Science.gov

Sample records for air volume hvac

  1. The Energy Implications of Air-Side Fouling in Constant Air Volume HVAC Systems

    NASA Astrophysics Data System (ADS)

    Wilson, Eric J. H.

    2011-12-01

    This thesis examines the effect of air-side fouling on the energy consumption of constant air volume (CAV) heating, ventilating, and air conditioning (HVAC) systems in residential and small commercial buildings. There is a particular focus on evaluating the potential energy savings that may result from the remediation of such fouling from coils, filters, and other air system components. A computer model was constructed to simulate the behavior of a building and its duct system under various levels of fouling. The model was verified through laboratory and field testing and then used to run parametric simulations to examine the range of energy impacts for various climates and duct system characteristics. A sensitivity analysis was conducted to determine the impact of parameters like duct insulation, duct leakage, duct location, and duct design on savings potential. Duct system pressures, temperatures, and energy consumption for two houses were monitored for one month. The houses' duct systems, which were both in conditioned space, were given a full cleaning, and were then monitored for another month. The flow rates at the houses improved by 10% and 6%. The improvements were primarily due to installing a new filter, as both houses had only light coil fouling. The results indicate that there was negligible change in heating energy efficiency due to the system cleaning. The parametric simulation results are in agreement with the field experiment: for systems in all eight climates, with flowrates degraded by 20% or less, if ducts are located within the thermal zone, HVAC source energy savings from cleaning are negligible or even slightly negative. However, if ducts are outside the thermal zone, savings are in the 1 to 5% range. For systems with flowrates degraded by 40%, if ducts are within the thermal zone, savings from cleaning occurs only for air conditioning energy, up to 8% in climates like Miami, FL. If ducts are outside the thermal zone, savings occurs with both

  2. HVAC system performance and indoor air quality

    SciTech Connect

    Newman, J.L. )

    1991-01-01

    This paper reports that in the mid-seventies, the American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) promulgated ASHRAE Standard 90-75 Energy Conservation in New Building Design, which called for revised minimum ventilation rates and the elimination of energy-wasting HVAC systems. Most building codes which cover energy conservation in the late seventies and eighties referred to this standard. This lowering of ventilation rates, coupled with the tighter building envelope (walls, windows, doors and roof) led to a reduction in outside air, both by engineering design and by minimizing infiltration through the structure. The minimum ventilation rates are based on the assumption that average concentrations of tobacco smoke exist in all enclosed spaces (30 percent of the population being smokers at two cigarettes per hour), rather than having separate rates for smoking and nonsmoking areas, as in the 1981 revision of the Standard. If tobacco smoke is ever declared a carcinogen, it will undoubtedly prompt a review of Standard 62-1989, as well as hasten totally smoke-free buildings.

  3. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Introduction to Construction Series. Instructor Edition.

    ERIC Educational Resources Information Center

    Associated General Contractors of America, Washington, DC.

    This module on introductory heating, ventilating, and air conditioning (HVAC) is one of a series of modules designed to teach basic skills necessary for entry-level employment in this field. The module contains four instructional units that cover the following topics: (1) HVAC materials; (2) HVAC tools; (3) HVAC layout; and (4) HVAC basic skills.…

  4. HVAC SYSTEMS AS EMISSION SOURCES AFFECTING INDOOR AIR QUALITY: A CRITICAL REVIEW

    EPA Science Inventory

    The study evaluates heating, ventilating, and air-conditioning (HVAC) systems as contaminant emission sources that affect indoor air quality (IAQ). Various literature sources and methods for characterizing HVAC emission sources are reviewed. Available methods include in situ test...

  5. Air Cleaning Devices for HVAC Supply Systems in Schools. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.

    Guidelines for maintaining indoor air quality in schools with HVAC air cleaning systems are provided in this document. Information is offered on the importance of air cleaning, sources of air contaminants and indoor pollutants, types of air cleaners and particulate filters used in central HVAC systems, vapor and gas removal, and performance…

  6. Introduction to Heating, Ventilation and Air Conditioning (HVAC). Instructor Edition. Introduction to Construction Series.

    ERIC Educational Resources Information Center

    Oklahoma State Dept. of Vocational and Technical Education, Stillwater. Curriculum and Instructional Materials Center.

    This instructor's guide contains the materials required to teach a competency-based introductory course in heating, ventilating, and air conditioning (HVAC) to students who have chosen to explore careers in construction. It contains three units: HVAC materials, HVAC tools, and applied skills. Each instructional unit includes some or all of the…

  7. Designing Forced-Air HVAC Systems

    SciTech Connect

    2010-08-31

    This guide explains proper calculation of heating and cooling design loads for homes.used to calculated for the home using the protocols set forth in the latest edition of the Air Conditioning Contractors of America’s (ACCA) Manual J (currently the 8th edition), ASHRAE 2009 Handbook of Fundamentals, or an equivalent computation procedure.

  8. HVAC SYSTEMS AS EMISSION SOURCES AFFECTING INDOOR AIR QUALITY: A CRITICAL REVIEW

    EPA Science Inventory

    The paper discusses results of an evaluation of literature on heating, ventilating, and air-conditioning (HVAC) systems as contaminant emission sources that affect indoor air quality (IAQ). The various literature sources and methods for characterizing HVAC emission sources are re...

  9. Building America Top Innovations 2014 Profile: HVAC Cabinet Air Leakage Test Method

    SciTech Connect

    none,

    2014-11-01

    This 2014 Top Innovation profile describes Building America-funded research by teams and national laboratories that resulted in the development of an ASHRAE standard and a standardized testing method for testing the air leakage of HVAC air handlers and furnace cabinets and has spurred equipment manufacturers to tighten the cabinets they use for residential HVAC systems.

  10. HVAC SYSTEMS AS A TOOL IN CONTROLLING INDOOR AIR QUALITY: A LITERATURE REVIEW

    EPA Science Inventory

    The report gives results of a review of literature on the use of heating, ventilating, and air-conditioning (HVAC) systems to control indoor air quality (IAQ). Although significant progress has been made in reducing the energy consumption of HVAC systems, their effect on indoor a...

  11. HVAC System Automatic Controls and Indoor Air Quality in Schools. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.

    Fans, motors, coils, and other control components enable a heating, ventilating, and air-conditioning (HVAC) system to function smoothly. An explanation of these control components and how they make school HVAC systems work is provided. Different systems may be compared by counting the number of controlled devices that are required. Control…

  12. Application information on typical hygrometers used in heating, ventilating and air conditioning (HVAC) systems

    SciTech Connect

    Kao, J.Y.; Snyder, W.J.

    1982-01-01

    Hygrometer selection information is provided for application in heating, ventilating and air-conditioning (HVAC) systems. A general review of hygrometer literature has been provided and the most commonly used ones for HVAC are discussed. Typical hygrometer parameters are listed to indicate the type of performance that can be expected. Laboratory test results of self-regulating, salt-phase transition hygrometers are presented and discussed in detail.

  13. HVAC (heating, ventilation, air conditioning) literature in Japan: A critical review

    SciTech Connect

    Hane, G.J.

    1988-02-01

    Japanese businessmen in the heating, ventilation, air conditioning, and refrigeration (HVACandR) industry consider the monitoring of technical and market developments in the United States to be a normal part of their business. In contrast, efforts by US businessmen to monitor Japanese HVAC and R developments are poorly developed. To begin to redress this imbalance, this report establishes the groundwork for a more effective system for use in monitoring Japanese HVAC and R literature. Discussions of a review of the principal HVAC and R publications in Japan and descriptions of the type of information contained in each of those publications are included in this report. Since the Japanese HVAC and R literature is abundant, this report also provides practical suggestions on how a researcher or research manager can limit the monitoring effort to the publications and type of information that would most likely be of greatest value.

  14. INFLUENCE OF RESIDENTIAL HVAC DUTY CYCLE ON INDOOR AIR QUALITY

    EPA Science Inventory

    Measurements of duty cycle, the fraction of time the heating and cooling (HVAC) system was operating, were made in homes during the spring season of the RTP Particulate Matter Panel Study and the Tampa Asthmatic Children's Study. A temperature sensor/logger placed on an outlet...

  15. Building America Best Practices Series Volume 14 - HVAC. A Guide for Contractors to Share with Homeowners

    SciTech Connect

    Baechler, Michael C.; Gilbride, Theresa L.; Hefty, Marye G.; Hand, James R.; Love, Pat M.

    2011-08-01

    This guide, which is part of a series of Best Practices guides produced by DOE’s Building America program, describes ways homeowners can reduce their energy costs and improve the comfort, health, and safety of their homes by upgrading their heating, ventilation, and air conditioning (HVAC) equipment.

  16. Selecting HVAC Systems for Schools To Balance the Needs for Indoor Air Quality, Energy Conservation and Maintenance. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.; Kunz, Walter S., Jr.

    Although poor air quality in a school can have multiple causes, the heating, ventilating, and air-conditioning (HVAC) system plays a major role. Suggestions that architects, facilities managers, school board members, and administrators can use in selecting HVAC systems are discussed. Focus is on the performance criteria for classroom systems, and…

  17. An approach to monitoring HVAC (heating ventilating and air conditioning) technology developments in Japan

    SciTech Connect

    Lewis, P.M.; Ashton, W.B.; McDonald, S.C.

    1987-12-01

    This paper presents a discussion of methods for periodicaly monitoring Japanese advanced technology developments for equipment and components in the heating ventilating and air conditioning (HVAC) industry. The emphasis in the approach recommended is on evaluation of foreign literature - both technical and trade publications - because of both the increasing availability of these materials and the usefulness of information they present. Although not a comprehensive nor completely detailed source of information, HVAC technology literature is an important component of ''scanning the business/technical environmental'' for many purposes. Moreover, despite obstacles in obtaining and translating some important literature, useful knowledge can be obtained from many foreign literature sources for relatively modest costs.

  18. Improving air handler efficiency in residential HVAC applications

    SciTech Connect

    Walker, Iain S.; Mingee, Michael D.; Brenner, Douglas E.

    2003-08-01

    In continuing the development of energy efficiency standards, consideration has turned to air handlers used for heating and air conditioning of consumer residences. These air handlers have typical efficiencies of about 10% to 15% due to poor electric motor performance and aerodynamically poor fans and fan housings. This study was undertaken to examine some of these performance issues, under carefully controlled laboratory conditions, to support potential regulatory changes. In addition, this study examined the performance of a prototype air handler fan assembly that offers the potential for substantial increases in performance. This prototype and a standard production fan were tested in a full-scale duct system and test chamber at LBNL which was specifically designed for testing heating, ventilation, and air conditioning systems. The laboratory tests compared efficiency, total airflow, sensitivity to duct system flow resistance, and the effects of installation in a smaller cabinet. The test results showed that, averaged over a wide range of operating conditions, the prototype air handler had about twice the efficiency of the standard air handler and was less sensitive to duct system flow resistance changes. The performance of both air handlers was significantly reduced by reducing the space between the air handler and the cabinet it was installed in. Therefore any fan rating needs to be performed using the actual cabinet it will be used in.

  19. Fan electricity consumption for variable air volume

    SciTech Connect

    Spitler, J.D.; Pedersen, C.O.; Hittle, D.C.; Johnson, D.L.

    1986-01-01

    HVAC designers choosing variable air volume (VAV) systems have several options for modulating the flow. Some of the more popular methods for centrifugal fans are discharge dampers, inlet vanes, and motor speed control. This paper describes a study in which these different methods of fan modulation are compared for two prototypical buildings in five locations in the United States. The tool used to compare the methods is the Building Loads Analysis and System Thermodynamics (BLAST) program. In addition, factors affecting the results are also examined. In particular, a detailed examination of the annual building load distribution is made.

  20. Self-Correcting HVAC Controls: Algorithms for Sensors and Dampers in Air-Handling Units

    SciTech Connect

    Fernandez, Nicholas; Brambley, Michael R.; Katipamula, Srinivas

    2009-12-31

    This report documents the self-correction algorithms developed in the Self-Correcting Heating, Ventilating and Air-Conditioning (HVAC) Controls project funded jointly by the Bonneville Power Administration and the Building Technologies Program of the U.S. Department of Energy. The algorithms address faults for temperature sensors, humidity sensors, and dampers in air-handling units and correction of persistent manual overrides of automated control systems. All faults considered create energy waste when left uncorrected as is frequently the case in actual systems.

  1. The NYC native air sampling pilot project: using HVAC filter data for urban biological incident characterization.

    PubMed

    Ackelsberg, Joel; Leykam, Frederic M; Hazi, Yair; Madsen, Larry C; West, Todd H; Faltesek, Anthony; Henderson, Gavin D; Henderson, Christopher L; Leighton, Terrance

    2011-09-01

    Native air sampling (NAS) is distinguished from dedicated air sampling (DAS) devices (eg, BioWatch) that are deployed to detect aerosol disseminations of biological threat agents. NAS uses filter samples from heating, ventilation, and air conditioning (HVAC) systems in commercial properties for environmental sampling after DAS detection of biological threat agent incidents. It represents an untapped, scientifically sound, efficient, widely distributed, and comparably inexpensive resource for postevent environmental sampling. Calculations predict that postevent NAS would be more efficient than environmental surface sampling by orders of magnitude. HVAC filter samples could be collected from pre-identified surrounding NAS facilities to corroborate the DAS alarm and delineate the path taken by the bioaerosol plume. The New York City (NYC) Native Air Sampling Pilot Project explored whether native air sampling would be acceptable to private sector stakeholders and could be implemented successfully in NYC. Building trade associations facilitated outreach to and discussions with property owners and managers, who expedited contact with building managers of candidate NAS properties that they managed or owned. Nominal NAS building requirements were determined; procedures to identify and evaluate candidate NAS facilities were developed; data collection tools and other resources were designed and used to expedite candidate NAS building selection and evaluation in Manhattan; and exemplar environmental sampling playbooks for emergency responders were completed. In this sample, modern buildings with single or few corporate tenants were the best NAS candidate facilities. The Pilot Project successfully demonstrated that in one urban setting a native air sampling strategy could be implemented with effective public-private collaboration. PMID:21793731

  2. Energy Renovations: Volume 14: HVAC - A Guide for Contractors to Share with Homeowners

    SciTech Connect

    Gilbride, Theresa L.; Baechler, Michael C.; Hefty, Marye G.; Hand, James R.; Love, Pat M.

    2011-08-29

    This report was prepared by PNNL for DOE's Building America program and is intended as a guide that energy performance contractors can share with homeowners to describe various energy-efficient options for heating, cooling, and ventilating existing homes. The report provides descriptions of many common and not-so-common HVAC systems, including their advantages and disadvantages, efficiency ranges and characteristics of high-performance models, typical costs, and climate considerations. The report also provides decision trees and tables of useful information for homeowners who are making decisions about adding, replacing, or upgrading existing HVAC equipment in their homes. Information regarding home energy performance assessments (audits) and combustion safety issues when replacing HVAC equipment are also provided.

  3. HVAC equipment and noise

    SciTech Connect

    Cerami, V.J.

    1996-03-01

    The purpose of this article is to define how the selection of HVAC equipment and layout impact the achievable noise criteria (NC) levels in occupied spaces. It will focus on the design of HVAC systems that employ floor-by-floor air handling/air conditioning units and their acoustical ramifications. This is of increasing importance since tenants require incorporation of noise limits in lease agreements.

  4. RELATIONSHIP BETWEEN HVAC SYSTEM OPERATION, AIR EXCHANGE RATE, AND INDOOR-OUTDOOR PARTICULATE MATTER RATIOS

    EPA Science Inventory

    Measurements of duty cycle , the fraction of time the heating and cooling (HVAC) system was operating, were made in each participant's home during the spring season of the RTP Particulate Matter Panel Study. A miniature temperature sensor/data logger combination placed on the ...

  5. Next Generation HVAC System

    NASA Astrophysics Data System (ADS)

    Takagi, Yasuo; Murakami, Yoshiki; Hanada, Yuuichi; Nishimura, Nobutaka; Yamazaki, Kenichi; Itoh, Yasuyuki

    A new HVAC (Heating, Ventilating, and Air-Conditioning) system for buildings is proposed. The key technology for the system is a twin coil air handling unit (AHU) and its advanced control method. One coil is equipped to cool and dehumidify the fresh air intake, and the other coil is for cooling circulated air. The deeply chilled water is necessary only for removing the moisture from the fresh air. The latter coil requires moderately cool water according to the HVAC load. Then 2 kinds of chilled water in terms of temperature should be prepared. The structure helps saving the energy consumption for air-conditioning because the higher chilled water temperature implies the better chiller efficiency (COP: Coefficient of Performance). In addition, an advanced control method that is called an ‘Air-Water cooperation system’ is introduced. The control system mainly focuses on energy savings through changing the temperature of the chilled water and supply air according to the HVAC load and weather conditions. In this paper, we introduce a Next Generation HVAC system with its control system and present evaluation results of the system for the model-building simulator.

  6. Attenuating noise generated by variable-air-volume systems

    SciTech Connect

    Stokes, R.

    1985-03-01

    Sound generated by HVAC systems is receiving much attention because they are generally the principal contributors to room background sound levels that may become irritating and distracting noise if not controlled. This article discusses the creation of a quiet working environment through an analysis of the three traditional sound paths associated with air handling systems: radiated sound, inlet or return air sound and discharge sound. Recommended standards are given as well as a brief overview of materials used to fabricate HVAC system components.

  7. Chlorofluorocarbon (CFC) limitation in heating, ventilating, and air conditioning (HVAC) systems. Engineering technical letter

    SciTech Connect

    Not Available

    1991-08-21

    Conversion of existing HVAC equipment, typically centrifugal chillers, to operate on the alternative refrigerants should be undertaken only when economically or operationally appropriate. An engineered conversion should be made in consultation with the original equipment manufacturer to ascertain the effect on capacity and energy usage, and to determine the proper conversion program to minimize degradation in capacity and increase in energy consumption. Consideration should be given to supplementing lost capacity with an additional chiller by comparing the cost of this approach to the cost of the various conversion options.

  8. R and D opportunities for commercial HVAC (heating, air conditioning, and ventilation) equipment

    SciTech Connect

    Chiu, S.A.; Zaloudek, F.R.

    1987-03-01

    The overall objective of this project is to identify and characterize generic HVAC equipment research that will provide the best investment opportunities for DOE R and D funds. The prerequisites of a DOE research program include research efforts that are potentially significant in energy conservation impact and that are cost-effective, long-term, and high risk. These prerequisites form the basic guidelines for the R and D opportunities assessed. The assessment excludes the R and D areas that have potential or current private sector sponsors. Finally, R and D areas which are included in DOE programs generally are not addressed.

  9. Validation of the criteria for initiating the cleaning of heating, ventilation, and air-conditioning (HVAC) ductwork under real conditions.

    PubMed

    Lavoie, Jacques; Marchand, Geneviève; Cloutier, Yves; Lavoué, Jérôme

    2011-08-01

    Dust accumulation in the components of heating, ventilation, and air-conditioning (HVAC) systems is a potential source of contaminants. To date, very little information is available on recognized methods for assessing dust buildup in these systems. The few existing methods are either objective in nature, involving numerical values, or subjective in nature, based on experts' judgments. An earlier project aimed at assessing different methods of sampling dust in ducts was carried out in the laboratories of the Institut de recherche Robert-Sauvé en santé et en sécurité du travail (IRSST). This laboratory study showed that all the sampling methods were practicable, provided that a specific surface-dust cleaning initiation criterion was used for each method. However, these conclusions were reached on the basis of ideal conditions in a laboratory using a reference dust. The objective of this present study was to validate these laboratory results in the field. To this end, the laboratory sampling templates were replicated in real ducts and the three sampling methods (the IRSST method, the method of the U.S. organization National Air Duct Cleaner Association [NADCA] and that of the French organization Association pour la Prévention et l'Étude de la Contamination [ASPEC]) were used simultaneously in a statistically representative number of systems. The air return and supply ducts were also compared. Cleaning initiation criteria under real conditions were found to be 6.0 mg/100 cm(2) using the IRSST method, 2.0 mg/100 cm(2) using the NADCA method, and 23 mg/100 cm(2) using the ASPEC method. In the laboratory study, the criteria using the same methods were 6.0 for the IRSST method, 2.0 for the NADCA method, and 3.0 for the ASPEC method. The laboratory criteria for the IRSST and NADCA methods were therefore validated in the field. The ASPEC criterion was the only one to change. The ASPEC method therefore allows for the most accurate evaluation of dust accumulation in HVAC

  10. Cold Vacuum Drying facility HVAC system design description

    SciTech Connect

    SINGH, G.

    2000-09-22

    This System Design Description (SDD) addresses the HVAC system for the CVDF. The CVDF HVAC system consists of five subsystems: (1) Administration building HVAC system; (2) Process bay recirculation HVAC system; (3) Process bay local exhaust HVAC and process vent system; (4) Process general supply/exhaust HVAC system; and (5) Reference air system. The HVAC and reference air systems interface with the following systems: the fire protection control system, Monitoring and Control System (MCS), electrical power distribution system (including standby power), compressed air system, Chilled Water (CHW) system, drainage system, and other Cold Vacuum Drying (CVD) control systems not addressed in this SDD.

  11. Cold Vacuum Drying facility HVAC system design description (SYS 30-1 THRU 30-5)

    SciTech Connect

    PITKOFF, C.C.

    1999-07-02

    This document describes the Cold Vacuum Drying Facility (CVDF) heating, ventilation, and air conditioning system (HVAC). The CVDF HVAC system consists of the Administrative building HVAC system, the process bay recirculation HVAC system, the process bay local HVAC and process vent system, the process general supply/exhaust HVAC system, and the Reference air system. These HVAC sub-systems support the CVDF process and provide secondary confinement of contamination and the required filtration of exhaust.

  12. Impact of HVAC filter on indoor air quality in terms of ozone removal and carbonyls generation

    NASA Astrophysics Data System (ADS)

    Lin, Chi-Chi; Chen, Hsuan-Yu

    2014-06-01

    This study aims at detecting ozone removal rates and corresponding carbonyls generated by ozone reaction with HVAC filters from various building, i.e., shopping mall, school, and office building. Studies were conducted in a small-scale environmental chamber. By examining dust properties including organic carbon proportion and specific surface area of dusts adsorbed on filters along with ozone removal rates and carbonyls generation rate, the relationship among dust properties, ozone removal rates, and carbonyls generation was identified. The results indicate a well-defined positive correlation between ozone removal efficiency and carbonyls generation on filters, as well as a positive correlation among the mass of organic carbon on filters, ozone removal efficiency and carbonyls generations.

  13. Strategy Guideline: HVAC Equipment Sizing

    SciTech Connect

    Burdick, A.

    2012-02-01

    The heating, ventilation, and air conditioning (HVAC) system is arguably the most complex system installed in a house and is a substantial component of the total house energy use. A right-sized HVAC system will provide the desired occupant comfort and will run efficiently. This Strategy Guideline discusses the information needed to initially select the equipment for a properly designed HVAC system. Right-sizing of an HVAC system involves the selection of equipment and the design of the air distribution system to meet the accurate predicted heating and cooling loads of the house. Right-sizing the HVAC system begins with an accurate understanding of the heating and cooling loads on a space; however, a full HVAC design involves more than just the load estimate calculation - the load calculation is the first step of the iterative HVAC design procedure. This guide describes the equipment selection of a split system air conditioner and furnace for an example house in Chicago, IL as well as a heat pump system for an example house in Orlando, Florida. The required heating and cooling load information for the two example houses was developed in the Department of Energy Building America Strategy Guideline: Accurate Heating and Cooling Load Calculations.

  14. Quieting the HVAC system

    SciTech Connect

    Johnson, J.; Rose, T.

    1984-03-01

    Since nearly all occupied buildings in the U.S. are air conditioned to control the interior environment for the benefit of occupants and machines, criteria have been established for the type of continuous noise generally created by HVAC systems in buildings. This article reviews sound isolation and absorbing products and quieter air conditioning components. Given are methods for analyzing sound reduction, for selecting standards and for vibration isolation.

  15. Laboratory Evaluation of Air Flow Measurement Methods for Residential HVAC Returns

    SciTech Connect

    Walker, Iain; Stratton, Chris

    2015-07-01

    This project improved the accuracy of air flow measurements used in commissioning California heating and air conditioning systems in Title 24 (Building and Appliance Efficiency Standards), thereby improving system performance and efficiency of California residences. The research team at Lawrence Berkeley National Laboratory addressed the issue that typical tools used by contractors in the field to test air flows may not be accurate enough to measure return flows used in Title 24 applications. The team developed guidance on performance of current diagnostics as well as a draft test method for use in future evaluations. The series of tests performed measured air flow using a range of techniques and devices. The measured air flows were compared to reference air flow measurements using inline air flow meters built into the test apparatus. The experimental results showed that some devices had reasonable results (typical errors of 5 percent or less) but others had much bigger errors (up to 25 percent).

  16. Aging assessment of essential HVAC chillers used in nuclear power plants. Phase 1, Volume 1

    SciTech Connect

    Blahnik, D.E.; Klein, R.F.

    1993-09-01

    The Pacific Northwest Laboratory conducted a Phase I aging assessment of chillers used in the essential safety air-conditioning systems of nuclear power plants. Centrifugal chillers in the 75- to 750-ton refrigeration capacity range are the predominant type used. The chillers used, and air-conditioning systems served, vary in design from plant-to-plant. It is crucial to keep chiller internals very clean and to prevent the leakage of water, air, and other contaminants into the refrigerant containment system. Periodic operation on a weekly or monthly basis is necessary to remove moisture and noncondensable gases that gradually build up inside the chiller. This is especially desirable if a chiller is required to operate only as an emergency standby unit. The primary stressors and aging mechanisms that affect chillers include vibration, excessive temperatures and pressures, thermal cycling, chemical attack, and poor quality cooling water. Aging is accelerated by moisture, non-condensable gases (e.g., air), dirt, and other contamination within the refrigerant containment system, excessive start/stop cycling, and operating below the rated capacity. Aging is also accelerated by corrosion and fouling of the condenser and evaporator tubes. The principal cause of chiller failures is lack of adequate monitoring. Lack of performing scheduled maintenance and human errors also contribute to failures.

  17. Laboratory Evaluation of Air Flow Measurement Methods for Residential HVAC Returns for New Instrument Standards

    SciTech Connect

    Walker, Iain; Stratton, Chris

    2015-08-01

    This project improved the accuracy of air flow measurements used in commissioning California heating and air conditioning systems in Title 24 (Building and Appliance Efficiency Standards), thereby improving system performance and efficiency of California residences. The research team at Lawrence Berkeley National Laboratory addressed the issue that typical tools used by contractors in the field to test air flows may not be accurate enough to measure return flows used in Title 24 applications. The team developed guidance on performance of current diagnostics as well as a draft test method for use in future evaluations. The study team prepared a draft test method through ASTM International to determine the uncertainty of air flow measurements at residential heating ventilation and air conditioning returns and other terminals. This test method, when finalized, can be used by the Energy Commission and other entities to specify required accuracy of measurement devices used to show compliance with standards.

  18. LABORATORY EVALUATION OF AIR FLOW MEASUREMENT METHODS FOR RESIDENTIAL HVAC RETURNS

    SciTech Connect

    Walker, Iain; Stratton, Chris

    2015-02-01

    This project improved the accuracy of air flow measurements used in commissioning California heating and air conditioning systems in Title 24 (Building and Appliance Efficiency Standards), thereby improving system performance and efficiency of California residences. The research team at Lawrence Berkeley National Laboratory addressed the issue that typical tools used by contractors in the field to test air flows may not be accurate enough to measure return flows used in Title 24 applications. The team developed guidance on performance of current diagnostics as well as a draft test method for use in future evaluations. The series of tests performed measured air flow using a range of techniques and devices. The measured air flows were compared to reference air flow measurements using inline air flow meters built into the test apparatus. The experimental results showed that some devices had reasonable results (typical errors of 5 percent or less) but others had much bigger errors (up to 25 percent). Because manufacturers’ accuracy estimates for their equipment do not include many of the sources of error found in actual field measurements (and replicated in the laboratory testing in this study) it is essential for a test method that could be used to determine the actual uncertainty in this specific application. The study team prepared a draft test method through ASTM International to determine the uncertainty of air flow measurements at residential heating ventilation and air conditioning returns and other terminals. This test method, when finalized, can be used by the Energy Commission and other entities to specify required accuracy of measurement devices used to show compliance with standards.

  19. Breathing Easier: HVAC Specifications for Schools.

    ERIC Educational Resources Information Center

    Trent, C. Curtis; Trent, Warren C.

    1996-01-01

    A major source of indoor air contamination in schools originates within the heating, ventilating, and air-conditioning systems (HVAC), with draw-through systems being the worst offenders. Lists provisions for designing an HVAC system and a set of criteria to adhere to when planning new construction or renovations. (nine references) (MLF)

  20. Indoor air quality impacts of residential HVAC systems. Phase 2.a report: Baseline and preliminary simulations

    SciTech Connect

    Emmerich, S.J.; Persily, A.K.

    1995-01-01

    NIST is performing whole building airflow and contaminant dispersal computer simulations with the program CONTAM93 to assess the ability of modifications of central forced-air heating and cooling systems to control pollutant sources relevant to the residential environment. The report summarizes the results of Phase II.A of this project, which consisted of three major efforts: baseline simulations of contaminant levels without indoor air quality (IAQ) controls, design of the IAQ control retrofits, and preliminary simulations of contaminant levels with the IAQ control retrofits. In Phase II.B of the study, all of the baseline cases will be modified to incorporate the IAQ control retrofits. The retrofit results will then be compared to the baseline results to evaluate the effectiveness of the retrofits.

  1. Workplace Trends In HVAC/R

    ERIC Educational Resources Information Center

    Strang, Lynn; Todd, CeCe

    2013-01-01

    This article presents trends in the heating, ventilation, air conditioning and refrigeration (HVAC/R) industry, with an emphasis on the importance of technician training programs as exemplified at the East Valley Institute of Technology (EVIT) in Mesa, Arizona. The article states that HVAC workers are increasingly helping their consumers "go…

  2. Value impact analysis of Generic Issue 143, Availability of Heating, Ventilation, Air Conditioning (HVAC) and Chilled Water Systems

    SciTech Connect

    Daling, P.M.; Marler, J.E.; Vo, T.V.; Phan, H.; Friley, J.R.

    1993-11-01

    This study evaluates the values (benefits) and impacts (costs) associated with potential resolutions to Generic Issue 143, ``Availability of HVAC and Chilled Water Systems.`` The study identifies vulnerabilities related to failures of HVAC, chilled water, and room cooling systems; develops estimates of room heatup rates and safety-related equipment vulnerabilities following losses of HVAC/room cooler systems; develops estimates of the core damage frequencies and public risks associated with failures of these systems; develops three proposed resolution strategies to this generic issue; and performs a value/impact analysis of the proposed resolutions. Existing probabilistic risk assessments for four representative plants, including one plant from each vendor, form the basis for the core damage frequency and public risk calculations. Both internal and external events were considered. It was concluded that all three proposed resolution strategies exceed the $1,000/person-rem cost-effectiveness ratio. Additional evaluations were performed to develop ``generic`` insights on potential design-related and configuration-related vulnerabilities and potential high-frequency ({approximately}1E-04/RY) accident sequences that involve failures of HVAC/room cooling functions. It was concluded that, although high-frequency accident sequences may exist at some plants, these high-frequency sequences are plant-specific in nature or have been resolved through hardware and/or operational changes. The plant-specific Individual Plant Examinations are an effective vehicle for identification and resolution of these plant-specific anomalies and hardware configurations.

  3. Fault detection and diagnosis of HVAC systems

    SciTech Connect

    Han, C.Y.; Xiao, Y.; Ruther, C.J.

    1999-07-01

    This paper presents a model-based fault detection and diagnosis (FDD) system for building heating, ventilating, and air conditioning (HVAC). Model-based fault detection is based on the strategy of determining the difference or the residuals between the normal and the existing patterns. Their approach was to attack the problem on many levels of abstraction: from the signal level, controller programming level, and system component, all the way up to the information and knowledge processing level. The various issues of real implementation of the system and the processing of real-time on-line data in actual systems of campus buildings using the proven technology and off-the-shelf commercial tools are discussed. The research was based on input and output points and software control programs found in typical direct digital control systems used for variable-air-volume air handlers and VAV cooling and hot water reheat terminal units.

  4. Job Prospects in HVAC Engineering.

    ERIC Educational Resources Information Center

    Basta, Nicholas

    1985-01-01

    Although heating, ventilation, and air conditioning (HVAC) engineering degrees are not offered, there is a serious need for specialists and consultants in this area (since most have been trained as mechanical engineers). Opportunities exist for individuals possessing a customer-oriented attitude, with knowledge in computerized controls, innovative…

  5. Air Quality Instrumentation. Volume 1.

    ERIC Educational Resources Information Center

    Scales, John W., Ed.

    To insure a wide dissemination of information describing advances in measurement and control techniques, the Instrument Society of America (ISA) has published this monograph of selected papers from recent ISA symposia dealing with air pollution. Papers range from a discussion of some relatively new applications of proven techniques to discussions…

  6. Air Quality Instrumentation. Volume 2.

    ERIC Educational Resources Information Center

    Scales, John W., Ed.

    To insure a wide dissemination of information describing advances in measurement and control techniques, the Instrument Society of America (ISA) has published this monograph of selected papers, the second in a series, from recent ISA symposia dealing with air pollution. Papers range from a discussion of individual pollutant measurements to…

  7. Air volume measurement of 'Braeburn' apple fruit.

    PubMed

    Drazeta, Lazar; Lang, Alexander; Hall, Alistair J; Volz, Richard K; Jameson, Paula E

    2004-05-01

    The radial disposition of air in the flesh of fruit of Malus domestica Borkh., cv 'Braeburn' was investigated using a gravimetric technique based on Archimedes' principle. Intercellular air volume was measured by weighing a small tissue sample under water before and after vacuum infiltration to remove the air. In a separate procedure, the volume of the same sample was measured by recording the buoyant upthrust experienced by it when fully immersed in water. The method underestimates tissue air volume due to a slight invasion of the intercellular air spaces around the edges of the sample when it is immersed in water. To correct for this error, an adjustment factor was made based upon an analysis of a series of measurements of air volume in samples of different dimensions. In 'Braeburn' there is a gradient of declining air content from just beneath the skin to the centre of the fruit with a sharp discontinuity at the core line. Cell shape and cell packing were observed in the surface layers of freshly excised and stained flesh samples using a dissecting microscope coupled to a video camera and a PC running proprietary software. Tissue organization changed with distance below the skin. It is speculated that reduced internal gas movement, due to the tightly packed tissue of 'Braeburn' and to the potential diffusion barrier at the core line between the cortex and the pith, may increase susceptibility of the flesh to disorders associated with tissue browning and breakdown. PMID:15047764

  8. High air volume to low liquid volume aerosol collector

    DOEpatents

    Masquelier, Donald A.; Milanovich, Fred P.; Willeke, Klaus

    2003-01-01

    A high air volume to low liquid volume aerosol collector. A high volume flow of aerosol particles is drawn into an annular, centripetal slot in a collector which directs the aerosol flow into a small volume of liquid pool contained is a lower center section of the collector. The annular jet of air impinges into the liquid, imbedding initially airborne particles in the liquid. The liquid in the pool continuously circulates in the lower section of the collector by moving to the center line, then upwardly, and through assistance by a rotating deflector plate passes back into the liquid at the outer area adjacent the impinging air jet which passes upwardly through the liquid pool and through a hollow center of the collector, and is discharged via a side outlet opening. Any liquid droplets escaping with the effluent air are captured by a rotating mist eliminator and moved back toward the liquid pool. The collector includes a sensor assembly for determining, controlling, and maintaining the level of the liquid pool, and includes a lower centrally located valve assembly connected to a liquid reservoir and to an analyzer for analyzing the particles which are impinged into the liquid pool.

  9. HVAC Trials.

    ERIC Educational Resources Information Center

    Greim, Clifton W.; D'Angelo, David

    1999-01-01

    Explains how commissioning can help to ensure that all components in a new heating, ventilation, and air conditioning system will work together as designed. Bowdoin College's experience with commissioning is highlighted. (GR)

  10. Study of lubricant circulation in HVAC systems. Volume 1: Description of technical effort and results; Final technical report, March 1995--April 1996

    SciTech Connect

    Biancardi, F.R.; Michels, H.H.; Sienel, T.H.; Pandy, D.R.

    1996-10-01

    The purpose of this program was to conduct experimental and analytical efforts to determine lubricant circulation characteristics of new HFC/POE pairs and HFC/mineral oil pairs in a representative central residential HVAC system and to compare their behavior with the traditional HCFC-22/mineral oil (refrigerant/lubricant) pair. A dynamic test facility was designed and built to conduct the experimental efforts. This facility provided a unique capability to visually and physically measure oil circulation rates, on-line, in operating systems. A unique on-line ultraviolet-based measurement device was used to obtain detailed data on the rate and level of lubricant oil circulated within the operating heat pump system. The experimental and analytical data developed during the program are presented as a function of vapor velocity, refrigerant/lubricant viscosity, system features and equipment. Both visual observations and instrumentation were used to understand ``worst case`` oil circulation situations. This report is presented in two volumes. Volume 1 contains a complete description of the program scope, objective, test results summary, conclusions, description of test facility and recommendations for future effort. Volume 2 contains all of the program test data essentially as taken from the laboratory dynamic test facility during the sequence of runs.

  11. Why HVAC commissioning procedures do not work in humid climates

    SciTech Connect

    DuBose, G.H.; Odom, J.D. III; Fairey, P.W.

    1993-12-01

    This article discusses ways to avoid moisture damage to buildings caused by improper commissioning of HVAC systems during periods of high humidity. The topics of the article include moisture control strategies, air leakage in hot, humid climates, commissioning HVAC systems, and case studies covering central exhaust systems, building chases being used as air distribution systems, and leakage at guest room fan coil units.

  12. HVAC [Heating, Ventilation and Air Conditioning] subsystem design description: 4 x 350 MW(t) Modular HTGR [High-Temperature Gas-Cooled Reactor] Plant

    SciTech Connect

    1986-06-01

    The HVAC system is a subsystem within the Mechanical Services Group (MSG). The HVAC system for the 4 x 350 MW(t) Modular HTGR Plant presently consists of ten, nonsafety-related subsystems located in the Nuclear Island (NI) and Energy Conversion Area (ECA) of the plant.

  13. Fault Diagnosis in HVAC Chillers

    NASA Technical Reports Server (NTRS)

    Choi, Kihoon; Namuru, Setu M.; Azam, Mohammad S.; Luo, Jianhui; Pattipati, Krishna R.; Patterson-Hine, Ann

    2005-01-01

    Modern buildings are being equipped with increasingly sophisticated power and control systems with substantial capabilities for monitoring and controlling the amenities. Operational problems associated with heating, ventilation, and air-conditioning (HVAC) systems plague many commercial buildings, often the result of degraded equipment, failed sensors, improper installation, poor maintenance, and improperly implemented controls. Most existing HVAC fault-diagnostic schemes are based on analytical models and knowledge bases. These schemes are adequate for generic systems. However, real-world systems significantly differ from the generic ones and necessitate modifications of the models and/or customization of the standard knowledge bases, which can be labor intensive. Data-driven techniques for fault detection and isolation (FDI) have a close relationship with pattern recognition, wherein one seeks to categorize the input-output data into normal or faulty classes. Owing to the simplicity and adaptability, customization of a data-driven FDI approach does not require in-depth knowledge of the HVAC system. It enables the building system operators to improve energy efficiency and maintain the desired comfort level at a reduced cost. In this article, we consider a data-driven approach for FDI of chillers in HVAC systems. To diagnose the faults of interest in the chiller, we employ multiway dynamic principal component analysis (MPCA), multiway partial least squares (MPLS), and support vector machines (SVMs). The simulation of a chiller under various fault conditions is conducted using a standard chiller simulator from the American Society of Heating, Refrigerating, and Air-conditioning Engineers (ASHRAE). We validated our FDI scheme using experimental data obtained from different types of chiller faults.

  14. 19. Interior view of HVAC room in Components Test Laboratory ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    19. Interior view of HVAC room in Components Test Laboratory (T-27), looking toward east wall. Photograph shows upgraded instrumentation, machinery, and technological modifications for HVAC system installed in 1997-99 to accommodate component testing requirements for the Atlas V missile. - Air Force Plant PJKS, Systems Integration Laboratory, Components Test Laboratory, Waterton Canyon Road & Colorado Highway 121, Lakewood, Jefferson County, CO

  15. 18. Interior view of HVAC room in Components Test Laboratory ...

    Library of Congress Historic Buildings Survey, Historic Engineering Record, Historic Landscapes Survey

    18. Interior view of HVAC room in Components Test Laboratory (T-27), showing northwest corner. Photograph shows upgraded instrumentation, piping, and technological modifications for HVAC system installed in 1997-99 to accommodate component testing requirements for the Atlas V missile. - Air Force Plant PJKS, Systems Integration Laboratory, Components Test Laboratory, Waterton Canyon Road & Colorado Highway 121, Lakewood, Jefferson County, CO

  16. Design Concepts for Optimum Energy Use in HVAC Systems.

    ERIC Educational Resources Information Center

    Electric Energy Association, New York, NY.

    Much of the innovative work in the design and application of heating, ventilating, and air conditioning (HVAC) systems is concentrated on improving the cost effectiveness of such systems through optimizing energy use. One approach to the problem is to reduce a building's HVAC energy demands by designing it for lower heat gains and losses in the…

  17. RECOMMENDED HVAC STANDARD OF THE FLORIDA RADON RESEARCH PROGRAM

    EPA Science Inventory

    The report contains the recommended language for the heating, ventilation, and air conditioning (HVAC) section of the "Florida Code for Radon-resistant Construction and Mitigation." t deals with elements of construction that relate to the HVAC of houses. ts primary intent is to p...

  18. RECOMMENDED HVAC STANDARDS OF THE FLORIDA RADON RESEARCH PROGRAM

    EPA Science Inventory

    The report contains the recommended language for the heating, ventilation, and air conditioning (HVAC) section of the "Florida Code for Radon-resistant Construction and Mitigation." t deals with elements of construction that relate to the HVAC of houses. ts primary intent is to p...

  19. Measuring advances in HVAC distribution system designs

    SciTech Connect

    Franconi, Ellen

    1998-07-01

    Substantial commercial building energy savings have been achieved by improving the performance of the HVAC distribution system. The energy savings result from distribution system design improvements, advanced control capabilities, and use of variable-speed motors. Yet, much of the commercial building stock remains equipped with inefficient systems. Contributing to this is the absence of a definition for distribution system efficiency as well as the analysis methods for quantifying performance. This research investigates the application of performance indices to assess design advancements in commercial building thermal distribution systems. The index definitions are based on a first and second law of thermodynamics analysis of the system. The second law or availability analysis enables the determination of the true efficiency of the system. Availability analysis is a convenient way to make system efficiency comparisons since performance is evaluated relative to an ideal process. A TRNSYS simulation model is developed to analyze the performance of two distribution system types, a constant air volume system and a variable air volume system, that serve one floor of a large office building. Performance indices are calculated using the simulation results to compare the performance of the two systems types in several locations. Changes in index values are compared to changes in plant energy, costs, and carbon emissions to explore the ability of the indices to estimate these quantities.

  20. Self-Correcting HVAC Controls Project Final Report

    SciTech Connect

    Fernandez, Nicholas; Brambley, Michael R.; Katipamula, Srinivas; Cho, Heejin; Goddard, James K.; Dinh, Liem H.

    2010-01-04

    This document represents the final project report for the Self-Correcting Heating, Ventilating and Air-Conditioning (HVAC) Controls Project jointly funded by Bonneville Power Administration (BPA) and the U.S. Department of Energy (DOE) Building Technologies Program (BTP). The project, initiated in October 2008, focused on exploratory initial development of self-correcting controls for selected HVAC components in air handlers. This report, along with the companion report documenting the algorithms developed, Self-Correcting HVAC Controls: Algorithms for Sensors and Dampers in Air-Handling Units (Fernandez et al. 2009), document the work performed and results of this project.

  1. Indoor air quality impacts of residential hvac systems phase II.B report: IAQ control retrofit simulations and analysis

    SciTech Connect

    Emmerich, S.J.; Persily, A.K.

    1995-09-01

    The National Institute of Standards and Technology (NIST) performed a preliminary study of the potential for using central forced-air heating and cooling system modifications to control indoor air quality (IAQ) in residential buildings. The objective of this effort was to provide insight into the use of state-of-the-art IAQ models to evaluate such modifications, the potential of these modifications to mitigate residential IAQ problems, the pollutant sources they are most likely to impact, and their potential limitations. This study was not intended to determine definitively whether the IAQ control options studied are reliable and cost-effective. The report summarizes the results on Phase II.B of this project, which consisted of three main efforts: computer simulations of contaminant levels with IAQ control retrofits, evaluation of the effectiveness of the IAQ control retrofits, and development of recommendations for future research.

  2. Residential and Light Commercial HVAC. Teacher Edition.

    ERIC Educational Resources Information Center

    Stephenson, David; Fulkerson, Dan, Ed.

    This curriculum guide contains 18 units of instruction for a competency-based course in residential and light commercial heating, ventilating, and air conditioning (HVAC). Introductory materials include a competency profile and an instructional/task analysis that correlates job training with related information for this course. Each instructional…

  3. HVAC systems and energy conservation in hotels

    SciTech Connect

    Wagner, J.R.

    1986-01-01

    This paper discusses the effect that the design of the basic HVAC has on the relative success of energy conservation efforts in hotels. The unusual nature of a hotel is explained along with the impact that it has on the HVAC system. The paper stresses the practical considerations which must be made by the HVAC system designer when he designs the guest rooms, public areas, back-of-the-house areas, temperature control system, and energy management system. The advantages of providing separate air-handling systems are presented. The benefits of line voltage electric controls for guest room fan coil units are explained. General recommendations for arrangement of ventilation systems and possible opportunities for heat recovery are included.

  4. Strategy Guideline. Transitioning HVAC Companies to Whole House Performance Contractors

    SciTech Connect

    Burdick, Arlan

    2012-05-01

    This report describes the findings from research IBACOS conducted related to heating, ventilation, and air conditioning (HVAC) companies who have made the decision to transition to whole house performance contracting (WHPC).

  5. Strategy Guideline: Transitioning HVAC Companies to Whole House Performance Contractors

    SciTech Connect

    Burdick, A.

    2012-05-01

    This report describes the findings from research IBACOS conducted related to heating, ventilation, and air conditioning (HVAC) companies who have made the decision to transition to whole house performance contracting (WHPC).

  6. Implementation of PFC (Predictive Functional Control) in a PLC (Programmable Logic Controller) for a HVAC (Heating, Ventilation and Air Conditioning) system

    NASA Astrophysics Data System (ADS)

    Kreutz, M.; Richalet, J.; Mocha, K.; Haber, R.

    2014-12-01

    HVAC systems of industrial buildings consume a lot of energy. Therefore it is important to know the performance of these systems and strategies to optimize the hardware and the control. Tackling the temperature control of the HVAC system promises quick savings by tuning the control within specified tolerance limits, which mostly can be done by low investment. This paper mainly deals with the implementation strategy of a new controller in a PLC using the predictive functional control for temperature control. The different stages of the implementation from the simulation over the SCL code till to the real-time operation are presented. A bumpless switch between the PI(D) and the PFC control was realized, as well.

  7. Considerations to Prevent Growth and Spread of Legionella in HVAC Systems.

    ERIC Educational Resources Information Center

    Coleman, Jeff

    1998-01-01

    Discusses the threat posed by the Legionnaire's Disease bacterium and the germ's ability to thrive in heating, ventilating, and air conditioning (HVAC) systems, especially in standing water. Describes ways to minimize disease risk through HVAC system design (such as locating cooling towers away from air intakes) and ways to maintain a clean…

  8. 17th DOE nuclear air cleaning conference: proceedings. Volume 2

    SciTech Connect

    First, M.W.

    1983-02-01

    Volume 2 contains papers presented at the following sessions: adsorption; noble gas treatment; personnel education and training; filtration and filter testing; measurement and instrumentation; air cleaning equipment response to accident related stress; containment venting air cleaning; and an open end session. Twenty-eight papers were indexed separately for inclusion in the Energy Data Base. Ten papers had been entered earlier.

  9. Air Pollution Translations: A Bibliography with Abstracts - Volume 4.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Air Pollution Technical Information Center.

    This volume is the fourth in a series of compilations presenting abstracts and indexes of translations of technical air pollution literature. The entries are grouped into 12 subject categories: Emission Sources, Control Methods, Measurement Methods, Air Quality Measurements, Atmospheric Interaction, Basic Science and Technology, Effects--Human…

  10. HVAC pipe/duct sizing using artificial neural networks

    SciTech Connect

    Yeh, S.J.D.; Wong, K.F.V.

    1995-12-31

    The main objective of this study is to demonstrate that artificial neural networks (ANN`s) serve as useful aids to Heating, Ventilating and Air-Conditioning (HVAC) system design. In the present work, the design process for sizing fluid systems in HVAC is simulated by using ANN`S. Four ANN`s have been constructed in a personal computer, one for air duct sizing and three for pipe sizing. The air duct network was trained to output the friction rate and duct size. The three pipe sizing neural networks product pressure drops and pipe diameters. By using the trained artificial neural networks, data can be obtained instantly with errors less than 3%. Thus, ANN`s have been shown to simplify traditional methods and procedures in HVAC pipe and air duct sizing.

  11. Control strategy optimization of HVAC plants

    SciTech Connect

    Facci, Andrea Luigi; Zanfardino, Antonella; Martini, Fabrizio; Pirozzi, Salvatore; Ubertini, Stefano

    2015-03-10

    In this paper we present a methodology to optimize the operating conditions of heating, ventilation and air conditioning (HVAC) plants to achieve a higher energy efficiency in use. Semi-empiric numerical models of the plant components are used to predict their performances as a function of their set-point and the environmental and occupied space conditions. The optimization is performed through a graph-based algorithm that finds the set-points of the system components that minimize energy consumption and/or energy costs, while matching the user energy demands. The resulting model can be used with systems of almost any complexity, featuring both HVAC components and energy systems, and is sufficiently fast to make it applicable to real-time setting.

  12. Commissioning HVAC systems

    SciTech Connect

    Schiess, K.

    1995-12-01

    In recent years, commissioning has been viewed as a separate process that had to be specified and implemented by a specialized entity. This article discusses commissioning in the HVAC field and looks at it from an international perspective. The author has worked in Europe, South Africa (British system) and the USA. The differences between the British and the American methods of commissioning are discussed, with examples given where the American way was unsuccessful. It is the design engineer`s job to test and accept (commission) an installation after the contractor has demonstrated the performance to the satisfaction of the design engineer. Once the plant is commissioned, it is put into service.

  13. HVAC design for jails

    SciTech Connect

    Gill, K.E. )

    1994-07-01

    The purpose of this article is to provide an overview of the mechanical, life safety, and IAQ issues in current jail HVAC design. The term jail, as used in this article, is more correctly adult local detention facility, as defined by the American Correctional Association (ACA). It will be used to describe those facilities that (1) are operated at the city and county level by local jurisdictions, not state or federal agencies, and (2) are secure for the detention of both pretrial detainees and sentenced inmates serving terms of less than one year or awaiting assignment to state or federal facilities (prisons).

  14. Chapter 19: HVAC Controls (DDC/EMS/BAS) Evaluation Protocol

    SciTech Connect

    Romberger, J.

