to optimize strategies to remove airborne contaminants in residences, it is necessary to determine how contaminant concentrations respond to changes in the air exchange rate. The impact of air exchange rate on the indoor concentrations of 39 target volatile organic compounds (VOCs) was assessed by measuring air exchange rates and VOC concentrations at three ventilation settings in nine residences. Active sampling methods were used for VOC concentration measurements, and passive perfluorocarbon tracer gas emitters with active sampling were used to determine the overall air exchange rate corresponding to the VOC measurements at each ventilation setting. The concentration levelsmore » and emission rates of the target VOCs varied by as much as two orders of magnitude across sites. Aldehyde and terpene compounds were typically the chemical classes with highest concentrations, followed by alkanes, aromatics, and siloxanes. For each home, VOC concentrations tended to decrease as the air exchange rate was increased, however, measurement uncertainty was significant. The indoor concentration was inversely proportional to air exchange rate for most compounds. For a subset of compounds including formaldehyde, however, the indoor concentration exhibited a non-linear dependence on the timescale for air exchange.« less

  1. Temperature of gas delivered from ventilators.

    PubMed

    Chikata, Yusuke; Onodera, Mutsuo; Imanaka, Hideaki; Nishimura, Masaji

    2013-01-01

    Although heated humidifiers (HHs) are the most efficient humidifying device for mechanical ventilation, some HHs do not provide sufficient humidification when the inlet temperature to the water chamber is high. Because portable and home-care ventilators use turbines, blowers, pistons, or compressors to inhale in ambient air, they may have higher gas temperature than ventilators with piping systems. We carried out a bench study to investigate the temperature of gas delivered from portable and home-care ventilators, including the effects of distance from ventilator outlet, fraction of inspiratory oxygen (FIO2), and minute volume (MV). We evaluated five ventilators equipped with turbine, blower, piston, or compressor system. Ambient air temperature was adjusted to 24°C ± 0.5°C, and ventilation was set at FIO2 0.21, 0.6, and 1.0, at MV 5 and 10 L/min. We analyzed gas temperature at 0, 40, 80, and 120 cm from ventilator outlet and altered ventilator settings. While temperature varied according to ventilators, the outlet gas temperature of ventilators became stable after, at the most, 5 h. Gas temperature was 34.3°C ± 3.9°C at the ventilator outlet, 29.5°C ± 2.2°C after 40 cm, 25.4°C ± 1.2°C after 80 cm and 25.1°C ± 1.2°C after 120 cm (P < 0.01). FIO2 and MV did not affect gas temperature. Gas delivered from portable and home-care ventilator was not too hot to induce heated humidifier malfunctioning. Gas soon declined when passing through the limb.

  2. Key Factors Determining Indoor Air PM10 Concentrations in Naturally Ventilated Primary Schools in Belgrade, Serbia

    PubMed Central

    Matic, Branislava; Rakic, Uros; Jovanovic, Verica; Dejanovic, Snezana; Djonovic, Nela

    2017-01-01

    Abstract Introduction Indoor air quality (IAQ) is rated as a serious public health issue. Knowing children are accounted as more vulnerable to environmental health hazards, data are needed on air quality in schools. Methods A project was conducted from 2007 until 2009 (SEARCH, School Environment and Respiratory Health of Children), aiming to verify links between IAQ and children’s respiratory health. Study was conducted in ten primary schools on 735 children, in 44 classrooms. Children were randomly selected. Research tools and indicators used for children’s exposure to school environment were indoor and outdoor pollutants, two standardized questionnaires for school and classroom characteristics. In both classroom air and ambient air in front of them we measured, during a 5-day exposure period for continuous 24h measuring: carbon monoxide, carbon dioxide, indoor air temperature, relative humidity, and PM10 during classes. Results PM10 concentrations were significantly most frequent in an interval of ≥80.1μg/m3, that is, in the interval above 50μg/m3. Mean PM10 value was 82.24±42.43 μg/m3, ranging from 32.00μg/m3 to of 197.00μg/m3. Conclusion The increase of outdoor PM10 concentration significantly affects the increase of indoor PM10. A statistically significant difference exists for average IAQ PM10 concentrations vs. indicators of indoor thermal comfort zone (p<0.0001); they are lower in the classrooms with indicators within the comfort zone. Moreover, dominant factors for the increase of PM10 are: high occupancy rate in the classroom (<2m2 of space per child), high relative humidity (>75%), and indoor temperature beyond 23°C, as well as bad ventilation habits (keeping windows shut most of the time). PMID:29062397

  3. The effect of helium on ventilator performance: study of five ventilators and a bedside Pitot tube spirometer.

    PubMed

    Oppenheim-Eden, A; Cohen, Y; Weissman, C; Pizov, R

    2001-08-01

    To assess in vitro the performance of five mechanical ventilators-Siemens 300 and 900C (Siemens-Elma; Solna, Sweden), Puritan Bennett 7200 (Nellcor Puritan Bennett; Pleasanton, CA), Evita 4 (Dragerwerk; Lubeck, Germany), and Bear 1000 (Bear Medical Systems; Riverside CA)-and a bedside sidestream spirometer (Datex CS3 Respiratory Module; Datex-Ohmeda; Helsinki, Finland) during ventilation with helium-oxygen mixtures. In vitro study. ICUs of two university-affiliated hospitals. Each ventilator was connected to 100% helium through compressed air inlets and then tested at three to six different tidal volume (VT) settings using various helium-oxygen concentrations (fraction of inspired oxygen [FIO(2)] of 0.2 to 1.0). FIO(2) and VT were measured with the Datex CS3 spirometer, and VT was validated with a water-displacement spirometer. The Puritan Bennett 7200 ventilator did not function with helium. With the other four ventilators, delivered FIO(2) was lower than the set FIO(2). For the Siemens 300 and 900C ventilators, this difference could be explained by the lack of 21% oxygen when helium was connected to the air supply port, while for the other two ventilators, a nonlinear relation was found. The VT of the Siemens 300 ventilator was independent of helium concentration, while for the other three ventilators, delivered VT was greater than the set VT and was dependent on helium concentration. During ventilation with 80% helium and 20% oxygen, VT increased to 125% of set VT for the Siemens 900C ventilator, and more than doubled for the Evita 4 and Bear 1000 ventilators. Under the same conditions, the Datex CS3 spirometer underestimated the delivered VT by about 33%. At present, no mechanical ventilator is calibrated for use with helium. This investigation offers correction factors for four ventilators for ventilation with helium.

  4. A preliminary investigation of the drag and ventilation characteristics of livestock haulers

    NASA Technical Reports Server (NTRS)

    Hoffman, J. A.; Sandin, D. R.

    1983-01-01

    A wind tunnel evaluation of the drag and ventilation characteristics of a conventional (unmodified) and five modified subscale model livestock haulers at 0 deg yaw angle has been made. The unmodified livestock hauler has a relatively high drag coefficient, and a low velocity recirculation region exists in the forward portion of the hauler. The use of a streamlined forebody and enclosed gap reduced the drag coefficient of one model by 42% and improved the rate at which contaminants can be flushed from the cargo compartment by a factor of 2.5. From the limited data obtained, any increase in the fraction of open area of the trailer sides was found to improve the trailer ventilation. The use of a ram air inlet can improve the ventilation within the hauler and remove the low velocity recirculation region at the expense of a modest increase in the truck's drag coefficient. A mathematical model for vehicles with ram air or NACA submerged inlets was developed and appears to adequately predict the ventilation characteristics of livestock haulers.

  5. Indoor Air Quality Assessment of the San Francisco Federal Building

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Apte, Michael; Bennett, Deborah H.; Faulkner, David

    2008-07-01

    An assessment of the indoor air quality (IAQ) of the San Francisco Federal Building (SFFB) was conducted on May 12 and 14, 2009 at the request of the General Services Administration (GSA). The purpose of the assessment was for a general screening of IAQ parameters typically indicative of well functioning building systems. One naturally ventilated space and one mechanically ventilated space were studied. In both zones, the levels of indoor air contaminants, including CO2, CO, particulate matter, volatile organic compounds, and aldehydes, were low, relative to reference exposure levels and air quality standards for comparable office buildings. We found slightlymore » elevated levels of volatile organic compounds (VOCs) including two compounds often found in"green" cleaning products. In addition, we found two industrial solvents at levels higher than typically seen in office buildings, but the levels were not sufficient to be of a health concern. The ventilation rates in the two study spaces were high by any standard. Ventilation rates in the building should be further investigated and adjusted to be in line with the building design. Based on our measurements, we conclude that the IAQ is satisfactory in the zone we tested, but IAQ may need to be re-checked after the ventilation rates have been lowered.« less

  6. Preventing Airborne Disease Transmission: Review of Methods for Ventilation Design in Health Care Facilities

    PubMed Central

    Aliabadi, Amir A.; Rogak, Steven N.; Bartlett, Karen H.; Green, Sheldon I.

    2011-01-01

    Health care facility ventilation design greatly affects disease transmission by aerosols. The desire to control infection in hospitals and at the same time to reduce their carbon footprint motivates the use of unconventional solutions for building design and associated control measures. This paper considers indoor sources and types of infectious aerosols, and pathogen viability and infectivity behaviors in response to environmental conditions. Aerosol dispersion, heat and mass transfer, deposition in the respiratory tract, and infection mechanisms are discussed, with an emphasis on experimental and modeling approaches. Key building design parameters are described that include types of ventilation systems (mixing, displacement, natural and hybrid), air exchange rate, temperature and relative humidity, air flow distribution structure, occupancy, engineered disinfection of air (filtration and UV radiation), and architectural programming (source and activity management) for health care facilities. The paper describes major findings and suggests future research needs in methods for ventilation design of health care facilities to prevent airborne infection risk. PMID:22162813

  7. Preventing airborne disease transmission: review of methods for ventilation design in health care facilities.

    PubMed

    Aliabadi, Amir A; Rogak, Steven N; Bartlett, Karen H; Green, Sheldon I

    2011-01-01

    Health care facility ventilation design greatly affects disease transmission by aerosols. The desire to control infection in hospitals and at the same time to reduce their carbon footprint motivates the use of unconventional solutions for building design and associated control measures. This paper considers indoor sources and types of infectious aerosols, and pathogen viability and infectivity behaviors in response to environmental conditions. Aerosol dispersion, heat and mass transfer, deposition in the respiratory tract, and infection mechanisms are discussed, with an emphasis on experimental and modeling approaches. Key building design parameters are described that include types of ventilation systems (mixing, displacement, natural and hybrid), air exchange rate, temperature and relative humidity, air flow distribution structure, occupancy, engineered disinfection of air (filtration and UV radiation), and architectural programming (source and activity management) for health care facilities. The paper describes major findings and suggests future research needs in methods for ventilation design of health care facilities to prevent airborne infection risk.

  8. [Biological contamination in office buildings related to ventilation/air conditioning system].

    PubMed

    Bródka, Karolina; Sowiak, Małgorzata; Kozajda, Anna; Cyprowski, Marcin; Irena, Szadkowska-Stańczyk

    2012-01-01

    Indoor air is contaminated with microorganisms coming from both the atmospheric air and sources present in premises. The aim of this study was to analyze the concentrations of biological agents in office buildings, dependending on ventilation/air conditioning system and season. The study covered office buildings (different in the system of ventila-tion/air conditioning). Air samples for assessing the levels of inhalable dust, endotoxins and (1-->3)-beta-D-glucans, were taken at the selected stationary points of each building during summer and winter. The air was sampled for 6 h, using portable sets consisting of the GilAir 5 pump and the head filled with a filter of fiber glass. The samples for the presence of airborne bacteria and fungi were collected twice during the day using the impaction method. Average concentrations of inhalable dust, bacteria, fungi, endotoxins and (1-->3)-beta-D-glucans in office premises were 0.09 mg/m3, 6.00 x 10(2) cfu/m3, 4.59 x 10(1) cfu/m3, 0.42 ng/m3 and 3.91 ng/m3, respectively. Higher concentrations of the investigated agents were found in summer. In premises with air conditioning concentrations of airborne fungi, (1-->3)-beta-D-glucans and inhalable dust were significantly lower in winter. In summer the trend was reverse except for (1-->3)-beta-D-glucans. Concentrations of biological agents were affected by the season and the presence of air conditioning. Concentrations of inhalable dust, bacteria, fungi, endotoxins and (1-->3)-beta-D-glucans, observed inside the office buildings, were significantly higher in summer than in winter. The presence of the air conditioning system modified in various ways the levels of biological agents. Its influence was greater on the concentration of fungi and (1-->3)-beta-D-glucans than on that of bacteria and endotoxins.

  9. Ventilator-associated pneumonia rates in critical care units in 3 Arabian Gulf countries: A 6-year surveillance study.

    PubMed

    El-Saed, Aiman; Al-Jardani, Amina; Althaqafi, Abdulhakeem; Alansari, Huda; Alsalman, Jameela; Al Maskari, Zaina; El Gammal, Ayman; Al Nasser, Wafa; Al-Abri, Seif S; Balkhy, Hanan H

    2016-07-01

    Data estimating the rates of ventilator-associated pneumonia (VAP) in critical patients in Gulf Cooperation Council (GCC) countries are very limited. The aim of this study was to estimate VAP rates in GCC hospitals and to compare rates with published reports of the U.S. National Healthcare Safety Network (NHSN) and International Nosocomial Infection Control Consortium (INICC). VAP rates and ventilator utilization between 2008 and 2013 were calculated from aggregate VAP surveillance data using NHSN methodology pooled from 6 hospitals in 3 GCC countries: Saudi Arabia, Oman, and Bahrain. The standardized infection ratios of VAP in GCC hospitals were compared with published reports of the NHSN and INICC. A total of 368 VAP events were diagnosed during a 6-year period covering 76,749 ventilator days and 134,994 patient days. The overall VAP rate was 4.8 per 1,000 ventilator days (95% confidence interval, 4.3-5.3), with an overall ventilator utilization of 0.57. The VAP rates showed a wide variability between different types of intensive care units (ICUs) and were decreasing over time. After adjusting for the differences in ICU type, the risk of VAP in GCC hospitals was 217% higher than NHSN hospitals and 69% lower than INICC hospitals. The risk of VAP in ICU patients in GCC countries is higher than pooled U.S. VAP rates but lower than pooled rates from developing countries participating in the INICC. Copyright © 2016 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.

  10. Demonstration of Split-Flow Ventilation and Recirculation as Flow- Reduction Methods in an Air Force Paint Spray Booth. Volume 1

    DTIC Science & Technology

    1994-07-27

    of the split-flow and recirculation modifications in typical Air Force painting operations; itwas a proof-of- concept study only. It is recognized...recirculating ventilation. 4 To Implement this flow-reduction concept , it must first be established that recirculation does not cause an accumulation of toxic...ventilation concept . The concentration gradient is determined by height and direction of paint application. If the concentration in the top portion is

  11. Non-invasive ventilation with intelligent volume-assured pressure support versus pressure-controlled ventilation: effects on the respiratory event rate and sleep quality in COPD with chronic hypercapnia.

    PubMed

    Nilius, Georg; Katamadze, Nato; Domanski, Ulrike; Schroeder, Maik; Franke, Karl-Josef

    2017-01-01

    COPD patients who develop chronic hypercapnic respiratory failure have a poor prognosis. Treatment of choice, especially the best form of ventilation, is not well known. This study compared the effects of pressure-controlled (spontaneous timed [ST]) non-invasive ventilation (NIV) and NIV with intelligent volume-assured pressure support (IVAPS) in chronic hypercapnic COPD patients regarding the effects on alveolar ventilation, adverse patient/ventilator interactions and sleep quality. This prospective, single-center, crossover study randomized patients to one night of NIV using ST then one night with the IVAPS function activated, or vice versa. Patients were monitored using polysomnography (PSG) and transcutaneous carbon dioxide pressure (PtcCO 2 ) measurement. Patients rated their subjective experience (total score, 0-45; lower scores indicate better acceptability). Fourteen patients were included (4 females, age 59.4±8.9 years). The total number of respiratory events was low, and similar under pressure-controlled (5.4±6.7) and IVAPS (8.3±10.2) conditions ( P =0.064). There were also no clinically relevant differences in PtcCO 2 between pressure-controlled and IVAPS NIV (52.9±6.2 versus 49.1±6.4 mmHg). Respiratory rate was lower under IVAPS overall; between-group differences reached statistical significance during wakefulness and non-rapid eye movement sleep. Ventilation pressures were 2.6 cmH 2 O higher under IVAPS versus pressure-controlled ventilation, resulting in a 20.1 mL increase in breathing volume. Sleep efficiency was slightly higher under pressure-controlled ventilation versus IVAPS. Respiratory arousals were uncommon (24.4/h [pressure-controlled] versus 25.4/h [IVAPS]). Overall patient assessment scores were similar, although there was a trend toward less discomfort during IVAPS. Our results show that IVAPS NIV allows application of higher nocturnal ventilation pressures versus ST without affecting sleep quality or inducing ventilation- associated

  12. Technology Solutions Case Study: Evaluation of Ventilation Strategies in New Construction Multifamily Buildings, New York, New York

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    None

    2014-09-01

    In multifamily buildings, particularly in the Northeast, exhaust ventilation strategies are the norm as a means of meeting both local exhaust and whole-unit mechanical ventilation rates. The issue of where the "fresh" air is coming from is gaining significance as air-tightness standards for enclosures become more stringent, and the "normal leakage paths through the building envelope" disappear. Consortium for Advanced Residential Buildings researchers have found that the majority of high performance, new construction, multifamily housing in the Northeast use one of four general strategies for ventilation: continuous exhaust only with no designated supply or make-up air source, continuous exhaust withmore » ducted make-up air to apartments, continuous exhaust with supply through a make-up air device integral to the unit HVAC, and continuous exhaust with supply through a passive inlet device, such as a trickle vent. This research effort included several weeks of building pressure monitoring to validate system performance of the different strategies for providing make-up air to apartments.« less

  13. Assessing Thermal Comfort Due to a Ventilated Double Window

    NASA Astrophysics Data System (ADS)

    Carlos, Jorge S.; Corvacho, Helena

    2017-10-01

    Building design and its components are the result of a complex process, which should provide pleasant conditions to its inhabitants. Therefore, indoor acceptable comfort is influenced by the architectural design. ISO and ASHRAE standards define thermal comfort as the condition of mind that expresses satisfaction with the thermal environment. The energy demand for heating, beside the building’s physical properties, also depend on human behaviour, like opening or closing windows. Generally, windows are the weakest façade element concerning to thermal performance. A lower thermal resistance allows higher thermal conduction through it. When a window is very hot or cold, and the occupant is very close to it, it may result in thermal discomfort. The functionality of a ventilated double window introduces new physical considerations to a traditional window. In consequence, it is necessary to study the local effect on human comfort in function of the boundary conditions. Wind, solar availability, air temperature and therefore heating and indoor air quality conditions will affect the relationship between this passive system and the indoor environment. In the present paper, the influence of thermal performance and ventilation on human comfort resulting from the construction and geometry solutions is shown, helping to choose the best solution. The presented approach shows that in order to save energy it is possible to reduce the air changes of a room to the minimum, without compromising air quality, enhancing simultaneously local thermal performance and comfort. The results of the study on the effect of two parallel windows with a ventilated channel in the same fenestration on comfort conditions for several different room dimensions, are also presented. As the room dimensions’ rate changes so does the window to floor rate; therefore, under the same climatic conditions and same construction solution, different results are obtained.

  14. Energy and IAQ Implications of Alternative Minimum Ventilation Rates in California Retail and School Buildings

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Dutton, Spencer M.; Fisk, William J.

    For a stand-alone retail building, a primary school, and a secondary school in each of the 16 California climate zones, the EnergyPlus building energy simulation model was used to estimate how minimum mechanical ventilation rates (VRs) affect energy use and indoor air concentrations of an indoor-generated contaminant. The modeling indicates large changes in heating energy use, but only moderate changes in total building energy use, as minimum VRs in the retail building are changed. For example, predicted state-wide heating energy consumption in the retail building decreases by more than 50% and total building energy consumption decreases by approximately 10% asmore » the minimum VR decreases from the Title 24 requirement to no mechanical ventilation. The primary and secondary schools have notably higher internal heat gains than in the retail building models, resulting in significantly reduced demand for heating. The school heating energy use was correspondingly less sensitive to changes in the minimum VR. The modeling indicates that minimum VRs influence HVAC energy and total energy use in schools by only a few percent. For both the retail building and the school buildings, minimum VRs substantially affected the predicted annual-average indoor concentrations of an indoor generated contaminant, with larger effects in schools. The shape of the curves relating contaminant concentrations with VRs illustrate the importance of avoiding particularly low VRs.« less

  15. The effect of increased classroom ventilation rate indicated by reduced CO2 concentration on the performance of schoolwork by children.

    PubMed

    Petersen, S; Jensen, K L; Pedersen, A L S; Rasmussen, H S

    2016-06-01

    The article reports on an experiment which investigated the effect of increased classroom ventilation rate on the performance of children aged 10-12 years. The experiment was executed at two different schools (two classrooms at each school) as a double-blind 2 × 2 crossover intervention where four different performance tests were used as surrogates for short-term concentration and logical thinking. Only complete pairs of test responses were included in the within-subject comparisons of performance, and data were not corrected for learning and fatigue effects. Analysis of the total sample suggested the number of correct answers was improved significantly in four of four performance test, addition (6.3%), number comparison (4.8%), grammatical reasoning (3.2%), and reading and comprehension (7.4%), when the outdoor air supply rate was increased from an average of 1.7 (1.4-2.0) to 6.6 l/s per person. The increased outdoor air supply rate did not have any significant effect on the number of errors in any of the performance tests. Results from questionnaires regarding pupil perception of the indoor environment, reported Sick Building Syndrome symptoms, and motivation suggested that the study classroom air was perceived more still and pupil were experiencing less pain in the eyes in the recirculation condition compared to the fresh air condition. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  16. Effects of animal activity and air temperature on methane and ammonia emissions from a naturally ventilated building for dairy cows

    NASA Astrophysics Data System (ADS)

    Ngwabie, N. M.; Jeppsson, K.-H.; Gustafsson, G.; Nimmermark, S.

    2011-12-01

    Knowledge of how different factors affect gas emissions from animal buildings can be useful for emission prediction purposes and for the improvement of emission abatement techniques. In this study, the effects of dairy cow activity and indoor air temperature on gas emissions were examined. The concentrations of CH 4, NH 3, CO 2 and N 2O inside and outside a dairy cow building were measured continuously between February and May together with animal activity and air temperature. The building was naturally ventilated and had a solid concrete floor which sloped towards a central urine gutter. Manure was scraped from the floor once every hour in the daytime and once every second hour at night into a partly covered indoor pit which was emptied daily at 6 a.m. and at 5 p.m. Gas emissions were calculated from the measured gas concentrations and ventilation rates estimated by the CO 2 balance method. The animal activity and emission rates of CH 4 and NH 3 showed significant diurnal variations with two peaks which were probably related to the feeding routine. On an average day, CH 4 emissions ranged from 7 to 15 g LU -1 h -1 and NH 3 emissions ranged from 0.4 to 1.5 g LU -1 h -1 (1 LU = 500 kg animal weight). Mean emissions of CH 4 and NH 3 were 10.8 g LU -1 h -1 and 0.81 g LU -1 h -1, respectively. The NH 3 emissions were comparable to emissions from tied stall buildings and represented a 4% loss in manure nitrogen. At moderate levels, temperature seems to affect the behaviour of dairy cows and in this study where the daily indoor air temperature ranged from about 5 up to about 20 °C, the daily activity of the cows decreased with increasing indoor air temperature ( r = -0.78). Results suggest that enteric fermentation is the main source of CH 4 emissions from systems of the type in this study, while NH 3 is mainly emitted from the manure. Daily CH 4 emissions increased significantly with the activity of the cows ( r = 0.61) while daily NH 3 emissions increased

  17. Enhanced Photoacoustic Gas Analyser Response Time and Impact on Accuracy at Fast Ventilation Rates during Multiple Breath Washout

    PubMed Central

    Horsley, Alex; Macleod, Kenneth; Gupta, Ruchi; Goddard, Nick; Bell, Nicholas

    2014-01-01

    Background The Innocor device contains a highly sensitive photoacoustic gas analyser that has been used to perform multiple breath washout (MBW) measurements using very low concentrations of the tracer gas SF6. Use in smaller subjects has been restricted by the requirement for a gas analyser response time of <100 ms, in order to ensure accurate estimation of lung volumes at rapid ventilation rates. Methods A series of previously reported and novel enhancements were made to the gas analyser to produce a clinically practical system with a reduced response time. An enhanced lung model system, capable of delivering highly accurate ventilation rates and volumes, was used to assess in vitro accuracy of functional residual capacity (FRC) volume calculation and the effects of flow and gas signal alignment on this. Results 10–90% rise time was reduced from 154 to 88 ms. In an adult/child lung model, accuracy of volume calculation was −0.9 to 2.9% for all measurements, including those with ventilation rate of 30/min and FRC of 0.5 L; for the un-enhanced system, accuracy deteriorated at higher ventilation rates and smaller FRC. In a separate smaller lung model (ventilation rate 60/min, FRC 250 ml, tidal volume 100 ml), mean accuracy of FRC measurement for the enhanced system was minus 0.95% (range −3.8 to 2.0%). Error sensitivity to flow and gas signal alignment was increased by ventilation rate, smaller FRC and slower analyser response time. Conclusion The Innocor analyser can be enhanced to reliably generate highly accurate FRC measurements down at volumes as low as those simulating infant lung settings. Signal alignment is a critical factor. With these enhancements, the Innocor analyser exceeds key technical component recommendations for MBW apparatus. PMID:24892522

  18. Impact of varying area of polluting surface materials on perceived air quality.

    PubMed

    Sakr, W; Knudsen, H N; Gunnarsen, L; Haghighat, F

    2003-06-01

    A laboratory study was performed to investigate the impact of the concentration of pollutants in the air on emissions from building materials. Building materials were placed in ventilated test chambers. The experimental set-up allowed the concentration of pollution in the exhaust air to be changed either by diluting exhaust air with clean air (changing the dilution factor) or by varying the area of the material inside the chamber when keeping the ventilation rate constant (changing the area factor). Four different building materials and three combinations of two or three building materials were studied in ventilated small-scale test chambers. Each individual material and three of their combinations were examined at four different dilution factors and four different area factors. An untrained panel of 23 subjects assessed the air quality from the chambers. The results show that a certain increase in dilution improves the perceived air quality more than a similar decrease in area. The reason for this may be that the emission rate of odorous pollutants increases when the concentration in the chamber decreases. The results demonstrate that, in some cases the effect of increased ventilation on the air quality may be less than expected from a simple dilution model.

  19. Effects of ventilation rate per person and per floor area on perceived air quality, sick building syndrome symptoms, and decision-making.

    PubMed

    Maddalena, R; Mendell, M J; Eliseeva, K; Chan, W R; Sullivan, D P; Russell, M; Satish, U; Fisk, W J

    2015-08-01

    Ventilation rates (VRs) in buildings must adequately control indoor levels of pollutants; however, VRs are constrained by the energy costs. Experiments in a simulated office assessed the effects of VR per occupant on perceived air quality (PAQ), Sick Building Syndrome (SBS) symptoms, and decision-making performance. A parallel set of experiments assessed the effects of VR per unit floor area on the same outcomes. Sixteen blinded healthy young adult subjects participated in each study. Each exposure lasted four hours and each subject experienced two conditions in a within-subject study design. The order of presentation of test conditions, day of testing, and gender were balanced. Temperature, relative humidity, VRs, and concentrations of pollutants were monitored. Online surveys assessed PAQ and SBS symptoms and a validated computer-based tool measured decision-making performance. Neither changing the VR per person nor changing the VR per floor area, had consistent statistically significant effects on PAQ or SBS symptoms. However, reductions in either occupant-based VR or floor-area-based VR had a significant and independent negative impact on most decision-making measures. These results indicate that the changes in VR employed in the study influence performance of healthy young adults even when PAQ and SBS symptoms are unaffected. The study results indicate the importance of avoiding low VRs per person and low VRs per floor area to minimize decrements in cognitive performance. © 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  20. VOLATILIZATION RATES FROM WATER TO INDOOR AIR ...

    EPA Pesticide Factsheets

    Contaminated water can lead to volatilization of chemicals to residential indoor air. Previous research has focused on only one source (shower stalls) and has been limited to chemicals in which gas-phase resistance to mass transfer is of marginal significance. As a result, attempts to extrapolate chemical emissions from high-volatility chemicals to lower volatility chemicals, or to sources other than showers, have been difficult or impossible. This study involved the development of two-phase, dynamic mass balance models for estimating chemical emissions from washing machines, dishwashers, and bathtubs. An existing model was adopted for showers only. Each model required the use of source- and chemical-specific mass transfer coefficients. Air exchange (ventilation) rates were required for dishwashers and washing machines as well. These parameters were estimated based on a series of 113 experiments involving 5 tracer chemicals (acetone, ethyl acetate, toluene, ethylbenzene, and cyclohexane) and 4 sources (showers, bathtubs, washing machines, and dishwashers). Each set of experiments led to the determination of chemical stripping efficiencies and mass transfer coefficients (overall, liquid-phase, gas-phase), and to an assessment of the importance of gas- phase resistance to mass transfer. Stripping efficiencies ranged from 6.3% to 80% for showers, 2.6% to 69% for bathtubs, 18% to 100% for dishwashers, and 3.8% to 100% for washing machines. Acetone and cyclohexane al

  1. Reduced bleed air extraction for DC-10 cabin air conditioning

    NASA Technical Reports Server (NTRS)

    Newman, W. H.; Viele, M. R.; Hrach, F. J.

    1980-01-01

    It is noted that a significant fuel savings can be achieved by reducing bleed air used for cabin air conditioning. Air in the cabin can be recirculated to maintain comfortable ventilation rates but the quality of the air tends to decrease due to entrainment of smoke and odors. Attention is given to a development system designed and fabricated under the NASA Engine Component Improvement Program to define the recirculation limit for the DC-10. It is shown that with the system, a wide range of bleed air reductions and recirculation rates is possible. A goal of 0.8% fuel savings has been achieved which results from a 50% reduction in bleed extraction from the engine.

  2. Impact of surface disinfection and sterile draping of furniture on room air quality in a cardiac procedure room with a ventilation and air-conditioning system (extrusion airflow, cleanroom class 1b (DIN 1946-4)).

    PubMed

    Below, Harald; Ryll, Sylvia; Empen, Klaus; Dornquast, Tina; Felix, Stefan; Rosenau, Heike; Kramer, Sebastian; Kramer, Axel

    2010-09-21

    In a cardiac procedure room, ventilated by a ventilation and air-conditioning system with turbulent mixed airflow, a protection zone in the operating area could be defined through visualization of airflows. Within this protection zone, no turbulence was detectable in the room air.Under the given conditions, disinfection of all surfaces including all furniture and equipment after the last operation and subsequent draping of furniture and all equipment that could not be removed from the room with sterile surgical drapes improved the indoor room air quality from cleanroom class C to cleanroom class B. This also allows procedures with elevated requirements to be performed in room class 1b.

  3. Impact of surface disinfection and sterile draping of furniture on room air quality in a cardiac procedure room with a ventilation and air-conditioning system (extrusion airflow, cleanroom class 1b (DIN 1946-4))

    PubMed Central

    Below, Harald; Ryll, Sylvia; Empen, Klaus; Dornquast, Tina; Felix, Stefan; Rosenau, Heike; Kramer, Sebastian; Kramer, Axel

    2010-01-01

    In a cardiac procedure room, ventilated by a ventilation and air-conditioning system with turbulent mixed airflow, a protection zone in the operating area could be defined through visualization of airflows. Within this protection zone, no turbulence was detectable in the room air. Under the given conditions, disinfection of all surfaces including all furniture and equipment after the last operation and subsequent draping of furniture and all equipment that could not be removed from the room with sterile surgical drapes improved the indoor room air quality from cleanroom class C to cleanroom class B. This also allows procedures with elevated requirements to be performed in room class 1b. PMID:20941336

  4. Talaromyces rubrifaciens, a new species discovered from heating, ventilation and air conditioning systems in China.

    PubMed

    Luo, Yi; Lu, Xiaohong; Bi, Wu; Liu, Fan; Gao, Weiwei

    2016-01-01

    A new Talaromyces species, T. rubrifaciens, was isolated from supply air outlets of heating, ventilation and air conditioning (HVAC) systems in three kinds of public building in Beijing and Nanjing, China. Morphologically it exhibits many characters of section Trachyspermi but is distinguished from other species of this section by restricted growth and broad and strictly biverticillate conidiophores. Phylogenetic analyses based on the internal transcribed spacer rDNA (ITS), β-tubulin (BenA), calmodulin (CaM) and RNA polymerase second largest subunit (RPB2) genes reveal that T. rubrifaciens is a distinct species in section Trachyspermi. © 2016 by The Mycological Society of America.

  5. Transmission of Mycobacterium chimaera from Heater–Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System

    PubMed Central

    Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P.

    2016-01-01

    Heater–cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices. PMID:27070958

  6. Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System.

    PubMed

    Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P; Sax, Hugo

    2016-06-01

    Heater-cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices.

  7. Multifamily Individual Heating and Ventilation Systems, Lawrence, Massachusetts (Fact Sheet)

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Not Available

    The conversion of an older Massachusetts building into condominiums illustrates a safe, durable, and cost-effective solution for heating and ventilation systems that can potentially benefit millions of multifamily buildings. Merrimack Valley Habitat for Humanity (MVHfH) partnered with U.S. Department of Energy Building America team Building Science Corporation (BSC) to provide high performance affordable housing for 10 families in the retrofit of an existing mass masonry building (a former convent). The original ventilation design for the project was provided by a local engineer and consisted of a single large heat recovery ventilator (HRV) located in a mechanical room in the basementmore » with a centralized duct system providing supply air to the main living space and exhausting stale air from the single bathroom in each apartment. This design was deemed to be far too costly to install and operate for several reasons: the large central HRV was oversized and the specified flows to each apartment were much higher than the ASHRAE 62.2 rate; an extensive system of ductwork, smoke and fire dampers, and duct chases were specified; ductwork required a significant area of dropped ceilings; and the system lacked individual ventilation control in the apartments« less

  8. Mobile laminar air flow screen for additional operating room ventilation: reduction of intraoperative bacterial contamination during total knee arthroplasty.

    PubMed

    Sossai, D; Dagnino, G; Sanguineti, F; Franchin, F

    2011-12-01

    Surgical site infections are important complications in orthopedic surgery. A mobile laminar air flow (LAF) screen could represent a useful addition to an operating room (OR) with conventional turbulent air ventilation (12.5 air changes/h), as it could decrease the bacterial count near the operating field. The purpose of this study was to evaluate LAF efficacy at reducing bacterial contamination in the surgical area during 34 total knee arthroplasties (TKAs). The additional unit was used in 17 operations; the LAF was positioned beside the operating table between two of the surgeons, with the air flow directed towards the surgical area (wound). The whole team wore conventional OR clothing and the correct hygiene procedures and rituals were used. Bacterial air contamination (CFU/m(3)) was evaluated in the wound area in 17 operations with the LAF unit and 17 without the LAF unit. The LAF unit reduced the mean bacterial count in the wound area from 23.5 CFU/m(3) without the LAF to 3.5 CFU/m(3) with the LAF (P < 0.0001), which is below the suggested limit for an OR with ultraclean laminar ventilation. There were no significant differences in the mean bacterial count in the instrument table area: 28.6 CFU/m(3) were recorded with the LAF (N = 6) unit and 30.8 CFU/m(3) (N = 6) without the LAF unit (P = 0.631). During six operations with LAF and six without LAF, particle counts were performed and the number of 0.5 μm particles was analyzed. The particle counts decreased significantly when the LAF unit was used (P = 0.003). When a mobile LAF unit was added to the standard OR ventilation, bacterial contamination of the wound area significantly decreased to below the accepted level for an ultraclean OR, preventing SSI infections.

  9. Ventilation requirements in buildings—I. Control of occupancy odor and tobacco smoke odor

    NASA Astrophysics Data System (ADS)

    Cain, William S.; Leaderer, Brian P.; Isseroff, Ruth; Berglund, Larry G.; Huey, Raymond J.; Lipsitt, Eric D.; Perlman, Dan

    Psychophysical measurements of odor, supplemented with certain physical measurements, were taken to examine ventilation requirements during smoking and nonsmoking occupancy in an environmental chamber. The facility provided the means to compare impressions of visitors (persons who inhaled air from the chamber only briefly) with impressions of occupants. For nonsmoking occupancy, 47 combinations of temperature, humidity, ventilation rate and occupancy density were examined. Odor level depended entirely on ventilation rate per person irrespective of the number of persons in the chamber. The ventilation necessary to satisfy 75 % of visitors equalled only about 4 ℓ s -1 per person. Occupants, however, were satisfied with far less. In an array of 38 conditions of smoking occupancy, the ventilation deemed necessary to satisfy 75 % of visitors under customary conditions of occupancy equalled 17.5 ℓ s -1 per person. For both smoking and nonsmoking conditions, a combination of high temperature (25.5°C) and humidity (r.h. > 70 %) exacerbated the odor problem. During smoking, carbon monoxide rarely reached dangerous levels, but suspended particulate matter often reached levels considered unacceptable outdoors. The results highlight the energy penalty incurred in ventilation for smoking occupancy.