    2014-11-01

    The HVAC Controls Evaluation Protocol is designed to address evaluation issues for direct digital controls/energy management systems/building automation systems (DDC/EMS/BAS) that are installed to control heating, ventilation, and air-conditioning (HVAC) equipment in commercial and institutional buildings. (This chapter refers to the DDC/EMS/BAS measure as HVAC controls.) This protocol may also be applicable to industrial facilities such as clean rooms and labs, which have either significant HVAC equipment or spaces requiring special environmental conditions. This protocol addresses only HVAC-related equipment and the energy savings estimation methods associated with installing such control systems as an energy efficiency measure. The affected equipment includes: Air-side equipment (air handlers, direct expansion systems, furnaces, other heating- and cooling-related devices, terminal air distribution equipment, and fans); Central plant equipment (chillers, cooling towers, boilers, and pumps). These controls may also operate or affect other end uses, such as lighting, domestic hot water, irrigation systems, and life safety systems such as fire alarms and other security systems. Considerable nonenergy benefits, such as maintenance scheduling, system component troubleshooting, equipment failure alarms, and increased equipment lifetime, may also be associated with these systems. When connected to building utility meters, these systems can also be valuable demand-limiting control tools. However, this protocol does not evaluate any of these additional capabilities and benefits.

  15. Reducing Building HVAC Costs with Site-Recovery Energy

    ERIC Educational Resources Information Center

    Pargeter, Stephen J.

    2012-01-01

    Building owners are caught between two powerful forces--the need to lower energy costs and the need to meet or exceed outdoor air ventilation regulations for occupant health and comfort. Large amounts of energy are wasted each day from commercial, institutional, and government building sites as heating, ventilation, and air conditioning (HVAC)…

  16. Advanced Strategy Guideline. Air Distribution Basics and Duct Design

    SciTech Connect

    Burdick, Arlan

    2011-12-01

    This report discusses considerations for designing an air distribution system for an energy efficient house that requires less air volume to condition the space. Considering the HVAC system early in the design process will allow adequate space for equipment and ductwork and can result in cost savings.

  17. Energy-Smart Choices for Schools. An HVAC Comparison Tool. [CD-ROM].

    ERIC Educational Resources Information Center

    Geothermal Heat Pump Consortium, Inc., Washington, DC.

    A CD ROM program provides comparison construction cost capabilities for heating, ventilation, and air conditioning (HVAC) systems in educational facilities. The program combines multiple types of systems with square footage data on low and high construction cost and school size to automatically calculate HVAC comparative construction costs. (GR)

  18. HVAC SYSTEMS IN THE CURRENT STOCK OF US K-12 SCHOOLS

    EPA Science Inventory

    The report summarizes information on heating, ventilating, an air- conditioning (HVAC) systems commonly found in U. S. school buildings and the effect that operating these systems has on indoor radon levels. The report describes the ability of various HVAC systems to pressurize a...

  19. Air Pollution Translations: A Bibliography with Abstracts - Volume 2.

    ERIC Educational Resources Information Center

    National Air Pollution Control Administration (DHEW), Raleigh, NC.

    This volume is the second in a series of compilations presenting abstracts and indexes of translations of technical air pollution literature. The 444 entries are grouped into 12 subject categories: General; Emission Sources; Atmospheric Interaction; Measurement Methods; Control Methods; Effects--Human Health; Effects--Plants and Livestock;…

  20. Commissioning of HVAC systems

    SciTech Connect

    Schiess, K.

    1995-06-01

    In recent years various presentation and discussions have taken place which looked at commissioning as a separate process that had to be specified and implemented by a specialized entity in a project. This presentation discusses commissioning in the HVAC field and looks at it from an international perspective. The author has worked in Europe, South Africa (British system) and in the USA. The differences are discussed between the British and the American methods with some examples where the American way of commissioning was unsuccessful. The conclusion is that it is the design engineer`s job to test and accept (commission) an installation after the contractor has demonstrated the performance to the satisfaction of the design engineer. Once the plant is commissioned, it is put into service.

  1. Study of lubricant circulation in HVAC systems. Volume 2: Compilation of program test data; Final technical report, March 1995--April 1996

    SciTech Connect

    Biancardi, F.R.; Michels, H.H.; Sienel, T.H.; Pandy, D.R.

    1996-10-01

    This volume contains all of the program test data essentially as taken from the laboratory dynamic test facility during the sequence of runs. For the readers` convenience Table 3.1 from Volume 1 of the report, is included to describe the refrigerant/lubricant test series (six) and the actual chronological test run number. Figures 2.1 and 2.2 from Volume 1 are also included here for reference. In the body of this Volume, each of the test series is presented separately, again for the convenience of the reader. Volume 1 contains a complete description of the program scope, objective, test results summary, conclusions, description of test facility and recommendations for future effort. This reports contains two diagrams of the test facilities and approximately 100 graphs of system performance.

  2. Illinois Occupational Skill Standards: HVAC/R Technician Cluster.

    ERIC Educational Resources Information Center

    Illinois Occupational Skill Standards and Credentialing Council, Carbondale.

    This document, which is intended to serve as a guide for work force preparation program providers, details the Illinois occupational skill standards for programs preparing students for employment in jobs in the heating, ventilation, air conditioning, and refrigeration (HVAC/R) industry. Agency partners involved in this project include: the…

  3. Maximize Benefits, Minimize Risk: Selecting the Right HVAC Firm.

    ERIC Educational Resources Information Center

    Golden, James T.

    1993-01-01

    An informal survey of 20 major urban school districts found that 40% were currently operating in a "break down" maintenance mode. A majority, 57.9%, also indicated they saw considerable benefits in contracting for heating, ventilating, and air conditioning (HVAC) maintenance services with outside firms. Offers guidelines in selecting HVAC…

  4. Active noise control: A tutorial for HVAC designers

    SciTech Connect

    Gelin, L.J.

    1997-08-01

    This article will identify the capabilities and limitations of ANC in its application to HVAC noise control. ANC can be used in ducted HVAC systems to cancel ductborne, low-frequency fan noise by injecting sound waves of equal amplitude and opposite phase into an air duct, as close as possible to the source of the unwanted noise. Destructive interference of the fan noise and injected noise results in sound cancellation. The noise problems that it solves are typically described as rumble, roar or throb, all of which are difficult to address using traditional noise control methods. This article will also contrast the use of active against passive noise control techniques. The main differences between the two noise control measures are acoustic performance, energy consumption, and design flexibility. The article will first present the fundamentals and basic physics of ANC. The application to real HVAC systems will follow.

  5. HIGH VOLUME INJECTION FOR GCMS ANALYSIS OF PARTICULATE ORGANIC SPECIES IN AMBIENT AIR

    EPA Science Inventory

    Detection of organic species in ambient particulate matter typically requires large air sample volumes, frequently achieved by grouping samples into monthly composites. Decreasing the volume of air sample required would allow shorter collection times and more convenient sample c...

  6. Model-based flow rate control for an orfice-type low-volume air sampler

    Technology Transfer Automated Retrieval System (TEKTRAN)

    The standard method of measuring air suspended particulate matter concentration per volume of air consists of continuously drawing a defined volume of air across a filter over an extended period of time, then measuring the mass of the filtered particles and dividing it by the total volume sampled ov...

  7. 1999 NASA Seal/secondary Air System Workshop. Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

    2000-01-01

    NASA Glenn hosted the Seals/Secondary Air System Workshop on October 28-29, 1999. Each year NASA and our industry and university partners share their respective seal technology development. We use these workshops as a technical forum to exchange recent advancements and "lessons-leamed" in advancing seal technology and solving problems of common interest. As in the past we are publishing two volumes. Volume 1 will be publicly available and volume 2 will be restricted under International Traffic and Arms Regulations (I.T.A.R.). The 1999 NASA Seal/Secondary Air System Workshop was divided into four areas; (i) overviews of the government-sponsored gas turbine programs (NASA Ultra Efficient Engine Technology program and DOE Advanced Turbine System program) and the general aviation program (GAP) with emphasis on program goals and seal needs; (ii) turbine engine seal issues from the perspective of an airline customer (i.e., United Airlines), (iii) sealing concepts, methods and results including experimental facilities and numerical predictions; and (iv) reviews of seal requirements for next generation aerospace vehicles (Trailblazer, Bantam and X-38).

  8. Modification of various metals by volume discharge in air atmosphere

    NASA Astrophysics Data System (ADS)

    Shulepov, Mikhail A.; Erofeev, Mikhail V.; Oskomov, Konstantin V.; Tarasenko, Victor F.

    2015-12-01

    The results of the modification of stainless steel, niobium and titanium by volume discharge induced by a beam of runaway electrons in air under normal pressure are presented. Changes in the chemical composition of the surface layers of metal by the action of the discharge, structural changes and changes of hardness were studied. It has been found that the concentration of oxygen and carbon in the surface layers of the samples depend on the number of discharge pulses. The aim of this work is to find possible application of this type of discharge in science and industrial production.

  9. Handbook of environmental chemistry. Volume 4. Part A, air pollution

    SciTech Connect

    Hutzinger, O.

    1986-01-01

    Five authors have each contributed one chapter to this first part (A) of the series on Air Pollution (Volume 4). Thus the book is neither a handbook compilation of reference data nor a text on the subject of air pollution. The first and shortest chapter (22 pages) by A. Wint of the University of Nottingham, England, is an overview called Air Pollution in Perspective. The second chapter, by P. Fabian of Max-Planck-Institute fuer Aeronomie, FRG, is titled Halogenated Hydrocarbons in the Atmosphere. This chapter, in 29 pages, summarizes current data on twenty of these compounds. Hans Guesten of the Institute fuer Radiochemie, Karlsruhe, FRG, contributed chapter 3 on Formation, Transport, and Control of Photochemical Smog (52 pages). This chapter is a good survey of current understanding of smog although each of the three topics promised in the title could by itself take up a good sized book. Atmospheric Distribution of Pollutants and Modeling of Air Pollution Dispersion by H. van Dop of the Royal Netherlands Meteorological Institute, the Netherlands, makes up Chapter 4 (42 pages). The article is written from a meteorological perspective. The last chapter, by J.M. Hales of Battelle Pacific Northwest Laboratories, USA, is titled The Mathematical Characterization of Precipitation Scavenging and Precipitation Chemistry (74 pages). Removal of pollutants from the atmosphere by precipitation is good news/bad news.

  10. Technical Assessment: WRAP 1 HVAC Passive Shutdown

    SciTech Connect

    Ball, D.E.; Nash, C.R.; Stroup, J.L.

    1993-08-12

    As the result of careful interpretation of DOE Order 6430.lA and other DOE Orders, the HVAC system for WRAP 1 has been greatly simplified. The HVAC system is now designed to safely shut down to Passive State if power fails for any reason. The fans cease functioning, allowing the Zone 1 and Zone 2 HVAC Confinement Systems to breathe with respect to atmospheric pressure changes. Simplifying the HVAC system avoided overdesign. Construction costs were reduced by eliminating unnecessary equipment. This report summarizes work that was done to define the criteria, physical concepts, and operational experiences that lead to the passive shutdown design for WRAP 1 confinement HVAC systems.

  11. Novel multi-slit large-volume air sampler.

    PubMed

    Buchanan, L M; Decker, H M; Frisque, D E; Phillips, C R; Dahlgren, C M

    1968-08-01

    Scientific investigators who are interested in the various facets of airborne transmission of disease in research laboratories and hospitals need a simple, continuous, high-volume sampling device that will recover a high percentage of viable microorganisms from the atmosphere. Such a device must sample a large quantity of air. It should effect direct transfer of the air into an all-purpose liquid medium in order to collect bacteria, viruses, rickettsia, and fungi, and it should be easy to use. A simple multi-slit impinger sampler that fulfills these requirements has been developed. It operates at an air-sampling rate of 500 liters/min, has a high collection efficiency, functions at a low pressure drop, and, in contrast to some earlier instruments, does not depend upon electrostatic precipitation at high voltages. When compared to the all-glass impinger, the multi-slit impinger sampler collected microbial aerosols of Serratia marcescens at 82% efficiency, and aerosols of Bacillus subtilis var. niger at 78% efficiency. PMID:4970892

  12. Environmental Technology Verification: Supplement to Test/QA Plan for Biological and Aerosol Testing of General Ventilation Air Cleaners; Bioaerosol Inactivation Efficiency by HVAC In-Duct Ultraviolet Light Air Cleaners

    EPA Science Inventory

    The Air Pollution Control Technology Verification Center has selected general ventilation air cleaners as a technology area. The Generic Verification Protocol for Biological and Aerosol Testing of General Ventilation Air Cleaners is on the Environmental Technology Verification we...

  13. D-Zero HVAC Heat Pump Controls

    SciTech Connect

    Markley, Dan; /Fermilab

    2004-04-14

    This engineering note documents the integration of Dzero Heat Pump 1 through Heat Pump 15 into the cryo/gas process control system commonly referred to as the cryo control system. Heat pumps 1 through 15 control the ambient air temperature on the 3rd, 5th, and 6th floor office areas at Dzero. The entire Johnson HVAC control system was replaced with a Siemens control system in 1999 leaving behind the 15 heat pumps with stand-alone Johnson controllers. Now, these 15 heat pump Johnson controllers are being replaced with small stand alone Beckhoff BC9000 controllers. The Beckhoff BC9000 controllers are network able into the existing Intellution control system. The Beckhoff BC9000 controllers use the cryo private Ethernet network and an OPC driver to get data into the Intellution SCADA node databases. The BC9000 is also programmed over this same Ethernet network.

  14. SURFACE INDUSTRIAL HVAC SYSTEM DESCRIPTION DOCUMENT

    SciTech Connect

    M.M. Ansari

    2005-04-05

    The purpose of this system description document (SDD) is to establish requirements that drive the design of the surface industrial heating, ventilation, and air-conditioning (HVAC) system and its bases to allow the design effort to proceed to license application. This SDD will be revised at strategic points as the design matures. This SDD identifies the requirements and describes the system design, as it currently exists, with emphasis on attributes of the design provided to meet the requirements. This SDD is an engineering tool for design control; accordingly, the primary audience and users are design engineers. This SDD is part of an iterative design process. It leads the design process with regard to the flowdown of upper tier requirements onto the system. Knowledge of these requirements is essential to performing the design process. The SDD follows the design with regard to the description of the system. The description that provided in this SDD reflects the current results of the design process.

  15. Strategy Guideline. Compact Air Distribution Systems

    SciTech Connect

    Burdick, Arlan

    2013-06-01

    This guideline discusses the benefits and challenges of using a compact air distribution system to handle the reduced loads and reduced air volume needed to condition the space within an energy efficient home. The decision criteria for a compact air distribution system must be determined early in the whole-house design process, considering both supply and return air design. However, careful installation of a compact air distribution system can result in lower material costs from smaller equipment, shorter duct runs, and fewer outlets; increased installation efficiencies, including ease of fitting the system into conditioned space; lower loads on a better balanced HVAC system, and overall improved energy efficiency of the home.

  16. Fume hood performance: Face velocity variability inconsistent air volume systems

    SciTech Connect

    Volin, C.E.; Joao, R.V.; Gershey, E.L.; Reiman, J.S.; Party, E.

    1998-09-01

    A 3-year survey of 366 bench-type fume hoods in working laboratories in conventional, constant air volume settings showed that face velocities varied greatly from unit to unit and over time. Fume hoods with bypasses performed better than those without; however, even newly fabricated bypass hoods exhibited large variations. These variations were due to several factors; however, face velocities at 100 {+-} 10 ft/min at working sash heights in the range of 20 to 40 cm (8 to 16 inches) were attainable. The use of smoke showed poor containment, especially at face velocities below 85 ft/min (0.425 m/s) or above 130 ft/min (0.65 m/s) and when the hoods were obstructed by large items placed on the work surface. Auxiliary/supplemental air created unstable face velocities and poor smoke patterns. The analysis of 3 years of fume hood monitoring showed clearly the need for and importance of a maintenance program where the fume hood lower slots are cleaned and fans, ducts, dampers, and hoods are checked periodically.

  17. ANFIS -Based Navigation for HVAC Service Robot with Image Processing

    NASA Astrophysics Data System (ADS)

    Salleh, Mohd Zoolfadli Md; Rashid, Nahrul Khair Alang Md; Mohd Mustafah, Yasir

    2013-12-01

    In this paper, we present an ongoing work on the autonomous navigation of a mobile service robot for Heat, Ventilation and Air Condition (HVAC) ducting. CCD camera mounted on the front-end of our robot is used to analyze the ducts openings (blob analysis) in order to differentiate them from other landmarks (blower fan, air outlets and etc). Distance between the robot and duct openings is measured using ultrasonic sensor. Controller chosen is ANFIS where its architecture accepts three inputs; recognition of duct openings, robot positions and distance while the outputs is maneuver direction (left or right).45 membership functions are created from which produces 46 training epochs. In order to demonstrate the functionality of the system, a working prototype is developed and tested inside HVAC ducting in ROBOCON Lab, IIUM.

  18. Integrated high efficiency blower apparatus for HVAC systems

    DOEpatents

    Liu, Xiaoyue; Weigman, Herman; Wang, Shixiao

    2007-07-24

    An integrated centrifugal blower wheel for a heating, ventilation and air conditioning (HVAC) blower unit includes a first blade support, a second blade support, and a plurality of S-shaped blades disposed between the first and second blade supports, wherein each of the S-shaped blades has a trailing edge bent in a forward direction with respect to a defined direction of rotation of the wheel.

  19. Measuring rates of outdoor airflow into HVAC systems

    SciTech Connect

    Fisk, William J.; Faulkner, David; Sullivan, Douglas P.; Delp, Woody

    2002-10-01

    During the last few years, new technologies have been introduced for measuring the flow rates of outside air into HVAC systems. This document describes one particular technology for measuring these airflows, a system and a related protocol developed to evaluate this and similar measurement technologies under conditions without wind, and the results of our evaluations. We conclude that the measurement technology evaluated can provide a reasonably accurate measurement of OA flow rate over a broad range of flow, without significantly increasing airflow resistance.

  20. Experimental results of a predictive neural network HVAC controller

    SciTech Connect

    Jeannette, E.; Assawamartbunlue, K.; Kreider, J.F.; Curtiss, P.S.

    1998-12-31

    Proportional, integral, and derivative (PID) control is widely used in many HVAC control processes and requires constant attention for optimal control. Artificial neural networks offer the potential for improved control of processes through predictive techniques. This paper introduces and shows experimental results of a predictive neural network (PNN) controller applied to an unstable hot water system in an air-handling unit. Actual laboratory testing of the PNN and PID controllers show favorable results for the PNN controller.

  1. Thermal model of solar absorption HVAC systems

    SciTech Connect

    Bergquam, J.B.; Brezner, J.M. |

    1995-11-01

    This paper presents a thermal model that describes the performance of solar absorption HVAC systems. The model considers the collector array, the building cooling and heating loads, the absorption chiller and the high temperature storage. Heat losses from the storage tank and piping are included in the model. All of the results presented in the paper are for an array of flat plate solar collectors with black chrome (selective surface) absorber plates. The collector efficiency equation is used to calculate the useful heat output from the array. The storage is modeled as a non-stratified tank with polyurethane foam insulation. The system is assumed to operate continuously providing air conditioning during the cooling season, space heating during the winter and hot water throughout the year. The amount of heat required to drive the chiller is determined from the coefficient of performance of the absorption cycle. Results are presented for a typical COP of 0.7. The cooling capacity of the chiller is a function of storage (generator) temperature. The nominal value is 190 F (88 C) and the range of values considered is 180 F (82 C) to 210 F (99 C). Typical building cooling and heating loads are determined as a function of ambient conditions. Performance results are presented for Sacramento, CA and Washington, D.C. The model described in the paper makes use of National Solar Radiation Data Base (NSRDB) data and results are presented for these two locations. The uncertainties in the NSRDB are estimated to be in a range of 6% to 9%. This is a significant improvement over previously available data. The model makes it possible to predict the performance of solar HVAC systems and calculate quantities such as solar fraction, storage temperature, heat losses and parasitic power for every hour of the period for which data are available.

  2. Measuring air layer volumes retained by submerged floating-ferns Salvinia and biomimetic superhydrophobic surfaces.

    PubMed

    Mayser, Matthias J; Bohn, Holger F; Reker, Meike; Barthlott, Wilhelm

    2014-01-01

    Some plants and animals feature superhydrophobic surfaces capable of retaining a layer of air when submerged under water. Long-term air retaining surfaces (Salvinia-effect) are of high interest for biomimetic applications like drag reduction in ship coatings of up to 30%. Here we present a novel method for measuring air volumes and air loss under water. We recorded the buoyancy force of the air layer on leaf surfaces of four different Salvinia species and on one biomimetic surface using a highly sensitive custom made strain gauge force transducer setup. The volume of air held by a surface was quantified by comparing the buoyancy force of the specimen with and then without an air layer. Air volumes retained by the Salvinia-surfaces ranged between 0.15 and 1 L/m(2) depending on differences in surface architecture. We verified the precision of the method by comparing the measured air volumes with theoretical volume calculations and could find a good agreement between both values. In this context we present techniques to calculate air volumes on surfaces with complex microstructures. The introduced method also allows to measure decrease or increase of air layers with high accuracy in real-time to understand dynamic processes. PMID:24991518

  3. Fume hood performance: Using a bypass in variable air volume systems

    SciTech Connect

    Joao, R.V.; Party, E.; Gershey, E.L.

    1998-10-01

    Variable air volume (VAV) exhaust systems provide sophisticated engineering controls for maintaining laboratory ventilation. Depending on how they are installed, they may be very responsive to changes in air flows and air pressures. Some of these changes are a consequence of natural phenomena and some are induced by the transit and actions of laboratory occupants. While the responsiveness of VAV controls can provide tight regulation, the dynamic nature of the VAV system may also introduce undesirable air flow fluctuations. Furthermore, since the volumes of air being exhausted vary, the amount of air available for fume hood capture and containment will also vary. These studies examine the responsiveness and consequences of ventilation system perturbations, as well as the effect of fume hood exhaust being reduced to very low air volumes. Face velocity and air volumes were measured at different sash heights and in response to rapid sash movements. In addition, capture of contaminants was evaluated at different sash heights by American National Standards Institute/American Society of Heating, Refrigerating, and Air-Conditioning Engineers 110-85 tests. The authors have found that at low sash heights the total volume of air may be reduced to a level that is insufficient to efficiently capture airborne contaminants. The addition of a fume hood bypass was necessary to ensure that the volume of air exhausted is sufficient to remove the contaminants present. Understanding the causes and characteristics of fume hood instabilities provides insight into how to prevent these perturbations.

  4. Strategy Guideline: Compact Air Distribution Systems

    SciTech Connect

    Burdick, A.

    2013-06-01

    This Strategy Guideline discusses the benefits and challenges of using a compact air distribution system to handle the reduced loads and reduced air volume needed to condition the space within an energy efficient home. Traditional systems sized by 'rule of thumb' (i.e., 1 ton of cooling per 400 ft2 of floor space) that 'wash' the exterior walls with conditioned air from floor registers cannot provide appropriate air mixing and moisture removal in low-load homes. A compact air distribution system locates the HVAC equipment centrally with shorter ducts run to interior walls, and ceiling supply outlets throw the air toward the exterior walls along the ceiling plane; alternatively, high sidewall supply outlets throw the air toward the exterior walls. Potential drawbacks include resistance from installing contractors or code officials who are unfamiliar with compact air distribution systems, as well as a lack of availability of low-cost high sidewall or ceiling supply outlets to meet the low air volumes with good throw characteristics. The decision criteria for a compact air distribution system must be determined early in the whole-house design process, considering both supply and return air design. However, careful installation of a compact air distribution system can result in lower material costs from smaller equipment, shorter duct runs, and fewer outlets; increased installation efficiencies, including ease of fitting the system into conditioned space; lower loads on a better balanced HVAC system, and overall improved energy efficiency of the home.

  5. Design and tuning of robust PID controller for HVAC systems

    SciTech Connect

    Kasahara, Masato; Matsuba, Tadahiko; Kuzuu, Yoshiaki; Yamazaki, Takanori; Hashimoto, Yukihiro; Kamimura, Kazuyuki; Kurosu, Shigeru

    1999-07-01

    This paper concerns the development of a new design and tuning method for use with robust proportional-plus-integral-plus-derivative (PID) controllers that are commonly used in the heating, ventilating, and air-conditioning (HVAC) fields. The robust PID controller is designed for temperature control of a single-zone environmental space. Although the dynamics of environmental space are described by higher-order transfer functions, most HVAC plants are approximated by first-order lag plus deadtime systems. Its control performance is examined for this commonly approximated controlled plant. Since most HVAC plants are complex with nonlinearity, distributed parameters, and multivariables, a single set of PID gains does not necessarily yield a satisfactory control performance. For this reason, the PID controller must be designed as a robust control system considering model uncertainty caused by changes in characteristics of the plant. The PID gains obtained by solving a two-disk type of mixed sensitivity problem can be modified by contrast to those tuned by the traditional Ziegler-Nichols rule. The results, which are surprisingly simple, are given as linear functions of ratio of deadtime to time constant for robustness. The numerical simulation and the experiments on a commercial-size test plant for air conditioning suggest that the robust PID controller proposed in this paper is effective enough for practical applications.

  6. Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

    SciTech Connect

    Wang, Liping; Hong, Tianzhen

    2013-01-01

    Almost half of the total energy used in the U.S. buildings is consumed by heating, ventilation and air conditionings (HVAC) according to EIA statistics. Among various driving factors to energy performance of building, operations and maintenance play a significant role. Many researches have been done to look at design efficiencies and operational controls for improving energy performance of buildings, but very few study the impacts of HVAC systems maintenance. Different practices of HVAC system maintenance can result in substantial differences in building energy use. If a piece of HVAC equipment is not well maintained, its performance will degrade. If sensors used for control purpose are not calibrated, not only building energy usage could be dramatically increased, but also mechanical systems may not be able to satisfy indoor thermal comfort. Properly maintained HVAC systems can operate efficiently, improve occupant comfort, and prolong equipment service life. In the paper, maintenance practices for HVAC systems are presented based on literature reviews and discussions with HVAC engineers, building operators, facility managers, and commissioning agents. We categorize the maintenance practices into three levels depending on the maintenance effort and coverage: 1) proactive, performance-monitored maintenance; 2) preventive, scheduled maintenance; and 3) reactive, unplanned or no maintenance. A sampled list of maintenance issues, including cooling tower fouling, boiler/chiller fouling, refrigerant over or under charge, temperature sensor offset, outdoor air damper leakage, outdoor air screen blockage, outdoor air damper stuck at fully open position, and dirty filters are investigated in this study using field survey data and detailed simulation models. The energy impacts of both individual maintenance issue and combined scenarios for an office building with central VAV systems and central plant were evaluated by EnergyPlus simulations using three approaches: 1) direct

  7. Neural network based optimal control of HVAC&R systems

    NASA Astrophysics Data System (ADS)

    Ning, Min

    Heating, Ventilation, Air-Conditioning and Refrigeration (HVAC&R) systems have wide applications in providing a desired indoor environment for different types of buildings. It is well acknowledged that 30%-40% of the total energy generated is consumed by buildings and HVAC&R systems alone account for more than 50% of the building energy consumption. Low operational efficiency especially under partial load conditions and poor control are part of reasons for such high energy consumption. To improve energy efficiency, HVAC&R systems should be properly operated to maintain a comfortable and healthy indoor environment under dynamic ambient and indoor conditions with the least energy consumption. This research focuses on the optimal operation of HVAC&R systems. The optimization problem is formulated and solved to find the optimal set points for the chilled water supply temperature, discharge air temperature and AHU (air handling unit) fan static pressure such that the indoor environment is maintained with the least chiller and fan energy consumption. To achieve this objective, a dynamic system model is developed first to simulate the system behavior under different control schemes and operating conditions. The system model is modular in structure, which includes a water-cooled vapor compression chiller model and a two-zone VAV system model. A fuzzy-set based extended transformation approach is then applied to investigate the uncertainties of this model caused by uncertain parameters and the sensitivities of the control inputs with respect to the interested model outputs. A multi-layer feed forward neural network is constructed and trained in unsupervised mode to minimize the cost function which is comprised of overall energy cost and penalty cost when one or more constraints are violated. After training, the network is implemented as a supervisory controller to compute the optimal settings for the system. In order to implement the optimal set points predicted by the

  8. Imaging air volume fraction in sea ice using non-destructive X-ray tomography

    NASA Astrophysics Data System (ADS)

    Crabeck, Odile; Galley, Ryan; Delille, Bruno; Else, Brent; Geilfus, Nicolas-Xavier; Lemes, Marcos; Des Roches, Mathieu; Francus, Pierre; Tison, Jean-Louis; Rysgaard, Søren

    2016-05-01

    Although the presence of a gas phase in sea ice creates the potential for gas exchange with the atmosphere, the distribution of gas bubbles and transport of gases within the sea ice are still poorly understood. Currently no straightforward technique exists to measure the vertical distribution of air volume fraction in sea ice. Here, we present a new fast and non-destructive X-ray computed tomography technique to quantify the air volume fraction and produce separate images of air volume inclusions in sea ice. The technique was performed on relatively thin (4-22 cm) sea ice collected from an experimental ice tank. While most of the internal layers showed air volume fractions < 2 %, the ice-air interface (top 2 cm) systematically showed values up to 5 %. We suggest that the air volume fraction is a function of both the bulk ice gas saturation factor and the brine volume fraction. We differentiate micro bubbles (Ø < 1 mm), large bubbles (1 mm < Ø < 5 mm) and macro bubbles (Ø > 5 mm). While micro bubbles were the most abundant type of gas bubbles, most of the air porosity observed resulted from the presence of large and macro bubbles. The ice texture (granular and columnar) as well as the permeability state of ice are important factors controlling the air volume fraction. The technique developed is suited for studies related to gas transport and bubble migration.

  9. Field Operations and Enforcement Manual for Air Pollution Control. Volume I: Organization and Basic Procedures.

    ERIC Educational Resources Information Center

    Weisburd, Melvin I.

    The Field Operations and Enforcement Manual for Air Pollution Control, Volume I, explains in detail the following: sources and classification of pollutants; meteorological influence on air quality; the air pollution control agency; the field enforcement officer; the enforcement process; prosecuting violation; and inspection techniques including…

  10. Non-Intrusive Load Monitoring of HVAC Components using Signal Unmixing

    SciTech Connect

    Rahimpour, Alireza; Qi, Hairong; Fugate, David L; Kuruganti, Teja

    2015-01-01

    Heating, Ventilating and Air Conditioning units (HVAC) are a major electrical energy consumer in buildings. Monitoring of the operation and energy consumption of HVAC would increase the awareness of building owners and maintenance service providers of the condition and quality of performance of these units, enabling conditioned-based maintenance which would help achieving higher energy efficiency. In this paper, a novel non-intrusive load monitoring method based on group constrained non-negative matrix factorization is proposed for monitoring the different components of HVAC unit by only measuring the whole building aggregated power signal. At the first level of this hierarchical approach, power consumption of the building is decomposed to energy consumption of the HVAC unit and all the other electrical devices operating in the building such as lighting and plug loads. Then, the estimated power signal of the HVAC is used for estimating the power consumption profile of the HVAC major electrical loads such as compressors, condenser fans and indoor blower. Experiments conducted on real data collected from a building testbed maintained at the Oak Ridge National Laboratory (ORNL) demonstrate high accuracy on the disaggregation task.

  11. An Evaluation of the HVAC Load Potential for Providing Load Balancing Service

    SciTech Connect

    Lu, Ning

    2012-09-30

    This paper investigates the potential of providing aggregated intra-hour load balancing services using heating, ventilating, and air-conditioning (HVAC) systems. A direct-load control algorithm is presented. A temperature-priority-list method is used to dispatch the HVAC loads optimally to maintain consumer-desired indoor temperatures and load diversity. Realistic intra-hour load balancing signals were used to evaluate the operational characteristics of the HVAC load under different outdoor temperature profiles and different indoor temperature settings. The number of HVAC units needed is also investigated. Modeling results suggest that the number of HVACs needed to provide a {+-}1-MW load balancing service 24 hours a day varies significantly with baseline settings, high and low temperature settings, and the outdoor temperatures. The results demonstrate that the intra-hour load balancing service provided by HVAC loads meet the performance requirements and can become a major source of revenue for load-serving entities where the smart grid infrastructure enables direct load control over the HAVC loads.

  12. Case study field evaluation of a systems approach to retrofitting a residential HVAC system

    SciTech Connect

    Walker, Iain S.; McWiliams, Jennifer A.; Konopacki, Steven J.

    2003-09-01

    This case study focusing on a residence in northern California was undertaken as a demonstration of the potential of a systems approach to HVAC retrofits. The systems approach means that other retrofits that can affect the HVAC system are also considered. For example, added building envelope insulation reduces building loads so that smaller capacity HVAC system can be used. Secondly, we wanted to examine the practical issues and interactions with contractors and code officials required to accomplish the systems approach because it represents a departure from current practice. We identified problems in the processes of communication and installation of the retrofit that led to compromises in the final energy efficiency of the HVAC system. These issues must be overcome in order for HVAC retrofits to deliver the increased performance that they promise. The experience gained in this case study was used to optimize best practices guidelines for contractors (Walker 2003) that include building diagnostics and checklists as tools to assist in ensuring the energy efficiency of ''house as a system'' HVAC retrofits. The best practices guidelines proved to be an excellent tool for evaluating the eight existing homes in this study, and we received positive feedback from many potential users who reviewed and used them. In addition, we were able to substantially improve the energy efficiency of the retrofitted case study house by adding envelope insulation, a more efficient furnace and air conditioner, an economizer and by reducing duct leakage.

  13. RADON MITIGATION IN SCHOOLS: HVAC SYSTEMS IN SCHOOLS TEND TO HAVE A GREATER IMPACT ON RADON LEVELS THAN HVAC SYSTEMS IN HOMES

    EPA Science Inventory

    The first part of this two-part paper discusses radon entry into schools, radon mitigation approaches for schools, and school characteristics (e.g., heating, ventilation, and air conditioing -- HVAC-- system design and operationg) that influence radon entry and mitigation system ...

  14. RADON MITIGATION IN SCHOOLS: HVAC SYTEMS IN SCHOOLS TEND TO HAVE A GREATER IMPACT ON RADON LEVELS THAN HVAC SYSTEMS IN HOMES

    EPA Science Inventory

    The first part of this two-part paper discusses radon entry into schools, radon mitigation approaches for schools, and school characteristics (e.g., heating, ventilation, and air conditioing -- HVAC-- system design and operationg) that influence radon entry and mitigation system ...

  15. Fouling of HVAC fin and tube heat exchangers

    SciTech Connect

    Siegel, Jeffrey; Carey, Van P.

    2001-07-01

    Fin and tube heat exchangers are used widely in residential, commercial and industrial HVAC applications. Invariably, indoor and outdoor air contaminants foul these heat exchangers. This fouling can cause decreased capacity and efficiency of the HVAC equipment as well as indoor air quality problems related to microbiological growth. This paper describes laboratory studies to investigate the mechanisms that cause fouling. The laboratory experiments involve subjecting a 4.7 fins/cm (12 fins/inch) fin and tube heat exchanger to an air stream that contains monodisperse particles. Air velocities ranging from 1.5-5.2 m/s (295 ft/min-1024 ft/min) and particle sizes from 1--8.6 {micro}m are used. The measured fraction of particles that deposit as well as information about the location of the deposited material indicate that particles greater than about 1 {micro}m contribute to fouling. These experimental results are used to validate a scaling analysis that describes the relative importance of several deposition mechanisms including impaction, Brownian diffusion, turbophoresis, thermophoresis, diffusiophoresis, and gravitational settling. The analysis is extended to apply to different fin spacings and particle sizes typical of those found in indoor air.

  16. Advanced Strategy Guideline: Air Distribution Basics and Duct Design

    SciTech Connect

    Burdick, A.

    2011-12-01

    This report discusses considerations for designing an air distribution system for an energy efficient house that requires less air volume to condition the space. Considering the HVAC system early in the design process will allow adequate space for equipment and ductwork and can result in cost savings. Principles discussed that will maximize occupant comfort include delivery of the proper amount of conditioned air for appropriate temperature mixing and uniformity without drafts, minimization of system noise, the impacts of pressure loss, efficient return air duct design, and supply air outlet placement, as well as duct layout, materials, and sizing.

  17. Application of a dry-gas meter for measuring air sample volumes in an ambient air monitoring network

    SciTech Connect

    Fritz, Brad G.

    2009-05-24

    Ambient air monitoring for non-research applications (e.g. compliance) occurs at locations throughout the world. Often, the air sampling systems employed for these purposes employee simple yet robust equipment capable of handling the rigors of demanding sampling schedules. At the Hanford Site (near Richland, Washington) concentrations of radionuclides in ambient air are monitored continuously at 44 locations. In 2004, mechanical dry-gas meters were incorporated into the Hanford Site ambient air sample collection system to allow the direct measurement of sample volumes. These meters replaced a portable airflow measurement system that required two manual flow measurements and a sample duration measurement to determine sample volume. A six-month evaluation of the dry-gas meters compared sample volumes calculated using the original flow rate method to the direct sample volume measurement (new method). The results of the evaluation indicate that use of the dry-gas meters result in accurate sample volume measurements and provide greater confidence in the measured sample volumes. In several years of in-network use, the meters have proven to be reliable and have resulted in an improved sampling system.

  18. APEX (Air Pollution Exercise) Volume 4: City Politicians' Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The City Politicians' Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  19. APEX (Air Pollution Exercise) Volume 14; Developer's Manual No. 4.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 4 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  20. APEX (Air Pollution Exercise) Volume 1: Game Director's Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Game Director's Manual is the first in a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The participants, which may range in number from 18 to…

  1. APEX (Air Pollution Exercise) Volume 19: County Planner's Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The County Planner's Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  2. APEX (Air Pollution Exercise) Volume 17: Developer's Manual No. 7.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 7 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  3. APEX (Air Pollution Exercise) Volume 2: Computer Operator's Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Computer Operator's Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The information in the manual is sufficiently basic…

  4. APEX (Air Pollution Exercise) Volume 11: Developer's Manual No. 1.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 1 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  5. APEX (Air Pollution Exercise) Volume 13: Developer's Manual No. 3.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 3 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  6. APEX (Air Pollution Exercise) Volume 12: Developer's Manual No. 2.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 2 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  7. APEX (Air Pollution Exercise) Volume 16: Developer's Manual No. 6.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 6 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  8. APEX (Air Pollution Exercise) Volume 15: Developer's Manual No. 5.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Developer's Manual No. 5 is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two section, which are the same in each of…

  9. APEX (Air Pollution Exercise) Volume 18: City Planner's Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The City Planner's Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each of…

  10. APEX (Air Pollution Exercise) Volume 5: County Politicians' Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The County Politicians' Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections, which are the same in each…

  11. APEX (Air Pollution Exercise) Volume 20: Reference Materials.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Reference Materials Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. For the purposes of the gaming exercise, APEX…

  12. Towards energy efficient operation of Heating, Ventilation and Air Conditioning systems via advanced supervisory control design

    NASA Astrophysics Data System (ADS)

    Oswiecinska, A.; Hibbs, J.; Zajic, I.; Burnham, K. J.

    2015-11-01

    This paper presents conceptual control solution for reliable and energy efficient operation of heating, ventilation and air conditioning (HVAC) systems used in large volume building applications, e.g. warehouse facilities or exhibition centres. Advanced two-level scalable control solution, designed to extend capabilities of the existing low-level control strategies via remote internet connection, is presented. The high-level, supervisory controller is based on Model Predictive Control (MPC) architecture, which is the state-of-the-art for indoor climate control systems. The innovative approach benefits from using passive heating and cooling control strategies for reducing the HVAC system operational costs, while ensuring that required environmental conditions are met.

  13. Microbiological Evaluation of a Large-Volume Air Incinerator

    PubMed Central

    Barbeito, Manuel S.; Taylor, Larry A.; Seiders, Reginald W.

    1968-01-01

    Two semiportable metal air incinerators, each with a capacity of 1,000 to 2,200 standard ft3 of air per min, were constructed to sterilize infectious aerosols created for investigative work in a microbiological laboratory. Each unit has about the same air-handling capacity as a conventional air incinerator with a brick stack but costs only about one-third as much. The units are unique in that the burner housing and combustion chamber are air-tight and utilize a portion of the contaminated air stream to support combustion of fuel oil. Operation is continuous. Aerosols of liquid and dry suspensions of Bacillus subtilis var. niger spores and dry vegetative cells of Serratia marcescens were disseminated into the two incinerators to determine the conditions required for sterilization of contaminated air. With the latter organisms (concentration 2.03 × 107 cells/ft3 of air), a temperature of 525 F (274 C), measured at the firebox in front of the heat exchanger, was sufficient for sterilization. To sterilize 1.74 × 107 and 1.74 × 109 wet spores of B. subtilis per ft3, the required temperature ranged from 525 to 675 F (274 to 357 C) and 625 to 700 F (329 to 371 C), respectively. Air-sterilization temperature varied with each incinerator. This was because of innate differences of fabrication, different spore concentrations, and use of one or two burners With dry B. subtilis spores (1.86 × 108/ft3), a temperature of 700 F was required for sterilization. With dry spores, no difference was noted in the sterilization temperature for the two incinerators. PMID:4967758

  14. HVAC design considerations for cold climates

    SciTech Connect

    Armstrong, R.S. )

    1993-09-01

    The design of heating, ventilating and air-conditioning (HVAC) systems in cold climate areas requires modifications to the standard designs used in more temperate climates. While most of the US experiences freezing temperatures at least once during the winter months, certain areas experience several months of extended cold. No single location in the US experiences these extended cold conditions more than Alaska. While most areas in the continental US will not require modifications to standard design guidelines, many design modifications commonly used in the Arctic regions of Alaska and Canada can also be applied to any cold climate area in the continental US. The geographic area of Alaska is about one-third the size of the continental US. Climatic extremes range from Ketchikan with 6.697 heating degree days (at 55[degree]21 minutes N latitude) to Barrow with 20,341 heating degree days (at 71[degree]18 minutes N latitude), according to the Arctic Environmental Information and Data Center. The suggestions in this article are a compilation of general approaches the authors used to address the challenge of cold climate design. Of course, each detail design must be adapted to the specific climate and application at hand.

  15. Pumping glycol solutions in the HVAC industry

    SciTech Connect

    Rishel, J.B.; Schlachter, J.P.

    1997-12-31

    Ethylene and propylene glycols are used in heating, ventilating, and airconditioning (HVAC) water systems for operations that can occur below the freezing point of pure water. Typical applications are for generating ice storage and preventing freezing in coils that are exposed to outside air. The type of glycol and the percentage of solution to be used are decisions that are made by the designer of the water system utilizing the glycols. The purpose of this paper is to (1) present the basic procedures required for the selection of piping and pumps for the glycol that has been selected for a particular water system and (2) to demonstrate the effect that the specific gravity and the viscosity of the glycol solution can have on pipe friction and pump performance. Although much of this information has been presented in other ASHRAE technical documents, it is repeated here in the hopes that a relatively simple procedure will be provided for determining the effect of glycol solution viscosity and specific gravity upon piping design and pump operation. A brief review will be made of a glycol`s characteristics followed by the procedures for calculation of piping friction for a glycol system and computation of pump performance. Review also will be made of the use of variable-speed pumping on glycol systems. All of the information will be based upon ethylene glycol; similar data and calculations could be generated for propylene glycol.

  16. VARIABLE SPEED INTEGRATED INTELLIGENT HVAC BLOWER

    SciTech Connect

    Shixiao Wang; Herman Wiegman; Wilson Wu; John Down; Luana Iorio; Asha Devarajan; Jing Wang; Ralph Carl; Charlie Stephens; Jeannine Jones; Paul Szczesny

    2001-11-14

    This comprehensive topical report discusses the key findings in the development of a intelligent integrated blower for HVAC applications. The benefits of rearward inclined blades over that of traditional forward inclined blades is well documented and a prototype blower design is presented. A comparison of the proposed blower to that of three typical units from the industry is presented. The design of the blower housing is also addressed and the impact of size limitations on static efficiency is discussed. Issues of air flow controllability in the rearward inclined blower is addressed and a solution to this problem is proposed. Several motor design options are discussed including inside-out radial flux designs and novel axial flux designs, all are focused on the various blower needs. The control of the motor-blower and airflow through the use of a high density inverter stage and modern digital signal processor is presented. The key technical challenges of the approach are discussed. The use of the motor as a sensor in the larger heating/ventilating system is also discussed. Diagnostic results for both the motor itself and the blower system are presented.

  17. Journal of Air Transportation, Volume 12, No. 1

    NASA Technical Reports Server (NTRS)

    Bowers, Brent D. (Editor); Kabashkin, Igor (Editor)

    2007-01-01

    Topics discussed include: a) Data Mining Methods Applied to Flight Operations Quality Assurance Data: A Comparison to Standard Statistical Methods; b) Financial Comparisons across Different Business Models in the Canadian Airline Industry; c) Carving a Niche for the "No-Frills" Carrier, Air Arabia, in Oil-Rich Skies; d) Situational Leadership in Air Traffic Control; and e) The Very Light Jet Arrives: Stakeholders and Their Perceptions.

  18. Particle impactor assembly for size selective high volume air sampler

    DOEpatents

    Langer, Gerhard

    1988-08-16

    Air containing entrained particulate matter is directed through a plurality of parallel, narrow, vertically oriented impactor slots of an inlet element toward an adjacently located, relatively large, dust impaction surface preferably covered with an adhesive material. The air flow turns over the impaction surface, leaving behind the relatively larger particles according to the human thoracic separation system and passes through two elongate exhaust apertures defining the outer bounds of the impaction collection surface to pass through divergent passages which slow down and distribute the air flow, with entrained smaller particles, over a fine filter element that separates the fine particles from the air. The elongate exhaust apertures defining the impaction collection surface are spaced apart by a distance greater than the lengths of elongate impactor slots in the inlet element and are oriented to be normal thereto. By appropriate selection of dimensions and the number of impactor slots air flow through the inlet element is provided a nonuniform velocity distribution with the lower velocities being obtained near the center of the impactor slots, in order to separate out particles larger than a certain predetermined size on the impaction collection surface. The impaction collection surface, even in a moderately sized apparatus, is thus relatively large and permits the prolonged sampling of air for periods extending to four weeks.

  19. Cargo Logistics Airlift Systems Study (CLASS). Volume 1: Analysis of current air cargo system

    NASA Technical Reports Server (NTRS)

    Burby, R. J.; Kuhlman, W. H.

    1978-01-01

    The material presented in this volume is classified into the following sections; (1) analysis of current routes; (2) air eligibility criteria; (3) current direct support infrastructure; (4) comparative mode analysis; (5) political and economic factors; and (6) future potential market areas. An effort was made to keep the observations and findings relating to the current systems as objective as possible in order not to bias the analysis of future air cargo operations reported in Volume 3 of the CLASS final report.

  20. Construction manager steers school`s HVAC retrofit

    SciTech Connect

    Hill, W.; Teyema, B.R.

    1995-11-01

    This article reports on an air conditioning retrofit for 300,000 sq ft school that will include 900 tons of cooling using custom-built mechanical penthouses with DX cooling. New Trier High School located near Lake Michigan in the Chicago Northshore suburb of Winnetka, IL, is a 75-year-old landmark building. The school has long had a reputation for academic excellence. A two-year renovation project is currently underway to install a modern HVAC system and new lighting that will improve the indoor environment, thereby enhancing the overall learning environment.

  1. Mexico City Air Quality Research Initiative; Volume 5, Strategic evaluation

    SciTech Connect

    1994-03-01

    Members of the Task HI (Strategic Evaluation) team were responsible for the development of a methodology to evaluate policies designed to alleviate air pollution in Mexico City. This methodology utilizes information from various reports that examined ways to reduce pollutant emissions, results from models that calculate the improvement in air quality due to a reduction in pollutant emissions, and the opinions of experts as to the requirements and trade-offs that are involved in developing a program to address the air pollution problem in Mexico City. The methodology combines these data to produce comparisons between different approaches to improving Mexico City`s air quality. These comparisons take into account not only objective factors such as the air quality improvement or cost of the different approaches, but also subjective factors such as public acceptance or political attractiveness of the different approaches. The end result of the process is a ranking of the different approaches and, more importantly, the process provides insights into the implications of implementing a particular approach or policy.

  2. Air Force Russian: Aural Comprehension Course. Volume XXI, Lessons 92-95.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  3. Air Force Russian: Aural Comprehension Course. Volume XIX, Lessons 84-87.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  4. Air Force Russian: Aural Comprehension Course. Volume XXIV, Lessons 104-111.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force Students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  5. Air Force Russian: Aural Comprehension Course. Volume XXII, Lessons 96-99.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  6. Air Force Russian: Aural Comprehension Course. Volume XXVI, Lessons 120-133.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  7. Air Force Russian: Aural Comprehension Course. Volume XXIII, Lessons 100-103.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  8. Air Force Russian: Aural Comprehension Course. Volume XX, Lessons 88-91.

    ERIC Educational Resources Information Center

    Defense Language Inst., Washington, DC.

    This volume is one of a series in an intensive audiolingual course in Russian designed for Air Force students. The course, consisting of 133 lessons in 26 volumes and taught in 37 weeks, seeks to train native English language speakers to a level 3 proficiency in comprehension and a level 2 proficiency in speaking, reading, and writing. Tapes are…

  9. REGIONAL AIR POLLUTION STUDY. HIGH VOLUME FILTER MEASUREMENTS OF SUSPENDED PARTICULATE MATTER

    EPA Science Inventory

    Ten of the 25 stations making up the Regional Air Monitoring System were equipped with dichotomous samplers and high volume filter samplers for aerosol measurements. The high volume samplers collected samples every third day for 24-hour periods (0000-2400). Sample filters were re...

  10. IAQPC: INDOOR AIR QUALITY SIMULATOR FOR PERSONAL COMPUTERS: VOLUME 1. TECHNICAL MANUAL

    EPA Science Inventory

    The two-volume report describes the development of an indoor air quality simulator for personal computers (IAQPC), a program that addresses the problems of indoor air contamination. The program-- systematic, user-friendly, and computer-based--can be used by administrators and eng...

  11. IAQPC: INDOOR AIR QUALITY SIMULATOR FOR PERSONAL COMPUTERS: VOLUME 2. USER'S GUIDE

    EPA Science Inventory

    The two-volume report describes the development of an indoor air quality simulator for personal computers (IAQPC), a program that addresses the problems of indoor air contamination. The program-- systematic, user-friendly, and computer-based--can be used by administrators and eng...

  12. Journal of Air Transportation, Volume 11, No. 3

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Kabashkin, Igor (Editor); Fink, Mary (Editor)

    2007-01-01

    The mission of the Journal of Air Transportation (JAT) is to provide the global community immediate key resource information in all areas of air transportation. The goal of the Journal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JAT will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy

  13. Journal of Air Transportation, Volume 10, No. 2

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Unal, Mehmet (Editor); Gudmundsson, Sveinn Vidar (Editor); Kabashkin, Igor (Editor)

    2005-01-01

    Topics discussed include: Mitigation Alternatives for Carbon Dioxide Emissions by the Air Transport Industry in Brazil; Air Transport Regulation Under Transformation: The Case of Switzerland; An Estimation of Aircraft Emissions at Turkish Airports; Guide to the Implementation of Iso 14401 at Airports; The Impact of Constrained Future Scenarios on Aviation and Emissions; The Immediate Financial Impact of Transportation Deregulation on the Stockholders of the Airline Industry; Aviation Related Airport Marketing in an Overlapping Metropolitan Catchment Area: The Case of Milan's Three Airports; and Airport Pricing Systems and Airport Deregulation Effects on Welfare.

  14. Journal of Air Transportation; Volume 9, No. 3

    NASA Technical Reports Server (NTRS)

    Bowen, Brent D. (Editor); Kabashkin, Igor (Editor)

    2004-01-01

    The mission of the Journal of Air Transportation (JAT) is to provide the global community immediate key resource information in all areas of air transportation. The goal of the Journal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JAT will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

  15. Journal of Air Transportation, Volume 10, No. 1

    NASA Technical Reports Server (NTRS)

    Bowen, Brent D. (Editor); Kabashkin, Igor (Editor); Lucas, Sarah (Editor); Scarpellini-Metz, Nanette (Editor)

    2005-01-01

    The mission of the Journal of Air Transportation (JA is to provide the global community immediate key resource information in all areas of air transportation. The goal of the Journal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JAT will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

  16. Air & Space, Volume 2, Number 4, March-April, 1979.

    ERIC Educational Resources Information Center

    Forbush, Julie, Ed.