  10. Chlorhexidine and tooth-brushing as prevention strategies in reducing ventilator-associated pneumonia rates.

    PubMed

    Roberts, Nesta; Moule, Pam

    2011-01-01

    Ventilator-associated pneumonia (VAP) is a common complication of mechanical ventilation after endotracheal intubation. The role of chlorhexidine and tooth-brushing has been considered as a clinical intervention to reduce infection rates, however, evidence to inform this needs appraising. This paper presents a critical review on the effect of chlorhexidine gluconate (CHX) and tooth-brushing in decreasing rates of VAP in mechanically ventilated adult patients cared for in intensive care settings. A literature search was conducted using a number of bibliographic databases (n = 6). A number of parameters were used to exclude irrelevant papers. A total n = 17 papers were located and accessed, which were directly related to the field. Eight studies that met the criteria and addressed the study aims were reviewed. CHX was successful in reducing the rate of VAP and using a combination of CHX and colistine resulted in better oropharyngeal decontamination which reduced and delayed VAP. Chlorhexidine was also effective in reducing dental plaque in patients cared for in intensive care and had the potential to reduce nosocomial infections. Results of studies investigating the use of tooth-brushing in reducing VAP incidence proved inconsistent, although all recommend tooth-brushing as important in maintaining good oral hygiene. The use of chlorhexidine has been proven to be of some value in reducing VAP, although may be more effective when used with a solution which targets gram-negative bacteria. Tooth-brushing is recommended in providing a higher standard of oral care to mechanically ventilated patients and reducing VAP when used with chlorhexidine. However, limitations in study design and inconsistency in results suggest that further research is required into the effects of tooth-brushing. © 2011 The Authors. Nursing in Critical Care © 2011 British Association of Critical Care Nurses.

  11. Indoor Environmental Quality in Mechanically Ventilated, Energy-Efficient Buildings vs. Conventional Buildings.

    PubMed

    Wallner, Peter; Munoz, Ute; Tappler, Peter; Wanka, Anna; Kundi, Michael; Shelton, Janie F; Hutter, Hans-Peter

    2015-11-06

    Energy-efficient buildings need mechanical ventilation. However, there are concerns that inadequate mechanical ventilation may lead to impaired indoor air quality. Using a semi-experimental field study, we investigated if exposure of occupants of two types of buildings (mechanical vs. natural ventilation) differs with regard to indoor air pollutants and climate factors. We investigated living and bedrooms in 123 buildings (62 highly energy-efficient and 61 conventional buildings) built in the years 2010 to 2012 in Austria (mainly Vienna and Lower Austria). Measurements of indoor parameters (climate, chemical pollutants and biological contaminants) were conducted twice. In total, more than 3000 measurements were performed. Almost all indoor air quality and room climate parameters showed significantly better results in mechanically ventilated homes compared to those relying on ventilation from open windows and/or doors. This study does not support the hypothesis that occupants in mechanically ventilated low energy houses are exposed to lower indoor air quality.

  12. Brain Cooling With Ventilation of Cold Air Over Respiratory Tract in Newborn Piglets: An Experimental and Numerical Study

    PubMed Central

    Bakhsheshi, Mohammad Fazel; Moradi, Hadi Vafadar; Stewart, Errol E.; Keenliside, Lynn; Lee, Ting-Yim

    2015-01-01

    We investigate thermal effects of pulmonary cooling which was induced by cold air through an endotracheal tube via a ventilator on newborn piglets. A mathematical model was initially employed to compare the thermal impact of two different gas mixtures, O2-medical air (1:2) and O2-Xe (1:2), across the respiratory tract and within the brain. Following mathematical simulations, we examined the theoretical predictions with O2-medical air condition on nine anesthetized piglets which were randomized to two treatment groups: 1) control group (\\documentclass[12pt]{minimal} \\usepackage{amsmath} \\usepackage{wasysym} \\usepackage{amsfonts} \\usepackage{amssymb} \\usepackage{amsbsy} \\usepackage{upgreek} \\usepackage{mathrsfs} \\setlength{\\oddsidemargin}{-69pt} \\begin{document} }{}$n = 4$ \\end{document}) and 2) pulmonary cooling group (\\documentclass[12pt]{minimal} \\usepackage{amsmath} \\usepackage{wasysym} \\usepackage{amsfonts} \\usepackage{amssymb} \\usepackage{amsbsy} \\usepackage{upgreek} \\usepackage{mathrsfs} \\setlength{\\oddsidemargin}{-69pt} \\begin{document} }{}$n = 5$ \\end{document}). Numerical and experimental results using O2-medical air mixture show that brain temperature fell from 38.5 °C and 38.3 °C ± 0.3 °C to 35.7 °C ± 0.9 °C and 36.5 °C ± 0.6 °C during 3 h cooling which corresponded to a mean cooling rate of 0.9 °C/h ± 0.2 °C/h and 0.6 °C/h ± 0.1 °C/h, respectively. According to the numerical results, decreasing the metabolic rate and increasing air velocity are helpful to maximize the cooling effect. We demonstrated that pulmonary cooling by cooling of inhalation gases immediately before they enter the trachea can slowly reduce brain and core body temperature of newborn piglets. Numerical simulations show no significant differences between two different inhaled conditions, i.e., O2-medical air (1:2) and O2-Xe (1:2) with respect to cooling rate. PMID:27170888

  13. Characteristics of Resting Metabolic Rate in Critically Ill, Mechanically Ventilated Adults With Cystic Fibrosis.

    PubMed

    Frankenfield, David C; Ashcraft, Christine M; Drasher, Tammy L; Reid, Elizabeth K; Vender, Robert L

    2017-05-01

    Critically ill patients with cystic fibrosis may be especially sensitive to the negative consequences of overfeeding and underfeeding, yet there is almost no information available about the energy needs of these patients. The purpose of this study was to characterize the metabolic rate of critically ill adult patients with cystic fibrosis requiring mechanical ventilation. This was an observational study in which the resting metabolic rate, oxygen consumption, and carbon dioxide production of adult patients with cystic fibrosis requiring critical care, sedation, and mechanical ventilation were measured with indirect calorimetry. This group was compared with a cohort of adult critical care patients without cystic fibrosis. Twelve patients with cystic fibrosis were identified and measured. These were compared with a control group of 25 critically ill patients. Both groups were underweight (body mass index, 17.4 ± 4.0 kg/m 2 in cystic fibrosis and 18.4 ± 2.3 kg/m 2 in control). Adjusting for differences in age, sex, height, and weight, there was no difference in resting metabolic rate between the cystic fibrosis and control groups (1702 ± 193 vs 1642 ± 194 kcal/d, P = .388). Measured resting metabolic rate matched predicted values 58% of the time in cystic fibrosis and 60% of the time in control. The resting metabolic rate of sedated adult patients with cystic fibrosis being assisted with mechanical ventilation is not different from that of adult critical care patients without cystic fibrosis. In both these underweight groups, accurate prediction of resting metabolic rate is difficult to obtain.

  14. Assessment of the Indoor Odour Impact in a Naturally Ventilated Room

    PubMed Central

    Eusebio, Lidia; Derudi, Marco; Capelli, Laura; Nano, Giuseppe; Sironi, Selena

    2017-01-01

    Indoor air quality influences people’s lives, potentially affecting their health and comfort. Nowadays, ventilation is the only technique commonly used for regulating indoor air quality. CO2 is the reference species considered in order to calculate the air exchange rates of indoor environments. Indeed, regarding air quality, the presence of pleasant or unpleasant odours can strongly influence the environmental comfort. In this paper, a case study of indoor air quality monitoring is reported. The indoor field tests were conducted measuring both CO2 concentration, using a photoacoustic multi-gas analyzer, and odour trends, using an electronic nose, in order to analyze and compare the information acquired. The indoor air monitoring campaign was run for a period of 20 working days into a university room. The work was focused on the determination of both CO2 and odour emission factors (OEF) emitted by the human activity and on the evaluation of the odour impact in a naturally ventilated room. The results highlighted that an air monitoring and recycling system based only on CO2 concentration and temperature measurements might be insufficient to ensure a good indoor air quality, whereas its performances could be improved by integrating the existing systems with an electronic nose for odour detection. PMID:28379190

  15. Potential risk for bacterial contamination in conventional reused ventilator systems and disposable closed ventilator-suction systems.

    PubMed

    Li, Ya-Chi; Lin, Hui-Ling; Liao, Fang-Chun; Wang, Sing-Siang; Chang, Hsiu-Chu; Hsu, Hung-Fu; Chen, Sue-Hsien; Wan, Gwo-Hwa

    2018-01-01

    Few studies have investigated the difference in bacterial contamination between conventional reused ventilator systems and disposable closed ventilator-suction systems. The aim of this study was to investigate the bacterial contamination rates of the reused and disposable ventilator systems, and the association between system disconnection and bacterial contamination of ventilator systems. The enrolled intubated and mechanically ventilated patients used a conventional reused ventilator system and a disposable closed ventilator-suction system, respectively, for a week; specimens were then collected from the ventilator circuit systems to evaluate human and environmental bacterial contamination. The sputum specimens from patients were also analyzed in this study. The detection rate of bacteria in the conventional reused ventilator system was substantially higher than that in the disposable ventilator system. The inspiratory and expiratory limbs of the disposable closed ventilator-suction system had higher bacterial concentrations than the conventional reused ventilator system. The bacterial concentration in the heated humidifier of the reused ventilator system was significantly higher than that in the disposable ventilator system. Positive associations existed among the bacterial concentrations at different locations in the reused and disposable ventilator systems, respectively. The predominant bacteria identified in the reused and disposable ventilator systems included Acinetobacter spp., Bacillus cereus, Elizabethkingia spp., Pseudomonas spp., and Stenotrophomonas (Xan) maltophilia. Both the reused and disposable ventilator systems had high bacterial contamination rates after one week of use. Disconnection of the ventilator systems should be avoided during system operation to decrease the risks of environmental pollution and human exposure, especially for the disposable ventilator system. ClinicalTrials.gov PRS / NCT03359148.

  16. Antibiotic consumption and ventilator-associated pneumonia rates, some parallelism but some discrepancies

    PubMed Central

    Póvoa, Pedro

    2017-01-01

    Ventilator-associated pneumonia (VAP) is a common infection in intensive care units (ICUs) but its clinical definition is neither sensitive nor specific and lacks accuracy and objectivity. New defining criteria were proposed in 2013 by the National Healthcare Safety Network (NHSN) in order to more accurately conduct surveillance and track prevention progress. Although there is a consistent trend towards a decrease in VAP incidence during the last decade, significant differences in VAP rates have been reported and are persistently lower in NHSN and other American reports (0.0 to 4.4 VAP per 1,000 ventilator-days in 2012) compared to the European Centre for Disease Prevention and Control (ECDC) data (10 VAP per 1,000 ventilator-days in 2014). In the United States, VAP has been proposed as an indicator of quality of care in public reporting, and the threat of financial penalties for this diagnosis has put pressure on hospitals to minimize VAP rates that may lead to artificial lower values, independently of patient care. Although prevention bundles may contribute for encouraging reductions in VAP incidence, both pathophysiologic and epidemiologic factors preclude a zero-VAP rate. It would be expected from the trend of reduction of VAP incidence that the consumption of antibiotics would also decrease in particular in those hospitals with lowest VAP rates. However, ICU reports show a steadily use of antibiotics for nosocomial pneumonia in 15% of patients and both ECDC and NHSN data on antibiotic consumption showed no significant trend. Knowledge of bacterial epidemiology and resistance profiles for each ICU has great relevance in order to understand trends of antibiotic use. The new NHSN criteria provide a more objective and quantitative data based VAP definition, including an antibiotic administration criterion, allowing, in theory, a more comprehensive assessment and a reportable benchmark of the observed VAP and antibiotic consumption variability. PMID:29264367

  17. Antibiotic consumption and ventilator-associated pneumonia rates, some parallelism but some discrepancies.

    PubMed

    Nora, David; Póvoa, Pedro

    2017-11-01

    Ventilator-associated pneumonia (VAP) is a common infection in intensive care units (ICUs) but its clinical definition is neither sensitive nor specific and lacks accuracy and objectivity. New defining criteria were proposed in 2013 by the National Healthcare Safety Network (NHSN) in order to more accurately conduct surveillance and track prevention progress. Although there is a consistent trend towards a decrease in VAP incidence during the last decade, significant differences in VAP rates have been reported and are persistently lower in NHSN and other American reports (0.0 to 4.4 VAP per 1,000 ventilator-days in 2012) compared to the European Centre for Disease Prevention and Control (ECDC) data (10 VAP per 1,000 ventilator-days in 2014). In the United States, VAP has been proposed as an indicator of quality of care in public reporting, and the threat of financial penalties for this diagnosis has put pressure on hospitals to minimize VAP rates that may lead to artificial lower values, independently of patient care. Although prevention bundles may contribute for encouraging reductions in VAP incidence, both pathophysiologic and epidemiologic factors preclude a zero-VAP rate. It would be expected from the trend of reduction of VAP incidence that the consumption of antibiotics would also decrease in particular in those hospitals with lowest VAP rates. However, ICU reports show a steadily use of antibiotics for nosocomial pneumonia in 15% of patients and both ECDC and NHSN data on antibiotic consumption showed no significant trend. Knowledge of bacterial epidemiology and resistance profiles for each ICU has great relevance in order to understand trends of antibiotic use. The new NHSN criteria provide a more objective and quantitative data based VAP definition, including an antibiotic administration criterion, allowing, in theory, a more comprehensive assessment and a reportable benchmark of the observed VAP and antibiotic consumption variability.

  18. Achieving 'excellent' indoor air quality in commercial offices equipped with air-handling unit--respirable suspended particulate.

    PubMed

    Lam, K S; Chan, F S; Fung, W Y; Lui, B S S; Lau, L W L

    2006-04-01

    A study was carried out to investigate the feasibility of achieving ultra low respirable suspended particulates (RSP) in commercial offices without major modification of existing ventilation systems by enhancing the particulates removal efficiency of existing central ventilation systems. Four types of filters which include pre-filters, cartridge filters, bag filters and high efficiency particulates air (HEPA) filters were tested in a commercial building in Causeway Bay. The results show that an RSP objective of <20 microg/m3 could be met by removing RSP from both the return air and outdoor air supply simultaneously. This level of performance is classed as 'excellent' by the Hong Kong Government, Environmental Protection Department. Filters with efficiency that exceed 80% placed both in the return air and outdoor air were sufficient to meet the objective. It is not necessary to install HEPA filters to achieve the 'excellent' class. The outdoor air filter has great influence on the steady state indoor RSP concentration while the effective cleaning rate is governed by the return air filter. Higher efficiency filters increased the static drop but the volume flow of the air fan was not affected significantly. The additional cost incurred was <5% of the existing operation cost. This paper reports a field study of RSP control for an indoor office environment. The results are directly applicable to building service engineering in the design of ventilation systems using air-handling units. Field observations indicated that indoor RSP in an office environment could be suppressed below 20 microg/m3 within 1 h by the simultaneous filtration of outdoor air and return air. Outdoor air filtration has a great influence on the steady state indoor concentration and return air filtration governs the cleaning rate. It is believed that the results of this study could be extended to the cleaning of other indoor pollutants such as volatile organic compounds.

  19. Utilization of ventilation air methane as a supplementary fuel at a circulating fluidized bed combustion boiler.

    PubMed

    You, Changfu; Xu, Xuchang

    2008-04-01

    Ventilation air methane (VAM) accounts for 60-80% of the total emissions from coal mining activities in China, which is of serious greenhouse gas concerns as well as a waste of valuable fuel sources. This contribution evaluates the use of the VAM utilization methods as a supplementary fuel at a circulating fluidized bed combustion boiler. The paper describes the system design and discusses some potential technical challenges such as methane oxidation rate, corrosion, and efficiency. Laboratory experimentation has shown that the VAM can be burnt completely in circulated fluidized bed furnaces, and the VAM oxidation does not obviously affect the boiler operation when the methane concentration is less than 0.6%. The VAM decreased the incomplete combustion loss for the circulating fluidized bed combustion furnace. The economic benefit from the coal saving insures that the proposed system is more economically feasible.

  20. Contaminants in ventilated filling boxes

    NASA Astrophysics Data System (ADS)

    Bolster, D. T.; Linden, P. F.

    While energy efficiency is important, the adoption of energy-efficient ventilation systems still requires the provision of acceptable indoor air quality. Many low-energy systems, such as displacement or natural ventilation, rely on temperature stratification within the interior environment, always extracting the warmest air from the top of the room. Understanding buoyancy-driven convection in a confined ventilated space is key to understanding the flow that develops with many of these modern low-energy ventilation schemes. In this work we study the transport of an initially uniformly distributed passive contaminant in a displacement-ventilated space. Representing a heat source as an ideal sourced of buoyancy, analytical and numerical models are developed that allow us to compare the average efficiency of contaminant removal between traditional mixing and modern low-energy systems. A set of small-scale analogue laboratory experiments was also conducted to further validate our analytical and numerical solutions.We find that on average traditional and low-energy ventilation methods are similar with regard to pollutant flushing efficiency. This is because the concentration being extracted from the system at any given time is approximately the same for both systems. However, very different vertical concentration gradients exist. For the low-energy system, a peak in contaminant concentration occurs at the temperature interface that is established within the space. This interface is typically designed to sit at some intermediate height in the space. Since this peak does not coincide with the extraction point, displacement ventilation does not offer the same benefits for pollutant flushing as it does for buoyancy removal.

  1. Bench performance of ventilators during simulated paediatric ventilation.

    PubMed

    Park, M A J; Freebairn, R C; Gomersall, C D

    2013-05-01

    This study compares the accuracy and capabilities of various ventilators using a paediatric acute respiratory distress syndrome lung model. Various compliance settings and respiratory rate settings were used. The study was done in three parts: tidal volume and FiO2 accuracy; pressure control accuracy and positive end-expiratory pressure (PEEP) accuracy. The parameters set on the ventilator were compared with either or both of the measured parameters by the test lung and the ventilator. The results revealed that none of the ventilators could consistently deliver tidal volumes within 1 ml/kg of the set tidal volume, and the discrepancy between the delivered volume and the volume measured by the ventilator varied greatly. The target tidal volume was 8 ml/kg, but delivered tidal volumes ranged from 3.6-11.4 ml/kg and the volumes measured by the ventilator ranged from 4.1-20.6 ml/kg. All the ventilators maintained pressure within 20% of the set pressure, except one ventilator which delivered pressures of up to 27% higher than the set pressure. Two ventilators maintained PEEP within 10% of the prescribed PEEP. The majority of the readings were also within 10%. However, three ventilators delivered, at times, PEEPs over 20% higher. In conclusion, as lung compliance decreases, especially in paediatric patients, some ventilators perform better than others. This study highlights situations where ventilators may not be able to deliver, nor adequately measure, set tidal volumes, pressure, PEEP or FiO2.

  2. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... 14 Aeronautics and Space 4 2014-01-01 2014-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking whenever...

  3. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2013 CFR

    2013-01-01

    ... 14 Aeronautics and Space 4 2013-01-01 2013-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking whenever...

  4. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2011 CFR

    2011-01-01

    ... 14 Aeronautics and Space 4 2011-01-01 2011-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking whenever...

  5. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... 14 Aeronautics and Space 4 2012-01-01 2012-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking whenever...

  6. 14 CFR 252.9 - Ventilation systems.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 14 Aeronautics and Space 4 2010-01-01 2010-01-01 false Ventilation systems. 252.9 Section 252.9 Aeronautics and Space OFFICE OF THE SECRETARY, DEPARTMENT OF TRANSPORTATION (AVIATION PROCEEDINGS) ECONOMIC REGULATIONS SMOKING ABOARD AIRCRAFT § 252.9 Ventilation systems. Air carriers shall prohibit smoking whenever...

  7. Effect of forced-air warming on the performance of operating theatre laminar flow ventilation.

    PubMed

    Dasari, K B; Albrecht, M; Harper, M

    2012-03-01

    Forced-air warming exhaust may disrupt operating theatre airflows via formation of convection currents, which depends upon differences in exhaust and operating room air temperatures. We investigated whether the floor-to-ceiling temperatures around a draped manikin in a laminar-flow theatre differed when using three types of warming devices: a forced-air warming blanket (Bair Hugger™); an over-body conductive blanket (Hot Dog™); and an under-body resistive mattress (Inditherm™). With forced-air warming, mean (SD) temperatures were significantly elevated over the surgical site vs those measured with the conductive blanket (+2.73 (0.7) °C; p<0.001) or resistive mattress (+3.63 (0.7) °C; p<0.001). Air temperature differences were insignificant between devices at floor (p=0.339), knee (p=0.799) and head height levels (p=0.573). We conclude that forced-air warming generates convection current activity in the vicinity of the surgical site. The clinical concern is that these currents may disrupt ventilation airflows intended to clear airborne contaminants from the surgical site. Anaesthesia © 2012 The Association of Anaesthetists of Great Britain and Ireland.

  8. Correlation between alveolar ventilation and electrical properties of lung parenchyma.

    PubMed

    Roth, Christian J; Ehrl, Andreas; Becher, Tobias; Frerichs, Inéz; Schittny, Johannes C; Weiler, Norbert; Wall, Wolfgang A

    2015-06-01

    One key problem in modern medical imaging is linking measured data and actual physiological quantities. In this article we derive such a link between the electrical bioimpedance of lung parenchyma, which can be measured by electrical impedance tomography (EIT), and the magnitude of regional ventilation, a key to understanding lung mechanics and developing novel protective ventilation strategies. Two rat-derived three-dimensional alveolar microstructures obtained from synchrotron-based x-ray tomography are each exposed to a constant potential difference for different states of ventilation in a finite element simulation. While the alveolar wall volume remains constant during stretch, the enclosed air volume varies, similar to the lung volume during ventilation. The enclosed air, serving as insulator in the alveolar ensemble, determines the resulting current and accordingly local tissue bioimpedance. From this we can derive a relationship between lung tissue bioimpedance and regional alveolar ventilation. The derived relationship shows a linear dependence between air content and tissue impedance and matches clinical data determined from a ventilated patient at the bedside.

  9. The impact of a ventilator bundle on preventing ventilator-associated pneumonia: a multicenter study.

    PubMed

    Eom, Joong Sik; Lee, Mi-Suk; Chun, Hee-Kyung; Choi, Hee Jung; Jung, Sun-Young; Kim, Yeon-Sook; Yoon, Seon Jin; Kwak, Yee Gyung; Oh, Gang-Bok; Jeon, Min-Hyok; Park, Sun-Young; Koo, Hyun-Sook; Ju, Young-Su; Lee, Jin Seo

    2014-01-01

    For prevention of ventilator-associated pneumonia (VAP), a bundle approach was applied to patients receiving mechanical ventilation in intensive care units. The incidence of VAP and the preventive efficacy of the VAP bundle were investigated. A quasi-experimental study was conducted in adult intensive care units of 6 university hospitals with similar VAP rates. We implemented the VAP bundle between March 2011 and June 2011, then compared the rate of VAP after implementation of the VAP bundle with the rate in the previous 8 months. Our ventilator bundle included head of bed elevation, peptic ulcer disease prophylaxis, deep venous thrombosis prophylaxis, and oral decontamination with chlorhexidine 0.12%. Continuous aspiration of subglottic secretions was an option. Implementation of the VAP bundle reduced the VAP rate from a mean of 4.08 cases per 1,000 ventilator-days to 1.16 cases per 1,000 ventilator-days. The incidence density ratio (rate) was 0.28 (95% confidence interval, 0.275-0.292). Implementing the appropriate VAP bundle significantly decreased the incidence of VAP in patients with mechanical ventilation. Copyright © 2014 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Mosby, Inc. All rights reserved.

  10. Potential risk for bacterial contamination in conventional reused ventilator systems and disposable closed ventilator-suction systems

    PubMed Central

    Li, Ya-Chi; Lin, Hui-Ling; Liao, Fang-Chun; Wang, Sing-Siang; Chang, Hsiu-Chu; Hsu, Hung-Fu; Chen, Sue-Hsien

    2018-01-01

    Background Few studies have investigated the difference in bacterial contamination between conventional reused ventilator systems and disposable closed ventilator-suction systems. The aim of this study was to investigate the bacterial contamination rates of the reused and disposable ventilator systems, and the association between system disconnection and bacterial contamination of ventilator systems. Methods The enrolled intubated and mechanically ventilated patients used a conventional reused ventilator system and a disposable closed ventilator-suction system, respectively, for a week; specimens were then collected from the ventilator circuit systems to evaluate human and environmental bacterial contamination. The sputum specimens from patients were also analyzed in this study. Results The detection rate of bacteria in the conventional reused ventilator system was substantially higher than that in the disposable ventilator system. The inspiratory and expiratory limbs of the disposable closed ventilator-suction system had higher bacterial concentrations than the conventional reused ventilator system. The bacterial concentration in the heated humidifier of the reused ventilator system was significantly higher than that in the disposable ventilator system. Positive associations existed among the bacterial concentrations at different locations in the reused and disposable ventilator systems, respectively. The predominant bacteria identified in the reused and disposable ventilator systems included Acinetobacter spp., Bacillus cereus, Elizabethkingia spp., Pseudomonas spp., and Stenotrophomonas (Xan) maltophilia. Conclusions Both the reused and disposable ventilator systems had high bacterial contamination rates after one week of use. Disconnection of the ventilator systems should be avoided during system operation to decrease the risks of environmental pollution and human exposure, especially for the disposable ventilator system. Trial registration Clinical

  11. Nasal mask ventilation is better than face mask ventilation in edentulous patients.

    PubMed

    Kapoor, Mukul Chandra; Rana, Sandeep; Singh, Arvind Kumar; Vishal, Vindhya; Sikdar, Indranil

    2016-01-01

    Face mask ventilation of the edentulous patient is often difficult as ineffective seating of the standard mask to the face prevents attainment of an adequate air seal. The efficacy of nasal ventilation in edentulous patients has been cited in case reports but has never been investigated. Consecutive edentulous adult patients scheduled for surgery under general anesthesia with endotracheal intubation, during a 17-month period, were prospectively evaluated. After induction of anesthesia and administration of neuromuscular blocker, lungs were ventilated with a standard anatomical face mask of appropriate size, using a volume controlled anesthesia ventilator with tidal volume set at 10 ml/kg. In case of inadequate ventilation, the mask position was adjusted to achieve best-fit. Inspired and expired tidal volumes were measured. Thereafter, the face mask was replaced by a nasal mask and after achieving best-fit, the inspired and expired tidal volumes were recorded. The difference in expired tidal volumes and airway pressures at best-fit with the use of the two masks and number of patients with inadequate ventilation with use of the masks were statistically analyzed. A total of 79 edentulous patients were recruited for the study. The difference in expiratory tidal volumes with the use of the two masks at best-fit was statistically significant (P = 0.0017). Despite the best-fit mask placement, adequacy of ventilation could not be achieved in 24.1% patients during face mask ventilation, and 12.7% patients during nasal mask ventilation and the difference was statistically significant. Nasal mask ventilation is more efficient than standard face mask ventilation in edentulous patients.

  12. Natural ventilation for the prevention of airborne contagion.

    PubMed

    Escombe, A Roderick; Oeser, Clarissa C; Gilman, Robert H; Navincopa, Marcos; Ticona, Eduardo; Pan, William; Martínez, Carlos; Chacaltana, Jesus; Rodríguez, Richard; Moore, David A J; Friedland, Jon S; Evans, Carlton A

    2007-02-01

    Institutional transmission of airborne infections such as tuberculosis (TB) is an important public health problem, especially in resource-limited settings where protective measures such as negative-pressure isolation rooms are difficult to implement. Natural ventilation may offer a low-cost alternative. Our objective was to investigate the rates, determinants, and effects of natural ventilation in health care settings. The study was carried out in eight hospitals in Lima, Peru; five were hospitals of "old-fashioned" design built pre-1950, and three of "modern" design, built 1970-1990. In these hospitals 70 naturally ventilated clinical rooms where infectious patients are likely to be encountered were studied. These included respiratory isolation rooms, TB wards, respiratory wards, general medical wards, outpatient consulting rooms, waiting rooms, and emergency departments. These rooms were compared with 12 mechanically ventilated negative-pressure respiratory isolation rooms built post-2000. Ventilation was measured using a carbon dioxide tracer gas technique in 368 experiments. Architectural and environmental variables were measured. For each experiment, infection risk was estimated for TB exposure using the Wells-Riley model of airborne infection. We found that opening windows and doors provided median ventilation of 28 air changes/hour (ACH), more than double that of mechanically ventilated negative-pressure rooms ventilated at the 12 ACH recommended for high-risk areas, and 18 times that with windows and doors closed (p < 0.001). Facilities built more than 50 years ago, characterised by large windows and high ceilings, had greater ventilation than modern naturally ventilated rooms (40 versus 17 ACH; p < 0.001). Even within the lowest quartile of wind speeds, natural ventilation exceeded mechanical (p < 0.001). The Wells-Riley airborne infection model predicted that in mechanically ventilated rooms 39% of susceptible individuals would become infected following

  13. Natural ventilation of buildings: opposing wind and buoyancy

    NASA Astrophysics Data System (ADS)

    Linden, Paul; Hunt, Gary

    1998-11-01

    The use of natural ventilation in buildings is an attractive way to reduce energy usage thereby reducing costs and CO2 emissions. Generally, it is necessary to remove excess heat from a building and the designer can use the buoyancy forces associated with the above ambient temperatures within the building to drive a flow - 'stack' ventilation. The most efficient mode is displacement ventilation where warm air accumulates near the top of the building and flows out through upper level vents and cooler air flows in at lower levels. Ventilation will also be driven between these lower and upper openings by the wind. We report on laboratory modeling and theory which investigates the effects of an opposing wind on stack ventilation driven by a constant source of heat within a space under displacement ventilation. We show that there is a critical wind speed, expressed in dimensionless terms as a critical Froude number, above which displacement ventilation is replaced by (less efficient) mixing ventilation with reversed flow. Below this critical speed, displacement ventilation, in which the interior has a two-layer stratification, is maintained. The criterion for the change in ventilation mode is derived from general considerations of mixing efficiencies in stratified flows. We conclude that even when wind effects might appear to be dominant, the inhibition of mixing by the stable stratification within the space ensures that stack ventilation can operate over a wide range of apparently adverse conditions.

  14. Coal-Packed Methane Biofilter for Mitigation of Green House Gas Emissions from Coal Mine Ventilation Air

    PubMed Central

    Limbri, Hendy; Gunawan, Cindy; Thomas, Torsten; Smith, Andrew; Scott, Jason; Rosche, Bettina

    2014-01-01

    Methane emitted by coal mine ventilation air (MVA) is a significant greenhouse gas. A mitigation strategy is the oxidation of methane to carbon dioxide, which is approximately twenty-one times less effective at global warming than methane on a mass-basis. The low non-combustible methane concentrations at high MVA flow rates call for a catalytic strategy of oxidation. A laboratory-scale coal-packed biofilter was designed and partially removed methane from humidified air at flow rates between 0.2 and 2.4 L min−1 at 30°C with nutrient solution added every three days. Methane oxidation was catalysed by a complex community of naturally-occurring microorganisms, with the most abundant member being identified by 16S rRNA gene sequence as belonging to the methanotrophic genus Methylocystis. Additional inoculation with a laboratory-grown culture of Methylosinus sporium, as investigated in a parallel run, only enhanced methane consumption during the initial 12 weeks. The greatest level of methane removal of 27.2±0.66 g methane m−3 empty bed h−1 was attained for the non-inoculated system, which was equivalent to removing 19.7±2.9% methane from an inlet concentration of 1% v/v at an inlet gas flow rate of 1.6 L min−1 (2.4 min empty bed residence time). These results show that low-cost coal packing holds promising potential as a suitable growth surface and contains methanotrophic microorganisms for the catalytic oxidative removal of methane. PMID:24743729

  15. Development of an Outdoor Temperature-Based Control Algorithm for Residential Mechanical Ventilation Control

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Less, Brennan; Walker, Iain; Tang, Yihuan

    2014-06-01

    Smart ventilation systems use controls to ventilate more during those periods that provide either an energy or IAQ advantage (or both) and less during periods that provide a dis advantage. Using detailed building simulations, this study addresses one of the simplest and lowest cost types of smart controllers —outdoor temperature- based control. If the outdoor temperature falls below a certain cut- off, the fan is simply turned off. T he main principle of smart ventilation used in this study is to shift ventilation from time periods with large indoor -outdoor temperature differences, to periods where these differences are smaller, andmore » their energy impacts are expected to be less. Energy and IAQ performance are assessed relative to a base case of a continuously operated ventilation fan sized to comply with ASHRAE 62.2-2013 whole house ventilation requirements. In order to satisfy 62.2-2013, annual pollutant exposure must be equivalent between the temperature controlled and continuous fan cases. This requires ventilation to be greater than 62.2 requirements when the ventilation system operates. This is achieved by increasing the mechanical ventilation system air flow rates.« less

  16. Non-invasive positive-pressure ventilation with positive end-expiratory pressure counteracts inward air leaks during preoxygenation: a randomised crossover controlled study in healthy volunteers.

    PubMed

    Hanouz, J-L; Le Gall, F; Gérard, J-L; Terzi, N; Normand, H

    2018-04-01

    During preoxygenation, the lack of tight fit between the mask and the patient's face results in inward air leak preventing effective preoxygenation. We hypothesized that non-invasive positive-pressure ventilation and positive end-expiratory pressure (PEEP) could counteract inward air leak. Healthy volunteers were randomly assigned to preoxygenated through spontaneous breathing without leak (SB), spontaneous breathing with a calibrated air leak (T-shaped piece between the mouth and the breathing system; SB-leak), or non-invasive positive inspiratory pressure ventilation (inspiratory support +6 cm H 2 O; PEEP +5 cm H 2 O) with calibrated leak (PPV-leak). The volunteers breathed through a mouthpiece connected to an anaesthesia ventilator. The expired oxygen fraction (FeO 2 ) and air-leak flow (ml s -1 ) were measured. The primary end point was the proportion of volunteers with FeO 2 >90% at 3 min. The secondary end points were FeO 2 at 3 min, time to reach FeO 2 of 90%, and the inspiratory air-leak flow. Twenty healthy volunteers were included. The proportion of volunteers with FeO 2 >90% at 3 min was 0% in the SB-leak group, 95% in the SB group, and 100% in the PPV-leak group (P<0.001). At 3 min, the mean [standard deviation (sd)] FeO 2 was 89 (1)%, 76 (1)%, and 90 (0)% in the SB, SB-leak, and PPV-leak groups, respectively (P<0.001). The mean (sd) inward air leak was 59 (12) ml s -1 in the SB-leak group, but 0 (0) ml s -1 in the PPV-leak group (P<0.001). Preoxygenation through non-invasive positive-pressure ventilation and PEEP provided effective preoxygenation despite an inward air leak. NCT03087825. Copyright © 2017 British Journal of Anaesthesia. Published by Elsevier Ltd. All rights reserved.

  17. Gas-phase organics in environmental tobacco smoke. 1. Effects of smoking rate, ventilation, and furnishing level on emission factors.

    PubMed

    Singer, Brett C; Hodgson, Alfred T; Guevarra, Karla S; Hawley, Elisabeth L; Nazaroff, William W

    2002-03-01

    We measured the emissions of 26 gas-phase organic compounds in environmental tobacco smoke (ETS) using a model room that simulates realistic conditions in residences and offices. Exposure-relevant emission factors (EREFs), which include the effects of sorption and re-emission over a 24-h period, were calculated by mass balance from measured compound concentrations and chamber ventilation rates in a 50-m3 room constructed and furnished with typical materials. Experiments were conducted at three smoking rates (5, 10, and 20 cigarettes day(-1)), three ventilation rates (0.3, 0.6, and 2 h(-1)), and three furnishing levels (wallboard with aluminum flooring, wallboard with carpet, and full furnishings). Smoking rate did not affect EREFs, suggesting that sorption was linearly related to gas-phase concentration. Furnishing level and ventilation rate in the model room had little effect on EREFs of several ETS compounds including 1,3-butadiene, acrolein, acrylonitrile, benzene, toluene, and styrene. However, sorptive losses at low ventilation with full furnishings reduced EREFs for the ETS tracers nicotine and 3-ethenylpyridine by as much as 90 and 65% as compared to high ventilation, wallboard/aluminum experiments. Likewise, sorptive losses were 40-70% for phenol, cresols, naphthalene, and methylnaphthalenes. Sorption persisted for many compounds; for example, almost all of the sorbed nicotine and most of the sorbed cresol remained sorbed 3 days after smoking. EREFs can be used in models and with ETS tracer-based methods to refine and improve estimates of exposures to ETS constituents.

  18. Effect of metronome rates on the quality of bag-mask ventilation during metronome-guided 30:2 cardiopulmonary resuscitation: A randomized simulation study.