    This newsletter, produced by the National Air and Space Museum of the Smithsonian Institution, contains an article on the Apollo 11 spaceflight, an article on hypersonic and supersonic flight which compares the Concorde, the X-15, and the Shuttle Orbiter, an article presenting photographs of the construction of the Shuttle Orbiter, and an article…

  17. An analysis of short haul air passenger demand, volume 2

    NASA Technical Reports Server (NTRS)

    Blumer, T. P.; Swan, W. M.

    1978-01-01

    Several demand models for short haul air travel are proposed and calibrated on pooled data. The models are designed to predict demand and analyze some of the motivating phenomena behind demand generation. In particular, an attempt is made to include the effects of competing modes and of alternate destinations. The results support three conclusions: (1) the auto mode is the air mode's major competitor; (2) trip time is an overriding factor in intermodal competition, with air fare at its present level appearing unimportant to the typical short haul air traveler; and (3) distance appears to underly several demand generating phenomena, and therefore, must be considered very carefully to any intercity demand model. It may be the cause of the wide range of fare elasticities reported by researchers over the past 15 years. A behavioral demand model is proposed and calibrated. It combines the travel generating effects of income and population, the effects of modal split, the sensitivity of travel to price and time, and the effect of alternative destinations satisfying the trip purpose.

  18. METHODS DEVELOPMENT FOR ASSESSING AIR POLLUTION CONTROL BENEFITS. VOLUME I. EXPERIMENTS IN THE ECONOMICS OF AIR POLLUTION EPIDEMIOLOGY

    EPA Science Inventory

    The volume employs the analytical and empirical methods of economics to develop hypotheses on disease etiologies and to value labor productivity and consumer losses due to air pollution-induced mortality and morbidity. In the mortality work, 1970 city-wide mortality rates for maj...

  19. INVESTIGATION OF THE POTENTIAL ANTIMICROBIAL EFFICACY OF SEALANTS USED IN HVAC SYSTEMS: JOURNAL ARTICLE

    EPA Science Inventory

    NRMRL-RTP-P- 530a Foarde, K.K., VanOsdell, D.W., and Menetrez*, M.Y. Investigation of the Potential Antimicrobial Efficacy of Sealants Used in HVAC Systems. Published in: Journal of Air and Waste Management Association 51 (8):1219-1226 (2001). 07/06/2000 The paper gives result...

  20. Residential and Light Commercial HVAC. Teacher Edition and Student Edition. Second Edition.

    ERIC Educational Resources Information Center

    Stephenson, David

    This package contains teacher and student editions of a residential and light commercial heating, ventilation, and air conditioning (HVAC) course of study. The teacher edition contains information on the following: using the publication; national competencies; competency profile; related academic and workplace skills list; tools, equipment, and…

  1. APEX (Air Pollution Exercise) Volume 21: Legal References: Air Pollution Control Regulations.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Legal References: Air Pollution Control Regulations Manual is the last in a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The manual…

  2. APEX (Air Pollution Exercise) Volume 3: Air Pollution Control Officer's Manual.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Air Pollution Control Officer's (APCO) Manual is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise) a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties, The first two sections, which are…

  3. Reduced energy and volume air pump for a seat cushion

    DOEpatents

    Vaughn, Mark R.; Constantineau, Edward J.; Groves, Gordon E.

    1997-01-01

    An efficient pump system for transferring air between sets of bladders in a cushion. The pump system utilizes a reversible piston within a cylinder in conjunction with an equalizing valve in the piston which opens when the piston reaches the end of travel in one direction. The weight of a seated user then forces air back across the piston from an inflated bladder to the previously deflated bladder until the pressure is equalized. In this fashion the work done by the pump is cut in half. The inflation and deflation of the different bladders is controlled to vary the pressure on the several pressure points of a seated user. A principal application is for wheel chair use to prevent pressure ulcers.

  4. Reduced energy and volume air pump for a seat cushion

    DOEpatents

    Vaughn, M.R.; Constantineau, E.J.; Groves, G.E.

    1997-08-19

    An efficient pump system is described for transferring air between sets of bladders in a cushion. The pump system utilizes a reversible piston within a cylinder in conjunction with an equalizing valve in the piston which opens when the piston reaches the end of travel in one direction. The weight of a seated user then forces air back across the piston from an inflated bladder to the previously deflated bladder until the pressure is equalized. In this fashion the work done by the pump is cut in half. The inflation and deflation of the different bladders is controlled to vary the pressure on the several pressure points of a seated user. A principal application is for wheel chair use to prevent pressure ulcers. 12 figs.

  5. NREL Provides Guidance to Improve Air Mixing and Thermal Comfort in Homes (Fact Sheet)

    SciTech Connect

    Not Available

    2012-02-01

    NREL research determines optimal HVAC system design for proper air mixing and thermal comfort in homes. As U.S. homes become more energy efficient, heating, ventilation, and cooling (HVAC) systems will be downsized, and the air flow volumes required to meet heating and cooling loads may be too small to maintain uniform room air mixing-which can affect thermal comfort. Researchers at the National Renewable Energy Laboratory (NREL) evaluated the performance of high sidewall air supply inlets and confirmed that these systems can achieve good air mixing and provide suitable comfort levels for occupants. Using computational fluid dynamics modeling, NREL scientists tested the performance of high sidewall supply air jets over a wide range of parameters including supply air temperature, air velocity, and inlet size. This technique uses the model output to determine how well the supply air mixes with the room air. Thermal comfort is evaluated by monitoring air temperature and velocity in more than 600,000 control volumes that make up the occupied zone of a single room. The room has an acceptable comfort level when more than 70% of the control volumes meet the comfort criteria on both air temperature and velocity. The study shows that high sidewall supply air jets achieve uniform mixing in a room, which is essential for providing acceptable comfort levels. The study also provides information required to optimize overall space conditioning system design in both heating and cooling modes.

  6. Journal of Air Transportation, Volume 11, No. 1

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Kabashkin, Igor (Editor); Fink, Mary (Editor)

    2006-01-01

    Topics covered include: Analysis of System-wide Investment in the National Airspace System: A Portfolio Analytical Framework and an Example; Regional Air Transport in Europe: The Potential Role of the Civil Tiltrotor in Reducing Airside Congestion; The Development of Jomo Kenyatta International Airport as a Regional Aviation Hub; Corporate Social Responsibility in Aviation; The Competitive Effects of Airline Mergers and Acquisitions: More Capital Market Evidence; and The Competitive Position of Hub Airports in the Transatlantic Market.

  7. Energy Savings Potential and RD&D Opportunities for Non-Vapor-Compression HVAC Technologies

    SciTech Connect

    none,

    2014-03-01

    While vapor-compression technologies have served heating, ventilation, and air-conditioning (HVAC) needs very effectively, and have been the dominant HVAC technology for close to 100 years, the conventional refrigerants used in vapor-compression equipment contribute to global climate change when released to the atmosphere. This Building Technologies Office report: --Identifies alternatives to vapor-compression technology in residential and commercial HVAC applications --Characterizes these technologies based on their technical energy savings potential, development status, non-energy benefits, and other factors affecting end-user acceptance and their ability to compete with conventional vapor-compression systems --Makes specific research, development, and deployment (RD&D) recommendations to support further development of these technologies, should DOE choose to support non-vapor-compression technology further.

  8. Journal of Air Transportation, Volume 11, No. 2

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Kabashkin, Igor (Editor); Gudmundsson, Sveinn Vidar (Editor); EspiritoSanto, Jr. Respicio (Editor)

    2006-01-01

    The following topics were covered: How Do Airlines Perceive That Strategic Alliances Affect Their Individual Branding?; Airline Choice for Domestic Flights in Sao Paulo Metropolitan Area: An Application of the Conditional Logit Model; Consequences of Feeder Delays for the Success of A380 Operations; Inside the Mechanics of Network Development: How Competition and Strategy Reorganize European Air Traffic; The Opportunities and Threats of Turning Airports into Hubs; Another Approach to Enhance Airline Safety: Using System Safety Tools; A Simulation Based Approach for Contingency Planning for Aircraft Turnaround Activities in Airline Hubs; and The Council on Aviation Accreditation: Part One- Historical Foundation.

  9. Journal of Air Transportation, Volume 10, No. 3

    NASA Technical Reports Server (NTRS)

    Bowen, Brent D. (Editor); Kabashkin, Igor (Editor)

    2005-01-01

    The following topics are discussed: The Effects of Safety Information on Aeronautical Decision Making; Design, Development, and Validation of an Interactive Multimedia Training Simulator for Responding to Air Transportation Bomb Threats; Discovering the Regulatory Considerations of the Federal Aviation Administration: Interviewing the Aviation Rulemaking Advisory Committee; How to Control Airline Routes from the Supply Side: The Case of TAP; An Attempt to Measure the Traffic Impact of Airline Alliances; and Study Results on Knowledge Requirements for Entry-level Airport Operations and Management Personnel.

  10. Regional volume changes in canine lungs suspended in air

    NASA Technical Reports Server (NTRS)

    Abbrecht, Peter H.; Kyle, Richard R.; Bryant, Howard J.; Feuerstein, Irwin

    1995-01-01

    The purpose of this study was to determine the effect of the absence of a pleural pressure gradient (simulating the presumed condition found in microgravity) upon regional expansion of the lung. We attempted to produce a uniform pressure over the surface of the lung by suspending excised lungs in air. Such studies should help determine whether or not the absence of a pleural pressure gradient leads to uniform ventilation. A preparation in which there is no pleural pressure gradient should also be useful in studying non-gravitational effects on ventilation distribution.

  11. Electrostatic MEMS vibration energy harvester for HVAC applications

    NASA Astrophysics Data System (ADS)

    Oxaal, J.; Hella, M.; Borca-Tasciuc, D.-A.

    2015-12-01

    This paper reports on an electrostatic MEMS vibration energy harvester with gapclosing interdigitated electrodes, designed for and tested on HVAC air ducts. The device is fabricated on SOI wafers using a custom microfabrication process. A dual-level physical stopper system is implemented in order to control the minimum gap between the electrodes and maximize the power output. It utilizes cantilever beams to absorb a portion of the impact energy as the electrodes approach the impact point, and a film of parylene with nanometer thickness deposited on the electrode sidewalls, which defines the absolute minimum gap and provides electrical insulation. The fabricated device was first tested on a vibration shaker to characterize its resonant behavior. The device exhibits spring hardening behavior due to impacts with the stoppers and spring softening behavior with increasing voltage bias. Testing was carried out on HVAC air duct vibrating with an RMS acceleration of 155 mgRMS and a primary frequency of 60 Hz with a PSD of 7.15·10-2 g2/Hz. The peak power measured is 12nW (0.6 nW RMS) with a PSD of 6.9·10-11 W/Hz at 240 Hz (four times of the primary frequency of 60 Hz), which is the highest output reported for similar vibration conditions and biasing voltages.

  12. Modeling and Measurement Constraints in Fault Diagnostics for HVAC Systems

    SciTech Connect

    Najafi, Massieh; Auslander, David M.; Bartlett, Peter L.; Haves, Philip; Sohn, Michael D.

    2010-05-30

    Many studies have shown that energy savings of five to fifteen percent are achievable in commercial buildings by detecting and correcting building faults, and optimizing building control systems. However, in spite of good progress in developing tools for determining HVAC diagnostics, methods to detect faults in HVAC systems are still generally undeveloped. Most approaches use numerical filtering or parameter estimation methods to compare data from energy meters and building sensors to predictions from mathematical or statistical models. They are effective when models are relatively accurate and data contain few errors. In this paper, we address the case where models are imperfect and data are variable, uncertain, and can contain error. We apply a Bayesian updating approach that is systematic in managing and accounting for most forms of model and data errors. The proposed method uses both knowledge of first principle modeling and empirical results to analyze the system performance within the boundaries defined by practical constraints. We demonstrate the approach by detecting faults in commercial building air handling units. We find that the limitations that exist in air handling unit diagnostics due to practical constraints can generally be effectively addressed through the proposed approach.

  13. Robins Air Force Base solar cogeneration facility, volume 1

    NASA Astrophysics Data System (ADS)

    1981-08-01

    A conceptual design and cost estimate for a demonstration solar facility to generate electricity and deliver process steam to the existing base distribution systems is considered. The solar energy system is a central receiver arrangement. The technical approach to the project and the rationale for selecting the site at Robins Air Force Base are discussed. The evaluation of alternative configurations considered to have potential for improving the facility value is summarized. The solar facility is described, including system level functional requirements, design, operation, performance, cost, safety, environmental, institutional, and regulatory considerations. The design, functional requirements and operating characteristics which influence cost or performance for each subsystem are described. The subsystems are the collector, receiver/tower, master control, electric power generation, and facility steam and feedwater subsystems.

  14. Kitchen HVAC design: What's on the menu

    SciTech Connect

    Gill, K.E. ); Sipila, O.E. )

    1994-10-01

    This article presents an overview of the options available not only in kitchen hood selection but also in the overall design of kitchen HVAC systems. The majority of existing buildings have food services functions, and the production and delivery of these services result in the HVAC engineer's involvement in providing a healthy, comfortable, and productive indoor climate for the kitchen workers. The common denominator of a kitchen is the requirement of a kitchen hood located above the cooking appliances providing containment and exhaust of the products of cooking -- heat, grease, and vapors. The use of food service consultants to select food preparation equipment has, in many cases, resulted in the HVAC engineer no longer selecting the kitchen hood systems but being required to provide ventilation and makeup to hoods selected by others.

  15. Measurement of absolute regional lung air volumes from near-field x-ray speckles.

    PubMed

    Leong, Andrew F T; Paganin, David M; Hooper, Stuart B; Siew, Melissa L; Kitchen, Marcus J

    2013-11-18

    Propagation-based phase contrast x-ray (PBX) imaging yields high contrast images of the lung where airways that overlap in projection coherently scatter the x-rays, giving rise to a speckled intensity due to interference effects. Our previous works have shown that total and regional changes in lung air volumes can be accurately measured from two-dimensional (2D) absorption or phase contrast images when the subject is immersed in a water-filled container. In this paper we demonstrate how the phase contrast speckle patterns can be used to directly measure absolute regional lung air volumes from 2D PBX images without the need for a water-filled container. We justify this technique analytically and via simulation using the transport-of-intensity equation and calibrate the technique using our existing methods for measuring lung air volume. Finally, we show the full capabilities of this technique for measuring regional differences in lung aeration. PMID:24514306

  16. A source of PCB contamination in modified high-volume air samplers

    SciTech Connect

    Basu, I.; O'Dell, J.M.; Arnold, K.; Hites, R.A.

    2000-02-01

    Modified Anderson High Volume (Hi-Vol) air samplers are widely used for the collection of semi-volatile organic compounds (such as PCBs) from air. The foam gasket near the main air flow path in these samplers can become contaminated with PCBs if the sampler or the gasket is stored at a location with high indoor air PCB levels. Once the gasket is contaminated, it releases PCBs back into the air stream during sampling, and as a result, incorrectly high air PCB concentrations are measured. This paper presents data demonstrating this contamination problem using measurements from two Integrated Atmospheric Deposition Network sites: one at Sleeping Bear Dunes on Lake Michigan and the other at Point Petre on Lake Ontario. The authors recommend that these gaskets be replaced by Teflon tape and that the storage history of each sampler be carefully tracked.

  17. Journal of Air Transportation World Wide, Volume 3, No. 1. Volume 3

    NASA Technical Reports Server (NTRS)

    Bowen, Brent D. (Editor)

    1998-01-01

    The Journal of Air Transportation World Wide's (JATWW) mission is to provide the global community immediate key resource information in all areas of air transportation. Our goal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JATWW will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

  18. Journal of Air Transportation World Wide, Volume 2, No. 1. Volume 2

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor)

    1997-01-01

    The Journal of Air Transportation World Wide's (JATWW) mission is to provide the global community immediate key resource information in all areas of air transportation. Our goal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JATWW will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a key focal point of the journal will be in the area of aviation administration and policy.

  19. Journal of Air Transportation, Volume 9, No. 2. Volume 9, No. 2

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Kabashkin, Igor (Editor); Gudmundsson, Sveinn Vidar (Editor); Scarpellini, Nanette (Editor)

    2004-01-01

    The following articles from the "Journal of Air Transportation" were processed: Future Requirements and Concepts for Cabins of Blended Wing Body Configurations:A Scenario Approach; Future Scenarios for the European Airline Industry: A Marketing-Based Perspective; An Application of the Methodology for Assessment of the Sustainability of the Air Transport System; Modeling the Effect of Enlarged Seating Room on Passenger Preferences of Domestic Airlines in Taiwan; Developing a Fleet Standardization Index for Airline Pricing; and Future Airport Capacity Utilization in Germany: Peaked Congestion and/or Idle Capacity).

  20. Journal of Air Transportation World Wide, Volume 4, No. 2. Volume 4

    NASA Technical Reports Server (NTRS)

    Bowen, Brent D. (Editor); Kabashkin, Igor (Editor)

    1999-01-01

    The Journal of Air Transportation World Wide's (JATWW) mission is to provide the global community immediate key resource information in all areas of air transportation. The goal of the Journal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JATWW will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

  1. Journal of Air Transportation World Wide, Volume 5, No. 2. Volume 5, No. 2

    NASA Technical Reports Server (NTRS)

    Browen, Brent D.

    2000-01-01

    The Journal of Air Transportation World Wide's (JATWW) mission is to provide the global community immediate key resource information in all areas of air transportation. Our goal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international and interdisciplinary journal, the JATWW will provide a forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

  2. Increasing the Air Charge and Scavenging the Clearance Volume of a Compression-Ignition Engine

    NASA Technical Reports Server (NTRS)

    Spanogle, J A; Hicks, C W; Foster, H H

    1934-01-01

    The object of the investigation presented in this report was to determine the effects of increasing the air charge and scavenging the clearance volume of a 4-stroke-cycle compression-ignition engine having a vertical-disk form combustion chamber. Boosting the inlet-air pressure with normal valve timing increased the indicated engine power in proportion to the additional air inducted and resulted in smoother engine operation with less combustion shock. Scavenging the clearance volume by using a valve overlap of 145 degrees and an inlet-air boost pressure of approximately 2 1/2 inches of mercury produced a net increase in performance for clear exhaust operation of 33 percent over that obtained with normal valve timing and the same boost pressure. The improved combustion characteristics result in lower specific fuel consumption, and a clearer exhaust.

  3. 2007 NASA Seal/Secondary Air System Workshop. Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M.; Hendricks, Robert C.; Delgado, Irebert

    2008-01-01

    The 2007 NASA Seal/Secondary Air System workshop covered the following topics: (i) Overview of NASA's new Orion project aimed at developing a new spacecraft that will fare astronauts to the International Space Station, the Moon, Mars, and beyond; (ii) Overview of NASA's fundamental aeronautics technology project; (iii) Overview of NASA Glenn s seal project aimed at developing advanced seals for NASA's turbomachinery, space, and reentry vehicle needs; (iv) Reviews of NASA prime contractor, vendor, and university advanced sealing concepts, test results, experimental facilities, and numerical predictions; and (v) Reviews of material development programs relevant to advanced seals development. Turbine engine studies have shown that reducing seal leakage as well as high-pressure turbine (HPT) blade tip clearances will reduce fuel burn, lower emissions, retain exhaust gas temperature margin, and increase range. Turbine seal development topics covered include a method for fast-acting HPT blade tip clearance control, noncontacting low-leakage seals, intershaft seals, and a review of engine seal performance requirements for current and future Army engine platforms.

  4. 2002 NASA Seal/Secondary Air System Workshop. Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

    2003-01-01

    The 2002 NASA Seal/Secondary Air System Workshop covered the following topics: (i) Overview of NASA s perspective of aeronautics and space technology for the 21st century; (ii) Overview of the NASA-sponsored Ultra-Efficient Engine Technology (UEET), Turbine-Based Combined-Cycle (TBCC), and Revolutionary Turbine Accelator (RTA) programs; (iii) Overview of NASA Glenn's seal program aimed at developing advanced seals for NASA's turbomachinery, space propulsion, and reentry vehicle needs; (iv) Reviews of sealing concepts, test results, experimental facilities, and numerical predictions; and (v) Reviews of material development programs relevant to advanced seals development. The NASA UEET and TBCC/RTA program overviews illustrated for the reader the importance of advanced technologies, including seals, in meeting future turbine engine system efficiency and emission goals. For example, the NASA UEET program goals include an 8- to 15-percent reduction in fuel burn, a 15-percent reduction in CO2, a 70-percent reduction in NOx, CO, and unburned hydrocarbons, and a 30-dB noise reduction relative to program baselines. The workshop also covered several programs NASA is funding to investigate advanced reusable space vehicle technologies (X-38) and advanced space ram/scramjet propulsion systems. Seal challenges posed by these advanced systems include high-temperature operation, resiliency at the operating temperature to accommodate sidewall flexing, and durability to last many missions.

  5. 2006 NASA Seal/Secondary Air System Workshop; Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce, M. (Editor); Hendricks, Robert C. (Editor); Delgado, Irebert (Editor)

    2007-01-01

    The 2006 NASA Seal/Secondary Air System workshop covered the following topics: (i) Overview of NASA s new Exploration Initiative program aimed at exploring the Moon, Mars, and beyond; (ii) Overview of NASA s new fundamental aeronautics technology project; (iii) Overview of NASA Glenn Research Center s seal project aimed at developing advanced seals for NASA s turbomachinery, space, and reentry vehicle needs; (iv) Reviews of NASA prime contractor, vendor, and university advanced sealing concepts including tip clearance control, test results, experimental facilities, and numerical predictions; and (v) Reviews of material development programs relevant to advanced seals development. Turbine engine studies have shown that reducing seal leakages as well as high-pressure turbine (HPT) blade tip clearances will reduce fuel burn, lower emissions, retain exhaust gas temperature margin, and increase range. Several organizations presented development efforts aimed at developing faster clearance control systems and associated technology to meet future engine needs. The workshop also covered several programs NASA is funding to develop technologies for the Exploration Initiative and advanced reusable space vehicle technologies. NASA plans on developing an advanced docking and berthing system that would permit any vehicle to dock to any on-orbit station or vehicle. Seal technical challenges (including space environments, temperature variation, and seal-on-seal operation) as well as plans to develop the necessary "androgynous" seal technologies were reviewed. Researchers also reviewed seal technologies employed by the Apollo command module that serve as an excellent basis for seals for NASA s new Crew Exploration Vehicle (CEV).

  6. 2003 NASA Seal/Secondary Air System Workshop. Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

    2004-01-01

    The following reports were included in the 2003 NASA Seal/Secondary Air System Workshop:Low Emissions Alternative Power (LEAP); Overview of NASA Glenn Seal Developments; NASA Ultra Efficient Engine Technology Project Overview; Development of Higher Temperature Abradable Seals for Industrial Gas Turbines; High Misalignment Carbon Seals for the Fan Drive Gear System Technologies; Compliant Foil Seal Investigations; Test Rig for Evaluating Active Turbine Blade Tip Clearance Control Concepts; Controls Considerations for Turbine Active Clearance Control; Non-Contacting Finger Seal Developments and Design Considerations; Effect of Flow-Induced Radial Load on Brush Seal/Rotor Contact Mechanics; Seal Developments at Flowserve Corporation; Investigations of High Pressure Acoustic Waves in Resonators With Seal-Like Features; Numerical Investigations of High Pressure Acoustic Waves in Resonators; Feltmetal Seal Material Through-Flow; "Bimodal" Nuclear Thermal Rocket (BNTR) Propulsion for Future Human Mars Exploration Missions; High Temperature Propulsion System Structural Seals for Future Space Launch Vehicles; Advanced Control Surface Seal Development for Future Space Vehicles; High Temperature Metallic Seal Development for Aero Propulsion and Gas Turbine Applications; and BrazeFoil Honeycomb.

  7. 2005 NASA Seal/Secondary Air System Workshop, Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

    2006-01-01

    The 2005 NASA Seal/Secondary Air System workshop covered the following topics: (i) Overview of NASA s new Exploration Initiative program aimed at exploring the Moon, Mars, and beyond; (ii) Overview of the NASA-sponsored Propulsion 21 Project; (iii) Overview of NASA Glenn s seal project aimed at developing advanced seals for NASA s turbomachinery, space, and reentry vehicle needs; (iv) Reviews of NASA prime contractor, vendor, and university advanced sealing concepts including tip clearance control, test results, experimental facilities, and numerical predictions; and (v) Reviews of material development programs relevant to advanced seals development. Turbine engine studies have shown that reducing high-pressure turbine (HPT) blade tip clearances will reduce fuel burn, lower emissions, retain exhaust gas temperature margin, and increase range. Several organizations presented development efforts aimed at developing faster clearance control systems and associated technology to meet future engine needs. The workshop also covered several programs NASA is funding to develop technologies for the Exploration Initiative and advanced reusable space vehicle technologies. NASA plans on developing an advanced docking and berthing system that would permit any vehicle to dock to any on-orbit station or vehicle. Seal technical challenges (including space environments, temperature variation, and seal-on-seal operation) as well as plans to develop the necessary "androgynous" seal technologies were reviewed. Researchers also reviewed tests completed for the shuttle main landing gear door seals.

  8. Use of a massive volume air sampler to collect fly ash for biological characterization

    SciTech Connect

    Cheng, Y.S.

    1984-06-01

    A massive volume air sampler (MVAS) with a flow rate of some 17/SUP/3/min and designed to collect ambient aerosols was modified for the collection of fly ash emissions from the stack mouth of an experimental fluidised bed combustor for physicochemical and biological characterisation. The sampler consisted of 2 impactor stages and an electrostatic precipitator section. High volume filter fly ash samples and laboratory size cascade impactor samples were obtained simultaneously to verify the operation of the MVAS.

  9. The Conference Proceedings of the 2003 Air Transport Research Society (ATRS) World Conference, Volume 3

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Gudmundsson, Sveinn (Editor); Oum, Tae (Editor)

    2003-01-01

    Volume 3 of the 2003 Air Transport Reserch Society (ATRS) World Conference includes papers on topics relevant to airline operations worldwide. Specific topics include: European Union and civil aviation regimens;simulating decision making in airline operations, passenger points of view on convenient airports; route monopolies and nonlinear pricing; cooperation among airports in Europe; fleet modernizaiton in Brazil;the effects of deregulation on the growth of air transportation in Europe and the United States.

  10. A system for the disposal of large volumes of air containing oxygen-15

    NASA Astrophysics Data System (ADS)

    Peters, J. M.; Quaglia, L.; del Fiore, G.; Hannay, J.; Fissore, A.

    1991-01-01

    A method is described which permits large volumes of air containing the radionuclide 15O to be vented into the atmosphere. The short half-life of this isotope (124 s) enables use to be made of a large number of small vessels connected in series. Such a device has the effect of increasing the mean transit time. The system as installed results in a reduction of the radioactive concentration in the vented air to levels below the maximum permitted values.

  11. 2004 NASA Seal/Secondary Air System Workshop, Volume 1

    NASA Technical Reports Server (NTRS)

    2005-01-01

    The 2004 NASA Seal/Secondary Air System workshop covered the following topics: (1) Overview of NASA s new Exploration Initiative program aimed at exploring the Moon, Mars, and beyond; (2) Overview of the NASA-sponsored Ultra-Efficient Engine Technology (UEET) program; (3) Overview of NASA Glenn s seal program aimed at developing advanced seals for NASA s turbomachinery, space, and reentry vehicle needs; (4) Reviews of NASA prime contractor and university advanced sealing concepts including tip clearance control, test results, experimental facilities, and numerical predictions; and (5) Reviews of material development programs relevant to advanced seals development. The NASA UEET overview illustrated for the reader the importance of advanced technologies, including seals, in meeting future turbine engine system efficiency and emission goals. For example, the NASA UEET program goals include an 8- to 15-percent reduction in fuel burn, a 15-percent reduction in CO2, a 70-percent reduction in NOx, CO, and unburned hydrocarbons, and a 30-dB noise reduction relative to program baselines. The workshop also covered several programs NASA is funding to develop technologies for the Exploration Initiative and advanced reusable space vehicle technologies. NASA plans on developing an advanced docking and berthing system that would permit any vehicle to dock to any on-orbit station or vehicle, as part of NASA s new Exploration Initiative. Plans to develop the necessary mechanism and androgynous seal technologies were reviewed. Seal challenges posed by reusable re-entry space vehicles include high-temperature operation, resiliency at temperature to accommodate gap changes during operation, and durability to meet mission requirements.

  12. 2000 NASA Seal/Secondary Air System Workshop. Volume 1

    NASA Technical Reports Server (NTRS)

    Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

    2001-01-01

    The 2000 NASA Seal/Secondary Air System Workshop covered four main areas: (1) overviews of NASA-sponsored Ultra-Efficient Engine Technology (UEET) and Access to Space Programs, with emphasis on program goals and seal needs; (2) review of turbine engine seal issues from the perspective of end users such as United Airlines; (3) reviews of sealing concepts, test results, experimental facilities, and numerical predictions; and (4) reviews of material development programs relevant to advanced seals development. The NASA UEET overview illustrates for the reader the importance of advanced technologies, including seals, in meeting future engine system efficiency and emission goals. GE, Pratt & Whitney, and Honeywell presented advanced seal development work being performed within their organizations. The NASA-funded GE/Stein Seal team has successfully demonstrated a large (3-ft. diam) aspirating seal that can withstand all anticipated pressures, speeds, and rotor runouts anticipated for a GE90 L.P. turbine balance piston location. GE/Stein Seal are fabricating a full-scale seal to be tested in a GE-90 ground test engine in early 2002. Pratt & Whitney and Stein Seal are investigating carbon seals to accommodate large radial movements anticipated in future geared-fan gearbox locations. Honeywell presented a finger seal design being considered for a high-temperature static combustor location incorporating ceramic finger elements. Successful demonstration of the braided carbon rope thermal barriers to extreme temperatures (5500 F) for short durations provide a new form of very high temperature thermal barrier for future Shuttle solid rocket motor nozzle joints. The X-37, X-38, and future highly reusable launch vehicles pose challenging control surface seal demands that require new seal concepts made from emerging high temperature ceramics and other materials.

  13. IAQPC: AN INDOOR AIR QUALITY SIMULATOR

    EPA Science Inventory

    The paper discusses an Indoor Air Quality Simulator for Personal Computers (IAQPC), developed in response to the growing need for quick accurate predictions of indoor air contamination levels. eating, ventilating, and air conditioning (HVAC) system designers need ways to determin...

  14. Improving Indoor Environmental Quality And Energy Performance OfModular Classroom HVAC Systems

    SciTech Connect

    Apte, Michael G.; Spears, Michael; Lai, Chi-Ming; Shendell, Derek G.

    2005-03-01

    The factory-built relocatable classroom (RC) is a dominant force in the school facility construction industry in the US and elsewhere. it is estimated that there are approximately 650,000 RCs currently occupied in the US, housing about 16 million students. RCs receive public attention due to complaints about poor indoor environmental quality (IEQ). Both measured data and anecdotal evidence in California have suggested excessive acoustical noise from heating, ventilation, and air conditioning (HVAC) equipment as a central factor leading to degraded IEQ. In the US, RCs are typically equipped with unitary exterior wall-mount HVAC systems, and interior acoustical noise due to structural and airborne transmission can reach levels of about 58dB(A) with compressor cycling, under unoccupied conditions. Due to these noise levels, teachers often simply choose to turn off the HVAC, leading to inadequate ventilation, as well as poor thermal conditioning, and thus to poor indoor air quality. Elevated levels of carbon dioxide and volatile organic compounds including formaldehyde are common. They discuss the acoustic component of the efforts to develop and test energy efficient HVAC systems that address the ventilation, controls, and acoustic requirements necessary to ensure high quality indoor environments in RCs.

  15. Los Alamos Controlled Air Incinerator for radioactive waste. Volume I. Rationale, process, equipment, performance, and recommendations

    SciTech Connect

    Neuls, A.S.; Draper, W.E.; Koenig, R.A.; Newmyer, J.M.; Warner, C.L.

    1982-08-01

    This two-volume report is a detailed design and operating documentation of the Los Alamos National Laboratory Controlled Air Incinerator (CAI) and is an aid to technology transfer to other Department of Energy contractor sites and the commercial sector. Volume I describes the CAI process, equipment, and performance, and it recommends modifications based on Los Alamos experience. It provides the necessary information for conceptual design and feasibility studies. Volume II provides descriptive engineering information such as drawing, specifications, calculations, and costs. It aids duplication of the process at other facilities.

  16. Los Alamos Controlled Air Incinerator for radioactive waste. Volume II. Engineering design reference manual

    SciTech Connect

    Koenig, R.A.; Draper, W.E.; Newmyer, J.M.; Warner, C.L.

    1982-10-01

    This two-volume report is a detailed design and operating documentation of the Los Alamos National Laboratory Controlled Air Incinerator (CAI) and is an aid to technology transfer to other Department of Energy contractor sites and the commercial sector. Volume I describes the CAI process, equipment, and performance, and it recommends modifications based on Los Alamos experience. It provides the necessary information for conceptual design and feasibility studies. Volume II provides descriptive engineering information such as drawings, specifications, calculations, and costs. It aids duplication of the process at other facilities.

  17. Journal of Air Transportation, Volume 8, No. 2. Volume 8, No. 2

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Kabashkin, Igor (Editor); Nickerson, Jocelyn (Editor)

    2003-01-01

    The mission of the Journal of Air Transportation (JAT) is to provide the global community immediate key resource information in all areas of air transportation. This journal contains articles on the following:Fuel Consumption Modeling of a Transport Category Aircraft: A FlightOperationsQualityAssurance (F0QA) Analysis;Demand for Air Travel in the United States: Bottom-Up Econometric Estimation and Implications for Forecasts by Origin and Destination Pairs;Blind Flying on the Beam: Aeronautical Communication, Navigation and Surveillance: Its Origins and the Politics of Technology: Part I1 Political Oversight and Promotion;Blind Flying on the Beam: Aeronautical Communication, Navigation and Surveillance: Its Origins and the Politics of Technology: Part 111: Emerging Technologies;Ethics Education in University Aviation Management Programs in the US: Part Two B-Statistical Analysis of Current Practice;Integrating Human Factors into the Human-computer Interface: and How Best to Display Meteorological Information for Critical Aviation Decision-making and Performance.

  18. Controlling HVAC system noise and vibration

    SciTech Connect

    Schaffer, M.E. )

    1993-06-01

    This article examines techniques for design and placement of space HVAC system components as described in a new ASHRAE special publication. The topics of the article include cooperative design, acoustical system effects, and implications of cost cutting that result in increased noise and higher energy costs.

  19. Computer Review Can Cut HVAC Energy Use

    ERIC Educational Resources Information Center

    McClure, Charles J. R.

    1974-01-01

    A computerized review of construction bidding documents, usually done by a consulting engineer, can reveal how much money it will cost to operate various alternative types of HVAC equipment over a school's lifetime. The review should include a computerized load calculation, energy systems flow diagram, control system analysis, and a computerized…

  20. Field Operations and Enforcement Manual for Air Pollution Control. Volume III: Inspection Procedures for Specific Industries.

    ERIC Educational Resources Information Center

    Weisburd, Melvin I.

    The Field Operations and Enforcement Manual for Air Pollution Control, Volume III, explains in detail the following: inspection procedures for specific sources, kraft pulp mills, animal rendering, steel mill furnaces, coking operations, petroleum refineries, chemical plants, non-ferrous smelting and refining, foundries, cement plants, aluminum…

  1. AIR QUALITY CRITERIA FOR PARTICULATE MATTER, VOLUMES I-III, (EXTERNAL REVIEW DRAFT, 1995)

    EPA Science Inventory

    There is no abstract available for these documents.

    If further information is requested, please refer to the bibliographic citation and contact the Technical Information Staff at the number listed above.

    • Air Quality Criteria for Particulate Matter, Volume I, Extern...

    • EVALUATION OF HIGH VOLUME PARTICLE SAMPLING AND SAMPLE HANDLING PROTOCOLS FOR AMBIENT URBAN AIR MUTAGENICITY DETERMINATIONS

      EPA Science Inventory

      An investigation of high volume particle sampling and sample handling procedures was undertaken to evaluate variations of protocols being used by the U.S Environmental Protection Agency. hese protocols are used in urban ambient air studies which collect ambient and source samples...

    • INTEGRATED AIR POLLUTION CONTROL SYSTEM VERSION 5.0 - VOLUME 2: TECHNICAL DOCUMENTATION

      EPA Science Inventory

      The three volume report and two diskettes document the Integrated Air Pollution Control System (IAPCS), developed for the U.S. EPA to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, an eq...

    • INTEGRATED AIR POLLUTION CONTROL SYSTEM VERSION 5.0 - VOLUME 1: USER'S GUIDE

      EPA Science Inventory

      The three volume report and two diskettes document the Integrated Air Pollution Control System (IAPCS), developed for the U.S. EPA to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, an eq...

    • INTEGRATED AIR POLLUTION CONTROL SYSTEM VERSION 5.0 - VOLUME 3: PROGRAMMER'S MAINTENANCE MANUAL

      EPA Science Inventory

      The three volume report and two diskettes document the Integrated Air Pollution Control System (IAPCS), developed for the U.S. EPA to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, an eq...

    • Journal of Air Transportation World Wide, Volume 5, No. 1. Volume 5

      NASA Technical Reports Server (NTRS)

      Bowen, Brent D. (Editor)

      2000-01-01

      The Journal's mission is to provide the global community immediate key resource information in all areas of air transportation. The goal of the Journal is to be recognized as the preeminent scholarly journal in the aeronautical aspects of transportation. As an international forum for peer-reviewed articles in all areas of aviation and space transportation research, policy, theory, case study, practice, and issues. While maintaining a broad scope, a focal point of the journal will be in the area of aviation administration and policy.

    • Modeling of volume change phenomena in a Li-air battery

      NASA Astrophysics Data System (ADS)

      Yoo, Kisoo; Banerjee, Soumik; Dutta, Prashanta

      2014-07-01

      Volume change can occur in a lithium-air cell due to Li metal oxidation (reduction) in anode during discharge (charge) and due to solubility of reaction product (lithium peroxide) in the electrolyte at cathode. A mathematical model is developed to study the performance of lithium-air batteries considering the significant volume changes at the anode and cathode sides. Moving boundary technique is used to obtain the governing equations for transport of lithium ions and oxygen as well as for liquid phase potential. A numerical method is introduced to solve the moving boundary problem, and the electrical performance of lithium-air cell is obtained for various load conditions. Results obtained from this model are validated with experimental results for Lithium-air cell. Numerical results indicate that volume changes significantly affect the functioning of lithium-air cells. The high solubility of lithium peroxide in the electrolyte can reduce the passivation in the cathode, but it can also reduce the effective reaction area in the anode. However, the benefit of the former outweighs the detriment of the later phenomenon. On the other hand, if lithium peroxide is insoluble in electrolyte, electrolyte leakage can take place due to decrease in total available space for electrolyte.

    • Determination of radionuclide concentrations in ground level air using the ASS-500 high volume sampler

      SciTech Connect

      Frenzel, E.; Arnold, D.; Wershofen, H.

      1996-06-01

      A method for determination of radionuclide concentrations in air aerosol samples collected by the high volume aerosol sampler ASS-500 was elaborated. The aerosol sampling station ASS-500 is a Stand alone, all-weather proofed instrument. It is designed for representative sampling of airborne radionuclides from ground level air at a height of about 1.5 m above ground level. The ASS-500 station enables continuous air monitoring both normal and emergency Situations. The collection of aerosols on the Petrianov FPP-15-1.5 type filter out of an air volume of about 100,000 m{sup 3} (sampling period 1 wk) or of about 250,000 m{sup 3} (sampling period 3 wk) admits accurate spectrometric low level measurements of natural and artificial radionuclides. The achieved detection limit is 0.5 {mu}Bq m{sup -3} and 0.2 {mu}Bq m{sup -3} for {sup 137}Cs, respectively. A new developed air flow Meter system allows to enhance the collected air volume to about 150,000 m{sup 3} per week and lowers the detection limit to <0.4 {mu}Bq m{sup -3} for {sup 137}Cs for weekly collected aerosol samples. In Poland the CLOR uses 9 Stations ASS-500 at different sites as atmospheric radioactivity control system. On the basis of spectrometric measurements of natural and artificial radionuclides in the collected aerosol samples at the different sites, CLOR establishes a weekly report about the radiological situation at Poland for responsible authorities. The very low achievable detection limit of the Station ASS-500 due 10 the high air flow fate and the long possible sampling period were the key argument for other government radiation protection authorities in Europe to introduce the Station ASS-500 into their low level radionuclide atmospheric monitoring programs (Austria, Belarus, France, Germany, Iceland, Spain, Switzerland, Ukraine).

    • Strategy Guideline. HVAC Equipment Sizing

      SciTech Connect

      Burdick, Arlan

      2012-02-01

      This guide describes the equipment selection of a split system air conditioner and furnace for an example house in Chicago, IL as well as a heat pump system for an example house in Orlando, FL. The required heating and cooling load information for the two example houses was developed in the Department of Energy Building America Strategy Guideline: Accurate Heating and Cooling Load Calculations.

    • A large volume 2000 MPA air source for the radiatively driven hypersonic wind tunnel

      SciTech Connect

      Constantino, M

      1999-07-14

      An ultra-high pressure air source for a hypersonic wind tunnel for fluid dynamics and combustion physics and chemistry research and development must provide a 10 kg/s pure air flow for more than 1 s at a specific enthalpy of more than 3000 kJ/kg. The nominal operating pressure and temperature condition for the air source is 2000 MPa and 900 K. A radial array of variable radial support intensifiers connected to an axial manifold provides an arbitrarily large total high pressure volume. This configuration also provides solutions to cross bore stress concentrations and the decrease in material strength with temperature. [hypersonic, high pressure, air, wind tunnel, ground testing

    • Packaged HVAC Unit Diagnostician version 1.0

      2007-01-09

      The PHD automatically detects and diagnoses faults with respect to four major aspects of packaged heating, ventilating, and air conditioning (HVAC) unit operation: 1) air handling in which return-air and outdoor-air are mixed, then conditioned to appropriate temperature and humidity conditions, 2) vapor-compression refrigerant loop operation, 3) overall unit efficiency and its potential degradation over time, and 4) operation scheduling. When faults are detected, the software provides alarm codes corresponding to the detected problem(s). Thesemore » alarms map into explanations of the faults, possible causes for them, and suggested actions to remedy the faults. For air handling, the software also estimates energy and cost impacts of faults. The software is intended for implementation on a hardware systems that includes sensors, sensor signal processing, micro-processor unit for running this software, and communication to a web server. Results are made available to users via the world wide web using a computer with Web browser and Internet connection for access. The graphical web-based interface must be provided by an application service provider (not part of this software).« less

    • 2001 NASA Seal/secondary Air System Workshop, Volume 1. Volume 1

      NASA Technical Reports Server (NTRS)

      Steinetz, Bruce M. (Editor); Hendricks, Robert C. (Editor)

      2002-01-01

      The 2001 NASA Seal/Secondary Air System Workshop covered the following topics: (i) overview of NASA's Vision for 21st Century Aircraft; (ii) overview of NASA-sponsored Ultra-Efficient Engine Technology (UEET); (iii) reviews of sealing concepts, test results, experimental facilities, and numerical predictions; and (iv) reviews of material development programs relevant to advanced seals development. The NASA UEET overview illustrates for the reader the importance of advanced technologies, including seals, in meeting future turbine engine system efficiency and emission goals. The NASA UEET program goals include an 8-to 15-percent reduction in fuel burn, a 15-percent reduction in CO2, a 70-percent reduction in NOx, CO, and unburned hydrocarbons, and a 30-dB noise reduction relative to program baselines. The workshop also covered several programs NASA is funding to investigate advanced reusable space vehicle technologies (X-38) and advanced space ram/scramjet propulsion systems. Seal challenges posed by these advanced systems include high-temperature operation, resiliency at the operating temperature to accommodate sidewall flexing, and durability to last many missions.

    • Estimating the HVAC energy consumption of plug-in electric vehicles

      NASA Astrophysics Data System (ADS)

      Kambly, Kiran R.; Bradley, Thomas H.

      2014-08-01

      Plug in electric vehicles are vehicles that use energy from the electric grid to provide tractive and accessory power to the vehicle. Due to the limited specific energy of energy storage systems, the energy requirements of heating, ventilation, and air conditioning (HVAC) systems for cabin conditioning can significantly reduce their range between charges. Factors such as local ambient temperature, local solar radiation, local humidity, length of the trip and thermal soak have been identified as primary drivers of cabin conditioning loads and therefore of vehicle range. The objective of this paper is to develop a detailed systems-level approach to connect HVAC technologies and usage conditions to consumer-centric metrics of vehicle performance including energy consumption and range. This includes consideration of stochastic and transient inputs to the HVAC energy consumption model including local weather, solar loads, driving behavior, charging behavior, and regional passenger fleet population. The resulting engineering toolset is used to determine the summation of and geographical distribution of energy consumption by HVAC systems in electric vehicles, and to identify regions of US where the distributions of electric vehicle range are particularly sensitive to climate.

    • Occupancy sensors for HVAC gaining in hotel industry

      SciTech Connect

      Ladd, C.

      1985-12-02

      The hotel industry is overcoming its skepticism as occupancy sensors with built-in thermistors to control heating, ventilating, and air conditioning (HVAC) units demonstrate their ability to cut energy costs as much as 30%. Despite the successful demonstrations and acceptance by Holiday Inn, some hotel managers of other chains continue to resist. Occupancy sensors have either ultrasonic or infrared signals, but differ from lighting control devices by also having internal thermistors and remote door switches. This allows the rooms to reach comfort levels only when the guest is present since occupants are only minimally affected if temperatures are modified during unoccupied periods. The system works best for roadside-type motels rather than convention hotels, where occupants are in and out of their rooms.

    • United States Air Force 611th air support group 611th Civil Engineer Squadron, Elmendorf AFB, Alaska. Eareckson Air Station, Alaska Remedial Investigation/Feasibility Study Report, final. Volume 2. Report for July 1994-September 1996

      SciTech Connect

      1995-08-30

      The Volume II has been prepared to present the findings of the environmental investigation activities conducted at Eareckson Air Station. The RI/FS report has been divided into four primary volumes. This volume, Volume II, discusses 13 source areas that are recommended to be proposed for no further action.

    • The use of Whatman-41 filters for high volume air sampling

      NASA Technical Reports Server (NTRS)

      Neustadter, H. E.; Sidik, S. M.; King, R. B.; Fordyce, J. S.; Burr, J. C.

      1975-01-01

      The feasibility of using W41 filter media on a routine TSP high-volume monitoring network was determined by comparison with glass fiber (GF) filtering. Results indicate that suspended particulate samples from GF filters averaged slightly, but not significantly, higher than those from Whatman-41 filters. Some extra handling procedures were required to avoid errors due to the hygroscopic nature of W41 filters; these added procedures are not overly burdensome, however, and they allow the performance of analytical work, thus extending the capabilities of high-volume sampling. It was demonstrated that W41 filters are practical for air quality monitoring and elemental analysis in environments similar to Cleveland's.

    • Comparisons of HVAC Simulations between EnergyPlus and DOE-2.2 for Data Centers

      SciTech Connect

      Hong, Tianzhen; Sartor, Dale; Mathew, Paul; Yazdanian, Mehry

      2008-08-13

      This paper compares HVAC simulations between EnergyPlus and DOE-2.2 for data centers. The HVAC systems studied in the paper are packaged direct expansion air-cooled single zone systems with and without air economizer. Four climate zones are chosen for the study - San Francisco, Miami, Chicago, and Phoenix. EnergyPlus version 2.1 and DOE-2.2 version 45 are used in the annual energy simulations. The annual cooling electric consumption calculated by EnergyPlus and DOE-2.2 are reasonablely matched within a range of -0.4percent to 8.6percent. The paper also discusses sources of differences beween EnergyPlus and DOE-2.2 runs including cooling coil algorithm, performance curves, and important energy model inputs.

    • An adaptive maneuvering logic computer program for the simulation of one-on-one air-to-air combat. Volume 1: General description

      NASA Technical Reports Server (NTRS)

      Burgin, G. H.; Fogel, L. J.; Phelps, J. P.

      1975-01-01

      A technique for computer simulation of air combat is described. Volume 1 decribes the computer program and its development in general terms. Two versions of the program exist. Both incorporate a logic for selecting and executing air combat maneuvers with performance models of specific fighter aircraft. In the batch processing version the flight paths of two aircraft engaged in interactive aerial combat and controlled by the same logic are computed. The realtime version permits human pilots to fly air-to-air combat against the adaptive maneuvering logic (AML) in Langley Differential Maneuvering Simulator (DMS). Volume 2 consists of a detailed description of the computer programs.

    • METHODS DEVELOPMENT FOR ASSESSING AIR POLLUTION CONTROL BENEFITS. VOLUME IV. STUDIES ON PARTIAL EQUILIBRIUM APPROACHES TO VALUATION OF ENVIRONMENTAL AMENITIES

      EPA Science Inventory

      The research presented in this volume of a five volume study of the economic benefits of air pollution control explores various facets of the two central project objectives that have not been given adequate attention in the previous volumes. The valuations developed in these prev...

    • Active suppression of air refractive index fluctuation using a Fabry-Perot cavity and a piezoelectric volume actuator

      SciTech Connect

      Banh, Tuan Quoc; Ohkubo, Yuria; Murai, Yoshinosuke; Aketagawa, Masato

      2011-01-01

      Air refractive index fluctuation ({Delta}n{sub air}) is one of the largest uncertainty sources in precision interferometry systems that require a resolution of nanometer order or less. We introduce a method for the active suppression of {Delta}n{sub air} inside a normal air-environment chamber using a Fabry-Perot cavity and a piezoelectric volume actuator. The temporal air refractive index (n{sub air}) at a local point is maintained constant with an expanded uncertainty of {approx}4.2x10{sup -9} (k=2), a sufficiently low uncertainty for precise measurements unaffected by {Delta}n{sub air} to be made inside a chamber.

  1. Semi-volatile organic compounds in heating, ventilation, and air-conditioning filter dust in retail stores.

    PubMed

    Xu, Y; Liang, Y; Urquidi, J R; Siegel, J A

    2015-02-01

    Retail stores contain a wide range of products that can emit a variety of indoor pollutants. Among these chemicals, phthalate esters and polybrominated diphenyl ethers (PBDEs) are two important categories of semi-volatile organic compounds (SVOCs). Filters in heating, ventilation, and air-conditioning (HVAC) system collect particles from large volumes of air and thus potentially provide spatially and temporally integrated SVOC concentrations. This study measured six phthalate and 14 PBDE compounds in HVAC filter dust in 14 retail stores in Texas and Pennsylvania, United States. Phthalates and PBDEs were widely found in the HVAC filter dust in retail environment, indicating that they are ubiquitous indoor pollutants. The potential co-occurrence of phthalates and PBDEs was not strong, suggesting that their indoor sources are diverse. The levels of phthalates and PBDEs measured in HVAC filter dust are comparable to concentrations found in previous investigations of settled dust in residential buildings. Significant correlations between indoor air and filter dust concentrations were found for diethyl phthalate, di-n-butyl phthalate, and benzyl butyl phthalate. Reasonable agreement between measurements and an equilibrium model to describe SVOC partitioning between dust and gas-phase is achieved. PMID:24766478

  2. HVAC Fault Detection and Diagnosis Toolkit

    2004-12-31

    This toolkit supports component-level model-based fault detection methods in commercial building HVAC systems. The toolbox consists of five basic modules: a parameter estimator for model calibration, a preprocessor, an AHU model simulator, a steady-state detector, and a comparator. Each of these modules and the fuzzy logic rules for fault diagnosis are described in detail. The toolbox is written in C++ and also invokes the SPARK simulation program.