    PubMed

    Na, Ji Ung; Han, Sang Kuk; Choi, Pil Cho; Shin, Dong Hyuk

    2017-01-01

    Metronome guidance is a feasible and effective feedback technique to improve the quality of cardiopulmonary resuscitation (CPR). The rate of the metronome should be set between 100 to 120 ticks/minute and the speed of ventilation may have crucial effect on the quality of ventilation. We compared three different metronome rates (100, 110, 120 ticks/minute) to investigate its effect on the quality of ventilation during metronome-guided 30:2 CPR. This is a prospective, randomized, crossover observational study using a RespiTrainer○ r . To simulate 30 chest compressions, one investigator counted from 1 to 30 in cadence with the metronome rate (1 count for every 1 tick), and the participant performed 2 consecutive ventilations immediately following the counting of 30. Thirty physicians performed 5 sets of 2 consecutive (total 10) bag-mask ventilations for each metronome rate. Participants were instructed to squeeze the bag over 2 ticks (1.0 to 1.2 seconds depending on the rate of metronome) and deflate the bag over 2 ticks. The sequence of three different metronome rates was randomized. Mean tidal volume significantly decreased as the metronome rate was increased from 110 ticks/minute to 120 ticks/minute (343±84 mL vs. 294±90 mL, P =0.004). Peak airway pressure significantly increased as metronome rate increased from 100 ticks/minute to 110 ticks/minute (18.7 vs. 21.6 mmHg, P =0.006). In metronome-guided 30:2 CPR, a higher metronome rate may adversely affect the quality of bag-mask ventilations. In cases of cardiac arrest where adequate ventilation support is necessary, 100 ticks/minute may be better than 110 or 120 ticks/minute to deliver adequate tidal volume during audio tone guided 30:2 CPR.

  19. Effect of metronome rates on the quality of bag-mask ventilation during metronome-guided 30:2 cardiopulmonary resuscitation: A randomized simulation study

    PubMed Central

    Na, Ji Ung; Han, Sang Kuk; Choi, Pil Cho; Shin, Dong Hyuk

    2017-01-01

    BACKGROUND: Metronome guidance is a feasible and effective feedback technique to improve the quality of cardiopulmonary resuscitation (CPR). The rate of the metronome should be set between 100 to 120 ticks/minute and the speed of ventilation may have crucial effect on the quality of ventilation. We compared three different metronome rates (100, 110, 120 ticks/minute) to investigate its effect on the quality of ventilation during metronome-guided 30:2 CPR. METHODS: This is a prospective, randomized, crossover observational study using a RespiTrainer○r. To simulate 30 chest compressions, one investigator counted from 1 to 30 in cadence with the metronome rate (1 count for every 1 tick), and the participant performed 2 consecutive ventilations immediately following the counting of 30. Thirty physicians performed 5 sets of 2 consecutive (total 10) bag-mask ventilations for each metronome rate. Participants were instructed to squeeze the bag over 2 ticks (1.0 to 1.2 seconds depending on the rate of metronome) and deflate the bag over 2 ticks. The sequence of three different metronome rates was randomized. RESULTS: Mean tidal volume significantly decreased as the metronome rate was increased from 110 ticks/minute to 120 ticks/minute (343±84 mL vs. 294±90 mL, P=0.004). Peak airway pressure significantly increased as metronome rate increased from 100 ticks/minute to 110 ticks/minute (18.7 vs. 21.6 mmHg, P=0.006). CONCLUSION: In metronome-guided 30:2 CPR, a higher metronome rate may adversely affect the quality of bag-mask ventilations. In cases of cardiac arrest where adequate ventilation support is necessary, 100 ticks/minute may be better than 110 or 120 ticks/minute to deliver adequate tidal volume during audio tone guided 30:2 CPR. PMID:28458759

  20. Particulate matter dynamics in naturally ventilated freestall dairy barns

    NASA Astrophysics Data System (ADS)

    Joo, H. S.; Ndegwa, P. M.; Heber, A. J.; Ni, J.-Q.; Bogan, B. W.; Ramirez-Dorronsoro, J. C.; Cortus, E. L.

    2013-04-01

    Particulate matter (PM) concentrations and ventilation rates, in two naturally ventilated freestall dairy barns, were continuously monitored for two years. The first barn (B1) housed 400 fresh lactating cows, while the second barn (B2) housed 835 non-fresh lactating cows and 15 bulls. The relationships between PM concentrations and accepted governing parameters (environmental conditions and cattle activity) were examined. In comparison with other seasons, PM concentrations were lowest in winter. Total suspended particulate (TSP) concentrations in spring and autumn were relatively higher than those in summer. Overall: the concentrations in the barns and ambient air, for all the PM categories (PM2.5, PM10, and TSP), exhibited non-normal positively skewed distributions, which tended to overestimate mean or average concentrations. Only concentrations of PM2.5 and PM10 increased with ambient air temperature (R2 = 0.60-0.82), whereas only concentrations of TSP increased with cattle activity. The mean respective emission rates of PM2.5, PM10, and TSP for the two barns ranged between 1.6-4.0, 11.9-15.0, and 48.7-52.5 g d-1 cow-1, indicating similar emissions from the two barns.

  1. Air pollution and human fertility rates.

    PubMed

    Nieuwenhuijsen, Mark J; Basagaña, Xavier; Dadvand, Payam; Martinez, David; Cirach, Marta; Beelen, Rob; Jacquemin, Bénédicte

    2014-09-01

    Some reports have suggested effects of air pollution on semen quality and success rates of in vitro fertilization (IVF) in humans and lower fertility rates in mice. However, no studies have evaluated the impact of air pollution on human fertility rates. We assessed the association between traffic related air pollution and fertility rates in humans in Barcelona, Spain (2011-2012). We hypothesized that higher air pollution levels would be associated with lower fertility rates. We calculated the general fertility rate which is the number of live births per 1000 women between the ages of 15 and 44 years per census tract. We used land use regression (LUR) modeling to estimate the air pollution concentrations (particulate matter, NO2/NOx) per census tract. We used Besag-York-Mollié models to quantify the relationship between air pollution and fertility rates with adjustment for a number of potential confounders such as maternal age and area level socio-economic status. We found a statistically significant reduction of fertility rates with an increase in traffic related air pollution levels, particularly for the coarse fraction of particulate matter (IRR=0.87 95% CI 0.82, 0.94 per IQR). This is the first study in humans to show an association between reduced fertility rates and higher traffic related air pollution levels. Copyright © 2014 Elsevier Ltd. All rights reserved.

  2. Quantification of Methane and Ammonia Emissions in a Naturally Ventilated Barn by Using Defined Criteria to Calculate Emission Rates.

    PubMed

    Schmithausen, Alexander J; Schiefler, Inga; Trimborn, Manfred; Gerlach, Katrin; Südekum, Karl-Heinz; Pries, Martin; Büscher, Wolfgang

    2018-05-16

    Extensive experimentation on individual animals in respiration chambers has already been carried out to evaluate the potential of dietary changes and opportunities to mitigate CH₄ emissions from ruminants. Although it is difficult to determine the air exchange rate of open barn spaces, measurements at the herd level should provide similarly reliable and robust results. The primary objective of this study was (1) to define a validity range (data classification criteria (DCC)) for the variables of wind velocity and wind direction during long-term measurements at barn level; and (2) to apply this validity range to a feeding trial in a naturally cross-flow ventilated dairy barn. The application of the DCC permitted quantification of CH₄ and NH₃ emissions during a feeding trial consisting of four periods. Differences between the control group (no supplement) and the experimental group fed a ration supplemented with condensed Acacia mearnsii tannins (CT) became apparent. Notably, CT concentrations of 1% and 3% of ration dry matter did not reduce CH₄ emissions. In contrast, NH₃ emissions decreased 34.5% when 3% CT was supplemented. The data confirm that quantification of trace gases in a naturally ventilated barn at the herd level is possible.

  3. Simultaneous measurement of ventilation using tracer gas techniques and VOC concentrations in homes, garages and vehicles.

    PubMed

    Batterman, Stuart; Jia, Chunrong; Hatzivasilis, Gina; Godwin, Chris

    2006-02-01

    Air exchange rates and interzonal flows are critical ventilation parameters that affect thermal comfort, air migration, and contaminant exposure in buildings and other environments. This paper presents the development of an updated approach to measure these parameters using perfluorocarbon tracer (PFT) gases, the constant injection rate method, and adsorbent-based sampling of PFT concentrations. The design of miniature PFT sources using hexafluorotoluene and octafluorobenzene tracers, and the development and validation of an analytical GC/MS method for these tracers are described. We show that simultaneous deployment of sources and passive samplers, which is logistically advantageous, will not cause significant errors over multiday measurement periods in building, or over shorter periods in rapidly ventilated spaces like vehicle cabins. Measurement of the tracers over periods of hours to a week may be accomplished using active or passive samplers, and low method detection limits (<0.025 microg m(-3)) and high precisions (<10%) are easily achieved. The method obtains the effective air exchange rate (AER), which is relevant to characterizing long-term exposures, especially when ventilation rates are time-varying. In addition to measuring the PFT tracers, concentrations of other volatile organic compounds (VOCs) are simultaneously determined. Pilot tests in three environments (residence, garage, and vehicle cabin) demonstrate the utility of the method. The 4 day effective AER in the house was 0.20 h(-1), the 4 day AER in the attached garage was 0.80 h(-1), and 16% of the ventilation in the house migrated from the garage. The 5 h AER in a vehicle traveling at 100 km h(-1) under a low-to-medium vent condition was 92 h(-1), and this represents the highest speed test found in the literature. The method is attractive in that it simultaneously determines AERs, interzonal flows, and VOC concentrations over long and representative test periods. These measurements are

  4. Magnetic Resonance Imaging of Ventilation and Perfusion in the Lung

    NASA Technical Reports Server (NTRS)

    Prisk, Gordon Kim (Inventor); Hopkins, Susan Roberta (Inventor); Pereira De Sa, Rui Carlos (Inventor); Theilmann, Rebecca Jean (Inventor); Buxton, Richard Bruce (Inventor); Cronin, Matthew Vincent (Inventor)

    2017-01-01

    Methods, devices, and systems are disclosed for implementing a fully quantitative non-injectable contrast proton MRI technique to measure spatial ventilation-perfusion (VA/Q) matching and spatial distribution of ventilation and perfusion. In one aspect, a method using MRI to characterize ventilation and perfusion in a lung includes acquiring an MR image of the lung having MR data in a voxel and obtaining a breathing frequency parameter, determining a water density value, a specific ventilation value, and a perfusion value in at least one voxel of the MR image based on the MR data and using the water density value to determine an air content value, and determining a ventilation-perfusion ratio value that is the product of the specific ventilation value, the air content value, the inverse of the perfusion value, and the breathing frequency.

  5. The construction of ventilation turrets in Atta vollenweideri leaf-cutting ants: Carbon dioxide levels in the nest tunnels, but not airflow or air humidity, influence turret structure

    PubMed Central

    Roces, Flavio

    2017-01-01

    Nest ventilation in the leaf-cutting ant Atta vollenweideri is driven via a wind-induced mechanism. On their nests, workers construct small turrets that are expected to facilitate nest ventilation. We hypothesized that the construction and structural features of the turrets would depend on the colony’s current demands for ventilation and thus might be influenced by the prevailing environmental conditions inside the nest. Therefore, we tested whether climate-related parameters, namely airflow, air humidity and CO2 levels in the outflowing nest air influenced turret construction in Atta vollenweideri. In the laboratory, we simulated a semi-natural nest arrangement with fungus chambers, a central ventilation tunnel providing outflow of air and an aboveground building arena for turret construction. In independent series, different climatic conditions inside the ventilation tunnel were experimentally generated, and after 24 hours, several features of the built turret were quantified, i.e., mass, height, number and surface area (aperture) of turret openings. Turret mass and height were similar in all experiments even when no airflow was provided in the ventilation tunnel. However, elevated CO2 levels led to the construction of a turret with several minor openings and a larger total aperture. This effect was statistically significant at higher CO2 levels of 5% and 10% but not at 1% CO2. The construction of a turret with several minor openings did not depend on the strong differences in CO2 levels between the outflowing and the outside air, since workers also built permeated turrets even when the CO2 levels inside and outside were both similarly high. We propose that the construction of turrets with several openings and larger opening surface area might facilitate the removal of CO2 from the underground nest structure and could therefore be involved in the control of nest climate in leaf-cutting ants. PMID:29145459

  6. The construction of ventilation turrets in Atta vollenweideri leaf-cutting ants: Carbon dioxide levels in the nest tunnels, but not airflow or air humidity, influence turret structure.

    PubMed

    Halboth, Florian; Roces, Flavio

    2017-01-01

    Nest ventilation in the leaf-cutting ant Atta vollenweideri is driven via a wind-induced mechanism. On their nests, workers construct small turrets that are expected to facilitate nest ventilation. We hypothesized that the construction and structural features of the turrets would depend on the colony's current demands for ventilation and thus might be influenced by the prevailing environmental conditions inside the nest. Therefore, we tested whether climate-related parameters, namely airflow, air humidity and CO2 levels in the outflowing nest air influenced turret construction in Atta vollenweideri. In the laboratory, we simulated a semi-natural nest arrangement with fungus chambers, a central ventilation tunnel providing outflow of air and an aboveground building arena for turret construction. In independent series, different climatic conditions inside the ventilation tunnel were experimentally generated, and after 24 hours, several features of the built turret were quantified, i.e., mass, height, number and surface area (aperture) of turret openings. Turret mass and height were similar in all experiments even when no airflow was provided in the ventilation tunnel. However, elevated CO2 levels led to the construction of a turret with several minor openings and a larger total aperture. This effect was statistically significant at higher CO2 levels of 5% and 10% but not at 1% CO2. The construction of a turret with several minor openings did not depend on the strong differences in CO2 levels between the outflowing and the outside air, since workers also built permeated turrets even when the CO2 levels inside and outside were both similarly high. We propose that the construction of turrets with several openings and larger opening surface area might facilitate the removal of CO2 from the underground nest structure and could therefore be involved in the control of nest climate in leaf-cutting ants.

  7. City ventilation of Hong Kong at no-wind conditions

    NASA Astrophysics Data System (ADS)

    Yang, Lina; Li, Yuguo

    We hypothesize that city ventilation due to both thermally-driven mountain slope flows and building surface flows is important in removing ambient airborne pollutants in the high-rise dense city Hong Kong at no-wind conditions. Both spatial and temporal urban surface temperature profiles are an important boundary condition for studying city ventilation by thermal buoyancy. Field measurements were carried out to investigate the diurnal thermal behavior of urban surfaces (mountain slopes, and building exterior walls and roofs) in Hong Kong by using the infrared thermography. The maximum urban surface temperature was measured in the early noon hours (14:00-15:00 h) and the minimum temperature was observed just before sunrise (5:00 h). The vertical surface temperature of the building exterior wall was found to increase with height at daytime and the opposite occurred at nighttime. The solar radiation and the physical properties of the various urban surfaces were found to be important factors affecting the surface thermal behaviors. The temperature difference between the measured maximum and minimum surface temperatures of the four selected exterior walls can be at the highest of 16.7 °C in the early afternoon hours (15:00 h). Based on the measured surface temperatures, the ventilation rate due to thermal buoyancy-induced wall surface flows of buildings and mountain slope winds were estimated through an integral analysis of the natural convection flow over a flat surface. At no-wind conditions, the total air change rate by the building wall flows (2-4 ACH) was found to be 2-4 times greater than that by the slope flows due to mountain surface (1 ACH) due to larger building exterior surface areas and temperature differences with surrounding air. The results provide useful insights into the ventilation of a high-rise dense city at no-wind conditions.

  8. The Use of Stepper Motor-Controlled Proportional Valve for Fio2 Calculation in the Ventilator and its Control with Fuzzy Logic.

    PubMed

    Gölcük, Adem; Güler, İnan

    2017-01-01

    This article proposes the employment of a proportional valve that can calculate the amount of oxygen in the air to be given to patient in accordance with the amount of FiO 2 which is set from the control menu of the ventilation device. To actualize this, a stepper motor-controlled proportional valve was used. Two counts of valves were employed in order to control the gases with 2 bar pressure that came from both the oxygen and medical air tanks. Oxygen and medical air manometers alongside the pressure regulators were utilized to perform this task. It is a fuzzy-logic-based controller which calculates at what rate the proportional valves will be opened and closed for FiO 2 calculation. Fluidity and pressure of air given by the ventilation device were tested with a FlowMeter while the oxygen level was tested using the electronic lung model. The obtained results from the study revealed that stepper motor controlled proportional valve could be safely used in ventilation devices. In this article, it was indicated that fluidity and pressure control could be carried out with just two counts of proportional valve, which could be done with many solenoid valves, so this reduces the cost of ventilator, electrical power consumed by the ventilator, and the dimension of ventilator.

  9. Simulation of erosion by a particulate airflow through a ventilator

    NASA Astrophysics Data System (ADS)

    Ghenaiet, A.

    2015-08-01

    Particulate flows are a serious problem in air ventilation systems, leading to erosion of rotor blades and aerodynamic performance degradation. This paper presents the numerical results of sand particle trajectories and erosion patterns in an axial ventilator and the subsequent blade deterioration. The flow field was solved separately by using the code CFX- TASCflow. The Lagrangian approach for the solid particles tracking implemented in our inhouse code considers particle and eddy interaction, particle size distribution, particle rebounds and near walls effects. The assessment of erosion wear is based on the impact frequency and local values of erosion rate. Particle trajectories and erosion simulation revealed distinctive zones of impacts with high rates of erosion mainly on the blade pressure side, whereas the suction side is eroded around the leading edge.

  10. Nasal mask ventilation is better than face mask ventilation in edentulous patients

    PubMed Central

    Kapoor, Mukul Chandra; Rana, Sandeep; Singh, Arvind Kumar; Vishal, Vindhya; Sikdar, Indranil

    2016-01-01

    Background and Aims: Face mask ventilation of the edentulous patient is often difficult as ineffective seating of the standard mask to the face prevents attainment of an adequate air seal. The efficacy of nasal ventilation in edentulous patients has been cited in case reports but has never been investigated. Material and Methods: Consecutive edentulous adult patients scheduled for surgery under general anesthesia with endotracheal intubation, during a 17-month period, were prospectively evaluated. After induction of anesthesia and administration of neuromuscular blocker, lungs were ventilated with a standard anatomical face mask of appropriate size, using a volume controlled anesthesia ventilator with tidal volume set at 10 ml/kg. In case of inadequate ventilation, the mask position was adjusted to achieve best-fit. Inspired and expired tidal volumes were measured. Thereafter, the face mask was replaced by a nasal mask and after achieving best-fit, the inspired and expired tidal volumes were recorded. The difference in expired tidal volumes and airway pressures at best-fit with the use of the two masks and number of patients with inadequate ventilation with use of the masks were statistically analyzed. Results: A total of 79 edentulous patients were recruited for the study. The difference in expiratory tidal volumes with the use of the two masks at best-fit was statistically significant (P = 0.0017). Despite the best-fit mask placement, adequacy of ventilation could not be achieved in 24.1% patients during face mask ventilation, and 12.7% patients during nasal mask ventilation and the difference was statistically significant. Conclusion: Nasal mask ventilation is more efficient than standard face mask ventilation in edentulous patients. PMID:27625477

  11. Change Is In the Air: What You Need to Know About Pharmacy Ventilation Under United States Pharmacopeia <800>.

    PubMed

    Laniewicz, Cheryl

    2017-01-01

    On July 1, 2018, United States Pharmacopeia <800> takes effect in those states that adopt it, and the discussion within this article may be applicable to those states that develop their own standards. United States Pharmacopeia <800> changes requirements for storage and compounding of hazardous drugs. The new requirements have important implications for air management and ventilation in some pharmacies. This article discusses how United States Pharmacopeia <800> compares to United States Pharmacopeia <797>, how the changes impact room ventilation and pressurization requirements, and how high-performance airflow control systems that ensure compliance and safety are impacted. Copyright© by International Journal of Pharmaceutical Compounding, Inc.

  12. The muscular basis of aerial ventilation of the primitive lung of Amia calva.

    PubMed

    Deyst, K A; Liem, K F

    1985-02-01

    Anatomical analysis, electromyography, pressure recordings, high-speed X-ray and light movies of the mechanism of air ventilation in Amia calva reveal that aerial ventilation proceeds by the action of a specialized pulse pump. The interhyoideus muscle is the dominant muscle being active during both the preparatory phase and the final, prolonged compressive phase during which new air is forced into the lung. Amia retains a relatively large residual volume in the lung and does not repeat inhalation. It often expels excess air from the buccal cavity after the lung has been fully reinflated. The pressure, kinematic and air flow patterns during air ventilation in Amia closely resemble those of the air breath in the lungfish Protopterus. We hypothesize that the basically similar electromyographic profiles of homologous muscles so characteristic for the air ventilation mechanism of Protopterus and Amia reflect a homologous anatomical as well as functional neuromuscular pattern, which has had a common and early evolutionary origin among the Teleostomi.

  13. Effects of Residential Indoor Air Quality and Household Ventilation on Preterm Birth and Term Low Birth Weight in Los Angeles County, California

    PubMed Central

    Wilhelm, Michelle; Ritz, Beate

    2013-01-01

    Objectives. The purpose of our study was to examine the effects of indoor residential air quality on preterm birth and term low birth weight (LBW). Methods. We evaluated 1761 nonsmoking women from a case-control survey of mothers who delivered a baby in 2003 in Los Angeles County, California. In multinomial logistic regression models adjusted for maternal age, education, race/ethnicity, parity and birthplace, we evaluated the effects of living with smokers or using personal or household products that may contain volatile organic compounds and examined the influence of household ventilation. Results. Compared with unexposed mothers, women exposed to secondhand smoke (SHS) at home had increased odds of term LBW (adjusted odds ratio [OR] = 1.36; 95% confidence interval [CI] =  0.85, 2.18) and preterm birth (adjusted OR = 1.27; 95% CI = 0.95, 1.70), although 95% CIs included the null. No increase in risk was observed for SHS-exposed mothers reporting moderate or high window ventilation. Associations were also observed for product usage, but only for women reporting low or no window ventilation. Conclusions. Residential window ventilation may mitigate the effects of indoor air pollution among pregnant women in Los Angeles County, California. PMID:23409879

  14. Laboratory Ventilation and Safety.

    ERIC Educational Resources Information Center

    Steere, Norman V.

    1965-01-01

    In order to meet the needs of both safety and economy, laboratory ventilation systems must effectively remove air-borne toxic and flammable materials and at the same time exhaust a minimum volume of air. Laboratory hoods are the most commonly used means of removing gases, dusts, mists, vapors, and fumed from laboratory operations. To be effective,…

  15. Impact of ventilation scenario on air exchange rates and on indoor particle number concentrations in an air-conditioned classroom

    NASA Astrophysics Data System (ADS)

    Guo, H.; Morawska, L.; He, C.; Gilbert, D.

    A 2-week intensive measurement campaign of indoor and outdoor air pollution was carried out in September 2006, in a primary school to investigate indoor-outdoor correlations of particle number (PN) concentrations, and the impact of air exchange rate (ACH) on the indoor PN concentration. The ACHs in the classroom for different conditions associated with window opening and the operational status of air conditioners (A/C) and fans were tested. As expected, the lowest ACH (0.12 h -1) was found when the windows were closed and A/C and fans were off. In contrast, the highest ACH (7.92 h -1) was observed when the windows were opened and A/C and fans were all on. The analysis of the PN I/ O ratios at different ACHs in the absence of indoor sources indicates that the mean I/ O ratio was 0.621±0.007 (mean±95% confidence interval) when the windows were closed, and A/C and fans were off; 0.524±0.023 when windows were closed, fans were off and A/C was on; and 0.502±0.029 when windows were closed, A/C was off and fans were on. To further understand the relationship between indoor and outdoor PN concentrations, the impact of outdoor PN concentration on I/ O ratios at different ACHs was investigated. It was found that the relationship between outdoor PN concentration and the I/ O ratio at different ACHs followed a power trendline with an equation of I/ O ratio= A PN out-b ( A and b are coefficients, PN out is outdoor PN concentration), suggesting that the penetration efficiency decreased with increasing outdoor PN concentration. It is the first time we found that when the outdoor PN concentration increased there was an associated increase in the concentration of nano-particles, which have been demonstrated to have higher deposition rates and lower penetration efficiencies. Based on the above equation, the study also showed a significant effect of ACH on indoor PN concentrations under stable outdoor PN concentrations. In general, the higher the ACH was, the lower the indoor PN

  16. 46 CFR 194.10-25 - Ventilation.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... and shall serve no other space. Weather cowls shall be provided with a double layer of wire screen of... temperature below 100 °F. with 88 °F. weather air. Mechanical cooling may be used where ventilation... 130 °F. with an assumed outside temperature of 115 °F. (2) Ventilation supply weather openings shall...

  17. 46 CFR 194.10-25 - Ventilation.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... and shall serve no other space. Weather cowls shall be provided with a double layer of wire screen of... temperature below 100 °F. with 88 °F. weather air. Mechanical cooling may be used where ventilation... 130 °F. with an assumed outside temperature of 115 °F. (2) Ventilation supply weather openings shall...

  18. 46 CFR 194.10-25 - Ventilation.

    Code of Federal Regulations, 2013 CFR

    2013-10-01

    ... and shall serve no other space. Weather cowls shall be provided with a double layer of wire screen of... temperature below 100 °F. with 88 °F. weather air. Mechanical cooling may be used where ventilation... 130 °F. with an assumed outside temperature of 115 °F. (2) Ventilation supply weather openings shall...

  19. 46 CFR 194.10-25 - Ventilation.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... and shall serve no other space. Weather cowls shall be provided with a double layer of wire screen of... temperature below 100 °F. with 88 °F. weather air. Mechanical cooling may be used where ventilation... 130 °F. with an assumed outside temperature of 115 °F. (2) Ventilation supply weather openings shall...

  20. Ventilation-induced release of phosphatidylcholine from neonatal-rat lungs in vitro.

    PubMed Central

    Nijjar, M S

    1984-01-01

    Factors regulating the release of phosphatidylcholine (PC) from neonatal-rat lungs were investigated. The results show that the release of prelabelled PC from the newborn-rat lung was augmented by air ventilation at the onset of breathing. This response was mimicked in lungs of pups delivered 1 day before term and allowed to breathe for different time intervals. Anoxia further augmented the ventilation-enhanced PC release from the newborn-rat lungs. The ventilation-induced release of PC was not abolished by the prior treatment of pups in utero or mothers in vivo with phenoxybenzamine, propranolol or atropine, suggesting the lack of receptor stimulation in the ventilation-enhanced PC release at birth. The results also show that ventilation stimulated [methyl-14C]choline incorporation into lung PC, presumably to replenish the depleted surfactant stores. The ratio of adenylate cyclase/cyclic AMP phosphodiesterase activities, which reflects cyclic AMP levels in the developing rat lungs, did not change during the 120 min of air ventilation when the release of PC was much enhanced, implying that cyclic AMP may not be involved. This confirms our conclusion that stimulation of beta-adrenergic receptor was not involved in the air-ventilation-enhanced release of PC. Since the cell number or size did not change during 120 min of ventilation when the alveolar-cell surface was maximally distended, it is suggested that distension of alveolar wall by air ventilation at the onset of breathing may bring the lamellar bodies containing surfactant close to the luminal surface of alveolar type II cells, thereby enhancing their fusion and extrusion by exocytosis. PMID:6477485

  1. ASHRAE and residential ventilation

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Sherman, Max H.

    In the last quarter of a century, the western world has become increasingly aware of environmental threats to health and safety. During this period, people psychologically retreated away from outdoors hazards such as pesticides, smog, lead, oil spills, and dioxin to the seeming security of their homes. However, the indoor environment may not be healthier than the outdoor environment, as has become more apparent over the past few years with issues such as mold, formaldehyde, and sick-building syndrome. While the built human environment has changed substantially over the past 10,000 years, human biology has not; poor indoor air quality createsmore » health risks and can be uncomfortable. The human race has found, over time, that it is essential to manage the indoor environments of their homes. ASHRAE has long been in the business of ventilation, but most of the focus of that effort has been in the area of commercial and institutional buildings. Residential ventilation was traditionally not a major concern because it was felt that, between operable windows and envelope leakage, people were getting enough outside air in their homes. In the quarter of a century since the first oil shock, houses have gotten much more energy efficient. At the same time, the kinds of materials and functions in houses changed in character in response to people's needs. People became more environmentally conscious and aware not only about the resources they were consuming but about the environment in which they lived. All of these factors contributed to an increasing level of public concern about residential indoor air quality and ventilation. Where once there was an easy feeling about the residential indoor environment, there is now a desire to define levels of acceptability and performance. Many institutions--both public and private--have interests in Indoor Air Quality (IAQ), but ASHRAE, as the professional society that has had ventilation as part of its mission for over 100 years, is

  2. Impact of Fire Ventilation on General Ventilation in the Building

    NASA Astrophysics Data System (ADS)

    Zender-Świercz, Ewa; Telejko, Marek

    2017-10-01

    The fire of building is a threat to its users. The biggest threat is generation, during lifetime of fire, hot gases and smoke. The purpose of quick and efficient evacuation from the area covered by the fire, at first step the escape routes have to be secured from smokiness. The smoke ventilation systems are used for this purpose. The proper design and execution of smoke ventilation is important not only because of the safety, but also of the maintenance of comfort in the building at a time when there is no fire. The manuscript presents the effect of incorrectly realized smoke ventilation in the stairwell of the medium building. The analysis shows that the flaps of smoke ventilation located in the stairwell may have a significant impact on the proper functioning of mechanical ventilation in the period when there is no fire. The improperly installed or incorrect insulated components cause perturbation of air flow and they change pressure distribution in the building. The conclusion of the analysis is the need to include the entire technical equipment of the building during the design and realization of its individual elements. The impact of various installations at each other is very important, and the omission of any of them can cause disturbances in the proper work of another.

  3. Indoor Levels of Formaldehyde and Other Pollutants and Relationship to Air Exchange Rates and Human Activities

    NASA Astrophysics Data System (ADS)

    Huangfu, Y.; O'Keeffe, P.; Kirk, M.; Walden, V. P.; Lamb, B. K.; Jobson, B. T.

    2017-12-01

    This paper reports results on an indoor air quality study conducted on six homes in summer and winter, contrasting indoor and outdoor concentrations of O3, CO, CO2, NOx, PM2.5, and selected volatile organic hydrocarbons measured by PTR-MS. Data were collected as 1 minute averages. Air exchange rates of the homes were determined by CO2 tracer release. Smart home sensors, recording human activity level in various places in the home, and window and doors openings, were utilized to better understand the link between human activity and indoor air pollution. From our study, averaged air exchange rates of the homes ranged from 0.2 to 1.2 hour-1 and were greatly affected by the ventilation system type and window and door openings. In general, a negative correlation between air exchange rate and indoor VOCs levels was observed, with large variation of pollutant levels between the homes. For most of the VOCs measured in the house, including formaldehyde and acetaldehyde, summer levels were much higher than winter levels. In some homes formaldehyde levels displayed a time of day variation that was linked to changes in indoor temperature. During a wildfire period in the summer of 2015, outdoor levels of PM2.5, formaldehyde, and benzene dramatically increased, significantly impacting indoor levels due to infiltration. Human activities, such as cooking, can significantly change the levels of most of the compounds measured in the house and the levels can be significantly elevated for short periods of time, with peak levels can be several orders higher compared with typical levels. The data suggest that an outcome of state energy codes that require new homes to be energy efficient, and as a consequence built with lower air exchange rates, will be unacceptable levels of air toxics, notably formaldehyde.

  4. Ventilation through a small-bore catheter: optimizing expiratory ventilation assistance.

    PubMed

    Hamaekers, A E W; Borg, P A J; Götz, T; Enk, D

    2011-03-01

    Emergency ventilation through a small-bore transtracheal catheter can be lifesaving in a 'cannot intubate, cannot ventilate' situation. Ejectors, capable of creating suction by the Bernoulli principle, have been proposed to facilitate expiration through small-bore catheters. In this bench study, we compared a novel, purpose-built ventilation ejector (DE 5) with a previously proposed, modified industrial ejector (SBP 07). The generated insufflation pressures, suction pressures in static and dynamic situations, and also suction capacities and entrainment ratios of the SBP 07 and the DE 5 were determined. The DE 5 was also tested in a lung simulator with a simulated complete upper airway obstruction. Inspiratory and expiratory times through a transtracheal catheter were measured at various flow rates and achievable minute volumes were calculated. In a static situation, the SBP 07 showed a more negative pressure build-up compared with the DE 5. However, in a dynamic situation, the DE 5 generated a more negative pressure, resulting in a higher suction capacity. Employment of the DE 5 at a flow rate of 18 litre min(-1) allowed a minute volume through the transtracheal catheter of up to 8.27 litre min(-1) at a compliance of 100 ml cm H(2)O(-1). The efficiency of the DE 5 depended on the flow rate of the driving gas and the compliance of the lung simulator. In laboratory tests, the DE 5 is an optimized ventilation ejector suitable for applying expiratory ventilation assistance. Further research may confirm the clinical applicability as a portable emergency ventilator for use with small-bore catheters.

  5. Air-Q intubating laryngeal airway: A study of the second generation supraglottic airway device.

    PubMed

    Attarde, Viren Bhaskar; Kotekar, Nalini; Shetty, Sarika M

    2016-05-01

    Air-Q intubating laryngeal mask airway (ILA) is used as a supraglottic airway device and as a conduit for endotracheal intubation. This study aims to assess the efficacy of the Air-Q ILA regarding ease of insertion, adequacy of ventilation, rate of successful intubation, haemodynamic response and airway morbidity. Sixty patients presenting for elective surgery at our Medical College Hospital were selected. Following adequate premedication, baseline vital parameters, pulse rate and blood pressure were recorded. Air-Q size 3.5 for patients 50-70 kg and size 4.5 for 70-100 kg was selected. After achieving adequate intubating conditions, Air-Q ILA was introduced. Confirming adequate ventilation, appropriate sized endotracheal tube was advanced through the Air-Q blindly to intubate the trachea. Placement of the endotracheal tube in trachea was confirmed. Air-Q ILA was successfully inserted in 88.3% of patients in first attempt and 11.7% patients in second attempt. Ventilation was adequate in 100% of patients. Intubation was successful in 76.7% of patients with Air-Q ILA. 23.3% of patients were intubated by direct laryngoscopy following failure with two attempts using Air-Q ILA. Post-intubation the change in heart rate was statistically significant (P < 0.0001). 10% of patients were noted to have a sore throat and 5% of patients had mild airway trauma. Air-Q ILA is a reliable device as a supraglottic airway ensuring adequate ventilation as well as a conduit for endotracheal intubation. It benefits the patient by avoiding the stress of direct laryngoscopy and is also superior alternative device for use in a difficult airway.

  6. Review of Air Exchange Rate Models for Air Pollution Exposure Assessments

    EPA Science Inventory

    A critical aspect of air pollution exposure assessments is estimation of the air exchange rate (AER) for various buildings, where people spend their time. The AER, which is rate the exchange of indoor air with outdoor air, is an important determinant for entry of outdoor air pol...

  7. Occupational exposure to nitrous oxide - the role of scavenging and ventilation systems in reducing the exposure level in operating rooms.

    PubMed

    Krajewski, Wojciech; Kucharska, Malgorzata; Wesolowski, Wiktor; Stetkiewicz, Jan; Wronska-Nofer, Teresa

    2007-03-01

    The aim of this study was to assess the level of occupational exposure to nitrous oxide (N(2)O) in operating rooms (ORs), as related to different ventilation and scavenging systems used to remove waste anaesthetic gases from the work environment. The monitoring of N(2)O in the air covered 35 ORs in 10 hospitals equipped with different systems for ventilation and anaesthetic scavenging. The examined systems included: natural ventilation with supplementary fresh air provided by a pressure ventilation system (up to 6 air changes/h); pressure and exhaust ventilation systems equipped with ventilation units supplying fresh air to and discharging contaminated air outside the working area (more than 10 air changes/h); complete air-conditioning system with laminar air flow (more than 15 air changes/h). The measurements were carried out during surgical procedures (general anaesthesia induced intravenously and maintained with inhaled N(2)O and sevofluran delivered through cuffed endotracheal tubes) with connected or disconnected air scavenging. Air was collected from the breathing zone of operating personnel continuously through the whole time of anaesthesia to Tedlar((R)) bags, and N(2)O concentrations in air samples were analyzed by adsorption gas chromatography/mass spectrometry. N(2)O levels in excess of the occupational exposure limit (OEL) value of 180mg/m(3) were registered in all ORs equipped with ventilation systems alone. The OEL value was exceeded several times in rooms with natural ventilation plus supplementary pressure ventilations and twice or less in those with pressure/exhaust ventilation systems or air conditioning. N(2)O levels below or within the OEL value were observed in rooms where the system of air conditioning or pressure/exhaust ventilation was combined with scavenging systems. Systems combining natural/pressure ventilation with scavenging were inadequate to maintain N(2)O concentration below the OEL value. Air conditioning and an efficient pressure

  8. ENVIRONMENTAL TECHNOLOGY VERIFICATION TEST PROTOCOL, GENERAL VENTILATION FILTERS

    EPA Science Inventory

    The Environmental Technology Verification Test Protocol, General Ventilation Filters provides guidance for verification tests.

    Reference is made in the protocol to the ASHRAE 52.2P "Method of Testing General Ventilation Air-cleaning Devices for Removal Efficiency by P...

  9. Outcome-based ventilation: A framework for assessing performance, health, and energy impacts to inform office building ventilation decisions.

    PubMed

    Rackes, A; Ben-David, T; Waring, M S

    2018-07-01

    This article presents an outcome-based ventilation (OBV) framework, which combines competing ventilation impacts into a monetized loss function ($/occ/h) used to inform ventilation rate decisions. The OBV framework, developed for U.S. offices, considers six outcomes of increasing ventilation: profitable outcomes realized from improvements in occupant work performance and sick leave absenteeism; health outcomes from occupant exposure to outdoor fine particles and ozone; and energy outcomes from electricity and natural gas usage. We used the literature to set low, medium, and high reference values for OBV loss function parameters, and evaluated the framework and outcome-based ventilation rates using a simulated U.S. office stock dataset and a case study in New York City. With parameters for all outcomes set at medium values derived from literature-based central estimates, higher ventilation rates' profitable benefits dominated negative health and energy impacts, and the OBV framework suggested ventilation should be ≥45 L/s/occ, much higher than the baseline ~8.5 L/s/occ rate prescribed by ASHRAE 62.1. Only when combining very low parameter estimates for profitable impacts with very high ones for health and energy impacts were all outcomes on the same order. Even then, however, outcome-based ventilation rates were often twice the baseline rate or more. © 2018 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  10. Control of asthma triggers in indoor air with air cleaners: a modeling analysis.

    PubMed

    Myatt, Theodore A; Minegishi, Taeko; Allen, Joseph G; Macintosh, David L

    2008-08-06

    Reducing exposure to environmental agents indoors shown to increase asthma symptoms or lead to asthma exacerbations is an important component of a strategy to manage asthma for individuals. Numerous investigations have demonstrated that portable air cleaning devices can reduce concentrations of asthma triggers in indoor air; however, their benefits for breathing problems have not always been reproducible. The potential exposure benefits of whole house high efficiency in-duct air cleaners for sensitive subpopulations have yet to be evaluated. We used an indoor air quality modeling system (CONTAM) developed by NIST to examine peak and time-integrated concentrations of common asthma triggers present in indoor air over a year as a function of natural ventilation, portable air cleaners, and forced air ventilation equipped with conventional and high efficiency filtration systems. Emission rates for asthma triggers were based on experimental studies published in the scientific literature. Forced air systems with high efficiency filtration were found to provide the best control of asthma triggers: 30-55% lower cat allergen levels, 90-99% lower risk of respiratory infection through the inhalation route of exposure, 90-98% lower environmental tobacco smoke (ETS) levels, and 50-75% lower fungal spore levels than the other ventilation/filtration systems considered. These results indicate that the use of high efficiency in-duct air cleaners provide an effective means of controlling allergen levels not only in a single room, like a portable air cleaner, but the whole house. These findings are useful for evaluating potential benefits of high efficiency in-duct filtration systems for controlling exposure to asthma triggers indoors and for the design of trials of environmental interventions intended to evaluate their utility in practice.

  11. Simulations of the impacts of building height layout on air quality in natural-ventilated rooms around street canyons.

    PubMed

    Yang, Fang; Zhong, Ke; Chen, Yonghang; Kang, Yanming

    2017-10-01

    Numerical simulations were conducted to investigate the effects of building height ratio (i.e., HR, the height ratio of the upstream building to the downstream building) on the air quality in buildings beside street canyons, and both regular and staggered canyons were considered for the simulations. The results show that the building height ratio affects not only the ventilation fluxes of the rooms in the downstream building but also the pollutant concentrations around the building. The parameter, outdoor effective source intensity of a room, is then proposed to calculate the amount of vehicular pollutants that enters into building rooms. Smaller value of this parameter indicates less pollutant enters the room. The numerical results reveal that HRs from 2/7 to 7/2 are the favorable height ratios for the regular canyons, as they obtain smaller values than the other cases. While HR values of 5/7, 7/7, and 7/5 are appropriate for staggered canyons. In addition, in terms of improving indoor air quality by natural ventilation, the staggered canyons with favorable HR are better than those of the regular canyons.

  12. Supply Ventilation and Prevention of Carbon Monoxide (II) Ingress into Building Premises

    NASA Astrophysics Data System (ADS)

    Litvinova, N. A.

    2017-11-01

    The article contains the relationships of carbon monoxide (II) concentration versus height-above-ground near buildings derived based on results of studies. The results of studies are crucial in preventing external pollutants ingress into a ventilation system. Being generated by external emission sources, such as motor vehicles and city heating plants, carbon monoxide (II) enters the premises during operation of a supply ventilation system. Fresh air nomographic charts were drawn to select the height of a fresh air intake into the ventilation system. Nomographic charts take into account external sources. The selected emission sources are located at various levels above ground relative to the building. The recommendations allow designing supply ventilation taking into account the quality of ambient air through the whole building height.

  13. Three-year experience with neonatal ventilation from a tertiary care hospital in Delhi.

    PubMed

    Singh, M; Deorari, A K; Paul, V K; Mittal, M; Shanker, S; Munshi, U; Jain, Y

    1993-06-01

    Ninety neonates were ventilated over a period of 33 months of whom 50 (55.5%) survived. Fifty seven babies received IPPV while 33 CPAP. IPPV mode was being used more frequently recently and survival rates have steadily improved over past 3 years. Survival was cent per cent in babies above 1.5 kg on CPAP mode while 16/26 (57.7%) survived on IPPV mode. Of 22 extremely VLBW (< 1 kg) babies, six survived. HMD was the commonest indication of ventilation (50%), of which 53% (24/45) survived. The other important indications of ventilation were apnea in 13 and transient tachypnea in 11 babies. All babies requiring ventilation for transient tachypnea survived. Nosocomial infections were common in association with ventilation 34/90 (37.7%), out of which in 14 was responsible for about a third of deaths. Pulmonary air leaks developed in 12 babies of which 6 died. Two babies developed BPD and one ROP. Neonatal ventilation should be ventured in centres where basic facilities for level II care already exist. It may not be cost effective to ventilate extremely low birth weight neonates.

  14. Innovative method and equipment for personalized ventilation.

    PubMed

    Kalmár, F

    2015-06-01

    At the University of Debrecen, a new method and equipment for personalized ventilation has been developed. This equipment makes it possible to change the airflow direction during operation with a time frequency chosen by the user. The developed office desk with integrated air ducts and control system permits ventilation with 100% outdoor air, 100% recirculated air, or a mix of outdoor and recirculated air in a relative proportion set by the user. It was shown that better comfort can be assured in hot environments if the fresh airflow direction is variable. Analyzing the time step of airflow direction changing, it was found that women prefer smaller time steps and their votes related to thermal comfort sensation are higher than men's votes. © 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  15. Decrease in delivery room intubation rates after use of nasal intermittent positive pressure ventilation in the delivery room for resuscitation of very low birth weight infants.

    PubMed

    Biniwale, Manoj; Wertheimer, Fiona

    2017-07-01

    The literature supports minimizing duration of invasive ventilation to decrease lung injury in premature infants. Neonatal Resuscitation Program recommended use of non-invasive ventilation (NIV) in delivery room for infants requiring prolonged respiratory support. To evaluate the impact of implementation of non-invasive ventilation (NIV) using nasal intermittent positive pressure ventilation (NIPPV) for resuscitation in very low birth infants. Retrospective study was performed after NIPPV was introduced in the delivery room and compared with infants receiving face mask to provide positive pressure ventilation for resuscitation of very low birth weight infants prior to its use. Data collected from 119 infants resuscitated using NIPPV and 102 infants resuscitated with a face mask in a single institution. The primary outcome was the need for endotracheal intubation in the delivery room. Data was analyzed using IBM SPSS Statistics software version 24. A total of 31% of infants were intubated in the delivery room in the NIPPV group compared to 85% in the Face mask group (p=<0.001). Chest compression rates were 11% in the NIPPV group and 31% in the Face mask group (p<0.001). Epinephrine administration was also lower in NIPPV group (2% vs. 8%; P=0.03). Only 38% infants remained intubated at 24hours of age in the NIPPV group compared to 66% in the Face mask group (p<0.001). Median duration of invasive ventilation in the NIPPV group was shorter (2days) compared to the Face mask group (11days) (p=0.01). The incidence of air-leaks was not significant between the two groups. NIPPV was safely and effectively used in the delivery room settings to provide respiratory support for VLBW infants with less need for intubation, chest compressions, epinephrine administration and subsequent invasive ventilation. Copyright © 2017 Elsevier B.V. All rights reserved.

  16. Energy Use Consequences of Ventilating a Net-Zero Energy House

    PubMed Central

    Ng, Lisa C.; Payne, W. Vance

    2016-01-01

    A Net-Zero Energy Residential Test Facility (NZERTF) has been constructed at the National Institute of Standards and Technology (NIST) in Gaithersburg, Maryland to demonstrate that a home similar in size, aesthetics, and amenities to those in the surrounding communities can achieve net-zero energy use over the course of a year while meeting the average electricity and water use needs of a family of four in the United States. The facility incorporates renewable energy and energy efficient technologies, including an air-to-air heat pump system, a solar photovoltaic system, a solar thermal domestic hot water system, and a heat recovery ventilation system sized to meet American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) Standard 62.2-2010 ventilation requirements. The largest energy end use within the home was space conditioning, which included heat loss through the building envelope, ventilation air supplied by the heat recovery ventilator (HRV), and internal loads. While HRVs are often described as being able to save energy when compared to ventilating without heat recovery, there have been no studies using a full year of measured data that determine the thermal load and energy impacts of HRV-based ventilation on the central heating and cooling system. Over the course of a year, continuous operation of the HRV at the NZERTF resulted in an annual savings of 7 % in heat pump energy use compared with the hypothetical case of ventilating without heat recovery. The heat pump electrical use varied from an increase of 5 % in the cooling months to 36 % savings in the heating months compared with ventilation without heat recovery. The increase in the cooling months occurred when the outdoor temperature was lower than the indoor temperature, during which the availability of an economizer mode would have been beneficial. Nevertheless, the fan energy required to operate the selected HRV at the NZERTF paid for itself in the heat pump energy saved

  17. Energy Use Consequences of Ventilating a Net-Zero Energy House.

    PubMed

    Ng, Lisa C; Payne, W Vance

    2016-03-05

    A Net-Zero Energy Residential Test Facility (NZERTF) has been constructed at the National Institute of Standards and Technology (NIST) in Gaithersburg, Maryland to demonstrate that a home similar in size, aesthetics, and amenities to those in the surrounding communities can achieve net-zero energy use over the course of a year while meeting the average electricity and water use needs of a family of four in the United States. The facility incorporates renewable energy and energy efficient technologies, including an air-to-air heat pump system, a solar photovoltaic system, a solar thermal domestic hot water system, and a heat recovery ventilation system sized to meet American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) Standard 62.2-2010 ventilation requirements. The largest energy end use within the home was space conditioning, which included heat loss through the building envelope, ventilation air supplied by the heat recovery ventilator (HRV), and internal loads. While HRVs are often described as being able to save energy when compared to ventilating without heat recovery, there have been no studies using a full year of measured data that determine the thermal load and energy impacts of HRV-based ventilation on the central heating and cooling system. Over the course of a year, continuous operation of the HRV at the NZERTF resulted in an annual savings of 7 % in heat pump energy use compared with the hypothetical case of ventilating without heat recovery. The heat pump electrical use varied from an increase of 5 % in the cooling months to 36 % savings in the heating months compared with ventilation without heat recovery. The increase in the cooling months occurred when the outdoor temperature was lower than the indoor temperature, during which the availability of an economizer mode would have been beneficial. Nevertheless, the fan energy required to operate the selected HRV at the NZERTF paid for itself in the heat pump energy saved

  18. Field study on occupant comfort and the office thermal environment in rooms with displacement ventilation.

    PubMed

    Melikov, A; Pitchurov, G; Naydenov, K; Langkilde, G

    2005-06-01

    A field survey of occupants' response to the indoor environment in 10 office buildings with displacement ventilation was performed. The response of 227 occupants was analyzed. About 24% of the occupants in the survey complained that they were daily bothered by draught, mainly at the lower leg. Vertical air temperature difference measured between head and feet levels was less than 3 degrees C at all workplaces visited. Combined local discomfort because of draught and vertical temperature difference does not seem to be a serious problem in rooms with displacement ventilation. Almost one half (49%) of the occupants reported that they were daily bothered by an uncomfortable room temperature. Forty-eight per cent of the occupants were not satisfied with the air quality. The PMV and the Draught Rating indices as well as the specifications for local discomfort because of the separate impact of draught and vertical temperature difference, as defined in the present standards, are relevant for the design of a thermal environment in rooms with displacement ventilation and for its assessment in practice. Increasing the supply air temperature in order to counteract draught discomfort is a measure that should be considered carefully; even if the desired stratification of pollution in the occupied zone is preserved, an increase of the inhaled air temperature may have a negative effect on perceived air quality.

  19. Air Leakage and Air Transfer Between Garage and Living Space

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Rudd, A.

    2014-09-01

    This research project focused on evaluation of air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multi-point fan pressurization tests and additional zone pressure diagnostic testing characterized the garage and house air leakage, the garage-to-house air leakage, and garage and house pressuremore » relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed. For houses employing whole-house supply ventilation (positive pressure) or balanced ventilation (same pressure effect as the Baseline condition), adherence to the EPA Indoor airPLUS house-to-garage air sealing requirements should be sufficient to expect little to no garage-to-house air transfer.« less

  20. Implementation of a real-time compliance dashboard to help reduce SICU ventilator-associated pneumonia with the ventilator bundle.

    PubMed

    Zaydfudim, Victor; Dossett, Lesly A; Starmer, John M; Arbogast, Patrick G; Feurer, Irene D; Ray, Wayne A; May, Addison K; Pinson, C Wright

    2009-07-01

    Ventilator-associated pneumonia (VAP) causes significant morbidity and mortality in critically ill surgical patients. Recent studies suggest that the success of preventive measures is dependent on compliance with ventilator bundle parameters. Implementation of an electronic dashboard will improve compliance with the bundle parameters and reduce rates of VAP in our surgical intensive care unit (SICU). Time series analysis of VAP rates between January 2005 and July 2008, with dashboard implementation in July 2007. Multidisciplinary SICU at a tertiary-care referral center with a stable case mix during the study period. Patients admitted to the SICU between January 2005 and July 2008. Infection control data were used to establish rates of VAP and total ventilator days. For the time series analysis, VAP rates were calculated as quarterly VAP events per 1000 ventilator days. Ventilator bundle compliance was analyzed after dashboard implementation. Differences between expected and observed VAP rates based on time series analysis were used to estimate the effect of intervention. Average compliance with the ventilator bundle improved from 39% in August 2007 to 89% in July 2008 (P < .001). Rates of VAP decreased from a mean (SD) of 15.2 (7.0) to 9.3 (4.9) events per 1000 ventilator days after introduction of the dashboard (P = .01). Quarterly VAP rates were significantly reduced in the November 2007 through January 2008 and February through April 2008 periods (P < .05). For the August through October 2007 and May through July 2008 quarters, the observed rate reduction was not statistically significant. Implementation of an electronic dashboard improved compliance with ventilator bundle measures and is associated with reduced rates of VAP in our SICU.

  1. 46 CFR 194.15-5 - Ventilation.

    Code of Federal Regulations, 2014 CFR

    2014-10-01

    ... CONTROL OF EXPLOSIVES AND OTHER HAZARDOUS MATERIALS Chemistry Laboratory and Scientific Laboratory § 194... be equipped with acceptable flame screens. (b) Chemical laboratories shall be equipped with power...) Ventilation of air conditioning systems serving the chemical laboratory shall be designed so that air cannot...

  2. 46 CFR 194.15-5 - Ventilation.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... CONTROL OF EXPLOSIVES AND OTHER HAZARDOUS MATERIALS Chemistry Laboratory and Scientific Laboratory § 194... be equipped with acceptable flame screens. (b) Chemical laboratories shall be equipped with power...) Ventilation of air conditioning systems serving the chemical laboratory shall be designed so that air cannot...

  3. Numerical simulation and comparison of two ventilation methods for a restaurant - displacement vs mixed flow ventilation

    NASA Astrophysics Data System (ADS)

    Chitaru, George; Berville, Charles; Dogeanu, Angel

    2018-02-01

    This paper presents a comparison between a displacement ventilation method and a mixed flow ventilation method using computational fluid dynamics (CFD) approach. The paper analyses different aspects of the two systems, like the draft effect in certain areas, the air temperatureand velocity distribution in the occupied zone. The results highlighted that the displacement ventilation system presents an advantage for the current scenario, due to the increased buoyancy driven flows caused by the interior heat sources. For the displacement ventilation case the draft effect was less prone to appear in the occupied zone but the high heat emissions from the interior sources have increased the temperature gradient in the occupied zone. Both systems have been studied in similar conditions, concentrating only on the flow patterns for each case.

  4. A bench evaluation of fraction of oxygen in air delivery and tidal volume accuracy in home care ventilators available for hospital use

    PubMed Central

    Baboi, Loredana; Subtil, Fabien

    2016-01-01

    Background Turbine-powered ventilators are not only designed for long-term ventilation at home but also for hospital use. It is important to verify their capabilities in delivering fraction of oxygen in air (FIO2) and tidal volume (VT). Methods We assessed the FIO2 accuracy and the VT delivery in four home care ventilators (HCV) on the bench. The four HCV were Astral 150, Elisée 150, Monnal T50 and Trilogy 200 HCV, which were connected to a lung model (ASL 5000). For assessing FIO2 accuracy, lung model was set to mimic an obstructive lung and HCV were set in volume controlled mode (VC). They supplied with air, 3 or 15 L/min oxygen and FIO2 was measured by using a ventilator tester (Citrex H4TM). For the VT accuracy, the lung model was set in a way to mimic three adult configurations (normal, obstructive, or restrictive respiratory disorder) and one pediatric configuration. Each HCV was set in VC. Two VT (300 and 500 mL) in adult lung configuration and one 50 mL VT in pediatric lung configuration, at two positive end expiratory pressures 5 and 10 cmH2O, were tested. VT accuracy was measured as volume error (the relative difference between set and measured VT). Statistical analysis was performed by suing one-factor ANOVA with a Bonferroni correction for multiple tests. Results For Astral 150, Elisée 150, Monnal T50 and Trilogy 200, FIO2 averaged 99.2%, 93.7%, 86.3%, and 62.1%, respectively, at 15 L/min oxygen supplementation rate (P<0.001). Volume error was 0.5%±0%, −38%±0%, −9%±0%, −29%±0% and −36%±0% for pediatric lung condition (P<0.001). In adult lung configurations, Monnal T50 systematically over delivered VT and Trilogy 150 was sensitive to lung configuration when VT was set to 300 mL at either positive end-expiratory pressure (PEEP). Conclusions HCV are different in terms of FIO2 efficiency and VT delivery. PMID:28149559

  5. High resolution pCO2 monitoring reveals ventilation of Bunker Cave (NW Germany) and its impact on speleothem growth

    NASA Astrophysics Data System (ADS)

    Riechelmann, Sylvia; Breitenbach, Sebastian F. M.; Schröder-Ritzrau, Andrea; Immenhauser, Adrian

    2017-04-01

    Understanding the environmental processes that influence geochemical proxies archived in speleothems depends critically on detailed cave monitoring. Cave air pCO2 is one of the most important factors controlling speleothem growth. The pCO2 concentration of cave air depends on (i) the productivity of its source(s), (ii) CO2-transport dynamics through the epikarst and (iii) cave ventilation processes. We monitored the pCO2 concentration ca. 100 m from the lower entrance of the Bunker-Emst-Cave system (NW Germany) with a CORA CO2-logger at a two-hourly resolution between April 2012 and February 2014. Near-atmospheric minimum pCO2 concentrations of 408 ppm are observed in winter, while higher values up to 811 ppm are recorded in summer. Higher summer concentrations are due to increased plant and soil microbial activity, resulting in elevated CO2 in the soil, which is transferred to the cave with infiltrating water. Generally, the front passages of Bunker Cave are well ventilated. Besides the seasonal pattern, pCO2 concentrations vary at diurnal scale. Correlations of pCO2 with the temperature difference between surface and cave air are positive during summer and negative in winter, with no clear pattern for spring and autumn months. Thus, Bunker Cave ventilation is driven by temperature and density differences between cave and surface air, with two entrances at different elevations allowing dynamic ventilation. During summer, relatively cooler cave air flows from the upper to the lower entrance, while in winter this pattern is reversed due to ascending warm cave air. The situation is further complicated by preferential south/southwestern winds that point directly on the cave entrances. Thus, cave ventilation is frequently disturbed, especially during periods of higher wind speed. Modern ventilation systematics only developed when the two cave entrances were artificially opened (1863 and 1926). Before that, ventilation was restricted and cave pCO2 concentrations were

  6. Space station ventilation study

    NASA Technical Reports Server (NTRS)

    Colombo, G. V.; Allen, G. E.

    1972-01-01

    A ventilation system design and selection method which is applicable to any manned vehicle were developed. The method was used to generate design options for the NASA 33-foot diameter space station, all of which meet the ventilation system design requirements. System characteristics such as weight, volume, and power were normalized to dollar costs for each option. Total system costs for the various options ranged from a worst case $8 million to a group of four which were all approximately $2 million. A system design was then chosen from the $2 million group and is presented in detail. A ventilation system layout was designed for the MSFC space station mockup which provided comfortable, efficient ventilation of the mockup. A conditioned air distribution system design for the 14-foot diameter modular space station, using the same techniques, is also presented. The tradeoff study resulted in the selection of a system which costs $1.9 million, as compared to the alternate configuration which would have cost $2.6 million.

  7. [Determination of the anaerobic threshold by the rate of ventilation and cardio interval variability].

    PubMed

    Seluianov, V N; Kalinin, E M; Pak, G D; Maevskaia, V I; Konrad, A H

    2011-01-01

    The aim of this work is to develop methods for determining the anaerobic threshold according to the rate of ventilation and cardio interval variability during the test with stepwise increases load on the cycle ergometer and treadmill. In the first phase developed the method for determining the anaerobic threshold for lung ventilation. 49 highly skilled skiers took part in the experiment. They performed a treadmill ski-walking test with sticks with gradually increasing slope from 0 to 25 degrees, the slope increased by one degree every minute. In the second phase we developed a method for determining the anaerobic threshold according dynamics ofcardio interval variability during the test. The study included 86 athletes of different sports specialties who performed pedaling on the cycle ergometer "Monarch" in advance. Initial output was 25 W, power increased by 25 W every 2 min. The pace was steady--75 rev/min. Measurement of pulmonary ventilation and oxygen and carbon dioxide content was performed using gas analyzer COSMED K4. Sampling of arterial blood was carried from the ear lobe or finger, blood lactate concentration was determined using an "Akusport" instrument. RR-intervals registration was performed using heart rate monitor Polar s810i. As a result, it was shown that the graphical method for determining the onset of anaerobic threshold ventilation (VAnP) coincides with the accumulation of blood lactate 3.8 +/- 0.1 mmol/l when testing on a treadmill and 4.1 +/- 0.6 mmol/1 on the cycle ergometer. The connection between the measure of oxygen consumption at VAnP and the dispersion of cardio intervals (SD1), derived regression equation: VO2AnT = 0.35 + 0.01SD1W + 0.0016SD1HR + + 0.106SD1(ms), l/min; (R = 0.98, error evaluation function 0.26 L/min, p < 0.001), where W (W)--Power, HR--heart rate (beats/min), SD1--cardio intervals dispersion (ms) at the moment of registration of cardio interval threshold.

  8. Effect of enhanced ultraviolet germicidal irradiation in the heating ventilation and air conditioning system on ventilator-associated pneumonia in a neonatal intensive care unit.

    PubMed

    Ryan, R M; Wilding, G E; Wynn, R J; Welliver, R C; Holm, B A; Leach, C L

    2011-09-01

    The objective of this study was to test the hypothesis that enhanced ultraviolet germicidal irradiation (eUVGI) installed in our neonatal intensive care unit (NICU) heating ventilation and air conditioning system (HVAC) would decrease HVAC and NICU environment microbes, tracheal colonization and ventilator-associated pneumonia (VAP). The study was designed as a prospective interventional pre- and post-single-center study. University-affiliated Regional Perinatal Center NICU. Intubated patients in the NICU were evaluated for colonization, and a high-risk sub-population of infants <30 weeks gestation ventilated for ≥ 14 days was studied for VAP. eUVGI was installed in the NICU's remote HVACs. The HVACs, NICU environment and intubated patients' tracheas were cultured pre- and post-eUVGI for 12 months. The high-risk patients were studied for VAP (positive bacterial tracheal culture, increased ventilator support, worsening chest radiograph and ≥ 7 days of antibiotics). Pseudomonas, Klebsiella, Serratia, Acinetobacter, Staphylococcus aureus and Coagulase-negative Staphylococcus species were cultured from all sites. eUVGI significantly decreased HVAC organisms (baseline 500,000 CFU cm(-2); P=0.015) and NICU environmental microbes (P<0.0001). Tracheal microbial loads decreased 45% (P=0.004), and fewer patients became colonized. VAP in the high-risk cohort fell from 74% (n=31) to 39% (n=18), P=0.04. VAP episodes per patient decreased (Control: 1.2 to eUVGI: 0.4; P=0.004), and antibiotic usage was 62% less (P=0.013). eUVGI decreased HVAC microbial colonization and was associated with reduced NICU environment and tracheal microbial colonization. Significant reductions in VAP and antibiotic use were also associated with eUVGI in this single-center study. Large randomized multicenter trials are needed.

  9. Assessment of regional emphysema, air-trapping and Xenon-ventilation using dual-energy computed tomography in chronic obstructive pulmonary disease patients.

    PubMed

    Lee, Sang Min; Seo, Joon Beom; Hwang, Hye Jeon; Kim, Namkug; Oh, Sang Young; Lee, Jae Seung; Lee, Sei Won; Oh, Yeon-Mok; Kim, Tae Hoon

    2017-07-01

    To compare the parenchymal attenuation change between inspiration/expiration CTs with dynamic ventilation change between xenon wash-in (WI) inspiration and wash-out (WO) expiration CTs. 52 prospectively enrolled COPD patients underwent xenon ventilation dual-energy CT during WI and WO periods and pulmonary function tests (PFTs). The parenchymal attenuation parameters (emphysema index (EI), gas-trapping index (GTI) and air-trapping index (ATI)) and xenon ventilation parameters (xenon in WI (Xe-WI), xenon in WO (Xe-WO) and xenon dynamic (Xe-Dyna)) of whole lung and three divided areas (emphysema, hyperinflation and normal) were calculated on virtual non-contrast images and ventilation images. Pearson correlation, linear regression analysis and one-way ANOVA were performed. EI, GTI and ATI showed a significant correlation with Xe-WI, Xe-WO and Xe-Dyna (EI R = -.744, -.562, -.737; GTI R = -.621, -.442, -.629; ATI R = -.600, -.421, -.610, respectively, p < 0.01). All CT parameters showed significant correlation with PFTs except forced vital capacity (FVC). There was a significant difference in GTI, ATI and Xe-Dyna in each lung area (p < 0.01). The parenchymal attenuation change between inspiration/expiration CTs and xenon dynamic change between xenon WI- and WO-CTs correlate significantly. There are alterations in the dynamics of xenon ventilation between areas of emphysema. • The xenon ventilation change correlates with the parenchymal attenuation change. • The xenon ventilation change shows the difference between three lung areas. • The combination of attenuation and xenon can predict more accurate PFTs.

  10. Ventilation/Perfusion Positron Emission Tomography—Based Assessment of Radiation Injury to Lung

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Siva, Shankar, E-mail: shankar.siva@petermac.org; Sir Peter MacCallum Department of Oncology, University of Melbourne, Parkville; Hardcastle, Nicholas

    2015-10-01

    Purpose: To investigate {sup 68}Ga-ventilation/perfusion (V/Q) positron emission tomography (PET)/computed tomography (CT) as a novel imaging modality for assessment of perfusion, ventilation, and lung density changes in the context of radiation therapy (RT). Methods and Materials: In a prospective clinical trial, 20 patients underwent 4-dimensional (4D)-V/Q PET/CT before, midway through, and 3 months after definitive lung RT. Eligible patients were prescribed 60 Gy in 30 fractions with or without concurrent chemotherapy. Functional images were registered to the RT planning 4D-CT, and isodose volumes were averaged into 10-Gy bins. Within each dose bin, relative loss in standardized uptake value (SUV) was recorded for ventilation andmore » perfusion, and loss in air-filled fraction was recorded to assess RT-induced lung fibrosis. A dose-effect relationship was described using both linear and 2-parameter logistic fit models, and goodness of fit was assessed with Akaike Information Criterion (AIC). Results: A total of 179 imaging datasets were available for analysis (1 scan was unrecoverable). An almost perfectly linear negative dose-response relationship was observed for perfusion and air-filled fraction (r{sup 2}=0.99, P<.01), with ventilation strongly negatively linear (r{sup 2}=0.95, P<.01). Logistic models did not provide a better fit as evaluated by AIC. Perfusion, ventilation, and the air-filled fraction decreased 0.75 ± 0.03%, 0.71 ± 0.06%, and 0.49 ± 0.02%/Gy, respectively. Within high-dose regions, higher baseline perfusion SUV was associated with greater rate of loss. At 50 Gy and 60 Gy, the rate of loss was 1.35% (P=.07) and 1.73% (P=.05) per SUV, respectively. Of 8/20 patients with peritumoral reperfusion/reventilation during treatment, 7/8 did not sustain this effect after treatment. Conclusions: Radiation-induced regional lung functional deficits occur in a dose-dependent manner and can be estimated by simple linear models with 4D

  11. Exploring the consequences of climate change for indoor air quality

    NASA Astrophysics Data System (ADS)

    Nazaroff, William W.

    2013-03-01

    Climate change will affect the concentrations of air pollutants in buildings. The resulting shifts in human exposure may influence public health. Changes can be anticipated because of altered outdoor pollution and also owing to changes in buildings effected in response to changing climate. Three classes of factors govern indoor pollutant levels in occupied spaces: (a) properties of pollutants; (b) building factors, such as the ventilation rate; and (c) occupant behavior. Diversity of indoor conditions influences the public health significance of climate change. Potentially vulnerable subpopulations include not only the young and the infirm but also those who lack resources to respond effectively to changing conditions. Indoor air pollutant levels reflect the sum of contributions from indoor sources and from outdoor pollutants that enter with ventilation air. Pollutant classes with important indoor sources include the byproducts of combustion, radon, and volatile and semivolatile organic compounds. Outdoor pollutants of special concern include particulate matter and ozone. To ensure good indoor air quality it is important first to avoid high indoor emission rates for all pollutants and second to ensure adequate ventilation. A third factor is the use of air filtration or air cleaning to achieve further improvements where warranted. Reprinted with permission from Climate Change, the Indoor Environment, and Health (2011) by the National Academy of Sciences, Courtesy of the National Academies Press, Washington, DC.

  12. Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study.

    PubMed

    Mendell, M J; Lei-Gomez, Q; Mirer, A G; Seppänen, O; Brunner, G

    2008-08-01

    Building-related symptoms in office workers worldwide are common, but of uncertain etiology. One cause may be contaminants related to characteristics of heating, ventilating, and air-conditioning (HVAC) systems. We analyzed data from 97 representative air-conditioned US office buildings in the Building Assessment and Survey Evaluation (BASE) study. Using logistic regression models with generalized estimating equations, we estimated odds ratios (OR) and 95% confidence intervals for associations between building-related symptom outcomes and HVAC characteristics. Outdoor air intakes less than 60 m above ground level were associated with significant increases in most symptoms: e.g. for upper respiratory symptoms, OR for intake heights 30 to 60 m, 0 to <30 m, and below ground level were 2.7, 2.0, and 2.1. Humidification systems with poor condition/maintenance were associated with significantly increased upper respiratory symptoms, eye symptoms, fatigue/difficulty concentrating, and skin symptoms, with OR = 1.5, 1.5, 1.7, and 1.6. Less frequent cleaning of cooling coils and drain pans was associated with significantly increased eye symptoms and headache, with OR = 1.7 and 1.6. Symptoms may be due to microbial exposures from poorly maintained ventilation systems and to greater levels of vehicular pollutants at air intakes nearer the ground level. Replication and explanation of these findings is needed. These findings support current beliefs that moisture-related HVAC components such as cooling coils and humidification systems, when poorly maintained, may be sources of contaminants that cause adverse health effects in occupants, even if we cannot yet identify or measure the causal exposures. While finding substantially elevated risks for poorly maintained humidification systems, relative to no humidification systems, the findings do not identify important (symptom) benefits from well-maintained humidification systems. Findings also provide an initial suggestion, needing

  13. Control of asthma triggers in indoor air with air cleaners: a modeling analysis

    PubMed Central

    Myatt, Theodore A; Minegishi, Taeko; Allen, Joseph G; MacIntosh, David L

    2008-01-01

    Background Reducing exposure to environmental agents indoors shown to increase asthma symptoms or lead to asthma exacerbations is an important component of a strategy to manage asthma for individuals. Numerous investigations have demonstrated that portable air cleaning devices can reduce concentrations of asthma triggers in indoor air; however, their benefits for breathing problems have not always been reproducible. The potential exposure benefits of whole house high efficiency in-duct air cleaners for sensitive subpopulations have yet to be evaluated. Methods We used an indoor air quality modeling system (CONTAM) developed by NIST to examine peak and time-integrated concentrations of common asthma triggers present in indoor air over a year as a function of natural ventilation, portable air cleaners, and forced air ventilation equipped with conventional and high efficiency filtration systems. Emission rates for asthma triggers were based on experimental studies published in the scientific literature. Results Forced air systems with high efficiency filtration were found to provide the best control of asthma triggers: 30–55% lower cat allergen levels, 90–99% lower risk of respiratory infection through the inhalation route of exposure, 90–98% lower environmental tobacco smoke (ETS) levels, and 50–75% lower fungal spore levels than the other ventilation/filtration systems considered. These results indicate that the use of high efficiency in-duct air cleaners provide an effective means of controlling allergen levels not only in a single room, like a portable air cleaner, but the whole house. Conclusion These findings are useful for evaluating potential benefits of high efficiency in-duct filtration systems for controlling exposure to asthma triggers indoors and for the design of trials of environmental interventions intended to evaluate their utility in practice. PMID:18684328

  14. Pressure Dynamic Characteristics of Pressure Controlled Ventilation System of a Lung Simulator

    PubMed Central

    Shi, Yan; Ren, Shuai; Cai, Maolin; Xu, Weiqing; Deng, Qiyou

    2014-01-01

    Mechanical ventilation is an important life support treatment of critically ill patients, and air pressure dynamics of human lung affect ventilation treatment effects. In this paper, in order to obtain the influences of seven key parameters of mechanical ventilation system on the pressure dynamics of human lung, firstly, mechanical ventilation system was considered as a pure pneumatic system, and then its mathematical model was set up. Furthermore, to verify the mathematical model, a prototype mechanical ventilation system of a lung simulator was proposed for experimental study. Last, simulation and experimental studies on the air flow dynamic of the mechanical ventilation system were done, and then the pressure dynamic characteristics of the mechanical system were obtained. The study can be referred to in the pulmonary diagnostics, treatment, and design of various medical devices or diagnostic systems. PMID:25197318

  15. Air pollution in Boston bars before and after a smoking ban.

    PubMed

    Repace, James L; Hyde, James N; Brugge, Doug

    2006-10-27

    We quantified the air quality benefits of a smoke-free workplace law in Boston Massachusetts, U.S.A., by measuring air pollution from secondhand smoke (SHS) in 7 pubs before and after the law, comparing actual ventilation practices to engineering society (ASHRAE) recommendations, and assessing SHS levels using health and comfort indices. We performed real-time measurements of respirable particle (RSP) air pollution and particulate polycyclic aromatic hydrocarbons (PPAH), in 7 pubs and outdoors in a model-based design yielding air exchange rates for RSP removal. We also assessed ventilation rates from carbon dioxide concentrations. We compared RSP air pollution to the federal Air Quality Index (AQI) and the National Ambient Air Quality Standard (NAAQS) to assess health risks, and assessed odor and irritation levels using published SHS-RSP thresholds. Pre-smoking-ban RSP levels in 6 pubs (one pub with a non-SHS air quality problem was excluded) averaged 179 microg/m3, 23 times higher than post-ban levels, which averaged 7.7 microg/m3, exceeding the NAAQS for fine particle pollution (PM2.5) by nearly 4-fold. Pre-smoking ban levels of fine particle air pollution in all 7 of the pubs were in the Unhealthy to Hazardous range of the AQI. In the same 6 pubs, pre-ban indoor carcinogenic PPAH averaged 61.7 ng/m3, nearly 10 times higher than post-ban levels of 6.32 ng/m3. Post-ban particulate air pollution levels were in the Good AQI range, except for 1 venue with a defective gas-fired deep-fat fryer, while post-ban carcinogen levels in all 7 pubs were lower than outdoors. During smoking, although pub ventilation rates per occupant were within ASHRAE design parameters for the control of carbon dioxide levels for the number of occupants present, they failed to control SHS carcinogens or RSP. Nonsmokers' SHS odor and irritation sensory thresholds were massively exceeded. Post-ban air pollution measurements showed 90% to 95% reductions in PPAH and RSP respectively, differing

  16. Constant-flow ventilation in canine experimental pulmonary emphysema.

    PubMed

    Hachenberg, T; Wendt, M; Meyer, J; Struckmeier, O; Lawin, P

    1989-07-01

    The efficacy of constant-flow ventilation (CFV) was investigated in eight mongrel dogs before (control-phase) and after development of papain-induced panlobular emphysema (PLE-phase). For CFV, heated, humidified and oxygen-enriched air was continuously delivered via two catheters positioned within each mainstem bronchus at flow rates (V) of 0.33, 0.5 and 0.66 l/s. Data obtained during intermittent positive pressure ventilation (IPPV) served as reference. In the control-phase, Pao2 was lower (P less than or equal to 0.05) and alveolo-arterial O2 difference (P(A-a)O2) was higher (P less than or equal to 0.01) during CFV at all flow rates when compared with IPPV. This may be due to inhomogeneities of intrapulmonary gas distribution and increased ventilation-perfusion (VA/Q) mismatching. Paco2 and V showed a hyperbolic relationship; constant normocapnia (5.3 kPa) was achieved at 0.48 +/- 0.21 l/s (V53). Development of PLE resulted in an increase of functional residual capacity (FRC), residual volume (RV) and static compliance (Cstat) (P less than or equal to 0.05). PaO2 had decreased and P(A-a)O2 had increased (P less than or equal to 0.05), indicating moderate pulmonary dysfunction. Oxygenation during CFV was not significantly different in the PLE-phase when compared with the control-phase. Paco2 and V showed a hyperbolic relationship and V5.3 was even lower than in the control-group (0.42 +/- 0.13 l/s). In dogs with emphysematous lungs CFV maintains sufficient gas exchange. This may be due to preferential ventilation of basal lung units, thereby counterbalancing the effects of impaired lung morphometry and increased airtrapping. Conventional mechanical ventilation is more effective in terms of oxygenation and CO2-elimination.