  3. Cutting the cost of hospital HVAC.

    PubMed

    Ruddell, Steve

    2011-09-01

    Steve Ruddell, head of global marketing, Motors & Generators, at ABB, emphasises the importance of a good motor management and maintenance policy in getting the best performance from, and reducing the energy consumption of, hospitals' HVAC systems, also explaining why investing in energy-efficient, low voltage drives, and high efficiency electric motors, to control such equipment, can pay major dividends for estates and facilities teams. PMID:21961392

  4. Dynamic measures of regional lung air volume using phase contrast x-ray imaging

    NASA Astrophysics Data System (ADS)

    Kitchen, M. J.; Lewis, R. A.; Morgan, M. J.; Wallace, M. J.; Siew, M. L.; Siu, K. K. W.; Habib, A.; Fouras, A.; Yagi, N.; Uesugi, K.; Hooper, S. B.

    2008-11-01

    Phase contrast x-ray imaging can provide detailed images of lung morphology with sufficient spatial resolution to observe the terminal airways (alveoli). We demonstrate that quantitative functional and anatomical imaging of lung ventilation can be achieved in vivo using two-dimensional phase contrast x-ray images with high contrast and spatial resolution (<100 µm) in near real time. Changes in lung air volume as small as 25 µL were calculated from the images of term and preterm rabbit pup lungs (n = 28) using a single-image phase retrieval algorithm. Comparisons with plethysmography and computed tomography showed that the technique provided an accurate and robust method of measuring total lung air volumes. Furthermore, regional ventilation was measured by partitioning the phase contrast images, which revealed differences in aeration for different ventilation strategies.

  5. California residential indoor air quality study. Volume 3. Ancillary and exploratory analyses. Topical report

    SciTech Connect

    Wilson, A.L.; Colome, S.D.; Tian, Y.

    1995-10-01

    The topics covered in this report are: describe the relationship between measured benzene, toluene, NO2, and radon concentrations with building characteristics, appliance factors, meteorological conditions, other measured pollutants, geographical locations, and sampling parameters; extrapolate the measured CO distributions from the three service territories to the entire State of California; develop a mass balance model to predict CO concentrations from air exchange rate, home volume and cooking/heating type; and explore the relationship among CO concentrations, measured benzene levels, and smoking behaviors.

  6. MELSAR: a mesoscale air quality model for complex terrain. Volume 2. Appendices

    SciTech Connect

    Allwine, K.J.; Whiteman, C.D.

    1985-04-01

    This final report is submitted as part of the Green River Ambient Model Assessment (GRAMA) project conducted at the US Department of Energy's Pacific Northwest Laboratory for the US Environmental Protection Agency. The GRAMA Program has, as its ultimate goal, the development of validated air quality models that can be applied to the complex terrain of the Green River Formation of western Colorado, eastern Utah and southern Wyoming. The Green River Formation is a geologic formation containing large reserves of oil shale, coal, and other natural resources. Development of these resources may lead to a degradation of the air quality of the region. Air quality models are needed immediately for planning and regulatory purposes to assess the magnitude of these regional impacts. This report documents one of the models being developed for this purpose within GRAMA - specifically a model to predict short averaging time (less than or equal to 24 h) pollutant concentrations resulting from the mesoscale transport of pollutant releases from multiple sources. MELSAR has not undergone any rigorous operational testing, sensitivity analyses, or validation studies. Testing and evaluation of the model are needed to gain a measure of confidence in the model's performance. This report consists of two volumes. This volume contains the Appendices, which include listings of the FORTRAN code and Volume 1 contains the model overview, technical description, and user's guide. 13 figs., 10 tabs.

  7. The Conference Proceedings of the 2003 Air Transport Research Society (ATRS) World Conference, Volume 5

    NASA Technical Reports Server (NTRS)

    Bowen, Brent (Editor); Gudmundsson, Sveinn (Editor); Oum, Tae (Editor)

    2003-01-01

    The UNO Aviation Institute Monograph Series began in 1994 as a key component of the education outreach and information transfer missions of the Aviation Institute and the NASA Nebraska Space Grant & EPSCoR Programs. The series is an outlet for aviation materials to be indexed and disseminated through an efficient medium. Publications are welcome in all aspects of aviation. Publication formats may include, but are not limited to, conference proceedings, bibliographies, research reports, manuals, technical reports, and other documents that should be archived and indexed for future reference by the aviation and world wide communities. The Conference proceedings of the 2003 Air Transport Research Society (ATRS) world conference, volume 5 is presented. The topics include: 1) The Temporal Configuration of Airline Networks in Europe; 2) Determination and Applications of Environmental Costs at Different Sized Airports-Aircraft Noise and Engine Emissions; 3) Cost Effective Measures to Reduce CO2 Emissions in the Air Freight Sector; 4) An Assessment of the Sustainability of Air Transport System: Quantification of Indicators; 5) Regulation, Competition and Network Evolution in Aviation; 6) Regulation in the Air: Price and Frequency Cap; 7) Industry Consolidation and Future Airline Network Structures in Europe; 8) Application of Core Theory to the U.S. Airline Industry; 9) Air Freight Transshipment Route Choice Analysis; 10) A Fuzzy Approach of the Competition on Air Transport Market; and 11) Developing Passenger Demand Models for International Aviation from/to Egypt: A Case Study of Cairo Airport and Egyptair.

  8. HVAC Equipment Design Options for Near-Zero-Energy Homes (NZEH) -A Stage 2 Scoping Assessment

    SciTech Connect

    Baxter, Van D

    2005-11-01

    Although the energy efficiency of heating, ventilating, and air-conditioning (HVAC) equipment has increased substantially in recent years, new approaches are needed to continue this trend. Conventional unitary equipment and system designs have matured to a point where cost-effective, dramatic efficiency improvements that meet near-zero-energy housing (NZEH) goals require a radical rethinking of opportunities to improve system performance. The large reductions in HVAC energy consumption necessary to support the NZEH goals require a systems-oriented analysis approach that characterizes each element of energy consumption, identifies alternatives, and determines the most cost-effective combination of options. In particular, HVAC equipment must be developed that addresses the range of special needs of NZEH applications in the areas of reduced HVAC and water heating energy use, humidity control, ventilation, uniform comfort, and ease of zoning. This report describes results of a scoping assessment of HVAC system options for NZEH homes. ORNL has completed a preliminary adaptation, for consideration by The U.S. Department of Energy, Energy Efficiency and Renewable Energy Office, Building Technologies (BT) Program, of Cooper's (2001) stage and gate planning process to the HVAC and Water Heating element of BT's multi-year plan, as illustrated in Figure 1. In order to adapt to R&D the Cooper process, which is focused on product development, and to keep the technology development process consistent with an appropriate role for the federal government, the number and content of the stages and gates needed to be modified. The potential federal role in technology development involves 6 stages and 7 gates, but depending on the nature and status of the concept, some or all of the responsibilities can flow to the private sector for product development beginning as early as Gate 3. In the proposed new technology development stage and gate sequence, the Stage 2 'Scoping Assessment

  9. Detection and 3D representation of pulmonary air bubbles in HRCT volumes

    NASA Astrophysics Data System (ADS)

    Silva, Jose S.; Silva, Augusto F.; Santos, Beatriz S.; Madeira, Joaquim

    2003-05-01

    Bubble emphysema is a disease characterized by the presence of air bubbles within the lungs. With the purpose of identifying pulmonary air bubbles, two alternative methods were developed, using High Resolution Computer Tomography (HRCT) exams. The search volume is confined to the pulmonary volume through a previously developed pulmonary contour detection algorithm. The first detection method follows a slice by slice approach and uses selection criteria based on the Hounsfield levels, dimensions, shape and localization of the bubbles. Candidate regions that do not exhibit axial coherence along at least two sections are excluded. Intermediate sections are interpolated for a more realistic representation of lungs and bubbles. The second detection method, after the pulmonary volume delimitation, follows a fully 3D approach. A global threshold is applied to the entire lung volume returning candidate regions. 3D morphologic operators are used to remove spurious structures and to circumscribe the bubbles. Bubble representation is accomplished by two alternative methods. The first generates bubble surfaces based on the voxel volumes previously detected; the second method assumes that bubbles are approximately spherical. In order to obtain better 3D representations, fits super-quadrics to bubble volume. The fitting process is based on non-linear least squares optimization method, where a super-quadric is adapted to a regular grid of points defined on each bubble. All methods were applied to real and semi-synthetical data where artificial and randomly deformed bubbles were embedded in the interior of healthy lungs. Quantitative results regarding bubble geometric features are either similar to a priori known values used in simulation tests, or indicate clinically acceptable dimensions and locations when dealing with real data.

  10. Airflow Measurement of the Car HVAC Unit Using Hot-wire Anemometry

    NASA Astrophysics Data System (ADS)

    Fojtlín, Miloš; Planka, Michal; Fišer, Jan; Pokorný, Jan; Jícha, Miroslav

    2016-03-01

    Thermal environment in a vehicular cabin significantly influence drivers' fatigue and passengers' thermal comfort. This environment is traditionally managed by HVAC cabin system that distributes air and modifies its properties. In order to simulate cabin thermal behaviour, amount of the air led through car vents must be determined. The aim of this study was to develop methodology to measure airflow from the vents, and consequently calculate corresponding air distribution coefficients. Three climatic cases were selected to match European winter, summer, and spring / fall conditions. Experiments were conducted on a test vehicle in a climatic chamber. The car HVAC system was set to automatic control mode, and the measurements were executed after the system stabilisation—each case was independently measured three times. To be able to evaluate precision of the method, the airflow was determined at the system inlet (HVAC suction) and outlet (each vent), and the total airflow values were compared. The airflow was calculated by determining a mean value of the air velocity multiplied by an area of inlet / outlet cross-section. Hot-wire anemometry was involved to measure the air velocity. Regarding the summer case, total airflow entering the cabin was around 57 l s-1 with 60 % of the air entering the cabin through dashboard vents; no air was supplied to the feet compartment. The remaining cases had the same total airflow of around 42 l s-1, and the air distribution was focused mainly on feet and windows. The inlet and outlet airflow values show a good match with a maximum mass differential of 8.3 %.

  11. Fluid volume displacement at the oval and round windows with air and bone conduction stimulation

    NASA Astrophysics Data System (ADS)

    Stenfelt, Stefan; Hato, Naohito; Goode, Richard L.

    2004-02-01

    The fluids in the cochlea are normally considered incompressible, and the fluid volume displacement of the oval window (OW) and the round window (RW) should be equal and of opposite phase. However, other channels, such as the cochlear and vestibular aqueducts, may affect the fluid flow. To test if the OW and RW fluid flows are equal and of opposite phase, the volume displacement was assessed by multiple point measurement at the windows with a laser Doppler vibrometer. This was done during air conduction (AC) stimulation in seven fresh human temporal bones, and with bone conduction (BC) stimulation in eight temporal bones and one human cadaver head. With AC stimulation, the average volume displacement of the two windows is within 3 dB, and the phase difference is close to 180° for the frequency range 0.1 to 10 kHz. With BC stimulation, the average volume displacement difference between the two windows is greater: below 2 kHz, the volume displacement at the RW is 5 to 15 dB greater than at the OW and above 2 kHz more fluid is displaced at the OW. With BC stimulation, lesions at the OW caused only minor changes of the fluid flow at the RW.

  12. Deposition of biological aerosols on HVAC heat exchangers

    SciTech Connect

    Siegel, Jeffrey; Walker, Ian

    2001-09-01

    Many biologically active materials are transported as bioaerosols 1-10 {micro}m in diameter. These particles can deposit on cooling and heating coils and lead to serious indoor air quality problems. This paper investigates several of the mechanisms that lead to aerosol deposition on fin and tube heat exchangers. A model has been developed that incorporates the effects of several deposition mechanisms, including impaction, Brownian and turbulent diffusion, turbophoresis, thermophoresis, diffusiophoresis, and gravitational settling. The model is applied to a typical range of air velocities that are found in commercial and residential HVAC systems 1 - 6 m/s (200 - 1200 ft/min), particle diameters from 1 - 8 {micro}m, and fin spacings from 3.2 - 7.9 fins/cm (8 - 16 fins/inch or FPI). The results from the model are compared to results from an experimental apparatus that directly measures deposition on a 4.7 fins/cm (12 FPI) coil. The model agrees reasonably well with this measured data and suggests that cooling coils are an important sink for biological aerosols and consequently a potential source of indoor air quality problems.

  13. MODIFICATION AND EVALUATION OF A HIGH-VOLUME AIR SAMPLER FOR PESTICIDES AND SEMIVOLATILE INDUSTRIAL ORGANIC CHEMICALS

    EPA Science Inventory

    Previously we reported the development and evaluation of a high-volume air sampler for pesticides and other semivolatile industrial organic chemicals (1). This sampler has proved useful for monitoring airborne pesticides associated with agricultural applications (2) and polychlor...

  14. Fault detection, diagnosis, and data-driven modeling in HVAC chillers

    NASA Astrophysics Data System (ADS)

    Namburu, Setu M.; Luo, Jianhui; Azam, Mohammad; Choi, Kihoon; Pattipati, Krishna R.

    2005-05-01

    Heating, Ventilation and Air Conditioning (HVAC) systems constitute the largest portion of energy consumption equipment in residential and commercial facilities. Real-time health monitoring and fault diagnosis is essential for reliable and uninterrupted operation of these systems. Existing fault detection and diagnosis (FDD) schemes for HVAC systems are only suitable for a single operating mode with small numbers of faults, and most of the schemes are systemspecific. A generic real-time FDD scheme, applicable to all possible operating conditions, can significantly reduce HVAC equipment downtime, thus improving the efficiency of building energy management systems. This paper presents a FDD methodology for faults in centrifugal chillers. The FDD scheme compares the diagnostic performance of three data-driven techniques, namely support vector machines (SVM), principal component analysis (PCA), and partial least squares (PLS). In addition, a nominal model of a chiller that can predict system response under new operating conditions is developed using PLS. We used the benchmark data on a 90-ton real centrifugal chiller test equipment, provided by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), to demonstrate and validate our proposed diagnostic procedure. The database consists of data from sixty four monitored variables under nominal and eight fault conditions of different severities at twenty seven operating modes.

  15. Measuring Advances in HVAC Distribution System Design

    SciTech Connect

    Franconi, E.

    1998-05-01

    Substantial commercial building energy savings have been achieved by improving the performance of the HV AC distribution system. The energy savings result from distribution system design improvements, advanced control capabilities, and use of variable-speed motors. Yet, much of the commercial building stock remains equipped with inefficient systems. Contributing to this is the absence of a definition for distribution system efficiency as well as the analysis methods for quantifying performance. This research investigates the application of performance indices to assess design advancements in commercial building thermal distribution systems. The index definitions are based on a first and second law of thermodynamics analysis of the system. The second law or availability analysis enables the determination of the true efficiency of the system. Availability analysis is a convenient way to make system efficiency comparisons since performance is evaluated relative to an ideal process. A TRNSYS simulation model is developed to analyze the performance of two distribution system types, a constant air volume system and a variable air volume system, that serve one floor of a large office building. Performance indices are calculated using the simulation results to compare the performance of the two systems types in several locations. Changes in index values are compared to changes in plant energy, costs, and carbon emissions to explore the ability of the indices to estimate these quantities.

  16. Practical Study on HVAC Control Technology Based on the Learning Function and Optimum Multiple Objective Processes

    NASA Astrophysics Data System (ADS)

    Ueda, Haruka; Dazai, Ryota; Kaseda, Chosei; Ikaga, Toshiharu; Kato, Akihiro

    Demand among large office buildings for the energy-saving benefits of the HVAC (Heating, Ventilating and Air-Conditioning) System are increasing as more and more people become concerned with global environmental issues. However, immoderate measures taken in the interest of energy conservation may encroach on the thermal comfort and productivity level of office workers. Building management should satisfy both indoor thermal comfort and energy conservation while adapting to the many regulatory, social, climate, and other changes that occur during the lifespan of the building. This paper demonstrates how optimal control of the HVAC system, based on data modeling and the multi-objective optimal method, achieves an efficient equilibrium between thermal comfort and energy conservation.

  17. VARIABLE SPEED INTEGRATED INTELLIGENT HVAC BLOWER

    SciTech Connect

    Herman Wiegman; Charlie Stephens; Xiaoyue Liu; Ralph Carl; Sunny Zhuang; Paul Szczesny; Kamron Wright

    2003-09-23

    This comprehensive topical report discusses the key findings in the development of an advanced blower for HVAC applications. The benefits of rearward inclined blades over that of traditional forward inclined blades is well documented, and several prototype wheels are demonstrated in various housings. A comparison of retrofitted blowers to that of three typical units from the industry is presented. The design and modification of the blower housing is addressed and the impact of size limitations on static efficiency is discussed. The roadmap to rearward-inclined wheel technology insertion is presented and typical static efficiency gains are documented.

  18. Best practices guide for residential HVAC Retrofits

    SciTech Connect

    Walker, Iain S.

    2003-08-11

    This best practices guide for residential HVAC system retrofits is aimed at contractors who want guidance on delivering energy efficient, cost effective and innovative products. It has been developed around the idea of having packages of changes to the building HVAC system and building envelope that are climate and house construction dependent. These packages include materials, procedures and equipment and are designed to remove some of the guesswork from a builder, contractor, installer or homeowner decisions about how best to carry out HVAC changes. The packages are not meant to be taken as rigid requirements--instead they are systems engineered guidelines that form the basis for energy efficient retrofits. Similar approaches have been taken previously for new construction to develop extremely energy efficient homes that are comfortable safe and durable, and often cost less than standard construction. This is best epitomized by the Building America program whose partners have built thousands of residences throughout the U.S. using these principles. The differences between retrofitting and new construction tend to limit the changes one can make to a building, so these packages rely on relatively simple and non-intrusive technologies and techniques. The retrofits also focus on changes to a building that will give many years of service to the occupants. Another key aspect of these best practices is that we need to know how a house is working so that we know what parts have the potential for improvement. To do this we have put together a set of diagnostic tools that combine physical measurements and checklists/questionnaires. The measured test results, observations and homeowner answers to questions are used to direct us towards the best retrofits applicable to each individual house. The retrofits will depend on the current condition of the building envelope and HVAC system, the local climate, the construction methods used for the house, and the presence of various

  19. 27 CFR 30.66 - Table 6, showing respective volumes of alcohol and water and the specific gravity in both air and...

    Code of Federal Regulations, 2010 CFR

    2010-04-01

    ... respective volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor... volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor. This... gallon of water in air by the specific gravity in air of the spirits—8.32823 by 0.88862—the product...

  20. 27 CFR 30.66 - Table 6, showing respective volumes of alcohol and water and the specific gravity in both air and...

    Code of Federal Regulations, 2014 CFR

    2014-04-01

    ... respective volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor... volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor. This... gallon of water in air by the specific gravity in air of the spirits—8.32823 by 0.88862—the product...

  1. 27 CFR 30.66 - Table 6, showing respective volumes of alcohol and water and the specific gravity in both air and...

    Code of Federal Regulations, 2011 CFR

    2011-04-01

    ... respective volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor... volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor. This... gallon of water in air by the specific gravity in air of the spirits—8.32823 by 0.88862—the product...

  2. 27 CFR 30.66 - Table 6, showing respective volumes of alcohol and water and the specific gravity in both air and...

    Code of Federal Regulations, 2013 CFR

    2013-04-01

    ... respective volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor... volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor. This... gallon of water in air by the specific gravity in air of the spirits—8.32823 by 0.88862—the product...

  3. 27 CFR 30.66 - Table 6, showing respective volumes of alcohol and water and the specific gravity in both air and...

    Code of Federal Regulations, 2012 CFR

    2012-04-01

    ... respective volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor... volumes of alcohol and water and the specific gravity in both air and vacuum of spirituous liquor. This... gallon of water in air by the specific gravity in air of the spirits—8.32823 by 0.88862—the product...

  4. Proceedings of the 21st DOE/NRC nuclear air cleaning conference; Volume 2, Sessions 9--16

    SciTech Connect

    First, M.W.

    1991-02-01

    The 21st meeting of the Department of Energy/Nuclear Regulatory Commission (DOE/NRC) Nuclear Air Cleaning Conference was held in San Diego, CA on August 13--16, 1990. The proceedings have been published as a two volume set. Volume 2 contains sessions covering adsorbents, nuclear codes and standards, modelling, filters, safety, containment venting and a review of nuclear air cleaning programs around the world. Also included is the list of attendees and an index of authors and speakers. (MHB)

  5. HVAC & Building Management Control System Energy Efficiency Replacements

    SciTech Connect

    Hernandez, Adriana

    2012-09-21

    The project objective was the replacement of an aging, un-repairable HVAC system which has grown inefficient and a huge energy consumer with low energy and efficient HVAC units, and installation of energy efficient building control technologies at City's YMCA Community Center.

  6. 10 CFR 434.517 - HVAC systems and equipment.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... methods of analysis shall conform to those of subpart A of 10 CFR part 436. Energy costs shall be based on... RESIDENTIAL BUILDINGS Building Energy Cost Compliance Alternative § 434.517 HVAC systems and equipment. 517.1... 10 Energy 3 2014-01-01 2014-01-01 false HVAC systems and equipment. 434.517 Section 434.517...

  7. 10 CFR 434.517 - HVAC systems and equipment.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... methods of analysis shall conform to those of subpart A of 10 CFR part 436. Energy costs shall be based on... RESIDENTIAL BUILDINGS Building Energy Cost Compliance Alternative § 434.517 HVAC systems and equipment. 517... 10 Energy 3 2012-01-01 2012-01-01 false HVAC systems and equipment. 434.517 Section 434.517...

  8. Shuttle Entry Air Data System (SEADS) hardware development. Volume 2: History

    NASA Technical Reports Server (NTRS)

    While, D. M.

    1983-01-01

    Hardware development of the Shuttle Entry Air Data System (SEADS) is described. The system consists of an array of fourteen pressure ports, installed in an Orbiter nose cap, which, when coupled with existing fuselage mounted static pressure ports permits computation of entry flight parameters. Elements of the system that are described include the following: (1) penetration assemblies to place pressure port openings at the surface of the nose cap; (2) pressure tubes to transmit the surface pressure to transducers; (3) support posts or manifolds to provide support for, and reduce the length of, the individual pressure tubes; (4) insulation for the manifolds; and (5) a SEADS nose cap. Design, analyses, and tests to develop and certify design for flight are described. Specific tests included plasma arc exposure, radiant thermal, vibration, and structural. Volume one summarizes highlights of the program, particularly as they relate to the final design of SEADS. Volume two summarizes all of the Vought responsible activities in essentially a chronological order.

  9. Study of active noise control system for a commercial HVAC unit

    NASA Astrophysics Data System (ADS)

    Devineni, Naga

    Acoustic noise is a common problem in everyday life. If the appliances that are present in the work and living areas generate noise then it's a serious problem. One such appliance is the Heating, Ventilation and Air-conditioning system (HVAC) in which blower fan and compressor units are housed together. Operation of a HVAC system creates two kinds of noise. One is the noise due to the air flow and the other is the result of the compressor. Both of them exhibit different signal properties and need different strategies to control them. There has been previous efforts in designing noise control systems that can control noise from the HVAC system. These include passive methods which use sound absorption materials to attenuate noise and active methods which cancel noise by generating anti-noise. Passive methods are effective in limiting the high frequency noise, but are inefficient in controlling low frequency noise from the compressor. Compressor noise is one of the strong low frequency components that propagate through the walls, therefore there is need for deploying active signal processing methods that consider the signal properties into consideration to cancel the noise acoustically. The quasi periodic nature of the compressor noise is exploited in noise modeling which aids in implementing an adaptive linear prediction filter in estimating the anti noise [12]. In this thesis, a multi channel architecture has been studied for a specific HVAC system in order to improve noise cancellation by creating larger quiet zone. In addition to the multi-channel architecture, a real time narrow band Active Noise Control (ANC) was employed to cancel noise under practical conditions.

  10. Estimates of HVAC filtration efficiency for fine and ultrafine particles of outdoor origin

    NASA Astrophysics Data System (ADS)

    Azimi, Parham; Zhao, Dan; Stephens, Brent

    2014-12-01

    This work uses 194 outdoor particle size distributions (PSDs) from the literature to estimate single-pass heating, ventilating, and air-conditioning (HVAC) filter removal efficiencies for PM2.5 and ultrafine particles (UFPs: <100 nm) of outdoor origin. The PSDs were first fitted to tri-modal lognormal distributions and then mapped to size-resolved particle removal efficiency of a wide range of HVAC filters identified in the literature. Filters included those with a minimum efficiency reporting value (MERV) of 5, 6, 7, 8, 10, 12, 14, and 16, as well as HEPA filters. We demonstrate that although the MERV metric defined in ASHRAE Standard 52.2 does not explicitly account for UFP or PM2.5 removal efficiency, estimates of filtration efficiency for both size fractions increased with increasing MERV. Our results also indicate that outdoor PSD characteristics and assumptions for particle density and typical size-resolved infiltration factors (in the absence of HVAC filtration) do not drastically impact estimates of HVAC filter removal efficiencies for PM2.5. The impact of these factors is greater for UFPs; however, they are also somewhat predictable. Despite these findings, our results also suggest that MERV alone cannot always be used to predict UFP or PM2.5 removal efficiency given the various size-resolved removal efficiencies of different makes and models, particularly for MERV 7 and MERV 12 filters. This information improves knowledge of how the MERV designation relates to PM2.5 and UFP removal efficiency for indoor particles of outdoor origin. Results can be used to simplify indoor air quality modeling efforts and inform standards and guidelines.

  11. Mexico City air quality research initiative. Volume IV. Characterization and measurement

    SciTech Connect

    Mauzy, A.

    1994-04-01

    This volume describes the methods and the data gathered in an attempt to measure and characterize the meteorological factors and the concentration of different pollutants in the Mexico City Metropolitan Area. The main objective of this document was to provide input for the simulation models and to obtain information that could be used to test and improve the models` performance. Four field campaigns were conducted, as well as routine monitoring, in order to obtain a database of atmospheric dynamics and air pollution characteristics. Sections include Airborne measurements, Remote sensing measurements, and Traditional (in situ) measurements.

  12. Exposure to Severe Urban Air Pollution Influences Cognitive Outcomes, Brain Volume and Systemic Inflammation in Clinically Healthy Children

    ERIC Educational Resources Information Center

    Calderon-Garciduenas, Lilian; Engle, Randall; Mora-Tiscareno, Antonieta; Styner, Martin; Gomez-Garza, Gilberto; Zhu, Hongtu; Jewells, Valerie; Torres-Jardon, Ricardo; Romero, Lina; Monroy-Acosta, Maria E.; Bryant, Christopher; Gonzalez-Gonzalez, Luis Oscar; Medina-Cortina, Humberto; D'Angiulli, Amedeo

    2011-01-01

    Exposure to severe air pollution produces neuroinflammation and structural brain alterations in children. We tested whether patterns of brain growth, cognitive deficits and white matter hyperintensities (WMH) are associated with exposures to severe air pollution. Baseline and 1 year follow-up measurements of global and regional brain MRI volumes,…

  13. The Conference Proceedings of the 1998 Air Transport Research Group (ATRG) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Oum, Tae Hoon (Editor); Bowen, Brent D. (Editor)

    1998-01-01

    This report (Volume 1) is comprised of 5 sessions of the Air Transport Research Group (ATRG) Conference held in Antwerp, Belgium, July 1998. The sessions contain 3-4 papers (presentations) each. The session numbers and their respective headings are: (1) Airline alliances; (2) Airline Competition and Market Structure; (4) Liberalization, Open Skies, and Policy Issues; (5) Yield Management and Other Models; and (11) Air Traffic Control (ATC) and Air Navigational Systems (ANS).

  14. Patrick Air Force Base integrated resource assessment. Volume 2, Baseline detail

    SciTech Connect

    Wahlstrom, R.R.; King, D.A.; Parker, S.A.; Sandusky, W.F.

    1993-08-01

    The US Air Force has tasked the Pacific Northwest Laboratory (PNL), in support of the US Department of Energy (DOE) Federal Energy Management Program (FEMP), to assess energy use at Patrick Air Force Base (AFB). The information obtained from this assessment will be used in identifying energy resource opportunities to reduce overall energy consumption on the base. The primary focus of this report is to assess the current baseline energy consumption at Patrick AFB. It is a comparison report to Volume 1, the Executive Summary, and Volume 3, the Resource Assessment. This assessment requires that information be obtained and characterized for buildings, utilities, energy sources, energy uses, and load profile information to be used to improve the characterization of energy use on the base. The characteristics of electricity, natural gas, and No. 2 fuel oil are analyzed for on-base facilities and housing. The assessment examines basic regional information used to determine energy-use intensity (EUI) values for Patrick AFB facilities by building, fuel type, and energy end use. It also provides a summary of electricity consumption from Florida Power and Light Company (FPL) metered data for 1985-1991. Load profile information obtained from FPL data is presented for the north and south substations for the four seasons of the year, including weekdays and weekends.

  15. Patrick Air Force Base integrated resource assessment. Volume 3, Resource assessment

    SciTech Connect

    Sandusky, W.F.; Parker, S.A.; King, D.A.; Wahlstrom, R.R.; Elliott, D.B.; Shankle, S.A.

    1993-12-01

    The US Air Force has tasked the Pacific Northwest Laboratory (PNL) in support of the US Department of Energy Federal Energy Management Program to identify, evaluate, and assist in acquiring all cost effective energy projects at Patrick Air Force Base (AFB). This is part of a model program that PNL is designing to support energy-use decisions in the federal sector. This report provides the results of the fossil fuel and electric energy resource opportunity (ERO) assessments performed by PNL at Patrick AFB which is located south of Cocoa Beach, Florida. It is a companion report to Volume 1, Executive Summary, and Volume.2, Baseline Detail. The results of the analyses of EROs are presented in 11 common energy end-use categories. A narrative description of each ERO is provided, including information on the installed cost, energy and dollar savings, impacts on operations and maintenance, and, when applicable, a discussion of energy supply and demand, energy security, and environmental issues. A description of the evaluation methodologies and technical and cost assumptions is also provided for each ERO. Summary tables present the cost-effectiveness of energy end-use equipment before and after the implementation of each ERO and present the results of the life-cycle cost analysis indicating the net present value and value index of each ERO.

  16. Robins Air Force Base integrated resource assessment. Volume 3, Resource assessment

    SciTech Connect

    Sullivan, G.P.; Keller, J.M.; Stucky, D.J.; Wahlstrom, R.R.; Larson, L.L.

    1993-10-01

    The US Air Force Materiel Command (AFMC) has tasked the US Department of Energy (DOE) Federal Energy Management Program (FEMP), supported by the Pacific Northwest Laboratory (PNL), to identify, evaluate, and assist in acquiring all cost-effective energy projects at Robins Air Force Base (AFB). This is part of a model program that PNL is designing to support energy-use decisions in the federal sector. This report provides the results of the fossil fuel and electric energy resource opportunity (ERO) assessments performed by PNL at the AFMC Robins AFB facility located approximately 15 miles south of Macon, Georgia. It is a companion report to Volume 1, Executive Summary, and Volume 2, Baseline Detail. The results of the analyses of EROs are presented in 13 common energy end-use categories (e.g., boilers and furnaces, service hot water, and building lighting). A narrative-description of each ERO is provided, including information on the installed cost, energy and dollar savings; impacts on operation and maintenance (O&M); and, when applicable, a discussion of energy supply and demand, energy security, and environmental issues. A description of the evaluation methodologies and technical and cost assumptions is also provided for each ERO. Summary tables present the cost-effectiveness of energy end-use equipment before and after the implementation of each ERO and present the results of the life-cycle cost (LCC) analysis indicating the net present value (NPV) and savings to investment ratio (SIR) of each ERO.

  17. Cape Canaveral Air Force Station integrated resource assessment. Volume 2, Baseline detail

    SciTech Connect

    Wahlstrom, R.R.; McMordie, K.L.; Parker, S.A.; King, D.A.; Sandusky, W.F.

    1993-12-01

    The US Air Force (USAF) has tasked the Pacific Northwest Laboratory (PNL), in support of the US Department of Energy (DOE) Federal Energy Management Program (FEMP), to assess energy use at Cape Canaveral Air Force Station (AFS). The information obtained from this assessment will be used in identifying energy resource opportunities to reduce overall energy consumption by the station. The primary focus of this report is to assess the current baseline energy consumption at Cape Canaveral AFS. It is A companion report to Volume 1, the Executive Summary, and Volume 3, the Resource Assessment. This assessment requires that information be obtained and characterized for buildings, utilities, energy sources, energy uses, and load profiles to be used to improve the current energy system on the station. The characteristics of electricity, diesel fuel, No. 2 fuel oil, and motor vehicle gasoline (MOGAS) are analyzed for on-base facilities. The assessment examines basic regional information used to determine energy-use intensity (EUI) values for Cape Canaveral AFS facilities by building, fuel type, and energy end use. It also provides a summary of electricity consumption from Florida Power and Light Company (FPL) metered data for 1985--1991. Load profile information obtained from FPL data is presented for the North, South, and Titan Substations for the four seasons of the year, including weekdays and weekends.

  18. X-ray radiation from the volume discharge in atmospheric-pressure air

    NASA Astrophysics Data System (ADS)

    Bratchikov, V. B.; Gagarinov, K. A.; Kostyrya, I. D.; Tarasenko, V. F.; Tkachev, A. N.; Yakovlenko, S. I.

    2007-07-01

    X-ray radiation from the volume discharge in atmospheric-pressure air is studied under the conditions when the voltage pulse rise time varies from 0.5 to 100 ns and the open-circuit voltage amplitude of the generator varies from 20 to 750 kV. It is shown that a volume discharge from a needle-like cathode forms at a relatively wide voltage pulse (to ≈60 ns in this work). The volume character of the discharge is due to preionization by fast electrons, which arise when the electric field concentrates at the cathode and in the discharge gap. As the voltage pulse rise time grows, X-ray radiation comes largely from the discharge gap in accordance with previous experiments. Propagation of fast avalanche electrons in nitrogen subjected to a nonuniform unsteady electric field is simulated. It is demonstrated that the amount of hard X-ray photons grows not only with increasing voltage amplitude but also with shortening pulse rise time.

  19. Evaluation of sampling methods for Bacillus spore-contaminated HVAC filters

    PubMed Central

    Calfee, M. Worth; Rose, Laura J.; Tufts, Jenia; Morse, Stephen; Clayton, Matt; Touati, Abderrahmane; Griffin-Gatchalian, Nicole; Slone, Christina; McSweeney, Neal

    2016-01-01

    The objective of this study was to compare an extraction-based sampling method to two vacuum-based sampling methods (vacuum sock and 37 mm cassette filter) with regards to their ability to recover Bacillus atrophaeus spores (surrogate for Bacillus anthracis) from pleated heating, ventilation, and air conditioning (HVAC) filters that are typically found in commercial and residential buildings. Electrostatic and mechanical HVAC filters were tested, both without and after loading with dust to 50% of their total holding capacity. The results were analyzed by one-way ANOVA across material types, presence or absence of dust, and sampling device. The extraction method gave higher relative recoveries than the two vacuum methods evaluated (p ≤ 0.001). On average, recoveries obtained by the vacuum methods were about 30% of those achieved by the extraction method. Relative recoveries between the two vacuum methods were not significantly different (p > 0.05). Although extraction methods yielded higher recoveries than vacuum methods, either HVAC filter sampling approach may provide a rapid and inexpensive mechanism for understanding the extent of contamination following a wide-area biological release incident. PMID:24184312

  20. Evaluation of sampling methods for Bacillus spore-contaminated HVAC filters.

    PubMed

    Calfee, M Worth; Rose, Laura J; Tufts, Jenia; Morse, Stephen; Clayton, Matt; Touati, Abderrahmane; Griffin-Gatchalian, Nicole; Slone, Christina; McSweeney, Neal

    2014-01-01

    The objective of this study was to compare an extraction-based sampling method to two vacuum-based sampling methods (vacuum sock and 37mm cassette filter) with regards to their ability to recover Bacillus atrophaeus spores (surrogate for Bacillus anthracis) from pleated heating, ventilation, and air conditioning (HVAC) filters that are typically found in commercial and residential buildings. Electrostatic and mechanical HVAC filters were tested, both without and after loading with dust to 50% of their total holding capacity. The results were analyzed by one-way ANOVA across material types, presence or absence of dust, and sampling device. The extraction method gave higher relative recoveries than the two vacuum methods evaluated (p≤0.001). On average, recoveries obtained by the vacuum methods were about 30% of those achieved by the extraction method. Relative recoveries between the two vacuum methods were not significantly different (p>0.05). Although extraction methods yielded higher recoveries than vacuum methods, either HVAC filter sampling approach may provide a rapid and inexpensive mechanism for understanding the extent of contamination following a wide-area biological release incident. PMID:24184312

  1. The Impact of Uncertain Physical Parameters on HVAC Demand Response

    SciTech Connect

    Sun, Yannan; Elizondo, Marcelo A.; Lu, Shuai; Fuller, Jason C.

    2014-03-01

    HVAC units are currently one of the major resources providing demand response (DR) in residential buildings. Models of HVAC with DR function can improve understanding of its impact on power system operations and facilitate the deployment of DR technologies. This paper investigates the importance of various physical parameters and their distributions to the HVAC response to DR signals, which is a key step to the construction of HVAC models for a population of units with insufficient data. These parameters include the size of floors, insulation efficiency, the amount of solid mass in the house, and efficiency of the HVAC units. These parameters are usually assumed to follow Gaussian or Uniform distributions. We study the effect of uncertainty in the chosen parameter distributions on the aggregate HVAC response to DR signals, during transient phase and in steady state. We use a quasi-Monte Carlo sampling method with linear regression and Prony analysis to evaluate sensitivity of DR output to the uncertainty in the distribution parameters. The significance ranking on the uncertainty sources is given for future guidance in the modeling of HVAC demand response.

  2. Classroom HVAC: Improving ventilation and saving energy -- field study plan

    SciTech Connect

    Apte, Michael G.; Faulkner, David; Hodgson, Alfred T.; Sullivan, Douglas P.

    2004-10-14

    The primary goals of this research effort are to develop, evaluate, and demonstrate a very practical HVAC system for classrooms that consistently provides classrooms (CRs) with the quantity of ventilation in current minimum standards, while saving energy, and reducing HVAC-related noise levels. This research is motivated by the public benefits of energy efficiency, evidence that many CRs are under-ventilated, and public concerns about indoor environmental quality in CRs. This document provides a summary of the detailed plans developed for the field study that will take place in 2005 to evaluate the energy and IAQ performance of a new classroom HVAC technology. The field study will include measurements of HVAC energy use, ventilation rates, and IEQ conditions in 10 classrooms with the new HVAC technology and in six control classrooms with a standard HVAC system. Energy use and many IEQ parameters will be monitored continuously, while other IEQ measurements will be will be performed seasonally. Continuously monitored data will be remotely accessed via a LonWorks network. Instrument calibration plans that vary with the type of instrumentation used are established. Statistical tests will be employed to compare energy use and IEQ conditions with the new and standard HVAC systems. Strengths of this study plan include the collection of real time data for a full school year, the use of high quality instrumentation, the incorporation of many quality control measures, and the extensive collaborations with industry that limit costs to the sponsors.

  3. SU-E-I-84: Accuracy Comparison of Multi-Modality Image-Based Volumes of Rodent Solid Tumors Using In-Air Micro-CT Image Volume

    SciTech Connect

    Lee, Y; Fullerton, G; Goins, B

    2015-06-15

    Purpose: Tumor volume is considered as a better predictor for therapy response monitoring and tumor staging over Response Evaluation Criteria In Solid Tumors (RECIST) or World Health Organization (WHO) criteria. In this study, the accuracy of subcutaneous rodent tumor volumes using preclinical magnetic resonance imaging (MRI), micro-computed tomography (micro-CT) and ultrasound (US) equipment and with an external caliper was compared using in-air micro-CT image volume of excised tumors determined as reference tumor volume in our prior study. Methods: MR, US and micro-CT images of subcutaneous SCC4 head and neck tumor xenografts were acquired 4, 6, 9, 11 and 13 days after tumor cell inoculation. Before MR and US scans, caliper measurements were made. After tumors were excised, in-air micro-CT imaging and ex vivo caliper measurements were performed. Tumor volumes were calculated using formula V = (π/6)*a*b*c where a, b and c are the maximum diameters in three perpendicular dimensions determined by the three image modalities and caliper, and compared with reference tumor volume by linear regression analysis as well as Bland-Altman plots. A one-way Analysis of Variance (ANOVA) test was also performed to compare volumes among caliper measurements. Results: The correlation coefficients (R2) of the regression lines for tumor volumes measured by the three imaging modalities and caliper were 0.9939, 0.9669, 0.9806, 0.9274, 0.9619 and 0.9819 for MRI, US and micro-CT, caliperbeforeMRI, caliperbeforeUS and ex vivo caliper respectively. In Bland-Altman plots, the average of tumor volume difference from reference tumor volume (bias) was significant for caliper and micro- CT, but not for MRI and US. Comparison of caliper measurements showed a significant difference (p < 0.05). Conclusion: Using the in-air micro-CT image volume, tumor volume measured by MRI was the most accurate among the three imaging modalities. In vivo caliper volume measurements showed unreliability while ex

  4. Energy Savings Potential of Flexible and Adaptive HVAC Distribution Systems for Office Buildings

    SciTech Connect

    Loftness, Vivian; Brahme, Rohini; Mondazzi, Michelle; Vineyard, Edward; MacDonald, Michael

    2002-06-01

    It has been understood by architects and engineers that office buildings with easily re-configurable space and flexible mechanical and electrical systems are able to provide comfort that increases worker productivity while using less energy. Raised floors are an example of how fresh air, thermal conditioning, lighting needs, and network access can be delivered in a flexible manner that is not ''embedded'' within the structure. What are not yet documented is how well these systems perform and how much energy they can save. This area is being investigated in phased projects of the 21st Century Research Program of the Air-conditioning and Refrigeration Technology Institute. For the initial project, research teams at the Center for Building Performance and Diagnostics, Pittsburgh, Pennsylvania, and Oak Ridge National Laboratory, Oak Ridge, Tennessee, documented the diversity, performance, and incidence of flexible and adaptive HVAC systems. Information was gathered worldwide from journal and conference articles, case studies, manufactured products and assemblies, and interviews with design professionals. Their report thoroughly describes the variety of system types along with the various design alternatives observed for plenums, diffusers, individual control, and system integration. Many of the systems are illustrated in the report and the authors provide quantitative and qualitative comparisons. Among conclusions regarding key design issues, and barriers to widespread adoption, the authors state that flexible and adaptive HVAC systems, such as underfloor air, perform as well if not better than ceiling-based systems. Leading engineers have become active proponents after their first experience, which is resulting in these flexible and adaptive HVAC systems approaching 10 percent of the new construction market. To encourage adoption of this technology that improves thermal comfort and indoor air quality, follow-on work is required to further document performance

  5. Heat recovery and the economizer for HVAC systems

    SciTech Connect

    Anantapantula, V.S. . Alco Controls Div.); Sauer, H.J. Jr. )

    1994-11-01

    This articles examines why a combined heat reclaim/economizer system with priority to heat reclaim operation is most likely to result in the least annual total HVAC energy. PC-based, hour-by-hour simulation programs evaluate annual HVAC energy requirements when using combined operation of heat reclaim and economizer cycle, while giving priority to operation of either one. These simulation programs also enable the design engineer to select the most viable heat reclaim and/or economizer system for any given type of HVAC system serving the building internal load level, building geographical location and other building/system variables.

  6. Southern california offshore air quality model validation study. Volume I: executive summary. Final report

    SciTech Connect

    Zannetti, P.; Wilbur, D.M.; Baxter, R.A.

    1981-11-01

    This volume summarizes the significant results of a BLM-funded study conducted jointly by AeroVironment Inc. and the Naval Postgraduate School to validate and/or modify screening models commonly used to predict onshore air quality impacts from outer continental shelf (OCS) emission sources. The study involved both field experiments and computer modeling analysis to give a better understanding of dispersion over water and at the land/sea interface. Two field experiments were performed releasing SF6 tracer gas from a research vessel offshore the Ventura-Oxnard, California coastal area in September, 1980 and January, 1981. Modifications are discussed for standard Gaussian models to predict peak plume concentration values, the horizontal and vertical shape of the plume, and peak ground-level impacts from OCS emission sources.

  7. Southern california offshore air quality model validation study. Volume II: synthesis of findings. Final report

    SciTech Connect

    Zannetti, P.; Wilbur, D.M.; Baxter, R.A.

    1981-11-01

    This volume describes the significant results of a BLM-funded study conducted jointly by AeroVironment Inc. and the Naval Postgraduate School to validate and/or modify screening models commonly used to predict onshore air quality impacts from outer continental shelf (OCS) emission sources. The study involved both field experiments and computer modeling analysis to give a better understanding of dispersion over water and at the land/sea interface. Two field experiments were performed releasing SF tracer gas from a research vessel offshore the Ventura-Oxnard, California coastal area in September, 1980 and January, 1981. Modifications are discussed for standard Gaussian models to predict peak plume concentration values, the horizontal and vertical shape of the plume, and peak ground-level impacts from OCS emission sources.

  8. Venturi air-jet vacuum ejectors for high-volume atmospheric sampling on aircraft platforms

    NASA Technical Reports Server (NTRS)

    Hill, Gerald F.; Sachse, Glen W.; Young, Douglas C.; Wade, Larry O.; Burney, Lewis G.

    1992-01-01

    Documentation of the installation and use of venturi air-jet vacuum ejectors for high-volume atmospheric sampling on aircraft platforms is presented. Information on the types of venturis that are useful for meeting the pumping requirements of atmospheric-sampling experiments is also presented. A description of the configuration and installation of the venturi system vacuum line is included with details on the modifications that were made to adapt a venturi to the NASA Electra aircraft at GSFC, Wallops Flight Facility. Flight test results are given for several venturis with emphasis on applications to the Differential Absorption Carbon Monoxide Measurement (DACOM) system at LaRC. This is a source document for atmospheric scientists interested in using the venturi systems installed on the NASA Electra or adapting the technology to other aircraft.

  9. Demand modelling of passenger air travel: An analysis and extension, volume 2

    NASA Technical Reports Server (NTRS)

    Jacobson, I. D.

    1978-01-01

    Previous intercity travel demand models in terms of their ability to predict air travel in a useful way and the need for disaggregation in the approach to demand modelling are evaluated. The viability of incorporating non-conventional factors (i.e. non-econometric, such as time and cost) in travel demand forecasting models are determined. The investigation of existing models is carried out in order to provide insight into their strong points and shortcomings. The model is characterized as a market segmentation model. This is a consequence of the strengths of disaggregation and its natural evolution to a usable aggregate formulation. The need for this approach both pedagogically and mathematically is discussed. In addition this volume contains two appendices which should prove useful to the non-specialist in the area.

  10. Outdoor airflow into HVAC systems: An evaluation of measurement technologies

    SciTech Connect

    Fisk, William J.; Faulkner, David; Sullivan, Douglas P.; Delp, Woody

    2003-09-01

    During the last few years, new technologies have been introduced for measuring the flow rates of outdoor air (OA) into HVAC systems; however, an evaluation of these measurement technologies has not previously been published. This document describes a test system and protocols developed for controlled evaluation of these measurement technologies. The results of tests of three measurement technologies are also summarized. The test system and protocol were judged practical and very useful. The test results indicate that one measurement technology can measure OA flow rates with errors of 20% or less without a field-based calibration, as long as the OA velocities are sufficient to provide an accurately measurable pressure signal. The test results for a second measurement technology are similar; however, a difficult field-based calibration relating the OA flow rate with the pressure signal would be required to reduce errors below approximately 30%. The errors in OA flow rates measured with the third measurement technology, that uses six electronic airspeed sensors downstream of the OA inlet louver, exceeded 100%; however, these errors could be substantially reduced through a difficult field based calibration. The effects of wind on the accuracy of these measurement technologies still needs to be evaluated.

  11. State-of-the-art sports facility's HVAC

    SciTech Connect

    Horton, M.K. )

    1994-08-01

    This article describes the HVAC systems design to keep Cleveland's new Gateway sports and entertainment complex comfortable. This magnificent new facility embraces the 42,000-seat Jacobs Field, with its natural grass playing surface, and the 21,000-seat Arena at Gateway (the official name will be announced at its August 1 opening). The Arena is the new home of the Cleveland Cavaliers NBA basketball team and the Lumberjacks IHL ice hockey team. Other events that will be held here include arena football, circuses, ice shows, and concerts. It is anticipated that the Arena will be in use in excess of 200 days a year for these and other functions. The ballpark and the arena are separated by Gateway Plaza, a large illuminated public space that also will be the site of various entertainment events. An air conditioned pedestrian bridge, approximately 0.7 miles in length, connects the Arena with the Regional Transit Authority's downtown rapid transit station. Other enclosed walkways connect the Arena with two parking garages (3,158 vehicles total) and the larger garage with Jacobs Field.

  12. METHODS DEVELOPMENT FOR ASSESSING AIR POLLUTION CONTROL BENEFITS. VOLUME III. A PRELIMINARY ASSESSMENT OF AIR POLLUTION DAMAGES FOR SELECTED CROPS WITHIN SOUTHERN CALIFORNIA

    EPA Science Inventory

    This volume investigates the economic benefits that would accrue from reductions in oxidant/ozone air pollution-induced damages to 14 annual vegetable and field crops in southern California. Using the analytical perspective of economics, the study provides an up-to-date review of...

  13. Deflagration to detonation transition on large confined volume of lean hydrogen-air mixtures

    SciTech Connect

    Dorofeev, S.B.; Sidorov, V.P.; Dvoinishnikov, A.E.; Breitung, W.

    1996-01-01

    The results of large-scale experiments on turbulent flame propagation and transition to detonation in a confined volume of lean hydrogen-air mixtures are presented. The experiments were in a strong concrete enclosure of 480 m{sup 3}, and of 69.9 m length. The experimental volume consists first of a channel (34.6 m length, 2.3 m height, 2.5 m width) with or without obstacles, a canyon (10.55 {times} 6.3 {times} 2.5 m), and a final channel. Ignition was with a weak electric spark at the beginning of the first channel. The effect of hydrogen concentration (9.8%--14% vol.) on turbulent flame propagation and transition to detonation was studied. The obstacle configuration in the first channel (blockage ratio 0.3, 0.6, and no obstacles), exit cross section to the canyon (1.4, 2, and 5.6 m{sup 2}), and vent area at the end (0, 2.5, and 4 m{sup 2}) were varied in the tests. Details of turbulent flame propagation, of pressure field, and of detonation onset are presented. A minimum of 12.5% of hydrogen was found to be necessary for transition to detonation. This is a much less sensitive mixture than those in which the onset of spontaneous detonation has previously been observed (minimum of 15% of hydrogen in air). The effect of scale on the onset conditions for spontaneous detonation is discussed. The characteristic geometrical size of the mixture for transition to detonation is shown to be strongly related to the mixture sensitivity.

  14. Cape Canaveral Air Force Station integrated resource assessment. Volume 3, Resource assessment

    SciTech Connect

    Sandusky, W.F.; Eichman, C.J.; King, D.A.; McMordie, K.L.; Parker, S.A.; Shankle, S.A.; Wahlstrom, R.R.

    1994-03-01

    The U.S. Air Force (USAF) has tasked the Pacific Northwest Laboratory (PNL) in support of the U.S. Department of Energy (DOE) Federal Energy Management Program (FEMP), to identify, evaluate, and assist in acquiring all cost-effective energy projects at Cape Canaveral Air Force Station (AFS). Projects considered can be either in the form of energy management or energy conservation. The overall efforts of this task are based on a model program PNL is designing to support energy-use decisions in the federal sector. This report provides the results of the fossil fuel and electric energy resource opportunity (ERO) assessments performed by PNL at Cape Canaveral AFS, which is located approximately 10 miles north of Cocoa Beach, Florida. It is a companion report to Volume 1: Executive Summary and Volume 2: Baseline Detail. The results of the analyses of EROs are presented in 11 common energy end-use categories (e.g., boilers and furnaces, service hot water, and building lighting). A narrative description of each ERO is provided, including information on the installed cost, energy and dollar savings, impacts on operations and maintenance (O&M), and, when applicable, a discussion of energy supply and demand, energy security, and environmental issues. Descriptions of the evaluation methodologies and technical and cost assumptions are also provided for each ERO. Summary tables present the cost- effectiveness of energy end-use equipment before and after the implementation of each ERO and present the results of the life-cycle cost (LCC) analysis, indicating the net present value (NPV) and savings-to-investment ratio (SIR) of each ERO.