  17. Model-based setting of inspiratory pressure and respiratory rate in pressure-controlled ventilation.

    PubMed

    Schranz, C; Becher, T; Schädler, D; Weiler, N; Möller, K

    2014-03-01

    Mechanical ventilation carries the risk of ventilator-induced-lung-injury (VILI). To minimize the risk of VILI, ventilator settings should be adapted to the individual patient properties. Mathematical models of respiratory mechanics are able to capture the individual physiological condition and can be used to derive personalized ventilator settings. This paper presents model-based calculations of inspiration pressure (pI), inspiration and expiration time (tI, tE) in pressure-controlled ventilation (PCV) and a retrospective evaluation of its results in a group of mechanically ventilated patients. Incorporating the identified first order model of respiratory mechanics in the basic equation of alveolar ventilation yielded a nonlinear relation between ventilation parameters during PCV. Given this patient-specific relation, optimized settings in terms of minimal pI and adequate tE can be obtained. We then retrospectively analyzed data from 16 ICU patients with mixed pathologies, whose ventilation had been previously optimized by ICU physicians with the goal of minimization of inspiration pressure, and compared the algorithm's 'optimized' settings to the settings that had been chosen by the physicians. The presented algorithm visualizes the patient-specific relations between inspiration pressure and inspiration time. The algorithm's calculated results highly correlate to the physician's ventilation settings with r = 0.975 for the inspiration pressure, and r = 0.902 for the inspiration time. The nonlinear patient-specific relations of ventilation parameters become transparent and support the determination of individualized ventilator settings according to therapeutic goals. Thus, the algorithm is feasible for a variety of ventilated ICU patients and has the potential of improving lung-protective ventilation by minimizing inspiratory pressures and by helping to avoid the build-up of clinically significant intrinsic positive end-expiratory pressure.

  18. Change-over natural and mechanical ventilation system energy consumption in single-family buildings

    NASA Astrophysics Data System (ADS)

    Kostka, Maria; Szulgowska-Zgrzywa, Małgorzata

    2017-11-01

    The parameters of the outside air in Poland cause that in winter it is reasonable to use a mechanical ventilation equipped with a heat recovery exchanger. The time of spring, autumn, summer evenings and nights are often characterized by the parameters of the air, which allow for a natural ventilation and reduce the electricity consumption. The article presents the possibilities of energy consumption reduction for three energy standards of buildings located in Poland, ventilated by a change-over hybrid system. The analysis was prepared on the assumption that the air-to-water heat pump is the heat source for the buildings.

  19. DIRECT MEASUREMENT TECHNIQUE FOR THE DETERMINING VENTILATION RATE IN THE DEPOSIT FEEDING CLAM, MACOMA NASUTA (BIVALVIA, TELLINACEAE)

    EPA Science Inventory

    An exposure chamber, the "clambox", was developed to measure ventilation rate, sediment processing rate, and efficiency of pollutant uptake byMacoma nasuta Conrad, a surface surface deposit-feeding clams. Clams, collected from Yaquina, Bay, Oregon, USA, were cemented into a hole ...

  20. Reaerosolization of Fluidized Spores in Ventilation Systems▿

    PubMed Central

    Krauter, Paula; Biermann, Arthur

    2007-01-01

    This project examined dry, fluidized spore reaerosolization in a heating, ventilating, and air conditioning duct system. Experiments using spores of Bacillus atrophaeus, a nonpathogenic surrogate for Bacillus anthracis, were conducted to delineate the extent of spore reaerosolization behavior under normal indoor airflow conditions. Short-term (five air-volume exchanges), long-term (up to 21,000 air-volume exchanges), and cycled (on-off) reaerosolization tests were conducted using two common duct materials. Spores were released into the test apparatus in turbulent airflow (Reynolds number, 26,000). After the initial pulse of spores (approximately 1010 to 1011 viable spores) was released, high-efficiency particulate air filters were added to the air intake. Airflow was again used to perturb the spores that had previously deposited onto the duct. Resuspension rates on both steel and plastic duct materials were between 10−3 and 10−5 per second, which decreased to 10 times less than initial rates within 30 min. Pulsed flow caused an initial spike in spore resuspension concentration that rapidly decreased. The resuspension rates were greater than those predicted by resuspension models for contamination in the environment, a result attributed to surface roughness differences. There was no difference between spore reaerosolization from metal and that from plastic duct surfaces over 5 hours of constant airflow. The spores that deposited onto the duct remained a persistent source of contamination over a period of several hours. PMID:17293522

  1. SU-F-J-219: Predicting Ventilation Change Due to Radiation Therapy: Dependency On Pre-RT Ventilation and Effort Correction

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Patton, T; Du, K; Bayouth, J

    Purpose: Ventilation change caused by radiation therapy (RT) can be predicted using four-dimensional computed tomography (4DCT) and image registration. This study tested the dependency of predicted post-RT ventilation on effort correction and pre-RT lung function. Methods: Pre-RT and 3 month post-RT 4DCT images were obtained for 13 patients. The 4DCT images were used to create ventilation maps using a deformable image registration based Jacobian expansion calculation. The post-RT ventilation maps were predicted in four different ways using the dose delivered, pre-RT ventilation, and effort correction. The pre-RT ventilation and effort correction were toggled to determine dependency. The four different predictedmore » ventilation maps were compared to the post-RT ventilation map calculated from image registration to establish the best prediction method. Gamma pass rates were used to compare the different maps with the criteria of 2mm distance-to-agreement and 6% ventilation difference. Paired t-tests of gamma pass rates were used to determine significant differences between the maps. Additional gamma pass rates were calculated using only voxels receiving over 20 Gy. Results: The predicted post-RT ventilation maps were in agreement with the actual post-RT maps in the following percentage of voxels averaged over all subjects: 71% with pre-RT ventilation and effort correction, 69% with no pre-RT ventilation and effort correction, 60% with pre-RT ventilation and no effort correction, and 58% with no pre-RT ventilation and no effort correction. When analyzing only voxels receiving over 20 Gy, the gamma pass rates were respectively 74%, 69%, 65%, and 55%. The prediction including both pre- RT ventilation and effort correction was the only prediction with significant improvement over using no prediction (p<0.02). Conclusion: Post-RT ventilation is best predicted using both pre-RT ventilation and effort correction. This is the only prediction that provided a significant

  2. Ventilation Positive Pressure Intervention Effect on Indoor Air Quality in a School Building with Moisture Problems

    PubMed Central

    Vornanen-Winqvist, Camilla; Järvi, Kati; Toomla, Sander; Ahmed, Kaiser; Andersson, Maria A.; Mikkola, Raimo; Marik, Tamás; Salonen, Heidi

    2018-01-01

    This case study investigates the effects of ventilation intervention on measured and perceived indoor air quality (IAQ) in a repaired school where occupants reported IAQ problems. Occupants’ symptoms were suspected to be related to the impurities leaked indoors through the building envelope. The study’s aim was to determine whether a positive pressure of 5–7 Pa prevents the infiltration of harmful chemical and microbiological agents from structures, thus decreasing symptoms and discomfort. Ventilation intervention was conducted in a building section comprising 12 classrooms and was completed with IAQ measurements and occupants’ questionnaires. After intervention, the concentration of total volatile organic compounds (TVOC) and fine particulate matter (PM2.5) decreased, and occupants’ negative perceptions became more moderate compared to those for other parts of the building. The indoor mycobiota differed in species composition from the outdoor mycobiota, and changed remarkably with the intervention, indicating that some species may have emanated from an indoor source before the intervention. PMID:29385772

  3. Ventilation Positive Pressure Intervention Effect on Indoor Air Quality in a School Building with Moisture Problems.

    PubMed

    Vornanen-Winqvist, Camilla; Järvi, Kati; Toomla, Sander; Ahmed, Kaiser; Andersson, Maria A; Mikkola, Raimo; Marik, Tamás; Kredics, László; Salonen, Heidi; Kurnitski, Jarek

    2018-01-30

    This case study investigates the effects of ventilation intervention on measured and perceived indoor air quality (IAQ) in a repaired school where occupants reported IAQ problems. Occupants' symptoms were suspected to be related to the impurities leaked indoors through the building envelope. The study's aim was to determine whether a positive pressure of 5-7 Pa prevents the infiltration of harmful chemical and microbiological agents from structures, thus decreasing symptoms and discomfort. Ventilation intervention was conducted in a building section comprising 12 classrooms and was completed with IAQ measurements and occupants' questionnaires. After intervention, the concentration of total volatile organic compounds (TVOC) and fine particulate matter (PM 2.5 ) decreased, and occupants' negative perceptions became more moderate compared to those for other parts of the building. The indoor mycobiota differed in species composition from the outdoor mycobiota, and changed remarkably with the intervention, indicating that some species may have emanated from an indoor source before the intervention.

  4. 46 CFR 38.20-10 - Ventilation-T/ALL.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... equipped with power ventilation of the exhaust type having capacity sufficient to effect a complete change of air in not more than 3 minutes equal to the volume of the compartment and associated trunks. (b) The power ventilation units shall not produce a source of vapor ignition in either the compartment or...

  5. An expert system for the design of heating, ventilating, and air-conditioning systems

    NASA Astrophysics Data System (ADS)

    Camejo, Pedro Jose

    1989-12-01

    Expert systems are computer programs that seek to mimic human reason. An expert system shelf, a software program commonly used for developing expert systems in a relatively short time, was used to develop a prototypical expert system for the design of heating, ventilating, and air-conditioning (HVAC) systems in buildings. Because HVAC design involves several related knowledge domains, developing an expert system for HVAC design requires the integration of several smaller expert systems known as knowledge bases. A menu program and several auxiliary programs for gathering data, completing calculations, printing project reports, and passing data between the knowledge bases are needed and have been developed to join the separate knowledge bases into one simple-to-use program unit.

  6. Application of acoustic agglomeration to enhance air filtration efficiency in air-conditioning and mechanical ventilation (ACMV) systems.

    PubMed

    Ng, Bing Feng; Xiong, Jin Wen; Wan, Man Pun

    2017-01-01

    The recent episodes of haze in Southeast Asia have caused some of the worst regional atmospheric pollution ever recorded in history. In order to control the levels of airborne fine particulate matters (PM) indoors, filtration systems providing high PM capturing efficiency are often sought, which inadvertently also results in high airflow resistance (or pressure drop) that increases the energy consumption for air distribution. A pre-conditioning mechanism promoting the formation of particle clusters to enhance PM capturing efficiency without adding flow resistance in the air distribution ductwork could provide an energy-efficient solution. This pre-conditioning mechanism can be fulfilled by acoustic agglomeration, which is a phenomenon that promotes the coagulation of suspended particles by acoustic waves propagating in the fluid medium. This paper discusses the basic mechanisms of acoustic agglomeration along with influencing factors that could affect the agglomeration efficiency. The feasibility to apply acoustic agglomeration to improve filtration in air-conditioning and mechanical ventilation (ACMV) systems is investigated experimentally in a small-scale wind tunnel. Experimental results indicate that this novel application of acoustic pre-conditioning improves the PM2.5 filtration efficiency of the test filters by up to 10% without introducing additional pressure drop. The fan energy savings from not having to switch to a high capturing efficiency filter largely outstrip the additional energy consumed by the acoustics system. This, as a whole, demonstrates potential energy savings from the combined acoustic-enhanced filtration system without compromising on PM capturing efficiency.

  7. Application of acoustic agglomeration to enhance air filtration efficiency in air-conditioning and mechanical ventilation (ACMV) systems

    PubMed Central

    Xiong, Jin Wen; Wan, Man Pun

    2017-01-01

    The recent episodes of haze in Southeast Asia have caused some of the worst regional atmospheric pollution ever recorded in history. In order to control the levels of airborne fine particulate matters (PM) indoors, filtration systems providing high PM capturing efficiency are often sought, which inadvertently also results in high airflow resistance (or pressure drop) that increases the energy consumption for air distribution. A pre-conditioning mechanism promoting the formation of particle clusters to enhance PM capturing efficiency without adding flow resistance in the air distribution ductwork could provide an energy-efficient solution. This pre-conditioning mechanism can be fulfilled by acoustic agglomeration, which is a phenomenon that promotes the coagulation of suspended particles by acoustic waves propagating in the fluid medium. This paper discusses the basic mechanisms of acoustic agglomeration along with influencing factors that could affect the agglomeration efficiency. The feasibility to apply acoustic agglomeration to improve filtration in air-conditioning and mechanical ventilation (ACMV) systems is investigated experimentally in a small-scale wind tunnel. Experimental results indicate that this novel application of acoustic pre-conditioning improves the PM2.5 filtration efficiency of the test filters by up to 10% without introducing additional pressure drop. The fan energy savings from not having to switch to a high capturing efficiency filter largely outstrip the additional energy consumed by the acoustics system. This, as a whole, demonstrates potential energy savings from the combined acoustic-enhanced filtration system without compromising on PM capturing efficiency. PMID:28594862

  8. Conservative fluid management prevents age-associated ventilator induced mortality.

    PubMed

    Herbert, Joseph A; Valentine, Michael S; Saravanan, Nivi; Schneck, Matthew B; Pidaparti, Ramana; Fowler, Alpha A; Reynolds, Angela M; Heise, Rebecca L

    2016-08-01

    Approximately 800 thousand patients require mechanical ventilation in the United States annually with an in-hospital mortality rate of over 30%. The majority of patients requiring mechanical ventilation are over the age of 65 and advanced age is known to increase the severity of ventilator-induced lung injury (VILI) and in-hospital mortality rates. However, the mechanisms which predispose aging ventilator patients to increased mortality rates are not fully understood. Ventilation with conservative fluid management decreases mortality rates in acute respiratory distress patients, but to date there has been no investigation of the effect of conservative fluid management on VILI and ventilator associated mortality rates. We hypothesized that age-associated increases in susceptibility and incidence of pulmonary edema strongly promote age-related increases in ventilator associated mortality. 2month old and 20month old male C57BL6 mice were mechanically ventilated with either high tidal volume (HVT) or low tidal volume (LVT) for up to 4h with either liberal or conservative fluid support. During ventilation, lung compliance, total lung capacity, and hysteresis curves were quantified. Following ventilation, bronchoalveolar lavage fluid was analyzed for total protein content and inflammatory cell infiltration. Wet to dry ratios were used to directly measure edema in excised lungs. Lung histology was performed to quantify alveolar barrier damage/destruction. Age matched non-ventilated mice were used as controls. At 4h, both advanced age and HVT ventilation significantly increased markers of inflammation and injury, degraded pulmonary mechanics, and decreased survival rates. Conservative fluid support significantly diminished pulmonary edema and improved pulmonary mechanics by 1h in advanced age HVT subjects. In 4h ventilations, conservative fluid support significantly diminished pulmonary edema, improved lung mechanics, and resulted in significantly lower mortality rates in

  9. Conservative Fluid Management Prevents Age-Associated Ventilator Induced Mortality

    PubMed Central

    Herbert, Joseph A.; Valentine, Michael S.; Saravanan, Nivi; Schneck, Matthew B.; Pidaparti, Ramana; Fowler, Alpha A.; Reynolds, Angela M.; Heise, Rebecca L.

    2017-01-01

    Background Approximately 800 thousand patients require mechanical ventilation in the United States annually with an in-hospital mortality rate of over 30%. The majority of patients requiring mechanical ventilation are over the age of 65 and advanced age is known to increase the severity of ventilator-induced lung injury (VILI) and in-hosptial mortality rates. However, the mechanisms which predispose aging ventilator patients to increased mortality rates are not fully understood. Ventilation with conservative fluid management decreases mortality rates in acute respiratory distress patients, but to date there has been no investigation of the effect of conservative fluid management on VILI and ventilator associated mortality rates. We hypothesized that age-associated increases in susceptibility and incidence of pulmonary edema strongly promote age-related increases in ventilator associated mortality. Methods 2 month old and 20 month old male C57BL6 mice were mechanically ventilated with either high tidal volume (HVT) or low tidal volume (LVT) for up to 4 hours with either liberal or conservative fluid support. During ventilation, lung compliance, total lung capacity, and hysteresis curves were quantified. Following ventilation, bronchoalveolar lavage fluid was analyzed for total protein content and inflammatory cell infiltration. Wet to dry ratios were used to directly measure edema in excised lungs. Lung histology was performed to quantify alveolar barrier damage/destruction. Age matched non-ventilated mice were used as controls. Results At 4hrs, both advanced age and HVT ventilation significantly increased markers of inflammation and injury, degraded pulmonary mechanics, and decreased survival rates. Conservative fluid support significantly diminished pulmonary edema and improved pulmonary mechanics by 1hr in advanced age HVT subjects. In 4hr ventilations, conservative fluid support significantly diminished pulmonary edema, improved lung mechanics, and resulted in

  10. Collective fluid mechanics of honeybee nest ventilation

    NASA Astrophysics Data System (ADS)

    Gravish, Nick; Combes, Stacey; Wood, Robert J.; Peters, Jacob

    2014-11-01

    Honeybees thermoregulate their brood in the warm summer months by collectively fanning their wings and creating air flow through the nest. During nest ventilation workers flap their wings in close proximity in which wings continuously operate in unsteady oncoming flows (i.e. the wake of neighboring worker bees) and near the ground. The fluid mechanics of this collective aerodynamic phenomena are unstudied and may play an important role in the physiology of colony life. We have performed field and laboratory observations of the nest ventilation wing kinematics and air flow generated by individuals and groups of honeybee workers. Inspired from these field observations we describe here a robotic model system to study collective flapping wing aerodynamics. We microfabricate arrays of 1.4 cm long flapping wings and observe the air flow generated by arrays of two or more fanning robotic wings. We vary phase, frequency, and separation distance among wings and find that net output flow is enhanced when wings operate at the appropriate phase-distance relationship to catch shed vortices from neighboring wings. These results suggest that by varying position within the fanning array honeybee workers may benefit from collective aerodynamic interactions during nest ventilation.

  11. The Fluid Mechanics of Natural Ventilation

    NASA Astrophysics Data System (ADS)

    Linden, P. F.

    1999-01-01

    Natural ventilation of buildings is the flow generated by temperature differences and by the wind. The governing feature of this flow is the exchange between an interior space and the external ambient. Although the wind may often appear to be the dominant driving mechanism, in many circumstances temperature variations play a controlling feature on the ventilation since the directional buoyancy force has a large influence on the flow patterns within the space and on the nature of the exchange with the outside. Two forms of ventilation are discussed: mixing ventilation, in which the interior is at an approximately uniform temperature, and displacement ventilation, where there is strong internal stratification. The dynamics of these buoyancy-driven flows are considered, and the effects of wind on them are examined. The aim behind this work is to give designers rules and intuition on how air moves within a building; the research reveals a fascinating branch of fluid mechanics.

  12. Particle size distribution and composition in a mechanically ventilated school building during air pollution episodes.

    PubMed

    Parker, J L; Larson, R R; Eskelson, E; Wood, E M; Veranth, J M

    2008-10-01

    Particle count-based size distribution and PM(2.5) mass were monitored inside and outside an elementary school in Salt Lake City (UT, USA) during the winter atmospheric inversion season. The site is influenced by urban traffic and the airshed is subject to periods of high PM(2.5) concentration that is mainly submicron ammonium and nitrate. The school building has mechanical ventilation with filtration and variable-volume makeup air. Comparison of the indoor and outdoor particle size distribution on the five cleanest and five most polluted school days during the study showed that the ambient submicron particulate matter (PM) penetrated the building, but indoor concentrations were about one-eighth of outdoor levels. The indoor:outdoor PM(2.5) mass ratio averaged 0.12 and particle number ratio for sizes smaller than 1 microm averaged 0.13. The indoor submicron particle count and indoor PM(2.5) mass increased slightly during pollution episodes but remained well below outdoor levels. When the building was occupied the indoor coarse particle count was much higher than ambient levels. These results contribute to understanding the relationship between ambient monitoring station data and the actual human exposure inside institutional buildings. The study confirms that staying inside a mechanically ventilated building reduces exposure to outdoor submicron particles. This study supports the premise that remaining inside buildings during particulate matter (PM) pollution episodes reduces exposure to submicron PM. New data on a mechanically ventilated institutional building supplements similar studies made in residences.

  13. Silver zeolite antimicrobial activity in aluminium heating, ventilation and air conditioning system ducts.

    PubMed

    Rizzetto, R; Mansi, A; Panatto, D; Rizzitelli, E; Tinteri, C; Sasso, T; Gasparini, R; Crovari, P

    2008-03-01

    Air pollution in confined environments is a serious health problem, in that most people spend long periods indoors (in homes, offices, classrooms etc.). Some people (children, the elderly, heart disease patients, asthmatic or allergic subjects) are at greater risk because of their conditions of frailty. The growing use of air-conditioning systems in many public and private buildings aggravates this health risk, especially when these systems are not correctly installed or regularly serviced. The aim of our study was to verify the capacity of Ag+ ions to stop the growth of bacteria and moulds inside the ducts of Heating, Ventilation and Air Conditioning system ducts (HVAC) systems when these ducts were lined with active Ag+ ions zeolite-coated panels. A Y-shaped HVAC model with two branches was used; one branch was made of traditional galvanized iron, as was the whole system, while the other was lined with active Ag+ zeolite-coated polyurethane panels. During the test, samples of dust present inside both ducts were collected and seeded in liquid and solid media to detect bacteria and moulds. The presence of bacteria was also sought in the air emerging from the outlets of both ducts. Tests made on samples of particulate collected from the two different ducts revealed a lower total bacterial load in the samples collected from the Ag+ zeolite-coated duct than in the samples from the traditional Zn galvanized duct. In addition, the values of bacterial load found in the air emerging from the Ag+ ions zeolite-lined duct were 5 times lower than those found in the air from the traditional galvanized iron duct. The utilization of Ag+ zeolite-coated panels in air-conditioning systems could improve the quality of the emerging air in comparison with traditional installations in galvanized iron. This innovation could prove particularly advantageous in the event of accidents during the installation of air-conditioning systems or of contaminated aerosols coming from outside.

  14. Radon-222 signatures of natural ventilation regimes in an underground quarry.

    PubMed

    Perrier, Frédéric; Richon, Patrick; Crouzeix, Catherine; Morat, Pierre; Le Mouël, Jean Louis

    2004-01-01

    Radon-222 activity concentration has been monitored since 1999 in an underground limestone quarry located in Vincennes, near Paris, France. It is homogeneous in summer, with an average value of 1700 Bq m(-3), and varies from 730 to 1450 Bq m(-3) in winter, indicating natural ventilation with a rate ranging from 0.5 to 2.4 x 10(-6) s(-1) (0.04-0.22 day(-1)). This hypothesis is supported by measurements in the vertical access pit where, in winter, a turbulent air current produces a stable radon profile, smoothly decreasing from 700 Bq m(-3) at 20 m depth to 300 Bq m(-3) at surface. In summer, a thermal stratification is maintained in the pit, but the radon-222 concentration jumps repeatedly between 100 and 2000 Bq m(-3). These jumps are due to atmospheric pressure pumping, which induces ventilation in the quarry at a rate of about 0.1 x 10(-6) s(-1) (0.009 day(-1)). Radon-222 monitoring thus provides a dynamical characterisation of ventilation regimes, which is important for the assessment of the long-term evolution of underground systems.

  15. Simulation of air quality and operational cost to ventilate swine farrowing facilities in Midwest U.S. during winter

    PubMed Central

    Park, Jae Hong; Peters, Thomas M.; Altmaier, Ralph; Jones, Samuel M.; Gassman, Richard; Anthony, T. Renée

    2017-01-01

    We have developed a time-dependent simulation model to estimate in-room concentrations of multiple contaminants [ammonia (NH3), carbon dioxide (CO2), carbon monoxide (CO) and dust] as a function of increased ventilation with filtered recirculation for swine farrowing facilities. Energy and mass balance equations were used to simulate the indoor air quality (IAQ) and operational cost for a variety of ventilation conditions over a 3-month winter period for a facility located in the Midwest U.S., using simplified and real-time production parameters, comparing results to field data. A revised model was improved by minimizing the sum of squared errors (SSE) between modeled and measured NH3 and CO2. After optimizing NH3 and CO2, other IAQ results from the simulation were compared to field measurements using linear regression. For NH3, the coefficient of determination (R2) for simulation results and field measurements improved from 0.02 with the original model to 0.37 with the new model. For CO2, the R2 for simulation results and field measurements was 0.49 with the new model. When the makeup air was matched to hallway air CO2 concentrations (1,500 ppm), simulation results showed the smallest SSE. With the new model, the R2 for other contaminants were 0.34 for inhalable dust, 0.36 for respirable dust, and 0.26 for CO. Operation of the air cleaner decreased inhalable dust by 35% and respirable dust concentrations by 33%, while having no effect on NH3, CO2, in agreement with field data, and increasing operational cost by $860 (58%) for the three-month period. PMID:28775911

  16. Air velocity distributions inside tree canopies from a variable-rate air-assisted sprayer

    USDA-ARS?s Scientific Manuscript database

    A variable-rate, air assisted, five-port sprayer had been in development to achieve variable discharge rates of both liquid and air. To verify the variable air rate capability by changing the fan inlet diameter of the sprayer, air jet velocities impeded by plant canopies were measured at various loc...

  17. 46 CFR 185.352 - Ventilation of gasoline machinery spaces.

    Code of Federal Regulations, 2012 CFR

    2012-10-01

    ... 46 Shipping 7 2012-10-01 2012-10-01 false Ventilation of gasoline machinery spaces. 185.352... machinery spaces. The mechanical exhaust for the ventilation of a gasoline machinery space, required by... sufficient to insure at least one complete change of air in the space served. ...

  18. 46 CFR 185.352 - Ventilation of gasoline machinery spaces.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Ventilation of gasoline machinery spaces. 185.352... machinery spaces. The mechanical exhaust for the ventilation of a gasoline machinery space, required by... sufficient to insure at least one complete change of air in the space served. ...

  19. Development and Design of a User Interface for a Computer Automated Heating, Ventilation, and Air Conditioning System

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Anderson, B.; /Fermilab

    1999-10-08

    A user interface is created to monitor and operate the heating, ventilation, and air conditioning system. The interface is networked to the system's programmable logic controller. The controller maintains automated control of the system. The user through the interface is able to see the status of the system and override or adjust the automatic control features. The interface is programmed to show digital readouts of system equipment as well as visual queues of system operational statuses. It also provides information for system design and component interaction. The interface is made easier to read by simple designs, color coordination, and graphics.more » Fermi National Accelerator Laboratory (Fermi lab) conducts high energy particle physics research. Part of this research involves collision experiments with protons, and anti-protons. These interactions are contained within one of two massive detectors along Fermilab's largest particle accelerator the Tevatron. The D-Zero Assembly Building houses one of these detectors. At this time detector systems are being upgraded for a second experiment run, titled Run II. Unlike the previous run, systems at D-Zero must be computer automated so operators do not have to continually monitor and adjust these systems during the run. Human intervention should only be necessary for system start up and shut down, and equipment failure. Part of this upgrade includes the heating, ventilation, and air conditioning system (HVAC system). The HVAC system is responsible for controlling two subsystems, the air temperatures of the D-Zero Assembly Building and associated collision hall, as well as six separate water systems used in the heating and cooling of the air and detector components. The BYAC system is automated by a programmable logic controller. In order to provide system monitoring and operator control a user interface is required. This paper will address methods and strategies used to design and implement an effective user

  20. Use of Recirculating Ventilation with Dust Filtration to Improve Wintertime Air Quality in a Swine Farrowing Room

    PubMed Central

    Anthony, T. Renée; Altmaier, Ralph; Jones, Samuel; Gassman, Rich; Park, Jae Hong; Peters, Thomas M.

    2016-01-01

    The performance of a recirculating ventilation system with dust filtration was evaluated to determine its effectiveness to improve the air quality in a swine farrowing room of a concentrated animal feeding operation (CAFO). Air was exhausted from the room (0.47 m3sec−1; 1000 cfm), treated with a filtration unit (Shaker-Dust Collector), and returned to the farrowing room to reduce dust concentrations while retaining heat necessary for livestock health. The air quality in the room was assessed over a winter, during which time limited fresh air is traditionally brought into the building. Over the study period, dust concentrations ranged from 0.005 to 0.31 mg m−3 (respirable) and 0.17 to 2.09 mg m−3 (inhalable). In-room dust concentrations were reduced (41% for respirable and 33% for inhalable) with the system in operation, while gas concentrations (ammonia [NH3], hydrogen sulfide [H2S], carbon monoxide [CO], carbon dioxide [CO2]) were unchanged. The position of the exhaust and return air systems provided reasonably uniform contaminant distributions, although the respirable dust concentrations nearest one of the exhaust ducts was statistically higher than other locations in the room, with differences averaging only 0.05 mg m−3. Throughout the study, CO2 concentrations consistently exceeded 1540 ppm (industry recommendations) and on eight of the 18 study days it exceeded 2500 ppm (50% of the ACGIH TLV), with significantly higher concentrations near a door to a temperature-controlled hallway that was typically often left open. Alternative heaters are recommended to reduce CO2 concentrations in the room. Contaminant concentrations were modeled using production and environmental factors, with NH3 related to the number of sow in the room and outdoor temperatures and CO2 related to the number of piglets and outdoor temperatures. The recirculating ventilation system provided dust reduction without increasing concentrations of hazardous gases. PMID:25950713

  1. A Survey and Critical Review of the Literature on Indoor Air Quality, Ventilation and Health Symptoms in Schools. IEQ Strategies[TM].

    ERIC Educational Resources Information Center

    Daisey, Joan M.; Angell, William J.

    This report presents detailed results from a survey and critical review of existing published literature and reports on indoor air quality (IAQ), ventilation, and IAQ- and building-related health problems in schools, particularly California schools. The findings: (1) identify the most commonly reported building-related health symtoms involving…

  2. Ventilation and ventilators.

    PubMed

    Hayes, B

    1982-01-01

    The history of ventilation is reviewed briefly and recent developments in techniques of ventilation are discussed. Operating features of ventilators have changed in the past few years, partly as the result of clinical progress; yet, technology appears to have outstripped the clinician's ability to harness it most effectively. Clinical discipline and training of medical staff in the use of ventilators could be improved. The future is promising if clinician and designer can work together closely. Ergonomics of ventilators and their controls and the provision of alarms need special attention. Microprocessors are likely to feature prominently in the next generation of designs.

  3. Face mask ventilation in edentulous patients: a comparison of mandibular groove and lower lip placement.

    PubMed

    Racine, Stéphane X; Solis, Audrey; Hamou, Nora Ait; Letoumelin, Philippe; Hepner, David L; Beloucif, Sadek; Baillard, Christophe

    2010-05-01

    In edentulous patients, it may be difficult to perform face mask ventilation because of inadequate seal with air leaks. Our aim was to ascertain whether the "lower lip" face mask placement, as a new face mask ventilation method, is more effective at reducing air leaks than the standard face mask placement. Forty-nine edentulous patients with inadequate seal and air leak during two-hand positive-pressure ventilation using the ventilator circle system were prospectively evaluated. In the presence of air leaks, defined as a difference of at least 33% between inspired and expired tidal volumes, the mask was placed in a lower lip position by repositioning the caudal end of the mask above the lower lip while maintaining the head in extension. The results are expressed as mean +/- SD or median (25th-75th percentiles). Patient characteristics included age (71 +/- 11 yr) and body mass index (24 +/- 4 kg/m2). By using the standard method, the median inspired and expired tidal volumes were 450 ml (400-500 ml) and 0 ml (0-50 ml), respectively, and the median air leak was 400 ml (365-485 ml). After placing the mask in the lower lip position, the median expired tidal volume increased to 400 ml (380-490), and the median air leak decreased to 10 ml (0-20 ml) (P < 0.001 vs. standard method). The lower lip face mask placement with two hands reduced the air leak by 95% (80-100%). In edentulous patients with inadequate face mask ventilation, the lower lip face mask placement with two hands markedly reduced the air leak and improved ventilation.

  4. 5. VIEW OF VENTILATION HOUSES AND ROOF MONITOR FROM SOUTHEAST ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    5. VIEW OF VENTILATION HOUSES AND ROOF MONITOR FROM SOUTHEAST CORNER OF ROOF. ROOF MONITOR WINDOWS HAVE BEEN INFILLED WITH BRICK. THE VENTILATION HOUSES ARE PART OF THE ORIGINAL CENTRAL AIR CONDITIONING SYSTEM AND CONTAINED AIR WASHERS, FANS AND OTHER HUMIDFYING EQUIPMENT FROM PARKS-CRAMER COMPANY OF FITCHBURG, MASSACHUSETTS. LOCATING THIS EQUIPMENT ON THE ROOF MADE IT UNNECESSARY TO CONSTRUCT A FULL BASEMENT, AND THEREFORE LOWERED CONSTRUCTION COSTS. THIS ARRANGEMENT ALSO PUT THE AIR CONDITIONING EQUIPMENT CLOSEST TO THE TOP FLOOR SPINNING ROOM, WHICH HAD THE GREATEST COOLING REQUIREMENTS. - Stark Mill, 117 Corinth Road, Hogansville, Troup County, GA

  5. Analysis on ventilation pressure of fire area in longitudinal ventilation of underground tunnel

    NASA Astrophysics Data System (ADS)

    Li, Jiaxin; Li, Yanfeng; Feng, Xiao; Li, Junmei

    2018-03-01

    In order to solve the problem of ventilation pressure loss in the fire area under the fire condition, the wind pressure loss model of the fire area is established based on the thermodynamic equilibrium relation. The semi-empirical calculation formula is obtained by using the model experiment and CFD simulation. The validity of the formula is verified. The results show that the ventilation pressure loss in the fire zone is proportional to the convective heat release rate at the critical velocity, which is inversely proportional to the upstream ventilation velocity and the tunnel cross-sectional area. The proposed formula is consistent with the law of the tunnel fire test fitting formula that results are close, in contrast, the advantage lies in a clear theoretical basis and ventilation velocity values. The resistance of road tunnel ventilation system is calculated accurately and reliably, and then an effective emergency ventilation operation program is developed. It is necessary to consider the fire zone ventilation pressure loss. The proposed ventilation pressure loss formula can be used for design calculation after thorough verification.

  6. Analysis of the systems of ventilation of residential houses of Ukraine and Estonia

    NASA Astrophysics Data System (ADS)

    Savchenko, Olena; Zhelykh, Vasyl; Voll, Hendrik

    2017-12-01

    The most common ventilation system in residential buildings in Ukraine is natural ventilation. In recent years, due to increased tightness of structures, an increase in the content of synthetic finishing materials in them, the quality of microclimate parameters deteriorated. One of the measures to improve the parameters of indoor air in residential buildings is the use of mechanical inflow and exhaust ventilation system. In this article the regulatory documents concerning the design of ventilation systems in Ukraine and Estonia and the requirements for air exchange in residential buildings are considered. It is established that the existing normative documents in Ukraine are analogous to European norms, which allow design the system of ventilation of residential buildings according to European standards. However, the basis for the design of ventilation systems in Ukraine is the national standards, in which mechanical ventilation, unfortunately, is provided only for the design of high-rise buildings. To maintain acceptable microclimate parameters in residential buildings, it is advisable for designers to apply the requirements for designing ventilation systems in accordance with European standards.

  7. A dynamic ventilation model for gravity sewer networks.

    PubMed

    Wang, Y C; Nobi, N; Nguyen, T; Vorreiter, L

    2012-01-01

    To implement any effective odour and corrosion control technology in the sewer network, it is imperative that the airflow through gravity sewer airspaces be quantified. This paper presents a full dynamic airflow model for gravity sewer systems. The model, which is developed using the finite element method, is a compressible air transport model. The model has been applied to the North Head Sewerage Ocean Outfall System (NSOOS) and calibrated using the air pressure and airflow data collected during October 2008. Although the calibration is focused on forced ventilation, the model can be applied to natural ventilation as well.

  8. Investigation of turbine ventilator performance after added wind cup for room exhaust air applications

    NASA Astrophysics Data System (ADS)

    Harun, D.; Zulfadhli; Akhyar, H.

    2018-05-01

    The turbine ventilator is a wind turbine with a vertical axis that has a combined function of the wind turbine and a suction fan. In this study, the turbine ventilator modified by adding a wind cup on the top (cap) turbine ventilator. The purpose of this experiment is to investigated the effect of the addition of wind cup on the turbine ventilator. Turbine ventilator used is type v30 and wind cup with diameter 77 mm. The experiment was conducted using a triangular pentagon model space chamber which was cut off to place the ventilator turbine ventilation cup with a volume of 0.983 m3 (equivalent to 1 mm3). The results of this study indicate that at an average wind speed of 1.8 m/s, the rotation of the turbine produced without a wind cup is 60.6 rpm while with the addition of a wind cup in the turbine ventilator is 69 rpm. The average increase of rotation turbine after added win cup is 8.4 rpm and the efficiency improvement of turbine ventilator is 1.7 %.

  9. 46 CFR 108.437 - Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 46 Shipping 4 2010-10-01 2010-10-01 false Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment. 108.437 Section 108.437 Shipping COAST GUARD, DEPARTMENT OF... Systems Fixed Carbon Dioxide Fire Extinguishing Systems § 108.437 Pipe sizes and discharge rates for...

  10. High Lapse Rates in AIRS Retrieved Temperatures in Cold Air Outbreaks

    NASA Technical Reports Server (NTRS)

    Fetzer, Eric J.; Kahn, Brian; Olsen, Edward T.; Fishbein, Evan

    2004-01-01

    The Atmospheric Infrared Sounder (AIRS) experiment, on NASA's Aqua spacecraft, uses a combination of infrared and microwave observations to retrieve cloud and surface properties, plus temperature and water vapor profiles comparable to radiosondes throughout the troposphere, for cloud cover up to 70%. The high spectral resolution of AIRS provides sensitivity to important information about the near-surface atmosphere and underlying surface. A preliminary analysis of AIRS temperature retrievals taken during January 2003 reveals extensive areas of superadiabatic lapse rates in the lowest kilometer of the atmosphere. These areas are found predominantly east of North America over the Gulf Stream, and, off East Asia over the Kuroshio Current. Accompanying the high lapse rates are low air temperatures, large sea-air temperature differences, and low relative humidities. Imagery from a Visible / Near Infrared instrument on the AIRS experiment shows accompanying clouds. These lines of evidence all point to shallow convection in the bottom layer of a cold air mass overlying warm water, with overturning driven by heat flow from ocean to atmosphere. An examination of operational radiosondes at six coastal stations in Japan shows AIRS to be oversensitive to lower tropospheric lapse rates due to systematically warm near-surface air temperatures. The bias in near-surface air temperature is seen to be independent of sea surface temperature, however. AIRS is therefore sensitive to air-sea temperature difference, but with a warm atmospheric bias. A regression fit to radiosondes is used to correct AIRS near-surface retrieved temperatures, and thereby obtain an estimate of the true atmosphere-ocean thermal contrast in five subtropical regions across the north Pacific. Moving eastward, we show a systematic shift in this air-sea temperature differences toward more isothermal conditions. These results, while preliminary, have implications for our understanding of heat flow from ocean to

  11. Effect of accessory ostia on maxillary sinus ventilation: a computational fluid dynamics (CFD) study.

    PubMed

    Zhu, Jian Hua; Lee, Heow Pueh; Lim, Kian Meng; Gordon, Bruce R; Wang, De Yun

    2012-08-15

    We evaluated, by CFD simulation, effects of accessory ostium (AO) on maxillary sinus ventilation. A three-dimensional nasal model was constructed from an adult CT scan with two left maxillary AOs (sinus I) and one right AO (sinus II), then compared to an identical control model with all AOs sealed (sinuses III and IV). Transient simulations of quiet inspiration and expiration at 15 L/min, and nasal blow at 48 L/min, were calculated for both models using low-Reynolds-number turbulent analysis. At low flows, ventilation rates in sinuses with AOs (I ≈ 0.46 L/min, II ≈ 0.54 L/min), were both more than a magnitude higher than sinuses without AOs (II I ≈ 0.019 L/min, IV ≈ 0.020 L/min). Absence of AO almost completely prevented sinus ventilation. Increased ventilation of sinuses with AOs is complex. Under high flow conditions mimicking nose blowing, in sinuses II, III, and IV, the sinus flow rate increased. In contrast, the airflow direction through sinus I reversed between inspiration and expiration, while it remained almost constant throughout the respiration cycle in sinus II. CFD simulation demonstrated that AOs markedly increase maxillary sinus airflow rates and alter sinus air circulation patterns. Whether these airflow changes impact maxillary sinus physiology or pathophysiology is unknown. Copyright © 2012 Elsevier B.V. All rights reserved.

  12. Prediction of indoor radon/thoron concentration in a model room from exhalation rates of building materials for different ventilation rates

    NASA Astrophysics Data System (ADS)

    Kumar, Manish; Sharma, Navjeet; Sarin, Amit

    2018-05-01

    Studies have confirmed that elevated levels of radon/thoron in the human-environments can substantially increase the risk of lung cancer in general population. The building materials are the second largest contributors to indoor radon/thoron after soil and bedrock beneath dwellings. In present investigation, the exhalation rates of radon/thoron from different building materials samples have been analysed using active technique. Radon/thoron concentrations in a model room have been predicted based on the exhalation rates from walls, floor and roof. The indoor concentrations show significant variations depending upon the ventilation rate and type of building materials used.

  13. [Nasal CPAP versus mechanical ventilation in 28 to 32-week preterm infants with early surfactant administration].

    PubMed

    Pérez, Luis Alfonso; González, Diana Marcela; Álvarez, Karen Margarita de Jesús; Díaz-Martínez, Luis Alfonso

    2014-01-01

    Continuous positive airway pressure (CPAP) is useful in low birth weight infants with respiratory distress, but it is not known if it is a better alternative to mechanical ventilation after early pulmonary surfactant administration. To compare the incidence of adverse events in 28 to 32-week newborns with respiratory distress managed with mechanical ventilation or CPAP after early surfactant administration. In total, 176 newborns were treated with CPAP and 147 with mechanical ventilation, all with Apgar scores >3 at five minutes and without apnea. The incidence of CPAP failure was 6.5% (95% CI: 11.3-22.8%); 29 patients died: 7 with CPAP (4.0%) and 22 with mechanical ventilation (15.0%, p<0.001). The relative risk of dying with CPAP versus mechanical ventilation was 0.27 (95% CI: 0.12-0.61), but after adjusting for confounding factors, CPAP use did not imply a higher risk of dying (RR=0.60; 95% CI: 0.29-1.24). Mechanical ventilation fatality rate was 5.70 (95% CI: 3.75-8.66) deaths/1,000 days-patient, while with CPAP it was 1.37 (95% CI: 0.65-2.88, p<0.001). Chronic lung disease incidence was lower with CPAP than with mechanical ventilation (RR=0.71; 95% CI: 0.54-0.96), as were intracranial hemorrhage (RR=0.28, 95% CI: 0.09-0.84) and sepsis (RR=0.67; 95%CI: 0.52-0.86), and it was similar for air leaks (RR=2.51; 95% CI: 0.83-7.61) and necrotizing enterocolitis (RR=1.68, 95% CI: 0.59-4.81). CPAP exposure of premature infants with respiratory distress syndrome is protective against chronic lung disease, intraventricular hemorrhage and sepsis compared to mechanical ventilation. No differences were observed regarding air leak syndrome or death.

  14. A Study on The Development of Local Exhaust Ventilation System (LEV’s) for Installation of Laser Cutting Machine

    NASA Astrophysics Data System (ADS)

    Harun, S. I.; Idris, S. R. A.; Tamar Jaya, N.

    2017-09-01

    Local exhaust ventilation (LEV) is an engineering system frequently used in the workplace to protect operators from hazardous substances. The objective of this project is design and fabricate the ventilation system as installation for chamber room of laser cutting machine and to stimulate the air flow inside chamber room of laser cutting machine with the ventilation system that designed. LEV’s fabricated with rated voltage D.C 10.8V and 1.5 ampere. Its capacity 600 ml, continuously use limit approximately 12-15 minute, overall length LEV’s fabricated is 966 mm with net weight 0.88 kg and maximum airflow is 1.3 meter cubic per minute. Stimulate the air flow inside chamber room of laser cutting machine with the ventilation system that designed and fabricated overall result get 2 main gas vapor which air and carbon dioxide. For air gas which experimented by using anemometer, general duct velocity that produce is same with other gas produce, carbon dioxide which 5 m/s until 10 m/s. Overall result for 5 m/s and 10 m/s as minimum and maximum duct velocity produce for both air and carbon dioxide. The air gas flow velocity that captured by LEV’s fabricated, 3.998 m/s average velocity captured from 5 m/s duct velocity which it efficiency of 79.960% and 7.667 m/s average velocity captured from 10 m/s duct velocity with efficiency of 76.665%. For carbon dioxide gas flow velocity that captured by LEV’s fabricated, 3.674 m/s average velocity captured from 5 m/s duct velocity which it efficiency of 73.480% and 8.255 m/s average velocity captured from 10 m/s duct velocity with efficiency of 82.545%.

  15. HVAC (heating, ventilation, air conditioning) literature in Japan: A critical review

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Hane, G.J.

    1988-02-01

    Japanese businessmen in the heating, ventilation, air conditioning, and refrigeration (HVACandR) industry consider the monitoring of technical and market developments in the United States to be a normal part of their business. In contrast, efforts by US businessmen to monitor Japanese HVAC and R developments are poorly developed. To begin to redress this imbalance, this report establishes the groundwork for a more effective system for use in monitoring Japanese HVAC and R literature. Discussions of a review of the principal HVAC and R publications in Japan and descriptions of the type of information contained in each of those publications aremore » included in this report. Since the Japanese HVAC and R literature is abundant, this report also provides practical suggestions on how a researcher or research manager can limit the monitoring effort to the publications and type of information that would most likely be of greatest value.« less

  16. Confined space ventilation by shipyard welders: observed use and effectiveness.

    PubMed

    Pouzou, Jane G; Warner, Chris; Neitzel, Richard L; Croteau, Gerry A; Yost, Michael G; Seixas, Noah S

    2015-01-01

    Shipbuilding involves intensive welding activities within enclosed and confined spaces, and although ventilation is commonly used in the industry, its use and effectiveness has not been adequately documented. Workers engaged in welding in enclosed or confined spaces in two shipyards were observed for their use of ventilation and monitored for their exposure to particulate matter. The type of ventilation in use, its placement and face velocity, the movement of air within the space, and other ventilation-related parameters were recorded, along with task characteristics such as the type of welding, the welder's position, and the configuration of the space. Mechanical ventilation was present in about two-thirds of the 65 welding scenarios observed, with exhaust ventilation used predominantly in one shipyard and supply blowers predominantly in the other. Welders were observed working in apparent dead-spaces within the room in 53% of the cases, even where ventilation was in use. Respiratory protection was common in the two shipyards, observed in use in 77 and 100% of the cases. Welding method, the proximity of the welder's head to the fume, and air mixing were found to be significantly associated with the welder's exposure, while other characteristics of dilution ventilation did not produce appreciable differences in exposure level. These parameters associated with exposure reduction can be assessed subjectively and are thus good candidates for training on effective ventilation use during hot work in confined spaces. Ventilation used in confined space welding is often inadequate for controlling exposure to welding fume. © The Author 2014. Published by Oxford University Press on behalf of the British Occupational Hygiene Society.

  17. SBS symptoms in relation to dampness and ventilation in inspected single-family houses in Sweden.

    PubMed

    Smedje, Greta; Wang, Juan; Norbäck, Dan; Nilsson, Håkan; Engvall, Karin

    2017-10-01

    To investigate the relationships between symptoms compatible with the sick building syndrome (SBS) in adults and building dampness and ventilation in single-family houses. Within the Swedish BETSI study, a national sample of single-family houses were inspected by professional building experts, and adults living in the houses answered a questionnaire on SBS. Relationships between building factors and SBS were analysed using logistic regression. Of the respondents, 23% reported having had weekly SBS symptoms during the last three months. A large proportion of houses exhibited building or construction problems. In total, 40% of houses had dampness problems in the foundation, and this was related to a higher prevalence of both mucous and dermal symptoms, and any SBS symptoms. Furthermore, high air humidity was related to more symptoms, with the relationship with absolute humidity being stronger than that with relative humidity or moisture load. Symptoms were also more prevalent in houses with a high U value, reflecting a poor thermal insulation. Compared to natural ventilation, living in a house with mechanical supply and exhaust ventilation was related to a lower prevalence of general symptoms and any SBS symptoms, but there were only weak associations between measured air exchange rate and symptoms. A large proportion of single-family houses have dampness problems in the foundation, and pollutants may enter the living space of the house and affect the health of the occupants. Furthermore, absolute air humidity should be measured more often in indoor air studies.

  18. Indoor Air Quality in Chemistry Laboratories.

    ERIC Educational Resources Information Center

    Hays, Steve M.

    This paper presents air quality and ventilation data from an existing chemical laboratory facility and discusses the work practice changes implemented in response to deficiencies in ventilation. General methods for improving air quality in existing laboratories are presented and investigation techniques for characterizing air quality are…

  19. Omnidirectional ventilated acoustic barrier

    NASA Astrophysics Data System (ADS)

    Zhang, Hai-long; Zhu, Yi-fan; Liang, Bin; Yang, Jing; Yang, Jun; Cheng, Jian-chun

    2017-11-01

    As an important problem in acoustics, sound insulation finds applications in a great variety of situations. In the existing schemes, however, there has always been a trade-off between the thinness of sound-insulating devices and their ventilating capabilities, limiting their potentials in the control of low-frequency sound in high ventilation environments. Here, we design and experimentally implement an omnidirectional acoustic barrier with a planar profile, subwavelength thickness ( 0.18 λ ), yet high ventilation. The proposed mechanism is based on the interference between the resonant scattering of discrete states and the background scattering of continuous states which induces a Fano-like asymmetric transmission profile. Benefitting from the binary-structured design of the coiled unit and hollow pipe, it maximally simplifies the design and fabrication while ensuring the ventilation for all the non-resonant units with open tubes. The simulated and measured results agree well, showing the effectiveness of our proposed mechanism to block low frequency sound coming from various directions while allowing 63% of the air flow to pass. We anticipate our design to open routes to design sound insulators and to enable applications in traditionally unattainable cases such as those calling for noise reduction and cooling simultaneously.

  20. Influence of Courtyard Ventilation on Thermal Performance of Office Building in Hot-Humid Climate: A Case Study

    NASA Astrophysics Data System (ADS)

    Abbaas, Esra'a. Sh.; Saif, Ala'eddin A.; Munaaim, MAC; Azree Othuman Mydin, Md.

    2018-03-01

    The influence of courtyard on the thermal performance of Development Department office building in University Malaysia Perlis (UniMAP, Pauh Putra campus) is investigated through simulation study for the effect of ventilation on indoor air temperature and relative humidity of the building. The study is carried out using EnergyPlus simulator interface within OpenStudio and SketchUp plug in software to measure both of air temperature and relative humidity hourly on 21 April 2017 as a design day. The results show that the ventilation through the windows facing the courtyard has sufficient effect on reducing the air temperature compared to the ventilation through external windows since natural ventilation is highly effective on driving the indoor warm air out to courtyard. In addition, the relative humidity is reduced due to ventilation since the courtyard has high ability to remove or dilute indoor airborne pollutants coming from indoor sources. This indicates that the presence of courtyard is highly influential on thermal performance of the building.

  1. Hexavalent chromium and isocyanate exposures during military aircraft painting under crossflow ventilation.

    PubMed

    Bennett, James S; Marlow, David A; Nourian, Fariba; Breay, James; Hammond, Duane

    2016-01-01

    Exposure control systems performance was investigated in an aircraft painting hangar. The ability of the ventilation system and respiratory protection program to limit worker exposures was examined through air sampling during painting of F/A-18C/D strike fighter aircraft, in four field surveys. Air velocities were measured across the supply filter, exhaust filter, and hangar midplane under crossflow ventilation. Air sampling conducted during painting process phases (wipe-down, primer spraying, and topcoat spraying) encompassed volatile organic compounds, total particulate matter, Cr[VI], metals, nitroethane, and hexamethylene diisocyanate, for two worker groups: sprayers and sprayer helpers ("hosemen"). One of six methyl ethyl ketone and two of six methyl isobutyl ketone samples exceeded the short term exposure limits of 300 and 75 ppm, with means 57 ppm and 63 ppm, respectively. All 12 Cr[VI] 8-hr time-weighted averages exceeded the recommended exposure limit of 1 µg/m3, 11 out of 12 exceeded the permissible exposure limit of 5 µg/m3, and 7 out of 12 exceeded the threshold limit value of 10 µg/m3, with means 38 µg/m3 for sprayers and 8.3 µg/m3 for hosemen. Hexamethylene diisocyanate means were 5.95 µg/m3 for sprayers and 0.645 µg/m3 for hosemen. Total reactive isocyanate group--the total of monomer and oligomer as NCO group mass--showed 6 of 15 personal samples exceeded the United Kingdom Health and Safety Executive workplace exposure limit of 20 µg/m3, with means 50.9 µg/m3 for sprayers and 7.29 µg/m3 for hosemen. Several exposure limits were exceeded, reinforcing continued use of personal protective equipment. The supply rate, 94.4 m3/s (200,000 cfm), produced a velocity of 8.58 m/s (157 fpm) at the supply filter, while the exhaust rate, 68.7 m3/s (146,000 cfm), drew 1.34 m/s (264 fpm) at the exhaust filter. Midway between supply and exhaust locations, the velocity was 0.528 m/s (104 fpm). Supply rate exceeding exhaust rate created re

  2. 28. Ventilation Building located on front lawn of building 500, ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    28. Ventilation Building located on front lawn of building 500, looking southeast - Offutt Air Force Base, Strategic Air Command Headquarters & Command Center, Headquarters Building, 901 SAC Boulevard, Bellevue, Sarpy County, NE

  3. 29. Ventilation Building located on front lawn of building 500, ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    29. Ventilation Building located on front lawn of building 500, looking northeast - Offutt Air Force Base, Strategic Air Command Headquarters & Command Center, Headquarters Building, 901 SAC Boulevard, Bellevue, Sarpy County, NE

  4. Guide for Indoor Air Quality Surveys

    DTIC Science & Technology

    1992-05-01

    investigations, but is most useful as a tool for the Heating, Ventilating, and Air-Conditioning ( HVAC ) experts. The standard describes two procedures for...providing acceptable air quality and includes design criteria for HVAC systems. Perhaps the most important contribution from ASHRAE 62-1989 is its...Selected Selected Cause Subcauses Subrates(%) Overall Rate(%) A. Inadequate Design or Maintenance of HVAC 70 (32/46) Al. Mold 47 (15/32) 33 (15/46) A2

  5. The impact of recirculation, ventilation and filters on secondary organic aerosols generated by indoor chemistry

    NASA Astrophysics Data System (ADS)

    Fadeyi, M. O.; Weschler, C. J.; Tham, K. W.

    This study examined the impact of recirculation rates (7 and 14 h -1), ventilation rates (1 and 2 h -1), and filtration on secondary organic aerosols (SOAs) generated by ozone of outdoor origin reacting with limonene of indoor origin. Experiments were conducted within a recirculating air handling system that serviced an unoccupied, 236 m 3 environmental chamber configured to simulate an office; either no filter, a new filter or a used filter was located downstream of where outdoor air mixed with return air. For otherwise comparable conditions, the SOA number and mass concentrations at a recirculation rate of 14 h -1 were significantly smaller than at a recirculation rate of 7 h -1. This was due primarily to lower ozone concentrations, resulting from increased surface removal, at the higher recirculation rate. Increased ventilation increased outdoor-to-indoor transport of ozone, but this was more than offset by the increased dilution of SOA derived from ozone-initiated chemistry. The presence of a particle filter (new or used) strikingly lowered SOA number and mass concentrations compared with conditions when no filter was present. Even though the particle filter in this study had only 35% single-pass removal efficiency for 100 nm particles, filtration efficiency was greatly amplified by recirculation. SOA particle levels were reduced to an even greater extent when an activated carbon filter was in the system, due to ozone removal by the carbon filter. These findings improve our understanding of the influence of commonly employed energy saving procedures on occupant exposures to ozone and ozone-derived SOA.

  6. Night ventilation control strategies in office buildings

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Wang, Zhaojun; Yi, Lingli; Gao, Fusheng

    2009-10-15

    In moderate climates night ventilation is an effective and energy-efficient approach to improve the indoor thermal environment for office buildings during the summer months, especially for heavyweight construction. However, is night ventilation a suitable strategy for office buildings with lightweight construction located in cold climates? In order to answer this question, the whole energy-consumption analysis software EnergyPlus was used to simulate the indoor thermal environment and energy consumption in typical office buildings with night mechanical ventilation in three cities in northern China. The summer outdoor climate data was analyzed, and three typical design days were chosen. The most important factorsmore » influencing night ventilation performance such as ventilation rates, ventilation duration, building mass and climatic conditions were evaluated. When night ventilation operation time is closer to active cooling time, the efficiency of night ventilation is higher. With night ventilation rate of 10 ach, the mean radiant temperature of the indoor surface decreased by up to 3.9 C. The longer the duration of operation, the more efficient the night ventilation strategy becomes. The control strategies for three locations are given in the paper. Based on the optimized strategies, the operation consumption and fees are calculated. The results show that more energy is saved in office buildings cooled by a night ventilation system in northern China than ones that do not employ this strategy. (author)« less

  7. A miniature mechanical ventilator for newborn mice.

    PubMed

    Kolandaivelu, K; Poon, C S

    1998-02-01

    Transgenic/knockout mice with pre-defined mutations have become increasingly popular in biomedical research as models of human diseases. In some instances, the resulting mutation may cause cardiorespiratory distress in the neonatal or adult animals and may necessitate resuscitation. Here we describe the design and testing of a miniature and versatile ventilator that can deliver varying ventilatory support modes, including conventional mechanical ventilation and high-frequency ventilation, to animals as small as the newborn mouse. With a double-piston body chamber design, the device circumvents the problem of air leakage and obviates the need for invasive procedures such as endotracheal intubation, which are particularly important in ventilating small animals. Preliminary tests on newborn mice as early as postnatal day O demonstrated satisfactory restoration of pulmonary ventilation and the prevention of respiratory failure in mutant mice that are prone to respiratory depression. This device may prove useful in the postnatal management of transgenic/knockout mice with genetically inflicted respiratory disorders.

  8. Transient natural ventilation of a room with a distributed heat source

    NASA Astrophysics Data System (ADS)

    Fitzgerald, Shaun D.; Woods, Andrew W.

    We report on an experimental and theoretical study of the transient flows which develop as a naturally ventilated room adjusts from one temperature to another. We focus on a room heated from below by a uniform heat source, with both high- and low-level ventilation openings. Depending on the initial temperature of the room relative to (i) the final equilibrium temperature and (ii) the exterior temperature, three different modes of ventilation may develop. First, if the room temperature lies between the exterior and the equilibrium temperature, the interior remains well-mixed and gradually heats up to the equilibrium temperature. Secondly, if the room is initially warmer than the equilibrium temperature, then a thermal stratification develops in which the upper layer of originally hot air is displaced upwards by a lower layer of relatively cool inflowing air. At the interface, some mixing occurs owing to the effects of penetrative convection. Thirdly, if the room is initially cooler than the exterior, then on opening the vents, the original air is displaced downwards and a layer of ambient air deepens from above. As this lower layer drains, it is eventually heated to the ambient temperature, and is then able to mix into the overlying layer of external air, and the room becomes well-mixed. For each case, we present new laboratory experiments and compare these with some new quantitative models of the transient flows. We conclude by considering the implications of our work for natural ventilation of large auditoria.

  9. An experimental study on effects of increased ventilation flow on students' perception of indoor environment in computer classrooms.

    PubMed

    Norbäck, D; Nordström, K

    2008-08-01

    The effects of ventilation in computer classrooms were studied with university students (n = 355) in a blinded study, 31% were women and 3.8% had asthma. Two classrooms had a higher air exchange (4.1-5.2 ac/h); two others had a lower air exchange (2.3-2.6 ac/h). After 1 week, ventilation conditions were shifted. The students reported environmental perceptions during the last hour. Room temperature, RH, CO2, PM10 and ultra-fine particles were measured simultaneously. Mean CO2 was 1185 ppm at lower and 922 ppm at higher air exchange. Mean temperature was 23.2 degrees C at lower and 22.1 degrees C at higher air exchange. After mutual adjustment (temperature, RH, CO2, air exchange), measured temperature was associated with a perception of higher temperature (P < 0.001), lower air movement (P < 0.001), and poorer air quality (P < 0.001). Higher air exchange was associated with a perception of lower temperature (P < 0.001), higher air movement (P = 0.001), and better air quality (P < 0.001). In the longitudinal analysis (n = 83), increased air exchange caused a perception of lower temperature (P = 0.002), higher air movement (P < 0.001), better air quality (P = 0.001), and less odor (P = 0.02). In conclusion, computer classrooms have CO2 levels above 1000 ppm and temperatures above 22 degrees C. Increased ventilation from 7 l/s per person to 10-13 l/s per person can improve thermal comfort and air quality. Computer classrooms are crowded indoor environments with a high thermal load from both students and computer equipment. It is important to control room temperature either by air conditioning, sun shields, or sufficiently high ventilation flow. A high ventilation flow is also crucial to achieving good perceived air quality. Personal ventilation flow should be at least 10 l/s. Possible loss of learning ability due to poor indoor air quality in university buildings deserves more attention.

  10. The effect of helium-oxygen-assisted mechanical ventilation on chronic obstructive pulmonary disease exacerbation: A systemic review and meta-analysis.

    PubMed

    Wu, Xu; Shao, Chuan; Zhang, Liang; Tu, Jinjing; Xu, Hui; Lin, Zhihui; Xu, Shuguang; Yu, Biyun; Tang, Yaodong; Li, Shanqun

    2018-03-01

    Chronic obstructive pulmonary disease (COPD) is often accompanied by acute exacerbations. Patients of COPD exacerbation suffering from respiratory failure often need the support of mechanical ventilation. Helium-oxygen can be used to reduce airway resistance during mechanical ventilation. The aim of this study is to evaluate the effect of helium-oxygen-assisted mechanical ventilation on COPD exacerbation through a meta-analysis. A comprehensive literature search through databases of Pub Med (1966∼2016), Ovid MEDLINE (1965∼2016), Cochrane EBM (1991∼2016), EMBASE (1974∼2016) and Ovid MEDLINE was performed to identify associated studies. Randomized clinical trials met our inclusion criteria that focus on helium-oxygen-assisted mechanical ventilation on COPD exacerbation were included. The quality of the papers was evaluated after inclusion and information was extracted for meta-analysis. Six articles and 392 patients were included in total. Meta-analysis revealed that helium-oxygen-assisted mechanical ventilation reduced Borg dyspnea scale and increased arterial PH compared with air-oxygen. No statistically significant difference was observed between helium-oxygen and air-oxygen as regards to WOB, PaCO 2 , OI, tracheal intubation rates and mortality within hospital. Our study suggests helium-oxygen-assisted mechanical ventilation can help to reduce Borg dyspnea scale. In terms of the tiny change of PH, its clinical benefit is negligible. There is no conclusive evidence indicating the beneficial effect of helium-oxygen-assisted mechanical ventilation on clinical outcomes or prognosis of COPD exacerbation. © 2017 John Wiley & Sons Ltd.

  11. A new system for continuous and remote monitoring of patients receiving home mechanical ventilation

    NASA Astrophysics Data System (ADS)

    Battista, L.

    2016-09-01

    Home mechanical ventilation is the treatment of patients with respiratory failure or insufficiency by means of a mechanical ventilator at a patient's home. In order to allow remote patient monitoring, several tele-monitoring systems have been introduced in the last few years. However, most of them usually do not allow real-time services, as they have their own proprietary communication protocol implemented and some ventilation parameters are not always measured. Moreover, they monitor only some breaths during the whole day, despite the fact that a patient's respiratory state may change continuously during the day. In order to reduce the above drawbacks, this work reports the development of a novel remote monitoring system for long-term, home-based ventilation therapy; the proposed system allows for continuous monitoring of the main physical quantities involved during home-care ventilation (e.g., differential pressure, volume, and air flow rate) and is developed in order to allow observations of different remote therapy units located in different places of a city, region, or country. The developed remote patient monitoring system is able to detect various clinical events (e.g., events of tube disconnection and sleep apnea events) and has been successfully tested by means of experimental tests carried out with pulmonary ventilators typically used to support sick patients.

  12. A new system for continuous and remote monitoring of patients receiving home mechanical ventilation.

    PubMed

    Battista, L

    2016-09-01

    Home mechanical ventilation is the treatment of patients with respiratory failure or insufficiency by means of a mechanical ventilator at a patient's home. In order to allow remote patient monitoring, several tele-monitoring systems have been introduced in the last few years. However, most of them usually do not allow real-time services, as they have their own proprietary communication protocol implemented and some ventilation parameters are not always measured. Moreover, they monitor only some breaths during the whole day, despite the fact that a patient's respiratory state may change continuously during the day. In order to reduce the above drawbacks, this work reports the development of a novel remote monitoring system for long-term, home-based ventilation therapy; the proposed system allows for continuous monitoring of the main physical quantities involved during home-care ventilation (e.g., differential pressure, volume, and air flow rate) and is developed in order to allow observations of different remote therapy units located in different places of a city, region, or country. The developed remote patient monitoring system is able to detect various clinical events (e.g., events of tube disconnection and sleep apnea events) and has been successfully tested by means of experimental tests carried out with pulmonary ventilators typically used to support sick patients.

  13. Building America Case Study: Evaluation of Ventilation Strategies in New Construction Multifamily Buildings, New York, New York (Fact Sheet)

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Not Available

    2014-09-01

    In multifamily buildings, particularly in the Northeast, exhaust ventilation strategies are the norm as a means of meeting both local exhaust and whole-unit mechanical ventilation rates. The issue of where the 'fresh' air is coming from is gaining significance as air-tightness standards for enclosures become more stringent, and the 'normal leakage paths through the building envelope' disappear. CARB researchers have found that the majority of high performance, new construction, multifamily housing in the Northeast use one of four general strategies for ventilation: continuous exhaust only with no designated supply or make-up air source, continuous exhaust with ducted make-up air tomore » apartments, continuous exhaust with supply through a make-up air device integral to the unit HVAC, and continuous exhaust with supply through a passive inlet device, such as a trickle vent. Insufficient information is available to designers on how these various systems are best applied. Product performance data are based on laboratory tests, and the assumption is that products will perform similarly in the field. Proper application involves matching expected performance at expected building pressures, but there is no guarantee that those conditions will exist consistently in the finished building. This research effort, which included several weeks of building pressure monitoring, sought to provide field validation of system performance. The performance of four substantially different strategies for providing make-up air to apartments was evaluated.« less

  14. 46 CFR 182.465 - Ventilation of spaces containing diesel machinery.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... 46 Shipping 7 2010-10-01 2010-10-01 false Ventilation of spaces containing diesel machinery. 182... Ventilation of spaces containing diesel machinery. (a) A space containing diesel machinery must be fitted with... operation of main engines and auxiliary engines. (b) Air-cooled propulsion and auxiliary diesel engines...

  15. 46 CFR 182.465 - Ventilation of spaces containing diesel machinery.

    Code of Federal Regulations, 2011 CFR

    2011-10-01

    ... 46 Shipping 7 2011-10-01 2011-10-01 false Ventilation of spaces containing diesel machinery. 182... Ventilation of spaces containing diesel machinery. (a) A space containing diesel machinery must be fitted with... operation of main engines and auxiliary engines. (b) Air-cooled propulsion and auxiliary diesel engines...

  16. 30 CFR 77.201-2 - Methane accumulations; change in ventilation.

    Code of Federal Regulations, 2011 CFR

    2011-07-01

    ... 30 Mineral Resources 1 2011-07-01 2011-07-01 false Methane accumulations; change in ventilation... OF UNDERGROUND COAL MINES Surface Installations § 77.201-2 Methane accumulations; change in ventilation. If, at any time, the air in any structure, enclosure or other facility contains 1.0 volume per...

  17. EFFECT OF VENTILATION SYSTEMS AND AIR FILTERS ON DECAY RATES OF PARTICLES PRODUCED BY INDOOR SOURCES IN AN OCCUPIED TOWNHOUSE

    EPA Science Inventory

    Several studies have shown the importance of particle losses in real homes due to deposition and filtration; however, none have quantitatively shown the impact of using a central forced air fan and in-duct filter on particle loss rates. In an attempt to provide such data, we me...

  18. Computational Study of Ventilation and Disease Spread in Poultry Houses

    NASA Astrophysics Data System (ADS)

    Cimbala, John; Pawar, Sourabh; Wheeler, Eileen; Lindberg, Darla

    2006-11-01

    The air flow in and around poultry houses has been studied numerically with the goal of determining disease spread characteristics and comparing ventilation schemes. A typical manure-belt layer egg production facility is considered. The continuity, momentum, and energy equations are solved for flow both inside and outside poultry houses using the commercial computational fluid dynamics (CFD) code FLUENT. Both simplified two-dimensional and fully three-dimensional geometries are modeled. The spread of virus particles is considered to be analogous to diffusion of a tracer contaminant gas, in this case ammonia. The effect of thermal plumes produced by the hens in the poultry house is also considered. Two ventilation schemes with opposite flow directions are compared. Contours of temperature and ammonia mass fraction for both cases are obtained and compared. The analysis shows that ventilation and air quality characteristics are much better for the case in which the air flow is from bottom to top (enhancing the thermal plume) instead of from top to bottom (fighting the thermal plume) as in most poultry houses. This has implications in air quality control in the event of epidemic outbreaks of avian flu or other infectious diseases.

  19. The addition of a mobile ultra-clean exponential laminar airflow screen to conventional operating room ventilation reduces bacterial contamination to operating box levels.

    PubMed

    Friberg, S; Ardnor, B; Lundholm, R; Friberg, B

    2003-10-01

    A mobile screen producing ultra-clean exponential laminar airflow (LAF) was investigated as an addition to conventional turbulent/mixing operating room (OR) ventilation (16 air changes/h). The evaluation was performed in a small OR (50 m(3)) during 60 standardized operations for groin hernia including mesh implantation. The additional ventilation was used in 50 of the operations. The LAF passed from the foot-end of the OR table over the instrument and surgical area. Strict hygiene OR procedures including tightly woven and non-woven OR clothing were used. Sedimentation rates were recorded at the level of the patients' chests (N=60) (i.e. the air had passed the surgical team) and in the periphery of the OR. In addition bacterial air contamination was studied above the patients' chests in all 10 operations without the additional LAF and in 12 with the LAF. The screen reduced the mean counts of sedimenting bacteria (cfu/m(2)/h) on the patients' chests from 775 without the screen to 355 (P=0.0003). The screen also reduced the mean air counts of bacteria (cfu/m(3)) above the patients' chests from 27 to 9 (P=0.0001). No significant differences in mean sedimentation rates (cfu/m(2)/h) existed in the periphery of the OR where 628 without and 574 with screen were recorded. During the follow-up period of six months no surgical site infections were detected. In conclusion when the mobile LAF screen was added to conventional OR ventilation the counts of aerobic airborne and sedimenting bacteria-carrying particles downstream of the surgical team were reduced to the levels achieved with complete ultra-clean LAF OR ventilation (operating box).

  20. Urban ventilation corridors mapping using surface morphology data based GIS analysis

    NASA Astrophysics Data System (ADS)

    Wicht, Marzena; Wicht, Andreas; Osińska-Skotak, Katarzyna

    2017-04-01

    This paper describes deriving the most appropriate method for mapping urban ventilation corridors, which, if properly designed, reduce heat stress, air pollution and increase air quality, as well as increase the horizontal wind speed. Urban areas are - in terms of surface texture - recognized as one of the roughest surfaces, which results in wind obstruction and decreased ventilation of densely built up areas. As urban heat islands, private household and traffic emissions or large scale industries occur frequently in many cities, both in temperate and tropical regions. A proper ventilation system has been suggested as an appropriate mitigation mean [1] . Two concepts of morphometric analyses of the urban environment are used on the example of Warsaw, representing a dense, urban environment, located in the temperate zone. The utilized methods include firstly a roughness mapping calculation [2] , which analyses zero plane displacement height (zd) and roughness length (z0) and their distribution for the eight (inter-)cardinal wind directions and secondly a grid-based frontal area index mapping approach [3] , which uses least cost path analysis. Utilizing the advantages and minimizing the disadvantages of those two concepts, we propose a hybrid approach. All concepts are based on a 3D building database obtained from satellite imagery, aided by a cadastral building database. Derived areas (ventilation corridors), that facilitate the ventilation system, should be considered by the local authorities as worth preserving, if not expanding, in order to improve the air quality in the city. The results also include designation of the problematic areas, which greatly obscure the ventilation and might be investigated as to reshape or rebuilt to introduce the air flow in particularly dense areas like city centers. Keywords: roughness mapping; GIS; ventilation corridors; frontal area index Rizwan, A. M., Dennis, L. Y., & Chunho, L. I. U. (2008). A review on the generation

  1. 46 CFR 111.33-9 - Ventilation exhaust.