  15. Vandenberg Air Force Base integrated resource assessment. Volume 3, Resource assessment

    SciTech Connect

    Daellenbach, K.K.; Dagle, J.E.; Dittmer, A.L.; Elliott, D.B.; Halverson, M.A.; Hickman, B.J.; Parker, G.B.; Richman, E.E.; Shankle, S.A.

    1993-06-01

    The US Air Force Space Command (SPACECOM) has tasked the Pacific Northwest Laboratory (PNL), as the lead laboratory supporting the US Department of Energy (DOE) Federal Energy Management Program (FEMP), to identify, evaluate, and assist in acquiring all cost-effective energy projects at Vandenberg Air Force Base (VAFB). This is part of a model program that PNL is designing to support energy-use decisions in the federal sector. This report provides the results of the fossil fuel and electric energy resource opportunity (ERO) assessments performed by PNL at the SPACECOM VAFB facility located approximately 50 miles northwest of Santa Barbara, California. It is a companion report to Volume 1, Executive Summary, and Volume 2, Baseline Detail. The results of the analysis of EROs are presented in ten common energy end-use categories (e.g., boilers and furnaces, service hot water, and building lighting). In addition, a case study of process loads at Space Launch Complex-4 (SLC-4) is included. A narrative description of each ERO is provided, including information on the installed cost, energy and dollar savings; impacts on operation and maintenance (O and M); and, when applicable, a discussion of energy supply and demand, energy security, and environmental issues. A description of the evaluation methodologies and technical and cost assumptions is also provided for each ERO. Summary tables present the cost-effectiveness of energy end-use equipment before and after the implementation of each ERO and present the results of the life-cycle cost (LCC) analysis indicating the net present value (NPV) and value index (VI) of each ERO. Finally, an appendix includes a summary of an economic analysis case study of the South Vandenberg Power Plant (SVPP) operating scenarios.

  16. Vandenberg Air Force Base integrated resource assessment. Volume 2, Baseline detail

    SciTech Connect

    Halverson, M.A.; Richman, E.E.; Dagle, J.E.; Hickman, B.J.; Daellenbach, K.K.; Sullivan, G.P.

    1993-06-01

    The US Air Force Space Command has tasked the Pacific Northwest Laboratory, as the lead laboratory supporting the US Department of Energy Federal Energy Management Program, to identify, evaluate, and assist in acquiring all cost-effective energy projects at Vandenberg Air Force Base (VAFB). This is a model program PNL is designing for federal customers served by the Pacific Gas and Electric Company (PG and E). The primary goal of the VAFB project is to identify all electric energy efficiency opportunities, and to negotiate with PG and E to acquire those resources through a customized demand-side management program for its federal clients. That customized program should have three major characteristics: (1) 100% up-front financing; (2) substantial utility cost-sharing; and (3) utility implementation through energy service companies under contract to the utility. A similar arrangement will be pursued with Southern California Gas for non-electric resource opportunities if that is deemed desirable by the site and if the gas utility seems open to such an approach. This report documents the assessment of baseline energy use at VAFB located near Lompoc, California. It is a companion report to Volume 1, Executive Summary, and Volume 3, Resource Assessment. This analysis examines the characteristics of electric, natural gas, fuel oil, and propane use for fiscal year 1991. It records energy-use intensities for the facilities at VAFB by building type and energy end use. It also breaks down building energy consumption by fuel type, energy end use, and building type. A more complete energy consumption reconciliation is presented that includes the accounting of all energy use among buildings, utilities, and applicable losses.

  17. Cape Canaveral Air Force Station integrated resource assessment. Volume 1: Executive summary

    SciTech Connect

    Sandusky, W.F.; Wahlstrom, R.R.

    1994-08-01

    Some of the most difficult problems encountered at federal sites in reducing energy consumption in a cost-effective manner revolve around understanding where the energy is being used and what technologies can be employed to decrease energy use. The US Air Force (USAF) Space Command (SPACECOM) has tasked the Pacific Northwest Laboratory (PNL) to develop a model program that provides a systematic approach to evaluating energy opportunities. The program (1) identifies the building groups and end uses using the most energy (not just having the greatest energy-use intensity) and (2) evaluates the numerous options for retrofit or installation of new technology that will result in the selection of the most cost-effective technologies. In essence, this model program provides the federal energy managers with a road map to significantly reduce energy use in a planned, rational, cost-effective fashion that is not biased by the constraints of the typical funding sources available to federal sites. The results from this assessment process can easily be turned into a 5- to 10-year energy management plan that identifies where to start and how to proceed to reach the mandated energy consumption targets. This report provides the results of the fossil fuel and electric energy resource opportunity (ERO) assessments performed by PNL at one of Florida Power and Light`s (FPL`s) primary federal facilities--the USAF SPACECOM facility, Cape Canaveral Air Force Station (AFS)--located near Cocoa Beach, Florida. This is a companion report to Volume 2: Baseline Detail and Volume 3: Resource Assessment.

  18. VENTILATION RESEARCH: A REVIEW OF RECENT INDOOR AIR QUALITY LITERATURE

    EPA Science Inventory

    The report gives results of a literature review, conducted to survey and summarize recent and ongoing engineering research into building ventilation, air exchange rate, pollutant distribution and dispersion, and other effects of heating, ventilation, and air-conditioning (HVAC) s...

  19. United States Air Force 611th air support group 611th Civil Engineer Squadron, Elmendorf AFB, Alaska. Eareckson Air Station, Alaska. Remedial investigation/feasibility study report, final. Volume 1. Report for July 1994-September 1996

    SciTech Connect

    1995-08-25

    The Report, has been prepared to present the findings of the environmental investigation activities conducted at Eareckson Air Station. The RI/FS report has been divided into four primary volumes. This volume, Volume I, provides general information about environmental activities conducted at Eareckson AS to date (Section 1.0), summarizes 1993 and 1994 investigation activities (Section 2.0), outlines the decision process (Section 3.0), and presents basewide findings (Section 4.0).

  20. Air

    MedlinePlus

    ... do to protect yourself from dirty air . Indoor air pollution and outdoor air pollution Air can be polluted indoors and it can ... this chart to see what things cause indoor air pollution and what things cause outdoor air pollution! Indoor ...

  1. Review of Residential Low-Load HVAC Systems

    SciTech Connect

    Brown, Scott A.; Thornton, Brian; Widder, Sarah H.

    2013-09-01

    In support of the U.S. Department of Energy’s (DOE’s) Building America Program, Pacific Northwest National Laboratory (PNNL) conducted an investigation to inventory commercially available HVAC technologies that are being installed in low-load homes. The first step in this investigation was to conduct a review of published literature to identify low-load HVAC technologies available in the United States and abroad, and document the findings of existing case studies that have evaluated the performance of the identified technologies. This report presents the findings of the literature review, identifies gaps in the literature or technical understanding that must be addressed before low-load HVAC technologies can be fully evaluated, and introduces PNNL’s planned research and analysis for this project to address identified gaps and potential future work on residential low-load HVAC systems.

  2. Spectral fingerprinting of polycyclic aromatic hydrocarbons in high-volume ambient air samples by constant energy synchronous luminescence spectroscopy

    USGS Publications Warehouse

    Kerkhoff, M.J.; Lee, T.M.; Allen, E.R.; Lundgren, D.A.; Winefordner, J.D.

    1985-01-01

    A high-volume sampler fitted with a glass-fiber filter and backed by polyurethane foam (PUF) was employed to collect airborne particulate and gas-phase polycylic aromatic hydrocarbons (PAHs) in ambient air. Samples were collected from four sources representing a range of environmental conditions: gasoline engine exhaust, diesel engine exhaust, air near a heavily traveled interstate site, and air from a moderately polluted urban site. Spectral fingerprints of the unseparated particulate and gas-phase samples were obtained by constant energy synchronous luminescence spectroscopy (CESLS). Five major PAHs in the gas-phase extracts were characterized and estimated. The compatibility of a high-volume sampling method using polyurethane foam coupled with CESLS detection is explored for use as a screening technique for PAHs in ambient air. ?? 1985 American Chemical Society.

  3. Effects of lung volume on clearance of solutes from the air spaces of lungs

    SciTech Connect

    Peterson, B.T.; James, H.L.; McLarty, J.W.

    1988-03-01

    Several investigators have shown that the clearance rate of aerosolized 99mTc-labeled diethylenetriamine pentaacetate (DTPA, mol wt = 492, radius = 0.6 nm) from the air spaces of the lungs of humans and experimental animals increases with lung volume. To further investigate this phenomenon we performed a compartmental analysis of the 2-h clearance of DTPA from the lungs of anesthetized sheep using a new method to more accurately correct for the effects of DTPA recirculation. This analysis showed that the DTPA clearance in eight sheep ventilated with zero end-expired pressure was best described by a one-compartment model with a clearance rate of 0.42 +/- 0.15%/min. Ventilating eight sheep with an end-expired pressure of 10 cmH/sub 2/O throughout the study increased the end-expired volume 0.4 +/- 0.1 liter BTPS and created a clearance curve that was best described by a two-compartment model. In these sheep 56 +/- 16% of the DTPA cleared from the lungs at a rate of 7.9 +/- 2.9%/min. The remainder cleared at a rate similar to that measured in the sheep ventilated with zero end-expired pressure (0.35 +/- 0.18%/min). Additional control and lung inflation experiments were performed using /sup 99m/Tc-labeled human serum albumin (mol wt = 66,000, radius = 3.6 nm). In six control sheep ventilated with zero end-expired pressure the albumin clearance was best described by a one-compartment model with a clearance rate of 0.06 +/- 0.02%/min. The clearance rate in six sheep with increased lung volume was slightly larger (0.09 +/- 0.02, P less than 0.05) but was well described by a one-compartment model.

  4. Technical and economic assessment of fluidized bed augmented compressed air energy storage system. Volume III. Preconceptual design

    SciTech Connect

    Giramonti, A.J.; Lessard, R.D.; Merrick, D.; Hobson, M.J.

    1981-09-01

    A technical and economic assessment of fluidized bed combustion augmented compressed air energy storage systems is presented. The results of this assessment effort are presented in three volumes. Volume III - Preconceptual Design contains the system analysis which led to the identification of a preferred component configuration for a fluidized bed combustion augmented compressed air energy storage system, the results of the effort which transformed the preferred configuration into preconceptual power plant design, and an introductory evaluation of the performance of the power plant system during part-load operation and while load following.

  5. Zero Carryover Liquid-Desiccant Air Conditioner for Solar Applications: Preprint

    SciTech Connect

    Lowenstein, A.; Slayzak, S.; Kozubal, E.

    2006-07-01

    A novel liquid-desiccant air conditioner that dries and cools building supply air will transform the use of direct-contact liquid-desiccant systems in HVAC applications, improving comfort, air quality, and providing energy-efficient humidity control.

  6. Indoor Air Quality in Schools.

    ERIC Educational Resources Information Center

    Torres, Vincent M.

    Asserting that the air quality inside schools is often worse than outdoor pollution, leading to various health complaints and loss of productivity, this paper details factors contributing to schools' indoor air quality. These include the design, operation, and maintenance of heating, ventilating, and air conditioning (HVAC) systems; building…

  7. Residential Forced Air System Cabinet Leakage and Blower Performance

    SciTech Connect

    Walker, Iain S.; Dickerhoff, Darryl J.; Delp, William W.

    2010-03-01

    This project evaluated the air leakage and electric power consumption of Residential HVAC components, with a particular focus on air leakage of furnace cabinets. Laboratory testing of HVAC components indicated that air leakage can be significant and highly variable from unit to unit ? indicating the need for a standard test method and specifying maximum allowable air leakage in California State energy codes. To further this effort, this project provided technical assistance for the development of a national standard for Residential HVAC equipment air leakage. This standard is being developed by ASHRAE and is called"ASHRAE Standard 193P - Method of test for Determining the Air Leakage Rate of HVAC Equipment". The final part of this project evaluated techniques for measurement of furnace blower power consumption. A draft test procedure for power consumption was developed in collaboration with the Canadian General Standards Board: CSA 823"Performance Standard for air handlers in residential space conditioning systems".

  8. NREL's Advanced Thermal Conversion Laboratory at the Center for Buildings and Thermal Systems: On the Cutting-Edge of HVAC and CHP Technology (Revised)

    SciTech Connect

    Not Available

    2005-09-01

    This brochure describes how the unique testing capabilities of NREL's Advanced Thermal Conversion Laboratory at the Center For Buildings and Thermal Systems can help industry meet the challenge of developing the next generation of heating, ventilating, and air-conditioning (HVAC) and combined heat and power (CHP) equipment and concepts.

  9. Why use glycols in HVAC systems?

    SciTech Connect

    Eppelheimer, D.M.

    1997-12-31

    Glycols are used to prevent damage to heating, ventilating, and airconditioning (HVAC) equipment due to freezing and corrosion. Two glycols enjoy wide acceptance--ethylene glycol and propylene glycol. Both glycols have lower heat transfer characteristics and increased pumping requirements when compared to water. The loss of heat transfer and the increase in pumping power are influenced by temperature and the concentration of the fluid. The physical effects of glycol are almost unnoticed in heating systems where higher temperatures prevail. However, in cooling applications, the effect of glycol on system capacity and pump power must be carefully considered. Capricious addition of glycol to cooling systems is inappropriate. The effects of glycol can be mitigated by careful selection of equipment. This paper illustrates methods by which to reduce the impact of glycols when selecting cooling coils and chillers. Techniques such as increasing log mean temperature difference (LMTD) and modifications in coil circuiting or tube geometry can have a dramatic effect. The benefits of these techniques will be reviewed.

  10. PREVENTION REFERENCE MANUAL: CONTROL TECHNOLOGIES. VOLUME 1. PREVENTION AND PROTECTION TECHNOLOGIES FOR CONTROLLING ACCIDENTAL RELEASES OF AIR TOXICS

    EPA Science Inventory

    The volume discusses prevention and protection measures for controlling accidental releases of air toxics. The probability of accidental releases depends on the extent to which deviations (in magnitude and duration) in the process can be tolerated before a loss of chemical contai...

  11. PREVENTION REFERENCE MANUAL: CONTROL TECHNOLOGIES, VOLUME 2: POST-RELEASE MITIGATION MEASURES FOR CONTROLLING ACCIDENTAL RELEASES OF AIR TOXICS

    EPA Science Inventory

    The volume discusses prevention and protection measures for controlling accidental releases of air toxics. The probability of accidental releases depends on the extent to which deviations (in magnitude and duration) in the process can be tolerated before a loss of chemical contai...

  12. ENVIRONMENTAL ASSESSMENT OF A CRUDE-OIL HEATER USING STAGED AIR LANCES FOR NOX REDUCTION. VOLUME 1. TECHNICAL RESULTS

    EPA Science Inventory

    This volume of the report gives emission results from field tests of a crude-oil process heater burning a combination of oil and refinery gas. The heater had been modified by adding a system for injecting secondary air to reduce NOx emissions. One test was conducted with the stag...

  13. Field Operations and Enforcement Manual for Air Pollution Control. Volume II: Control Technology and General Source Inspection.

    ERIC Educational Resources Information Center

    Weisburd, Melvin I.

    The Field Operations and Enforcement Manual for Air Pollution Control, Volume II, explains in detail the following: technology of source control, modification of operations, particulate control equipment, sulfur dioxide removal systems for power plants, and control equipment for gases and vapors; inspection procedures for general sources, fuel…

  14. Stability limit of room air temperature of a VAV system

    SciTech Connect

    Matsuba, Tadahiko; Kamimura, Kazuyuki; Kasahara, Masato; Kimbara, Akiomi; Kurosu, Shigeru; Murasawa, Itaru; Hashimoto, Yukihiko

    1998-12-31

    To control heating, ventilating, and air-conditioning (HVAC) systems, it has been necessary to accept an analog system controlled mainly by proportional-plus-integral-plus-derivative (PID) action. However, when conventional PID controllers are replaced with new digital controllers by selecting the same PID parameters as before, the control loops have often got into hunting phenomena, which result in undamped oscillations. Unstable control characteristics (such as huntings) are thought to be one of the crucial problems faced by field operators. The PID parameters must be carefully selected to avoid instabilities. In this study, a room space is simulated as a thermal system that is air-conditioned by a variable-air-volume (VAV) control system. A dynamic room model without infiltration or exfiltration, which is directly connected to a simple air-handling unit without an economizer, is developed. To explore the possible existence of huntings, a numerical system model is formulated as a bilinear system with time-delayed feedback, and a parametric analysis of the stability limit is presented. Results are given showing the stability region affected by the selection of control and system parameters. This analysis was conducted to help us tune the PID controllers for optimal HVAC control.

  15. A uniform laminar air plasma plume with large volume excited by an alternating current voltage

    NASA Astrophysics Data System (ADS)

    Li, Xuechen; Bao, Wenting; Chu, Jingdi; Zhang, Panpan; Jia, Pengying

    2015-12-01

    Using a plasma jet composed of two needle electrodes, a laminar plasma plume with large volume is generated in air through an alternating current voltage excitation. Based on high-speed photography, a train of filaments is observed to propagate periodically away from their birth place along the gas flow. The laminar plume is in fact a temporal superposition of the arched filament train. The filament consists of a negative glow near the real time cathode, a positive column near the real time anode, and a Faraday dark space between them. It has been found that the propagation velocity of the filament increases with increasing the gas flow rate. Furthermore, the filament lifetime tends to follow a normal distribution (Gaussian distribution). The most probable lifetime decreases with increasing the gas flow rate or decreasing the averaged peak voltage. Results also indicate that the real time peak current decreases and the real time peak voltage increases with the propagation of the filament along the gas flow. The voltage-current curve indicates that, in every discharge cycle, the filament evolves from a Townsend discharge to a glow one and then the discharge quenches. Characteristic regions including a negative glow, a Faraday dark space, and a positive column can be discerned from the discharge filament. Furthermore, the plasma parameters such as the electron density, the vibrational temperature and the gas temperature are investigated based on the optical spectrum emitted from the laminar plume.

  16. Qualitative multiplatform microanalysis of individual heterogeneous atmospheric particles from high-volume air samples.

    PubMed

    Conny, Joseph M; Collins, Sean M; Herzing, Andrew A

    2014-10-01

    High-resolution microscopic analysis of individual atmospheric particles can be difficult, because the filters upon which particles are captured are often not suitable as substrates for microscopic analysis. Described here is a multiplatform approach for microscopically assessing chemical and optical properties of individual heterogeneous urban dust particles captured on fibrous filters during high-volume air sampling. First, particles embedded in fibrous filters are transferred to polished silicon or germanium wafers with electrostatically assisted high-speed centrifugation. Particles are clustered in an array of deposit areas, which allows for easily locating the same particle with different microscopy instruments. Second, particles with light-absorbing and/or light-scattering behavior are identified for further study from bright-field and dark-field light-microscopy modes, respectively. Third, particles identified from light microscopy are compositionally mapped at high definition with field-emission scanning electron microscopy and energy-dispersive X-ray spectroscopy. Fourth, compositionally mapped particles are further analyzed with focused ion-beam (FIB) tomography, whereby a series of thin slices from a particle are imaged, and the resulting image stack is used to construct a three-dimensional model of the particle. Finally, particle chemistry is assessed over two distinct regions of a thin FIB slice of a particle with energy-filtered transmission electron microscopy (TEM) and electron energy-loss spectroscopy associated with scanning transmission electron microscopy (STEM). PMID:25220253

  17. Practical Guide to HVAC for Schools.

    ERIC Educational Resources Information Center

    ASHRAE Journal, 1998

    1998-01-01

    Features six articles on heating, ventilation, and air-conditioning systems for schools. Examines how to avoid air temperature complaints when choosing a system; special system features; engineers, indoor air quality, and schools; mechanical systems noise in classrooms; operation and management issues related to design; and details on bids and…

  18. Autonomous Integrated Receive System (AIRS) requirements definition. Volume 4: Functional specification for the prototype Automated Integrated Receive System (AIRS)

    NASA Technical Reports Server (NTRS)

    Chie, C. M.

    1984-01-01

    The functional requirements for the performance, design, and testing for the prototype Automated Integrated Receive System (AIRS) to be demonstrated for the TDRSS S-Band Single Access Return Link are presented.

  19. Report on HVAC option selections for a relocatable classroom energy and indoor environmental quality field study

    SciTech Connect

    Apte, Michael G.; Delp, Woody W.; Diamond, Richard C.; Hodgson, Alfred T.; Kumar, Satish; Rainer, Leo I.; Shendell, Derek G.; Sullivan, Doug P.; Fisk, William J.

    2001-10-11

    It is commonly assumed that efforts to simultaneously develop energy efficient building technologies and to improve indoor environmental quality (IEQ) are unfeasible. The primary reason for this is that IEQ improvements often require additional ventilation that is costly from an energy standpoint. It is currently thought that health and productivity in work and learning environments requires adequate, if not superior, IEQ. Despite common assumptions, opportunities do exist to design building systems that provide improvements in both energy efficiency and IEQ. This report outlines the selection of a heating, ventilation, and air conditioning (HVAC) system to be used in demonstrating such an opportunity in a field study using relocatable school classrooms. Standard classrooms use a common wall mounted heat pump HVAC system. After reviewing alternative systems, a wall-mounting indirect/direct evaporative cooling system with an integral hydronic gas heating is selected. The anticipated advantages of this system include continuous ventilation of 100 percent outside air at or above minimum standards, projected cooling energy reductions of about 70 percent, inexpensive gas heating, improved airborne particle filtration, and reduced peak load electricity use. Potential disadvantages include restricted climate regions and possible increases in indoor relative humidity levels under some conditions.

  20. Combined solar and internal load effects on selection of heat reclaim-economizer HVAC systems

    SciTech Connect

    Sauer, H.J. Jr.; Howell, R.H.; Wang, Z. . Dept. of Mechanical Engineering)

    1990-05-01

    The concern for energy conservation has led to the development and use of heat recovery systems which reclaim the building internal heat before it is discarded in the exhaust air. On the other hand, economizer cycles have been widely used for many years in a variety of types of HVAC systems. Economizer cycles are widely accepted as a means to reduce operating time for chilling equipment when cool outside air is available. It has been suggested that heat reclaim systems should not be used in conjunction with an HVAC system which incorporates an economizer cycle because the economizer operation would result in heat being exhausted which might have been recovered. Others suggest that the economizer cycle can be used economically in a heat recovery system if properly controlled to maintain an overall building heat balance. This study looks at potential energy savings of such combined systems with particular emphasis on the effects of the solar load (amount of glass) and the internal load level (lights, people, appliances, etc.). For systems without thermal storage, annual energy savings of up to 60 percent are predicted with the use of heat reclaim systems in conjunction with economizers when the heat reclaim has priority. These results demonstrate the necessity of complete engineering evaluations if proper selection and operation of combined heat recovery and economizer cycles are to be obtained. This paper includes the basic methodology for making such evaluations.

  1. Cost Analysis of an Air Brayton Receiver for a Solar Thermal Electric Power System in Selected Annual Production Volumes

    NASA Technical Reports Server (NTRS)

    1981-01-01

    Pioneer Engineering and Manufacturing Company estimated the cost of manufacturing and Air Brayton Receiver for a Solar Thermal Electric Power System as designed by the AiResearch Division of the Garrett Corporation. Production costs were estimated at annual volumes of 100; 1,000; 5,000; 10,000; 50,000; 100,000 and 1,000,000 units. These costs included direct labor, direct material and manufacturing burden. A make or buy analysis was made of each part of each volume. At high volumes special fabrication concepts were used to reduce operation cycle times. All costs were estimated at an assumed 100% plant capacity. Economic feasibility determined the level of production at which special concepts were to be introduced. Estimated costs were based on the economics of the last half of 1980. Tooling and capital equipment costs were estimated for ach volume. Infrastructure and personnel requirements were also estimated.

  2. The Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Own, Tae Hoon (Editor); Bowen, Brent D. (Editor)

    1997-01-01

    The Aviation Institute University of Nebraska at Omaha (UNO) Monograph series has published the Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the World Conference on Transportation Research Society (WCTR) volume 1, number 3. The topics included in this document are: 1) Industrial Reform and Air Transport Development in China; 2) The Economic Effects of Airline Deregulation and the Open-Sky Policy of Korea; 3) The Economic Effects of Airline Deregulation and the Open-Sky Policy of Korea; 4) "Open Skies" in India-Is the policy succeeding? 5) The Japanese Domestic Air Fares under the Regulatory Regime: What will be expected after the revision of current charging system? 6) The Competitive Position of Airline Networks; and 7) Air Transport and Regional Economic Development in the European Union.

  3. DEVELOPMENT OF MESOSCALE AIR QUALITY SIMULATION MODELS. VOLUME 6. USER'S GUIDE TO MESOPAC (MESOSCALE METEOROLOGY PACKAGE)

    EPA Science Inventory

    MESOPAC is a mesoscale meteorological preprocessor program; it is designed to provide meteorological data to regional-scale air quality simulation models. Radiosonde data routinely available from National Weather Service (NWS) radiosonde ('upper air') and surface stations are use...

  4. AIR QUALITY CRITERIA FOR LEAD, VOLUMES 1-4. (1983) FIRST EXTERNAL REVIEW DRAFT

    EPA Science Inventory

    The document evaluates and assesses scientific information on the health and welfare effects associated with exposure to various concentrations of lead in ambient air. The literature through 1983 has been reviewed thoroughly for information relevant to air quality criteria, altho...

  5. AIR QUALITY CRITERIA FOR LEAD. VOLUMES 1-4. SECOND EXTERNAL REVIEW DRAFT

    EPA Science Inventory

    The document evaluates and assesses scientific information on the health and welfare effects associated with exposure to various concentrations of lead in ambient air. The literature through 1983 has been reviewed thoroughly for information relevant to air quality criteria, altho...

  6. Clean Air by Design.

    ERIC Educational Resources Information Center

    Crawford, Gary N.

    1995-01-01

    Planning new construction is an opportunity to recognize indoor environmental quality (IEQ) issues. Provides an overview of some common IEQ issues associated with construction projects. A building's heating, ventilating, and air-conditioning (HVAC) system is by far the single most common cause of IEQ problems and complaints. (MLF)

  7. AIR QUALITY CRITERIA FOR OZONE AND RELATED PHOTOCHEMICAL OXIDANTS VOLUME I OF III (Final, 1996)

    EPA Science Inventory

    The U.S. Environmental Protection Agency (EPA) promulgates the National Ambient Air Quality Standards (NAAQS) on the basis of scientific information contained in air quality criteria documents. The previous ozone (O3) criteria document, Air Quality Criteria for Ozone and Other Ph...

  8. Reference and Equivalent Methods Used to Measure National Ambient Air Quality Standards (NAAQS) Criteria Air Pollutants - Volume I

    EPA Science Inventory

    There are a number of Federal Reference Method (FRM) and Federal Equivalent Method (FEM) systems used to monitor the six criteria air pollutants (Lead [Pb], Carbon Monoxide [CO], Sulfur Dioxide [SO2], Nitrogen Dioxide [NO2], Ozone [O3], Particulate Matter [PM]) to determine if an...

  9. METHODS DEVELOPMENT FOR ASSESSING AIR POLLUTION CONTROL BENEFITS. VOLUME II. EXPERIMENTS IN VALUING NON-MARKET GOODS: A CASE STUDY OF ALTERNATIVE BENEFIT MEASURES OF AIR POLLUTION CONTROL IN THE SOUTH COAST AIR BASIN OF SOUTHERN CALIFORNIA

    EPA Science Inventory

    This volume includes the empirical results obtained from two experiments to measure the health and aesthetic benefits of air pollution control. Each experiment involved the same six neighborhood pairs, where the pairings were made on the basis of similarities in housing character...

  10. Laboratory measurement of secondary pollutant yields from ozone reaction with HVAC filters.

    SciTech Connect

    Destaillats, Hugo; Chen, Wenhao; Apte, Michael; Li, Nuan; Spears, Michael; Almosni, Jérémie; Zhang, Jianshun; Fisk, William J.

    2009-09-09

    We used Proton Transfer Reaction - Mass Spectrometry (PTR-MS) and conventional sampling methods to monitor and identify trace level organic pollutants formed in heterogeneous reactions between ozone and HVAC filters in real time. Experiments were carried out using a bench-scale flow tube reactor operating with dry air and humidified air (50% RH), at realistically high ozone concentrations (150 ppbv). We explored different filter media (i.e., fiberglass and cotton/polyester blends) and different particle loadings (i.e., clean filter and filters loaded with particles for 3 months at the Lawrence Berkeley National Laboratory and the Port of Oakland, CA). Detailed emission dynamics of very low levels of certain organic pollutants from filter media upon ozone exposure in the presence of moisture have been obtained and analyzed.

  11. Initial Business Case Analysis of Two Integrated Heat Pump HVAC Systems for Near-Zero-Energy Homes

    SciTech Connect

    Baxter, Van D

    2006-11-01

    The long range strategic goal of the Department of Energy's Building Technologies (DOE/BT) Program is to create, by 2020, technologies and design approaches that enable the construction of net-zero energy homes at low incremental cost (DOE/BT 2005). A net zero energy home (NZEH) is a residential building with greatly reduced needs for energy through efficiency gains, with the balance of energy needs supplied by renewable technologies. While initially focused on new construction, these technologies and design approaches are intended to have application to buildings constructed before 2020 as well resulting in substantial reduction in energy use for all building types and ages. DOE/BT's Emerging Technologies (ET) team is working to support this strategic goal by identifying and developing advanced heating, ventilating, air-conditioning, and water heating (HVAC/WH) technology options applicable to NZEHs. Although the energy efficiency of heating, ventilating, and air-conditioning (HVAC) equipment has increased substantially in recent years, new approaches are needed to continue this trend. Dramatic efficiency improvements are necessary to enable progress toward the NZEH goals, and will require a radical rethinking of opportunities to improve system performance. The large reductions in HVAC energy consumption necessary to support the NZEH goals require a systems-oriented analysis approach that characterizes each element of energy consumption, identifies alternatives, and determines the most cost-effective combination of options. In particular, HVAC equipment must be developed that addresses the range of special needs of NZEH applications in the areas of reduced HVAC and water heating energy use, humidity control, ventilation, uniform comfort, and ease of zoning. In FY05 ORNL conducted an initial Stage 1 (Applied Research) scoping assessment of HVAC/WH systems options for future NZEHs to help DOE/BT identify and prioritize alternative approaches for further development

  12. Autonomous Integrated Receive System (AIRS) requirements definition. Volume 3: Performance and simulation

    NASA Technical Reports Server (NTRS)

    Chie, C. M.; Su, Y. T.; Lindsey, W. C.; Koukos, J.

    1984-01-01

    The autonomous and integrated aspects of the operation of the AIRS (Autonomous Integrated Receive System) are discussed from a system operation point of view. The advantages of AIRS compared to the existing SSA receive chain equipment are highlighted. The three modes of AIRS operation are addressed in detail. The configurations of the AIRS are defined as a function of the operating modes and the user signal characteristics. Each AIRS configuration selection is made up of three components: the hardware, the software algorithms and the parameters used by these algorithms. A comparison between AIRS and the wide dynamics demodulation (WDD) is provided. The organization of the AIRS analytical/simulation software is described. The modeling and analysis is for simulating the performance of the PN subsystem is documented. The frequence acquisition technique using a frequency-locked loop is also documented. Doppler compensation implementation is described. The technological aspects of employing CCD's for PN acquisition are addressed.

  13. High spatiotemporal resolution measurement of regional lung air volumes from 2D phase contrast x-ray images

    SciTech Connect

    Leong, Andrew F. T.; Islam, M. Sirajul; Kitchen, Marcus J.; Fouras, Andreas; Wallace, Megan J.; Hooper, Stuart B.

    2013-04-15

    Purpose: Described herein is a new technique for measuring regional lung air volumes from two-dimensional propagation-based phase contrast x-ray (PBI) images at very high spatial and temporal resolution. Phase contrast dramatically increases lung visibility and the outlined volumetric reconstruction technique quantifies dynamic changes in respiratory function. These methods can be used for assessing pulmonary disease and injury and for optimizing mechanical ventilation techniques for preterm infants using animal models. Methods: The volumetric reconstruction combines the algorithms of temporal subtraction and single image phase retrieval (SIPR) to isolate the image of the lungs from the thoracic cage in order to measure regional lung air volumes. The SIPR algorithm was used to recover the change in projected thickness of the lungs on a pixel-by-pixel basis (pixel dimensions {approx}16.2 {mu}m). The technique has been validated using numerical simulation and compared results of measuring regional lung air volumes with and without the use of temporal subtraction for removing the thoracic cage. To test this approach, a series of PBI images of newborn rabbit pups mechanically ventilated at different frequencies was employed. Results: Regional lung air volumes measured from PBI images of newborn rabbit pups showed on average an improvement of at least 20% in 16% of pixels within the lungs in comparison to that measured without the use of temporal subtraction. The majority of pixels that showed an improvement was found to be in regions occupied by bone. Applying the volumetric technique to sequences of PBI images of newborn rabbit pups, it is shown that lung aeration at birth can be highly heterogeneous. Conclusions: This paper presents an image segmentation technique based on temporal subtraction that has successfully been used to isolate the lungs from PBI chest images, allowing the change in lung air volume to be measured over regions as small as the pixel size. Using

  14. The Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Oum, Tae Hoon (Editor); Bowen, Brent D. (Editor)

    1997-01-01

    The UNO Aviation Institute has published the 1997 Proceedings of the Air Transport Research Group of the World Conference on Transportation Research (WCTR) Society. Items published in this three volume, seven monograph series were presented at the triennial ATRG Conference held at the University of British Columbia, June 25-27, 1997. A wide variety of policy issues are discussed including the following: open- skies agreements, liberalization, globalization, airline competition, airport performance, pricing, hubs, and safety, among others.

  15. Installation Restoration Program. Remedial Investigation Report. Minnesota Air National Guard Base, Duluth International Airport, Duluth, Minnesota. Volume 1. Final report

    SciTech Connect

    Not Available

    1990-01-01

    This report describes the remedial actions performed on sites confirmed to contain hazardous waste contamination which endangers the human health. The actions performed are described and the potential for future problems. The study was conducted under the Air National Guard's Installation Restoration Program. Partial contents of Volume I include: description of Installation Restoration Program; physiography, climate and drainage; demography and land use; geology and topography; hydrology; water quality; history; drainage; ground water; sampling; surface water; soils; chemical contamination; migration; and sedimentation.

  16. MELSAR: a mesoscale air quality model for complex terrain. Volume 1. Overview, technical description and user's guide

    SciTech Connect

    Allwine, K.J.; Whiteman, C.D.

    1985-04-01

    This final report is submitted as part of the Green River Ambient Model Assessment (GRAMA) program conducted at the US Department of Energy's Pacific Northwest Laboratory for the US Environmental Protection Agency. The GRAMA program has, as its ultimate goal, the development of validated air quality models that can be applied to the complex terrain of the Green River Formation of western Colorado, eastern Utah, and southern Wyoming. The Green River Formation is a geologic formation containing large reserves of oil shale, coal, and other natural resources. Development of these resources may lead to a degradation of the air quality of the region. Air quality models are needed immediately for planning and regulatory purposes to assess the magnitude of these regional impacts. This report documents one of the models being developed for this purpose within GRAMA - specifically a model to predict short averaging time (less than or equal to 24 h) pollutant concentrations resulting from the mesoscale transport of pollutant releases from multiple sources. MELSAR has not undergone any rigorous operational testing, sensitivity analyses, or validation studies. Testing and evaluation of the model are needed to gain a measure of confidence in the model's performance. This report consists of two volumes. Volume 1 contains the model overview, technical description, and user's guide, and Volume 2 contains the Appendices which include listings of the FORTRAN code. 51 refs., 31 figs., 35 tabs.

  17. Storage of LWR spent fuel in air. Volume 3, Results from exposure of spent fuel to fluorine-contaminated air

    SciTech Connect

    Cunningham, M.E.; Thomas, L.E.

    1995-06-01

    The Behavior of Spent Fuel in Storage (BSFS) Project has conducted research to develop data on spent nuclear fuel (irradiated U0{sub 2}) that could be used to support design, licensing, and operation of dry storage installations. Test Series B conducted by the BSFS Project was designed as a long-term study of the oxidation of spent fuel exposed to air. It was discovered after the exposures were completed in September 1990 that the test specimens had been exposed to an atmosphere of bottled air contaminated with an unknown quantity of fluorine. This exposure resulted in the test specimens reacting with both the oxygen and the fluorine in the oven atmospheres. The apparent source of the fluorine was gamma radiation-induced chemical decomposition of the fluoro-elastomer gaskets used to seal the oven doors. This chemical decomposition apparently released hydrofluoric acid (HF) vapor into the oven atmospheres. Because the Test Series B specimens were exposed to a fluorine-contaminated oven atmosphere and reacted with the fluorine, it is recommended that the Test Series B data not be used to develop time-temperature limits for exposure of spent nuclear fuel to air. This report has been prepared to document Test Series B and present the collected data and observations.

  18. Investigation of IAQ-Relevant Surface Chemistry and Emissions on HVAC Filter Materials

    SciTech Connect

    Destaillats, Hugo; Fisk, William J.

    2010-02-01

    Chemical reactions involving ozone of outdoor origin and indoor materials are known to be significant sources of formaldehyde and other irritant gas-phase oxidation products in the indoor environment. HVAC filters are exposed to particularly high ozone concentrations--close to outdoor levels. In this study, we investigated chemical processes taking place on the surface of filters that included fiberglass, polyester, cotton/polyester blend and synthetic (e.g., polyolefin) filter media. Ozone reactions were studied on unused filter media, and on filters that were deployed for 3 months in two different locations: at the Lawrence Berkeley National Laboratory and at the Port of Oakland. Specimens from each filter were exposed to ozone under controlled conditions in a laboratory flow tube at a constant flow of dry or humidified air (50percent relative humidity). Ozone was generated with a UV source upstream of the flow tube, and monitored using a photometric detector. Ozone breakthrough curves were recorded for each sample exposed to ~;;150 ppbv O3 for periods of ~;;1000 min, from which we estimated their uptake rate. Most experiments were performed at 1.3 L/min (corresponding to a face velocity of 0.013 m/s), except for a few tests performed at a higher airflow rate, to obtain a face velocity of 0.093 m/s, slightly closer to HVAC operation conditions. Formaldehyde and acetaldehyde, two oxidation byproducts, were collected downstream of the filter and quantified. Emissions of these volatile aldehydes were consistently higher under humidified air than under dry conditions, at which levels were near the limit of detection. Our results confirm that there are significant reactions of ozone as air containing ozone flows through HVAC filters, particularly when the filters are loaded with particles and the air is humidified. The amount of ozone reacted was not clearly related to the types of filter media, e.g., fiberglass versus synthetic. Specific fiberglass filters that were

  19. Supplemental site inspection for Air Force Plant 59, Johnson City, New York, Volume 3: Appendices F-Q

    SciTech Connect

    Nashold, B.; Rosenblatt, D.; Hau, J.

    1995-08-01

    This summary describes a Supplemental Site Inspection (SSI) conducted by Argonne National Laboratory (ANL) at Air Force Plant 59 (AFP 59) in Johnson City, New York. All required data pertaining to this project were entered by ANL into the Air Force-wide Installation Restoration Program Information System (IRPIMS) computer format and submitted to an appropriate authority. The work was sponsored by the United States Air Force as part of its Installation Restoration Program (IRP). Previous studies had revealed the presence of contaminants at the site and identified several potential contaminant sources. Argonne`s study was conducted to answer questions raised by earlier investigations. This volume consists of appendices F-Q, which contain the analytical data from the site characterization.

  20. The Conference Proceedings of the 2001 Air Transport Research Society (ATRS) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Lee, Yeong-Heok (Editor); Bowen, Brent D. (Editor); Tarry, Scott E. (Editor)

    2001-01-01

    The ATRS held its Annual conference at Jeju Island, Korea in July 2001. The conference was a success with nearly 140 participants including 70 presenters. This report contains presentations from Volume 1 on the following: Airline and Travel Agent Relationships in Asia;Benchmarking Aviation Safety in the Commercial Airline Industry;Impact of Frequent Flyer Program on the Demand for Air Travel; Application of Genetic Algorithm on Airline Schedule;The Effects of Dual Carrier Designation and Partial Liberalization: The Case of Canada;Defense of Air Carriers and Air Agencies in FAA Enforcement proceedin gs - Damage Control Before the Case Arises; Cost Incentives for Airline Mergers? - An examination on the cost impact of U.S. airline mergers and acquisitions;Airport Regulation, Airline Competition and Canada's Airport System; Airline Competition: The Case of Israel's Domestic Doupoly; Non-Financial Indicators of Airline Distress: A Conceptual Approach;and Airport Privatization: An Empirical Analysis of Financial and Operational Efficiency.

  1. Supplemental site inspection for Air Force Plant 59, Johnson City, New York, Volume 2: Appendices A-E

    SciTech Connect

    Nashold, B.; Rosenblatt, D.; Tomasko, D.

    1995-08-01

    This summary describes a Supplemental Site Inspection (SSI) conducted by Argonne National Laboratory (ANL) at Air Force Plant 59 (AFP 59) in Johnson City, New York. All required data pertaining to this project were entered by ANL into the Air Force-wide Installation Restoration Program Information System (IRPIMS) computer format and submitted to an appropriate authority. The work was sponsored by the United States Air Force as part of its Installation Restoration Program (IRP). Previous studies had revealed the presence of contaminants at the site and identified several potential contaminant sources. Argonne`s study was conducted to answer questions raised by earlier investigations. This volume consists of appendices A-E, containing field data and data validation.

  2. Flexible HVAC System for Lab or Classroom.

    ERIC Educational Resources Information Center

    Friedan, Jonathan

    2001-01-01

    Discusses an effort to design a heating, ventilation, and air conditioning system flexible enough to accommodate an easy conversion of classrooms to laboratories and dry labs to wet labs. The design's energy efficiency and operations and maintenance are examined. (GR)

  3. Smart HVAC control in IoT: energy consumption minimization with user comfort constraints.

    PubMed

    Serra, Jordi; Pubill, David; Antonopoulos, Angelos; Verikoukis, Christos

    2014-01-01

    Smart grid is one of the main applications of the Internet of Things (IoT) paradigm. Within this context, this paper addresses the efficient energy consumption management of heating, ventilation, and air conditioning (HVAC) systems in smart grids with variable energy price. To that end, first, we propose an energy scheduling method that minimizes the energy consumption cost for a particular time interval, taking into account the energy price and a set of comfort constraints, that is, a range of temperatures according to user's preferences for a given room. Then, we propose an energy scheduler where the user may select to relax the temperature constraints to save more energy. Moreover, thanks to the IoT paradigm, the user may interact remotely with the HVAC control system. In particular, the user may decide remotely the temperature of comfort, while the temperature and energy consumption information is sent through Internet and displayed at the end user's device. The proposed algorithms have been implemented in a real testbed, highlighting the potential gains that can be achieved in terms of both energy and cost. PMID:25054163

  4. Energy efficient model based algorithm for control of building HVAC systems.

    PubMed

    Kirubakaran, V; Sahu, Chinmay; Radhakrishnan, T K; Sivakumaran, N

    2015-11-01

    Energy efficient designs are receiving increasing attention in various fields of engineering. Heating ventilation and air conditioning (HVAC) control system designs involve improved energy usage with an acceptable relaxation in thermal comfort. In this paper, real time data from a building HVAC system provided by BuildingLAB is considered. A resistor-capacitor (RC) framework for representing thermal dynamics of the building is estimated using particle swarm optimization (PSO) algorithm. With objective costs as thermal comfort (deviation of room temperature from required temperature) and energy measure (Ecm) explicit MPC design for this building model is executed based on its state space representation of the supply water temperature (input)/room temperature (output) dynamics. The controllers are subjected to servo tracking and external disturbance (ambient temperature) is provided from the real time data during closed loop control. The control strategies are ported on a PIC32mx series microcontroller platform. The building model is implemented in MATLAB and hardware in loop (HIL) testing of the strategies is executed over a USB port. Results indicate that compared to traditional proportional integral (PI) controllers, the explicit MPC's improve both energy efficiency and thermal comfort significantly. PMID:25869418

  5. Integrated Heat Pump HVAC Systems for Near-Zero-Energy Homes - Business Case Assessment

    SciTech Connect

    Baxter, Van D

    2007-05-01

    The long range strategic goal of the Department of Energy's Building Technologies (DOE/BT) Program is to create, by 2020, technologies and design approaches that enable the construction of net-zero energy homes at low incremental cost (DOE/BT 2005). A net zero energy home (NZEH) is a residential building with greatly reduced needs for energy through efficiency gains, with the balance of energy needs supplied by renewable technologies. While initially focused on new construction, these technologies and design approaches are intended to have application to buildings constructed before 2020 as well resulting in substantial reduction in energy use for all building types and ages. DOE/BT's Emerging Technologies (ET) team is working to support this strategic goal by identifying and developing advanced heating, ventilating, air-conditioning, and water heating (HVAC/WH) technology options applicable to NZEHs. Although the energy efficiency of heating, ventilating, and air-conditioning (HVAC) equipment has increased substantially in recent years, new approaches are needed to continue this trend. Dramatic efficiency improvements are necessary to enable progress toward the NZEH goals, and will require a radical rethinking of opportunities to improve system performance. The large reductions in HVAC energy consumption necessary to support the NZEH goals require a systems-oriented analysis approach that characterizes each element of energy consumption, identifies alternatives, and determines the most cost-effective combination of options. In particular, HVAC equipment must be developed that addresses the range of special needs of NZEH applications in the areas of reduced HVAC and water heating energy use, humidity control, ventilation, uniform comfort, and ease of zoning. In FY05 ORNL conducted an initial Stage 1 (Applied Research) scoping assessment of HVAC/WH systems options for future NZEHs to help DOE/BT identify and prioritize alternative approaches for further development

  6. COMPREHENSIVE DIAGNOSTIC AND IMPROVEMENT TOOLS FOR HVAC-SYSTEM INSTALLATIONS IN LIGHT COMMERCIAL BUILDINGS

    SciTech Connect

    Abram Conant; Mark Modera; Joe Pira; John Proctor; Mike Gebbie

    2004-10-31

    Proctor Engineering Group, Ltd. (PEG) and Carrier-Aeroseal LLP performed an investigation of opportunities for improving air conditioning and heating system performance in existing light commercial buildings. Comprehensive diagnostic and improvement tools were created to address equipment performance parameters (including airflow, refrigerant charge, and economizer operation), duct-system performance (including duct leakage, zonal flows and thermal-energy delivery), and combustion appliance safety within these buildings. This investigation, sponsored by the National Energy Technology Laboratory, a division of the U.S. Department of Energy, involved collaboration between PEG and Aeroseal in order to refine three technologies previously developed for the residential market: (1) an aerosol-based duct sealing technology that allows the ducts to be sealed remotely (i.e., without removing the ceiling tiles), (2) a computer-driven diagnostic and improvement-tracking tool for residential duct installations, and (3) an integrated diagnosis verification and customer satisfaction system utilizing a combined computer/human expert system for HVAC performance. Prior to this work the aerosol-sealing technology was virtually untested in the light commercial sector--mostly because the savings potential and practicality of this or any other type of duct sealing had not been documented. Based upon the field experiences of PEG and Aeroseal, the overall product was tailored to suit the skill sets of typical HVAC-contractor personnel.

  7. Smart HVAC Control in IoT: Energy Consumption Minimization with User Comfort Constraints

    PubMed Central

    Verikoukis, Christos

    2014-01-01

    Smart grid is one of the main applications of the Internet of Things (IoT) paradigm. Within this context, this paper addresses the efficient energy consumption management of heating, ventilation, and air conditioning (HVAC) systems in smart grids with variable energy price. To that end, first, we propose an energy scheduling method that minimizes the energy consumption cost for a particular time interval, taking into account the energy price and a set of comfort constraints, that is, a range of temperatures according to user's preferences for a given room. Then, we propose an energy scheduler where the user may select to relax the temperature constraints to save more energy. Moreover, thanks to the IoT paradigm, the user may interact remotely with the HVAC control system. In particular, the user may decide remotely the temperature of comfort, while the temperature and energy consumption information is sent through Internet and displayed at the end user's device. The proposed algorithms have been implemented in a real testbed, highlighting the potential gains that can be achieved in terms of both energy and cost. PMID:25054163

  8. Technology Solutions Case Study: Sealed Air-Return Plenum Retrofit

    SciTech Connect

    none,

    2012-08-01

    In this project, Pacific Northwest National Laboratory researchers greatly improved indoor air quality and HVAC performance by replacing an old, leaky air handler with a new air handler with an air-sealed return plenum with filter; they also sealed the ducts, and added a fresh air intake.

  9. Air/Superfund national technical guidance study series, Volume 2. Estimation of baseline air emission at Superfund sites. Interim report(Final)

    SciTech Connect

    Not Available

    1989-01-01

    This volume is one in a series of manuals prepared for EPA to assist its Remedial Project Managers in the assessment of the air contaminant pathway and developing input data for risk assessment. The manual provides guidance on developing baseline-emission estimates from hazardous waste sites. Baseline-emission estimates (BEEs) are defined as emission rates estimated for a site in its undisturbed state. Specifically, the manual is intended to: Present a protocol for selecting the appropriate level of effort to characterize baseline air emissions; Assist site managers in designing an approach for BEEs; Describe useful technologies for developing site-specific baseline emission estimates (BEEs); Help site managers select the appropriate technologies for generating site-specific BEEs.

  10. Autonomous Integrated Receive System (AIRS) requirements definition. Volume 2: Design and development

    NASA Technical Reports Server (NTRS)

    Chie, C. M.; White, M. A.; Lindsey, W. C.; Davarian, F.; Dixon, R. C.

    1984-01-01

    Functional requirements and specifications are defined for an autonomous integrated receive system (AIRS) to be used as an improvement in the current tracking and data relay satellite system (TDRSS), and as a receiving system in the future tracking and data acquisition system (TDAS). The AIRS provides improved acquisition, tracking, bit error rate (BER), RFI mitigation techniques, and data operations performance compared to the current TDRSS ground segment receive system. A computer model of the AIRS is used to provide simulation results predicting the performance of AIRS. Cost and technology assessments are included.

  11. HVAC component data modeling using industry foundation classes

    SciTech Connect

    Bazjanac, Vladimir; Forester, James; Haves, Philip; Sucic, Darko; Xu, Peng

    2002-07-01

    The Industry Foundation Classes (IFC) object data model of buildings is being developed by the International Alliance for Interoperability (IAI). The aim is to support data sharing and exchange in the building and construction industry across the life-cycle of a building. This paper describes a number of aspects of a major extension of the HVAC part of the IFC data model. First is the introduction of a more generic approach for handling HVAC components. This includes type information, which corresponds to catalog data, occurrence information, which defines item-specific attributes such as location and connectivity, and performance history information, which documents the actual performance of the component instance over time. Other IFC model enhancements include an extension of the connectivity model used to specify how components forming a system can be traversed and the introduction of time-based data streams. This paper includes examples of models of particular types of HVAC components, such as boilers and actuators, with all attributes included in the definitions. The paper concludes by describing the on-going process of model testing, implementation and integration into the complete IFC model and how the model can be used by software developers to support interoperability between HVAC-oriented design and analysis tools.