    Code of Federal Regulations, 2010 CFR

    2010-10-01

    ... REQUIREMENTS Power Semiconductor Rectifier Systems § 111.33-9 Ventilation exhaust. The exhaust of each forced-air semiconductor rectifier system must: (a) Terminate in a location other than a hazardous location...

  2. Technology Solutions Case Study: Air Leakage and Air Transfer Between Garage and Living Space, Waldorf, Maryland

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    None

    2014-11-01

    In this project, Building Science Corporation worked with production homebuilder K. Hovnanian to evaluate air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multipoint fan pressurization tests and additional zone pressure diagnostic testing measured the garage and house air leakage, the garage-to-housemore » air leakage, and garage and house pressure relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed. For houses employing whole-house supply ventilation (positive pressure) or balanced ventilation (same pressure effect as the baseline condition), adherence to the EPA Indoor airPLUS house-to-garage air sealing requirements should be sufficient to expect little to no garage-to-house air transfer.« less

  3. Assessment of Natural Ventilation System for a Typical Residential House in Poland

    NASA Astrophysics Data System (ADS)

    Antczak-Jarząbska, Romana; Krzaczek, Marek

    2016-09-01

    The paper presents the research results of field measurements campaign of natural ventilation performance and effectiveness in a residential building. The building is located in the microclimate whose parameters differ significantly in relation to a representative weather station. The measurement system recorded climate parameters and the physical variables characterizing the air flow in the rooms within 14 days of the winter season. The measurement results showed that in spite of proper design and construction of the ventilation system, unfavorable microclimatic conditions that differed from the predicted ones caused significant reduction in the efficiency of the ventilation system. Also, during some time periods, external climate conditions caused an opposite air flow direction in the vent inlets and outlets, leading to a significant deterioration of air quality and thermal comfort measured by CO2 concentration and PMV index in a residential area.

  4. Predicting residential air exchange rates from questionnaires and meteorology: model evaluation in central North Carolina.

    PubMed

    Breen, Michael S; Breen, Miyuki; Williams, Ronald W; Schultz, Bradley D

    2010-12-15

    A critical aspect of air pollution exposure models is the estimation of the air exchange rate (AER) of individual homes, where people spend most of their time. The AER, which is the airflow into and out of a building, is a primary mechanism for entry of outdoor air pollutants and removal of indoor source emissions. The mechanistic Lawrence Berkeley Laboratory (LBL) AER model was linked to a leakage area model to predict AER from questionnaires and meteorology. The LBL model was also extended to include natural ventilation (LBLX). Using literature-reported parameter values, AER predictions from LBL and LBLX models were compared to data from 642 daily AER measurements across 31 detached homes in central North Carolina, with corresponding questionnaires and meteorological observations. Data was collected on seven consecutive days during each of four consecutive seasons. For the individual model-predicted and measured AER, the median absolute difference was 43% (0.17 h(-1)) and 40% (0.17 h(-1)) for the LBL and LBLX models, respectively. Additionally, a literature-reported empirical scale factor (SF) AER model was evaluated, which showed a median absolute difference of 50% (0.25 h(-1)). The capability of the LBL, LBLX, and SF models could help reduce the AER uncertainty in air pollution exposure models used to develop exposure metrics for health studies.

  5. Indoor air quality, ventilation and respiratory health in elderly residents living in nursing homes in Europe.

    PubMed

    Bentayeb, Malek; Norback, Dan; Bednarek, Micha; Bernard, Alfred; Cai, Guihong; Cerrai, Sonia; Eleftheriou, Konstantinos Kostas; Gratziou, Christina; Holst, Gitte Juel; Lavaud, François; Nasilowski, Jacek; Sestini, Piersante; Sarno, Giuseppe; Sigsgaard, Torben; Wieslander, Gunilla; Zielinski, Jan; Viegi, Giovanni; Annesi-Maesano, Isabella

    2015-05-01

    Few data exist on respiratory effects of indoor air quality and comfort parameters in the elderly. In the context of the GERIE study, we investigated for the first time the relationships of these factors to respiratory morbidity among elderly people permanently living in nursing homes in seven European countries. 600 elderly people from 50 nursing homes underwent a medical examination and completed a standardised questionnaire. Air quality and comfort parameters were objectively assessed in situ in the nursing home. Mean concentrations of air pollutants did not exceed the existing standards. Forced expiratory volume in 1 s/forced vital capacity ratio was highly significantly related to elevated levels of particles with a 50% cut-off aerodynamic diameter of <0.1 µm (PM0.1) (adjusted OR 8.16, 95% CI 2.24-29.3) and nitrogen dioxide (aOR 3.74, 95% CI 1.06-13.1). Excess risks for usual breathlessness and cough were found with elevated PM10 (aOR 1.53 (95% CI 1.15-2.07) and aOR 1.73 (95% CI 1.17-10.3), respectively) and nitrogen dioxide (aOR 1.58 (95% CI 1.15-2.20) and aOR 1.56 (95% CI 1.03-2.41), respectively). Excess risks for wheeze in the past year were found with PM0.1 (aOR 2.82, 95% CI 1.15-7.02) and for chronic obstructive pulmonary disease and exhaled carbon monoxide with formaldehyde (aOR 3.49 (95% CI 1.17-10.3) and aOR 1.25 (95% CI 1.02-1.55), respectively). Breathlessness and cough were associated with higher carbon dioxide. Relative humidity was inversely related to wheeze in the past year and usual cough. Elderly subjects aged ≥80 years were at higher risk. Pollutant effects were more pronounced in the case of poor ventilation. Even at low levels, indoor air quality affected respiratory health in elderly people permanently living in nursing homes, with frailty increasing with age. The effects were modulated by ventilation. Copyright ©ERS 2015.

  6. Patient warming excess heat: the effects on orthopedic operating room ventilation performance.

    PubMed

    Belani, Kumar G; Albrecht, Mark; McGovern, Paul D; Reed, Mike; Nachtsheim, Christopher

    2013-08-01

    Patient warming has become a standard of care for the prevention of unintentional hypothermia based on benefits established in general surgery. However, these benefits may not fully translate to contamination-sensitive surgery (i.e., implants), because patient warming devices release excess heat that may disrupt the intended ceiling-to-floor ventilation airflows and expose the surgical site to added contamination. Therefore, we studied the effects of 2 popular patient warming technologies, forced air and conductive fabric, versus control conditions on ventilation performance in an orthopedic operating room with a mannequin draped for total knee replacement. Ventilation performance was assessed by releasing neutrally buoyant detergent bubbles ("bubbles") into the nonsterile region under the head-side of the anesthesia drape. We then tracked whether the excess heat from upper body patient warming mobilized the "bubbles" into the surgical site. Formally, a randomized replicated design assessed the effect of device (forced air, conductive fabric, control) and anesthesia drape height (low-drape, high-drape) on the number of bubbles photographed over the surgical site. The direct mass-flow exhaust from forced air warming generated hot air convection currents that mobilized bubbles over the anesthesia drape and into the surgical site, resulting in a significant increase in bubble counts for the factor of patient warming device (P < 0.001). Forced air had an average count of 132.5 versus 0.48 for conductive fabric (P = 0.003) and 0.01 for control conditions (P = 0.008) across both drape heights. Differences in average bubble counts across both drape heights were insignificant between conductive fabric and control conditions (P = 0.87). The factor of drape height had no significant effect (P = 0.94) on bubble counts. Excess heat from forced air warming resulted in the disruption of ventilation airflows over the surgical site, whereas conductive patient warming devices had

  7. Experimental investigation into the interaction between the human body and room airflow and its effect on thermal comfort under stratum ventilation.

    PubMed

    Cheng, Y; Lin, Z

    2016-04-01

    Room occupants' comfort and health are affected by the airflow. Nevertheless, they themselves also play an important role in indoor air distribution. This study investigated the interaction between the human body and room airflow under stratum ventilation. Simplified thermal manikin was employed to effectively resemble the human body as a flow obstacle and/or free convective heat source. Unheated and heated manikins were designed to fully evaluate the impact of the manikin at various airflow rates. Additionally, subjective human tests were conducted to evaluate thermal comfort for the occupants in two rows. The findings show that the manikin formed a local blockage effect, but the supply airflow could flow over it. With the body heat from the manikin, the air jet penetrated farther compared with that for the unheated manikin. The temperature downstream of the manikin was also higher because of the convective effect. Elevating the supply airflow rate from 7 to 15 air changes per hour varied the downstream airflow pattern dramatically, from an uprising flow induced by body heat to a jet-dominated flow. Subjective assessments indicated that stratum ventilation provided thermal comfort for the occupants in both rows. Therefore, stratum ventilation could be applied in rooms with occupants in multiple rows. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  8. Expert system for the design of heating, ventilating, and air-conditioning systems. Master's thesis

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Camejo, P.J.

    1989-12-01

    Expert systems are computer programs that seek to mimic human reason. An expert system shelf, a software program commonly used for developing expert systems in a relatively short time, was used to develop a prototypical expert system for the design of heating, ventilating, and air-conditioning (HVAC) systems in buildings. Because HVAC design involves several related knowledge domains, developing an expert system for HVAC design requires the integration of several smaller expert systems known as knowledge bases. A menu program and several auxiliary programs for gathering data, completing calculations, printing project reports, and passing data between the knowledge bases are neededmore » and have been developed to join the separate knowledge bases into one simple-to-use program unit.« less

  9. Iatrogenic pneumothorax related to mechanical ventilation

    PubMed Central

    Hsu, Chien-Wei; Sun, Shu-Fen

    2014-01-01

    Pneumothorax is a potentially lethal complication associated with mechanical ventilation. Most of the patients with pneumothorax from mechanical ventilation have underlying lung diseases; pneumothorax is rare in intubated patients with normal lungs. Tension pneumothorax is more common in ventilated patients with prompt recognition and treatment of pneumothorax being important to minimize morbidity and mortality. Underlying lung diseases are associated with ventilator-related pneumothorax with pneumothoraces occurring most commonly during the early phase of mechanical ventilation. The diagnosis of pneumothorax in critical illness is established from the patients’ history, physical examination and radiological investigation, although the appearances of a pneumothorax on a supine radiograph may be different from the classic appearance on an erect radiograph. For this reason, ultrasonography is beneficial for excluding the diagnosis of pneumothorax. Respiration-dependent movement of the visceral pleura and lung surface with respect to the parietal pleura and chest wall can be easily visualized with transthoracic sonography given that the presence of air in the pleural space prevents sonographic visualization of visceral pleura movements. Mechanically ventilated patients with a pneumothorax require tube thoracostomy placement because of the high risk of tension pneumothorax. Small-bore catheters are now preferred in the majority of ventilated patients. Furthermore, if there are clinical signs of a tension pneumothorax, emergency needle decompression followed by tube thoracostomy is widely advocated. Patients with pneumothorax related to mechanical ventilation who have tension pneumothorax, a higher acute physiology and chronic health evaluation II score or PaO2/FiO2 < 200 mmHg were found to have higher mortality. PMID:24834397

  10. Prototype of a computer method for designing and analyzing heating, ventilating and air conditioning proportional, electronic control systems

    NASA Astrophysics Data System (ADS)

    Barlow, Steven J.

    1986-09-01

    The Air Force needs a better method of designing new and retrofit heating, ventilating and air conditioning (HVAC) control systems. Air Force engineers currently use manual design/predict/verify procedures taught at the Air Force Institute of Technology, School of Civil Engineering, HVAC Control Systems course. These existing manual procedures are iterative and time-consuming. The objectives of this research were to: (1) Locate and, if necessary, modify an existing computer-based method for designing and analyzing HVAC control systems that is compatible with the HVAC Control Systems manual procedures, or (2) Develop a new computer-based method of designing and analyzing HVAC control systems that is compatible with the existing manual procedures. Five existing computer packages were investigated in accordance with the first objective: MODSIM (for modular simulation), HVACSIM (for HVAC simulation), TRNSYS (for transient system simulation), BLAST (for building load and system thermodynamics) and Elite Building Energy Analysis Program. None were found to be compatible or adaptable to the existing manual procedures, and consequently, a prototype of a new computer method was developed in accordance with the second research objective.

  11. Bench-test comparison of 26 emergency and transport ventilators.

    PubMed

    L'Her, Erwan; Roy, Annie; Marjanovic, Nicolas

    2014-10-15

    Numerous emergency and transport ventilators are commercialized and new generations arise constantly. The aim of this study was to evaluate a large panel of ventilators to allow clinicians to choose a device, taking into account their specificities of use. This experimental bench-test took into account general characteristics and technical performances. Performances were assessed under different levels of FIO2 (100%, 50% or Air-Mix), respiratory mechanics (compliance 30,70,120 mL/cmH2O; resistance 5,10,20 cmH2O/mL/s), and levels of leaks (3.5 to 12.5 L/min), using a test lung. In total 26 emergency and transport ventilators were analyzed and classified into four categories (ICU-like, n = 5; Sophisticated, n = 10; Simple, n = 9; Mass-casualty and military, n = 2). Oxygen consumption (7.1 to 15.8 L/min at FIO2 100%) and the Air-Mix mode (FIO2 45 to 86%) differed from one device to the other. Triggering performance was heterogeneous, but several sophisticated ventilators depicted triggering capabilities as efficient as ICU-like ventilators. Pressurization was not adequate for all devices. At baseline, all the ventilators were able to synchronize, but with variations among respiratory conditions. Leak compensation in most ICU-like and 4/10 sophisticated devices was able to correct at least partially for system leaks, but with variations among ventilators. Major differences were observed between devices and categories, either in terms of general characteristics or technical reliability, across the spectrum of operation. Huge variability of tidal volume delivery with some devices in response to modifications in respiratory mechanics and FIO2 should make clinicians question their use in the clinical setting.

  12. Integration of a photocatalytic multi-tube reactor for indoor air purification in HVAC systems: a feasibility study.

    PubMed

    van Walsem, Jeroen; Roegiers, Jelle; Modde, Bart; Lenaerts, Silvia; Denys, Siegfried

    2018-04-24

    This work is focused on an in-depth experimental characterization of multi-tube reactors for indoor air purification integrated in ventilation systems. Glass tubes were selected as an excellent photocatalyst substrate to meet the challenging requirements of the operating conditions in a ventilation system in which high flow rates are typical. Glass tubes show a low-pressure drop which reduces the energy demand of the ventilator, and additionally, they provide a large exposed surface area to allow interaction between indoor air contaminants and the photocatalyst. Furthermore, the performance of a range of P25-loaded sol-gel coatings was investigated, based on their adhesion properties and photocatalytic activities. Moreover, the UV light transmission and photocatalytic reactor performance under various operating conditions were studied. These results provide vital insights for the further development and scaling up of multi-tube reactors in ventilation systems which can provide a better comfort, improved air quality in indoor environments, and reduced human exposure to harmful pollutants.

  13. Reproductive Performance of Mice in Disposable and Standard Individually Ventilated Cages

    PubMed Central

    Ferguson, Danielle R; Bailey, Michele M

    2013-01-01

    This study assessed the reproductive performance of mice housed in 2 types of individually ventilated caging systems. Breeding pairs from 48 female and 24 male mice of 3 established transgenic mouse breeding colonies were placed in either a standard or disposable ventilated caging system. For 3 breeding cycles, the number of pups born, pup survival rate to weaning, time interval between litters, and pup weights were monitored for each breeding pair. Disposable and standard cages were maintained in the same location during breeding. Environmental parameters included intracage temperature, humidity, and ammonia and carbon dioxide levels and room light intensity and sound. Overall, 776 offspring were produced. Breeding performance did not differ significantly between the 2 cage types. By 11 wk of age, the weights of pups from both cage types were equivalent. The intracage temperature was 1.1 °F warmer and light intensity at the site of the nest was 34 lx dimmer in disposable cages than in standard caging. The difference in lighting likely was due to nest location; the nests in the disposable cages were at the back of the cages and away from the anterior air supply, whereas in standard caging, nests were at the front of the cages, with the air supply at the rear. Under these husbandry conditions, mice housed in disposable caging systems have comparable breeding performance to those housed in standard individually ventilated cages. PMID:23849403

  14. Simulation of deep ventilation in Crater Lake, Oregon, 1951–2099

    USGS Publications Warehouse

    Wood, Tamara M.; Wherry, Susan A.; Piccolroaz, Sebastiano; Girdner, Scott F

    2016-05-04

    The frequency of deep ventilation events in Crater Lake, a caldera lake in the Oregon Cascade Mountains, was simulated in six future climate scenarios, using a 1-dimensional deep ventilation model (1DDV) that was developed to simulate the ventilation of deep water initiated by reverse stratification and subsequent thermobaric instability. The model was calibrated and validated with lake temperature data collected from 1994 to 2011. Wind and air temperature data from three general circulation models and two representative concentration pathways were used to simulate the change in lake temperature and the frequency of deep ventilation events in possible future climates. The lumped model air2water was used to project lake surface temperature, a required boundary condition for the lake model, based on air temperature in the future climates.The 1DDV model was used to simulate daily water temperature profiles through 2099. All future climate scenarios projected increased water temperature throughout the water column and a substantive reduction in the frequency of deep ventilation events. The least extreme scenario projected the frequency of deep ventilation events to decrease from about 1 in 2 years in current conditions to about 1 in 3 years by 2100. The most extreme scenario considered projected the frequency of deep ventilation events to be about 1 in 7.7 years by 2100. All scenarios predicted that the temperature of the entire water column will be greater than 4 °C for increasing lengths of time in the future and that the conditions required for thermobaric instability induced mixing will become rare or non-existent.The disruption of deep ventilation by itself does not provide a complete picture of the potential ecological and water quality consequences of warming climate to Crater Lake. Estimating the effect of warming climate on deep water oxygen depletion and water clarity will require careful modeling studies to combine the physical mixing processes affected by

  15. 29 CFR 1926.57 - Ventilation.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... exhaust ventilation when used as described in (a) shall be designed to prevent dispersion into the air of... shall be so designed that dusts, fumes, mists, vapors, or gases are not drawn through the work area of employees. (c) Design and operation. Exhaust fans, jets, ducts, hoods, separators, and all necessary...

  16. Indoor to outdoor air quality associations with self-pollution implications inside passenger car cabins

    NASA Astrophysics Data System (ADS)

    Abi-Esber, L.; El-Fadel, M.

    2013-12-01

    In this study, in-vehicle and out-vehicle concentrations of fine particulate matter (PM2.5) and carbon monoxide (CO) are measured to assess commuter's exposure in a commercial residential area and on a highway, under three popular ventilation modes namely, one window half opened, air conditioning on fresh air intake, and air conditioning on recirculation and examine its relationship to scarcely studied parameters including self pollution, out-vehicle sample intake location and meteorological gradients. Self pollution is the intrusion of a vehicle's own engine fumes into the passenger's compartment. For this purpose, six car makes with different ages were instrumented to concomitantly monitor in- and out-vehicle PM2.5 and CO concentrations as well as meteorological parameters. Air pollution levels were unexpectedly higher in new cars compared to old cars, with in-cabin air quality most correlated to that of out-vehicle air near the front windshield. Self-pollution was observed at variable rates in three of the six tested cars. Significant correlations were identified between indoor to outdoor pressure difference and PM2.5 and CO In/Out (IO) ratios under air recirculation and window half opened ventilation modes whereas temperature and humidity difference affected CO IO ratios only under the air recirculation ventilation mode.

  17. Effects of types of ventilation system on indoor particle concentrations in residential buildings.

    PubMed

    Park, J S; Jee, N-Y; Jeong, J-W

    2014-12-01

    The objective of this study was to quantify the influence of ventilation systems on indoor particle concentrations in residential buildings. Fifteen occupied, single-family apartments were selected from three sites. The three sites have three different ventilation systems: unbalanced mechanical ventilation, balanced mechanical ventilation, and natural ventilation. Field measurements were conducted between April and June 2012, when outdoor air temperatures were comfortable. Number concentrations of particles, PM2.5 and CO2 , were continuously measured both outdoors and indoors. In the apartments with natural ventilation, I/O ratios of particle number concentrations ranged from 0.56 to 0.72 for submicron particles, and from 0.25 to 0.60 for particles larger than 1.0 μm. The daily average indoor particle concentration decreased to 50% below the outdoor level for submicron particles and 25% below the outdoor level for fine particles, when the apartments were mechanically ventilated. The two mechanical ventilation systems reduced the I/O ratios by 26% for submicron particles and 65% for fine particles compared with the natural ventilation. These results showed that mechanical ventilation can reduce exposure to outdoor particles in residential buildings. Results of this study confirm that mechanical ventilation with filtration can significantly reduce indoor particle levels compared with natural ventilation. The I/O ratios of particles substantially varied at the naturally ventilated apartments because of the influence of variable window opening conditions and unsteadiness of wind flow on the penetration of outdoor air particles. For better prediction of the exposure to outdoor particles in naturally ventilated residential buildings, it is important to understand the penetration of outdoor particles with variable window opening conditions. © 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  18. Exploration Mission Particulate Matter Filtration Technology Performance Testing in a Simulated Spacecraft Cabin Ventilation System

    NASA Technical Reports Server (NTRS)

    Agui, Juan H.; Vijayakumar, R.; Perry, Jay L.; Frederick, Kenneth R.; Mccormick, Robert M.

    2017-01-01

    Human deep space exploration missions will require advances in long-life, low maintenance airborne particulate matter filtration technology. As one of the National Aeronautics and Space Administrations (NASA) developments in this area, a prototype of a new regenerable, multi-stage particulate matter filtration technology was tested in an International Space Station (ISS) module simulation facility. As previously reported, the key features of the filter system include inertial and media filtration with regeneration and in-place media replacement techniques. The testing facility can simulate aspects of the cabin environment aboard the ISS and contains flight-like cabin ventilation system components. The filtration technology test article was installed at the inlet of the central ventilation system duct and instrumented to provide performance data under nominal flow conditions. In-place regeneration operations were also evaluated. The real-time data included pressure drop across the filter stages, process air flow rate, ambient pressure, humidity and temperature. In addition, two video cameras positioned at the filtration technology test articles inlet and outlet were used to capture the mechanical performance of the filter media indexing operation under varying air flow rates. Recent test results are presented and future design recommendations are discussed.

  19. Air Controlman 1 & C: Rate Training Manual.

    ERIC Educational Resources Information Center

    Naval Training Command, Pensacola, FL.

    The manual is designed for use in preparing for advancement within the Navy Air Controlman rating, which designates a professional air traffic controller, unlike the more specialized center or tower controllers. However, minimum qualifications for the rating include completion of the Federal Aviation Administration (FAA) written examination for…

  20. Cooperation of Horizontal Ground Heat Exchanger with the Ventilation Unit During Summer - Case Study

    NASA Astrophysics Data System (ADS)

    Romańska-Zapała, Anna; Furtak, Marcin; Dechnik, Mirosław

    2017-10-01

    Renewable energy sources are used in the modern energy-efficient buildings to improve their energy balance. One of them is used in the mechanical ventilation system ground air heat exchanger (earth-air heat exchanger - EAHX). This solution, right after heat recovery from exhaust air (recuperation), allows the reduction in the energy needed to obtain the desired temperature of supply air. The article presents the results of "in situ" measurements of pipe ground air heat exchanger cooperating with the air handling unit, supporting cooling the building in the summer season, in Polish climatic conditions. The laboratory consists of a ventilation unit intake - exhaust with rotor for which the source of fresh air is the air intake wall and two air intakes field cooperating with the tube with ground air heat exchangers. Selection of the source of fresh air is performed using sprocket with actuators. This system is part of the ventilation system of the Malopolska Laboratory of Energy-Efficient Building (MLBE) building of Cracow University of Technology. The measuring system are, among others, the sensors of parameters of air inlets and outlets of the heat exchanger channels EAHX and weather station that senses the local weather conditions. The measurement data are recorded and archived by the integrated process control system in the building of MLBE. During the study measurements of operating parameters of the ventilation unit cooperating with the selected source of fresh air were performed. Two cases of operation of the system: using EAHX heat exchanger and without it, were analyzed. Potentially the use of ground air heat exchanger in the mechanical ventilation system can reduce the energy demand for heating or cooling rooms by the pre-adjustment of the supply air temperature. Considering the results can be concluded that the continuous use of these exchangers is not optimal. This relationship is appropriate not only on an annual basis for the transitional periods (spring

  1. Ventilator-Associated Pneumonia in Trauma Patients: Different Criteria, Different Rates.

    PubMed

    Leonard, Kenji L; Borst, Gregory M; Davies, Stephen W; Coogan, Michael; Waibel, Brett H; Poulin, Nathaniel R; Bard, Michael R; Goettler, Claudia E; Rinehart, Shane M; Toschlog, Eric A

    2016-06-01

    No consensus exists regarding the definition of ventilator-associated pneumonia (VAP). Even within a single institution, inconsistent diagnostic criteria result in conflicting rates of VAP. As a Level 1 trauma center participating in the Trauma Quality Improvement Project (TQIP) and the National Healthcare Safety Network (NHSN), our institution showed inconsistencies in VAP rates depending on which criteria was applied. The purpose of this study was to compare VAP definitions, defined by culture-based criteria, National Trauma Data Bank (NTDB) and NHSN, using incidence in trauma patients. A retrospective chart review of consecutive trauma patients who were diagnosed with VAP and met pre-determined inclusion and exclusion criteria admitted to our rural, 861-bed, Level 1 trauma and tertiary care center between January 2008 and December 2011 was performed. These patients were identified from the National Trauma Registry of the American College of Surgeons (NTRACS) database and an in-house infection control database. Ventilator-associated pneumonia diagnosis criteria defined by the U.S. Center for Disease Control and Prevention (used by the NHSN), the NTDB, and our institutional, culture-based criteria gold standard were compared among patients. Two hundred seventy-nine patients were diagnosed with VAP (25.4% met NHSN criteria, 88.2% met NTDB, and 76.3% met culture-based criteria). Only 58 (20.1%) patients met all three criteria. When NHSN criteria were compared with culture-based criteria, NHSN showed a high specificity (92.5%) and low sensitivity (28.2%). The positive predictive value (PPV) was 84.5%, but the negative predictive value (NPV) was 47.1%. The agreement between the NHSN and the culture-based criteria was poor (κ = 0.18). Conversely, the NTDB showed a lower specificity (57.8%), but greater sensitivity (86.4%) compared with culture-based criteria. The PPV and NPV were both 74% and the two criteria showed fair agreement (κ = 0.41). The lack of

  2. 30 CFR 75.371 - Mine ventilation plan; contents.

    Code of Federal Regulations, 2013 CFR

    2013-07-01

    ... (see § 75.325(a)(3)). (k) The minimum mean entry air velocity in exhausting face ventilation systems where coal is being cut, mined, drilled for blasting, or loaded, if the velocity will be less than 60... loaded, where at least 60 feet per minute or some other minimum mean entry air velocity will be...

  3. 30 CFR 75.371 - Mine ventilation plan; contents.

    Code of Federal Regulations, 2014 CFR

    2014-07-01

    ... (see § 75.325(a)(3)). (k) The minimum mean entry air velocity in exhausting face ventilation systems where coal is being cut, mined, drilled for blasting, or loaded, if the velocity will be less than 60... loaded, where at least 60 feet per minute or some other minimum mean entry air velocity will be...

  4. 30 CFR 75.371 - Mine ventilation plan; contents.

    Code of Federal Regulations, 2012 CFR

    2012-07-01

    ... (see § 75.325(a)(3)). (k) The minimum mean entry air velocity in exhausting face ventilation systems where coal is being cut, mined, drilled for blasting, or loaded, if the velocity will be less than 60... loaded, where at least 60 feet per minute or some other minimum mean entry air velocity will be...

  5. Semi-volatile organic compounds in heating, ventilation, and air-conditioning filter dust in retail stores.

    PubMed

    Xu, Y; Liang, Y; Urquidi, J R; Siegel, J A

    2015-02-01

    Retail stores contain a wide range of products that can emit a variety of indoor pollutants. Among these chemicals, phthalate esters and polybrominated diphenyl ethers (PBDEs) are two important categories of semi-volatile organic compounds (SVOCs). Filters in heating, ventilation, and air-conditioning (HVAC) system collect particles from large volumes of air and thus potentially provide spatially and temporally integrated SVOC concentrations. This study measured six phthalate and 14 PBDE compounds in HVAC filter dust in 14 retail stores in Texas and Pennsylvania, United States. Phthalates and PBDEs were widely found in the HVAC filter dust in retail environment, indicating that they are ubiquitous indoor pollutants. The potential co-occurrence of phthalates and PBDEs was not strong, suggesting that their indoor sources are diverse. The levels of phthalates and PBDEs measured in HVAC filter dust are comparable to concentrations found in previous investigations of settled dust in residential buildings. Significant correlations between indoor air and filter dust concentrations were found for diethyl phthalate, di-n-butyl phthalate, and benzyl butyl phthalate. Reasonable agreement between measurements and an equilibrium model to describe SVOC partitioning between dust and gas-phase is achieved. © 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  6. Management and outcome of mechanically ventilated neurologic patients.

    PubMed

    Pelosi, Paolo; Ferguson, Niall D; Frutos-Vivar, Fernando; Anzueto, Antonio; Putensen, Christian; Raymondos, Konstantinos; Apezteguia, Carlos; Desmery, Pablo; Hurtado, Javier; Abroug, Fekri; Elizalde, José; Tomicic, Vinko; Cakar, Nahit; Gonzalez, Marco; Arabi, Yaseen; Moreno, Rui; Esteban, Andres

    2011-06-01

    To describe and compare characteristics, ventilatory practices, and associated outcomes among mechanically ventilated patients with different types of brain injury and between neurologic and nonneurologic patients. Secondary analysis of a prospective, observational, and multicenter study on mechanical ventilation. Three hundred forty-nine intensive care units from 23 countries. We included 552 mechanically ventilated neurologic patients (362 patients with stroke and 190 patients with brain trauma). For comparison we used a control group of 4,030 mixed patients who were ventilated for nonneurologic reasons. None. We collected demographics, ventilatory settings, organ failures, and complications arising during ventilation and outcomes. Multivariate logistic regression analysis was performed with intensive care unit mortality as the dependent variable. At admission, a Glasgow Coma Scale score ≤8 was observed in 68% of the stroke, 77% of the brain trauma, and 29% of the nonneurologic patients. Modes of ventilation and use of a lung-protective strategy within the first week of mechanical ventilation were similar between groups. In comparison with nonneurologic patients, patients with neurologic disease developed fewer complications over the course of mechanical ventilation with the exception of a higher rate of ventilator-associated pneumonia in the brain trauma cohort. Neurologic patients showed higher rates of tracheotomy and longer duration of mechanical ventilation. Mortality in the intensive care unit was significantly (p < .001) higher in patients with stroke (45%) than in brain trauma (29%) and nonneurologic disease (30%). Factors associated with mortality were: stroke (in comparison to brain trauma), Glasgow Coma Scale score on day 1, and severity at admission in the intensive care unit. In our study, one of every five mechanically ventilated patients received this therapy as a result of a neurologic disease. This cohort of patients showed a higher mortality

  7. Modeling spatial and temporal variability of residential air exchange rates for the Near-Road Exposures and Effects of Urban Air Pollutants Study (NEXUS).

    PubMed

    Breen, Michael S; Burke, Janet M; Batterman, Stuart A; Vette, Alan F; Godwin, Christopher; Croghan, Carry W; Schultz, Bradley D; Long, Thomas C

    2014-11-07

    Air pollution health studies often use outdoor concentrations as exposure surrogates. Failure to account for variability of residential infiltration of outdoor pollutants can induce exposure errors and lead to bias and incorrect confidence intervals in health effect estimates. The residential air exchange rate (AER), which is the rate of exchange of indoor air with outdoor air, is an important determinant for house-to-house (spatial) and temporal variations of air pollution infiltration. Our goal was to evaluate and apply mechanistic models to predict AERs for 213 homes in the Near-Road Exposures and Effects of Urban Air Pollutants Study (NEXUS), a cohort study of traffic-related air pollution exposures and respiratory effects in asthmatic children living near major roads in Detroit, Michigan. We used a previously developed model (LBL), which predicts AER from meteorology and questionnaire data on building characteristics related to air leakage, and an extended version of this model (LBLX) that includes natural ventilation from open windows. As a critical and novel aspect of our AER modeling approach, we performed a cross validation, which included both parameter estimation (i.e., model calibration) and model evaluation, based on daily AER measurements from a subset of 24 study homes on five consecutive days during two seasons. The measured AER varied between 0.09 and 3.48 h(-1) with a median of 0.64 h(-1). For the individual model-predicted and measured AER, the median absolute difference was 29% (0.19 h‑1) for both the LBL and LBLX models. The LBL and LBLX models predicted 59% and 61% of the variance in the AER, respectively. Daily AER predictions for all 213 homes during the three year study (2010-2012) showed considerable house-to-house variations from building leakage differences, and temporal variations from outdoor temperature and wind speed fluctuations. Using this novel approach, NEXUS will be one of the first epidemiology studies to apply calibrated and

  8. Measure Guideline: Ventilation Guidance for Residential High-Performance New Construction - Multifamily

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Lstiburek, Joseph

    2017-01-01

    The measure guideline provides ventilation guidance for residential high performance multifamily construction that incorporates the requirements of the ASHRAE 62.2 ventilation and indoor air quality standard. The measure guideline focus is on the decision criteria for weighing cost and performance of various ventilation systems. The measure guideline is intended for contractors, builders, developers, designers and building code officials. The guide may also be helpful to building owners wishing to learn more about ventilation strategies available for their buildings. The measure guideline includes specific design and installation instructions for the most cost effective and performance effective solutions for ventilation in multifamilymore » units that satisfies the requirements of ASHRAE 62.2-2016.« less

  9. Measure Guideline: Ventilation Guidance for Residential High-Performance New Construction - Multifamily

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Lstiburek, Joseph

    The measure guideline provides ventilation guidance for residential high performance multifamily construction that incorporates the requirements of the ASHRAE 62.2 ventilation and indoor air quality standard. The measure guideline focus is on the decision criteria for weighing cost and performance of various ventilation systems. The measure guideline is intended for contractors, builders, developers, designers and building code officials. The guide may also be helpful to building owners wishing to learn more about ventilation strategies available for their buildings. The measure guideline includes specific design and installation instructions for the most cost effective and performance effective solutions for ventilation in multifamilymore » units that satisfies the requirements of ASHRAE 62.2-2016.« less

  10. Flow currents and ventilation in Langstroth beehives due to brood thermoregulation efforts of honeybees.

    PubMed

    Sudarsan, Rangarajan; Thompson, Cody; Kevan, Peter G; Eberl, Hermann J

    2012-02-21

    Beekeepers universally agree that ensuring sufficient ventilation is vital for sustaining a thriving, healthy honeybee colony. Despite this fact, surprisingly little is known about the ventilation and flow patterns in bee hives. We take a first step towards developing a model-based approach that uses computational fluid dynamics to simulate natural ventilation flow inside a standard Langstroth beehive. A 3-D model of a Langstroth beehive with one brood chamber and one honey super was constructed and inside it the honeybee colony was distributed among different clusters each occupying the different bee-spaces between frames in the brood chamber. For the purpose of modeling, each honeybee cluster was treated as an air-saturated porous medium with constant porosity. Heat and mass transfer interactions of the honeybees with the air, the outcome of metabolism, were captured in the porous medium model as source and sink terms appearing in the governing equations of fluid dynamics. The temperature of the brood that results from the thermoregulation efforts of the colony is applied as a boundary condition for the governing equations. The governing equations for heat, mass transport and fluid flow were solved using Fluent(©), a commercially available CFD program. The results from the simulations indicate that (a) both heat and mass transfer resulting from honeybee metabolism play a vital role in determining the structure of the flow inside the beehive and mass transfer cannot be neglected, (b) at low ambient temperatures, the nonuniform temperature profile on comb surfaces that results from brood incubation enhances flow through the honeybee cluster which removes much of the carbon-dioxide produced by the cluster resulting in lower carbon-dioxide concentration next to the brood, (c) increasing ambient (outside) air temperature causes ventilation flow rate to drop resulting in weaker flow inside the beehive. Flow visualization indicates that at low ambient air temperatures

  11. The respiratory system during resuscitation: a review of the history, risk of infection during assisted ventilation, respiratory mechanics, and ventilation strategies for patients with an unprotected airway.

    PubMed

    Wenzel, V; Idris, A H; Dörges, V; Nolan, J P; Parr, M J; Gabrielli, A; Stallinger, A; Lindner, K H; Baskett, P J

    2001-05-01

    The fear of acquiring infectious diseases has resulted in reluctance among healthcare professionals and the lay public to perform mouth-to-mouth ventilation. However, the benefit of basic life support for a patient in cardiopulmonary or respiratory arrest greatly outweighs the risk for secondary infection in the rescuer or the patient. The distribution of ventilation volume between lungs and stomach in the unprotected airway depends on patient variables such as lower oesophageal sphincter pressure, airway resistance and respiratory system compliance, and the technique applied while performing basic or advanced airway support, such as head position, inflation flow rate and time, which determine upper airway pressure. The combination of these variables determines gas distribution between the lungs and the oesophagus and subsequently, the stomach. During bag-valve-mask ventilation of patients in respiratory or cardiac arrest with oxygen supplementation (> or = 40% oxygen), a tidal volume of 6-7 ml kg(-1) ( approximately 500 ml) given over 1-2 s until the chest rises is recommended. For bag-valve-mask ventilation with room-air, a tidal volume of 10 ml kg(-1) (700-1000 ml) in an adult given over 2 s until the chest rises clearly is recommended. During mouth-to-mouth ventilation, a breath over 2 s sufficient to make the chest rise clearly (a tidal volume of approximately 10 ml kg(-1) approximately 700-1000 ml in an adult) is recommended.