  12. D0 HVAC System Controls Evaluation of Upgrade Options

    SciTech Connect

    Markley, D.; Simon, P.; /Fermilab

    1998-05-05

    This engineering note documents three different options for upgrading the Dzero HVAC control system. All three options leave the current field hardware and field devices intact and upgrade the computer control hardware and software. Dzero will be heading into a physics run starting in 2000. This physics run could last several years. The Dzero HVAC system is an integral part of climate control and electronics cooling. The current HVAC control system is based upon a 1985 Johnson Controls System. In order to enter the next long-term physics run with a solid HVAC control system, the current control system needs to be upgraded. This proposal investigates three options: (1) Replacement to the next generation of Johnson Controls Hardware and Software with the Johnson Controls operator interface - FESS; (2) Replacement to the next generation of Johnson Controls Hardware and Software with the FIX32 Operator Interface - FESS/Dzero; and (3) Replacement with a commercially available Programmable Logic Controller (PLC) WITH THE FIX 32 Operator Interface - Dzero.

  13. Performance of a hydrogen burner to simulate air entering scramjet combustors. [simulation of total temperature, total pressure, and volume fraction of oxygen of air at flight conditions

    NASA Technical Reports Server (NTRS)

    Russin, W. R.

    1974-01-01

    Tests were conducted to determine the performance of a hydrogen burner used to produce a test gas that simulates air entering a scramjet combustor at various flight conditions. The test gas simulates air in that it duplicates the total temperature, total pressure, and the volume fraction of oxygen of air at flight conditions. The main objective of the tests was to determine the performance of the burner as a function of the effective exhaust port area. The conclusions were: (1) pressure oscillations of the chugging type were reduced in amplitude to plus or minus 2 percent of the mean pressure level by proper sizing of hydrogen, oxygen, and air injector flow areas; (2) combustion efficiency remained essentially constant as the exhaust port area was increased by a factor of 3.4; (3) the mean total temperature determined from integrating the exit radial gas property profiles was within plus or minus 5 percent of the theoretical bulk total temperature; (4) the measured exit total temperature profile had a local peak temperature more than 30 percent greater than the theoretical bulk total temperature; and (5) measured heat transfer to the burner liner was 75 percent of that predicted by theory based on a flat radial temperature profile.

  14. An Experimental Evaluation of HVAC-Grade Carbon-Dioxide Sensors: Part 3, Humidity, Temperature, and Pressure Sensitivity Test Results

    SciTech Connect

    Shrestha, Som S; Maxwell, Dr. Gregory

    2010-01-01

    This is the third paper in a four-part series reporting on the test and evaluation of typical carbon-dioxide sensors used in building HVAC applications. Fifteen models of NDIR HVAC-grade CO2 sensors were tested and evaluated to determine the humidity, temperature, and pressure sensitivity of the sensors. This paper reports the performance of the sensors at various relative humidity, temperature, and pressure levels common to building HVAC applications and provides a comparison with manufacturer specifications. Among the 15 models tested, eight models have a single-lamp, single-wavelength configuration, four models have a dual-lamp, single-wavelength configuration, and three models have a single-lamp, dual-wavelength configuration. The sensors were tested in a chamber specifically fabricated for this research. A description of the apparatus and the method of test are described in Part 1 (Shrestha and Maxwell 2009). The test result showed a wide variation in humidity, temperature, and pressure sensitivity of CO2 sensors among manufacturers. In some cases, significant variations in sensor performance exist between sensors of the same model. Even the natural variation in relative humidity could significantly vary readings of some CO2 sensor readings. The effects of temperature and pressure variation on NDIR CO2 sensors are unavoidable without an algorithm to compensate for the changes. For the range of temperature and pressure variation in an air-conditioned space, the effect of pressure variation is more significant compared to the effect of temperature variation.

  15. EPA THIRD-GENERATION AIR QUALITY MODELING SYSTEM - VOLUME 1: CONCEPT

    EPA Science Inventory

    A flexible environmental modeling and decision support system is being developed by the Office of Research and Development as part of EPA's High Performance Computing and Communications (HPCC) program. his report is Volume 1 of a multiple volume sat describing the development pro...

  16. INDOOR AIR POLLUTION IN THE RESIDENTIAL ENVIRONMENT. VOLUME I. DATA COLLECTION, ANALYSIS AND INTERPRETATION

    EPA Science Inventory

    A 24-month study was undertaken to characterize the indoor residential air quality. Seventeen residential dwellings were monitored, each for a 14-day period. Air samples were collected from four locations: one outdoor site adjacent to the building; and three indoor sites, the kit...

  17. HUMAN HEALTH DAMAGES FROM MOBILE SOURCE AIR POLLUTION: ADDITIONAL DELPHI DATA ANALYSIS. VOLUME II

    EPA Science Inventory

    The report contains the results of additional analyses of the data generated by a panel of medical experts for a study of Human Health Damages from Mobile Source Air Pollution (hereafter referred to as HHD) conducted by the California Air Resources Board in 1973-75 for the U.S. E...

  18. METRO-APEX Volume 7.1: Air Pollution Control Officer's Manual. Revised.

    ERIC Educational Resources Information Center

    University of Southern California, Los Angeles. COMEX Research Project.

    The Air Pollution Control Officer's Manual is one of a set of twenty-one manuals used in METRO-APEX 1974, a computerized college and professional level, computer-supported, role-play, simulation exercise of a community with "normal" problems. Stress is placed on environmental quality considerations. APEX 1974 is an expansion of APEX--Air Pollution…

  19. INTEGRATED AIR POLLUTION CONTROL SYSTEM, VERSION 4.0 - VOLUME 3: PROGRAMMER'S MAINTENANCE MANUAL

    EPA Science Inventory

    The Integrated Air Pollution Control System (IAPCS) was developed for the U.S. EPA's Air and Energy Engineering Research Laboratory to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, and ...

  20. APEX (Air Pollution Exercise) Volume 10: Industrialist's Manual No. 6, Dusty Rhodes' Cement Company.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Industrialist's Manual No. 6, Dusty Rhodes' Cement Company is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two…

  1. APEX (Air Pollution Exercise) Volume 7: Industrialist's Manual No. 2, People's Pulp Plant.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Industrialist's Manual No. 2, People's Pulp Plant is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections,…

  2. APEX (Air Pollution Exercise) Volume 9: Industrialist's Manual No. 5, Caesar's Rendering Plant.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Industrialist's Manual No. 5, Caesar's Rendering Plant is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections,…

  3. APEX (Air Pollution Exercise) Volume 6: Industrialist's Manual No. 1, Shear Power Company.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Industrialist's Manual No. 1, Shear Power Company is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections,…

  4. APEX (Air Pollution Exercise) Volume 8: Industrialist's Manual No. 3, Rusty's Iron Foundry.

    ERIC Educational Resources Information Center

    Environmental Protection Agency, Research Triangle Park, NC. Office of Manpower Development.

    The Industrialist's Manual No. 3, Rusty's Iron Foundry is part of a set of 21 manuals (AA 001 009-001 029) used in APEX (Air Pollution Exercise), a computerized college and professional level "real world" game simulation of a community with urban and rural problems, industrial activities, and air pollution difficulties. The first two sections,…

  5. INTEGRATED AIR POLLUTION CONTROL SYSTEM, VERSION 4.0 - VOLUME 2: TECHNICAL DOCUMENTATION MANUAL

    EPA Science Inventory

    The Integrated Air Pollution Control System (IAPCS) was developed for the U.S. EPA's Air and Energy Engineering Research Laboratory to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, and ...

  6. INTEGRATED AIR POLLUTION CONTROL SYSTEM, VERSION 4.0 - VOLUME 1: USER'S GUIDE

    EPA Science Inventory

    The Integrated Air Pollution Control System (IAPCS) was developed for the U.S. EPA's Air and Energy Engineering Research Laboratory to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, and ...

  7. INTEGRATED AIR POLLUTION CONTROL SYSTEM, VERSION 4.0 - VOLUME 3: PROGRAMMER'S MAINTENACE MANUAL

    EPA Science Inventory

    The Integrated Air Pollution Control System (IAPCS) was developed for the U.S. EPA's Air and Energy Engineering Research Laboratory to estimate costs and performance for emission control systems applied to coal-fired utility boilers. The model can project a material balance, and ...

  8. Airflow regulation in variable-speed systems for residential HVAC applications

    SciTech Connect

    Becerra, R.C.; Beifus, B.L.

    1996-11-01

    In the majority of heating, ventilating, and air-conditioning (HVAC) systems, air is the final medium for adding or extracting heat from or to the space to be air conditioned. Air is heated by passing it over a heat transfer device called a coil, which is a heat exchanger with air on the outside and the primary heating/cooling medium (water, steam, electricity, refrigerant, etc.) on the inside. One of the major factors determining heat transfer is the airflow rate, which can be controlled by mechanical means or by controlling the speed of the fan. Centrifugal fans driven by single-speed induction motors traditionally have been used in the JVAC industry but have an airflow characteristic that depends on the static pressure seen by the system. Variable-speed systems are starting to emerge as a strong alternative to traditional systems because of their ability to match the demand of the air-conditioned space, resulting in higher efficiencies and higher comfort. System efficiency can be improved by constraining the range of airflows provided by the fan or blower system in response to system pressure, that is, by controlling the airflow over the heat exchanger. This paper presents a method to regulate airflow independent of the static pressure and without the need for airflow sensors.

  9. The Conference Proceedings of the 2001 Air Transport Research Society (ATRS) of the WCTR Society. Volume 2

    NASA Technical Reports Server (NTRS)

    Lee, Yeong-Heok (Editor); Bowen, Brent D. (Editor); Tarry, Scott E. (Editor)

    2001-01-01

    The ATRS held its 5th Annual conference at the City University of Hong Kong Campus in July 2001. The conference was a success with nearly 140 participants including 70 presenters. Titles that comprise Volume 2 include: Intelligent Airport Gate Assignment System; A Study on the Effects of the Personality Compatibility to the Job Performance; ITS/CVO Application for Air cargo Transportation in Korea; An Airport as a Logistics and Economic Hub: The Case of Incheon International Airport; The Impact Of Aviation Safety over the Consumer's Behavior; The Integration of China and Taiwan Air Networks for Direct Air Cargo Services; Quality perception and carrier choice in Civil Aviation; Future Trends in Business Travel Decision Making; Cooperation Among German Airports in Europe; Inbound and Outbound Air Passenger Traffic Forecasting between the United States and Selected Asian countries; An Evaluation of Alternative Facilities for Airport Redevelopment using Fuzzy Linguistic Approach; Economic Analysis of Airline Alliances; The Aviation Cooperation between the two Koreas Preparing for the Reunification of the Peninsula; and A Study on the Air Transport Cooperation in Northeast Asia between China, Japan and Korea.

  10. Retro-Nasal Aroma Release Is Correlated with Variations in the In-Mouth Air Cavity Volume after Empty Deglutition

    PubMed Central

    Mishellany-Dutour, Anne; Woda, Alain; Labouré, Hélène; Bourdiol, Pierre; Lachaze, Pauline; Guichard, Elisabeth; Feron, Gilles

    2012-01-01

    We hypothesized that interindividual differences in motor activities during chewing and/or swallowing were determining factors for the transfer of volatile aroma from the in-mouth air cavity (IMAC) toward the olfactory mucosa. In our first experiment, we looked for changes in IMAC volume after saliva deglutition in 12 healthy subjects. The mean IMAC volume was measured after empty deglutition using an acoustic pharyngometer device. Based on the time course of the IMAC volume after swallowing, we discerned two groups of subjects. The first group displayed a small, constant IMAC volume (2.26 mL ±0.62) that corresponded to a high tongue position. The second group displayed a progressive increase in IMAC (from 6.82 mL ±2.37 to 22.82 mL ±3.04) that corresponded to a progressive lowering of the tongue to its resting position. In our second experiment, we investigated the relationship between IMAC volume changes after deglutition and the level of aroma release at the nostril. For this purpose, the release of menthone was measured at the nostril level in 25 subjects who consumed similar amounts of a mint tablet. The subjects were separated into two groups corresponding to two levels of menthone release: high (H) and low (L). The mean volume of IMAC was measured during and after empty deglutition. Group H displayed a small, constant amplitude of IMAC volume change after deglutition, while Group L displayed a progressive increase in IMAC. It is likely that Group H continuously released the aroma through the veloglossal isthmus as the mint was consumed, while Group L trapped the aroma in the oral cavity and then released it into the nasal cavity upon swallowing. These results show that the in vivo aroma release profile in humans depends closely on the different motor patterns at work during empty deglutition. PMID:22815986

  11. Supplemental site inspection for Air Force Plant 59, Johnson City, New York, Volume 1: Investigation report

    SciTech Connect

    Nashold, B.; Rosenblatt, D.; Hau, J.

    1995-08-01

    This summary describes a Supplemental Site Inspection (SSI) conducted by Argonne National Laboratory (ANL) at Air Force Plant 59 (AFP 59) in Johnson City, New York. All required data pertaining to this project were entered by ANL into the Air Force-wide Installation Restoration Program Information System (IRPIMS) computer format and submitted to an appropriate authority. The work was sponsored by the United States Air Force as part of its Installation Restoration Program (IRP). Previous studies had revealed the presence of contaminants at the site and identified several potential contaminant sources. Argonne`s study was conducted to answer questions raised by earlier investigations.

  12. Exposure to severe urban air pollution influences cognitive outcomes, brain volume and systemic inflammation in clinically healthy children.

    PubMed

    Calderón-Garcidueñas, Lilian; Engle, Randall; Mora-Tiscareño, Antonieta; Styner, Martin; Gómez-Garza, Gilberto; Zhu, Hongtu; Jewells, Valerie; Torres-Jardón, Ricardo; Romero, Lina; Monroy-Acosta, Maria E; Bryant, Christopher; González-González, Luis Oscar; Medina-Cortina, Humberto; D'Angiulli, Amedeo

    2011-12-01

    Exposure to severe air pollution produces neuroinflammation and structural brain alterations in children. We tested whether patterns of brain growth, cognitive deficits and white matter hyperintensities (WMH) are associated with exposures to severe air pollution. Baseline and 1 year follow-up measurements of global and regional brain MRI volumes, cognitive abilities (Wechsler Intelligence Scale for Children-Revised, WISC-R), and serum inflammatory mediators were collected in 20 Mexico City (MC) children (10 with white matter hyperintensities, WMH(+), and 10 without, WMH(-)) and 10 matched controls (CTL) from a low polluted city. There were significant differences in white matter volumes between CTL and MC children - both WMH(+) and WMH(-) - in right parietal and bilateral temporal areas. Both WMH(-) and WMH(+) MC children showed progressive deficits, compared to CTL children, on the WISC-R Vocabulary and Digit Span subtests. The cognitive deficits in highly exposed children match the localization of the volumetric differences detected over the 1 year follow-up, since the deficits observed are consistent with impairment of parietal and temporal lobe functions. Regardless of the presence of prefrontal WMH, Mexico City children performed more poorly across a variety of cognitive tests, compared to CTL children, thus WMH(+) is likely only partially identifying underlying white matter pathology. Together these findings reveal that exposure to air pollution may perturb the trajectory of cerebral development and result in cognitive deficits during childhood. PMID:22032805

  13. QUALITY ASSURANCE HANDBOOK FOR AIR POLLUTION MEASUREMENT SYSTEMS: VOLUME IV - METEOROLOGICAL MEASUREMENTS (REVISED - AUGUST 1994)

    EPA Science Inventory

    Procedures on installing, acceptance testing, operating, maintaining and quality assuring three types of ground-based, upper air meteorological measurement systems are described. he limitations and uncertainties in precision and accuracy measurements associated with these systems...

  14. Analysis of operational requirements for medium density air transportation. Volume 1: Summary

    NASA Technical Reports Server (NTRS)

    1975-01-01

    The medium density air travel market was studied to determine the aircraft design and operational requirements. The impact of operational characteristics on the air travel system and the economic viability of the study aircraft were also evaluated. Medium density is defined in terms of numbers of people transported (20 to 500 passengers per day on round trip routes), and frequency of service ( a minumium of two and maximum of eight round trips per day) for 10 regional carriers. The operational characteristics of aircraft best suited to serve the medium density air transportation market are determined and a basepoint aircraft is designed from which tradeoff studies and parametric variations could be conducted. The impact of selected aircraft on the medium density market, economics, and operations is ascertained. Research and technology objectives for future programs in medium density air transportation are identified and ranked.

  15. DEVELOPMENT OF MESOSCALE AIR QUALITY SIMULATION MODELS. VOLUME 5. USER'S GUIDE TO THE MESOFILE POSTPROCESSING PACKAGE

    EPA Science Inventory

    The MESOscale FILE management and analysis package (MESOFILE) is a highly flexible postprocessing system designed especially for interface with the MESOPLUME, MESOPUFF, and MESOGRID regional-scale air quality models, and the MESOPAC meteorology package. The MESOFILE package is co...

  16. Solar technology assessment project. Volume 4: Solar air conditioning: Active, hybrid and passive

    NASA Astrophysics Data System (ADS)

    Yellott, J. I.

    1981-04-01

    The status of absorption cycle solar air conditioning and the Rankine cycle solar cooling system is reviewed. Vapor jet ejector chillers, solar pond based cooling, and photovoltaic compression air conditioning are also briefly discussed. Hybrid solar cooling by direct and indirect evaporative cooling, and dehumidification by desiccation are described and discussed. Passive solar cooling by convective and radiative processes, evaporative cooling by passive processes, and cooling with roof ponds and movable insulation are reviewed. Federal and state involvement in solar cooling is discussed.

  17. Improved particle impactor assembly for size selective high volume air sampler

    DOEpatents

    Langer, G.

    1987-03-23

    Air containing entrained particulate matter is directed through a plurality of parallel, narrow, vertically oriented apertures of an inlet element toward an adjacently located, relatively large, dust impaction surface preferably covered with an adhesive material. The air flow turns over the impaction surface, leaving behind, the relatively larger particles and passes through two elongate apertures defining the outer bounds of the impaction collection surface to pass through divergent passages which slow down and distribute the air flow, with entrained smaller particles, over a fine filter element that separates the fine particles from the air. By appropriate selection of dimensions and the number of inlet apertures air flow through the inlet element is provided a nonuniform velocity distribution with the lower velocities being obtained near the center of the inlet apertures, to separate out particles larger than a certain predetermined size on the impaction collection surface. The impaction collection surface, even in a moderately sized apparatus, is thus relatively large and permits the prolonged sampling of air for periods extending to four weeks. 6 figs.

  18. DEMONSTRATION OF A HYBRID INTELLIGENT CONTROL STRATEGY FOR CRITICAL BUILDING HVAC SYSTEMS

    SciTech Connect

    Craig Rieger; D. Subbaram Naidu

    2010-06-01

    Many industrial facilities utilize pressure control gradients to prevent migration of hazardous species from containment areas to occupied zones, often using Proportional-Integral-Derivative (PID) control. Within these facilities, PID control is often inadequate to maintain desired performance due to changing operating conditions. As the goal of the Heating, Ventilation and Air-Conditioning (HVAC) control system is to optimize the pressure gradients and associated flows for the plant, Linear Quadratic Tracking (LQT) provides a time-based approach to guiding plant interactions. However, LQT methods are susceptible to modeling and measurement errors, and therefore a hybrid design using the integration of soft control methods with hard control methods is developed and demonstrated to account for these errors and nonlinearities.

  19. Radiation control coatings installed on federal buildings at Tyndall Air Force Base. Volume 2: Long-term monitoring and modeling

    SciTech Connect

    Petrie, T.W.; Childs, P.W.

    1998-06-01

    The US Department of Energy`s (DOE`s) Federal Energy Management Program (FEMP) supports efforts to reduce energy use and associated expenses in the federal sector. One such effort, the New Technology Demonstration Program (NTDP), seeks to evaluate new energy-saving US technologies and secure their more timely adoption by the US government. Through a partnership with a federal site, the utility serving the site, a manufacturer of an energy-related technology, and other organizations associated with these interests, DOE can evaluate a new technology. The results of the program give federal agency decision makers more hands-on information with which to validate a decision to utilize a new technology in their facilities. This is the second volume of a two-volume report that describes the effects of radiation control coatings installed on federal buildings at Tyndall Air Force Base (AFB) in Florida by ThermShield International. ORNL`s Buildings Technology Center (BTC) was assigned the responsibility for gathering, analyzing, and reporting on the data to describe the effects of the coatings. The first volume described the monitoring plan and its implementation, the results of pre-coating monitoring, the coating installation, results from fresh coatings compared to pre-coating results, and a plan to decommission the monitoring equipment. This second volume updates and completes the presentation of data to compare performance of fresh coatings with weathered coatings.

  20. Determination of respirable mass concentration using a high volume air sampler and a sedimentation method for fractionation

    SciTech Connect

    Johnson, J.

    1995-12-31

    A preliminary study of a new method for determining respirable mass concentration is described. This method uses a high volume air sampler and subsequent fractionation of the collected mass using a particle sedimentation technique. Side-by-side comparisons of this method with cyclones were made in the field and in the laboratory. There was good agreement among the samplers in the laboratory, but poor agreement in the field. The effect of wind on the samplers` capture efficiencies is the primary hypothesized source of error among the field results. The field test took place at the construction site of a hazardous waste landfill located on the Hanford Reservation.

  1. Spatio-temporal visualization of air-sea CO2 flux and carbon budget using volume rendering

    NASA Astrophysics Data System (ADS)

    Du, Zhenhong; Fang, Lei; Bai, Yan; Zhang, Feng; Liu, Renyi

    2015-04-01

    This paper presents a novel visualization method to show the spatio-temporal dynamics of carbon sinks and sources, and carbon fluxes in the ocean carbon cycle. The air-sea carbon budget and its process of accumulation are demonstrated in the spatial dimension, while the distribution pattern and variation of CO2 flux are expressed by color changes. In this way, we unite spatial and temporal characteristics of satellite data through visualization. A GPU-based direct volume rendering technique using half-angle slicing is adopted to dynamically visualize the released or absorbed CO2 gas with shadow effects. A data model is designed to generate four-dimensional (4D) data from satellite-derived air-sea CO2 flux products, and an out-of-core scheduling strategy is also proposed for on-the-fly rendering of time series of satellite data. The presented 4D visualization method is implemented on graphics cards with vertex, geometry and fragment shaders. It provides a visually realistic simulation and user interaction for real-time rendering. This approach has been integrated into the Information System of Ocean Satellite Monitoring for Air-sea CO2 Flux (IssCO2) for the research and assessment of air-sea CO2 flux in the China Seas.

  2. Mexico City air quality research initiative, volume 3, modeling and simulation

    SciTech Connect

    Mauzy, A.

    1994-06-01

    The objective of the modeling and simulation task was to develop, test, and apply an appropriate set of models that could translate emission changes into air quality changes. Specifically, we wanted to develop models that could describe how existing measurements of ozone (O{sub 3}), carbon monoxide (CO), and sulfur dioxide (SO{sub 2}) would be expected to change if their emissions were changed. The modeling must be able to address the effects of difference in weather conditions and changes in land use as well as the effects of changes in emission levels. It must also be able to address the effects of changes in the nature and distribution of the emissions as well as changes in the total emissions. A second objective was to provide an understanding of the conditions that lead to poor air quality in Mexico City. We know in a general sense that Mexico City`s poor air quality is the result of large quantities of emissions in a confined area that is subject to light winds, but we did not know much about many aspects of the problem. For example, is the air quality on a given day primarily the result of emissions on that day...or is there an important carryover from previous nights and days? With a good understanding of the important meteorological circumstances that lead to poor air quality, we learn what it take duce an accurate forecast of impending quality so that we can determine the advisability of emergency measures.

  3. Ultimate detectability of volatile organic compounds: how much further can we reduce their ambient air sample volumes for analysis?

    PubMed

    Kim, Yong-Hyun; Kim, Ki-Hyun

    2012-10-01

    To understand the ultimately lowest detection range of volatile organic compounds (VOCs) in air, application of a high sensitivity analytical system was investigated by coupling thermal desorption (TD) technique with gas chromatography (GC) and time-of-flight (TOF) mass spectrometry (MS). The performance of the TD-GC/TOF MS system was evaluated using liquid standards of 19 target VOCs prepared in the range of 35 pg to 2.79 ng per μL. Studies were carried out using both total ion chromatogram (TIC) and extracted ion chromatogram (EIC) mode. EIC mode was used for calibration to reduce background and to improve signal-to-noise. The detectability of 19 target VOCs, if assessed in terms of method detection limit (MDL, per US EPA definition) and limit of detection (LOD), averaged 5.90 pg and 0.122 pg, respectively, with the mean coefficient of correlation (R(2)) of 0.9975. The minimum quantifiable mass of target analytes, when determined using real air samples by the TD-GC/TOF MS, is highly comparable to the detection limits determined experimentally by standard. In fact, volumes for the actual detection of the major aromatic VOCs like benzene, toluene, and xylene (BTX) in ambient air samples were as low as 1.0 mL in the 0.11-2.25 ppb range. It was thus possible to demonstrate that most target compounds including those in low abundance could be reliably quantified at concentrations down to 0.1 ppb at sample volumes of less than 10 mL. The unique sensitivity of this advanced analytical system can ultimately lead to a shift in field sampling strategy with smaller air sample volumes facilitating faster, simpler air sampling (e.g., use of gas syringes rather than the relative complexity of pumps or bags/canisters), with greatly reduced risk of analyte breakthrough and minimal interference, e.g., from atmospheric humidity. The improved detection limits offered by this system can also enhance accuracy and measurement precision. PMID:22934885

  4. Main rotor free wake geometry effects on blade air loads and response for helicopters in steady maneuvers. Volume 2: Program listings

    NASA Technical Reports Server (NTRS)

    Sadler, S. G.

    1972-01-01

    A mathematical model and computer program was implemented to study the main rotor free wake geometry effects on helicopter rotor blade air loads and response in steady maneuvers. Volume 1 (NASA CR-2110) contains the theoretical formulation and analysis of results. Volume 2 contains the computer program listing.

  5. EVALUATION OF AN EPA (ENVIRONMENTAL PROTECTION AGENCY) HIGH-VOLUME AIR SAMPLER FOR POLYCHLORINATED DIBENZO-P-DIOXINS AND POLYCHLORINATED DIBENZOFURANS

    EPA Science Inventory

    A High-Volume air sampler was evaluated for collection of poly-chlorinated dibenzo-p-dioxins (PCDD) and polychlorinated dibenzofurans (PCDF). The sampler consists of a filter, polyurethane foam adsorbent cartridge, air pump, and environmental housing. The use of an alternative ad...

  6. Tools for Evaluating Fault Detection and Diagnostic Methods for HVAC Secondary Systems

    NASA Astrophysics Data System (ADS)

    Pourarian, Shokouh

    Although modern buildings are using increasingly sophisticated energy management and control systems that have tremendous control and monitoring capabilities, building systems routinely fail to perform as designed. More advanced building control, operation, and automated fault detection and diagnosis (AFDD) technologies are needed to achieve the goal of net-zero energy commercial buildings. Much effort has been devoted to develop such technologies for primary heating ventilating and air conditioning (HVAC) systems, and some secondary systems. However, secondary systems, such as fan coil units and dual duct systems, although widely used in commercial, industrial, and multifamily residential buildings, have received very little attention. This research study aims at developing tools that could provide simulation capabilities to develop and evaluate advanced control, operation, and AFDD technologies for these less studied secondary systems. In this study, HVACSIM+ is selected as the simulation environment. Besides developing dynamic models for the above-mentioned secondary systems, two other issues related to the HVACSIM+ environment are also investigated. One issue is the nonlinear equation solver used in HVACSIM+ (Powell's Hybrid method in subroutine SNSQ). It has been found from several previous research projects (ASRHAE RP 825 and 1312) that SNSQ is especially unstable at the beginning of a simulation and sometimes unable to converge to a solution. Another issue is related to the zone model in the HVACSIM+ library of components. Dynamic simulation of secondary HVAC systems unavoidably requires an interacting zone model which is systematically and dynamically interacting with building surrounding. Therefore, the accuracy and reliability of the building zone model affects operational data generated by the developed dynamic tool to predict HVAC secondary systems function. The available model does not simulate the impact of direct solar radiation that enters a zone

  7. Tools for Evaluating Fault Detection and Diagnostic Methods for HVAC Secondary Systems

    NASA Astrophysics Data System (ADS)

    Pourarian, Shokouh

    Although modern buildings are using increasingly sophisticated energy management and control systems that have tremendous control and monitoring capabilities, building systems routinely fail to perform as designed. More advanced building control, operation, and automated fault detection and diagnosis (AFDD) technologies are needed to achieve the goal of net-zero energy commercial buildings. Much effort has been devoted to develop such technologies for primary heating ventilating and air conditioning (HVAC) systems, and some secondary systems. However, secondary systems, such as fan coil units and dual duct systems, although widely used in commercial, industrial, and multifamily residential buildings, have received very little attention. This research study aims at developing tools that could provide simulation capabilities to develop and evaluate advanced control, operation, and AFDD technologies for these less studied secondary systems. In this study, HVACSIM+ is selected as the simulation environment. Besides developing dynamic models for the above-mentioned secondary systems, two other issues related to the HVACSIM+ environment are also investigated. One issue is the nonlinear equation solver used in HVACSIM+ (Powell's Hybrid method in subroutine SNSQ). It has been found from several previous research projects (ASRHAE RP 825 and 1312) that SNSQ is especially unstable at the beginning of a simulation and sometimes unable to converge to a solution. Another issue is related to the zone model in the HVACSIM+ library of components. Dynamic simulation of secondary HVAC systems unavoidably requires an interacting zone model which is systematically and dynamically interacting with building surrounding. Therefore, the accuracy and reliability of the building zone model affects operational data generated by the developed dynamic tool to predict HVAC secondary systems function. The available model does not simulate the impact of direct solar radiation that enters a zone

  8. HVAC modifications and computerized energy analysis for the Operations Support Building at the Mars Deep Space Station at Goldstone

    NASA Technical Reports Server (NTRS)

    Halperin, A.; Stelzmuller, P.

    1986-01-01

    The key heating, ventilation, and air-conditioning (HVAC) modifications implemented at the Mars Deep Space Station's Operation Support Building at Jet Propulsion Laboratories (JPL) in order to reduce energy consumption and decrease operating costs are described. An energy analysis comparison between the computer simulated model for the building and the actual meter data was presented. The measurement performance data showed that the cumulative energy savings was about 21% for the period 1979 to 1981. The deviation from simulated data to measurement performance data was only about 3%.

  9. Operation and maintenance, fire rescue air-pack. Volume 2: Communications

    NASA Technical Reports Server (NTRS)

    1972-01-01

    The operation and maintenance procedures are described for the development model of the fire rescue air pack (FRAP) voice amplifier assembly, including the battery charger. Operational instructions include a general description of the assembly, specifications, and installation and operation. Maintenance instructions include theory of operation, preventive maintenance, repair, adjustment, and a parts list. The FRAP is intended to permit fire rescue personnel to enter a smoke-filled, toxic or oxygen depleted environment carrying their own source of breathing air. The voice amplifier assembly permits the wearer to communicate by voice with other persons in the vicinity. The battery charger assembly provides a means of keeping the amplifier batteries fully charged.

  10. USAF Bioenvironmental Noise Data Handbook. Volume 167: MA-3M air conditioner

    NASA Astrophysics Data System (ADS)

    Rau, T. H.

    1982-06-01

    The MA-3M is an electric motor-driven air conditioner designed to cool electronic equipment on aircraft during ground maintenance. This report provides measured and extrapolated data defining the bioacoustic environments produced by this unit operating at a normal rated condition. Near-field data are reported for 37 locations in a wide variety of physical and psychoacoustic measures: overall and band sound pressure levels, C-weighted and A-weighted sound levels, preferred speech interference levels, perceived noise levels, and limiting times for total daily exposure of personnel with and without standard Air Force ear protectors.

  11. Operationally efficient propulsion system study (OEPSS) data book. Volume 10; Air Augmented Rocket Afterburning

    NASA Technical Reports Server (NTRS)

    Farhangi, Shahram; Trent, Donnie (Editor)

    1992-01-01

    A study was directed towards assessing viability and effectiveness of an air augmented ejector/rocket. Successful thrust augmentation could potentially reduce a multi-stage vehicle to a single stage-to-orbit vehicle (SSTO) and, thereby, eliminate the associated ground support facility infrastructure and ground processing required by the eliminated stage. The results of this preliminary study indicate that an air augmented ejector/rocket propulsion system is viable. However, uncertainties resulting from simplified approach and assumptions must be resolved by further investigations.

  12. Autonomous Integrated Receive System (AIRS) requirements definition. Volume 1: Executive summary

    NASA Astrophysics Data System (ADS)

    Chie, C. M.; Lindsey, W. C.

    1984-08-01

    Distributed processing in the design and operation of the augmented TDRSS and the succeeding TDAS in the 1990's is discussed with the emphasis on the development of the autonomous integrated receive system (AIRS) for the operation of the S-band single access (SSA) return link in the White Sands ground terminal. This receive system has the capability of self configuration, real-time operation, and self diagnostic. The tasks of Doppler correction, demodulation, detection, and decoding are performed in an integrated manner where useful information are shared and used by ALL portions of AIRS performing these tasks. Operating modes, maintenance, system architecture, and performance characteristics are described.

  13. Autonomous Integrated Receive System (AIRS) requirements definition. Volume 1: Executive summary

    NASA Technical Reports Server (NTRS)

    Chie, C. M.; Lindsey, W. C.

    1984-01-01

    Distributed processing in the design and operation of the augmented TDRSS and the succeeding TDAS in the 1990's is discussed with the emphasis on the development of the autonomous integrated receive system (AIRS) for the operation of the S-band single access (SSA) return link in the White Sands ground terminal. This receive system has the capability of self configuration, real-time operation, and self diagnostic. The tasks of Doppler correction, demodulation, detection, and decoding are performed in an integrated manner where useful information are shared and used by ALL portions of AIRS performing these tasks. Operating modes, maintenance, system architecture, and performance characteristics are described.

  14. The Symposium Proceedings of the 1998 Air Transport Research Group (ATRG). Volume 3

    NASA Technical Reports Server (NTRS)

    Reynolds-Feighan, Aisling (Editor); Bowen, Brent D. (Editor)

    1998-01-01

    Contents include the following: airline deregulation in Australia: a medium term assessment; why can't Japan deregulate the airline industry and open the sky immediately?; toward a market-oriented air transport system?: present developments in Russian civil aviation performance and policy; the asian economic crisis and its implications for aviation policy in asia pacific: industry outlook approaching the next millennium; a tale of two airlines: the post privatization performance of two caribbean airlines: the role of capital productivity in British Airways' financial recovery; airline privatization: does it matter?; airfright demand: responding to new developments in logistics; and air cargo business relationships.

  15. Analysis of operational requirements for medium density air transportation, volume 2

    NASA Technical Reports Server (NTRS)

    1975-01-01

    The medium density air travel market is examined and defined in terms of numbers of people transported per route per day and frequency of service. The operational characteristics for aircraft to serve this market are determined and a basepoint aircraft is designed from which tradeoff studies and parametric variations can be conducted. The impact of the operational characteristics on the air travel system is evaluated along with the economic viability of the study aircraft. Research and technology programs for future study consideration are identified.

  16. Noise and vibration control for HVAC and piping systems

    SciTech Connect

    Yerges, J.F.; Yerges, J.R.

    1997-10-01

    This article offers engineering advice on how to avoid noise and vibration problems through good mechanical engineering design and strategic communication with other members of the construction team. The design of ducted HVAC systems must address six distinct but related issues--airborne equipment noise, equipment vibration, ductborne fan noise, duct breakout noise, flow generated noise, and ductborne crosstalk. Each and every one of these issues must be addressed, or the design will fail.

  17. An inventory of aeronautical ground research facilities. Volume 2: Air breathing engine test facilities

    NASA Technical Reports Server (NTRS)

    Pirrello, C. J.; Hardin, R. D.; Heckart, M. V.; Brown, K. R.

    1971-01-01

    The inventory covers free jet and direct connect altitude cells, sea level static thrust stands, sea level test cells with ram air, and propulsion wind tunnels. Free jet altitude cells and propulsion wind tunnels are used for evaluation of complete inlet-engine-exhaust nozzle propulsion systems under simulated flight conditions. These facilities are similar in principal of operation and differ primarily in test section concept. The propulsion wind tunnel provides a closed test section and restrains the flow around the test specimen while the free jet is allowed to expand freely. A chamber of large diameter about the free jet is provided in which desired operating pressure levels may be maintained. Sea level test cells with ram air provide controlled, conditioned air directly to the engine face for performance evaluation at low altitude flight conditions. Direct connect altitude cells provide a means of performance evaluation at simulated conditions of Mach number and altitude with air supplied to the flight altitude conditions. Sea level static thrust stands simply provide an instrumented engine mounting for measuring thrust at zero airspeed. While all of these facilities are used for integrated engine testing, a few provide engine component test capability.

  18. Building America Best Practices Series, Volume 10: Retrofit Techniques and Technologies: Air Sealing

    SciTech Connect

    Baechler, Michael C.; Gilbride, Theresa L.; Hefty, Marye G.; Cole, Pamala C.; Williamson, Jennifer L.; Love, Pat M.

    2010-04-12

    This report was prepared by PNNL for the U.S. Department of Energy Building America Program. The report provides information to home owners who want to make their existing homes more energy efficient by sealing leaks in the building envelope (ceiling, walls, and floors) that let in drafts and let conditioned air escape. The report provides descriptions of 19 key areas of the home where air sealing can improve home performance and energy efficiency. The report includes suggestions on how to find a qualified weatherization or home performance contractor, what to expect in a home energy audit, opportune times for performing air sealing, and what safety and health concerns to be aware of. The report describes some basic building science concepts and topics related to air sealing including ventilation, diagnostic tools, and code requirements. The report will be available for free download from the DOE Building America website. It is a suitable consumer education tool for home performance and weatherization contractors to share with customers to describe the process and value of home energy retrofits.

  19. MECHANISMS OF PHOTOCHEMICAL REACTIONS IN URBAN AIR. VOLUME II. CHAMBER STUDIES

    EPA Science Inventory

    The smog chamber facility of the Statewide Air Pollution Research Center has been employed in a study designed to provide experimental data required for the validation of kinetic computer models of chemical transformations in polluted atmospheres. A 5800-l, Teflon-coated, evacuab...

  20. Development of CO2 laser Doppler instrumentation for detection of clear air turbulence, volume 1

    NASA Technical Reports Server (NTRS)

    Harris, C. E.; Jelalian, A. V.

    1979-01-01

    Modification, construction, test and operation of an advanced airborne carbon dioxide laser Doppler system for detecting clear air turbulence are described. The second generation CAT program and those auxiliary activities required to support and verify such a first-of-a-kind system are detailed: aircraft interface; ground and flight verification tests; data analysis; and laboratory examinations.

  1. Development of CO2 laser Doppler instrumentation for detection of clear air turbulence, volume 2: Appendices

    NASA Technical Reports Server (NTRS)

    Harris, C. E.; Jelalian, A. V.

    1979-01-01

    Analyses of the mounting and mount support systems of the clear air turbulence transmitters verify that satisfactory shock and vibration isolation are attained. The mount support structure conforms to flight crash safety requirements with high margins of safety. Restraint cables reinforce the mounts in the critical loaded forward direction limiting maximum forward system deflection to 1 1/4 inches.

  2. Mexico City air quality research initiative. Volume 2, Problem definition, background, and summary of prior research

    SciTech Connect

    Not Available

    1994-06-01

    Air pollution in Mexico City has increased along with the growth of the city, the movement of its population, and the growth of employment created by industry. The main cause of pollution in the city is energy consumption. Therefore, it is necessary to take into account the city`s economic development and its prospects when considering the technological relationships between well-being and energy consumption. Air pollution in the city from dust and other particles suspended in the air is an old problem. However, pollution as we know it today began about 50 years ago with the growth of industry, transportation, and population. The level of well-being attained in Mexico City implies a high energy use that necessarily affects the valley`s natural air quality. However, the pollution has grown so fast that the City must act urgently on three fronts: first, following a comprehensive strategy, transform the economic foundation of the city with nonpolluting activities to replace the old industries, second, halt pollution growth through the development of better technologies; and third, use better fuels, emission controls, and protection of wooded areas.

  3. An evaluation of technologies for real-time measurement of rates of outdoor airflow into HVAC systems

    SciTech Connect

    Fisk, William J.; Faulkner, David; Sullivan, Douglas P.

    2004-09-01

    During the last few years, new technologies have been introduced for real-time continuous measurement of the flow rates of outdoor air (OA) into HVAC systems; however, an evaluation of these measurement technologies has not previously been published. This document describes a test system and protocols developed for a controlled evaluation of these measurement technologies. The results of tests of four commercially available measurement technologies and one prototype based on a new design are also summarized. The test system and protocol were judged practical and very useful. The series of tests identified three commercially available measurement technologies that should provide reasonably accurate measurements of OA flow rates as long as air velocities are maintained high enough to produce accurately measurable pressure signals. In HVAC systems with economizer controls, to maintain the required air velocities the OA intake will need to be divided into two sections in parallel, each with a separate OA damper. The errors in OA flow rates measured with the fourth commercially available measurement technology were 20% to 30% with horizontal probes but much larger with vertical probes. The new prototype measurement technology was the only one that appears suitable for measuring OA flow rates over their full range from 20% OA to 100% OA without using two separate OA dampers. All of the measurement devices had pressure drops that are likely to be judged acceptable. The influence of wind on the accuracy of these measurement technologies still needs to be evaluated.

  4. An evaluation of three commercially available technologies forreal-time measurement of rates of outdoor airflow into HVAC systems

    SciTech Connect

    Fisk, William J.; Faulkner, David; Sullivan, Douglas P.

    2004-10-28

    During the last few years, new technologies have been introduced for real-time continuous measurement of the flow rates of outdoor air (OA) into HVAC systems; however, an evaluation of these measurements technologies has not previously been published. This document describes a test system and protocols developed for a controlled evaluation of these measurement technologies. The results of tests of three commercially available measurement technologies are also summarized. The test system and protocol were judged practical and very useful. The three commercially available measurement technologies should provide reasonably, e.g., 20%, accurate measurements of OA flow rates as long as air velocities are maintained high enough to produce accurately measurable pressure signals. In HVAC systems with economizer controls, to maintain the required air velocities the OA intake will need to be divided into two sections in parallel, each with a separate OA damper. All of the measurement devices had pressure drops that are likely to be judged acceptable. The influence of wind on the accuracy of these measurement technologies still needs to be evaluated.

  5. Residential commissioning to assess envelope and HVAC system performance

    SciTech Connect

    Wray, Craig P.; Sherman, Max H.

    2001-08-31

    Houses do not perform optimally or even as many codes and forecasts predict. For example, Walker et al. (1998a) found large variations in thermal distribution system efficiency, as much as a factor of two even between side-by-side houses with the same system design and installation crew. This and other studies (e.g., Jump et al. 1996) indicate that duct leakage testing and sealing can readily achieve a 25 to 30% reduction in installed cooling capacity and energy consumption. As another example, consider that the building industry has recognized for at least 20 years the substantial impact that envelope airtightness has on thermal loads, energy use, comfort, and indoor air quality. However, Walker et al. (1998a) found 50% variances in airtightness for houses with the same design and construction crews, within the same subdivision. A substantial reason for these problems is that few houses are now built or retrofitted using formal design procedures, most are field assembled from a large number of components, and there is no consistent process to identify problems or to correct them. Solving the problems requires field performance evaluations of houses using appropriate and agreed upon procedures. Many procedural elements already exist in a fragmented environment; some are ready now to be integrated into a new process called residential commissioning (Wray et al. 2000). For example, California's Title 24 energy code already provides some commissioning elements for evaluating the energy performance of new houses. A house consists of components and systems that need to be commissioned, such as building envelopes, air distribution systems, cooling equipment, heat pumps, combustion appliances, controls, and other electrical appliances. For simplicity and practicality, these components and systems are usually evaluated individually, but we need to bear in mind that many of them interact. Therefore, commissioning must not only identify the energy and non-energy benefits

  6. Shuttle Entry Air Data System (SEADS) hardware development. Volume 1: Summary

    NASA Technical Reports Server (NTRS)

    While, D. M.

    1983-01-01

    Hardware development of the Shuttle Entry Data System (SEADS) is described. The system consists of an array of fourteen pressure ports, installed in an Orbiter nose cap, which, when coupled with existing fuselage mounted static pressure ports permits computation of entry flight parameters. Elements of the system that are described include the following: (1) penetration assemblies to place pressure port openings at the surface of the nose cap; (2) pressure tubes to transmit the surface pressure to transducers; (3) support posts or manifolds to provide support for, and reduce the length of, the individual pressure tubes; (4) insulation for the manifolds; and (5) a SEADS nose cap. Design, analyses, and tests to develop and certify design for flight are described. Specific tests include plasma arc exposure, radiant thermal, vibration, and structural. Volume one summarizes highlights of the program, particularly as they relate to the final design of SEADS. Volume two summarizes all of the Vought responsible activities in essentially a chronological order.

  7. Demand modelling of passenger air travel: An analysis and extension. Volume 1: Background and summary

    NASA Technical Reports Server (NTRS)

    Jacobson, I. D.

    1978-01-01

    The framework for a model of travel demand which will be useful in predicting the total market for air travel between two cities is discussed. Variables to be used in determining the need for air transportation where none currently exists and the effect of changes in system characteristics on attracting latent demand are identified. Existing models are examined in order to provide insight into their strong points and shortcomings. Much of the existing behavioral research in travel demand is incorporated to allow the inclusion of non-economic factors, such as convenience. The model developed is characterized as a market segmentation model. This is a consequence of the strengths of disaggregation and its natural evolution to a usable aggregate formulation. The need for this approach both pedagogically and mathematically is discussed.

  8. Love Canal Emergency Declaration Area habitability study. Volume 2. Air assessment: indicator chemicals. Final report

    SciTech Connect

    Not Available

    1988-02-01

    Environmental studies were conducted to provide data that could be used by the Commissioner of Health for the State of New York in determining whether the Emergency Declaration Area (EDA) surrounding the Love Canal hazardous-waste site is habitable. An air assessment was conducted for Love Canal Indicator Chemicals. Homes throughout the EDA were sampled using the Trace Atmospheric Gas Analyzer Model 6000E.

  9. Characterization of stable brush-shaped large-volume plasma generated at ambient air

    SciTech Connect

    Tang Jie; Cao Wenqing; Zhao Wei; Wang Yishan; Duan Yixiang

    2012-01-15

    A brush-shaped, large-volume plasma was generated at ambient pressure with a dc power supply and flowing argon gas, as well as a narrow outlet slit. Based on the V-I curve and emission profiles obtained in our experiment, the plasma shows some typical glow discharge characteristics. The electron density in the positive column close to the anode is about 1.4x10{sup 14}cm{sup -3} high, which is desirable for generating abundant amounts of reactive species in the plasma. Emission spectroscopy diagnosis indicates that many reactive species, such as excited argon atoms, excited oxygen atoms, excited nitrogen molecules, OH and C{sub 2} radicals, etc., generated within the plasma are distributed symmetrically and uniformly, which is preferable to some chemical reactions in practical applications. Spectral measurement also shows that the concentration of some excited argon atoms increases with the argon flow rate when the applied voltage is unvaried, while that of these excited argon atoms declines with the discharge current in the normal/subnormal glow discharge mode with the argon flow rate fixed. The plasma size is about 15 mm x 1 mm x 19 mm (L, W, H), when 38-W of discharge power is used. Such a laminar brush-shaped large-volume plasma device ensures not only efficient utilization of the plasma gas, but also effective processing of objects with large volume and complicated structure that are susceptible to high temperatures.

  10. [Environmental investigation of ground water contamination at Wright-Patterson Air Force Base, Ohio]. Volume 9, Removal action system design

    SciTech Connect

    Not Available

    1992-04-01

    This Removal Action System Design has been prepared as a Phase I Volume for the implementation of the Phase II removal action at Wright-Patterson Air Force Base (WPAFB) near Dayton, Ohio. The objective of the removal action is to prevent, to the extent practicable, the migration of ground water contaminated with chlorinated volatile organic compounds (VOCS) across the southwest boundary of Area C. The Phase 1, Volume 9 Removal Action System Design compiles the design documents prepared for the Phase II Removal Action. These documents, which are presented in Appendices to Volume 9, include: Process Design, which presents the 30 percent design for the ground water treatment system (GWTS); Design Packages 1 and 2 for Earthwork and Road Construction, and the Discharge Pipeline, respectively; no drawings are included in the appendix; Design Package 3 for installation of the Ground Water Extraction Well(s); Design Package 4 for installation of the Monitoring Well Instrumentation; and Design Package 5 for installation of the Ground Water Treatment System; this Design Package is incorporated by reference because of its size.

  11. An analysis of long and medium-haul air passenger demand, volume 1

    NASA Technical Reports Server (NTRS)

    Eriksen, S. E.

    1978-01-01

    A basic model was developed which is a two equation pair econometric system in which air passenger demand and airline level-of-service are the endogenous variables. The model aims to identify the relationship between each of these two variables and its determining factors, and to identify the interaction of demand and level-of-service with each other. The selected variable for the measure of air passenger traffic activity in a given pair market is defined as the number of passengers in a given time that originate in one region and fly to the other region for purposes other than to make a connection to a third region. For medium and long haul markets, the model seems to perform better for larger markets. This is due to a specification problem regarding the route structure variable. In larger markets, a greater percentage of nonlocal passengers are accounted for by this variable. Comparing the estimated fare elasticities of long and medium haul markets, it appears that air transportation demand is more price elastic in longer haul markets. Long haul markets demand will saturate with a fewer number of departures than will demand in medium haul markets.

  12. Phase I: the pipeline-gas demonstration plant. Demonstration plant engineering and design. Volume 17. Plant section 2500 - Plant and Instrument Air

    SciTech Connect

    1981-05-01

    Contract No. EF-77-C-01-2542 between Conoco Inc. and the US Department of Energy provides for the design, construction, and operation of a demonstration plant capable of processing bituminous caking coals into clean pipeline quality gas. The project is currently in the design phase (Phase I). This phase is scheduled to be completed in June 1981. One of the major efforts of Phase I is the process and project engineering design of the Demonstration Plant. The design has been completed and is being reported in 24 volumes. This is Volume 17 which reports the design of Plant Section 2500 - Plant and Instrument Air. The plant and instrument air system is designed to provide dry, compressed air for a multitude of uses in plant operations and maintenance. A single centrifugal air compressor provides the total plant and instrument air requirements. An air drying system reduces the dew point of the plant and instrument air. Plant Section 2500 is designed to provide air at 100/sup 0/F and 100 psig. Both plant and instrument air are dried to a -40/sup 0/F dew point. Normal plant and instrument air requirements total 1430 standard cubic feet per minute.

  13. Undulator Hall Air Temperature Fault Scenarios

    SciTech Connect

    Sevilla, J.; Welch, J.; /SLAC

    2010-11-17

    Recent experience indicates that the LCLS undulator segments must not, at any time following tuning, be allowed to change temperature by more than about {+-}2.5 C or the magnetic center will irreversibly shift outside of acceptable tolerances. This vulnerability raises a concern that under fault conditions the ambient temperature in the Undulator Hall might go outside of the safe range and potentially could require removal and retuning of all the segments. In this note we estimate changes that can be expected in the Undulator Hall air temperature for three fault scenarios: (1) System-wide power failure; (2) Heating Ventilation and Air Conditioning (HVAC) system shutdown; and (3) HVAC system temperature regulation fault. We find that for either a system-wide power failure or an HVAC system shutdown (with the technical equipment left on), the short-term temperature changes of the air would be modest due to the ability of the walls and floor to act as a heat ballast. No action would be needed to protect the undulator system in the event of a system-wide power failure. Some action to adjust the heat balance, in the case of the HVAC power failure with the equipment left on, might be desirable but is not required. On the other hand, a temperature regulation failure of the HVAC system can quickly cause large excursions in air temperature and prompt action would be required to avoid damage to the undulator system.

  14. Effect of air temperature and relative humidity at various fuel-air ratios on exhaust emissions on a per-mode basis of an Avco Lycoming 0-320 DIAD light aircraft engine. Volume 2: Individual data points

    NASA Technical Reports Server (NTRS)

    Skorobatckyi, M.; Cosgrove, D. V.; Meng, P. R.; Kempke, E. R.

    1976-01-01

    A carbureted four cylinder air cooled 0-320 DIAD Lycoming aircraft engine was tested to establish the effects of air temperature and humidity at various fuel-air ratios on the exhaust emissions on a per-mode basis. The test conditions included carburetor lean-out at air temperatures of 50, 59, 80, and 100 F at relative humidities of 0, 30, 60, and 80 percent. Temperature-humidity effects at the higher values of air temperature and relative humidity tested indicated that the HC and CO emissions increased significantly, while the NOx emissions decreased. Even at a fixed fuel-air ratio, the HC emissions increase and the NOx emissions decrease at the higher values of air temperature and humidity. Volume II contains the data taken at each of the individual test points.

  15. Griffiss Air Force Base integrated resource assessment. Volume 3, Electric resource assessment

    SciTech Connect

    Armstrong, P.R.; Shankle, S.A.; Elliott, D.B.; Stucky, D.J.; Keller, J.M.; Wahlstrom, R.R.; Dagle, J.E.; Gu, A.Y.

    1993-09-01

    The US Air Force Air Combat Command (ACC) has tasked the US Department of Energy (DOE) Federal Energy Management Program (FEMP) to identify, evaluate, and assist in acquiring all cost-effective energy projects at Griffiss Air Force Base (AFB). FEMP, with support from the Pacific Northwest Laboratory (PNL), is designing this model program for federal customers served by the Niagara Mohawk Power Company. The program with Griffiss AFB will (1) identify and evaluate all cost-effective electric energy projects; (2) develop a schedule for project acquisition considering project type, size, timing, capital requirements, as well as energy and dollar savings; and (3) secure 100% of the financing required to implement electric energy efficiency projects from Niagara Mohawk and have them procure the necessary contractors to perform detailed audits and install the technologies. This report provides the results of the electric energy resource opportunity (ERO) assessments performed by PNL at one of Niagara Mohawk`s primary federal facilities, the ACC Griffiss AFB facility located near Rome, New York. The results of the analyses of EROs are presented in seven common energy end-use categories. A narrative description of each ERO provides information on the initial cost, energy and dollar savings; impacts on operations and maintenance (O&M); and, when applicable, a discussion of energy supply and demand, energy security, and environmental issues. The evaluation methodology and technical and cost assumptions are also described for each ERO. Summary tables present the operational performance of energy end-use equipment before and after the implementation of each ERO and the results of the life-cycle cost analysis indicating the net present value (NPV) and savings-to-investment ratio (SIR) of each ERO.

  16. Compilation of air pollutant emission factors. Volume 1. Stationary point and area sources. Supplement E

    SciTech Connect

    Not Available

    1992-10-01

    In the Supplement to the Fourth Edition of AP-42 Volume I, new or revised emissions data are presented for Anthracite Coal Combustion; Natural Gas Combustion; Liquified Petroleum Gas Combustion; Wood Waste Combustion In Boilers; Bagasse Combustion In Sugar Mills; Residential Fireplaces; Residential Wood Stoves; Waste Oil Combustion; Automobile Body Incineration; Conical Burners; Open Burning; Stationary Gas Turbines for Electricity Generation; Heavy Duty Natural Gas Fired Pipeline Compressor Engines; Gasoline and Diesel Industrial Engines; Large Stationary Diesel and All Stationary Dual Fuel Engines; Soap and Detergents; and Storage of Organic Liquids.

  17. Thermal Components Boost Performance of HVAC Systems

    NASA Technical Reports Server (NTRS)

    2012-01-01

    As the International Space Station (ISS) travels 17,500 miles per hour, normal is having a constant sensation of free-falling. Normal is no rain, but an extreme amount of shine.with temperatures reaching 250 F when facing the Sun. Thanks to a number of advanced control systems onboard the ISS, however, the interior of the station remains a cool, comfortable, normal environment where astronauts can live and work for extended periods of time. There are two main control systems on the ISS that make it possible for humans to survive in space: the Thermal Control System (TCS) and the Environmental Control and Life Support system. These intricate assemblies work together to supply water and oxygen, regulate temperature and pressure, maintain air quality, and manage waste. Through artificial means, these systems create a habitable environment for the space station s crew. The TCS constantly works to regulate the temperature not only for astronauts, but for the critical instruments and machines inside the spacecraft as well. To do its job, the TCS encompasses several components and systems both inside and outside of the ISS. Inside the spacecraft, a liquid heat-exchange process mechanically pumps fluids in closed-loop circuits to collect, transport, and reject heat. Outside the ISS, an external system circulates anhydrous ammonia to transport heat and cool equipment, and radiators release the heat into space. Over the years, NASA has worked with a variety of partners.public and private, national and international. to develop and refine the most complex thermal control systems ever built for spacecraft, including the one on the ISS.

  18. Aging assessment of nuclear air-treatment system HEPA filters and adsorbers. Volume 1, Phase 1

    SciTech Connect

    Winegardner, W.K.

    1993-08-01

    A Phase I aging assessment of high-efficiency particulate air (HEPA) filters and activated carbon gas adsorption units (adsorbers) was performed by the Pacific Northwest Laboratory (PNL) as part of the US Nuclear Regulatory Commission`s (NRC) Nuclear Plant Aging Research (NPAR) Program. Information concerning design features; failure experience; aging mechanisms, effects, and stressors; and surveillance and monitoring methods for these key air-treatment system components was compiled. Over 1100 failures, or 12 percent of the filter installations, were reported as part of a Department of Energy (DOE) survey. Investigators from other national laboratories have suggested that aging effects could have contributed to over 80 percent of these failures. Tensile strength tests on aged filter media specimens indicated a decrease in strength. Filter aging mechanisms range from those associated with particle loading to reactions that alter properties of sealants and gaskets. Low radioiodine decontamination factors associated with the Three Mile Island (TMI) accident were attributed to the premature aging of the carbon in the adsorbers. Mechanisms that can lead to impaired adsorber performance include oxidation as well as the loss of potentially available active sites as a result of the adsorption of pollutants. Stressors include heat, moisture, radiation, and airborne particles and contaminants.

  19. Fuel Injector: Air swirl characterization aerothermal modeling, phase 2, volume 2

    NASA Technical Reports Server (NTRS)

    Nikjooy, M.; Mongia, H. C.; Mcdonell, V. G.; Samuelson, G. S.

    1993-01-01

    A well integrated experimental/analytical investigation was conducted to provide benchmark quality data relevant to prefilming type airblast fuel nozzle and its interaction with combustor dome air swirler. The experimental investigation included a systematic study of both single-phase flows that involved single and twin co-axial jets with and without swirl. A two-component Phase Doppler Particle Analyzer (PDPA) equipment was used to document the interaction of single and co-axial air jets with glass beads that simulate nonevaporating spray and simultaneously avoid the complexities associated with fuel atomization processes and attendant issues about the specification of relevant boundary conditions. The interaction of jets with methanol spray produced by practical airblast nozzle was also documented in the spatial domain of practical interest. Model assessment activities included the use of three turbulence models (k-epsilon, algebraic second moment (ASM) and differential second moment (DSM)) for the carrier phase, deterministic or stochastic Lagrangian treatment of the dispersed phase, and advanced numerical schemes. Although qualitatively good comparison with data was obtained for most of the cases investigated, the model deficiencies in regard to modeled dissipation rate transport equation, single length scale, pressure-strain correlation, and other critical closure issues need to be resolved before one can achieve the degree of accuracy required to analytically design combustion systems.

  20. Fuel injector: Air swirl characterization aerothermal modeling, phase 2, volume 1

    NASA Technical Reports Server (NTRS)

    Nikjooy, M.; Mongia, H. C.; Mcdonell, V. G.; Samuelsen, G. S.

    1993-01-01

    A well integrated experimental/analytical investigation was conducted to provide benchmark quality relevant to a prefilming type airblast fuel nozzle and its interaction with the combustor dome air swirler. The experimental investigation included a systematic study of both single-phase flows that involved single and twin co-axial jets with and without swirl. A two-component Phase Doppler Particle Analyzer (PDPA) was used to document the interaction of single and co-axial air jets with glass beads that simulate nonevaporating spray and simultaneously avoid the complexities associated with fuel atomization processes and attendant issues about the specification of relevant boundary conditions. The interaction of jets with methanol spray produced by practical airblast nozzle was also documented in the spatial domain of practical interest. Model assessment activities included the use of three turbulence models (k-epsilon, algebraic second moment (ASM), and differential second moment (DSM)) for the carrier phase, deterministic or stochastic Lagrangian treatment of the dispersed phase, and advanced numerical schemes. Although qualitatively good comparison with data was obtained for most of the cases investigated, the model deficiencies in regard to modeled dissipation rate transport equation, single length scale, pressure-strain correlation, and other critical closure issues need to be resolved before one can achieve the degree of accuracy required to analytically design combustion systems.

  1. Design architecture for multi-zone HVAC control systems from existing single-zone systems using wireless sensor networks

    NASA Astrophysics Data System (ADS)

    Redfern, Andrew; Koplow, Michael; Wright, Paul

    2007-01-01

    Most residential heating, ventilating, and air-conditioning (HVAC) systems utilize a single zone for conditioning air throughout the entire house. While inexpensive, these systems lead to wide temperature distributions and inefficient cooling due to the difference in thermal loads in different rooms. The end result is additional cost to the end user because the house is over conditioned. To reduce the total amount of energy used in a home and to increase occupant comfort there is a need for a better control system using multiple temperature zones. Typical multi-zone systems are costly and require extensive infrastructure to function. Recent advances in wireless sensor networks (WSNs) have enabled a low cost drop-in wireless vent register control system. The register control system is controlled by a master controller unit, which collects sensor data from a distributed wireless sensor network. Each sensor node samples local settings (occupancy, light, humidity and temperature) and reports the data back to the master control unit. The master control unit compiles the incoming data and then actuates the vent resisters to control the airflow throughout the house. The control system also utilizes a smart thermostat with a movable set point to enable the user to define their given comfort levels. The new system can reduce the run time of the HVAC system and thus decreasing the amount of energy used and increasing the comfort of the home occupations.

  2. Compressed air demand-type firefighter's breathing system, volume 1. [design analysis and performance tests

    NASA Technical Reports Server (NTRS)

    Sullivan, J. L.

    1975-01-01

    The commercial availability of lightweight high pressure compressed air vessels has resulted in a lightweight firefighter's breathing apparatus. The improved apparatus, and details of its design and development are described. The apparatus includes a compact harness assembly, a backplate mounted pressure reducer assembly, a lightweight bubble-type facemask with a mask mounted demand breathing regulator. Incorporated in the breathing regulator is exhalation valve, a purge valve and a whistle-type low pressure warning that sounds only during inhalation. The pressure reducer assembly includes two pressure reducers, an automatic transfer valve and a signaling device for the low pressure warning. Twenty systems were fabricated, tested, refined through an alternating development and test sequence, and extensively examined in a field evaluation program. Photographs of the apparatus are included.

  3. Supplement B to compilation of air pollutant emission factors, volume 1. Stationary point and area sources

    SciTech Connect

    1996-11-01

    This document contains emission factors and process information for more than 200 air pollution source categories. This Supplement to AP-42 addresses pollutant-generating activity from Bituminous And Subbituminous Coal Combustion, Anthracite Coal Combustion, Fuel Oil Combustion, Natural Gas Combustion, Liquefied Petroleum Gas Combustion, Wood Waste Combustion In Boilers, Lignite Combustion, Bagasse Combustion In Sugar Mills, Residential Fireplaces, Residential Wood Stoves, Waste Oil Combustion, Stationary Gas Turbines For Electricity Generation, Heavy-duty Natural Gas-fired Pipeline Compressor Engines And Turbines, Gasoline and Diesel Industrial Engines, Large Stationary Diesel And All Stationary Dual-fuel Engines, Adipic Acid, Cotton Ginning, Alfafalfa Dehydrating, Malt Beverages, Ceramic Products Manufacturing, Electroplating, Wildfires And Prescribed Burning, Emissions From Soils-Greenhouse Gases, Termites-Greenhouse Gases, and Lightning Emissions-Greenhouse Gases.

  4. A Model Using Local Weather Data to Determine the Effective Sampling Volume for PCB Congeners Collected on Passive Air Samplers

    PubMed Central

    2016-01-01

    We have developed and evaluated a mathematical model to determine the effective sampling volumes (Veff) of PCBs and similar compounds captured using polyurethane foam passive air samplers (PUF–PAS). We account for the variability in wind speed, air temperature, and equilibrium partitioning over the course of the deployment of the samplers. The model, provided as an annotated Matlab script, predicts the Veff as a function of physical-chemical properties of each compound and meteorology from the closest Integrated Surface Database (ISD) data set obtained through NOAA’s National Centers for Environmental Information (NCEI). The model was developed to be user-friendly, only requiring basic Matlab knowledge. To illustrate the effectiveness of the model, we evaluated three independent data sets of airborne PCBs simultaneously collected using passive and active samplers: at sites in Chicago, Lancaster, UK, and Toronto, Canada. The model provides Veff values comparable to those using depuration compounds and calibration against active samplers, yielding an average congener specific concentration method ratio (active/passive) of 1.1 ± 1.2. We applied the model to PUF–PAS samples collected in Chicago and show that previous methods can underestimate concentrations of PCBs by up to 40%, especially for long deployments, deployments conducted under warming conditions, and compounds with log Koa values less than 8. PMID:26963482

  5. A Model Using Local Weather Data to Determine the Effective Sampling Volume for PCB Congeners Collected on Passive Air Samplers.

    PubMed

    Herkert, Nicholas J; Martinez, Andres; Hornbuckle, Keri C

    2016-07-01

    We have developed and evaluated a mathematical model to determine the effective sampling volumes (Veff) of PCBs and similar compounds captured using polyurethane foam passive air samplers (PUF-PAS). We account for the variability in wind speed, air temperature, and equilibrium partitioning over the course of the deployment of the samplers. The model, provided as an annotated Matlab script, predicts the Veff as a function of physical-chemical properties of each compound and meteorology from the closest Integrated Surface Database (ISD) data set obtained through NOAA's National Centers for Environmental Information (NCEI). The model was developed to be user-friendly, only requiring basic Matlab knowledge. To illustrate the effectiveness of the model, we evaluated three independent data sets of airborne PCBs simultaneously collected using passive and active samplers: at sites in Chicago, Lancaster, UK, and Toronto, Canada. The model provides Veff values comparable to those using depuration compounds and calibration against active samplers, yielding an average congener specific concentration method ratio (active/passive) of 1.1 ± 1.2. We applied the model to PUF-PAS samples collected in Chicago and show that previous methods can underestimate concentrations of PCBs by up to 40%, especially for long deployments, deployments conducted under warming conditions, and compounds with log Koa values less than 8. PMID:26963482

  6. Technology Solutions Case Study: Overcoming Comfort Issues Due to Reduced Flow Room Air Mixing

    SciTech Connect

    2015-03-01

    Energy efficiency upgrades reduce heating and cooling loads on a house. With enough load reduction and if the HVAC system warrants replacement, the HVAC system is often upgraded with a more efficient, lower capacity system that meets the loads of the upgraded house. In this project, IBACOS studied when HVAC equipment is downsized and ducts are unaltered to determine conditions that could cause a supply air delivery problem and to evaluate the feasibility of modifying the duct systems using minimally invasive strategies to improve air distribution.

  7. Review of Pre- and Post-1980 Buildings in CBECS - HVAC Equipment

    SciTech Connect

    Winiarski, David W.; Jiang, Wei; Halverson, Mark A.

    2006-12-01

    PNNL was tasked by DOE to look at HVAC systems and equipment for Benchmark buildings based on 2003 CBECS data. This white paper summarizes the results of PNNL’s analysis of 2003 CBECS data and provides PNNL’s recommendations for HVAC systems and equipment for use in the Benchmark buildings.

  8. The Symposium Proceedings of the 1998 Air Transport Research Group (ATRG). Volume 2

    NASA Technical Reports Server (NTRS)

    Reynolds-Feighan, Aisling (Editor); Bowen, Brent D. (Editor)

    1998-01-01

    The Air Transport Research Group of the World Conference on Transportation Research (WCTR) Society was formally launched as a special interest group at the 7th Triennial WCTR in Sydney, Australia in 1995. Since then, our membership base has expanded rapidly, and now includes over 400 active transportation researchers, policy-makers, industry executives, major corporations and research institutes from 28 countries. It became a tradition that the ATRG would hold an international conference at least once a year. In 1998, the ATRG organized a consecutive stream of 14 aviation sessions at the 8th Triennial WCTR Conference (July 12-17: Antwerp). Again, on 19-21 July, 1998, the ATRG Symposium was organized and executed very successfully by Dr. Aisling Reynolds-Feighan of the University College of Dublin. The Aviation Institute at the University of Nebraska at Omaha has published the Proceedings of the 1998 ATRG Dublin Symposium (being co-edited by Dr. Aisling Reynolds-Feighan and Professor Brent Bowen), and the Proceedings of the 1998 WCTR-ATRG Conference (being co-edited by Professors Tae H. Oum and Brent Bowen).

  9. Cargo Logistics Airlift Systems Study (CLASS). Volume 3: Cross impact between the 1990 market and the air physical distribution systems, book 2

    NASA Technical Reports Server (NTRS)

    Burby, R. J.; Kuhlman, W. H.

    1978-01-01

    Book 2 of this volume is divided into the following sections: (1) commodities and system networks; (2) future mode choice decisions and commodity air eligibility; (3) comparative cargo transportation costs - air, truck, rail and water; (4) elasticities of demand; (5) operating cost; (6) operating profit, rate making, and returns; (7) importance of rate and service on future aircraft; (8) potential market demand for new aircraft; (9) scenario of events affecting system/market growth; and (10) future study and technology requirements.

  10. Are Ventilation Filters Degrading Indoor Air Quality in California Classrooms?

    SciTech Connect

    Fisk, William J.; Destaillats, H.; Apte, M.G.; Destaillats,, Hugo; Fisk, Michael G. Apte and William J.

    2008-10-01

    Heating, ventilating, and cooling classrooms in California consume substantial electrical energy. Indoor air quality (IAQ) in classrooms affects studenthealth and performance. In addition to airborne pollutants that are emitted directly by indoor sources and those generated outdoors, secondary pollutants can be formed indoors by chemical reaction of ozone with other chemicals and materials. Filters are used in nearly all classroom heating, ventilation and air?conditioning (HVAC) systems to maintain energy-efficient HVAC performance and improve indoor air quality; however, recent evidence indicates that ozone reactions with filters may, in fact, be a source of secondary pollutants. This project quantitatively evaluated ozone deposition in HVAC filters and byproduct formation, and provided a preliminary assessment of the extent towhich filter systems are degrading indoor air quality. The preliminary information obtained will contribute to the design of subsequent research efforts and the identification of energy efficient solutions that improve indoor air quality in classrooms and the health and performance of students.

  11. Patrick Air Force Base integrated resource assessment. Volume 1, Executive summary

    SciTech Connect

    Sandusky, W.F.; Wahlstrom, R.R.

    1994-03-01

    Some of the most difficult problems encountered at federal sites in reducing energy consumption in a cost-effective manner revolve around understanding where energy is being used and what technologies can be employed to decrease energy use. Many large federal sites have one or two meters to track electric energy use for several thousand buildings and numerous industrial processes. Even where meters are available on individual buildings or family housing units, the meters are not consistently read. When the federal energy manager has been able to identify high energy users, the energy manager may not have the background, training, or resources to determine the most cost-effective options for reducing this energy use. This limitation can lead to selection of suboptimal projects that prevent the site from achieving full life-cycle cost savings. The USDOE Federal Energy Management Program has been tasked by the US Air Force Space Command to identify, evaluate, and acquire all cost-effective energy projects at selected federal facilities. This is part of a model program developed to provide a systematic approach to evaluating energy opportunities. The program (1) identifies the building groups and end uses using the most energy (not just having the greatest energy-use intensity) and (2) evaluates the numerous options for retrofit or installation of new technology that will result in the selection of the most cost-effective technologies. This model program provides the federal energy manager with a road map to significantly reduce energy use in a planned, rational, cost-effective fashion that is not biased by the constraints of the typical funding sources available to federal sites. The results from this assessment process can easily be turned into a 5- to 10-year energy management plan.

  12. A systems approach to retrofitting residential HVAC systems

    SciTech Connect

    McWilliams, J.A.; Walker, I.S.

    2004-05-01

    A Best Practices Guide for retrofitting residential HVAC systems has recently been completed by DOE. The guide uses diagnostics and checklists to guide the user to specific retrofit packages that maximize retrofit energy savings, comfort and safety potential. The guide uses a systems approach to retrofitting where the interaction of different building components is considered throughout the retrofit selection process. For example, added building envelope insulation reduces building loads so that smaller capacity HVAC systems can be used. In this study, several houses were surveyed using the Best Practices Guide and a single house was selected for retrofitting. The objectives were to demonstrate how a successful system-wide retrofit can be carried out and to provide feedback to improve the guide. Because it represents a departure from current practice, a key aspect of this study was to investigate the interactions with contractors and code officials who are unfamiliar with the systems approach. The study found that the major barrier to the systems approach in retrofits was in changing the working practices of contractors and code officials.

  13. Measurement of HVAC system performance and local ventilation using passive perfluorocarbon tracer technology

    SciTech Connect

    Dietz, R.N.; Goodrich, R.W.

    1995-06-01

    In April of 1993, two (2) perfluorocarbon tracer (PFT) ventilation/indoor air quality assessment tests were performed in the Gleeson Hall building of the SUNY Farmingdale campus. The building was being modified, in part, as a result of significant occupant complaints of perceived poor air quality. The four story building had a basement first floor with air supplied normally by an HVAC system labelled as AC1. During this study, AC1 was inoperational and the basement interior rooms (walls) were primarily gone; the other three floors were still being used for classes. It is possible that a sense of poor air quality may have been perceived by first-floor occupants because they were working in the basement, but this issue could not be addressed. The second floor had two (2) lecture halls--Rm 202 (handled by AC4) and Rm 204 (handled by AC5); the balance of the second floor interior rooms and corridors was split between two other air handling systems, AC2 for the west side of the building and AC3 for the east side. The remaining 3rd and 4th floors were also split about evenly between AC2 and AC3. The perimeter rooms, equipped with wall units having their own outside air (OA) source plus centralized return air (RA) bypasses, were not included in this testing which was restricted to the basement floor (1st floor) and the four operating air handling systems, AC2 to AC5, during Test 1 and only AC2 to AC5 during Test 2. Two types of tests were performed using the full suite of 5 PFT types available. The first test was designed to measure the infiltration, exfiltration, and air exchange between the 5 AC zones above and the second test used the 5th tracer, which had been in the basement, as a distributed source throughout the four other zones to act as a surrogate pollutant source. This report provides final conclusions of both tests and suggestions regarding its usefulness in similar building ventilation and indoor air quality assessments.

  14. Impact of traffic volume and composition on the air quality and pedestrian exposure in urban street canyon

    NASA Astrophysics Data System (ADS)

    Rakowska, Agata; Wong, Ka Chun; Townsend, Thomas; Chan, Ka Lok; Westerdahl, Dane; Ng, Simon; Močnik, Griša; Drinovec, Luka; Ning, Zhi

    2014-12-01

    Vehicle emissions are identified as a major source of air pollution in metropolitan areas. Emission control programs in many cities have been implemented as part of larger scale transport policy interventions to control traffic pollutants and reduce public health risks. These interventions include provision of traffic-free and low emission zones and congestion charging. Various studies have investigated the impact of urban street configurations, such as street canyon in urban centers, on pollutants dispersion and roadside air quality. However, there are few investigations in the literature to study the impact of change of fleet composition and street canyon effects on the on-road pollutants concentrations and associated roadside pedestrian exposure to the pollutants. This study presents an experimental investigation on the traffic related gas and particle pollutants in and near major streets in one of the most developed business districts in Hong Kong, known as Central. Both street canyon and open roadway configurations were included in the study design. Mobile measurement techniques were deployed to monitor both on-road and roadside pollutants concentrations at different times of the day and on different days of a week. Multiple traffic counting points were also established to concurrently collect data on traffic volume and fleet composition on individual streets. Street canyon effects were evident with elevated on-road pollutants concentrations. Diesel vehicles were found to be associated with observed pollutant levels. Roadside black carbon concentrations were found to correlate with their on-road levels but with reduced concentrations. However, ultrafine particles showed very high concentrations in roadside environment with almost unity of roadside/on-road ratios possibly due to the accumulation of primary emissions and secondary PM formation. The results from the study provide useful information for the effective urban transport design and bus route

  15. Development of Alternative Continuing Educational Systems for Preventing the Technological Obsolescence of Air Force Scientists and Engineers. Volume 1. Basic Study.

    ERIC Educational Resources Information Center

    Slebodnick, Edward B.; And Others

    Volume 1 of the study reports a work effort to define and give guidelines for the acquisition of cost-effective alternative continuing education (CE) systems to prevent the technological obsolescence of Air Force military scientific and engineering officer personnel. A detailed background survey of the problem was conducted using questionnaires,…

  16. The Conference Proceedings of the 1999 Air Transport Research Group (ATRG) of the WCTR Society. Volume 4

    NASA Technical Reports Server (NTRS)

    Zhang, Anming (Editor); Bowen, Brent D. (Editor)

    1999-01-01

    Issues around direct flights across Taiwan Strait are always one of the hottest topics in eastern Asia transport market. Although the direct links have not been connected yet, they are still highly concerned by different disciplines of politics, laws, and management. Airlines and related business also watch closely to these issues for policy changes will easily affect their interests in Chinese market which the future of the air transportation in eastern Asia is heavily depending on. In the past decades, Hong Kong was the most important hub in this market; it will still be an important one in the future. It is proved, however, traffic on the link between Hong Kong and Taiwan can be shifted to the link between Macau and Taiwan, so can it be shifted to the links across Taiwan Strait. Moreover, outgoing passengers from China transferred in Hong Kong can also find transit services in Taiwan. These movements will possibly cause a big change in eastern Asian air transport system for there are millions of passengers travelling in this area. The uncertainties of direct links across Taiwan Strait are still leaving, some problems unsolved. Whether the direct links will be defined as international routes or domestic' routes are not clear; the selection of hubs and airlines to provide direct services are not yet made; even the type of freedoms and bilateral agreements can also change the market and network quite a lot. A much bigger volume of passengers can also be found if further travelling deregulation for Chinese to travel across Taiwan Strait can be made. All these variables are making issues around direct flights worthy of continuous observant.

  17. Overestimation of thoracic gas volume during the airway resistance maneuver. A potential error in the diagnosis of air trapping.

    PubMed

    Nigro, Carlos A; Dibur, Eduardo; Lima, Sandra; Giavedoni, Santiago; Prieto, Ernesto J; Rhodius, Edgardo E

    2005-01-01

    There are no data published about the agreement between the measurement of thoracic gas volume (TGV) during the airway resistance (TGV-Raw) and the conventional technique described by Dubois. The aim of this study was to establish the agreement between both methods to measure TGV. We studied eighty consecutive subjects. Only sixty-six performed acceptable plethysmography maneuvers. The patients were measured with a constant volume plethysmograph (Medical Graphics 1085 DL). TGV was performed in the same patient with two techniques: 1) during the airway resistance (Raw) measurement (TGV-Raw) and 2) during quiet breathing at the end of expiration (TGV). The panting frequency was 1 to 2 Hz with both maneuvers. The differences between both techniques were expressed in percentage (deltaTGV %) and absolute values (deltaTGV). The TGV-Raw of the whole group was higher than TGV (3.69 +/- 1.08 l vs 3.28 +/- 1.05 l, p < 0.001). Similarly, the subgroups of patients had a greater TGV-Raw than TGV (Normal: 3.44 +/- 0.77 l vs 2.98 +/- 0.72 l , p < 0.001; Obstructive: 4.08 +/- 1.19 l vs 3.71 +/- 1.15 l, p < 0.001; Restrictive: 2.62 +/- 0.49 l vs 2.25 +/- 0.51 l, p < 0.01). There was a considerable lack of agreement between the TGV-Raw and TGV, with discrepancies of up to +0.95 l or +34%. The deltaTGV % was similar between the patients' subgroups and between the subjects with different degree of airflow obstruction (Normal: 16.5 +/- 10%, Obstructive: 10.8 +/- 9.4%, Restrictive: 18 +/- 14.3%, p NS; mild obstruction: 10.7 +/- 11%, moderate obstruction: 12.3 +/- 5.7, severe obstruction: 10.1+/- 6.6, p NS). In conclusion, TGV-Raw was larger than TGV. This was because the patients generally panted at a volume above FRC when performing the TGV-Raw maneuver. TGV-Raw should not be used to estimate FRC because FRC would be overestimated and the diagnosis of air trapping may be erroneous. PMID:15830790

  18. Influence of pulsed nanosecond volume discharge in atmospheric-pressure air on the electrical characteristics of MCT epitaxial films

    NASA Astrophysics Data System (ADS)

    Grigoryev, Denis V.; Voitsekhovskii, Alexandr V.; Lozovoy, Kirill A.; Nesmelov, Sergey N.; Dzyadukh, Stanislav M.; Tarasenko, Viktor F.; Shulepov, Michail A.; Dvoretskii, Sergei A.

    2015-12-01

    The purpose of this paper was investigating the effect of volume nanosecond discharge in air at atmospheric pressure on the electro-physical properties of the HgCdTe (MCT) epitaxial films grown by molecular beam epitaxy. Hall measurements of electro-physical parameters of MCT samples after irradiation have shown that there is a layer of epitaxial films exhibiting n-type conductivity that is formed in the near-surface area. After more than 600 pulses of influence parameters and thickness of the resulting n-layer is such that the measured field dependence of Hall coefficient corresponds to the material of n-type conductivity. Also it is shown that the impact of the discharge leads to significant changes in electro-physical characteristics of MIS structures. This fact is demonstrated by increase in density of positive fixed charge, change in the hysteresis type of the capacitance-voltage characteristic, an increase in density of surface states. The preliminary results show that it is possible to use such actions in the development of technologies of the controlled change in the properties of MCT.

  19. Characterization and control of the microbial community affiliated with copper or aluminum heat exchangers of HVAC systems.

    PubMed

    Schmidt, Michael G; Attaway, Hubert H; Terzieva, Silva; Marshall, Anna; Steed, Lisa L; Salzberg, Deborah; Hamoodi, Hameed A; Khan, Jamil A; Feigley, Charles E; Michels, Harold T

    2012-08-01

    Microbial growth in heating ventilation and air-conditioning (HVAC) systems with the subsequent contamination of indoor air is of increasing concern. Microbes and the subsequent biofilms grow easily within heat exchangers. A comparative study where heat exchangers fabricated from antimicrobial copper were evaluated for their ability to limit microbial growth was conducted using a full-scale HVAC system under conditions of normal flow rates using single-pass outside air. Resident bacterial and fungal populations were quantitatively assessed by removing triplicate sets of coupons from each exchanger commencing the fourth week after their installation for the next 30 weeks. The intrinsic biofilm associated with each coupon was extracted and characterized using selective and differential media. The predominant organisms isolated from aluminum exchangers were species of Methylobacterium of which at least three colony morphologies and 11 distinct PFGE patterns we found; of the few bacteria isolated from the copper exchangers, the majority were species of Bacillus. The concentrations and type of bacteria recovered from the control, aluminum, exchangers were found to be dependent on the type of plating media used and were 11,411-47,257 CFU cm(-2) per coupon surface. The concentration of fungi was found to average 378 CFU cm(-2). Significantly lower concentrations of bacteria, 3 CFU cm(-2), and fungi, 1 CFU cm(-2), were recovered from copper exchangers regardless of the plating media used. Commonly used aluminum heat exchangers developed stable, mixed, bacterial/fungal biofilms in excess of 47,000 organisms per cm(2) within 4 weeks of operation, whereas the antimicrobial properties of metallic copper were able to limit the microbial load affiliated with the copper heat exchangers to levels 99.97 % lower during the same time period. PMID:22569892

  20. Operational maintenance data for power generation distribution and HVAC components

    SciTech Connect

    Hollis, H.D.; Hale, P.S. Jr.; Arno, R.G.; Briggs, S.J.

    1995-12-31

    This paper describes the culmination of a 24,000 man hour effort to collect operational and maintenance data on 239 power generation, power distribution and HVAC items, including gas turbine generators, diesel engine generators, switch gear assemblies, cables, boilers, piping, valves and chillers. This program was designed to determine the effects of new technology equipment, i.e., equipment installed after 1971, on availability. The central hypothesis was that this new equipment would exhibit a significant increase in availability, with corresponding decreases in required maintenance and the occurrence of failures. Information was obtained on a variety of commercial and industrial facility types (including office buildings, hospitals, water treatment facilities, prisons, utilities, manufacturing facilities, school universities and bank computer centers), with varying degrees of maintenance quality.

  1. Co-simulation of innovative integrated HVAC systems in buildings

    SciTech Connect

    Trcka, Marija; Hensena, Jan L.M.; Wetter, Michael

    2010-06-21

    Integrated performance simulation of buildings HVAC systems can help in reducing energy consumption and increasing occupant comfort. However, no single building performance simulation (BPS) tool offers sufficient capabilities and flexibilities to analyze integrated building systems and to enable rapid prototyping of innovative building and system technologies. One way to alleviate this problem is to use co-simulation, as an integrated approach to simulation. This article elaborates on issues important for co-simulation realization and discusses multiple possibilities to justify the particular approach implemented in the here described co-simulation prototype. The prototype is validated with the results obtained from the traditional simulation approach. It is further used in a proof-of-concept case study to demonstrate the applicability of the method and to highlight its benefits. Stability and accuracy of different coupling strategies are analyzed to give a guideline for the required coupling time step.

  2. Building America Expert Meeting Report: Transitioning Traditional HVAC Contractors to Whole House Performance Contractors

    SciTech Connect

    Burdick, A.

    2011-10-01

    This report outlines findings resulting from a U.S. Department of Energy Building America expert meeting to determine how HVAC companies can transition from a traditional contractor status to a service provider for whole house energy upgrade contracting. IBACOS has embarked upon a research effort under the Building America Program to understand business impacts and change management strategies for HVAC companies. HVAC companies can implement these strategies in order to quickly transition from a 'traditional' heating and cooling contractor to a service provider for whole house energy upgrade contracting. Due to HVAC service contracts, which allow repeat interaction with homeowners, HVAC companies are ideally positioned in the marketplace to resolve homeowner comfort issues through whole house energy upgrades. There are essentially two primary ways to define the routes of transition for an HVAC contractor taking on whole house performance contracting: (1) Sub-contracting out the shell repair/upgrade work; and (2) Integrating the shell repair/upgrade work into their existing business. IBACOS held an Expert Meeting on the topic of Transitioning Traditional HVAC Contractors to Whole House Performance Contractors on March 29, 2011 in San Francisco, CA. The major objectives of the meeting were to: Review and validate the general business models for traditional HVAC companies and whole house energy upgrade companies Review preliminary findings on the differences between the structure of traditional HVAC Companies and whole house energy upgrade companies Seek industry input on how to structure information so it is relevant and useful for traditional HVAC contractors who are transitioning to becoming whole house energy upgrade contractors Seven industry experts identified by IBACOS participated in the session along with one representative from the National Renewable Energy Laboratory (NREL). The objective of the meeting was to validate the general operational profile of an

  3. United States Air Force 611th Civil Engineer Squadron, Elmendorf AFB, Alaska. Final remedial investigation report, Galena Airport and Campion Air Station, Alaska. Volume 1. Text

    SciTech Connect

    1996-03-01

    The U.S. Air Force (USAF) has conducted a Remedial Investigation (RI) at the Galena Airport (formerly Galena Air Force Station) and Campion Air Station (AS), Alaska. The purpose of this report is to summarize the activities and findings of the investigation and, on the basis of this information, make recommendations on future activities at the Galena Airport and Campion AS sites. Information from the RI at these sites was also used to support a baseline risk assessment.

  4. Simulations of sizing and comfort improvements for residential forced-air heating and cooling systems

    SciTech Connect

    Walker, I.S.; Degenetais, G.; Siegel, J.A.

    2002-05-01

    In many parts of North America residential HVAC systems are installed outside conditioned space. This leads to significant energy losses and poor occupant comfort due to conduction and air leakage losses from the air distribution ducts. In addition, cooling equipment performance is sensitive to air flow and refrigerant charge that have been found to be far from manufacturers specifications in most systems. The simulation techniques discussed in this report were developed in an effort to provide guidance on the savings potentials and comfort gains that can be achieved by improving ducts (sealing air leaks) and equipment (correct air-flow and refrigerant charge). The simulations include the complex air flow and thermal interactions between duct systems, their surroundings and the conditioned space. They also include cooling equipment response to air flow and refrigerant charge effects. Another key aspect of the simulations is that they are dynamic to account for cyclic losses from the HVAC system and the effect of cycle length on energy and comfort performance. To field test the effect of changes to residential HVAC systems requires extensive measurements to be made for several months for each condition tested. This level of testing is often impractical due to cost and time limitations. Therefore the Energy Performance of Buildings Group at LBNL developed a computer simulation tool that models residential HVAC system performance. This simulation tool has been used to answer questions about equipment downsizing, duct improvements, control strategies and climate variation so that recommendations can be made for changes in residential construction and HVAC installation techniques that would save energy, reduce peak demand and result in more comfortable homes. Although this study focuses on California climates, the simulation tool could easily be applied to other climates. This report summarizes the simulation tool and discusses the significant developments that allow

  5. Improved modelling of HVAC system/envelope inteactions in residential buildings

    SciTech Connect

    Modera, M.P.; Treidler, B.

    1995-03-01

    General building energy simulation programs do not typically simulate interactions between HVAC systems and building envelopes. For this reason, a simulation tool which includes interactions between duct systems, building envelopes, and heating and cooling appliances in residential buildings has been developed. The simulation tool uses DOE- 2 (to model space conditioning loads and zone temperatures), COMIS (an airflow network solver), and a model of duct leakage and conduction losses. Three augmentations to the simulation tool are presented herein, along with sample results. These include: (1) modeling of steady-state thermosiphon flows in ducts, (2) improved simplified modeling of duct thermal mass effects, and (3) modeling of multi-speed space conditioning equipment. Multi-speed air conditioners are shown to be more sensitive to duct efficiency than single-speed equipment, because their efficiency decreases with increasing cooling load. Thermosiphon flows through duct systems are estimated to be 5-16% of the total heating load, depending on the duct insulation level. The duct dynamics model indicates that duct thermal mass decreases the energy delivery efficiency of the distribution system by 1-6 percentage points.

  6. An implementation of co-simulation for performance prediction of innovative integrated HVAC systems in buildings

    SciTech Connect

    Trcka, Marija; Wetter, Michael; Hensen, Jan L.M.

    2010-07-01

    Integrated performance simulation of buildings and heating, ventilation and air-conditioning (HVAC) systems can help reducing energy consumption and increasing level of occupant comfort. However, no singe building performance simulation (BPS) tool offers sufficient capabilities and flexibilities to accommodate the ever-increasing complexity and rapid innovations in building and system technologies. One way to alleviate this problem is to use co-simulation. The co-simulation approach represents a particular case of simulation scenario where at least two simulators solve coupled differential-algebraic systems of equations and exchange data that couples these equations during the time integration. This paper elaborates on issues important for co-simulation realization and discusses multiple possibilities to justify the particular approach implemented in a co-simulation prototype. The prototype is verified and validated against the results obtained from the traditional simulation approach. It is further used in a case study for the proof-of-concept, to demonstrate the applicability of the method and to highlight its benefits. Stability and accuracy of different coupling strategies are analyzed to give a guideline for the required coupling frequency. The paper concludes by defining requirements and recommendations for generic cosimulation implementations.

  7. Estimating occupant satisfaction of HVAC system noise using quality assessment index.

    PubMed

    Forouharmajd, Farhad; Nassiri, Parvin; Monazzam, Mohammad R; Yazdchi, Mohammadreza

    2012-01-01

    Noise may be defined as any unwanted sound. Sound becomes noise when it is too loud, unexpected, uncontrolled, happens at the wrong time, contains unwanted pure tones or unpleasant. In addition to being annoying, loud noise can cause hearing loss, and, depending on other factors, can affect stress level, sleep patterns and heart rate. The primary object for determining subjective estimations of loudness is to present sounds to a sample of listeners under controlled conditions. In heating, ventilation and air conditioning (HVAC) systems only the ventilation fan industry (e.g., bathroom exhaust and sidewall propeller fans) uses loudness ratings. In order to find satisfaction, percent of exposure to noise is the valuable issue for the personnel who are working in these areas. The room criterion (RC) method has been defined by ANSI standard S12.2, which is based on measured levels of in HVAC systems noise in spaces and is used primarily as a diagnostic tool. The RC method consists of a family of criteria curves and a rating procedure. RC measures background noise in the building over the frequency range of 16-4000 Hz. This rating system requires determination of the mid-frequency average level and determining the perceived balance between high-frequency (HF) sound and low-frequency (LF) sound. The arithmetic average of the sound levels in the 500, 1000 and 2000 Hz octave bands is 44.6 dB; therefore, the RC 45 curve is selected as the reference for spectrum quality evaluation. The spectral deviation factors in the LF, medium-frequency sound and HF regions are 2.9, 7.5 and -2.3, respectively, giving a Quality Assessment Index (QAI) of 9.8. This concludes the QAI is useful in estimating an occupant's probable reaction when the system design does not produce optimum sound quality. Thus, a QAI between 5 and 10 dB represents a marginal situation in which acceptance by an occupant is questionable. However, when sound pressure levels in the 16 or 31.5 Hz octave bands exceed 65

  8. Building America Expert Meeting Report. Transitioning Traditional HVAC Contractors to Whole House Performance Contractors

    SciTech Connect

    Burdick, Arlan

    2011-10-01

    This expert meeting was hosted by the IBACOS Building America research team to determine how HVAC companies can transition from a traditional contractor status to a service provider for whole house energy upgrade contracting.

  9. Changes in the electro-physical properties of MCT epitaxial films affected by a plasma volume discharge induced by an avalanche beam in atmospheric-pressure air

    NASA Astrophysics Data System (ADS)

    Grigoryev, D. V.; Voitsekhovskii, A. V.; Lozovoy, K. A.; Tarasenko, V. F.; Shulepov, M. A.

    2015-11-01

    In this paper the influence of the plasma volume discharge of nanosecond duration formed in a non-uniform electric field at atmospheric pressure on samples of epitaxial films HgCdTe (MCT) films are discussed. The experimental data show that the action of pulses of nanosecond volume discharge in air at atmospheric pressure leads to changes in the electrophysical properties of MCT epitaxial films due to formation of a near-surface high- conductivity layer of the n-type conduction. The preliminary results show that it is possible to use such actions in the development of technologies for the controlled change of the properties of MCT.

  10. Comparison of Cryotop and micro volume air cooling methods for cryopreservation of bovine matured oocytes and blastocysts

    PubMed Central

    PUNYAWAI, Kanchana; ANAKKUL, Nitira; SRIRATTANA, Kanokwan; AIKAWA, Yoshio; SANGSRITAVONG, Siwat; NAGAI, Takashi; IMAI, Kei; PARNPAI, Rangsun

    2015-01-01

    This study was designed to compare the efficiency of the Cryotop method and that of two methods that employ a micro volume air cooling (MVAC) device by analyzing the survival and development of bovine oocytes and blastocysts vitrified using each method. In experiment I, in vitro-matured (IVM) oocytes were vitrified using an MVAC device without direct contact with liquid nitrogen (LN2; MVAC group) or directly plunged into LN2 (MVAC in LN2 group). A third group of IVM oocytes was vitrified using a Cryotop device (Cryotop group). After warming, vitrified oocytes were fertilized in vitro. There were no significant differences in cleavage and blastocyst formation rates among the three vitrified groups, with the rates ranging from 53.1% to 56.6% and 20.0% to 25.5%, respectively; however, the rates were significantly lower (P < 0.05) than those of the fresh control group (89.3% and 43.3%, respectively) and the solution control group (87.3% and 42.0%, respectively). In experiment II, in vitro-produced (IVP) expanded blastocysts were vitrified using the MVAC, MVAC in LN2 and Cryotop methods, warmed and cultured for survival analysis and then compared with the solution control group. The rate of development of vitrified-warmed expanded blastocysts to the hatched blastocyst stage after 24 h of culture was lower in the MVAC in LN2 group than in the solution control group; however, after 48–72 h of culture, the rates did not significantly differ between the groups. These results indicate that the MVAC method without direct LN2 contact is as effective as the standard Cryotop method for vitrification of bovine IVM oocytes and IVP expanded blastocysts. PMID:26119929

  11. In pursuit of clean air: a data book of problems and strategies at the state level. Volume 3: Federal Regions IV and VI

    SciTech Connect

    Garvey, D.B.; Streets, D.G.

    1980-02-01

    This is the third volume of a five-volume report, designed to provide useful information for policy analysis in the Department of Energy, especially for the examination of possible areas of conflict between the implementation of a national energy policy calling for the increased use of coal and the pursuit of clean air. Information is presented for each state in Federal Regions IV and VI under the following section headings: state title page (includes a summary of air quality data); revised state implementation plan outline; maps of nonattainment areas, as designated; Storage and Retrieval of Aerometric Data (SAROAD); SAROAD data maps; power plant data; power plant maps; and county maps. States in Federal Region IV include: Alabama, Florida, Georgia, Kentucky, Mississippi, North Carolina, South Carolina, and Tennessee. Those in Federal Region VI include: Arkansas, Louisiana, New Mexico, Oklahoma, and Texas. (JGB)

  12. In pursuit of clean air: a data book of problems and strategies at the state level. Volume 2. Federal Regions I, II, and III

    SciTech Connect

    Garvey, D.B.; Streets, D.G.

    1980-02-01

    The Clean Air Act Amendments of 1977 and EPA regulations set up stringent requirements for the control of emissions in areas where the National Ambient Air Quality Standards were being exceeded. Implementation plans have been devised by the various states for the attainment of those standards. This second volume of the five-volume series presents outlines of the plans in Federal Regions I, II, and III and maps of the nonattainment status of counties and subcounty areas in each state. Federal Region I consists of the following states: Connecticut, Maine, Massachusetts, New Hampshire, Rhode Island, and Vermont. Federal Region II is made up of New Jersey and New York; Federal Region III is composed of Delaware, Maryland, Pennsylvania, Virginia, and West Virginia. (JGB)

  13. Simulation model air-to-air plate heat exchanger

    SciTech Connect

    Wetter, Michael

    1999-01-01

    A simple simulation model of an air-to-air plate heat exchanger is presented. The model belongs to a collection of simulation models that allows the eflcient computer simulation of heating, ventilation, and air-conditioning (HVAC) systems. The main emphasis of the models is to shorten computation time and to use only input data that are known in the design process of an HVAC system. The target of the models is to describe the behavior of HVAC components in the part-load operation mode, which is becoming increasingly important in energy eficient HVAC systems. The models are intended to be used for yearly energy calculations or load calculations with time steps of about 10 minutes or larger. Short- time dynamic effects, which are of interest for different aspects of control theory, are neglected. The part-load behavior is expressed in terms of the nominal condition and the dimensionless variation of the heat transfer with change of mass flow and temperature. The effectiveness- NTU relations are used to parametrize the convective heat transfer at nominal conditions and to compute the part-load condition. If the heat transfer coefficients on the two exchanger sides are not equal (i. e. due to partial bypassing of air), their ratio can be easily calculated and set as a parameter. The model is static and uses explicit equations only. The explicit model formulation ensures short computation time and numerical stability, which allows using the model with sophisticated engineering methods like automatic system optimization. This paper fully outlines the algorithm description and its simplifications. It is not tailored for any particular simulation program to ensure easy implementation in any simulation program.

  14. Installation restoration program. Site investigation report, Volume 1. 182 Airlift Wing, Illinois Air National Guard, Greater Peoria Regional Airport, Peoria, Illinois. Final report

    SciTech Connect

    1996-06-01

    Site Investigation Report, Illinois Air National Guard, 182nd Airlift Wing, Greater Peoria Regional Airport, Peoria, Illinois, Volume I - Text. This is the first volume of a two volume Site Investigation Report. Three sites (Site 1 - Septic System Filter Beds, Site 2 - Grassy Area Along Facility Boundary East of the Aircraft Apron, and Site 3 - Grass Area West of Aircraft Apron and East of Fuel Truck Parking) were investigated under the Installation Restoration Program. Soil and groundwater samples were collected and analyzed. A Remedial Investigation was recommended for the soils at Site 1. No further action was recommended for Site 2 and the soils at Site 3. A groundwater investigation was recommended to identify the source of low concentrations of VOCs in the groundwater.

  15. Installation restoration program. Site investigation report, Volume 2. 182 Airlift Wing, Illinois Air National Guard, Greater Peoria Regional Airport, Peoria, Illinois. Final report

    SciTech Connect

    1996-06-01

    Site Investigation Report, Illinois Air National Guard, 182nd Airlift Wing, Greater Peoria Regional Airport, Peoria, Illinois, Volume II - Appendices A-K. This is the second volume of a two volume Site Investigation Report. Three sites (Site 1 - Septic System Filter Beds Site 2 Grassy Area Facility Boundary East of the Aircraft Apron, and Site 3 - Grass Area West of Aircraft Apron and East of Fuel Truck Parking) were investigated under the Installation Restoration Program. Soil and groundwater samples were collected and analyzed. A Remedial Investigation was recommended for the soils at Site 1. No further action was recommended for Site 2 and the soils at Site 3. A groundwater investigation was recommended to identify the source of low concentrations of VOCs in the groundwater.

  16. The Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Oum, Tae Hoon (Editor); Bowen, Brent D. (Editor)

    1997-01-01

    Topics reported on in the proceedings include: Industrial reform and air transport development in China; the economic effects of airline deregulation and the Open-Sky policy of Korea; Open Skies in India; Japanese domestic air fares under the regulatory regime; the competitive position of airline networks; air transport and regional economic development in the European Union; and corporate dilemmas and strategies of European Airlines.

  17. HVAC system of the Seavans multi-use complex

    SciTech Connect

    Ishikawa, Masayuki ); Yazawa, Kunio )

    1994-12-01

    This article describes a unique project which features radiant heating and cooling, pressurized smoke control and a cogeneration system. This project, which is located in the Tokyo, Japan waterfront area, has turned a site previously occupied by factory warehouses into an attractive zone with a great deal of water and greenery. Before the project, the site was bordered by a river, a channel and spur railroad tracks. Today, it is a modern urban space complete with such essential infrastructures as roads, bridge, water supply, sewage, and a local HVAC system. The main building consists of two towers--the Seavans South with head-quarters facilities and the Seavans North with rental office spaces--with an atrium (called Amall) in the center. The structure has a plot area of 26,468 m[sup 2] (284,909 ft[sup 2]), and a total floor space of 167,807 m[sup 2] (1,806,319 ft[sup 2]). The Seavans South and North towers are each 24 stores (99 m; 324 ft) high, and both have two penthouses and two levels of basements.

  18. Causes of Indoor Air Quality Problems in Schools: Summary of Scientific Research. Revised Edition.

    ERIC Educational Resources Information Center

    Bayer, Charlene W.; Crow, Sidney A.; Fischer, John

    Understanding the primary causes of indoor air quality (IAQ) problems and how controllable factors--proper heating, ventilation and air-conditioning (HVAC) system design, allocation of adequate outdoor air, proper filtration, effective humidity control, and routine maintenance--can avert problems may help all building owners, operators, and…

  19. Compressed-Air Energy Storage: Preliminary design and site development program in an aquifer. Volume 1: Executive summary

    NASA Astrophysics Data System (ADS)

    McCafferty, T. W.; Walke, W. C.; Bonk, J. S.

    1981-07-01

    The behavior and suitability of an aquifer-based compressed air energy storage (CAES) facility were investigated. The project was part of a five-phase program to promote compressed air energy storage and underground pumped hydro in the United States. The background, project organization, and summarization of all project work are provided.