  12. Wii, Kinect, and Move. Heart Rate, Oxygen Consumption, Energy Expenditure, and Ventilation due to Different Physically Active Video Game Systems in College Students.

    PubMed

    Scheer, Krista S; Siebrant, Sarah M; Brown, Gregory A; Shaw, Brandon S; Shaw, Ina

    Nintendo Wii, Sony Playstation Move , and Microsoft XBOX Kinect are home video gaming systems that involve player movement to control on-screen game play. Numerous investigations have demonstrated that playing Wii is moderate physical activity at best, but Move and Kinect have not been as thoroughly investigated. The purpose of this study was to compare heart rate, oxygen consumption, and ventilation while playing the games Wii Boxing, Kinect Boxing, and Move Gladiatorial Combat. Heart rate, oxygen consumption, and ventilation were measured at rest and during a graded exercise test in 10 males and 9 females (19.8 ± 0.33 y, 175.4 ± 2.0 cm, 80.2 ± 7.7 kg,). On another day, in a randomized order, the participants played Wii Boxing, K inect Boxing, and Move Gladiatorial Combat while heart rate, ventilation, and oxygen consumption were measured. There were no differences in heart rate (116.0 ± 18.3 vs. 119.3 ± 17.6 vs. 120.1 ± 17.6 beats/min), oxygen consumption (9.2 ± 3.0 vs. 10.6 ± 2.4 vs. 9.6 ± 2.4 ml/kg/min), or minute ventilation (18.9 ± 5.7 vs. 20.8 ± 8.0 vs. 19.7 ± 6.4 L/min) when playing Wii boxing, Kinect boxing, or Move Gladiatorial Combat (respectively). Playing Nintendo Wii Boxing, XBOX Kinect Boxing, and Sony PlayStation Move Gladiatorial Combat all increase heart rate, oxygen consumption, and ventilation above resting levels but there were no significant differences between gaming systems. Overall, playing a "physically active" home video game system does not meet the minimal threshold for moderate intensity physical activity, regardless of gaming system.

  13. Wii, Kinect, and Move. Heart Rate, Oxygen Consumption, Energy Expenditure, and Ventilation due to Different Physically Active Video Game Systems in College Students

    PubMed Central

    SCHEER, KRISTA S.; SIEBRANT, SARAH M.; BROWN, GREGORY A.; SHAW, BRANDON S.; SHAW, INA

    2014-01-01

    Nintendo Wii, Sony Playstation Move, and Microsoft XBOX Kinect are home video gaming systems that involve player movement to control on-screen game play. Numerous investigations have demonstrated that playing Wii is moderate physical activity at best, but Move and Kinect have not been as thoroughly investigated. The purpose of this study was to compare heart rate, oxygen consumption, and ventilation while playing the games Wii Boxing, Kinect Boxing, and Move Gladiatorial Combat. Heart rate, oxygen consumption, and ventilation were measured at rest and during a graded exercise test in 10 males and 9 females (19.8 ± 0.33 y, 175.4 ± 2.0 cm, 80.2 ± 7.7 kg,). On another day, in a randomized order, the participants played Wii Boxing, Kinect Boxing, and Move Gladiatorial Combat while heart rate, ventilation, and oxygen consumption were measured. There were no differences in heart rate (116.0 ± 18.3 vs. 119.3 ± 17.6 vs. 120.1 ± 17.6 beats/min), oxygen consumption (9.2 ± 3.0 vs. 10.6 ± 2.4 vs. 9.6 ± 2.4 ml/kg/min), or minute ventilation (18.9 ± 5.7 vs. 20.8 ± 8.0 vs. 19.7 ± 6.4 L/min) when playing Wii boxing, Kinect boxing, or Move Gladiatorial Combat (respectively). Playing Nintendo Wii Boxing, XBOX Kinect Boxing, and Sony PlayStation Move Gladiatorial Combat all increase heart rate, oxygen consumption, and ventilation above resting levels but there were no significant differences between gaming systems. Overall, playing a “physically active” home video game system does not meet the minimal threshold for moderate intensity physical activity, regardless of gaming system. PMID:27182399

  14. Air Leakage and Air Transfer Between Garage and Living Space

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Rudd, Armin

    2014-09-01

    This research project focused on evaluation of air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multi-point fan pressurization tests and additional zone pressure diagnostic testing characterized the garage and house air leakage, the garage-to-house air leakage, and garage and house pressuremore » relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed.« less

  15. 14 CFR 27.831 - Ventilation.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 14 Aeronautics and Space 1 2010-01-01 2010-01-01 false Ventilation. 27.831 Section 27.831... the presence of excessive quantities of fuel fumes and carbon monoxide. (b) The concentration of carbon monoxide may not exceed one part in 20,000 parts of air during forward flight or hovering in still...

  16. Continuous High-Frequency Oscillation Therapy in Invasively Ventilated Pediatric Subjects in the Critical Care Setting.

    PubMed

    Morgan, Stephen; Hornik, Christoph P; Patel, Niyati; Williford, Walter L; Turner, David A; Cheifetz, Ira M

    2016-11-01

    Continuous high-frequency oscillation (CHFO) creates a pressure gradient in the small airways that accelerates expiratory flow. The intended use of CHFO therapy is to facilitate secretion removal and treat atelectasis. Our objective was to assess the feasibility, safety, and efficacy of CHFO in the mechanically ventilated pediatric population. After institutional review board approval, we retrospectively reviewed medical records of mechanically ventilated children treated with CHFO (the MetaNeb system) at our institution from July 1, 2007 through August 31, 2012. Patients supported with extracorporeal membrane oxygenation were excluded. We evaluated changes in ventilator settings in subjects with ventilator data documented within 6 h pre- and post-treatment. We evaluated arterial blood gas (ABG) results for individual treatments, comparing ABG results within 8 h pre-therapy to ABG results within 3 h post-treatment. Oxygen index and P aO 2 /F IO 2 were calculated. Demographic data, blood pressure, heart rate, and development of new air leak while being treated with CHFO were recorded. Pre- and post-CHFO measurements were compared using Wilcoxon signed-rank testing. Our cohort included 59 invasively ventilated subjects. Median age was 2 y (range 1 month to 19 y), and median weight was 14 kg (2-81 kg). We evaluated data on 528 total treatments (range per subject 1-39 treatments). Peak inspiratory pressure significantly decreased with CHFO, whereas other parameters, including P aCO 2 and breathing frequency, remained stable. There was no significant change in systolic blood pressure, diastolic blood pressure, or heart rate following treatment with CHFO. One subject (2%) developed a clinically insignificant pneumothorax during CHFO. CHFO is feasible and seems safe in our cohort of mechanically ventilated pediatric subjects. The rate of pneumothorax was consistent with that seen in similar pediatric ICU populations. These preliminary results suggest that CHFO may be

  17. Building America Case Study: Air Leakage and Air Transfer Between Garage and Living Space, Waldorf, Maryland (Fact Sheet)

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Not Available

    2014-11-01

    This research project focused on evaluation of air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multi-point fan pressurization tests and additional zone pressure diagnostic testing characterized the garage and house air leakage, the garage-to-house air leakage, and garage and house pressuremore » relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed. For houses employing whole-house supply ventilation (positive pressure) or balanced ventilation (same pressure effect as the Baseline condition), adherence to the EPA Indoor airPLUS house-to-garage air sealing requirements should be sufficient to expect little to no garage-to-house air transfer.« less

  18. Sonic Anemometry to Measure Natural Ventilation in Greenhouses

    PubMed Central

    López, Alejandro; Valera, Diego Luis; Molina-Aiz, Francisco

    2011-01-01

    The present work has developed a methodology for studying natural ventilation in Mediterranean greenhouses by means of sonic anemometry. In addition, specific calculation programmes have been designed to enable processing and analysis of the data recorded during the experiments. Sonic anemometry allows us to study the direction of the airflow at all the greenhouse vents. Knowing through which vents the air enters and leaves the greenhouse enables us to establish the airflow pattern of the greenhouse under natural ventilation conditions. In the greenhouse analysed in this work for Poniente wind (from the southwest), a roof vent designed to open towards the North (leeward) could allow a positive interaction between the wind and stack effects, improving the ventilation capacity of the greenhouse. The cooling effect produced by the mass of turbulent air oscillating between inside and outside the greenhouse at the side vents was limited to 2% (for high wind speed, uo ≥ 4 m s−1) reaching 36.3% when wind speed was lower (uo = 2 m s−1). PMID:22163728

  19. Sonic anemometry to measure natural ventilation in greenhouses.

    PubMed

    López, Alejandro; Valera, Diego Luis; Molina-Aiz, Francisco

    2011-01-01

    The present work has developed a methodology for studying natural ventilation in Mediterranean greenhouses by means of sonic anemometry. In addition, specific calculation programmes have been designed to enable processing and analysis of the data recorded during the experiments. Sonic anemometry allows us to study the direction of the airflow at all the greenhouse vents. Knowing through which vents the air enters and leaves the greenhouse enables us to establish the airflow pattern of the greenhouse under natural ventilation conditions. In the greenhouse analysed in this work for Poniente wind (from the southwest), a roof vent designed to open towards the North (leeward) could allow a positive interaction between the wind and stack effects, improving the ventilation capacity of the greenhouse. The cooling effect produced by the mass of turbulent air oscillating between inside and outside the greenhouse at the side vents was limited to 2% (for high wind speed, u(o) ≥ 4 m s(-1)) reaching 36.3% when wind speed was lower (u(o) = 2 m s(-1)).

  20. Measuring and modeling air exchange rates inside taxi cabs in Los Angeles, California

    NASA Astrophysics Data System (ADS)

    Shu, Shi; Yu, Nu; Wang, Yueyan; Zhu, Yifang

    2015-12-01

    Air exchange rates (AERs) have a direct impact on traffic-related air pollutant (TRAP) levels inside vehicles. Taxi drivers are occupationally exposed to TRAP on a daily basis, yet there is limited measurement of AERs in taxi cabs. To fill this gap, AERs were quantified in 22 representative Los Angeles taxi cabs including 10 Prius, 5 Crown Victoria, 3 Camry, 3 Caravan, and 1 Uplander under realistic driving (RD) conditions. To further study the impacts of window position and ventilation settings on taxi AERs, additional tests were conducted on 14 taxis with windows closed (WC) and on the other 8 taxis with not only windows closed but also medium fan speed (WC-MFS) under outdoor air mode. Under RD conditions, the AERs in all 22 cabs had a mean of 63 h-1 with a median of 38 h-1. Similar AERs were observed under WC condition when compared to those measured under RD condition. Under WC-MFS condition, AERs were significantly increased in all taxi cabs, when compared with those measured under RD condition. A General Estimating Equation (GEE) model was developed and the modeling results showed that vehicle model was a significant factor in determining the AERs in taxi cabs under RD condition. Driving speed and car age were positively associated with AERs but not statistically significant. Overall, AERs measured in taxi cabs were much higher than typical AERs people usually encounter in indoor environments such as homes, offices, and even regular passenger vehicles.

  1. Preoperational test report, recirculation ventilation systems

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Clifton, F.T.

    1997-11-11

    This represents a preoperational test report for Recirculation Ventilation Systems, Project W-030. Project W-030 provides a ventilation upgrade for the four Aging Waste Facility tanks. The system provides vapor space cooling of tanks AY1O1, AY102, AZ1O1, AZ102 and supports the ability to exhaust air from each tank. Each system consists of a valved piping loop, a fan, condenser, and moisture separator; equipment is located inside each respective tank farm in its own hardened building. The tests verify correct system operation and correct indications displayed by the central Monitor and Control System.

  2. Field study of exhaust fans for mitigating indoor air quality problems: Final report

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Grimsrud, D.T.; Szydlowski, R.F.; Turk, B.H.

    1986-09-01

    Residential ventilation in the United States housing stock is provided primarily by infiltration, the natural leakage of outdoor air into a building through cracks and holes in the building shell. Since ventilation is the dominant mechanism for control of indoor pollutant concentrations, low infiltration rates caused fluctuation in weather conditions may lead to high indoor pollutant concentrations. Supplemental mechanical ventilation can be used to eliminate these periods of low infiltration. This study examined effects of small continuously-operating exhaust fan on pollutant concentrations and energy use in residences.

  3. Design and Evaluation of a Ventilated Garment for Use in Temperatures up to 200°C

    PubMed Central

    Crockford, G. W.; Hellon, R. F.

    1964-01-01

    The protection of personnel against high air and radiant temperatures is a problem that has been confronting industry for many years now, and for many industrial situations it still has not been solved. The experiments reported here were intended to determine the most suitable form of insulation for a hot entry suit for use primarily in furnace wrecking where mean radiant temperatures of 200°C. are met and where heat-reflecting garments are unsuitable due to the rapid deterioration of the reflecting surface. From a preliminary consideration of the problem it was concluded that a ventilated garment was required and that conventional ventilated garments in which air is induced to flow parallel to the body surfaces (axial ventilation) are basically unsound in design as the air is not utilized for the transfer of heat in the most efficient manner. A new form of ventilation was therefore developed in which air flows out through a permeable suit (radial ventilation). This form of ventilation produces what is called dynamic insulation, and this method of insulation, when compared with two alternative methods on a physical model, was found to be very effective. The model experiments were confirmed by comparative trials of three ventilated suits each using one of three different forms of insulation thought to be suitable for use in heat-protective clothing. Physiological measurements made on the subjects and physical measurement made on the suits confirmed that dynamic insulation is the most suitable insulation for a hot entry suit for furnace wrecking. With the air flows used in these experiments, dynamic insulation had a thermal conductance one-fifth that of conventional static insulation, and sweat losses and oral temperature rises were reduced by one-third and one-half respectively. PMID:14180476

  4. Three-dimensional visualization of morphology and ventilation procedure (air flow and diffusion) of a subdivision of the acinus using synchrotron radiation microtomography of the human lung specimens

    NASA Astrophysics Data System (ADS)

    Shimizu, Kenji; Ikura, Hirohiko; Ikezoe, Junpei; Nagareda, Tomofumi; Yagi, Naoto; Umetani, Keiji; Imai, Yutaka

    2004-04-01

    We have previously reported a synchrotron radiation (SR) microtomography system constructed at the bending magnet beamline at the SPring-8. This system has been applied to the lungs obtained at autopsy and inflated and fixed by Heitzman"s method. Normal lung and lung specimens with two different types of pathologic processes (fibrosis and emphysema) were included. Serial SR microtomographic images were stacked to yield the isotropic volumetric data with high-resolution (12 μm3 in voxel size). Within the air spaces of a subdivision of the acinus, each voxel is segmented three-dimensionally using a region growing algorithm ("rolling ball algorithm"). For each voxel within the segmented air spaces, two types of voxel coding have been performed: single-seeded (SS) coding and boundary-seeded (BS) coding, in which the minimum distance from an initial point as the only seed point and all object boundary voxels as a seed set were calculated and assigned as the code values to each voxel, respectively. With these two codes, combinations of surface rendering and volume rendering techniques were applied to visualize three-dimensional morphology of a subdivision of the acinus. Furthermore, sequentially filling process of air into a subdivision of the acinus was simulated under several conditions to visualize the ventilation procedure (air flow and diffusion). A subdivision of the acinus was reconstructed three-dimensionally, demonstrating the normal architecture of the human lung. Significant differences in appearance of ventilation procedure were observed between normal and two pathologic processes due to the alteration of the lung architecture. Three-dimensional reconstruction of the microstructure of a subdivision of the acinus and visualization of the ventilation procedure (air flow and diffusion) with SR microtomography would offer a new approach to study the morphology, physiology, and pathophysiology of the human respiratory system.

  5. Numerical analyses of ventilated cavitation over a 2-D NACA0015 hydrofoil using two turbulence modeling methods

    NASA Astrophysics Data System (ADS)

    Yang, Dan-dan; Yu, An; Ji, Bin; Zhou, Jia-jian; Luo, Xian-wu

    2018-04-01

    The present paper studies the ventilated cavitation over a NACA0015 hydrofoil by numerical methods. The corresponding cavity evolutions are obtained at three ventilation rates by using the level set method. To depict the complicated turbulent flow structure, the filter-based density corrected model (FBDCM) and the modified partially-averaged Navier-Stokes (MPANS) model are applied in the present numerical analyses. It is indicated that the predicted results of the cavitation shedding dynamics by both turbulence models agree fairly well with the experimental data. It is also noted that the shedding frequency and the super cavity length predicted by the MPANS method are closer to the experiment data as compared to that predicted by the FBDCM model. The simulation results show that in the ventilated cavitation, the vapor cavity and the air cavity have the same shedding frequency. As the ventilated rate increases, the vapor cavity is depressed rapidly. The cavitation-vortex interaction in the ventilated cavitation is studied based on the vorticity transport equation (VTE) and the Lagrangian coherent structure (LCS). Those results demonstrate that the vortex dilatation and baroclinic torque terms are highly dependent on the evolution of the cavitation. In addition, from the LCSs and the tracer particles in the flow field, one may see the process from the attached cavity to the cloud cavity.

  6. Ventilator-associated pneumonia: the influence of bacterial resistance, prescription errors, and de-escalation of antimicrobial therapy on mortality rates.

    PubMed

    Souza-Oliveira, Ana Carolina; Cunha, Thúlio Marquez; Passos, Liliane Barbosa da Silva; Lopes, Gustavo Camargo; Gomes, Fabiola Alves; Röder, Denise Von Dolinger de Brito

    2016-01-01

    Ventilator-associated pneumonia is the most prevalent nosocomial infection in intensive care units and is associated with high mortality rates (14-70%). This study evaluated factors influencing mortality of patients with Ventilator-associated pneumonia (VAP), including bacterial resistance, prescription errors, and de-escalation of antibiotic therapy. This retrospective study included 120 cases of Ventilator-associated pneumonia admitted to the adult adult intensive care unit of the Federal University of Uberlândia. The chi-square test was used to compare qualitative variables. Student's t-test was used for quantitative variables and multiple logistic regression analysis to identify independent predictors of mortality. De-escalation of antibiotic therapy and resistant bacteria did not influence mortality. Mortality was 4 times and 3 times higher, respectively, in patients who received an inappropriate antibiotic loading dose and in patients whose antibiotic dose was not adjusted for renal function. Multiple logistic regression analysis revealed the incorrect adjustment for renal function was the only independent factor associated with increased mortality. Prescription errors influenced mortality of patients with Ventilator-associated pneumonia, underscoring the challenge of proper Ventilator-associated pneumonia treatment, which requires continuous reevaluation to ensure that clinical response to therapy meets expectations. Copyright © 2016. Published by Elsevier Editora Ltda.

  7. Towards energy efficient operation of Heating, Ventilation and Air Conditioning systems via advanced supervisory control design

    NASA Astrophysics Data System (ADS)

    Oswiecinska, A.; Hibbs, J.; Zajic, I.; Burnham, K. J.

    2015-11-01

    This paper presents conceptual control solution for reliable and energy efficient operation of heating, ventilation and air conditioning (HVAC) systems used in large volume building applications, e.g. warehouse facilities or exhibition centres. Advanced two-level scalable control solution, designed to extend capabilities of the existing low-level control strategies via remote internet connection, is presented. The high-level, supervisory controller is based on Model Predictive Control (MPC) architecture, which is the state-of-the-art for indoor climate control systems. The innovative approach benefits from using passive heating and cooling control strategies for reducing the HVAC system operational costs, while ensuring that required environmental conditions are met.

  8. Water content of delivered gases during non-invasive ventilation in healthy subjects.

    PubMed

    Lellouche, François; Maggiore, Salvatore Maurizio; Lyazidi, Aissam; Deye, Nicolas; Taillé, Solenne; Brochard, Laurent

    2009-06-01

    No clear recommendation exists concerning humidification during non-invasive ventilation (NIV) and high flow CPAP, and few hygrometric data are available. We measured hygrometry during NIV delivered to healthy subjects with different humidification strategies: heated humidifier (HH), heat and moisture exchanger, (HME) or no humidification (NoH). For each strategy, a turbine and an ICU ventilator were used with different FiO(2) settings, with and without leaks. During CPAP, two different HH and NoH were tested. Inspired gases hygrometry was measured, and comfort was assessed. On a bench, we also assessed the impact of ambient air temperature, ventilator temperature and minute ventilation on HH performances (with NIV settings). During NIV, with NoH, gas humidity was very low when an ICU ventilator was used (5 mgH(2)O/l), but equivalent to ambient air hygrometry with a turbine ventilator at minimal FiO(2) (13 mgH(2)O/l). HME and HH had comparable performances (25-30 mgH(2)O/l), but HME's effectiveness was reduced with leaks (15 mgH(2)O/l). HH performances were reduced by elevated ambient air and ventilator output temperatures. During CPAP, dry gases (5 mgH(2)O/l) were less tolerated than humidified gases. Gases humidified at 15 or 30 mgH(2)O/l were equally tolerated. This study provides data on the level of humidity delivered with different humidification strategies during NIV and CPAP. HH and HME provide gas with the highest water content. Comfort data suggest that levels above 15 mgH(2)O/l are well tolerated. In favorable conditions, HH and HMEs are capable of providing such values, even in the presence of leaks.

  9. Carbon monoxide poisonings from small, gasoline-powered, internal combustion engines: just what is a "well-ventilated area"?

    PubMed

    Earnest, G S; Mickelsen, R L; McCammon, J B; O'Brien, D M

    1997-11-01

    This study modeled the time required for a gasoline-powered, 5 horsepower (hp), 4-cycle engine to generate carbon monoxide (CO) concentrations exceeding the National Institute for Occupational Safety and Health 200-ppm ceiling and 1200-ppm immediately dangerous to life and health concentration for various room sizes and ventilation rates. The model permitted the ambiguous term "well-ventilated area" to be defined. The model was compared with field data collected at a site where two workers were poisoned while operating a 5-hp concrete saw in a bathroom having open doors and an operating ventilation system. There is agreement between both the modeled and field-generated data, indicating that hazardous CO concentrations can develop within minutes. Comparison of field and modeling data showed the measured CO generation rate at approximately one-half of the value used in the model, which may be partially because the engine used in the field was not under load during data collection. The generation rate and room size from the actual poisoning was then used in the model. The model determined that ventilation rates of nearly 5000 ft3/min (120 air changes per hour) would be required to prevent the CO concentration from exceeding the 200-ppm ceiling for short periods. Results suggest that small gasoline-powered engines should not be operated inside of buildings or in semienclosed spaces and that manufacturers of such tools should improve their warnings and develop engineering control options for better user protection.

  10. Operating and maintaining your heat recovery ventilator (HRV) -- Revised edition. Home heating and cooling series, Number 8

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    NONE

    Heat recovery ventilators (HRVs) differ from other mechanical ventilation devices by their ability to exchange heat between supply and exhaust air streams, which reduces the cost of heating or cooling fresh air. This booklet discusses the need for mechanical ventilation in conventional and energy-efficient homes, an explains the components of a HRV system, how to operate and maintain the system, and how to solve operating problems. A maintenance chart and schedule and a HRV troubleshooting guide are included.

  11. Hexavalent Chromium and Isocyanate Exposures during Military Aircraft Painting under Crossflow Ventilation

    PubMed Central

    Bennett, James S.; Marlow, David A.; Nourian, Fariba; Breay, James; Hammond, Duane

    2016-01-01

    Exposure control systems performance was investigated in an aircraft painting hangar. The ability of the ventilation system and respiratory protection program to limit worker exposures was examined through air sampling during painting of F/A-18C/D strike fighter aircraft, in four field surveys. Air velocities were measured across the supply filter, exhaust filter, and hangar midplane under crossflow ventilation. Air sampling conducted during painting process phases (wipe-down, primer spraying, and topcoat spraying) encompassed volatile organic compounds, total particulate matter, Cr[VI], metals, nitroethane, and hexamethylene diisocyanate, for two worker groups: sprayers and sprayer helpers (“hosemen”). One of six methyl ethyl ketone and two of six methyl isobutyl ketone samples exceeded the short term exposure limits of 300 and 75 ppm, with means 57 ppm and 63 ppm, respectively. All 12 Cr[VI] 8-hr time-weighted averages exceeded the recommended exposure limit of 1 µg/m3, 11 out of 12 exceeded the permissible exposure limit of 5 µg/m3, and 7 out of 12 exceeded the threshold limit value of 10 µg/m3, with means 38 µg/m3 for sprayers and 8.3 µg/m3 for hosemen. Hexamethylene diisocyanate means were 5.95 µg/m3 for sprayers and 0.645 µg/m3 for hosemen. Total reactive isocyanate group—the total of monomer and oligomer as NCO group mass—showed six of 15 personal samples exceeded the United Kingdom Health and Safety Executive workplace exposure limit of 20 µg/m3, with means 50.9 µg/m3 for sprayers and 7.29 µg/m3 for hosemen. Several exposure limits were exceeded, reinforcing continued use of personal protective equipment. The supply rate, 94.4 m3/s (200,000 cfm), produced a velocity of 8.58 m/s (157 fpm) at the supply filter, while the exhaust rate, 68.7 m3/s (146,000 cfm), drew 1.34 m/s (264 fpm) at the exhaust filter. Midway between supply and exhaust locations, the velocity was 0.528 m/s (104 fpm). Supply rate exceeding exhaust rate created re

  12. Energy Savings Potential and Research, Development, & Demonstration Opportunities for Commercial Building Heating, Ventilation, and Air Conditioning Systems

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    none,

    2011-09-01

    This report covers an assessment of 182 different heating, ventilation, and air-conditioning (HVAC) technologies for U.S. commercial buildings to identify and provide analysis on 17 priority technology options in various stages of development. The analyses include an estimation of technical energy-savings potential, description of technical maturity, description of non-energy benefits, description of current barriers for market adoption, and description of the technology’s applicability to different building or HVAC equipment types. From these technology descriptions, are suggestions for potential research, development and demonstration (RD&D) initiatives that would support further development of the priority technology options.

  13. Estimated effect of ventilation and filtration on chronic health risks in U.S. offices, schools, and retail stores.

    PubMed

    Chan, W R; Parthasarathy, S; Fisk, W J; McKone, T E

    2016-04-01

    We assessed the chronic health risks from inhalation exposure to volatile organic compounds (VOCs) and particulate matter (PM2.5) in U.S. offices, schools, grocery, and other retail stores and evaluated how chronic health risks were affected by changes in ventilation rates and air filtration efficiency. Representative concentrations of VOCs and PM2.5 were obtained from available data. Using a mass balance model, changes in exposure to VOCs and PM2.5 were predicted if ventilation rate were to increase or decrease by a factor of two, and if higher efficiency air filters were used. Indoor concentrations were compared to health guidelines to estimate percentage exceedances. The estimated chronic health risks associated with VOC and PM2.5 exposures in these buildings were low relative to the risks from exposures in homes. Chronic health risks were driven primarily by exposures to PM2.5 that were evaluated using disease incidence of mortality, chronic bronchitis, and non-fatal stroke. The leading cancer risk factor was exposure to formaldehyde. Using disability-adjusted life years (DALYs) to account for both cancer and non-cancer effects, results suggest that increasing ventilation alone is ineffective at reducing chronic health burdens. Other strategies, such as pollutant source control and the use of particle filtration, should also be considered. © 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

  14. Validating and improving CT ventilation imaging by correlating with ventilation 4D-PET/CT using {sup 68}Ga-labeled nanoparticles

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Kipritidis, John, E-mail: john.kipritidis@sydney.edu.au; Keall, Paul J.; Siva, Shankar

    Purpose: CT ventilation imaging is a novel functional lung imaging modality based on deformable image registration. The authors present the first validation study of CT ventilation using positron emission tomography with{sup 68}Ga-labeled nanoparticles (PET-Galligas). The authors quantify this agreement for different CT ventilation metrics and PET reconstruction parameters. Methods: PET-Galligas ventilation scans were acquired for 12 lung cancer patients using a four-dimensional (4D) PET/CT scanner. CT ventilation images were then produced by applying B-spline deformable image registration between the respiratory correlated phases of the 4D-CT. The authors test four ventilation metrics, two existing and two modified. The two existing metricsmore » model mechanical ventilation (alveolar air-flow) based on Hounsfield unit (HU) change (V{sub HU}) or Jacobian determinant of deformation (V{sub Jac}). The two modified metrics incorporate a voxel-wise tissue-density scaling (ρV{sub HU} and ρV{sub Jac}) and were hypothesized to better model the physiological ventilation. In order to assess the impact of PET image quality, comparisons were performed using both standard and respiratory-gated PET images with the former exhibiting better signal. Different median filtering kernels (σ{sub m} = 0 or 3 mm) were also applied to all images. As in previous studies, similarity metrics included the Spearman correlation coefficient r within the segmented lung volumes, and Dice coefficient d{sub 20} for the (0 − 20)th functional percentile volumes. Results: The best agreement between CT and PET ventilation was obtained comparing standard PET images to the density-scaled HU metric (ρV{sub HU}) with σ{sub m} = 3 mm. This leads to correlation values in the ranges 0.22 ⩽ r ⩽ 0.76 and 0.38 ⩽ d{sub 20} ⩽ 0.68, with r{sup ¯}=0.42±0.16 and d{sup ¯}{sub 20}=0.52±0.09 averaged over the 12 patients. Compared to Jacobian-based metrics, HU-based metrics lead to statistically

  15. Forecasting Foreign Currency Exchange Rates for Air Force Budgeting

    DTIC Science & Technology

    2015-03-26

    FORECASTING FOREIGN CURRENCY EXCHANGE RATES FOR AIR FORCE BUDGETING THESIS MARCH 2015...States. AFIT-ENV-MS-15-M-178 FORECASTING FOREIGN CURRENCY EXCHANGE RATES FOR AIR FORCE BUDGETING THESIS Presented to the Faculty...FORECASTING FOREIGN CURRENCY EXCHANGE RATES FOR AIR FORCE BUDGETING Nicholas R. Gardner, BS Captain, USAF Committee Membership: Lt Col Jonathan

  16. Effects of changing ambient temperature on metabolic, heart, and ventilation rates during steady state hibernation in golden-mantled ground squirrels (Spermophilus lateralis).

    PubMed

    Zimmer, M B; Milsom, W K

    2001-01-01

    To determine whether metabolic rate is suppressed in a temperature-independent fashion in the golden-mantled ground squirrel during steady state hibernation, we measured body temperature and metabolic rate in ground squirrels during hibernation at different T(a)'s. In addition, we attempted to determine whether heart rate, ventilation rate, and breathing patterns changed as a function of body temperature or metabolic rate. We found that metabolic rate changed with T(a) as it was raised from 5 degrees to 14 degrees C, which supports the theory that different species sustain falls in metabolic rate during hibernation in different ways. Heart rate and breathing pattern also changed with changing T(a), while breathing frequency did not. That the total breathing frequency did not correlate closely with oxygen consumption or body temperature, while the breathing pattern did, raises important questions regarding the mechanisms controlling ventilation during hibernation.

  17. The growing role of noninvasive ventilation in patients requiring prolonged mechanical ventilation.

    PubMed

    Hess, Dean R

    2012-06-01

    For many patients with chronic respiratory failure requiring ventilator support, noninvasive ventilation (NIV) is preferable to invasive support by tracheostomy. Currently available evidence does not support the use of nocturnal NIV in unselected patients with stable COPD. Several European studies have reported benefit for high intensity NIV, in which setting of inspiratory pressure and respiratory rate are selected to achieve normocapnia. There have also been studies reporting benefit for the use of NIV as an adjunct to exercise training. NIV may be useful as an adjunct to airway clearance techniques in patients with cystic fibrosis. Accumulating evidence supports the use of NIV in patients with obesity hypoventilation syndrome. There is considerable observational evidence supporting the use of NIV in patients with chronic respiratory failure related to neuromuscular disease, and one randomized controlled trial reported that the use of NIV was life-prolonging in patients with amyotrophic lateral sclerosis. A variety of interfaces can be used to provide NIV in patients with stable chronic respiratory failure. The mouthpiece is an interface that is unique in this patient population, and has been used with success in patients with neuromuscular disease. Bi-level pressure ventilators are commonly used for NIV, although there are now a new generation of intermediate ventilators that are portable, have a long battery life, and can be used for NIV and invasive applications. Pressure support ventilation, pressure controlled ventilation, and volume controlled ventilation have been used successfully for chronic applications of NIV. New modes have recently become available, but their benefits await evidence to support their widespread use. The success of NIV in a given patient population depends on selection of an appropriate patient, selection of an appropriate interface, selection of an appropriate ventilator and ventilator settings, the skills of the clinician, the

  18. Household ventilation and tuberculosis transmission in Kampala, Uganda.

    PubMed

    Chamie, G; Wandera, B; Luetkemeyer, A; Bogere, J; Mugerwa, R D; Havlir, D V; Charlebois, E D

    2013-06-01

    To test the feasibility of measuring household ventilation and evaluate whether ventilation is associated with tuberculosis (TB) in household contacts in Kampala, Uganda. Adults with pulmonary TB and their household contacts received home visits to ascertain social and structural household characteristics. Ventilation was measured in air changes per hour (ACH) in each room by raising carbon dioxide (CO₂) levels using dry ice, removing the dry ice, and measuring changes in the natural log of CO₂ (lnCO2) over time. Ventilation was compared in homes with and without co-prevalent TB. Members of 61 of 66 (92%) households approached were enrolled. Households averaged 5.4 residents/home, with a median of one room/home. Twelve homes (20%) reported co-prevalent TB in household contacts. Median ventilation for all rooms was 14 ACH (interquartile range [IQR] 10-18). Median ventilation was 12 vs. 15 ACH in index cases' sleeping rooms in households with vs. those without co-prevalent TB (P = 0.12). Among smear-positive indexes not infected by the human immunodeficiency virus (HIV), median ventilation was 11 vs. 17 ACH in index cases' sleeping rooms in homes with vs. those without co-prevalent TB (P = 0.1). Our findings provide evidence that a simple CO₂ decay method used to measure ventilation in clinical settings can be adapted to homes, adding a novel tool and a neglected variable, ventilation, to the study of household TB transmission.

  19. Gill and lung ventilation responses to steady-state aquatic hypoxia and hyperoxia in the bullfrog tadpole.

    PubMed

    West, N H; Burggren, W W

    1982-02-01

    Gill ventilation frequency (fG), the pressure amplitude (PBC) and stroke volume (VS) of buccal ventilation cycles, the frequency of air breaths (fL), water flow over the gills (VW), gill oxygen uptake (MGO2), oxygen utilization (U), and heart frequency (fH) have been measured in unanaesthetized, air breathing Rana catesbeiana tadpoles (stage XVI-XIX). The animals were unrestrained except for ECG leads or cannulae, and were able to surface voluntarily for air breathing. They were subjected to aquatic normoxia, hyperoxia and three levels of aquatic hypoxia, and their respiratory responses recorded in the steady state. The experiments were performed at 20 +/- 0.5 degrees C. In hyperoxia there was an absence of air breathing, and fG, PBC and VW fell from the normoxic values, while U increased, resulting in no significant change in MGO2. Animals in normoxia showed a very low fL which increased in progressively more hypoxic states. VW increased from the normoxic value in mild hypoxia (PO2 = 96 +/- 2 mm Hg), but fell, associated with a reduction in PBC, in moderate (PO2 = 41 +/- 1 mm Hg) and severe (PO2 = 21 +/- 3 mm Hg) hypoxia in the presence of lung ventilation. Gill MGO2 was not significantly different from the normoxic value in mild hypoxia but fell in moderate hypoxia, while in severe hypoxia oxygen was lost to the ventilating water from the blood perfusing the gills. There was no significant change in fH from the normoxic value in either hypoxia or hyperoxia. These data indicate, that in the bimodally breathing bullfrog tadpole, aquatic PO2 exerts a strong control over both gill and lung ventilation. Furthermore, there is an interaction between gill and lung ventilation such that the onset of a high frequency of lung ventilation in moderate and severe hypoxia promotes a suppression of gill ventilation cycles.

  20. Predicting indoor pollutant concentrations, and applications to air quality management

    DOE Office of Scientific and Technical Information (OSTI.GOV)

    Lorenzetti, David M.

    Because most people spend more than 90% of their time indoors, predicting exposure to airborne pollutants requires models that incorporate the effect of buildings. Buildings affect the exposure of their occupants in a number of ways, both by design (for example, filters in ventilation systems remove particles) and incidentally (for example, sorption on walls can reduce peak concentrations, but prolong exposure to semivolatile organic compounds). Furthermore, building materials and occupant activities can generate pollutants. Indoor air quality depends not only on outdoor air quality, but also on the design, maintenance, and use of the building. For example, ''sick building'' symptomsmore » such as respiratory problems and headaches have been related to the presence of air-conditioning systems, to carpeting, to low ventilation rates, and to high occupant density (1). The physical processes of interest apply even in simple structures such as homes. Indoor air quality models simulate the processes, such as ventilation and filtration, that control pollutant concentrations in a building. Section 2 describes the modeling approach, and the important transport processes in buildings. Because advection usually dominates among the transport processes, Sections 3 and 4 describe methods for predicting airflows. The concluding section summarizes the application of these models.« less