  20. OHIO RIVER BASIN ENERGY STUDY: AIR QUALITY AND RELATED IMPACTS. VOLUME I. DOCUMENTATION IN SUPPORT OF KEY ORBES AIR QUALITY FINDINGS

    EPA Science Inventory

    This report was prepared as part of the Ohio River Basin Energy Study (ORBES), a multi-disciplinary research program supported by the Environmental Protection Agency. The extensive air quality analysis undertaken for the ORBES included examination of pollutant emissions and resul...

  1. IAQ and air handling unit design

    SciTech Connect

    Gill, K.E.

    1996-01-01

    Indoor air quality (IAQ) concerns are affecting the design of air handlers currently being offered by the manufacturers of equipment in the marketplace. These design changes are being driven by increased awareness, code changes, literature, and lawsuits within the HVAC industry. The design professionals who apply the manufacturers` products are acutely aware of the need to improve the quality of air within buildings. With the new awareness of indoor air quality issues come more options, different construction techniques, and modularity in air handling unit design.

  2. Prototype of a computer method for designing and analyzing heating, ventilating and air conditioning proportional, electronic control systems

    NASA Astrophysics Data System (ADS)

    Barlow, Steven J.

    1986-09-01

    The Air Force needs a better method of designing new and retrofit heating, ventilating and air conditioning (HVAC) control systems. Air Force engineers currently use manual design/predict/verify procedures taught at the Air Force Institute of Technology, School of Civil Engineering, HVAC Control Systems course. These existing manual procedures are iterative and time-consuming. The objectives of this research were to: (1) Locate and, if necessary, modify an existing computer-based method for designing and analyzing HVAC control systems that is compatible with the HVAC Control Systems manual procedures, or (2) Develop a new computer-based method of designing and analyzing HVAC control systems that is compatible with the existing manual procedures. Five existing computer packages were investigated in accordance with the first objective: MODSIM (for modular simulation), HVACSIM (for HVAC simulation), TRNSYS (for transient system simulation), BLAST (for building load and system thermodynamics) and Elite Building Energy Analysis Program. None were found to be compatible or adaptable to the existing manual procedures, and consequently, a prototype of a new computer method was developed in accordance with the second research objective.

  3. The Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the WCTR Society. Volume 1

    NASA Technical Reports Server (NTRS)

    Oum, Tae Hoon (Editor); Bowen, Brent D. (Editor)

    1997-01-01

    Topics included in the proceedings are: The effect of liberalized air transport bilaterals; cost competitiveness of major airlines; economic effects of duopoly competition in Korea; transforming Canada's aviation regulations; liberalization in Europe; airline labor cost in a liberalized Europe; noncooperative collusion; European air transport deregulation; public ownership and deregulation in the Scandanavian airline industry; airline competition between London and Amsterdam; and a banker's view of the European airline industry.

  4. Screening analysis for EPACT-covered commercial HVAC and water-heating equipment

    SciTech Connect

    S Somasundaram; PR Armstrong; DB Belzer; SC Gaines; DL Hadley; S Katipumula; DL Smith; DW Winiarski

    2000-05-25

    EPCA requirements state that if the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE) amends efficiency levels prescribed in Standard 90.1-1989, then DOE must establish an amended uniform national manufacturing standard at the minimum level specified in amended Standard 90.1. However, DOE can establish higher efficiency levels if it can show through clear and convincing evidence that a higher efficiency level, that is technologically feasible and economically justified, would produce significant additional energy savings. On October 29, 1999, ASHRAE approved the amended Standard 90.1, which increases the minimum efficiency levels for some of the commercial heating, cooling, and water-heating equipment covered by EPCA 92. DOE asked Pacific Northwest National Laboratory (PNNL) to conduct a screening analysis to determine the energy-savings potential of the efficiency levels listed in Standard 90.1-1999. The analysis estimates the annual national energy consumption and the potential for energy savings that would result if the EPACT-covered products were required to meet these efficiency levels. The analysis also estimates additional energy-savings potential for the EPACT-covered products if they were to exceed the efficiency levels prescribed in Standard 90-1-1999. In addition, a simple life-cycle cost (LCC) analysis was performed for some alternative efficiency levels. This paper will describe the methodology, data assumptions, and results of the analysis. The magnitude of HVAC and SWH loads imposed on equipment depends on the building's physical and operational characteristics and prevailing climatic conditions. To address this variation in energy use, coil loads for 7 representative building types at 11 climate locations were estimated based on a whole-building simulation.

  5. Effect of car speed on amount of air supplied by ventilation system to the space of car cabin

    NASA Astrophysics Data System (ADS)

    Fišer, Jan; Pokorný, Jan

    2014-03-01

    The amount of air supplied by ventilation system (HVAC system) of a car into a cabin is one of the main parameters for the correct simulation and prediction of a car cabin heat load. This amount is not based only on the current setting of the HVAC system, but also on the actual operating conditions and speed of the car. The authors therefore carried out experiments in the cabin of a passenger car in real traffic, while observing the amount of air on the speed of the car and setting of flap in mixing chamber. In a subsequent analysis the authors defined dependence of the airflow rate supplied by HVAC system on the speed of the car. Obtained empirical formulas were then used as a part of the code which calculates the data for the HVAC boundary conditions in the simulation of the car cabin environment.

  6. Pilots' use of a traffic alert and collision-avoidance system (TCAS 2) in simulated air carrier operations. Volume 1: Methodology, summary and conclusions

    NASA Technical Reports Server (NTRS)

    Chappell, Sheryl L.; Billings, Charles E.; Scott, Barry C.; Tuttell, Robert J.; Olsen, M. Christine; Kozon, Thomas E.

    1989-01-01

    Pilots' use of and responses to a traffic alert and collision-avoidance system (TCAS 2) in simulated air carrier line operations are described in Volume 1. TCAS 2 monitors the positions of nearby aircraft by means of transponder interrogation, and it commands a climb or descent when conflicting aircraft are projected to reach an unsafe closest point-of-approach within 20 to 25 seconds. A different level of information about the location of other air traffic was presented to each of three groups of flight crews during their execution of eight simulated air carrier flights. A fourth group of pilots flew the same segments without TCAS 2 equipment. Traffic conflicts were generated at intervals during the flights; many of the conflict aircraft were visible to the flight crews. The TCAS equipment successfully ameliorated the seriousness of all conflicts; three of four non-TCAS crews had hazardous encounters. Response times to TCAS maneuver commands did not differ as a function of the amount of information provided, nor did response accuracy. Differences in flight experience did not appear to contribute to the small performance differences observed. Pilots used the displays of conflicting traffic to maneuver to avoid unseen traffic before maneuver advisories were issued by the TCAS equipment. The results indicate: (1) that pilots utilize TCAS effectively within the response times allocated by the TCAS logic, and (2) that TCAS 2 is an effective collision avoidance device. Volume II contains the appendices referenced in Volume I, providing details of the experiment and the results, and the text of two reports written in support of the program.

  7. Pilots' use of a traffic alert and collision-avoidance system (TCAS 2) in simulated air carrier operations. Volume 2: Appendices

    NASA Technical Reports Server (NTRS)

    Chappell, Sheryl L.; Billings, Charles E.; Scott, Barry C.; Tuttell, Robert J.; Olsen, M. Christine; Kozon, Thomas E.

    1989-01-01

    Pilots' use of and responses to a traffic alert and collision-avoidance system (TCAS 2) in simulated air carrier line operations are discribed in Volume 1. TCAS 2 monitors the positions of nearby aircraft by means of transponder interrogation, and it commands a climb or descent which conflicting aircraft are projected to reach an unsafe closest point-of-approach within 20 to 25 seconds. A different level of information about the location of other air traffic was presented to each of three groups of flight crews during their execution of eight simulated air carrier flights. A fourth group of pilots flew the same segments without TCAS 2 equipment. Traffic conflicts were generated at intervals during the flights; many of the conflict aircraft were visible to the flight crews. The TCAS equipment successfully ameliorated the seriousness of all conflicts; three of four non-TCAS crews had hazardous encounters. Response times to TCAS maneuver commands did not differ as a function of the amount of information provided, nor did response accuracy. Differences in flight experience did not appear to contribute to the small performance differences observed. Pilots used the displays of conflicting traffic to maneuver to avoid unseen traffic before maneuver advisories were issued by the TCAS equipment. The results indicate: (1) that pilots utilize TCAS effectively within the response times allocated by the TCAS logic, and (2) that TCAS 2 is an effective collision avoidance device. Volume 2 contains the appendices referenced in Volume 1, providing details of the experiment and the results, and the text of two reports written in support of the program.

  8. Analytical modeling of operating characteristics of premixing-prevaporizing fuel-air mixing passages. Volume 1: Analysis and results

    NASA Technical Reports Server (NTRS)

    Anderson, O. L.; Chiappetta, L. M.; Edwards, D. E.; Mcvey, J. B.

    1982-01-01

    A model for predicting the distribution of liquid fuel droplets and fuel vapor in premixing-prevaporizing fuel-air mixing passages of the direct injection type is reported. This model consists of three computer programs; a calculation of the two dimensional or axisymmetric air flow field neglecting the effects of fuel; a calculation of the three dimensional fuel droplet trajectories and evaporation rates in a known, moving air flow; a calculation of fuel vapor diffusing into a moving three dimensional air flow with source terms dependent on the droplet evaporation rates. The fuel droplets are treated as individual particle classes each satisfying Newton's law, a heat transfer, and a mass transfer equation. This fuel droplet model treats multicomponent fuels and incorporates the physics required for the treatment of elastic droplet collisions, droplet shattering, droplet coalescence and droplet wall interactions. The vapor diffusion calculation treats three dimensional, gas phase, turbulent diffusion processes. The analysis includes a model for the autoignition of the fuel air mixture based upon the rate of formation of an important intermediate chemical species during the preignition period.

  9. Building America Case Study: Evaluating Through-Wall Air Transfer Fans, Pittsburgh, Pennsylvania (Fact Sheet)

    SciTech Connect

    Not Available

    2014-10-01

    In this project, Building America team IBACOS performed field testing in a new construction unoccupied test house in Pittsburgh, Pennsylvania to evaluate heating, ventilating, and air conditioning (HVAC) distribution systems during heating, cooling, and midseason conditions. Four air-based HVAC distribution systems were assessed:-a typical airflow ducted system to the bedrooms, a low airflow ducted system to the bedrooms, a system with transfer fans to the bedrooms, and a system with no ductwork to the bedrooms. The relative ability of each system was considered with respect to relevant Air Conditioning Contractors of America and ASHRAE standards for house temperature uniformity and stability, respectively.

  10. Technical and economic assessment of fluidized-bed-augmented compressed-air energy-storage system. Volume I. Executive summary

    SciTech Connect

    Giramonti, A.J.; Lessard, R.D.; Merrick, D.; Hobson, M.J.

    1981-09-01

    An energy storage system which could be attractive for future electric utility peak-load applications is a modified gas turbine power system utilizing underground storage of very high pressure air. The compressed air energy storage (CAES) concept involves using off-peak electricity generated from indigenous coal or nuclear sources to compress air, storing the air in large underground facilities, and withdrawing the air during peak-load periods when it would be heated by combustion and expanded through gas turbines to generate power. The attractiveness of the CAES concept is based upon its potential to supply competitively priced peaking energy, to reduce peak-load power plant dependence on petroleum-based fuels, and to provide a means for leveling the utility system load demand. Therefore, a technical and economic assessment of coal-fired fluidized bed (FBC) combustor/compressed air energy storage (FBC/CAES) systems was performed and is described. The conclusions drawn from the FBC/CAES study program are encouraging. They indicate that pressurized FBC/CAES power plants should be technologically feasible, provide good performance, and be economically competitive. Specifically, it is concluded that: coal-fired FBC/CAES systems should be technically feasible in the near future and potentially attractive for peak-load power generation; and an open-bed PFBC/CAES configuration would provide the best candidate for early commercialization. It has relatively low risk combined with moderate cost and reasonable round-trip heat rate. It also has the potential for future growth options which tend to reduce costs and lower fuel consumption.

  11. The Maintenance of Heating, Ventilating and Air-Conditioning Systems and Indoor Air Quality in Schools: A Guide for School Facility Managers. Technical Bulletin.

    ERIC Educational Resources Information Center

    Wheeler, Arthur E.

    To help maintain good indoor air quality (IAQ) in schools, guidance for the development and implementation of an effective program for maintenance and operation of heating, ventilating, and air-conditioning (HVAC) systems are discussed. Frequently, a building's occupants will complain about IAQ when the temperature or humidity are at uncomfortable…

  12. The Conference Proceedings of the 2001 Air Transport Research Society (ATRS) of the WCTR Society. Volume 3

    NASA Technical Reports Server (NTRS)

    Lee, Yeong-Heok (Editor); Bowen, Brent D. (Editor); Tarry, Scott E. (Editor)

    2001-01-01

    The papers presented at this conference include: 1) The Global Airline Company: Agent of Market Power or Competition? 2) Airport Pavement Management; 3) Reservation System Providers and the Impact of Codeshare Arrangements on Screen Display; 4) Strategic Classification of Current Airline Alliances and Examination of Critical Factors Involving the Formations - an Explorative Perspective; 5) Airport Privatization Policy and Performance Measurement in Korea; 6) Pilot and Air Traffic Controller Relationships: The Role of Interdependence and Relative Influence; 7) Liberalization of Air Cargo Services: Background and an Economic Analysis; 8) The Implication of Hub and Spoke Network on the Airline Alliance Strategy.

  13. Laboratory validation of vost and semivost for halogenated hydrocarbons from the Clean Air Act amendments list. Volume 2. Final report

    SciTech Connect

    Jackson, M.D.; Bursey, J.T.; Merrill, R.G.; McAllister, R.A.; McGaughey, J.F.

    1993-04-29

    The Clean Air Act Amendments of 1990, Title III, present a need for stationary source sampling and analytical methods for the list of 189 compounds. EPA has used Volatile Organic Sampling Train (VOST) and Semivolatile Organic Sampling Train (SemiVOST) sampling and analytical methods for the type of sampling of organic compounds in the past, but these methodologies have been completely validated for only a few of the organic compounds. In the study, the applicability of VOST and SemiVOST techniques to Clean Air Act halogenated compounds has been evaluated under laboratory conditions. The methods were evaluated first to determine whether the compounds could be analyzed successfully.

  14. Small-scale on-line diagnostics for an HVAC system

    SciTech Connect

    Dodier, R.H.; Kreider, J.F.; Curtiss, P.S.

    1998-10-01

    This paper describes an automated fault detection and diagnosis scheme for HVAC equipment, the Real-Time Diagnostic System (RTDS). The principles of operation of the RTDS are outlined, a computer implementation of the RTDS is described, and results of applying the RTDS to HVAC laboratory data are presented. The tests indicated that application of this inference system to the diagnosis of mixing box failures yields encouraging results. Although misdiagnosis of failure conditions is more frequent than the authors might like, false alarms are uncommon. The tests also show that training a diagnostic model on one mixing box and using the model on the other mixing boxes yields good results.

  15. Student Understanding of the Volume, Mass, and Pressure of Air within a Sealed Syringe in Different States of Compression.

    ERIC Educational Resources Information Center

    de Berg, Kevin Charles

    1995-01-01

    Investigation of (n=101) 17- to 18-year-old students' responses to a task relating to Boyle's Law for gases found that 34% to 38% of students did not understand the concepts of volume and mass, respectively, of a gas under the given circumstances. (Author/MKR)

  16. The Conference Proceedings of the 1997 Air Transport Research Group (ATRG) of the WCTR Society. Volume 3

    NASA Technical Reports Server (NTRS)

    Oum, T. H.; Bowen, B. D.

    1997-01-01

    This paper covers topics such as: Safety and Air Fares; International Airline Safety; Multi-fare Seat Allocation Problem; Dynamic Allocation of Airline Seat Inventory; Seat Allocation on Flights with Two Fares; Effects of Intercontinental Alliances; Domestic Airline Mergers; Simulating the Effects of Airline Deregulation on Frequency Choice; and Firm Size Inequality and Market Power.

  17. Articulated, Performance-Based Instruction Objectives Guide for Air Conditioning, Refrigeration, and Heating. Volume II (Second Year).

    ERIC Educational Resources Information Center

    Henderson, William Edward, Jr., Ed.

    This articulation guide contains 17 units of instruction for the second year of a two-year vocational program designed to prepare the high school graduate to install, maintain, and repair various types of residential and commercial heating, air conditioning, and refrigeration equipment. The units are designed to help the student to expand and…

  18. The 1980 Guide to the Evaluation of Educational Experiences in the Armed Services. [Volume] 1: Air Force.

    ERIC Educational Resources Information Center

    Sullivan, Eugene J.; And Others

    For more than 35 years, this Guide has been the standard reference work for recognizing learning acquired in military life. All the courses offered by the Air Force are listed and briefly described. Each course description includes the course title and number: the length of the course, and where and when it was offered; the course objectives; the…

  19. PROCEEDINGS OF THE 1991 EPA/AWMA INTERNATIONAL SYMPOSIUM: MEASUREMENT OF TOXIC AND RELATED AIR POLLUTANTS - VOLUME II

    EPA Science Inventory

    A joint conference of the sixth year co-sponsored by the Atmospheric Research and Exposure Assessment Laboratory (AREAL) of the U.S. Environmental Protection Agency and the Air and Waste Management Association was held in Durham, North Carolina, May 6-19, 1991. he technical progr...

  20. PROCEEDINGS OF THE 1991 EPA/AWMA INTERNATIONAL SYMPOSIUM: MEASUREMENT OF TOXIC AND RELATED AIR POLLUTANTS - VOLUME I

    EPA Science Inventory

    A joint conference of the sixth year co-sponsored by the Atmospheric Research and Exposure Assessment Laboratory (AREAL) of the U.S. Environmental Protection Agency and the Air and Waste Management Association was held in Durham, North Carolina, May 6-19, 1991. he technical progr...

  1. Survey and bibliography on attainment of laminar flow control in air using pressure gradient and suction, volume 1

    NASA Technical Reports Server (NTRS)

    Bushnell, D. M.; Tuttle, M. H.

    1979-01-01

    A survey was conducted and a bibliography compiled on attainment of laminar flow in air through the use of favorable pressure gradient and suction. This report contains the survey, summaries of data for both ground and flight experiments, and abstracts of referenced reports. Much early information is also included which may be of some immediate use as background material for LFC applications.

  2. Commercialization of air conditioning heat pump/water heater. Final technical report, Volume 1: Transmittal documents; Executive summary; Project summary

    SciTech Connect

    1996-01-30

    This is the final technical report on a commercialization project for an air conditioning heat pump water heater. The objective of the project was to produce a saleable system which would be economically competitive with natural gas and cost effective with regard to initial cost versus annual operating costs. The development and commercialization of the system is described.

  3. Surface Environmental Surveillance Project: Locations Manual Volume 1 – Air and Water Volume 2 – Farm Products, Soil & Vegetation, and Wildlife

    SciTech Connect

    Fritz, Brad G.; Patton, Gregory W.; Stegen, Amanda; Poston, Ted M.

    2009-01-01

    This report describes all environmental monitoring locations associated with the Surface Environmental Surveillance Project. Environmental surveillance of the Hanford site and surrounding areas is conducted by the Pacific Northwest National Laboratory (PNNL) for the U.S. Department of Energy (DOE). Sampling is conducted to evaluate levels of radioactive and nonradioactive pollutants in the Hanford environs, as required in DOE Order 450.1, Environmental Protection Program, and DOE Order 5400.5, Radiation Protection of the Public and the Environment. The environmental surveillance sampling design is described in the Hanford Site Environmental Monitoring Plan, United States Department of Energy, Richland Operation Office (DOE/RL-91-50). This document contains the locations of sites used to collect samples for the Surface Environmental Surveillance Project (SESP). Each section includes directions, maps, and pictures of the locations. A general knowledge of roads and highways on and around the Hanford Site is necessary to successfully use this manual. Supplemental information (Maps, Gazetteer, etc.) may be necessary if user is unfamiliar with local routes. The SESP is a multimedia environmental surveillance effort to measure the concentrations of radionuclides and chemicals in environmental media to demonstrate compliance with applicable environmental quality standards and public exposure limits, and assessing environmental impacts. Project personnel annually collect selected samples of ambient air, surface water, agricultural products, fish, wildlife, and sediments. Soil and vegetation samples are collected approximately every 5 years. Analytical capabilities include the measurement of radionuclides at very low environmental concentrations and, in selected media, nonradiological chemicals including metals, anions, volatile organic compounds, and total organic carbon.

  4. Benefits and technological challenges in the implementation of TiO2-based ultraviolet photocatalytic oxidation (UVPCO) air cleaners

    SciTech Connect

    Hodgson, Al; Destaillats, Hugo; Hotchi, Toshifumi; Fisk, William J.

    2008-10-01

    Heating, ventilating, and cooling classrooms in California consume substantial electrical energy. Indoor air quality (IAQ) in classrooms affects student health and performance. In addition to airborne pollutants that are emitted directly by indoor sources and those generated outdoors, secondary pollutants can be formed indoors by chemical reaction of ozone with other chemicals and materials. Filters are used in nearly all classroom heating, ventilation and air-conditioning (HVAC) systems to maintain energy-efficient HVAC performance and improve indoor air quality; however, recent evidence indicates that ozone reactions with filters may, in fact, be a source of secondary pollutants. This project quantitatively evaluated ozone deposition in HVAC filters and byproduct formation, and provided a preliminary assessment of the extent to which filter systems are degrading indoor air quality. The preliminary information obtained will contribute to the design of subsequent research efforts and the identification of energy efficient solutions that improve indoor air quality in classrooms and the health and performance of students.

  5. Field test of two high-pressure, direct-contact downhole steam generators. Volume I. Air/diesel system

    SciTech Connect

    Marshall, B.W.

    1983-05-01

    As a part of the Project DEEP STEAM to develop technology to more efficiently utilize steam for the recovery of heavy oil from deep reservoirs, a field test of a downhole steam generator (DSG) was performed. The DSG burned No. 2 diesel fuel in air and was a direct-contact, high pressure device which mixed the steam with the combustion products and injected the resulting mixture directly into the oil reservoir. The objectives of the test program included demonstration of long-term operation of a DSG, development of operational methods, assessment of the effects of the steam/combustion gases on the reservoir and comparison of this air/diesel DSG with an adjacent oxygen/diesel direct contact generator. Downhole operation of the air/diesel DSG was started in June 1981 and was terminated in late February 1982. During this period two units were placed downhole with the first operating for about 20 days. It was removed, the support systems were slightly modified, and the second one was operated for 106 days. During this latter interval the generator operated for 70% of the time with surface air compressor problems the primary source of the down time. Thermal contact, as evidenced by a temperature increase in the production well casing gases, and an oil production increase were measured in one of the four wells in the air/diesel pattern. Reservoir scrubbing of carbon monoxide was observed, but no conclusive data on scrubbing of SO/sub x/ and NO/sub x/ were obtained. Corrosion of the DSG combustor walls and some other parts of the downhole package were noted. Metallurgical studies have been completed and recommendations made for other materials that are expected to better withstand the downhole combustion environment. 39 figures, 8 tables.

  6. Indoor air quality and work-environment study. Library of Congress, Madison Building. Volume 2. Results of indoor air environmental monitoring

    SciTech Connect

    Not Available

    1990-07-01

    A systematic study was designed to assess the nature and spatial distribution of employee health symptoms and comfort concerns in the Madison Building of the Library of Congress (LOC), Washington, DC. Environmental monitoring was conducted at more than 100 sites within the building. The mean temperature for the building was 73.1 F, with a general trend for the temperature to increase throughout the building on all days from morning to afternoon. The mean relative humidity was 49.2 percent. Mean carbon-dioxide (124389) measurements increased at all sampling locations throughout the morning. Whole building air exchanges were relatively constant averaging between 0.85 and 0.79 air changes per hour. The real time respirable particle measurement mean value was 5.5 micrograms/cubic meter (microg/cu m). Nicotine (54115) was detected in several areas of the building ranging as high as 18.5 microg/cu m. Formaldehyde (50000) concentration was very low as was the acetaldehyde (75070) concentration. The mean acetone (67641) concentration was 32.5 microg/cu m. Volatile organic compounds ranged as high as 2ppm with the most predominant ones being xylene (1330207). The mean benzene (71432) concentration was 2 parts per billion. Total volatile organic compounds averaged 1.1 parts per million (ppm). Chlorpyrifos (2921882) was the only targeted pesticide observed above the analytical limit of detection and was documented in only one sample at 0.004 microg/cu m. Whole building carbon-monoxide (630080) (CO) levels averaged between 1 and 2ppm.

  7. Project W-320, 241-C-106 sluicing HVAC calculations, Volume 4

    SciTech Connect

    Bailey, J.W.

    1998-07-30

    This supporting document has been prepared to make the FDNW calculations for Project W-320, readily retrievable. The report contains the following design calculations: Cooling load in pump pit 241-AY-102; Pressure relief seal loop design; Process building piping stress analysis; Exhaust skid maximum allowable leakage criteria; and Recirculation heat, N509 duct requirements.

  8. Project W-320, 241-C-106 sluicing HVAC calculations, Volume 1

    SciTech Connect

    Bailey, J.W.

    1998-08-07

    This supporting document has been prepared to make the FDNW calculations for Project W-320, readily retrievable. The report contains the following calculations: Exhaust airflow sizing for Tank 241-C-106; Equipment sizing and selection recirculation fan; Sizing high efficiency mist eliminator; Sizing electric heating coil; Equipment sizing and selection of recirculation condenser; Chiller skid system sizing and selection; High efficiency metal filter shielding input and flushing frequency; and Exhaust skid stack sizing and fan sizing.

  9. State Skill Standards: Heating, Ventilation, Air Conditioning, and Refrigeration

    ERIC Educational Resources Information Center

    Ball, Larry; Soukup, Dennis

    2006-01-01

    The Department of Education has undertaken an ambitious effort to develop statewide career and technical education skill standards. The standards in this document are for Heating, Ventilation, Air Conditioning and Refrigeration (HVAC&R) programs and are designed to clearly state what the student should know and be able to do upon completion of an…

  10. Indoor air quality standards of performance applications guide

    SciTech Connect

    Linder, R.J.; Dorgan, C.B.; Dorgan, C.E.

    1999-07-01

    This paper discusses the development and application of standards of performance (SOPs) for HVAC and R equipment, plumbing systems, and building envelope systems in relation to maintaining acceptable indoor air quality (IAQ) in buildings. The utilization of the SOP procedure, developed in ASHRAE Research Project 853, will aid in the proper operation of systems and verify that acceptable building IAQ levels are obtained.

  11. Indoor air quality & airborne disease control in healthcare facilities

    SciTech Connect

    Turner, S.

    1997-06-01

    This article is concerned with indoor air quality (IAQ) in the context of healthcare facilities. It defines what is meant by IAQ, lists health outcomes of poor IAQ, addresses specific healthcare IAQ issues, discusses solutions by means of HVAC systems, and covers relevant regulations and standards.

  12. Measuring Outdoor Air Intake Rates into Existing Building

    SciTech Connect

    Fisk, William; Sullivan, Douglas; Cohen, Sebastian; Han, Hwataik

    2009-04-16

    Practical and accurate technologies are needed for continuously measuring and controlling outdoor air (OA) intake rates in commercial building heating, ventilating, and air conditioning (HVAC) systems. This project evaluated two new measurement approaches. Laboratory experiments determined that OA flow rates were measurable with errors generally less than 10 percent using electronic air velocity probes installed between OA intake louver blades or at the outlet face of louvers. High accuracy was maintained with OA flow rates as low as 15 percent of the maximum for the louvers. Thus, with this measurement approach HVAC systems do not need separate OA intakes for minimum OA supply. System calibration parameters are required for each unique combination of louver type and velocity sensor location but calibrations are not necessary for each system installation. The research also determined that the accuracy of measuring OA flow rates with velocity probes located in the duct downstream of the intake louver was not improved by installing honeycomb airflow straighteners upstream of the probes. Errors varied with type of upstream louver, were as high as 100 percent, and were often greater than 25 percent. In conclusion, use of electronic air velocity probes between the blades of OA intake louvers or at the outlet face of louvers is a highly promising means of accurately measuring rates of OA flow into HVAC systems. The use of electronic velocity probes downstream of airflow straighteners is less promising, at least with the relatively small OA HVAC inlet systems employed in this research.

  13. Optimum coil shape for a given volume of conductor to obtain maximum central field in an air core solenoid

    SciTech Connect

    Hernandez, P.

    1995-02-01

    This paper is an expansion of engineering notes prepared in 1961 to address the question of how to wind circular coils so as to obtain the maximum axial field with the minimum volume of conductor. At the time this was a germain question because of the advent of superconducting wires which were in very limited supply, and the rapid push for generation of very high fields, with little concern for uniformity.

  14. The impact of traffic volume, composition, and road geometry on personal air pollution exposures among cyclists in Montreal, Canada.

    PubMed

    Hatzopoulou, Marianne; Weichenthal, Scott; Dugum, Hussam; Pickett, Graeme; Miranda-Moreno, Luis; Kulka, Ryan; Andersen, Ross; Goldberg, Mark

    2013-01-01

    Cyclists may experience increased exposure to traffic-related air pollution owing to increased minute ventilation and close proximity to vehicle emissions. The aims of this study were to characterize personal exposures to air pollution among urban cyclists and to identify potential determinants of exposure including the type of cycling lane (separated vs on-road), traffic counts, and meteorological factors. In total, personal air pollution exposure data were collected over 64 cycling routes during morning and evening commutes in Montreal, Canada, over 32 days during the summer of 2011. Measured pollutants included ultrafine particles (UFPs), fine particles (PM(2.5)), black carbon (BC), and carbon monoxide (CO). Counts of diesel vehicles were important predictors of personal exposures to BC, with each 10 vehicle/h increase associated with a 15.0% (95% confidence interval (CI): 5.7%, 24.0%) increase in exposure. Use of separated cycling lanes had less impact on personal exposures with a 12% (95% CI: -43%, 14%) decrease observed for BC and smaller decreases observed for UFPs (mean: -1.3%, 95% CI: -20%, 17%) and CO (mean: -5.6%, 95% CI: -17%, 4%) after adjusting for meteorological factors and traffic counts. On average, PM(2.5) exposure increased 7.8% (95% CI: -17%, 35%) with separate cycling lane use, but this estimate was imprecise and not statistically significant. In general, our findings suggest that diesel vehicle traffic is an important contributor to personal BC exposures and that separate cycling lanes may have a modest impact on personal exposure to some air pollutants. Further evaluation is required, however, as the impact of separate cycling lanes and/or traffic counts on personal exposures may vary between regions. PMID:22910003

  15. Commercialization of air conditioning heat pump/water heater. Final technical report, Volume 3: Appendix F through I

    SciTech Connect

    1996-01-30

    This is the final technical report on a commercialization project for an air conditioning heat pump water heater. The objective of the project was to produce a saleable system which would be economically competitive with natural gas and cost effective with regard to initial cost versus annual operating costs. The development and commercialization of the system is described. Compiled data included in numerous figures, tables and graphs.

  16. Comprehensive monitoring program: Final air quality data assessment report for FY90, version 3.1 volume 2. Final report

    SciTech Connect

    1991-09-01

    The objective of this CMP is to verify and evaluate potential air quality health hazards, to verify progress that has been made to date in removing contaminants resulting from previous activities, to provide baseline data for the evaluation of progress that will be made in future remedial activities, to develop real-time guidelines, standard procedures, and data collection methods, as appropriate, to indicate impacts of ongoing, remedial actions, and to validate and document database reliability.

  17. Comprehensive monitoring program: Final air quality data assessment report for FY90, version 3.1 volume 3. Final report

    SciTech Connect

    1991-09-01

    The objective of this CMP is to verify and evaluate potential air quality health hazards, to verify progress that has been made to date in removing contaminats resulting from previous activities, to provide baseline data for the evaluation of progress that will be made in future remedial activities, to develop real-time guidelines, standard procedures, and data collection methods, as appropriate, to indicate impacts of ongoing, remedial actions, and to validate and document database reliability.

  18. Commercialization of air conditioning heat pump/water heater. Final technical report, Volume 2: Appendix A through E

    SciTech Connect

    1996-01-30

    This is the final technical report on a commercialization project for an air conditioning heat pump water heater. The objective of the project was to produce a saleable system which would be economically competitive with natural gas and cost effective with regard to initial cost versus annual operating costs. The development and commercialization of the system is described. Compiled data included in numerous figures, tables and graphs.

  19. CARETS: A prototype regional environmental information system. Volume 7: Land use information and air quality planning. [Norfolk and Portsmouth, Virginia

    NASA Technical Reports Server (NTRS)

    Alexander, R. H. (Principal Investigator); Reed, W. E.; Lewis, J. E.

    1975-01-01

    The author has identified the following significant results. The pilot air quality system provided data for updating information on the sources of point and area emissions of SO2 and particulate matter affecting the Norfolk-Portsmouth area of Virginia for 1971-72 winter and the annual 1972 period. During the 1971-72 winter, estimated SO2 amounts over an area with a SW-NE axis in the central section of Norfolk exceeded both primary and secondary levels.

  20. Review Of Low-Flow Bladder Pump And High-Volume Air Piston Pump Groundwater Sampling Systems At Sandia National Laboratories, New Mexico

    SciTech Connect

    Collins, S. S.; Bailey, G. A.; Jackson, T. O.

    2003-02-25

    Since 1996, Sandia National Laboratories, New Mexico (SNL/NM) has run both a portable high-volume air-piston pump system and a dedicated, low-flow bladder pump system to collect groundwater samples. The groundwater contaminants of concern at SNL/NM are nitrate and the volatile organic compounds trichloroethylene (TCE) and tetrachloethene (PCE). Regulatory acceptance is more common for the high-volume air piston pump system, especially for programs like SNL/NM's, which are regulated under the Resource Conservation and Recovery Act (RCRA). This paper describes logistical and analytical results of the groundwater sampling systems used at SNL/NM. With two modifications to the off-the-shelf low-flow bladder pump, SNL/NM consistently operates the dedicated low-flow system at depths greater than 450 feet below ground surface. As such, the low-flow sampling system requires fewer personnel, less time and materials, and generates less purge and decontamination water than does the high-volume system. However, the bladder pump cannot work in wells with less than 4 feet of water. A review of turbidity and laboratory analytical results for TCE, PCE, and chromium (Cr) from six wells highlight the affect or lack of affects the sampling systems have on groundwater samples. In the PVC wells, turbidity typically remained < 5 nephelometric turbidity units (NTU) regardless of the sampling system. In the wells with a stainless steel screen, turbidity typically remained < 5 NTU only with the low-flow system. When the high-volume system was used, the turbidity and Cr concentration typically increased an order of magnitude. TCE concentrations at two wells did not appear to be sensitive to the sampling method used. However, PCE and TCE concentrations dropped an order of magnitude when the high-volume system was used at two other wells. This paper recommends that SNL/NM collaborate with other facilities with similar groundwater depths, continue to pursue regulatory approval for using

  1. Walk-through survey report: HVLV (high velocity low volume) control technology for aircraft bonded wing and radome maintenance at Air Force Logistics Command, McClellan Air Force Base, Sacramento, California

    SciTech Connect

    Hollett, B.A.

    1983-08-01

    A walk through survey was conducted at the Sacramento Air Logistics Center, McClellan Air Force Base, California, on June 13, 1983, to evaluate the use of High Velocity Low Volume (HVLV) technology in the aircraft-maintenance industry. The HVLV system consisted of 65 ceiling drops in the bonded honeycomb shop where grinding and sanding operations created glass fiber and resin dusts. Preemployment and periodic physical examinations were required. Workers were required to wear disposable coveralls, and disposable dust masks were available. Workers walked through decontamination air jet showers before leaving the area to change clothes. Environmental monitoring revealed no significant dust exposures when the HVLV system was in use. Performance of the exhaust system on the eight-inch-diameter nose cone sanding operation was good, but the three-inch-diameter tools were too large and the shrouds too cumbersome for use on many hand-finishing tasks. The author concludes that the HVLV system is partially successful but requires additional shroud design. Further development of small tool shrouds is recommended.

  2. Thermal issues associated with the HVAC and lighting systems influences on the performance of the national ignition facility beam transport tubes

    SciTech Connect

    Bernardin, J.D.; Parietti, L.; Martin, R.A.

    1998-01-01

    This report summarizes an investigation of the thermal issues related to the National Ignition Facility. In particular, the influences of the HVAC system and lighting fixtures on the operational performance of the laser guide beam tubes are reviewed and discussed. An analytical model of the oscillating HVAC air temperatures in the NIF switchyard and target bay will cause significant amounts of beam distortion. However, these negative effects can be drastically reduced by adding thermal insulation to the outside of the beam tubes. A computational fluid dynamics model and an analytical investigation found that the light-fixture to beam-tube separation distance must be on the order of 5.7 m (18.7 ft) to maintain acceptable beam operating performance in the current NIF design. By reducing the fluorescent light fixture power by 33% this separation distance can be reduced to 3.5 m (11.5 ft). If in addition, thermal insulation with a reflective aluminum foil covering is added to the outside of the beam tubes, the separation distance can be reduced further to 1.6m (5.2 ft). A 1.27 cm (0.5 in.) rigid foam insulation sheet with aluminum foil covering will provide adequate insulation for the beam tubes in the NIF switchyards and target bay. The material cost for this amount of insulation would be roughly $30,000.

  3. Causes of Indoor Air Quality Problems in Schools: Summary of Scientific Research.

    ERIC Educational Resources Information Center

    Bayer, Charlene W.; Crow, Sidney A.; Fischer, John

    Research show that one in five U.S. schools has indoor air quality (IAQ) problems; 36 percent have inadequate heating, ventilation, and air conditioning (HVAC) systems; and there appears to be a correlation between IAQs and the proportion of a school's students coming from low-income households. This report examines the IAQ issue in U.S. public…

  4. Non-HVAC water lines provide cost effective four-pipe fancoil system for motel

    SciTech Connect

    Clark, S.J. )

    1994-03-01

    This article examines the design for a cost effective and energy efficient HVAC system for a motel. The topics of the article include a utility funded energy study, innovative design features of a centralized system integrated with plumbing and fire sprinkler design, implementation of the design, payback period, energy savings, utility's investment, and additional benefits.

  5. 10 CFR 431.402 - Preemption of State regulations for commercial HVAC & WH products.

    Code of Federal Regulations, 2012 CFR

    2012-01-01

    ... 10 Energy 3 2012-01-01 2012-01-01 false Preemption of State regulations for commercial HVAC & WH products. 431.402 Section 431.402 Energy DEPARTMENT OF ENERGY ENERGY CONSERVATION ENERGY EFFICIENCY PROGRAM... regulation concerning the energy efficiency or energy use of that product, except as provided for in...

  6. 10 CFR 431.402 - Preemption of State regulations for commercial HVAC & WH products.

    Code of Federal Regulations, 2014 CFR

    2014-01-01

    ... 10 Energy 3 2014-01-01 2014-01-01 false Preemption of State regulations for commercial HVAC & WH products. 431.402 Section 431.402 Energy DEPARTMENT OF ENERGY ENERGY CONSERVATION ENERGY EFFICIENCY PROGRAM... regulation concerning the energy efficiency or energy use of that product, except as provided for in...

  7. 10 CFR 431.402 - Preemption of State regulations for commercial HVAC & WH products.

    Code of Federal Regulations, 2010 CFR

    2010-01-01

    ... 10 Energy 3 2010-01-01 2010-01-01 false Preemption of State regulations for commercial HVAC & WH products. 431.402 Section 431.402 Energy DEPARTMENT OF ENERGY ENERGY CONSERVATION ENERGY EFFICIENCY PROGRAM... regulation concerning the energy efficiency or energy use of that product, except as provided for in...

  8. 10 CFR 431.402 - Preemption of State regulations for commercial HVAC & WH products.

    Code of Federal Regulations, 2013 CFR

    2013-01-01

    ... 10 Energy 3 2013-01-01 2013-01-01 false Preemption of State regulations for commercial HVAC & WH products. 431.402 Section 431.402 Energy DEPARTMENT OF ENERGY ENERGY CONSERVATION ENERGY EFFICIENCY PROGRAM... regulation concerning the energy efficiency or energy use of that product, except as provided for in...

  9. 10 CFR 431.402 - Preemption of State regulations for commercial HVAC & WH products.

    Code of Federal Regulations, 2011 CFR

    2011-01-01

    ... 10 Energy 3 2011-01-01 2011-01-01 false Preemption of State regulations for commercial HVAC & WH products. 431.402 Section 431.402 Energy DEPARTMENT OF ENERGY ENERGY CONSERVATION ENERGY EFFICIENCY PROGRAM... regulation concerning the energy efficiency or energy use of that product, except as provided for in...

  10. Predicted versus measured thoracic gas volumes of collegiate athletes made by the BOD POD air displacement plethysmography system.

    PubMed

    Wagner, Dale R

    2015-10-01

    Measured (TGVm) and predicted (TGVp) thoracic gas volumes from the BOD POD were compared in 33 lean, university athletes. On average, TGVp (3.529 L) was not significantly different (p = 0.343) from TGVm (3.628 L); however, there was a bias (r = -0.703, p < 0.001). The difference in the percentage of body fat (BF) was within ±2% BF for 76% of the sample, but athletes at the extremes of height should have TGV measured. PMID:26316087

  11. Method, system and apparatus for monitoring and adjusting the quality of indoor air

    DOEpatents

    Hartenstein, Steven D.; Tremblay, Paul L.; Fryer, Michael O.; Hohorst, Frederick A.

    2004-03-23

    A system, method and apparatus is provided for monitoring and adjusting the quality of indoor air. A sensor array senses an air sample from the indoor air and analyzes the air sample to obtain signatures representative of contaminants in the air sample. When the level or type of contaminant poses a threat or hazard to the occupants, the present invention takes corrective actions which may include introducing additional fresh air. The corrective actions taken are intended to promote overall health of personnel, prevent personnel from being overexposed to hazardous contaminants and minimize the cost of operating the HVAC system. The identification of the contaminants is performed by comparing the signatures provided by the sensor array with a database of known signatures. Upon identification, the system takes corrective actions based on the level of contaminant present. The present invention is capable of learning the identity of previously unknown contaminants, which increases its ability to identify contaminants in the future. Indoor air quality is assured by monitoring the contaminants not only in the indoor air, but also in the outdoor air and the air which is to be recirculated. The present invention is easily adaptable to new and existing HVAC systems. In sum, the present invention is able to monitor and adjust the quality of indoor air in real time by sensing the level and type of contaminants present in indoor air, outdoor and recirculated air, providing an intelligent decision about the quality of the air, and minimizing the cost of operating an HVAC system.

  12. Evaluation of PARIS performance in the South Central Coast Air Basin. Volume 2. Technical report. Final report

    SciTech Connect

    Douglas, S.G.; Daly, C.; Moore, G.E.; Myers, T.C.

    1991-12-01

    The primary goal of the study was to compare PARIS model performance in simulating ozone in the South Central Coast Air Basin (SCCAB) for 22-24 September 1985 using alternative wind fields. One wind field was generated by the Diagnostic Wind Model (DWM), and the other by the Colorado State University Mesoscale Model (CSUMM). The overall objective of the South Central Coast Cooperative Aerometric Monitoring Program (SCCCAMP) project was to develop a means of assessing the aggregate impact of offshore petroleum industry sources on onshore ozone (O3) and nitrogen dioxide (NO2) concentrations.

  13. Evaluation of PARIS performance in the South Central Coast Air Basin. Volume 1. Executive Summary. Final report

    SciTech Connect

    Douglas, S.G.; Daly, C.; Moore, G.E.; Myers, T.C.

    1991-12-01

    The primary goal of the study was to compare PARIS model performance in simulating ozone in the South Central Coast Air Basin (SCCAB) for 22-24 September 1985 using alternative wind fields. One wind field was generated by the Diagnostic Wind Model (DWM), and the other by the Colorado State University Mesoscale Model (CSUMM). The overall objective of the South Central Coast Cooperative Aerometric Monitoring Program (SCCCAMP) project was to develop a means of assessing the aggregate impact of offshore petroleum industry sources on onshore ozone (O3) and nitrogen dioxide (NO2) concentrations.

  14. Preliminary design study of underground pumped hydro and compressed-air energy storage in hard rock. Volume 1: Executive summary

    NASA Astrophysics Data System (ADS)

    1981-05-01

    A preliminary design study of water compensated Compressed Air Energy Storage (CAES) and Underground Pumped Hydroelectric (UPH) plants for siting in geological conditions suitable for hard rock excavations was performed. The study was divided into five primary tasks as follows: establishment of design criteria and analysis of impact on power system; selection of site and establishment of site characteristics; formulation of design approaches; assessment of environmental and safety aspects; and preparation of preliminary design of plant. The salient aspects considered and the conclusions reached during the consideration of the five primary tasks for both CAES and UPH are presented.

  15. Personality factors in flight operations. Volume 1: Leader characteristics and crew performance in a full-mission air transport simulation

    NASA Technical Reports Server (NTRS)

    Chidester, Thomas R.; Kanki, Barbara G.; Foushee, H. Clayton; Dickinson, Cortlandt L.; Bowles, Stephen V.

    1990-01-01

    Crew effectiveness is a joint product of the piloting skills, attitudes, and personality characteristics of team members. As obvious as this point might seem, both traditional approaches to optimizing crew performance and more recent training development highlighting crew coordination have emphasized only the skill and attitudinal dimensions. This volume is the first in a series of papers on this simulation. A subsequent volume will focus on patterns of communication within crews. The results of a full-mission simulation research study assessing the impact of individual personality on crew performance is reported. Using a selection algorithm described in previous research, captains were classified as fitting one of three profiles along a battery of personality assessment scales. The performances of 23 crews led by captains fitting each profile were contrasted over a one-and-one-half-day simulated trip. Crews led by captains fitting a positive Instrumental-Expressive profile (high achievement motivation and interpersonal skill) were consistently effective and made fewer errors. Crews led by captains fitting a Negative Expressive profile (below average achievement motivation, negative expressive style, such as complaining) were consistently less effective and made more errors. Crews led by captains fitting a Negative Instrumental profile (high levels of competitiveness, verbal aggressiveness, and impatience and irritability) were less effective on the first day but equal to the best on the second day. These results underscore the importance of stable personality variables as predictors of team coordination and performance.

  16. The Conference Proceedings of the 1999 Air Transport Research Group (ATRG) of the WCTR Society. Volume 2

    NASA Technical Reports Server (NTRS)

    Zhang, Anming (Editor); Bowen Brent D. (Editor)

    1999-01-01

    In this paper, we develop a model with which allows us to measure not only the changes in equilibrium outcomes and welfare consequences of liberalizing a bilateral air transport agreement, but also the distribution of the gains and losses to carriers and consumers of each bilateral country and those of the third foreign countries. Our model also allows to measure the effects of changes in a bilateral agreement on the amount of traffic diversion between the direct bilateral routes and the indirect routes via a third country. We also provide an extension of our model to a case of oligopoly market outcome (Coumot Nash equilibrium). In our model, quality aspects are treated in the framework of hedonic price theory by specifying the quality-adjusted price (quantity) as a multiplication of the observed price (quantity) by the reciprocal quality index function (the quality index function). Numerical simulations were conducted to measure the effects of changing the following major policy levers in a bilateral air transport agreement: 1) Removing price regulation while retaining frequency and entry restrictions; 2) Removing price and entry regulation while retaining frequency restrictions; 3) Removing frequency regulations while retaining price and entry regulations; 4) Removing frequency and entry regulations while retaining price regulation; 5) Removing price and frequency regulations while retaining entry restriction; and 6) Removing all price, frequency and entry regulations (de facto, open skies).

  17. Indoor air quality and work-environment study. Library of Congress, Madison Building. Volume 1. Results of employee survey

    SciTech Connect

    Not Available

    1991-01-01

    A systematic study was designed to assess the nature and spatial distribution of employee health symptoms and comfort concerns in the Madison Building of the Library of Congress (LOC), Washington, DC. This report documented the design of the study and the results of a detailed questionnaire survey of all Madison Building employees conducted in February of 1989. The questionnaire included questions on health symptoms, comfort concerns, background health data, and demographic characteristics. The overall response rate to the survey was 90 percent with 2845 of 3176 employees participating. More than 1200 employees also took the opportunity to make additional comments in the comments section at the end of the survey. The predominant type of symptoms reported among these employees were those that may be associated with poor indoor air quality. Almost half of the respondents reported that a symptom or symptoms reduced their ability to work at least some of the time. Almost half reported more frequent infections since beginning work in the building. Approximately two thirds reported satisfaction with their physical workstations. They did report that the air was often too dry with too little movement.

  18. Multivariate analysis comparing microbial air content of an air-conditioned building and a naturally ventilated building over one year

    NASA Astrophysics Data System (ADS)

    Parat, Sylvie; Perdrix, Alain; Fricker-Hidalgo, Hélène; Saude, Isabelle; Grillot, Renee; Baconnier, Pierre

    Heating, ventilation and air-conditioning (HVAC) may be responsible for the production and spread of airborne microorganisms in office buildings. In order to compare airborne microbiological flora in an air-conditioned building with that in a naturally ventilated building, eight sets of measurements were made over a 1-year period. Concurrently with other environmental measurements, air samples were collected in each building, from three offices and from the outdoor air, using the Andersen single-stage sampler. Three different media were used to culture fungi, staphylococci and mesophilic bacteria. Multivariate analysis revealed a group of offices more contaminated than others, and a marked seasonal variation in fungal concentrations. A comparison of mean levels of microorganisms measured in the two buildings showed that the air microbial content was significantly higher and more variable in the naturally ventilated building than in the air-conditioned building. Moreover, in the naturally ventilated building, the interior fungal content was strongly dependent on the outdoor content, while in the air-conditioned building fungal concentrations remained constant despite significant variations measured outside. This was confirmed by a statistical comparison of the correlation coefficients between indoor and outdoor concentrations. No difference was observed regarding gaseous pollutants and temperature, but relative humidity was significantly higher in the air-conditioned building. The effect of HVAC was to prevent the intake of outdoor particles and to dilute the indoor concentrations. These results are consistent with the presence of high-efficiency filters and a steam humidifier in the HVAC system under study.

  19. Building air quality: A guide for building owners and facility managers

    SciTech Connect

    Not Available

    1991-12-01

    The guide was intended to help those individuals responsible for air quality control in buildings to prevent indoor air quality problems from developing and resolving such problems quickly should they develop. Background information and guidance on dealing with indoor air quality problems were provided. Specific topics included: factors which affect indoor air quality; sources of indoor air contaminants; heating, ventilation and air conditioning (HVAC) systems; the role of building occupants; effective communication between managers and others involved; developing an indoor air quality (IAQ) profile; managing a building for good IAQ; diagnosing IAQ problems; mitigating IAQ problems, hiring professional assistance to solve an IAQ problem; common IAQ measurements; HVAC systems and IAQ; moisture with resultant mold and mildew conditions; asbestos (1332214); radon (10043922); and resources through which additional information can be obtained. Indoor air quality forms were included which can be modified to meet individual needs.

  20. Air resources

    SciTech Connect

    1995-10-01

    This section describes the ambient (surrounding) air quality of the TVA region, discusses TVA emission contributions to ambient air quality, and identifies air quality impacts to human health and welfare. Volume 2 Technical Document 2, Environmental Consequences, describes how changes in TVA emissions could affect regional air quality, human health, environmental resources, and materials. The primary region of the affected environment is broadly defined as the state of Tennessee, as well as southern Kentucky, western Virginia, southern West Virginia, western North Carolina, and northern Georgia, Alabama, and Mississippi. This area represents the watershed of the Tennessee River and the 201 counties of the greater TVA service area. Emissions from outside the Tennessee Valley region contribute to air quality in the Valley. Also, TVA emissions are transported outside the Valley and have some impact on air quality beyond the primary study area. Although the study area experiences a number of air quality problems, overall air quality is good.